Drawing Description Drawing No. Drawing Register SL 001 - 005 Introduction Series 000 StoLite Construction System Introduction SL 006 StoLite Construction System FC Sheet Information SL 007 StoLite Construction System Sheet layout SL 008 Panel Layout Series 100 StoLite Construction System Cavity Batten Setout (600 ctrs) - Isometric SL 100 StoLite Construction System Cavity Batten Setout (400 ctrs) - Isometric SL 101 StoLite Construction System Cavity Batten Setout Steel Frame/Thermal Break (600 ctrs) SL 102 StoLite Construction System Cavity Batten Setout (300 & 600 ctrs) Elevation SL 103 Foundation Series 200 StoLite Construction System Foundation Slab-on-ground SL 200 StoLite Construction System Insulated Slab-on-Ground SL 201 StoLite Construction System Rebated Slab-on-Ground - Render Finish SL 202 StoLite Construction System ESP Block Foundation Detail SL 203 StoLite Construction System Conc. Block Foundation Edge Detail SL 204 StoLite Construction System Solid Conc. Foundation Edge Detail SL 205 StoLite Construction System Conc.Continuous Perimeter Found.Wall SL 206 StoLite Construction System Timber Pile/Subfloor Ventilation (Parallel Wall) SL 207 StoLite Construction System Timber Pile/Subfloor Ventilation (Right Angled Wall) SL 208 StoLite Construction System Timber Subfloor with Jack Studs SL 209 StoLite Construction System Masonry Conc.Block in-ground Wall SL 210 StoLite Construction System Ribraft Floor System / Edge Detail SL 211 StoLite Construction System Maxraft Floor System / Edge Detail SL 212 Walls Series 300 StoLite Construction System Sheet layout SL 300 StoLite Construction System Cross Section SL 301 StoLite Construction System External Corner SL 302 StoLite Construction System Internal Corner SL 303 StoLite Construction System Vertical Control Joint SL 304 StoLite Construction System Horizontal inter-storey Control Joint SL 305 StoLite Construction System Drained Joint at Third Storey SL 306 StoLite Construction System Boxed Beam SL 307 StoLite Construction System Post Detail SL 308 THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC. VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TO ENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUAL MANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS. RBW DETAILS MUST BE ISSUED BY A; REGISTERED ARCHITECT, LICENSED DESIGNER OR CHARTERED ENGINEER STO DRAWING REGISTER PAGE 1 OF 5 The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site. STOLITE SYSTEM STOLITE CONSTRUCTION SYSTEM DRAWING REGISTER SL 001 2017

STOLITE CONSTRUCTION SYSTEM DRAWING REGISTER 2017

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Introduction Series 000 StoLite Construction System Introduction SL 006 StoLite Construction System FC Sheet Information SL 007 StoLite Construction System Sheet layout SL 008
Panel Layout Series 100 StoLite Construction System Cavity Batten Setout (600 ctrs) - Isometric SL 100 StoLite Construction System Cavity Batten Setout (400 ctrs) - Isometric SL 101 StoLite Construction System Cavity Batten Setout Steel Frame/Thermal Break (600 ctrs) SL 102 StoLite Construction System Cavity Batten Setout (300 & 600 ctrs) Elevation SL 103
Foundation Series 200 StoLite Construction System Foundation Slab-on-ground SL 200 StoLite Construction System Insulated Slab-on-Ground SL 201 StoLite Construction System Rebated Slab-on-Ground - Render Finish SL 202 StoLite Construction System ESP Block Foundation Detail SL 203 StoLite Construction System Conc. Block Foundation Edge Detail SL 204 StoLite Construction System Solid Conc. Foundation Edge Detail SL 205 StoLite Construction System Conc.Continuous Perimeter Found.Wall SL 206 StoLite Construction System Timber Pile/Subfloor Ventilation (Parallel Wall) SL 207 StoLite Construction System Timber Pile/Subfloor Ventilation (Right Angled Wall) SL 208 StoLite Construction System Timber Subfloor with Jack Studs SL 209 StoLite Construction System Masonry Conc.Block in-ground Wall SL 210 StoLite Construction System Ribraft Floor System / Edge Detail SL 211 StoLite Construction System Maxraft Floor System / Edge Detail SL 212
Walls Series 300 StoLite Construction System Sheet layout SL 300 StoLite Construction System Cross Section SL 301 StoLite Construction System External Corner SL 302 StoLite Construction System Internal Corner SL 303 StoLite Construction System Vertical Control Joint SL 304 StoLite Construction System Horizontal inter-storey Control Joint SL 305 StoLite Construction System Drained Joint at Third Storey SL 306 StoLite Construction System Boxed Beam SL 307 StoLite Construction System Post Detail SL 308
THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC. VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TO ENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUAL MANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS. RBW DETAILS MUST BE ISSUED BY A; REGISTERED ARCHITECT, LICENSED DESIGNER OR CHARTERED ENGINEER
STO DRAWING REGISTER
PAGE 1 OF 5
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
Drawing Description Drawing No.
Wall Penetrations & Fittings Series 350 StoLite Construction System Pipe Penetration Detail SL 350 StoLite Construction System Light Fitting/Fixing Detail SL 351 StoLite Construction System Tap Fitting/Fixing Detail SL 352 StoLite Construction System Handrail Bracket/Fixing Detail SL 353 StoLite Construction System Meterbox - Isometric SL 354 StoLite Construction System Meterbox - Cross Section SL 355 StoLite Construction System Downpipe Saddle Fixing & Wiring Details SL 356 StoLite Construction System Fan Vent Detail SL 357 StoLite Construction System Inter-Storey Junction with Poly Profile SL 358 StoLite Construction System Joint at Third Storey with Poly profile SL 359
Joinery Series 400 StoLite Construction System Alu. Joinery - Head Detail SL 400 StoLite Construction System Alu. Joinery - Sill Detail SL 401 StoLite Construction System Alu. Joinery - Jamb Detail SL 402 StoLite Construction System Int. Cnr Alu. Window/Door Joinery Jamb Detail SL 403 StoLite Construction System Entry Door Threshold Detail SL 404 StoLite Construction System Entry Door/Deck Threshold Detail SL 405 StoLite Construction System Bifold Door/Threshold Detail SL 406 StoLite Construction System Level Entry Threshold Detail SL 407 StoLite Construction System Garage Door - Timber Head Detail SL 408 StoLite Construction System Garage Door - Timber Jamb Detail SL 409 StoLite Construction System Garage Door - Rendered Head Detail SL 410 StoLite Construction System Garage Door - Rendered Jamb Detail SL 411
Parapets, Balustrades, Decks Series 500 StoLite Construction System Parapet/Metal Flashing Detail SL 500 StoLite Construction System Rendered Parapet Balustrade Detail SL 501 StoLite Construction System Parapet and/or Encl.Balustrade Wall Junction - Plan View SL 502 StoLite Construction System Flexible Flashing Install - Isometric SL 503 StoLite Construction System Metal Saddle Flashing & Cap Install - Isometric SL 504 StoLite Construction System StoFlexyl Meshed Saddle Flashing Install - Isometric SL 505 StoLite Construction System StoFlexyl Meshed Waterproofing Cap - Isometric SL 506 StoLite Construction System Balustrade/Enclosed Deck Detail SL 507 StoLite Construction System Enclosed Deck Cross Section SL 508 StoLite Construction System Cantilevered Slatted Deck SL 509 StoLite Construction System Non Cantilevered Slatted Deck SL 510 StoLite Construction System Independent Slatted Deck SL 511 StoLite Construction System Timber Beam / Pergola Detail SL 512 StoLite Construction System RWH/Scupper Opening SL 513
STO DRAWING REGISTER
THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC. VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TO ENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUAL MANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS. RBW DETAILS MUST BE ISSUED BY A; REGISTERED ARCHITECT, LICENSED DESIGNER OR CHARTERED ENGINEER
PAGE 2 OF 5
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
Drawing Description Drawing No.
Soffit Series 600 StoLite Construction System Flat Soffit/Wall Junction SL 600 StoLite Construction System Raking Soffit/Wall Junction SL 601 StoLite Construction System Face Fixed Fascia SL 602 StoLite Construction System Raking Soffit (Reversed) SL 603 StoLite Construction System Raking Soffit - Sto uPVC Control Joint SL 604 StoLite Construction System Soffit to Cladding Detail SL 605 StoLite Construction System Gutter/Wall Junction SL 606 StoLite Construction System Soffit at Window/Door Head SL 607
Roof Series 700 StoLite Construction System Apron Flashing SL 700 StoLite Construction System Parallel Apron Flashing SL 701 StoLite Construction System Inter-storey Transverse (Apron) Roof/Stopend Flashing SL 702 StoLite Construction System Inter-storey Flat (Membrane) Roof/Stopend Flashing SL 703 StoLite Construction System Inter-storey Roof Stop End Flashing - PlanView SL 704 StoLite Construction System Roof Penetration Gutter SL 705 StoLite Construction System Roof Parallel/Hidden Gutter SL 706 StoLite Construction System Face Fixed Fascia/Barge SL 707 StoLite Construction System Face Fixed Fascia/Membrane Roof SL 708 StoLite Construction System Roof/Wall Ridge SL 709 StoLite Construction System Framed Chimney or Penetration upto 1200mm SL 710
Dissimilar Material
Weatherboard Series 800 StoLite Construction System Ext. Corner Weatherboard/StoLite - Opt 1 SL 800 StoLite Construction System Ext. Corner Weatherboard/StoLite - Opt 2 SL 800-1 StoLite Construction System Ext. Corner Weatherboard/StoLite - Direct Fix SL 801 StoLite Construction System Int. Corner Weatherboard/StoLite - Opt 1 SL 802 StoLite Construction System Int. Corner Weatherboard/StoLite - Opt 2 SL 802-1 StoLite Construction System Int. Corner Weatherboard/StoLite - Direct Fix SL 803 StoLite Construction System Vertical Joint Flashing Weatherboard/StoLite - Opt 1 SL 804 StoLite Construction System Vertical Joint Flashing Weatherboard/StoLite - Opt 2 SL 804-1 StoLite Construction System Vertical Joint Flashing Weatherboard/StoLite - Opt 3 SL 804-2 StoLite Construction System Horizontal Junction Weatherboard/StoLite SL 805 StoLite Construction System Gable End Weatherboard/StoLite SL 806
STO DRAWING REGISTER
THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC. VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TO ENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUAL MANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS. RBW DETAILS MUST BE ISSUED BY A; REGISTERED ARCHITECT, LICENSED DESIGNER OR CHARTERED ENGINEER
PAGE 3 OF 5
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
Brick Series 810 StoLite Construction System External Corner Brick Veneer/StoLite SL 810 StoLite Construction System Internal Corner Brick Veneer/StoLite - Opt 1 SL 811 StoLite Construction System Internal Corner Brick Veneer/StoLite - Opt 2 SL 812 StoLite Construction System Interstorey Junction Brick Veneer/StoLite SL 813
Fibre Cement Sheet Series 820 series not issued
Concrete Block Series 830 StoLite Construction System External Corner Concrete Block/StoLite S L830 StoLite Construction System Internal Corner Concrete Block/StoLite SL 831 StoLite Construction System Vertical Joint Concrete Block/StoLite SL 832 StoLite Construction System Horizontal Junction Concrete Block/StoLite SL 833
Manufactured Stone - Schist & Natural Stone Series 840 StoLite Construction System Ext.Cnr Manuf. Stone/StoLite SL 840 StoLite Construction System Boxed Ext. Cnr Stone Veneer/StoLite S L841 StoLite Construction System Int. Cnr Manuf. Stone/StoLite SL 842 StoLite Construction System Vertical Junction Manuf. Stone/StoLite SL 843 StoLite Construction System Ext. Cnr Schist or Stone Veneer/StoLite SL 844 StoLite Construction System Int. Cnr Schist or Stone Veneer/StoLite SL 845 StoLite Construction System Vertical Junction Schist or StoneVeneer/StoLite SL 846 StoLite Construction System Horiz. Junction Schist or StoneVeneer/StoLite SL 847
Profile Metal Series 850 StoLite Construction System Ext. Cnr Horiz. Profiled Metal/StoLite SL 850 StoLite Construction System Int. Cnr Horiz. Profiled Metal/StoLite SL 851 StoLite Construction System Vertical Junction Horiz. Profiled Metal/StoLite SL 852 StoLite Construction System Horizontal Junction Horiz. Profiled Metal/StoLite SL 853 StoLite Construction System External Corner Vertical Profiled Metal/StoLite SL 854 StoLite Construction System Internal Corner Vertical Profiled Metal/StoLite SL 855 StoLite Construction System Horiz. Junction Vertical Profiled Metal/StoLite SL 856
STO DRAWING REGISTER
THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC. VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TO ENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUAL MANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS. RBW DETAILS MUST BE ISSUED BY A; REGISTERED ARCHITECT, LICENSED DESIGNER OR CHARTERED ENGINEER
PAGE 4 OF 5
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
StoTherm Panel EIFS Series 860 StoLite Construction System Ext. Cnr StoTherm/StoLite SL 860 StoLite Construction System Int. Cnr StoTherm/StoLite SL 861 StoLite Construction System Vertical Joint StoTherm/StoLite SL 862
DISSIMILAR JOINERY Series 870 TIMBER JOINERY StoLite Construction System Timber Window Joinery - Head Detail SL 870 StoLite Construction System Timber Window Joinery - Sill Detail SL 871 StoLite Construction System Timber Window Joinery - Jamb Detail SL 872 StoLite Construction System Timber Joinery - Timber Floor/Threshold Detail SL 873 StoLite Construction System Timber Joinery - Concrete Floor/Threshold Detail SL 874 NK PVCu JOINERY StoLite Construction System NK PVCu - Head Detail SL 875 StoLite Construction System NK PVCu - Sill Detail SL 876 StoLite Construction System NK PVCu - Jamb Detail SL 877 FLASHMAN JOINERY FLASHING SYSTEM StoLite Construction System Flashman Head Flashing SL 878 StoLite Construction System Flashman Sill Flashing SL 879 StoLite Construction System Flashman Jamb Flashing SL 880 HOMERIT PVC JOINERY StoLite Construction System Homerit PVC Joinery - Head Detail SL 881 StoLite Construction System Homerit PVC Joinery - Sill Detail SL 882 StoLite Construction System Homerit PVC Joinery - Jamb Detail SL 883
MOULDINGS & SHAPES Refer to - www.accumen.co.nz Lightweight exterior decorative moldings and shapes, including columns, architraves, cornices, window sills, fence caps, quoins that can be finished in Stolit K or MP sponge coloured finishing render. Note: Decorative mouldings require min. 10° slope to top surface and a drip edge.
STO DRAWING REGISTER
THESE DETAILS ARE ISSUED AS A GUIDE USING STANDARD BUILDING PRACTICES BASED ON THE NZBC. VARIOUS BUILDING COMPONENTS ARE DETAILED AND IT IS THE RESPONSIBILITY OF EACH TRADE INVOLVED TO ENSURE THAT THEIR PARTICULAR ELEMENTS ARE INSTALLED CORRECTLY. NOTE: REFER TO INDIVIDUAL MANUFACTURES FOR CURRENT DETAILS AND SPECIFICATIONS - SEE www.sto.co.nz FOR CURRENT DETAILS. RBW DETAILS MUST BE ISSUED BY A; REGISTERED ARCHITECT, LICENSED DESIGNER OR CHARTERED ENGINEER
PAGE 5 OF 5
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
DRAWING REGISTER
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
STOLITE CONSTRUCTION SYSTEM
THE STOLITE CONSTRUCTION SYSTEM HAS BEEN APPRAISED AS AN EXTERNAL WALL CLADDING SYSTEM FOR BUILDINGS WITHIN THE FOLLOWING SCOPE: · THE SCOPE LIMITATIONS OF NZBC ACCEPTABLE SOLUTION E2/AS1, PARAGRAPH 1.1; AND, · CONSTRUCTED WITH TIMBER FRAMING COMPLYING WITH THE NZBC; AND, · WITH A RISK SCORE OF 0-20, CALCULATED IN ACCORDANCE WITH NZBC ACCEPTABLE SOLUTION E2/AS1, TABLE 2;
AND, · SITUATED IN NZS 3604 WIND ZONES UP TO, AND INCLUDING ‘EXTRA HIGH’.
THE STOLITE CONSTRUCTION SYSTEM HAS ALSO BEEN APPRAISED FOR WEATHERTIGHTNESS AND STRUCTURAL WIND LOADING WHEN USED AS AN EXTERNAL WALL CLADDING SYSTEM FOR BUILDINGS WITHIN THE FOLLOWING SCOPE: · THE SCOPE LIMITATIONS OF NZBC ACCEPTABLE SOLUTION E2/AS1, PARAGRAPH 1.1; AND, · CONSTRUCTED WITH TIMBER OR STEEL FRAMING COMPLYING WITH THE NZBC; AND, · SITUATED IN SPECIFIC DESIGN WIND PRESSURES UP TO A MAXIMUM DESIGN DIFFERENTIAL ULTIMATE LIMIT STATE
(ULS) OF 2.5 KPa.
STOLITE RENDER SYSTEM
INCORPORATING: 1. 8mm LEVELITE BASECOAT RENDER 20kg BAG 2. STOARMAT MESHED REINFORCEMENT RENDER 23kg BAG 3. STOLIT K or MP COLOURED FINISHING RENDER 25kg PAIL 4. STOCOLOR : MAXICRYL MATT FACADE PAINT 15lt PAIL
: LASTIC SATIN FACADE PAINT 15lt PAIL : LOTUSAN MINERAL RESIN PAINT 15lt PAIL
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
ALL EDGES MUST BE SUPPORTED WITH H3.1 CAVITY BATTENS ON
FRAMING, ALL SHEETS FIXED VERTICALLY.
CAVITY BATTEN LAYOUT AND FIXINGS AS PER MANUFACTURERS
RECOMMENDATIONS AND WIND ZONES
UP TO VH WIND ZONES GENERALLY 600mm FRAMING 200mm CENTRES ON STUDS 150mm CENTRES ON TOP AND
BOTTOM PLATES AND MIDWAY THROUGH DWANGS & 150mm CTRS ON
ALL FRAMING
BACK PRIME ANY AREAS SUBJECT TO MOISTURE
SHEET MANUFACTURER
1200mm
24 00
m m
6mm MIN.
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
STO LITE SHEETS
1. KEEP DRY BEFORE USING. 2. READ SPECIFICATIONS AND CHECK DRAWINGS, DETAILS, FRAMING, UNDERLAY, FLASHING TAPES, AND BLOCKING IS SATISFACTORY 3. INSTALL STO PVC TRAY AND JOINERY FLASHINGS AS PER STO DETAILS (BUILDER TO SUPPLY ALUMINIUM HEAD FLASHINGS WITH STOPENDS) 4. CHECK LAYOUT AND INSTALL SHEETS VERTICALLY STARTING FROM BOTTOM PLATE 5. STAGGER VERTICAL SHEET JOINTS TO AVOID CONTINUOUS JOINS - EXCEPT AT CONTROL JOINTS 6. SECURE SHEETS WITH FIXINGS AS PER MANUFACTURER DETAILS 7. BUTT INTERNAL CORNERS 8. MEASURE DISTANCES ACCURATELY TO AVOID NARROW IN FILLS OR GAPS
SAFE WORKING PRACTICE
1. HAVE SUFFICIENT PEOPLE TO LIFT SHEETS ON SITE 2. WEAR PROTECTIVE CLOTHING, EYE AND EAR PROTECTION AND DUST MASK OR RESPIRATOR WHEN CUTTING OR SANDING 3. USE A CIRCULAR SAW FITTED WITH A DIAMOND BLADE OR F/C SCRIBER AND HEPA VACUUM WHEN CUTTING 4. CONTAIN CUTTING AREA TO MINIMIZE DUST - HEPA VACUUM UP RESIDUE 5. PROVIDE SUITABLE ACCESS PLATFORMS, EQUIPMENT AND TOOLS TO CARRY OUT THE WORK 6. COMPLY WITH HEALTH AND SAFETY REGULATIONS AND MAINTAIN FIRST AID EQUIPMENT AS PER THE LEGISLATION
HORIZONTAL CONTROL JOINTS AT INTER-STOREY JUNCTIONS OR AT 5400mm MAX. ON CONTINUOUS STUDS
VERTICAL CONTROL JOINTS - 5400mm MAX.CTRS OR AT DISSIMILAR MATERIAL
200
VERTICAL CONTROL JOINT OR 200mm OVERLAP
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
H3.1 TIMBER CAVITY BATTENS @ 300mm MIN.CTRS
STOLITE RENDER SYSTEM
6mm FC SHEET INSTALL AS PER MANUFACTURERS INSTRUCTION
STO uPVC CLIPON FOOT TRAY REMOVE BACK TAB IF REQUIRED uPVC VERMIN TRAY WITH 15mm MIN. DRIP EDGE
WALL UNDERLAY MEETING REQUIREMENTS E2/AS1
CONCRETE FOUNDATION AS PER NZS3604 OR SPECIFIC ENGINEERING REQUIREMENTS
MESH SHEET JOINT
FIXINGS: 200mm on STUDS 150mm on TOP & BOTTOM PLATES 300mm on DWANGS
SHEETS FIXED VERTICALLY
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 100
H3.1 TIMBER CAVITY BATTENS @ 400mm MIN.CTRS
STOLITE RENDER SYSTEM
STO uPVC CLIPON FOOT TRAY REMOVE BACK TAB IF REQUIRED uPVC VERMIN TRAY WITH 15mm MIN. DRIP EDGE
WALL UNDERLAY MEETING REQUIREMENTS E2/AS1
CONCRETE FOUNDATION AS PER NZS3604 OR SPECIFIC ENGINEERING REQUIREMENTS
8mm LEVELITE BASECOAT RENDER
6mm FC SHEET INSTALL AS PER MANUFACTURERS INSTRUCTION
MESH SHEET JOINT
SHEETS FIXED VERTICALLY
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 101
STOLITE RENDER SYSTEM
6mm FC SHEET INSTALL AS PER MANUFACTURERS INSTRUCTION
STO uPVC CLIPON FOOT TRAY REMOVE BACK TAB IF REQUIRED uPVC VERMIN TRAY WITH 15mm MIN. DRIP EDGE
WALL UNDERLAY MEETING REQUIREMENTS E2/AS1
CONCRETE FOUNDATION AS PER NZS3604 OR SPECIFIC ENGINEERING REQUIREMENTS
THERMAL BREAK STRIPS WITH A MIN. R VALUE of 0.3 TO ALL STEEL FRAMING
MESH SHEET JOINT
SHEETS FIXED VERTICALLY
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 102
STUDS
H3.1 TIMBER BATTENS FIXED OVER FRAME & BUILDING
UNDERLAY H3.1 HORIZONTAL SPACERS x
100mm LONG, FIX WITH ONE NAIL CENTERED. HORIZONTAL SPACERS
MUST BE SET TO A FALL 5° MIN.
NOTE: IF STUDS ARE PLACED AT 400 mm CTRS NO INTERMEDIATE BATTENS ARE REQUIRED. 100mm LONG SPACERS WILL BE REQUIRED ON BOTTOM PLATE & FIXINGS ARE ALL AT 200mm CTRS
2nd LEVEL
INTERMEDIATE CAVITY BATTENS REQUIRED ON 600mm FRAMING
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 103
TIMBER FRAMING TO NZS 3604
DPC
STOLITE RENDER SYSTEM
CAVITY SPACERS TO SUIT FIXINGS
AS PER NZS 3604
STO RENDER SYSTEM ON FOUNDATION
CONCRETE SLAB/REINFORCING AS PER NZS 3604 OR ENGINEER SPECIFIC DESIGN - NOT SHOWN
FOR CLARITYINSULATION AS PER NZBC
- clause H1
STO uPVC CLIPON FOOT TRAY REMOVE BACK TAB IF REQUIRED
10 0m
m M
S to
R en
de r
50 m
m Fl
ex yl
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
STO uPVC CLIPON FOOT TRAY REMOVE BACK TAB IF REQUIRED
6mm OVERHANG RECOMMENDED TO AVOID VARIANCES IN FOUNDATION
TIMBER FRAMING TO NZS 3604
DPC
SCALE 1:5
22 5m
m M
WALL UNDERLAY
STOLITE RENDER SYSTEM
CAVITY SPACERS TO SUIT FIXINGS
6mm 5
DPM
CONCRETE SLAB/REINFORCING AS PER NZS 3604 OR ENGINEER SPECIFIC DESIGN - NOT SHOWN
FOR CLARITYINSULATION AS PER NZBC -
clause H1
10 0m
m M
S to
R en
de r
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
TIMBER FRAMING TO NZS 3604
DPC
SCALE 1:5
INTERNAL LINING
STO uPVC CLIPON FOOT TRAY REMOVE BACK TAB IF REQUIRED
WALL UNDERLAY
CAVITY SPACERS TO SUIT FRAMING
50 m
m C
la d.
TO P
A V
E D
G L
CONCRETE SLAB/REINFORCING AS PER NZS 3604 OR ENGINEER SPECIFIC DESIGN - NOT SHOWN
FOR CLARITYINSULATION AS PER NZBC - clause H1
10 0m
m M
NOMINAL 20x45mm H3.1 TIMBER CAVITY VERTICAL BATTENS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SPECIFIC DESIGN
DPM REQUIRED ON FOUNDATION FOR POORLY DRAINED SITES OTHERWISE TERMINATE AT BOTTOM EXTERNAL CORNER OF FOUNDATION
WALL UNDERLAY NOMINAL 20x45mm H3.1 TIMBER CAVITY BATTENS
STOLITE RENDER SYSTEM
6mm FIBRE CEMENT SHEET
uPVC VERMIN TRAY WITH min. 15mm DRIP EDGE STO uPVC CLIPON FOOT TRAY REMOVE BACK TAB IF REQUIRED
DPC
SPECIFIC DESIGN
STOFLEXYL WATERPROOFING TO REBATE, CONTINUE TO 50mm PAST STO RENDER TERMINATION POINT
NOTE: INSTALL STOFLEXYL UNDER DPM AT TRANSITION IF REQUIRED FOR POORLY DRAINED SITES.
DPM
50 m
m cl
ad di
5m m
G AP
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SPECIFIC DESIGN
SPECIFIC DESIGN
DPC
NOTE: SHELL OF BLOCK CAN SUPPORT BOTTOM PLATE WHEN SLAB IS TIED TO FOUNDATION
50 m
m cl
ad di
ng 15
0m m
to p
av ed
DPM
6mm FIBRE CEMENT SHEET STOLITE RENDER SYSTEM
CAVITY SPACERS TO SUIT FIXINGS uPVC VERMIN TRAY WITH min.15mm DRIP EDGE STO uPVC CLIPON FOOT TRAY - REMOVE BACK TAB IF REQUIRED
NOMINAL 20x45mm H3.1 TIMBER CAVITY BATTENS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
DPM
ENGINEER DESIGN (SED)
6mm FIBRE CEMENT SHEET STOLITE RENDER SYSTEM
CAVITY SPACERS TO SUIT FIXINGS uPVC VERMIN TRAY WITH min.15mm DRIP EDGE STO uPVC CLIPON FOOT TRAY - REMOVE BACK TAB IF REQUIRED
NOMINAL 20x45mm H3.1 TIMBER CAVITY BATTENS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 205
DPC
- REFER NZBC - Clause H1 as
p er
N ZS
36 04
or S
E D
as p
er N
ZS 36
04 or
S E
STO uPVC CLIPON FOOT TRAY REMOVE BACK TAB IF REQUIRED
WALL UNDERLAY
STOLITE RENDER SYSTEM
FIBRE CEMENT SHEET
uPVC VERMIN TRAY WITH min. 15mm DRIP EDGE CAVITY SPACERS TO SUIT FIXINGS
NOTE: 1. CONTINUOUS PERIMETER
2. CLEARANCE BETWEEN CLADDING AND ADJACENT GROUND - REFER NZS3604:2011
3. SED - Specific Engineer Design
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SCALE 1:5
FOR TIMBER & PILE SETOUT REQUIREMENTS 20
H4 TREATED BASEBOARDS WITH 20mm CONTINUOUS SUB FLOOR VENTILATION GAP BETWEEN
6mm FIBRE CEMENT SHEET
WALL UNDERLAY
20
STO uPVC CLIPON FOOT TRAY REMOVE BACK TAB IF REQUIRED
uPVC VERMIN TRAY WITH min. 15mm DRIP EDGE
50 m
m C
la d.
CAVITY SPACER SET TO A FALL (5° MIN.FROM THE HORIZONTAL)
100mm DRAPE TO DOUBLE-SIDED PERFORATED
FOIL INSULATION R = 0.9 - REFER NZBC - Clause H1
NOTE: FOR CLEARANCE BETWEEN CLADDING AND ADJACENT GROUND - REFER NZS3604:2011
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 207
SELECTED FLOORING
H5 TREATED PILE - REFER NZS 3604 FOR TIMBER & PILE
SET OUT REQUIREMENTS H4 TREATED BASEBOARDS WITH 20mm CONTINUOUS SUB FLOOR VENTILATION GAP BETWEEN
100mm MIN.DRAPE TO DOUBLE-SIDED PERFORATED
FOIL INSULATION R = 0.9 - REFER NZBC - Clause H1
STO uPVC VENTED VERMIN TRAY WITH min 15mm DRIP EDGE STO uPVC CLIPON TRAY REMOVE BACK TAB IF REQUIRED
CAVITY SPACER SET TO A FALL (5° MIN.FROM THE HORIZONTAL)
MIN. H1.2 TREATED FLOOR JOISTS BOUNDARY FLOOR JOISTS UNDER LOAD BEARING WALLS
20 20
NOTE: FOR CLEARANCE BETWEEN CLADDING AND ADJACENT GROUND - REFER NZS3604:2011
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 208
FOIL INSULATION R = 0.9 - REFER NZBC - Clause H1
JACK FRAMING IN AS PER NZS3604 6.10.2
50 50
OVERHANG BOUNDARY JOIST TO ALLOW CLADDING TO LAP SUBFLOOR CLADDING
6mm FIBRE CEMENT SHEET
WALL UNDERLAY
STO uPVC CLIPON FOOT TRAY REMOVE BACK TAB IF REQUIRED
uPVC VERMIN TRAY WITH min. 15mm DRIP EDGE
CAVITY SPACER SET TO A FALL (5° MIN.FROM THE HORIZONTAL)
PROVIDE SHEET BRACING MATERIAL and VENTILATION AS PER NZS 3604
NOTE: FOR CLEARANCE BETWEEN CLADDING AND ADJACENT GROUND - REFER NZS3604:2011
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 209
SLAB-ON-GROUND FLOOR & CONC.MASONRY WALLS AS PER NZS 4210/4229/4230 & 4218 AND ENGINEERS DRAWINGS
ALLOW ADEQUATE TIME FOR BLOCK TO DRY/STABALISE BEFORE PLASTERING NORMALLY FROM 4-8 WEEKS IN AVERAGE DRYING CONDITIONS.
TIMBER FRAMING TO NZS 3604
50 m
SELECTED INTERIOR RENDER/FINISH
NZBC COMPLIANT WATERPROOF TANKING MEMBRANE
STO FLEXYL MESHED WATERPROOFING BANDAGE OVER TANKING SYSTEM FROM 150mm ABOVE GROUND
STOARMAT RENDER SYSTEM
STOLITE RENDER SYSTEM
NOMINAL 20x45mm H3.1 TIMBER CAVITY BATTENS
STO uPVC VENTED VERMIN TRAY WITH min 15mm DRIP EDGE STO uPVC CLIPON TRAY REMOVE BACK TAB IF REQUIRED
6mm FIBRE CEMENT SHEET
NOTE: FOR CLEARANCE BETWEEN CLADDING AND ADJACENT GROUND - REFER NZS3604:2011
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
DESIGN OR ENGINEER (SED) Reinforcing not shown for clarity
WALL UNDERLAY
6mm FIBRE CEMENT SHEET STOLITE RENDER SYSTEM
CAVITY SPACERS TO SUIT FIXINGS uPVC VERMIN TRAY WITH min.15mm DRIP EDGE STO uPVC CLIPON FOOT TRAY - REMOVE BACK TAB IF REQUIRED
RIBRAFT POLYSTYRENE POD INSTALLATION IN ACCORDANCE TO FIRTH RIBRAFT CONSTRUCTION DETAILS
300
NOMINAL 20x45mm H3.1 TIMBER CAVITY BATTENS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 211
STO uPVC CLIPON FOOT TRAY - REMOVE BACK TAB IF REQUIRED
SCALE 1:10
1. CONCRETE SLAB/REINFORCING AS PER NZS 3604, SPECIFIC DESIGN OR ENGINEER (SED)
Reinforcing not shown for clarity 2. WHERE INSULATION OS BELOW GROUND, APPLY TWO (2) COATS OF
STOFLEXYL TO MAXRAFT INSULATION BEFORE COMMENCING 3. 150mm MIN. CLEARANCE FROM SLAB LEVEL TO EXTERIOR PAVING,
225mm MIN. CLEARANCE FROM SLAB LEVEL TO UNPAVED GROUND TO E2/AS1
SOLID COMPACTION 800mm MIN.PAST EDGE OF FOUNDATION
10 0
10 0
50 25
0 50 10
450 STOMULTI SCREED MESHED BASECOAT FINISHED IN 1.0mm FLOAT or STOLIT K FINISHING RENDER, PAINTED IN STOCOLOR MAXICRYL
NOMINAL 20x45mm H3.1 TIMBER CAVITY BATTENS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 212
SCALE: N.T.S
SHEET LAYOUT - LINE UP SHEETS WITH OPENINGS, TO FORM STO CONTROL JOINTS
100min. x 200mm DIAGONAL BUTTERFLY REINFORCEMENT
PREMESHED STO CORNER ANGLE
STOARMAT RENDER MESH COAT OVER LEVELLITE BASE COAT
1. SHEET JOINTS MUST NOT COINCIDE WITH EDGE OF JOINERY UNLESS A CONTROL JOINT IS TO BE FORMED. 2. ALL SHEET EDGES SHALL LINE THROUGH AND BE SUPPORTED BY A FRAMING MEMBER. 3. INSTALL SHEETS AS PER DETAILS USING NOMINAL 20x45mm H3.1 TIMBER CAVITY BATTENS 4. STAGGER VERTICAL SHEET JOINTS AT INTERSTOREY JOINT. 5. ALL SHEET EDGES SHALL BE A TIGHT BUTT FIT MESHED WITH 100mm JOINTING TAPE IN BASECOAT. 6. FLASHING AS FOLLOWS
- HORIZONTAL STO uPVC 12mm CONTROL JOINT AT INTERSTOREY JUNCTIONS - STO 8mm VERTICAL CONTROL JOINTS @ 5.4m crs max. - INTER-STOREY DRAINED JOINT EVERY THIRD STOREY
SHEET JOINT min. 200mm FROM ANY PARALLEL
OPENINGS IF NOT CONTROL JOINT
100mm JOINTING MESH OVER ALL JOINTS
INTER-STOREY CONTROL JOINT
OVERLAP OPENINGS AT LEAST 200mm
PREMESHED STO CORNER ANGLE
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
TIMBER FRAMING TO NZS3604
100mm min. HORIZONTAL SPACER AT 5° ON FRAMING min 50mm VERTICAL GAP BETWEEN OTHER SPACERS AND VERTICAL BATTENS WALL UNDERLAY H3.1 TIMBER CAVITY BATTENS 6mm FIBRE CEMENT SHEET
STO LEVELLITE BASE COAT 8mm
100mm JOINTING MESH STOARMAT MESH COAT RENDER STO COLOURED FINISHING RENDER STO COATING
STO uPVC CLIP-ON FOOT TRAY TO OVERHANG BOTTOM PLATE BY 50mm
VENTED VERMIN TRAY WITH min 15mm DRIP EDGE TO BOTTOM OF SHEET
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
6mm FIBRE CEMENT SHEET 20mm DRAINED CAVITY STOLITE RENDER SYSTEM
STO PREMESHED CORNER BEAD OR STAINLESS STEEL CORNER ANGLE
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SHEET FIXING AS PER MANUFACTURERS RECOMMENDATIONS
STO RENDER SYSTEM
BUILDING UNDERLAY CONTINUOUS AROUND CORNERS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
STO CAVITY BATTEN
WALL UNDERLAY CONTINUOUS
WITH MS SEALANT IN STOARMAT MESH COAT
NOTE: REMOVE CONTROL JOINT TAB CAREFULLY AS SOON AS STOARMAT RENDER HAS SET TO AVOID CRACKS IN SYSTEM
VERTICAL CONTROL JOINTS REQUIRED AT 5.4M MAXIMUM CENTERS
USE A POLY PACKER TO FORM GAP IN BASECOAT BEFORE INSTALLING
STO uPVC CONTROL JOINT STOLITE RENDER SYSTEM
6mm FIBRE CEMENT SHEET
NOMINAL 20x45mm H3.1 TIMBER CAVITY BATTEN
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
STOLITE RENDER SYSTEM
1. ALTERNATIVELY USE PRE-MESHED EPS MOLDING TO COVER INTER-STOREY JOINT 2. INSTALL STO uPVC 12mm CONTROL JOINT IN STOARMAT MESH COAT 3. ONLY SUITABLE FOR 2 STOREY. SEE SL 306 FOR THIRD STOREY 4. ENSURE THERE ARE NO FIXINGS INTO THE FLOOR JOIST 5. VERTICAL CAVITY BATTENS ARE INSTALLED WITH A 15mm GAP AT INTERSTOREY JOINT
SCALE: 1:2
A
1/3 WAY DOWN FROM TOP OF THE JOIST.
HORIZONTAL CAVITY SPACERS
USE A POLY PACKER TO FORM GAP IN BASECOAT BEFORE INSTALLING STO uPVC 12mm CONTROL JOINT WITH MS SEALANT IN STOARMAT MESH COAT
WALL UNDERLAY - ENSURE UNDERLAY RUNS CONTINUOUS OVER JOINT 6mm FIBRE CEMENT SHEET
STOLITE RENDER SYSTEM
HORIZONTAL CAVITY SPACERS
NOMINAL 20x45mm H3.1 TIMBER CAVITY BATTEN
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
STOLITE CLIP-ON FOOT TRAY
ALLOW TO RENDER BEHIND THEN SEAL WITH MS SEALANT OR STO SEAL TAPE
1. AS REQUIRED TO LIMIT CONTINUOUS CAVITY CONSTRUCTION TO TWO STOREYS. FLASHING BACK AND FRONT COVER TO BE A MINIMUM 35mm EXCLUDING DRIP EDGES
2. IN EXTRA HIGH WIND ZONE INCREASE FLASHING COVER TO 60mm MIN.AND USE A RIGID UNDERLAY
TIMBER FRAMING TO NZS 3604
SCALE: 1:2
M IN
.C O
V E
R M
IN .C
O V
E R
35 m
m 35
m m
20mm DRAINED & VENTED CAVITY
100mm HORIZONTAL CAVITY SPACER SET TO A FALL
WALL UNDERLAY - ENSURE UNDERLAY RUNS CONTINUOUS OVER JOINT
WALL UNDERLAY - ENSURE UNDERLAY RUNS CONTINUOUS OVER JOINT
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 306
MIN. 35mm HIGH BACK FLASHING ON H3.1 PACKER AT VENTS
FIBRE CEMENT SOFFIT
CAVITY BATTEN
NOTE: STOARMAT RENDER ON FIBRE CEMENT SOFFIT WITH 3mm STO FINISHING EDGE
STO uPVC CLIP ON TRAYS
WALL UNDERLAY
TRAY
TIMBER FRAMING TO NZS 3604
5mm GAP 5mm GAP
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
STOLITE RENDER SYSTEM
VERTICAL BATTEN
STO uPVC CLIPON FOOT TRAY REMOVE BACK TAB IF REQUIRED
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
NOMINAL 20x45mm H3.1 CAVITY BATTENS
8/10mm SEALANT BEAD ON PEF ROD BETWEEN PIPE AND RENDER
PIPE OR OTHER PENETRATION SLOPED DOWNWARDS
NOTE: INSTALL FLASHING TAPE WITH 100mm CLEARANCE AROUND PIPE ONTO WALL UNDERLAY AND WRAP 25mm ROUND PIPE.
WHERE MIN 75mm BLOCKING SUPPORTS THE WALL UNDERLAY AROUND THE PENETRATION THE FLASHING TAPE CAN BE OMITTED BUT A FACE FIXED EXTERIOR FLANGE WITH SEALANT IS REQUIRED AS PER E2AS1 FIG.68
TIMBER FRAMING TO
NZS3604
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
CAVITY BATTENS
SCALE 1:2
WALL UNDERLAY
50 x 3mm EPDM WASHER GASKETS REQUIRED AROUND FIXINGS AND PLATE TO PROVIDE WATERTIGHTNESS
TIMBER PACKER SLOPED AT 5° 50mm min CLEARANCE FROM
CAVITY BATTENS
ALL WIRING SHOULD BE ENCLOSED IN CONDUIT
CABLES SLOPE OUT
STOLITE RENDER SYSTEM
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
PROVIDE TIMBER BLOCKING AT TAP
FLASHING TAPE 100mm ONTO UNDERLAY
25mm ONTO TAP CONNECTION
CAVITY BATTENS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SELECTED HANDRAIL
DEGREES min. 50mm CLEARANCE FROM CAVITY
BATTENS
NOTE: USE A FIXING PLATE ON HANDRAILS TO AVOID POINT LOADING
50 x 3 mm EPDM WASHER GASKETS REQUIRED AROUND FIXINGS BETWEEN PLATE AND RENDER TO PROVIDE WATERTIGHTNESS
TIMBER BLOCKING BETWEEN STUDS AS
REQUIRED
20mm DRAINED CAVITY
INSTALL HANDRAIL PLATES OVER STO RENDER SYSTEM USING METAL SPACERS TAKEN BACK TO STRUCTURE TO TAKE LOAD IF REQUIRED TO AVOID STRESSING RENDER
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SCALE 1:10
STOLITE RENDER SYSTEM FIBRE CEMENT SHEET FLASHING TAPE HORIZONTAL CAVITY BATTEN AT MIN.10° SLOPE. EXTEND 100mm INTO CAVITY MS SEALANT
STOLITE CLIPON FOOT TRAY OR STO 10mm RENDER STOP BEAD TO BE USED AROUND PERIMETER OF METER BOX AS FINISHING EDGE WITH MS SEALANT BEAD
CAVITY BATTEN
ONTO WALL UNDERLAY
OF METERBOX
50 m
m G
A P
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SCALE 1:2
CAVITY BATTEN WITH 50mm GAP FROM HORIZONTAL SLOPED BATTEN AT BOTTOM JUNCTION
FLASHING TAPE MIN. 10° SLOPED BATTEN ONTO WALL UNDERLAY
HORIZONTAL BATTEN SLOPED AT 10°
FLASHING TAPE SEALED TO METERBOX AND WALL UNDERLAY
METERBOX
WALL UNDERLAY RETURNED INTO OPENING WITH FLASHING TAPE 25mm ONTO METERBOX
8 8
INTERNAL LINING
MS SEALANT OVER PEF BACKER ROD TO PERIMETER OF METERBOX
MS SEALANT OVER PEF BACKER ROD TO PERIMETER OF METERBOX
STO 10mm FINISHING EDGE
BUILDER
BUILDER
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
uPVC OR OTHER DOWNPIPE - SIZE REFER NZBC E1 Table 5
6mm FIBRE CEMENT SHEET
CLEARANCE FROM VERTICAL CAVITY
VERTICAL BATTENS
WALL UNDERLAY
CABLE/WIRING
PVC CONDUIT SLEEVE INSTALLED AT 5 DEGREES DOWNWARD SLOPE TO MESH COAT
1. DOWNPIPE/CLIP - SADDLE DETAIL
2. WIRING PENETRATION DETAIL NOTE: ENSURE THE AMOUNT OF PENETRATIONS THROUGH THE SYSTEM IS KEPT TO A MINIMUM. THE WEATHERSEALING OF ALL WIRING, ETC AS SHOWN, IS THE RESPONSIBILITY OF THE APPLICABLE TRADE
STOLITE RENDER SYSTEM 6mm FIBRE CEMENT SHEET VERTICAL BATTENS WALL UNDERLAY
TIMBER FRAMING TO NZS3604
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 356
LEAVE 40mm DRAINAGE GAP IN MIDDLE
FA N
C O
V E
CAVITY BATTENS
NOTE: LEAVE 40mm DRAINAGE GAP IN SEALANT AT BOTTOM OF FAN COVER. INSTALL FLASHING TAPE 100mm AROUND PIPE ONTO WALL UNDERLAY AND WRAP 25mm ROUND PIPE. FOR FLEXIBLE PIPES, TAPE PIPE TO FAN COVER, APPLY STO JOINT SEAL, TAPE AROUND TAPE BEFORE PLACING IN HOLE. ALWAYS FINISH RENDER BEFORE INSTALLING FAN COVER
TIMBER FRAMING AS PER NZS 3604
SCREW FIXING
MS SEALANT AT PIPE JUNCTION (STO SEAL TAPE ON FLEXIBLE PIPES)
MS SEALANT TO HEAD AND SIDES
FLEXIBLE FLASHING TAPE
MS SEALANT AT PIPE JUNCTION (STO SEAL TAPE ON FLEXIBLE PIPES)
PEF ROD
PEF ROD
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
PREMESHED ARCHITECTURAL MOLDING OVER INTERSTOREY JOINT FIXED OVER STOARMAT MESH COAT
STOLITE RENDER SYSTEM
A: INTERSTOREY PANEL JOINT CENTRED 1/3 WAY
DOWN FROM TOP OF JOIST
NOTE: 1. ENSURE VERTICAL CAVITY BATTENS ARE INSTALLED WITH A min.15mm GAP AT INTER-STOREY JOINT 2. INSTALL STO uPVC 12mm CONTROL JOINT OVER 75mm CAP ON ANCHOR 3. ONLY SUITABLE FOR 2 STOREY - REFER DRAWING SHEET SL 359 FOR THIRD STOREY DETAIL 4. ENSURE THERE ARE NO FIXINGS INTO FLOOR JOIST
A 15
6mm FIBRE CEMENT SHEET
5mm GAP
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 358
PREMESHED ARCHITECTURAL MOLDING OVER INTER-STOREY JOINT FIXED OVER STOARMAT MESH COAT
STOLITE RENDER SYSTEM
DRIP EDGE STOLITE PLASTER SYSTEM
1. AS REQUIRED TO LIMIT CONTINUOUS CAVITY CONSTRUCTION TO TWO STOREYS, FLASHING BACK AND FRONT COVER TO BE A MINIMUM 35mm EXCLUDING DRIP EDGES
2. IN EXTRA HIGH WIND ZONES INCREASE THE FLASHING COVER TO 60mm MIN.AND USE A RIGID UNDERLAY
35 m
m M
INTER-STOREY FLASHING 15°MIN.SLOPE AND 5mm MIN.GAP
ADDITIONAL WALL UNDERLAY DRESSED OVER FLASHING
VERMIN TRAY/CAVITY BASE CLOSER WITH MIN.15mm DRIP EDGE
STOLITE CLIP-ON FOOT TRAY
100mm HORIZONTAL CAVITY SPACER SET TO A FALL
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 359
2017
1. FIBRE CEMENT SHEET TO OVERHANG CAVITY CLOSER BY 15mm min. FIT CLIPON TRAY AND LEAVE 5mm min. CLEARANCE TO HEAD FLASHING.
2. PROPRIETARY ALUM. HEAD FLASHING TO COVER WINDOW FACING BY 10mm SLOPED 15° WITH min. 35mm UPSTAND TAPED TO WALL UNDERLAY. ALLOW HEAD FLASHING TO PASS JAMBS BY 20mm FIT STOP ENDS IN CAVITY. FLASHING TAPE SYSTEM TO BE INSTALLED AROUND JOINERY OPENINGS AS PER E2/AS1 BY BUILDER.
3. IN EXTRA HIGH WIND ZONES INCREASE FLASHING COVER TO 60mm MIN.AND USE A RIGID UNDERLAY
SCALE 1:2
FLASHING TAPE ONTO WALL UNDERLAY
VENTED CAVITY CLOSER min. 15mm UP STOLITE CLIP-ON TRAY WITH MIN 5mm GAP
ALUMINIUM WINDOW HEAD FLASHING WITH 15° SLOPE AND 10mm COVER AT WINDOW HEAD
MIN. 5mm GAP REQUIRED
SEALANT REQUIRED FOR VERY HIGH AND EXTRA HIGH WIND ZONES
35 m
m M
WALL UNDERLAY
STOLITE RENDER SYSTEM
20mm DRAINED CAVITY
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
JOINERY SUPPORT BAR REQUIRE FOR OPENINGS OVER 600mm
1. SEALANT IS APPLIED TO THE SILL AND JAMBS 2. uPVC SILL FLASHING TO BE PLACED UNDER JAMB FLASHING - CUT TABS
OFF SILL APPROX 30mm EITHER END AND SLIP UNDER uPVC JAMB FLASHING 3. ALLOW 3mm GAP BETWEEN WINDOW JOINERY AND FIBRE CEMENT SHEET FOR
STOLITE uPVC FLASHINGS
WARNING: SOME BRANDS OF ALUMINIUM JOINERY HAVE DRAINAGE VENTS IN THE BOTTOM EDGE OF THE SILL FLANGE. ENSURE DRAINAGE VENTS REMAIN CLEAR.
PROPRIETARY ALUM.WINDOW JOINERY
MS SEALANT STO uPVC SILL FLASHING FIX ONTO BACKERBOARD; UNDER JAMBS
STOLITE RENDER SYSTEM
AIRSEAL ON PEF ROD GAP 7.5-8mm APPROX.
INTERIOR LINING
WALL UNDERLAY RETURNED INTO OPENINGS & FLASHING
TAPE CONTINUOUS ALONG SILL MIN 100mm UP JAMBS & 50mm ONTO FACE OF WALL
UNDERLAY
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
INTERNAL LINING
MS SEALANT TO JAMBS
AIRSEAL ON PEF ROD GAP 7.5-8mm APPROX.
LINE OF HEAD FLASHING OVER WITH STOPEND
ALLOW 3mm GAP BETWEEN WINDOW JOINERY AND FIBRE CEMENT SHEET FOR STOLITE uPVC FLASHING PROVIDE MIN 6mm FILLET BEAD OF MS SEALANT TO uPVC JAMBS AND SILL FLASHINGS AT WINDOW TRANSITION STOLITE uPVC SILL TO BE PLACED UNDER STO uPVC JAMB FLASHING FLASHING TAPE TO OPENINGS AS PER E2/AS1 INSTALLED BY BUILDER
STOLITE RENDER SYSTEM
CAVITY BATTENS
PLACE BEFORE RENDERING
5 10mm MIN.COVER
LINE OF HEAD FLASHING 20mm MIN.PAST JAMB
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
INTERNAL LINING
MS SEALANT
STOLITE RENDER SYSTEM
CAVITY BATTENS
STOLITE uPVC JAMB FLASHING GLUE OR BED FLASHING IN PLACE BEFORE RENDERING
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 403
LINE OF CLADDING BEYOND ALUMINIUM DOOR JOINERY
FLASHING TAPE TAPE OVER SILL AND MIN. 100mm UP FRAME FINISH AT
BOTTOM EDGE OF SILL SUPPORT BAR
UNDER DOOR TRIM BY BUILDER
REFER TO E2/AS1 FIG. 17 A,B,C & D INCLUDING SECTION 9.1.10 . GROUND LEVELS 150mm MIN.FROM TOP OF FINISHED FLOOR COVERING TO PAVED GROUND
10 0
CONTINUOUS AIR SEAL
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
LINE OF STOLITE CLADDING BEYOND - SHOWN DASHED
SELECTED ALU.DOOR JOINERY INSTALLED TO MANUFACTURERS RECOMMENDATIONS
REFER TO E2/AS1 FIG. 17 A,B,C & D INCLUDING SECTION 9.1.10 MIN.THRESHOLD 100mm FROM FLOOR TO FINISHED DECK
NOTE: ADJUST 35mm TO ALLOW FOR SELECTED TILES AS REQUIRED, UNDER DOOR TRIM BY BUILDER
10 0
SELECTED FLOORING WANZ SUPPORT BAR COMPLETE WITH VENTILATION/DRAINAGE HOLES INSTALLED TO MANUFACTURERS RECOMMENDATIONS
SELECTED MEMBRANE FINISH OVER H3 "C" GRADE FACED PLYWOOD LAID TO 1:40MIN.FALL. GLUE & SCREW TO TIMBER JOISTS, ALL EDGES SUPPORTED ON TIMBER
TIMBER STRUCTURE AS PER NZS3604
20mm MIN.ANGLE FILLET
TRIMMER STUDS
MEMBRANE REINFORCING STRIP
CONTINUOUS AIR SEAL
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
LINE OF STOLITE CLADDING SYSTEM BEYOND SELECTED ALU.BIFOLD DOOR JOINERY INSTALLED TO MANUFACTURERS RECOMMENDATIONS
FLASHING TAPE TAPE OVER SILL AND MIN. 100mm UP FRAME FINISH AT
BOTTOM EDGE OF SILL SUPPORT BAR
10 0
8
REFER TO E2/AS1 FIG. 17 A,B,C & D INCLUDING SECTION 9.1.10 . 150mm MIN. FROM TOP OF FFL COVERING TO PAVED GROUND
UNDER DOOR TRIM BY BUILDER
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SCALE 1:5
LINE OF STOLITE CLADDING SYSTEM - SHOWN DASHED SELECTED ALU.ENTRY DOOR JOINERY
DRAINAGE CHANNEL FALL ALONG LENGTH
TO OUTLET
SELECTED FLOOR FINISH
FLASHING TAPE TAPE OVER SILL AND MIN. 100mm UP FRAME FINISH AT
BOTTOM EDGE OF SILL SUPPORT BAR
10 0
NOTE REFER TO E2/AS1 FIG. 17 A,B,C & D INCLUDING SECTION 9.1.10
15 0
FLASHING TAPE
CONTINUOUS AIR SEAL
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
WALL UNDERLAY
20mm DRAINED CAVITY
STOLITE CLIP-ON TRAY WITH MIN 5mm GAP
ALUMINIUM HEAD FLASHING WITH 15° SLOPE AND 10mm COVER
MIN. 5mm GAP REQUIRED
UNDERLAY AT CORNERS
1. HEIGHT WORK TO UNDERSIDE SOFFIT. MEASURE DOOR HEIGHT ON SITE & CHECK GARAGE DOOR SPECIFICATIONS FOR INTERNAL CORNER REQUIREMENTS
2. SEAL FLASHING FOR VERY HIGH or EXTRA HIGH WIND ZONE
3. IN EXTRA HIGH WIND ZONES INCREASE FLASHING COVER TO 60mm AND USE A RIGID UNDERLAY
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 408
SELECTED GARAGE DOOR
FLASHING TAPE OVER WALL UNDERLAY TO CORNERS OF OPENINGS PRE PRIMED H3.1 JAMB LINER
STO uPVC CLIP ON FLASHING, REMOVE
DRIP EDGE TABS
STOLITE CLADDING SYSTEM
REBATE IN GARAGE FLOOR TO SUIT GARAGE DOOR
NOTE: HEIGHT WORK TO UNDERSIDE SOFFIT. MEASURE DOOR HEIGHT ON SITE & CHECK GARAGE DOOR SPECIFICATIONS FOR INTERNAL CORNER REQUIREMENTS
MS SEALANT ON STO JOINT SEAL TAPE OR PEF ROD
6
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 409
STOLITE CLIP-ON TRAY
FC SHEET TO FINISH 10mm MIN.PAST TO FORM DRIP EDGE
GARAGE DOOR TRIM - REFER TO GARAGE DOOR
MANUFACTURERS RECOMENDATIONS
WALL UNDERLAY
PURPOSE MADE METAL FLASHING
FLASHING TAPE OVER FLASHING
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 410
HEIGHT WORK TO UNDERSIDE OF SOFFIT. INSTALL TO MANUFACTURERS INSTRUCTIONS
STO PREMESHED CORNER BEAD OR S/S CNR ANGLE
FLASHING TAPE OVER WALL UNDERLAY TO CORNERS OF OPENINGS
STOLITE RENDER SYSTEM STO CAVITY BATTENS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 411
WALL UNDERLAY CONTINUOUS OVER TOP OF WALL FRAME
6mm FIBRE CEMENT SHEET
STOLITE RENDER SYSTEM
20mm DRAINED CAVITY
1. INSTALL METAL SADDLE FLASHING AT WALL JUNCTION 2. ENSURE TOP IS TEMPORARILY WATERPROOFED BEFORE COMMENCING RENDERING 3. METAL CAPPING EXCLUDING DRIP EDGE MUST OVERLAP SHEET BY
50mm MIN.IN LOW, MED or HIGH WIND ZONE, 70mm MIN.IN VERY HIGH, 90mm MIN.IN EXTRA HIGH WIND ZONES
4. INSTALL METAL CAPPING TO ALL ROOF PARAPETS
V A
R IE
9mm H3 PLY PACKED TO A FALL
PRE FINISHED METAL CAPPING TO PARAPET
5° 5° MIN.FALL TO TOP OF PARAPET
STO JOINT SEAL TAPE OR SEALANT IF REQUIRED TO CLOSE GAPS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
2017
OVERLAY OF STO FLEXYL MEMBRANE UNDER MESH COAT TO TOP & SIDES, 75mm MIN.DOWNTURN OVER BASE COAT
WALL UNDERLAY CONTINUOUS OVER TOP OF WALL FRAME
6mm FIBRE CEMENT SHEET
10 °
H3.1 TIMBER PACKER CUT TO FALL
STO PREMESHED PVC ADJUSTABLE CORNER ANGLES
NOTE: STO FLEXYL MESHED WATERPROOFING MEMBRANE HAS BEEN TESTED BY BRANZ TO MEET THE REQUIREMENTS OF AS/NZS4858 WATERPROOF MEMBRANE AS REQUIRED BY E2/AS1
EXTRA HIGH WID ZONES REQUIRE A RIDGID UNDERLAY. FLASHING MUST BE TAPED TO RIDGID UNDERLAY
SCALE 1:5
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
BALUSTRADE WALL UNDERLAY LAPPED AROUND CORNER
150
150mm MIN. TO FACE OF WINDOW OR DOOR JAMB STUD
DRAIN FORMED IN CORNER
STOLITE RENDER SYSTEM
20mm DRAINED CAVITY
NOTE: BALUSTRADE OR PARAPET MUST BE OFFSET FROM ADJACENT WALL IN THE SAME PLANE (STOLITE 85mm MIN.) FOR CORNER FLASHING E2/AS2 6.4.1
FLEXIBLE FLASHING TAPE ON CORNER 75mm EACH WAY OVER WALL UNDERLAY
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 502
ADHERED TO WALL UNDERLAY AT REAR OF CAVITY AND
DRESSED A MIN. 50mm DOWN FACE OF BATTENS
9mm H3 PLY PACKED TO A FALL
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
STOLITE CONSTRUCTION SYSTEM
RIVET THROUGH SEALANT
50x50mm CNR FLASHING ON FACE OF BATTENS BEHIND SADDLE FLASHING
2 LINES OF SEALANT CAPPING TO SADDLE FLASHING
CAPPING FLASHING
METAL PARAPET CAP FLASHING
RIVET THROUGH TOP OF CAP TO SADDLE FLASHING. MS SEALANT TO RIVETS EXTENT OF SADDLE FLASHING
8mm EXPANSION GAP BETWEEN PARAPET CAP AND SADDLE
FLASHING - USE MS SEALANT
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 504
WALL UNDERLAY WALL FRAMING
NOTE: APPLY STOFLEXYL MESHED WATERPROOFING OVER LEVELITE BASECOAT STOFLEXYL MESHED WATERPROOFING HAS BEEN TESTED BY BRANZ TO MEET THE REQUIREMENTS OF AS/NZS4858 FOR A WATERPROOFING MEMBRANE AS REQUIRED BY E2/AS1
75
75
OVERLAY OF STOFLEXYL MEMBRANE UNDER MESH COAT TO TOP & SIDES 75mm MIN.DOWNTURN OVER LEVELITE BASE COAT
LEVELLITE BASECOAT RENDER
LEVELITE BASECOAT ON FIBRE CEMENT SHEET
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 505
SCALE 1:5
E2/AS1 REQUIRES BALCONY & PARAPET WALLS TO BE OFFSET FROM THE MAIN WALL PLAIN TO ALLOW FOR SADDLE FLASHINGS
NOTE:
STOFLEXYL MESHED WATERPROOFING HAS BEEN TESTED BY BRANZ TO MEET AS/NZS4858 AS REQUIRED BY E2/AS1. ALL WALL CAPS (MIN.10° FALL) ARE TO HAVE STOFLEXYL WATERPROOFING AS SHOWN OVER THE STOLITE BASECOAT RENDER. STOFLEXYL TO EXTEND 75mm MIN. DOWN THE WALL FACE AND ONTO ADJACENT WALLS
BASECOAT 6mm SHEET ON PACKER
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 506
35
10° MIN.FALL TO TOP OF PARAPET
H3.1 TIMBER PACKER CUT TO FALL
6mm FIBRE CEMENT SHEET STOLITE RENDER SYSTEM
20mm DRAINED CAVITY 6mm FIBRE CEMENT SHEET
STOLITE RENDER SYSTEM
20mm DRAINED CAVITY
STO PREMESHED PVC ADJUSTABLE CORNER ANGLES IN STOARMAT MESH COAT
STO uPVC CLIP ON FOOT RAY - REMOVE BACK TAB IF REQUIRED
VENTED CAVITY BASE CLOSER
OVERLAY OF STO FLEXYL MEMBRANE UNDER MESH COAT TO TOP & SIDES, 75mm MIN.DOWNTURN OVER BASE COAT RENDER
FULLY SUPPORTED MEMBRANE UPSTAND 20mm MIN.ANGLE FILLET
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SCALE 1:5
NOTE: - 100mm MIN. FROM FLOOR LEVEL FOR ENCLOSED DECKS - MIN.FALLS: 1:40 FOR DECKS, 1:30 FOR ROOFS & 1:100 FOR GUTTERS - ALLOW FOR TILES IF REQUIRED
35 15
0
SELECTED MEMBRANE FINISH OVER H3 "C" GRADE FACED PLYWOOD LAID TO A 1:40 MIN. FALL. GLUE , SCREW TO TIMBER JOISTS ALL EDGES SUPPORTED ON TIMBER. 20mm MIN. ANGLE FILLET
STOLITE RENDER SYSTEM
20mm DRAINED CAVITY
VENTED CAVITY BASE CLOSER
STO uPVC CLIPON FLASHING (can remove back tabs if required)
MEMBRANE REINFORCING STRIP
MEMBRANE TO RUN UP 150mm MIN.
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
STOLITE RENDER SYSTEM 20mm DRAINED CAVITY WALL UNDERLAY
FLOORING STO JOINT SEAL TAPE & MS SEALANT TO TOP AND SIDES
LINE OF CANTILEVER JOIST - SHOWN DASHED
5mm MIN. GAP BETWEEN STOLITE RENDER SYSTEM
AND SADDLE FLASHING
LINE OF CLADDING BETWEEN JOISTS - SHOWN DASHED, CUT AROUND JOIST
CLADDING BELOW DECK
NOTE: REFER E2/AS1 Fig.16 FOR FLASHING REQUIREMENTS. PROVIDE 6-8mm WIDE SEALANT JOINT AT CLADDING/SADDLE FLASHING JUNCTION.
50mm MIN. SET DOWN FROM FLOOR OR THRESHOLD FOR CANTILEVERED SLATTED DECKS
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
INTERNAL LINING
STOLITE RENDER SYSTEM 20mm DRAINED CAVITY WALL UNDERLAY
50mmØ x3mm EPDM WASHERS AROUND FIXINGS
BLOCKING TO BE WRAPPED USING FLASHING TAPE. THIS IS TO BE CARRIED A MIN.OF 50MM OVER ALL EDGES
H3.2 STRINGER - REFER NZS3604 FOR SIZE H3.2 PACKER
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SCALE 1:5
NOTE: INSTALL FLASHING TAPE OVER BRACKET ONTO BUILDING UNDERLAY AS PER E2/AS1 fig 68, ALSO REFER TO DETAIL 513
MANUFACTURED GALVANIZED STEEL 'H' OR 'U' BRACKET FOR PARALLEL JOISTS OR USE 'L' BRACKET FOR RIGHT ANGLE CONNECTIONS
DECK JOIST/BEAM TO BE INSTALLED ONCE CLADDING HAS BEEN FINISHED - 40mm GAP RECOMMENDED FOR FIXINGS
STRUCTURAL REQUIREMENTS AS PER ENGINEER
GALVANIZED OR STAINLESS STEEL 'H' or 'U' BRACKET, SEAL BRACKET WITH MS SEALANT OVER PEF ROD
12mm MIN.GAP. 40mm REQUIRED FOR FIXINGS
20mm DRAINED CAVITY WALL UNDERLAY
TIMBER FRAMING TO NZS 3604
6mm FIBRE CEMENT SHEET
CEMENT BRACKET
40mm GAP
BLOCK AS REQUIRED
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
12mm MIN.
SCALE 1:2
GALVANISED L BRACKET ENGINEERED FOR LOAD. FLASHING TAPE TO WALL UNDERLAY IN ACCORDANCE WITH NZBC E2/AS1 FIG. 68 DOUBLE MS SEALANT BRACKET/BACKERBOARD AND AGAIN AT BRACKET/MESH COAT TRANSITIONS
NOTE: CARPENTER MUST FIT BOARD NEATLY WITH 8mm GAP
TIMBER BEAM
WALL UNDERLAY 20mm DRAINED CAVITY
STOLITE RENDER SYSTEM FLASHING TAPE 100MM ONTO WALL UNDERLAY 25MM ONTO BRACKET STO JOINT SEAL TAPE, 10mm FINISHING EDGE & MS SEALANT
GALVANIZED OR STAINLESS STEEL L BRACKET ENGINEERED FOR LOAD
NOTE: 'L' BRACKET ENGINEERED FOR LOAD. FLASHING TAPE TO BUILDING UNDERLAY IN ACCORDANCE WITH E2/AS1 FIG. 68
6mm FIBRE CEMENT BOARD
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
EPDM WASHERS REQUIRED AROUND FIXINGS AND PLATE TO PROVIDE WATERTIGHTNESS
RWH HEAD FIXED DIRECTLY ABOVE & BELOW SCUPPER PENETRATION
PRE FINISHED 0.55MM BMT STEEL CUSTOM FOLDED AND RIVETED RAIN WATER HEAD
MS SEALANT AROUND OPENING/RHW FINISHED TO STOSTUCCO SOFFIT EDGE
MEMBRANE DRESSED OVER 50x50mm ALU.ANGLE REBATED INTO SUBSTRATE
50mm LIP
25 50
200mm MIN. OUTLET THROUGH WALL
SELECTED MEMBRANE FINISH OVER H3 "C" FACED PLYWOOD LAID TO 1:60MIN.FALL. GLUE & SCREW TO TIMBER JOISTS, ALL EDGES SUPPORTED ON TIMBER
20mm MIN.ANGLE FILLET
OUTLET THROUGH WALL
DEBRIS SCREEN
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
VARIES
PREFABRICATED TRUSS TOP CHORD OVERHANG
MS SEALANT 6-8mm (before rendering)
SOFFIT LINING TO CLOSE OFF CAVITY
NOTE: IF BLOCKING IS MISSING, STAPLE WALL UNDERLAY TO SOFFIT PLATE TO AVOID ANY VENTILATION GAPS.
REFER TO E2/AS1 TABLE 1 FOR RISK LEVELS. EAVE FLASHINGS REQUIRED WHEN FASCIA IS 100mm OR LESS FROM WALL CLADDING AND ROOF SLOPE IS LESS THAN 10° OR WIND ZONES ARE VERY HIGH OR EXTRA HIGH
STOLITE RENDER SYSTEM
6mm FIBRE CEMENT SHEET 20mm DRAINED CAVITY
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
H3.1 PRE PRIMED & PAINTED FASCIA BOARD
STOLITE RENDER SYSTEM
PREFINISHED METAL ROOFING OVER ROOF UNDERLAY PREFABRICATED TRUSS TOP CHORD OVERHANG
SOFFIT LINING TO CLOSE OFF CAVITY
VARIES
NOTE: REFER TO E2/AS1 TABLE 1 FOR RISK LEVELS. EAVE FLASHINGS REQUIRED WHEN FASCIA IS 100mm OR LESS FROM WALL CLADDING AND ROOF SLOPE IS LESS THAN 10° OR WIND ZONES ARE HIGH OR VERY HIGH
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
NOTE:
REFER TO E2/AS1 TABLE 1 FOR RISK LEVELS. EAVE FLASHINGS ARE REQUIRED WHEN FASCIA IS 100mm OR LESS FROM WALL CLADDING AND ROOF SLOPE IS LESS THAN 10°
H3.1 PRE PRIMED & PAINTED FASCIA BOARD
PREFINISHED METAL ROOFING OVER ROOF UNDERLAY
PREFABRICATED TRUSS
50mm MIN.FASCIA COVER OVER RENDER SYSTEM
PRE FINISHED METAL E2 EAVES FLASHING, LAP 125mm MIN. UNDER ROOF CLADDING, TURN DOWN INTO GUTTER
50
125
WALL UNDERLAY 20mm DRAINED CAVITY 6mm FIBRE CEMENT SHEET STOLITE RENDER SYSTEM
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
50
35
STOLITE RENDER SYSTEM
50x35mm MIN.METAL FLASHING 6mm MAX.GAP WITH MS SEALANT
NOTE:
SOFFITS ARE TO BE FIXED AFTER CLADDING
6
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
50
35
STOLITE RENDER SYSTEM
STO uPVC JOINERY CONNECTOR FINISH WITH WITH MS SEALANT
NOTE:
6
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or Sto contractor to insure they have and use the current Sto details and specifications on site.
STOLITE SYSTEM
SL 604
15
FIBRE CEMENT SOFFIT - STOARMAT RENDER SYSTEM WITH STO uPVC FINISHING EDGE
5mm MIN.GAP
BACK OF FC SHEET TO FINISH WITH 15mm DRIP EDGE
WALL UNDERLAY
CAVITY BATTENS
NOTE:
USE STOARMAT RENDER WHEN RENDERING uPVC TRAYS AND SOFFIT WITH FINISHING EDGE
STOLITE CLIP ON TRAY
VENTED VERMIN TRAY
The information contained on this page is based on our experience and research at the date of issue. The detail is for use by Registered Architects, Licensed Designers or Chartered Engineers to assist in developing project details using Sto Systems. Stoanz Ltd reserve the right to alter or update information at any time without prior notice and it is the responsibility of the designer, project manager or St