Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :1 of 48
Specification for:
Tapered Tubular Steel Poles 161 kv, 400 kv
Prepared by: Eng. Bella Shomer
Approved by: Eng. Yeheskel Samoocha (-signed-)
Edition no. 3,4,5 – prepared by Eng. David Chen (-signed-)
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :2 of 48
Contents:
No. Of Para. Page No. 1. General 4 2. Threshold Conditions 4 3.Documents For the Proposal 4-6 4. Design and Fabrication Standards 6-7 5. Design
5.1 Material
5.2 Geometry
5.3 Tolerances
5.4 Loading
5.5 Pole joints
5.6 Anchoring
5.7 Climbing devices
5.8 Additional items
7-16
6. Test Inspection and Report 16 7. Marking
7.1 marking of pole segments
7.2 marking of crossarms
7.3 marking of ladders
7.4 marking of templates
7.5 marking of base plate
7.6 marking of cases
7.7 marking of beams for carrying and leveling the
templates and anchor bolts
17-26
8. Shop drawings set
8.1 pole assembly diagram
8.2 shop drawing of all pole components and accesories
26-27
9. Fabrication:
9.1 General
9.2 Welding
9.3 Galvanizing
9.4 Punching and drilling
9.5 Documentation
28-31
10. Shipping:
10.1General
10.2 Anchor bolts
31-32
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :3 of 48
10.3 Poles
10.4 Destination
10.5 Packing
11.Quality assurance 32 12 Quality control 33 13. Final documents to be submitted by the Contractor
winner before poles fabrication 33
14. documents to be submitted by the Contractor winner
during and after poles fabrication 34
15. List of drawings 35-38 16. Revisions 39-42
APPENDIX Page No.
1. General drawing of the pole 43
2. Summary table 44
3. Delivery time schedule 44
4. Packing list of goods 45
5. Statement of manufacturing experience 46
6. drawings 47
7. I.E.C quality specification Q – APP - 02 48
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :4 of 48
1.GENERAL
This specification describes the requirements of the ISRAEL ELECTRIC
CORPORATION (IEC) pertaining to the design, manufacture and supply of
Tapered Tubular Steel Transmission Pole Structures,(including accessories), which
hereafter shall be called "Poles".
The "Design of Steel Transmission Pole Structures" - ASCE /SEI 48-11 standard ,
shall be the relevant governing standard in conjunction with this order.
In case of discrepancies or nonconformity between documents, priority shall be as
follows:
1. The present specification, or written approval by IEC engineers.
2. ASCE /SEI 48-11 standard.
All documentation to be submitted shall be presented in English, shall be clear and
understood by IEC engineers and shall be submitted in due time to enable IEC's
engineers to check and comment them.
2. THRESHOLD CONDITIONS
According to attached documents of the "IEC Procurement Division".
3. DOCUMENTS FOR THE PROPOSAL
The bidder shall submit together with his offer the following:
3.1 Signed Appendix 5: "Statement of manufacturing experience".
3.2 Valid ISO 9001certificate, issued by a Certification Body , as specified in the
threshold conditions of the tender.
3.3 Declaration indicating that the proposal fully satisfies the requirements of this
specification.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :5 of 48
3.2 A list of the relevant standards to which all respective stages of pole design and
manufacture comply.
3.3 For each type of pole: The design moments at the base and at the slip joints and
at any other critical points along the pole, inlcuding the effects of the secondary
moments due to deflection.
- ground line reactions.
- weight of each structure.
- distance across the angles and thickness at the top and at base of each segment
of the pole.
- Anchor bolts diameter, length and quantity (for anchor base only).
- Stud bolts diameter and quantity per each connection of crossarm to the pole.
- The materials (code name, yield stress) of the all pole components.
3.4 General drawing (Appendix 1) of all pole segments for each structure type
(Shop drawings are not required).
General drawing must represent the following informations:
- Length, thickness, top and bottom outside diameter across angles and flats, for
all pole segments and crossarms.
- Overlap length for all slip joints.
- Total length of pole, distance between crossarms from tip to tip.
- Cross arms raising and overhang.
- Distance between crossarms tips and pole axel.
- number, diameter and distance between bolts in connections of crossarms to
the pole.
- descriptions of pole segments (shafts) and cross arms sections (round or
polygon) and material (code name, yield stress).
- material of bolts (code name, yield stress).
3.5 Summary table (Appendix 2)
3.6 General drawing of templates and anchor bolts assembly (for anchor base only).
The general drawing of templates and anchor bolts assembly must represent the
following informations:
- bolt circle diameter.
- outside and inside diameter of upper and lower templats, and their thicknesses.
- anchor bolts length and diameter, thread length and bond (development)length in
the concrete.
- quantity of anchor bolts, nuts and washers.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :6 of 48
- descriptions of material (type, code name, yield stress and coating) for all parts
of assembly.
3.7 Delivery schedule (Appendix 3).
3.8 The bidder shall submit detailed procedures for the hot dip galvanizing and
metallizing process as described in para.9.3.
3.9 A declaration of capability by the supplier that shall include:
3.9.1 Manufacturer's capability with respect to quantity and types of poles.
The above mentioned documents shall be in English. The units in drawings and
summary table must be SI units.
4. DESIGN AND FABRICATION STANDARDS
Design, materials and fabrication of steel poles shall be in accordance with the latest
edition of international codes and standards listed hereafter:
- ASCE /SEI 48-11 - Design of Steel Transmission Pole Structures.
- EN 10025 - Hot rolled products of structural steels.
- EN 10149-2 - Hot-rolled flat products made of high yield strength for cold forming.
- ASTM A36 - Structural Steel.
- ASTM A572 - High-Strength Low-Alloy Columbium-Vanadium Steels of Structures
Quality.
- ACI 318 - Building Code Requirements for Reinforced Concrete.
- ASTM A615 - Deformed and plain billet steel bars for concrete reinforcement.
- ASTM A563 - Carbon and Alloy Steel Nuts.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :7 of 48
- ASTM F436 - Hardened Steel Washers.
- ASTM A354 - Quench and Tempered Alloy Steel Bolts, Studs and Other Externally
Threaded Fasteners.
- ANSI B18.21.1. - Lock Washers.
- ASTM A449 – Quench and Tempered Steel Bolts and Studs.
- DIN 127B - Lock Washers.
- ASTM A143 - Safeguarding Against Embrittlement of Hot – Dip Galvanized
Structural Steel Products and Procedure for Detecting Embrittlement.
- AWS D1.1 - Structural Welding Code – steel.
- ASTM A123 - Zinc (Hot-Dip Galvanized) coatings on Iron and Steel Products.
- ASTM A780 - Repair of Damages and Uncoated Areas of Hot-Dip Galvanized
Coatings.
- ASTM 153 - Zinc Coating (Hot Dip) on Iron and Steel Hardware.
- AWS C2.23M - Application of Thermal Spray Coatings (Metallizing) of Aluminum,
Zinc, and Their Alloys and Composites for the Corrosion Protection
of Steel.
or
- ISO 2063 - Thermal spraying – Metallic and other inorganic coatings – Zinc,
aluminum and their alloys.
5. DESIGN
The design of the poles shall include:
- material requirements, relevant standards.
- pole and crossarms design: thickness and radius of each section accesories,
joints, additional items, climbing devices (see para. 5.2-5.8).
- deflection calculations shall be submitted.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :8 of 48
- foundation design recommendations (see para. 5.6).
- shop drawings (see para. 8).
5.1 Material
5.1.1 General
All material shall comply with the applicable requirements of the appropriate
standard.
The supplier is entitled to propose industrial standards acceptable in his own
country, for IEC approval.
The steel shall be of "Hot Deep Galvanizing Quality" and suitable for welding.
The steel shall have Si (Silicon) and P (Phosphorus) contents:
Si <= 0.03% and (Si + 2.5P)<=0.09
or
0.14% <=Si<= 0.25% and P<=0.035%
The Energy - Impact Values should be included in the manufacturer's proposal
and should comply with an accepted authority, e.g., ASTM, DIN.
The certificate of steel composition shall be submitted before galvanizing.
5.1.2 Pole shaft, crossarms, crossarms attachment to pole shaft
Material shall conform to EN 10025 type S235JR, S235J0, S355J2,
ASTM A36, A572 grade 50, A572 grade 65, or equivalent types
according to relevant standards.
5.1.3 cross arms axles
- All studs bolts for crossarm connections shall conform to ASTM A354 grade
B.C. MOD.
- All nuts for crossarm connections shall conform to ASTM A563 grade DH.
- All lock washers for crossarm connections shall conform to ANSI B18.21.1.
5.1.4 Threaded fasteners
- Other bolts shall conform to ASTM A449.
- Other nuts shall conform to ASTM A563 grade C.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :9 of 48
- Other lock washers shall conform to DIN 127B.
5.1.5 Anchor bolts
Anchor bolts shall conform to ASTM A615 Grad 75 MOD (deformed ribbed
bar).
The anchor bolt nuts shall conform to ASTM A563 Grad DH.
The anchor bolt washers shall conform to ASTM F436.
5.2 Geometry
Poles shall have a 12 - 16 sided regular polygonal cross section for suspension and
tension poles.
Cross-arms shall have a tapered polygonal, or round, or square cross section.
According the tender requirements, suspension poles 400 kV may be in two options:
cross-arms with I string or with V string isulators.
Pole height, base diameter ; crossarms shape and length shall be according
to IEC requirements.
compact 161 kV lines crossarms :
For suspension poles - crossarms shall be a composite insulators assemblies with
pivoting base , see drawing NCD 2646, supplied by IEC.
For tension poles - post insulator, see sketch 5370, supplied by IEC .
Compact 400 kV lines insulators:
For suspension poles - composite insulators assemblies is used, see drawing NCD
2658, supplied by IEC.
The vertical insulator is connected to the pole crossarm.
Max. length of segments shall be 16 meters and under certain conditions (after
approval of the Israel Electric Corp. Ltd.) -18 meters.
Please note that if a segment is composed of partial segments, each partial segment
must be not shorter than 3 meters length.
A maximum of one horizontal weld per segment is permissible and under certain
conditions (after approval of the Israel Electric Corp. Ltd.) - two welds.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :10 of 48
All common segments for the same type of pole (pole with all required extensions)
shall be interchangeable.
For each pole, left and right crossarms connection and number of bolts shall be the
same.
Max. weight of segment shall be 28.0 tons. The weight of the first upper part with
the crossarms, platforms, handrailings, ladders, insulators, running block shall be less
than 9.0 tons.
The material thickness shall be not less than 5.0 mm.
A sufficient number of holes should be provided to enable the free flow of the
molten Zinc, and to prevent the build-up of pressures inside closed structural
elements (i.e cross-arms).
5.3 Tolerances
The permitted tolerances shall be as follows:
a. The overall assembled length of each pole: -0.5% / +1.5%.
b. The length of pole segments: -25 mm / +75 mm.
c. Member straightness: less than 3 mm per meter.
d. Bottom part diameter shall be -1.0% / +2.0%.
The supplier shall supply a list of fabrication tolerances to the purchaser for
approval.
5.4 Loadings
5.4.1 General
The poles shall be designed to withstand the specified loadings without
exceeding the specified yield strength of the pole steel (see sketches).
All the loadings are according to IEC standards and include overload factors.
161 kV poles:
The earth wires on poles - OPGW.
The connection of OPGW can be suspension or tension type - for all the
poles
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :11 of 48
(tension and suspension). Therefore on earth crossarms there are two type of
connection plates:
- plates no.9 for tension type
- hinge no.1 for suspension type.
Loads for OPGW (see sketches of load trees) shall be applied either on plate
no.9, or on hinge no.1, see sketch 3703.
400 kV poles:
2 types of earth wires are used on poles: 241 ALLOY and OPGW.
The connection of OPGW can be suspension or tension type - for all
the poles (tension and suspension). Therefor on earth crossarms there are
two types of connection plates:
- plates no.17 for tension type
- hinge no.18 for suspension type.
Loads for OPGW (see sketches of load trees) shall be applied either on
plate no.17, or on hinge no.18, see sketch 3192.
5.4.2 Wind load on the pole
The wind loads on the pole shall apply in transverse direction only.
The wind loads on the pole are calculated as follows:
Three (3) values are given in the sketches:
- for normal and cascade (or longitudinal) loading condition.
- for broken wire loading condition
- for service loading condition
These values must be multiplied by the shape factor Ct, by the height factor M1
and by the net pole area (in squaremeters, m²) perpendicular to the wind
direction.
The value of the shape factor Ct is determined from table 1.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :12 of 48
Table 1
SHAPE SQUARE 8 SIDED 12 SIDED 16
SIDED
ROUN
D
Ct 1.5 1.3
0.9 0.85 0.8
The value of the height factor M1 is determined from table 2.
Table 2
Height factor M1 Height above ground level (m)
0.92 0 -25
1.10 25 - 45
1.21 45 - 70
1.31 70 - 100
5.5 Pole joints
Pole sections shall be made with telescopic slip joints.
The sections should be detailed for nominal overlapping length that shall assure a
minimum overlapping length of 1.52 times the maximum inside diameter (across
flats) of the female section.
Nominal overlapping length shall be 1.7 times the maximum inside diameter (across
flats) of the female section.
The maximum overlapping length shall be nominal overlapping length + 100 mm.
The taper of each section at a slip joint should match the taper of the adjacent section
to provide proper splice tolerances.
Joints shall resist compression, tension, bending, shear and torsion under ultimate
loads conditions.
On both sides of slip joints, pole shall be provided with special jacking studs, which
were welded to the pole sections.
For each section of the slip joint, two jacks are required, one jack on each side.
The place of jacking studs shall be according to IEC sketches.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :13 of 48
Minimum distance between segment joint edge and bottom of crossarms connection
attachment shall be equal or more than 1.2 m (see sketch 3183).
Pole assembling shall be by segments - in vertical or horizontal position.
For vertical assembling - the jacking operation shall be made when the assembling
of pole shall be completed.
The jacking studs type shall be selected according to jacking forces from horizontal
position assembling. The possible local buckling, caused by the jacking operation,
shall be checked to jacking forces multiplied by overload factor of 1.3.
Grinding of longitudinal welds, within the maximum slip joint area plus 100 mm,
shall be done. Internal grinding of female and external grinding of male.
5.6 Anchoring
Poles may be furnished for either anchor base construction or for direct embedment
in concrete foundation, or for extended pile reinforcement.
5.6.1 Anchor base
For anchor base construction, anchor bolts are to be used. For anchor bolts
calculation, ultimate loads must be multiplied by safety factor of 1.1 .
Concrete presently in use has the compressive cube strength after 28 days –
300 kg/cm2 (for concrete cube dimensions 10x10 cm).
The number of bolts, their size, thickness, templates, etc., are to be
recommended and supplied by the supplier. Four of the anchor bolts shall be
supplied with extensions of 100 mm, to facilitate positioning of the pole on
the anchor bolt group.
The anchor bolts shall be deformed ribbed bar.
The materials of anchor bolts and nuts are according to para. 5.1.5.
The anchor bolts development length shall conform to ASCE /SEI 48-11
standard.
The development length shall be calculated without taking into account the
template.
The actual development length shall be the calculated development length
plus 300 mm.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :14 of 48
The number of bolts shall be symmetrically relation to the two axes and can
be divided by four.
The templates shall be rounded shape.
Rigid bottom template shall be designed for carrying all anchor bolts with
very small deflections (see drawing NCD 2663).
Each anchor bolt shall be connected to base plate by three nuts and two
washers. The supplier shall provide drawing datail of base plate setting (see
drawing NCD 2663).
The holes diameter on templates shall be threaded diameter of anchor bolt
plus 1 mm.
The holes diameter on base plate shall be threaded diameter of anchor bolt
plus 6 mm. minimum.
The supplier shall provide instructions and drawing datails for anchor bolts
instalation in the concrete foundation.
The supplier shall design two beams for carrying and leveling the anchor
bolts assemblies above the foundation hole (see drawing NCD 2692).
For each pole type, the supplier shall supply two couples of beams for
ordering more then one pole, and one couple for ordering one pole, in the
all period of one contract.
5.6.2 Embeded in concrete foundation
For embedded poles, the length of the embedment shall be as shown in
sketches- Sketch 3562, NCD 1026.
5.6.3 Extended pile reinforcement
For poles for extended pile reinforcement, a bottom part of the pole shall be
placed over the exposed reinforcing structure.
Concrete shall be poured into the pole section to height of 1.5 times of
bottom largest outside diameter.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :15 of 48
Quantity, geometry and position of weld plates shall be according to IEC
requirements (see sketch 3562).
5.7 Climbing devices
A ladder shall start at a height of about 4 m from ground level, and shall be
continuous to a point at about 0.3 m below the top of the pole (see sketch 3183).
For 161 kV poles an additional ladder shall start on opposite side from the platform
bellow upper crossarm and shall be continuous to a point at about 0.3 m below the
top of the pole.
For upper segment of ladder two meters shall be with doubled steps, see sketch 3690.
The length of each ladder segment must be 3 m (except for upper and lower parts).
The ladder, its connecting points and all the welds shall be straight and smooth-
surfaced.
Each segment of ladder shall be straight and its tolerance must be less than 0.001 of
its length. All these requirements are in order to ensure proper work with safety
devices -railblock of PROTECTA AC 101.
The supplier shall check ladders and crossarms rail with railblock before delivery.
For compact 161 kV line poles, no ladder shall be used.
5.8 Additional items
- Plates for warning spheres attachment. For exact position of the attachment on
each pole, see sketch 3183.
- Removable railings and platforms shall be placed on pole according to sketch
3711. No bolts shall protrude above the surface of railing pass, in order to ensure
proper work with safety devices - railblock.
- Holes for lifting and attachments for centralizing shall be according to sketch 3183,
5363 for compact 161 kV line.
- Adjusting handles shall be placed on bottom and on each segment of pole, see
sketch 3562, 3183, 5363 for compact 161 kV line .
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :16 of 48
- Attachment for anchoring shall be welded on tension pole crossarms, see sketches
3703 for 161 kV, 3186, 3192 for 400 kV.
The main method for devices to climb and work on crossarms is stepping stones -
(see sketch 3685).
Stepping stones shall be placed on all crossarms of suspension
poles, and on only earth wire crossarms of tention poles.
- Attachment for the ladder shall be welded at the end of crossarms, see sketch
3182, 3186.
Sharp edges shall be smooth rounded.
- Attachment for anchoring shall be welded on tension poles crossarms, see sketches
3186, 3192.
- Lifting bars, holes and devices shall be calculated for two segment weights
(except for bottom part that shall be lifted alone).
- Lifting bar and hole shall be calculated for 2/3 of total lifting weight. For
placement see sketch 3183, 3192.
- Lifting devices shall be placed on each segment calculated for doubled
weight of segment, see sketch 3183.
6. TEST INSPECTION AND REPORT
The Purchaser, at his expense, may request that one or more poles, selected from
production at random, be tested to the full design load according testing
procedure of ASCE /SEI 48-11 standard "Design of Steel Transmission Pole
Structures" and IEC 60652 standard "loading tests on overhead line structures".
The Contractor shall furnish a test report for each structure tested. The test report
shall include the method of application of the loads, the deflection under the
various loading conditions and mill test reports for the steel used in the tested
structure.
The pole shall be tested to withstand the full design loads.
The pole shall not sustain any permanent deformation.
After passing the test the pole shall be dismantled.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :17 of 48
7. MARKING
Markings shall be made on all design drawings, calculations, pole elements,
crossarms, pole parts and accessories, so as to define each item individually.
Markings on steel segments shall be clearly engraved or embossed. The size of
the marking shall be in accordance with figure 1. The markings shall be clearly
visible on each part of each pole.
7.1 marking of pole segments
The location of marking on pole segments desceibed in figure 3.
7.1.1 engraved or embossed marking on pole segments
The markings of pole segments shall include the following data:
- trademark of the manufacturer.
- name of pole.
- catalogue number of segment or bottom part (catalogue number
shall be supplied by the purchaser).
- number of section (the section number shall be clearly marked in
accordance with drawing).
see figure 1.
FIGURE 1- engraved or embossed marking of pole segments
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :18 of 48
7.1.2 label and painted marking of pole segments
Labels marking shall be attached on the inner part at both ends of
each segment of the pole, see figure 3.
Additional painted markings on steel segments shall be on each
segment of each pole on both sides according figure 3. Markings
shall be according to Figure 3.
The markings of pole segments shall include the following data:
- trademark of the manufacturer
- name of pole
- catalogue number of segment or bottom part (catalogue number
shall be supplied by purchaser)
- number of section (the section number shall be clearly marked in
accordance with drawing).
See figure 2.
FIGURE 2- label and painted marking of pole segments
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :19 of 48
FIGURE 3- The locations of marking on pole segments
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :20 of 48
7.1.3 center lines marking of pole segments
The center lines on each bottom part shall be marked at 4 sides on
upper & lower edge of the part.
The center lines on each part shall be marked only at two sides, only
on lower edge of the part.
The marking shall be by red paint.
The dimensions of the marking shall be:
- 300 mm -length, 10 mm - width.
See figure 4.
7.1.4 center of gravity marking of pole segments
The center of gravity on each segment shall be marked at 4 sides.
The marking shall be by red paint.
The dimensions of the marking shall be:
- 300 mm -length, 10 mm - width.
See figure 4.
7.1.5 min. and max. overlapping length marking of pole segments
The min. and max. overlapping length shall be marked at one side, near
to jacking studs line.
The marking shall be by black paint.
The dimensions of the marking shall be:
- 200 mm -length, 3 mm - width.
See figure 4.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :21 of 48
FIGURE 4 –center lines marking of pole segments
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :22 of 48
7.2 marking of crossarms
The marking shall be engraved or embossed.
The markings of pole crossarms shall include the following data:
- trademark of the manufacturer
- name of pole
- catalogue number of crossarm (catalogue number shall be supplied
by the purchaser)
- part number in accordance with drawing
- crossarms position (level on pole and right or left position)
See figure 5.
FIGURE 5- marking of pole crossarms
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :23 of 48
7.3 marking of ladders
7.3.1 engraved or embosed marking of ladders
The marking of each ladder shall include the following data:
- trademark of the manufacturer.
7.3.2 marking plate
Marking plate should be fastened to a bundle of ladders of one
pole (see appendix 4).
The marking shall be by paint.
The marking plate shall include the following data:
- trademark of the manufacturer.
- name of pole.
7.4 marking of templates
7.4.1 engraved or embosed marking of template
The marking of template shall include the following data:
- trademark of the manufacturer.
- name of pole.
- catalogue number of anchor bolts & templates (catalogue
number shall be supplied by purchaser).
7.4.2 Axes marking on upper template
The upper template shall be marked by paint on the two axes ( strait line &
“ARM” for arm centerline, and “^” & “LINE” for line (front) centerline).
see figure 6.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :24 of 48
FIGURE 6- axes marking on upper template
7.5 Axes marking on base plate
The base plate shall be marked by paint on the two axes ( strait line &
“ARM” for arm centerline, and “^” & “LINE” for line (front) centerline).
See figure 7.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :25 of 48
FIGURE 7- axes marking on base plate
7.6 marking of cases
Each case for accessories shall be marked, on visible position, by
painted marking.
The marking of case shall include the following data:
- trademark of the manufacturer.
- name of pole.
- catalogue number of case (catalogue
number shall be supplied by purchaser).
See appendix 4.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :26 of 48
7.7 marking of beams for carrying and leveling the templates and anchor
bolts
Each beam shall be marked, on visible position, by
engraved or embossed marking.
The marking of beam shall include the following data:
- trademark of the manufacturer.
- name of pole.
- catalogue number beam (catalogue
number shall be supplied by purchaser).
See drawing NCD 2692.
8. SHOP DRAWINGS SET
shop drawings set must include pole assembly diagram and shop drawing of each
component of the pole.
The supplier shall prepare and submit to the purchaser approval, two prints of each
shop drawing set.
After all corrections are made, a set of revised reproducible prints and
AUTOCAD files shall be sent to the purchaser.
All shop drawings shall be approved by the purchaser before fabrication.
8.1 pole assembly diagram
pole assembly diagram of each pole type shall include the following information:
- Pole type
- Geomtric outline of the pole with all component and dimensions, as
described in appendix 1.
- The geometric outline shall include also the plats and accessories
connected to the pole, and include numbers of pole elements.
- C.O.G. of pole (including crossarms)
- Pole orientation- Cross section of the pole with the location of ladder
and jacking studs, with axes (writing – “ crossarm axis”) and
numbering the angels points.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :27 of 48
- Details of base plate setting (for anchor base only).
- Shipping weight, thickness, length and cross-sectional geometry (upper
and bottom diameter across angle and flats) for each segment of the
pole.
- Shipping weight, thickness, length and cross-sectional geometry (small
and large diameter across angle and flats) for each crossarm.
- Stud bolts (sizes and quantity) for each crossarm conection to pole.
- parts list of pole segments (shafts), crossarms, anchor bolts &
templats with I.E.C catalogue, climbing devices, accessories, bolts,nuts
washers and lockwashers.
- Table with moments and reactions at the pole base.
- Min. and max. jacking forces (for each type of assembling).
8.2 shop drawings of all pole components and accessories
- Detail drawings of all pole segments and crossarms, and the location
and orientation of all plates and accessories welded to them.
- Detail drawings of all plates and accessories that are welded to the pole
segments or crossarms.
- Typical arm to pole fastener connection detail.
- Detail drawings of climbing devices.
- Detail drawing of all the accessories for climbing. - List of material specification: Material types, minimum yield stress and
relevant specifications
- Details about finishing.
- For each element, to show the location and details of marking
(according to para. 7).
- Detail drawing of anchor bolts and templates and details of base plate
setting
(for anchor base only, see drawind NCD 2663).
- Detail drawing of beams for carrying and leveling the anchor bolts and
templates assembly (see drawing NCD 2692).
- Welding details. - Bill of material for each drawing. - The title of each drawing shall include : the subject of drawing, pole
type, element name and number,cat. No.,400 or 161 kv and “israel
electric corporation ltd”.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :28 of 48
9. FABRICATION
9.1 General
After shop drawing approval, prior to mass production for each type of pole
prototype assembly of all removable parts for each segment and cross-arms shall be
done and approved by IEC.
All fabrication checks and procedures are to be performed according to ISO 9001
standard. The manufacturer shall verify correct fitting of every part using suitable
inspection jigs.
Fabrication shall be in according with the latest edition of ASTM A 143.
9.2 Welding
All weldings are to be performed in the shop, prior to galvanization. Welding shall
be in conformance with the AWS D1.1 of the American Welding Society Structural
Welding Code or similar accepted by IEC Material Laboratory.
All welding filler metal used for welding (including tack welds) should be from the
low hydrogen type and shall meet, as a minimum, an impact value of 15 ft/lbs at -20F
as measured by the standard Charpy V - notch test.
They shall equal or exceed the specified physical properties of the base metal being
welded when tested with the applicable AWS specification for welding electrodes.
Welding may be done by the shielded metal-arc, gas shielded flux core, or
submerged- arc process.
Shielded metal-arc welding shall be done with appropriate strength low hydrogen
electrodes.
Welding joint details shall be detailed by the bidder and approved by the IEC.
Longitudinal welds shall be minimum 80% penetration welds, except within the slip
joint area (female and male) plus 200 mm where the penetration shall be full (100%)
penetration welds.
Longitudinal welds within 100 mm of circumferential welds shall be full (100%)
penetration welds.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :29 of 48
All circumferential welds shall be full (100%) penetration welds.
Welding quality shall be according to AWS D1.1.
The bidder may use any combination of inspection methods to satisfy the welding
quality requirements of the above standard.
Ultrasonic or radiographic inspection (in accordance with Israel Electrical Company
laboratory requirements) shall be performed on all full penetration welds -
longitudinal welds in the slip joint area, flange and base plate to pole shaft welds,
crossarm bracket to arm shaft welds, hinges attachment welds and safety related
welds.
Furthermore two ultrasonic or radiographic inspections of the circumferential seams
and one longitudinal seam in each of the other segments must be performed.
Ultrasonic or Radiographic inspection shall be done for every T joint
(horizontal and longitudinal welds junction).
If the quality and number of rejected welds shall be minimum, the number of
radiografic tests can be reduced according to IEC laboratory autorisation.
All welding shall be performed by qualified welders, or welder operators, using only
qualified welding procedures in accordance with the Code AWS D1.1 - prequalifed
WPS shall not be accepted.
All WPS, WPQR and welder's qualifications shall be submitted to I.E.C for review
and for approval.
9.3 Galvanizing
The pole segments (parts) and all accessories shall be hot dip zinc galvanized
according to ASTM A-123 standard, or acceptable equal standard (approved by
IEC). The minimum thickness of the zinc coating shall be 85 microns.
All hollow members shall be galvanized both inside and outside surfaces.
The segments length shall be designed for one dipping. In special cases, double
dipping will be don only after IEC confirmation.
Repair of damaged and uncoated areas of hot dip galvanized coating shall be by
sprayed zinc ((Metallizing), according to ASTM A780 specification.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :30 of 48
All attachment bolts and the full length of anchor bolts shall be hot dip galvanized.
Bolts, nuts and washers shall be galvanized in accordance with ASTM 153.
(For attachment bolts, the bidder can propose another coating method for IEC
approval).
The minimum thickness of the zinc coating for bolts and nuts shall be 40 microns
The coating of small bolts for ladders can be:
- hot dip galvanized, minimum thickness of coating shall be 40 microns
- electrogalvanized on cyanide base, minimum thickness of coating shall be 40
microns with pasivation.
- sheradizing, minimum thickness of coating shall be 40 microns + pasivation.
Thread of nuts for bolts coated by hot dip galvanized, electrogalvanized on cyanide
base or sheradizing, shall be tapped, after coating, to oversize 0.38 mm of bolt
diameter.
Nuts coated by hot dip galvanized,shall be oiled after tapping.
Pole segments that are impossible (according to the diameter of pole segments) to be
coated by hot dip galvanizing, shall be zinc sprayed (metallizing)
according to AWS C2.23M or EN ISO 2063.
The minimum thickness of the metallizing zinc coating shall be 120 microns.
The coating shall be continuous and reasonably smooth and uniform in thickness.
Galvanized articles shall be free from uncoated areas, blisters, flux deposits, and
gross dross inclusions. Lumps, projections, globules, or heavy deposits of zinc which
will interfere with the intended use of the material will not be permitted.
The zinc coating color, on all areas of the articles, shall be uniform, without marks.
The bidder shall submit, with his technical bid, detailed procedures for the hot dip
galvanizing and metallizing process as described above, for IEC approval.
9.4 Punching and drilling
Holes in plates of thickness more than 11 mm may be partially punched. Punched
hole shall be enlarged to a final dimension by drilling.
Flame cut holes are not permitted.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :31 of 48
9.5 Documentation
The supplier shall submit all relevant certifications concerning material quality,
welding rods, fabrication inspections etc., as all other documents mentioned herein,
according to ISO-EN-10204-3.1B.
10.SHIPPING
10.1 General
The delivery schedule shall be coordinated with and approved by IEC prior to
delivery.
Prior notification of delivery shall be given.
Each shipment and each invoice shall be accompanied by a packing list of all parts
on that particular shipment. Bolts, nuts and other hardware shall be either boxed or
bundled. All bolts, nuts and miscellaneous hardware shall be clearly identified in the
packing list to enable efficient match-up with their respective pole shafts.
The packing shall prevent any damage to the pole elements.
10.2 Anchor Bolts (for anchor base only)
Anchor bolts shall be assembled to the top and bottom template by the supplier.
The supplier shall supply the assembly of anchor bolts and templates (of each
pole) to the purchaser store. The assembly of Anchor bolts and templates shall be
supplied in advance of the poles supply, if so required.
The thread lengths of anchor bolts shall be protected from damage at transportation
stage.
10.3 Poles
Poles shall be normally shipped in open top containers ( unless the pole dimensions
do not permit this) or connventional shipped.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :32 of 48
10.4 Destination
Unless otherwise agreed to by the Purchaser, the shipment shall be forwarded
according to the shipping instructions shown in the enquiry.
The Purchaser shall be notified when each shipment is ready for delivery.
10.5 Packing
Poles segments shall be packaged and securely tied with synthetic band or galvanized
steel band with protection band, for transportation. The minimum width of the band
is 2".
Pole segments shall be placed on durable wooden rods, covered by rubber sheets.
All the accessories, bolts, fasteners (packed in plastic bags) for each pole shall be
packed in the wooden case with their packing list.
The wooden case shall resist external environmental conditions for years.
Ladders for each pole shall be packed and securetly tied with slings and placed on
wooden rods.
Safety rails shall be bundled and tied for each pole.
See appendix 4.
11. QUALITY ASSURANCE
11.1 Bidder’s Quality Assurance Program shall meet the requirements that described in
ISO 9001.
11.2 The purchaser shall have the right to audit and comment on Bidder’s Quality
Assurance System regarding of whether it was previously audited by a certifying
agency or any other body.
11.3 The bidder shall submit with his proposal a copy of his Quality Assurance Manual
including Quality Procedures (if applicable).
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :33 of 48
12. QUALITY CONTROL
12.1 Quality control requirements shall be according to I.E.C specification
Q – APP – 02 (Appendix 7).
12.2 The bidder shall submit with his proposal a copy of the inspection and test plan
which is applied during the production of the equipment.
Representatives of IEC shall be authorized to visit the manufacturer’s plant and
obtain details of each phase of the equipment’s production.
12.3 Test and inspection certificates as required in the specification and the
applicable standards, shall be submitted immediately following their generation.
The certificates shall be original, signed by the contractor and contain actual
values measured. The generation of certificates, including those generated by sub-
suppliers, shall bear no extra cost to purchaser.
13. FINAL DOCUMENTS TO BE SUBMITTED BY THE CONTRACTOR
BEFORE POLES FABRICATION
After reception purchase order ,the contractor winner shall prepare and submit to
the purchaser :
1. Within two weeks after reception of order - the calculations and geometric
outline of each pole type, for IEC approval.
2. Within one month after reception of order - one print of all shop drawings set
for each pole type, for IEC approval.
After making all corrections on the shop drawings, according to IEC remarks, and
final IEC approval, a set of final shop drawings prints and AUTOCAD files shall be
sent to the purchaser.
All shop drawings shall be approved by the purchaser before fabrication.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :34 of 48
14. DOCUMENTS TO BE SUBMITTED BY THE CONTRACTOR
DURIND AND AFTER POLES FABRICATION
1. The contractor winner shall send a list of material identification, welder
identity, inspection results and inspector identity.
The contractor winner shall send records of welding procedure and weld
quality tests.
2. For each type of pole, the contractor winner shall prepare and send packing list
according to appendix 4. The packing list shall be approved by IEC, before poles
shipping.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :35 of 48
15. LIST OF DRAWINGS
400 kv - Catalogue number for tender only Sketch no.
Catalogue number for poles ZDSC2 B, +5B, +10B NCD 171 e/4
Catalogue number for poles ZDS2 B,G, +5B,+4G JDHK 8603e/3
Catalogue number for poles ZDT2 B,G, +3B, +3G JDHK 8604e/1
Catalogue number for poles ZDT1 +3D, +3H JDHK 8605e/1
Catalogue number for poles ZDSM2 B, +5 B, +10B,
ZDTM2 B, +5 B
JDHK 9420e/1
400 kV
Sketch no.
Loading tree ZDSC2 B, +5B, +10B SKETCH 5131b/3
Loading tree ZDS2 B,G, +5B,+4G NCD 175/2
Loading tree ZDT2 B, +3B NCD 179/1
Loading tree ZDT2 G, +3G NCD 180/1
Loading tree ZDT1 +3D, +3H NCD 194/2
Loading tree ZDSM2 B, +5 B, +10B SKETCH 5850/3
Loading tree ZDTM2 B, +5 B SKETCH 5861/3
Diameter, thickness ZDSC2 B, +5B, +10B SKETCH 5132b/3
Diameter, thickness ZDS2 B,G, +5B, +4G NCD 142/3
Diameter, thickness ZDT2 B,G, +3B, +3G NCD 178/0
Diameter, thickness ZDT1 +3D, +3H NCD 193/1
Diameter, thickness ZDSM2 B, +5 B, +10B SKETCH 5851/2
Diameter, thickness ZDTM2 B, +5 B SKETCH 5862/2
Attachments for crossarms (ZDS2C A, B, G) I - string SKETCH 3182/14
Attachments for crossarms (ZDT2 B, G) SKETCH 3186/17
Attachments for crossarms (ZDT1 G, D, H) SKETCH 3192/13
Suspension and tension hinges SKETCH 3191/12
Attachments for composite insulators assemblies NCD 2658/0
Attachments for v string crossarms SKETCH 5847/3
v- string synthetic insulators for poles:zdsc2, zds2b,zds2g NCD 2677/2
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :36 of 48
400 & 161 kV Sketch no.
Details for tubular steel poles SKETCH 3183/25
Arrangement for warning spheres on tubular poles SKETCH 3698/9
Ladder for tubular poles SKETCH 3690/6
Types of foundations SKETCH 3562/12
Templates and anchor bolts NCD 2663/1
Beams for carrying and leveling the templates and anchor
bolts
NCD 2692/2
Removable stepping stones for suspension poles SKETCH 3685/17
Details of removable platforms and handrailings on pole SKETCH 3711/11
161 kv - Catalogue number for tender only Sketch no.
Catalogue number for poles ZS1 B, G +6, +12 JDHK 7581e/0
Catalogue number for poles ZT1 B, D, +6, +9 JDHK 7582e/0
Catalogue number for poles ZS2 B, +6, +12 JDHK 7584e/0
Catalogue number for poles ZT2 B, D, +6, +9 JDHK 7583e/0
Catalogue number for poles ZMS2 B, G, +6, +12 JDHK 7579e/0
Catalogue number for poles ZTM2 G, H,T +6, +9 JDHK 7580e/0
Catalogue number for poles ZMSC1 B, G, +2,
+4;ZTMC1, +2, +4
JDHK 9011e/0
Catalogue number for poles ZMSC1 D, +4.5D, +9D,
+13.5D; ZTMC1 B, +5B, +10B
NCD 2374/1
Catalogue number for poles ZMSC2 B, G, +2, +4 NCD 496e/1
Catalogue number for poles ZMSM2 B +5, +10 NCD 890 /1
Catalogue number for poles ZTMM2 B, G, +6, +12 NCD 891/1
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :37 of 48
161 kV Sketch no.
Loading tree ZS1 B,G SKETCH 3522/5
Loading tree ZT1B,G,D SKETCH 3524/5
Loading tree ZS2 B,G SKETCH 3526/5
Loading tree ZT2 B,G,D SKETCH 3528/5
Loading tree ZMS2 B,G SKETCH 3567/5
Loading tree ZTM2 G,D,H SKETCH 3071/6
Loading tree ZTM2 V,T SKETCH 3070/6
Loading tree ZMSC1 B, G SKETCH 5102/3
Loading tree ZMSC1 D NCD 2382/2
Loading tree ZTMC1 SKETCH 5100/2
Loading tree ZTMC1 B NCD 2391/2
Loading tree ZMSC2 B,G SKETCH 5104/1
Loading tree ZMSM2 B NCD 824/1
Loading tree ZTMM2 B,G NCD 822/2
Diameter, thickness ZS1 B,G SKETCH 3530/4
Diameter, thickness ZS2 B,G SKETCH 3534/3
Diameter, thickness ZT1 B,G,D SKETCH 3532/4
Diameter, thickness ZT2 B,G,D SKETCH 3536/4
Diameter, thickness ZMS2 B,G SKETCH 3566/4
Diameter, thickness ZTM2 G,D,H,V,T SKETCH 3166/5
Diameter, thickness ZMSC1 B, G SKETCH 5101/1
Diameter, thickness ZMSC1 D NCD 2379/1
Diameter, thickness ZTMC1 SKETCH 4099/2
Diameter, thickness ZTMC1 B NCD 2380/2
Diameter, thickness ZMSC2 B,G SKETCH 5103/0
Diameter, thickness ZMSM2 B NCD 825/1
Diameter, thickness ZTMM2 B,G NCD 823/1
Attachments for phase crossarms (V-string insulators) for
ZMSM2 B
NCD 889/1
v- string insulators for ZMSM2 B NCD 2688/0
Attachments for phase crossarms for ZTMM2 B,G pole NCD 888/0
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :38 of 48
Attachments for tubular steel poles and crossarms SKETCH 3703/13
Suspension and tension hinges SKETCH 3553/10
Details for tubular steel poles - compact line SKETCH 5363/8
Attachments for suspension steel poles and crossarms - compact
line
SKETCH 5369/3
Attachments for composite insulators assemblies NCD 2646/1
Attachments for tension steel poles- compact line SKETCH 5370/3
Method of handrailing and platforms on crossarms SKETCH 3708/5
Length of embedment (H) NCD 1026/1
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :39 of 48
16. REVISIONS
Edition no: 1 - November 2000
1. Added 161 kV 3 type of poles: ZMSM2 B, ZTMM2 B,G
Added new drawings- NCD 822,823,824,825,890E,
2. Added method of galvanization, see para 9.3
3. Added option of conventional shipping, see para 10.3
4. Change drawing 3191/9 to 3191/10, drawing 3553/8 to 3553/9
Edition no: 2 - January 2001
1. Added length of embedment to 161 kV poles - see para. 5.6, drawing NCD 1023.
2. In para. 5.7 added that additional ladder in 161 kV poles shall started from platform
bellow the upper crossarm.
3. Added thickness and methods of galvanization for bolts and nuts - see para.9.3.
4. Para. 2 - threshold conditions -was changed.
5. Change of drawings:
5861 to 5861/2
5862 to 5862/2
NCD 171 e/1 to NCD 171 e/2
8603 e/1 to 8603 e/2
3070/4 to 3070/5
3071/4 to 3071/5
NCD 822 to NCD 822/1
NCD 823 to NCD 823/1
NCD 890 e to NCD 890/1
3562/10 to 3562/11
Edition no: 3 - March 2003 (prepared by Eng. David Chen)
1. Added two 161 kv compact poles : ZMSC1 D, ZTMC1 B.
2. updated para. 3.3, 3.4, 3.6.
3. Added standard ACI 318 for anchor bolts length - see para.4.
4. Added material of anchor bolts and their nuts - see para.5.1.5.
5. Changed drawings of 161 & 400kv composite insulator assemblies - see para.5.2.
6. updated para 5.2.
7. updated para 5.4.2
8. updated para 5.5.
9. Added details of anchor bolts and templates - see para.5.6.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :40 of 48
10. Added details for marking - see Para. 7.
11. updated para 8.
12. Para. 9.3. – galvanizing- apdated.
13. Changed anchor bolts shiping – see para. 10.2.
14. Added new drawings –NCD 2382/1, 2391/1, 2379/1, 2380/1, 2374/1, 2658/0,
2677/0, 2646/0, 2688/0, 2663/0, 2692/0.
15. Changed of drawings:
sketch 5850 to sketch 5850/1
sketch 5851 to sketch 5851/1
sketch 5132b/1 to sketch 5132b/2
NCD 825 to NCD 825/1
NCD 142/1 to NCD 142/2
sketch 5100 to sketch 5100/1
sketch 5102 to sketch 5102/1
sketch 4099 to sketch 4099/1
sketch 5101 to sketch 5101/1
NCD 496e to NCD 496e/1
NCD 1026 to NCD 1026/1
sketch 5363/4 to sketch 5363/5
sketch 3192/10 to sketch 3192/11
sketch 5363/4 to sketch 5363/5
sketch 3183/22 to sketch 3183/23
NCD 889 to NCD 889/1
sketch 3703/11 to sketch 3703/12
sketch 3192/10 to sketch 3192/11
sketch 5847/2 to sketch 5847/3
sketch 3685/15 to sketch 3685/16
sketch 3191/10 to sketch 3191/11
sketch 5370/1 to sketch 5370/2
16. Deleted drawing sketch 5860/1 (instead, added drawing NCD 2658/0).
Edition no: 4 –January 2010 (prepared by Eng. David Chen)
1. updated para. 1, 2, 3, 4, 5.1, 5.2, 5.5, 5.8, 6.
2. Changed figures 3, 4.
3. Added para.7.1.4, 7.1.5, 7.7.
4. updated para 9.2, 9.3, 10.2, 10.5, 13.
5. Added para 14.
6. updated appendix 4.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :41 of 48
7. Changed of drawings:
JDHK 9420e to JDHK 9420e/1.
SKETCH 5131b/1 to SKETCH 5131b/2.
NCD 175/1 to NCD 175/2.
NCD 180 to NCD 180/1.
NCD 194/1 to NCD 194/2.
SKETCH 5850/2 to SKETCH 5850/3.
SKETCH 5861/2 to SKETCH 5861/3.
SKETCH 3182/12 to SKETCH 3182/13.
SKETCH 3186/15 to SKETCH 3186/16.
SKETCH 3192/11 to SKETCH 3192/12.
NCD 2677 to NCD 2677/1.
SKETCH 3183/23 to SKETCH 3183/24.
SKETCH 3698/7 to SKETCH 3698/8.
SKETCH 3690/5 to SKETCH 3690/6.
SKETCH 3562/11 to SKETCH 3562/12.
NCD 2663 to NCD 2663/1.
NCD 2692 to NCD 2692/1.
SKETCH 3711/9 to SKETCH 3711/10.
SKETCH 3522/4 to SKETCH 3522/5.
SKETCH 3524/4 to SKETCH 3524/5.
SKETCH 3526/4 to SKETCH 3526/5.
SKETCH 3528/4 to SKETCH 3528/5.
SKETCH 3567/4 to SKETCH 3567/5.
SKETCH 3071/5 to SKETCH 3071/6.
SKETCH 3070/5 to SKETCH 3070/6.
SKETCH 5102/1 to SKETCH 5102/3.
NCD 2382/1 to NCD 2382/2.
SKETCH 5100/1 to SKETCH 5100/2.
NCD 2391/1 to NCD 2391/2.
SKETCH 5104 to SKETCH 5104/1.
NCD 824 to NCD 824/1.
NCD 822/1 to NCD 822/2.
SKETCH 4099/1 to SKETCH 4099/2.
NCD 2380/1 to NCD 2380/2.
SKETCH 3703/12 to SKETCH 3703/13.
SKETCH 3553/9 to SKETCH 3553/10.
SKETCH 5363/5 to SKETCH 5363/8.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :42 of 48
SKETCH 5369/2 to SKETCH 5369/3.
NCD 2646 to NCD 2646/1.
SKETCH 5370/2 to SKETCH 5370/3.
Edition no: 5 –August 2019 (prepared by Eng. David Chen)
1. Updated para. 1, 3, 4, 5.1.1, 5.1.2, 5.2, 5.3, 5.5, 5.6.1, 5.8, 6, 8.1, 9.1, 9.2, 9.3, 11,
12.
2. Appendix 5 was added.
3. Changed of drawings:
SKETCH 3182/13 to SKETCH 3182/14.
SKETCH 3186/16 to SKETCH 3186/17.
SKETCH 3192/12 to SKETCH 3192/13.
SKETCH 3191/11 to SKETCH 3191/12.
SKETCH 3183/24 to SKETCH 3183/25.
SKETCH 3182/13 to SKETCH 3182/14.
SKETCH 3698/8 to SKETCH 3698/9.
NCD 2692/1 to NCD 2692/2.
SKETCH 3685/16 to SKETCH 3685/17.
SKETCH 3711/10 to SKETCH 3711/11.
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :43 of 48
APPENDIX 1 – GENERAL DRAWING OF THE POLE
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :44 of 48
APPENDIX 2 - SUMMARY TABLE
Name
of
pole
Total
length
(m)
Total
weight
(ton)
External diameter
across angles (mm)
Maximum force and
moment at the base of pole
(ton x m)
Top
displacement
under service
load (m)
Note
Thickness (mm) B
endin
g
mom
ent
Tors
ion
mom
ent
Tra
n. or
Long. fo
rce
Ver
t. f
orc
e
Top
Bott
om
Gro
und
level
APPENDIX 3 - DELIVERY SCHEDULE
ITEM WEEKS Date of
delivery
to port
in
abroad
Date of
delivery
in
ISRAEL
1 2 3 4 5 ------
Bottom
part
Pole
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :45 of 48
APPENDIX 4 – PACKING LIST OF GOODS
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :46 of 48
APPENDIX 5- STATEMENT OF MANUFACTURING EXPERIENCE
I, ______________ (enter name), hereby state the following:
1. I________________ (enter name), am authorized to sign this statement on the
behalf of_________________("the manufacture").
2. I hold the position of _________________________________________ (enter
job title and description i.e. partner, production manager, sale manager, etc.) at
the Manufacturer.
3. I have been in this position since _______________ (enter date).
4. I am providing this statement with regards to I.E.C's tender number _______
("The Tender").
5.___________________ (the Manufacturer) have experience in manufacturing at least 10 (ten)
tapered tubular steel poles for at least 161 kv transmission line, in the last 10 (ten) years
(preceding the last date of submission the first stage documents).
6. The facts/details given in this statement have been checked and verified by me.
7. I hereby under take to provide, upon IEC's request and at its sole discretion, any
other documents (reference list, quantity, dates of supply, letter of recommendation etc.)
or other information requested for this Tender for purposes of proving said experience.
Signature: ______________
Date: __________________
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :47 of 48
APPENDIX 6 – DRAWINGS
Israel Electric Corp. Ltd.
Engineering Projects
Transmission Lines Division
Transmission Lines Engineering Headquarter
Specification NCS 14
For Tapered Tubular Steel Poles
161 kv, 400 kV
Edition no.: 5
Issued date: 27.8.2019
Page no. :48 of 48
APPENDIX 7
I.E.C QUALITY SPECIFICATION
Q – APP – 02
PROCUREMENT QUALITY REQUIREMENTS