NATIONAL CENTER FOR EARTHQUAKE ENGINEERING RESEARCH State University of New York at Buffalo 1111111111111111111111111111111 PB95-138533 Study of Seismic Isolation Systems for Computer Floors by V. Lambrou and M.C. Constantinou State University of New York at Buffalo Department of Civil Engineering Buffalo, New York 14260 Technical Report NCEER-94-0020 July 19, 1994 This research was conducted at the State University of New York at Buffalo and was partially supported by the National Science Foundation under Grant No. BCS 90-25010 and the New York State Science and Technology Foundation under Grant No. NEC-91029.

Study of Seismic Isolation Systems for Computer Floors

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Study of Seismic Isolation Systems for Computer Floors

NATIONAL CENTER FOR EARTHQUAKE ENGINEERING RESEARCH

State University of New York at Buffalo

1111111111111111111111111111111 PB95-138533

Study of Seismic Isolation Systems for Computer Floors

by

V. Lambrou and M.C. Constantinou State University of New York at Buffalo

Department of Civil Engineering Buffalo, New York 14260

Technical Report NCEER-94-0020

July 19, 1994

This research was conducted at the State University of New York at Buffalo and was partially supported by the National Science Foundation under Grant No. BCS 90-25010

and the New York State Science and Technology Foundation under Grant No. NEC-91029.

Page 2: Study of Seismic Isolation Systems for Computer Floors

NOTICE This report was prepared by the State University of New York at Buffalo as a result of research sponsored by the National Center for Earthquake Engineering Research (NCEER) through grants from the National Science Foundation, the New York State Science and Technology Foundation, and other sponsors. Neither NCEER, associates of NCEER, its sponsors, the State Universi­ty of New York at Buffalo, nor any person acting on their behalf:

a. makes any warranty, express or implied, with respect to the use of any information, apparatus, method, or process disclosed in this report or that such use may not infringe upon privately owned rights; or

b. assumes any liabilities of whatsoever kind with respect to the use of, or the damage resulting from the use of, any informa­tion, apparatus, method or process disclosed in this report.

Any opinions, findings, and conclusions or recommendations expressed in this publication are those of the author(s) and do not necessarily reflect the views of the National Science Founda­tion, the New York State Science and Technology Foundation, or other sponsors.

Page 3: Study of Seismic Isolation Systems for Computer Floors

111 1 -------

Study of Seismic Isolation Systems for Computer Floors

by

v. Lambrou1 and M.C. Constantinou2

July 19, 1994

Technical Report NCEER-94-0020

NCEER Task Number 92-5201B

NSF Master Contract Number BCS 90-25010 and

NYSSTF Grant Number NEC-91 029

1 Research Assistant, Department of Civil Engineering, State University of New York at Buffalo

2 Professor, Department of Civil Engineering, State University of New York at Buffalo

NATIONAL CENTER FOR EARTHQUAKE ENGINEERING RESEARCH State University of New York at Buffalo Red Jacket Quadrangle, Buffalo, NY 14261

Page 4: Study of Seismic Isolation Systems for Computer Floors
Page 5: Study of Seismic Isolation Systems for Computer Floors

PREFACE

The National Center for Earthquake Engineering Research (NCEER) was established to expand and disseminate knowledge about earthquakes, improve earthquake-resistant design, and implement seismic hazard mitigation procedures to minimize loss of lives and property. The emphasis is on structures in the eastern and central United States and lifelines throughout the country that are found in zones of low, moderate, and high seismicity.

NCEER's research and implementation plan in years six through ten (1991-1996) comprises four interlocked elements, as shown in the figure below. Element I, Basic Research, is carried out to support projects in the Applied Research area. Element II, Applied Research, is the major focus of work for years six through ten. Element III, Demonstration Projects, have been planned to support Applied Research projects, and will be either case studies or regional studies. Element IV, Implementation, will result from activity in the four Applied Research projects, and from Demon­stration Projects.

ELEMENT I BASIC RESEARCH

• Seismic hazard and ground motion

• Soils and geotechnical engineering

• Structures and systems

• Risk and reliability

• Protective and intelligent systems

• Societal and economic studies

ELEMENT II APPLIED RESEARCH

• The Building Project

• The Nonstructural Components Project

• The Lifelines Project

The Highway Project

ELEMENT III DEMONSTRATION PROJECTS

Case Studies • Active and hybrid control • Hospital and data processing

facilities • Short and medium span bridges • Water supply systems in

Memphis and San Francisco Regional Studies

• New York City • MiSSissippi Valley • San Francisco Bay Area

ELEMENT IV IMPLEMENTATION

• Conferences/Workshops • EducationlTraining courses • Publications • Public Awareness

Research tasks in the NonstructuraI Components Project focus on analytical and experimental investigations of seismic behavior of secondary systems, investigating hazard mitigation through optimization and protection, and developing rational criteria and procedures for seismic design and performance evaluation. Specifically, tasks are being performed to: (l) provide a risk analysis of a selected group of nonstructural elements; (2) improve simplified analysis so that research results can be readily used by practicing engineers; (3) protect sensitive equipment and critical subsystems using passive, active or hybrid systems; and (4) develop design and performance evaluation guidelines.

111

Page 6: Study of Seismic Isolation Systems for Computer Floors

The end product of the Nonstructural Components Project will be a set of simple guidelines for design, performance evaluation, support design, and protection and mitigation measures in the form of handbooks or computer codes, and software and hardware associated with innovative protection technology.

The protective and intelligent systems program constitutes one ofthe important areas of research in the Nonstructural Components Project. Current tasks include the following:

1. Evaluate the performance of full-scale active bracing and active mass dampers already in place in terms of performance, power requirements, maintenance, reliability and cost.

2. Compare passive and active control strategies in terms of structural type, degree of effectiveness, cost and long-term reliability.

3. Perform fundamental studies of hybrid control. 4. Develop and test hybrid control systems.

The objective of the test program described in this report was to investigate seismic effectiveness of computer floor isolation systems by utilizing devices which have beenfound to be effective in seismic isolation of buildings or shock isolation of military equipment. The isolation systems tested in the laboratory consisted of spherically shaped sliding bearings which were highly damped either by utilizing highjriction in the bearings or by installing fluid viscous dampers. The experimental results demonstrated substantial reductions in the response of a generic computer cabinet on top of the isolated floor subject to simulated ground motions. Under non-isolated conditions, the cabinet underwent rocking and experienced acceleration which could cause either interruption of operation or failure. In contrast, the cabinet on the isolatedfloor with long isolation periods did not experience rocking and developed substantially less acceleration. An analytical model of the tested system was also developed and shown to be capable of predicting the experimental results with good accuracy.

IV

Page 7: Study of Seismic Isolation Systems for Computer Floors

ABSTRACT

The work described in this report concentrated on the development and testing of computer

floor seismic isolation systems by utilizing devices of established effectiveness in the seismic

isolation of buildings and shock isolation of military equipment. A computer floor system

with raised floor and a generic slender equipment was constructed. It was isolated by

spherically shaped sliding bearings and was highly damped either by utilizing high friction in

the bearings or by installing fluid viscous dampers. The spherically shaped bearings provided

the simplest means of achieving long period in the isolation system under low gravity load.

The isolation system prevented rocking of the cabinet on top of the isolated floor and

substantially reduced its acceleration response in comparison to that of a conventional

computer floor. An analytical study was also conducted in order to extend the results to a

range of parameters which could not be tested.

v

Page 8: Study of Seismic Isolation Systems for Computer Floors
Page 9: Study of Seismic Isolation Systems for Computer Floors

ACKNOWLEDGEMENTS

Financial support for this project has been provided by the National Center for Earthquake

Engineering Research, Project No. 925201B.

Earthquake Protection Systems, Inc. of San Francisco, California supplied the FPS bearings

and Taylor Devices, Inc. of North Tonawanda, NY supplied the fluid viscous dampers. The

raised floor system was a Tate Access Floor system, supplied by Rochester Davis-Fetch

Corporation of Lancaster, NY.

VB

Page 10: Study of Seismic Isolation Systems for Computer Floors
Page 11: Study of Seismic Isolation Systems for Computer Floors

TABLE OF CONTENTS

SEC. TITLE PAGE

1 INTRODUCTION 1-1

2 DESCRIPTION OF COMPONENTS OF FLOOR ISOLATION SYSTEM 2-1

2.1 Introduction 2-1

2.2 Friction Pendulum System Bearings (FPS) 2-1

2.2.1 Principles of Operation 2-3

2.3 Fluid Viscous Dampers 2-6

2.3.1 Operation of Fluid Damper 2-7

3

3.1

3.2

3.3

3.4

3.5

3.5.1

3.5.2

3.5.3

3.6

3.7

4

4.1

4.2

4.3

5

5.1

5.2

5.3

TESTED SYSTEM

Description of Tested System

Description of Cabinet

Description of Base Floor

Description of Raised Floor

Tested Configurations

Isolation System 1

Isolation System 2

Isolation System 3

Experimental Program

Instrumentation

TEST RESULTS AND INTERPRETATION

Test Results

Comparison of Behavior ofIsolated and Non-isolated Computer Floor

Displacement Demand in Isolation System

ANALYTICAL PREDICTION OF RESPONSE

Introduction

Analytical Model

Comparison of Analytical and Experimental Results

IX

3-1

3-1

3-2

3-6

3-6

3-7

3-12

3-12

3-16

3-18

3-37

4-1

4-1

4-2

4-6

5-1

5-1

5-1

5-7

Page 12: Study of Seismic Isolation Systems for Computer Floors

TABLE OF CONTENTS (cont'd)

SEC. TITLE

5.4 Analytical Parametric Study

6 SUMMARY AND CONCLUSIONS

7 REFERENCES

APPENDIX A EXPERIMENTAL RESULTS

x

PAGE

5-20

6-1

7-1

A-I

Page 13: Study of Seismic Isolation Systems for Computer Floors

LIST OF ILLVSTRA TIONS

FIG. TITLE PAGE

2-1 Construction of Friction Pendulum System (FPS) Bearing 2-2

2-2 Basic Principle of Operation ofFPS Bearing 2-5

2-3 View ofFPS Bearing 2-6

2-4 Construction of Fluid Viscous Damper 2-8

3-1 View of Tested System on Shake Table 3-1

3-2 View of Cabinet on Raised Floor 3-3

3-3 Tested Equipment Cabinet (Units:m) 3-4

3-4 Schematic of Tested Isolation Floor System (Units:m) 3-8

3-5 Coefficient of Sliding Friction as a Function of Bearing Pressure and Sliding Velocity 3-11

3-6 Recorded Isolation System 1 Force-Displacement Loops in Identification Test at 1 Hz Frequency 3-13

3-7 View ofIsolation System 2 3-14

3-8 Recorded Isolation System 2 Force-Displacement Loops in Identification Test at 1 Hz Frequency 3-15

3-9 View ofIsolation System 3 3-16

3-10 Recorded Isolation System 3 Force-Displacement Loops in Identification Test at 1 Hz Frequency 3-17

3-11 Acceleration, Velocity and Displacement Histories and Response Spectrum of Taft (Horizontal) - Ground in Prototype Scale 3-24

3-12 Acceleration, Velocity and Displacement Histories and Response Spectrum of Taft (Horizontal) - 5th Floor in Prototype Scale 3-25

3-13 Acceleration, Velocity and Displacement Histories and Response Spectrum of Taft (Horizontal) - 7th Floor in Prototype Scale 3-26

3 -14 Acceleration, Velocity and Displacement Histories and Response Spectrum ofEI Centro (Horizontal) - Ground in Prototype Scale 3-27

3-15 Acceleration, Velocity and Displacement Histories and Response Spectrum ofEI Centro (Horizontal) - 5th Floor in Prototype Scale 3-28

3-16 Acceleration, Velocity and Displacement Histories and Response Spectrum ofEI Centro (Horizontal) - 7th Floor in Prototype Scale 3-29

3 -17 Acceleration, Velocity and Displacement Histories and Response Spectrum of Pacoima Dam (Horizontal) - Ground in Prototype Scale 3-30

Xl

Page 14: Study of Seismic Isolation Systems for Computer Floors

LIST OF ILLUSTRATIONS (cont'd)

FIG. TITLE PAGE

3 -18 Acceleration, Velocity and Displacement Histories and Response Spectrum of Belle ore (Horizontal) in Prototype Scale 3-31

3-19 Acceleration, Velocity and Displacement Histories and Response Spectrum ofIBM 1 (Horizontal) in Prototype Scale 3-32

3-20 Acceleration, Velocity and Displacement Histories and Response Spectrum of IBM 2 (Horizontal) in Prototype Scale 3-33

3 -21 Acceleration, Velocity and Displacement Histories and Response Spectrum of Taft (Vertical) - Ground in Prototype Scale 3-34

3-22 Acceleration, Velocity and Displacement Histories and Response Spectrum ofEI Centro (Vertical) - Ground in Prototype Scale 3-35

3-23 Acceleration, Velocity and Displacement Histories and Response Spectrum of Pacoima Dam (Vertical) - Ground in Prototype Scale 3-36

3-24 Location of Accelerometers (Units:m) 3-39

3-25 Location of Displacement Transducers (Units:m)

3-26 Instrumentation on Cabinet (Units:m)

3-27 Three Dimensional View ofInstrumentation on Cabinet (Units:m)

4-1 Profiles of Peak Acceleration Along Height of Cabinet in Taft N21E Ground

3-40

3-41

3-42

Horizontal - Vertical Input 4-7

4-2 Profiles of Peak Acceleration Along Height of Cabinet in Taft N21E 5th Floor Horizontal - Vertical Input 4-8

4-3 Profiles of Peak Acceleration Along Height of Cabinet in Taft N21E 7th Floor Horizontal - Vertical Input 4-9

4-4 Profiles of Peak Acceleration Along Height of Cabinet in EI Centro SOOE Ground Horizontal - Vertical Input 4-10

4-5 Profiles of Peak Acceleration Along Height of Cabinet in EI Centro SOOE 5th Floor Horizontal - Vertical Input 4-11

4-6 Profiles of Peak Acceleration Along Height of Cabinet in EI Centro SOOE 7th Floor Horizontal - Vertical Input 4-12

4-7 Profiles of Peak Acceleration Along Height of Cabinet in Pacoima Dam S74W Ground Horizontal Input 4-13

4-8 Profiles of Peak Acceleration Along Height of Cabinet in Bellcore Horizontal - Vertical Input 4-14

4-9 Profiles of Peak Acceleration Along Height of Cabinet in IBM Level-l Horizontal - Vertical Input 4-15

XlI

Page 15: Study of Seismic Isolation Systems for Computer Floors

LIST OF ILLUSTRATIONS (cont'd)

FIG. TITLE PAGE

4-10 Profiles of Peak Acceleration Along Height of Cabinet in IBM Level-2 Horizontal - Vertical Input 4-16

4-11 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Taft N21E Ground Horizontal-Vertical Input and Length Scale of2 4-17

4-12 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Taft N21E 5th Floor Horizontal-Vertical Input and Length Scale of2 4-18

4-13 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Taft N21E 7th Floor Horizontal-Vertical Input and Length Scale of2 4-19

4-14 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in El Centro SOOE Ground Horizontal-Vertical Input and Length Scale of 2 4-20

4-15 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in EI Centro SOOE 5th Floor Horizontal-Vertical Input and Length Scale of 2 4-21

4-16 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in EI Centro SOOE 7th Floor Horizontal-Vertical Input and Length Scale of 2 4-22

4-17 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Pacoima Dam S74W Horizontal Input and Length Scale of2 4-23

4-18 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Bellcore Horizontal-Vertical Input and Length Scale of2 4-24

4-19 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in IBM Level-1 Horizontal-Vertical Input and Length Scale of 2 4-25

4-20 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in IBM Level-2 Horizontal-Vertical Input and Length Scale of 2 4-26

4-21 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Taft N21E Ground Horizontal-Vertical Input and Length Scale of 4 4-27

4-22 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Taft N21E 5th Floor Horizontal-Vertical Input and Length Scale of 4 4-28

4-23 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Taft N21E 7th Floor Horizontal-Vertical Input and Length Scale of 4 4-29

4-24 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in EI Centro SOOE Ground Horizontal-Vertical Input and Length Scale of 4 4-30

4-25 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in EI Centro SOOE 5th Floor Horizontal-Vertical Input and Length Scale of 4 4-31

4-26 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in EI Centro SOOE 7th Floor Horizontal-Vertical Input and Length Scale of 4 4-32

4-27 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Pacoima Dam S74W Horizontal Input and Length Scale of 4 4-33

X111

Page 16: Study of Seismic Isolation Systems for Computer Floors

LIST OF ILLUSTRATIONS (cont'd)

FIG. TITLE PAGE

4-28 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Bellcore Horizontal-Vertical Input and Length Scale of 4 4-34

4-29 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in IBM Level-l Horizontal-Vertical Input and Length Scale of 4 4-35

4-30 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in IBM Level-2 Horizontal-Vertical Input and Length Scale of 4 4-36

4-31 Comparison of Response of Internal Flexible Component (Level 3) for Various Excitations 4-37

4-32 Peak Bearing Displacement in Prototype Scale for the Taft Input. Length Scale of 2 Corresponds to isolation Period of 2.12 sees, Length Scale of 3 Corresponds to 2.60 sees, and Length Scale of 4 Corresponds to 3.00 sees 4-38

4-33 Peak Bearing Displacement in Prototype Scale for the EI Centro Input. Length Scale of 2 Corresponds to isolation Period of 2.12 sees, Length Scale of 3 Corresponds to 2.60 sees, and Length Scale of 4 Corresponds to 3.00 4-39 sees

4-34 Peak Bearing Displacement in Prototype Scale for the Artificial Input.

5-1

5-2

5-3

5-4

5-5

5-6

5-7

Length Scale of 2 Corresponds to isolation Period of 2.12 sees, Length Scale of 3 Corresponds to 2.60 sees, and Length Scale of 4 Corresponds to 3.00 4-40 sees

Longitudinal Direction Model of Isolated Floor System 5-2

Free Body Diagram of Floor System Model 5-2

Comparison of Analytical and Experimental Results of Floor System with Isolation System 1 in EI Centro 7th Floor plus Vertical Input at Length Scale of2 5-8

Comparison of Analytical and Experimental Results of Floor System with Isolation System 1 in EI Centro 7th Floor plus Vertical Input at Length Scale of3 5-9

Comparison of Analytical and Experimental Results of Floor System with Isolation System 1 in EI Centro 7th Floor plus Vertical Input at Length Scale of4 5-10

Comparison of Analytical and Experimental Results of Floor System with Isolation System 2 in EI Centro 7th Floor plus Vertical Input at Length Scale of2 5-11

Comparison of Analytical and Experimental Results of Floor System with Isolation System 2 in EI Centro 7th Floor plus Vertical Input at Length Scale of3 5-12

XIV

Page 17: Study of Seismic Isolation Systems for Computer Floors

LIST OF ILLUSTRATIONS (cont'd)

FIG. TITLE

5-8 Comparison of Analytical and Experimental Results of Floor System with Isolation System 3 in EI Centro 7th Floor plus Vertical Input at Length Scale

PAGE

of2 5-13

5-9 Comparison of Analytical and Experimental Results of Floor System with Isolation System 3 in EI Centro 7th Floor plus Vertical Input at Length Scale of3 5-14

5-10 Comparison of Analytical and Experimental Results of Floor System with Isolation System 3 in EI Centro 7th Floor plus Vertical Input at Length Scale of 4 5-15

5-11 Comparison of Analytical and Experimental Response of Floor System with Isolation System 1 in EI Centro 7th Floor plus Vertical Input at Length Scale of 2. Analysis Performed without Accounting for Dependence of Coefficient of Friction on Instantaneous Bearing Pressure 5-17

5-12 Comparison of Analytical and Experimental Response of Floor System with Isolation System 1 in EI Centro 7th Floor plus Vertical Input at Length Scale of 3. Analysis Performed without Accounting for Dependence of Coefficient of Friction on Instantaneous Bearing Pressure 5-18

5-13 Comparison of Analytical and Experimental Response of Floor System with Isolation System I in EI Centro 7th Floor plus Vertical Input at Length Scale of 4. Analysis Performed without Accounting for Dependence of Coefficient of Friction on Instantaneous Bearing Pressure 5-19

5-14 Analytical Response of Isolated Floor System with Cabinet of 5 Hz Frequency and Isolation Period of2.5 secs in Taft 7th Floor Motion 5-25

5-15 Analytical Response of Isolated Floor System with Cabinet of 5 Hz Frequency and Isolation Period of3.0 secs in Taft 7th Floor Motion 5-26

5-16 Analytical Response of Isolated Floor System with Cabinet of 10Hz Frequency and Isolation Period of2.5 secs in Taft 7th Floor Motion 5-27

5-17 Analytical Response of Isolated Floor System with Cabinet of 10 Hz Frequency and Isolation Period of3.0 secs in Taft 7th Floor Motion 5-28

5-18 Analytical Response of Isolated Floor System with Cabinet of 20 Hz Frequency and Isolation Period of2.5 secs in Taft 7th Floor Motion 5-29

5-19 Analytical Response of Isolated Floor System with Cabinet of 20 Hz Frequency and Isolation Period of3.0 secs in Taft 7th Floor Motion 5-30

5-20 Analytical Response of Isolated Floor System with Cabinet of 5 Hz Frequency and Isolation Period of2.5 secs in EI Centro 7th Floor Motion 5-31

5-21 Analytical Response of Isolated Floor System with Cabinet of 5 Hz Frequency and Isolation Period of3.0 secs in EI Centro 7th Floor Motion 5-32

xv

Page 18: Study of Seismic Isolation Systems for Computer Floors

LIST OF ILLUSTRATIONS (cont'd)

FIG. TITLE PAGE

5-22 Analytical Response of Isolated Floor System with Cabinet of 10Hz Frequency and Isolation Period of2.5 secs in EI Centro 7th Floor Motion 5-33

5-23 Analytical Response of Isolated Floor System with Cabinet of 10Hz Frequency and Isolation Period of3.0 secs in EI Centro 7th Floor Motion 5-34

5-24 Analytical Response of Isolated Floor System with Cabinet of 20 Hz Frequency and Isolation Period of2.5 secs in EI Centro 7th Floor Motion 5-35

5-25 Analytical Response of Isolated Floor System with Cabinet of 20 Hz Frequency and Isolation Period of3.0 secs in EI Centro 7th Floor Motion 5-36

5-26 Analytical Response of Isolated Floor System with Cabinet of 5 Hz Frequency and Isolation Period of2.5 secs in Pacoima Dam Ground Motion 5-37

5-26 Analytical Response of Isolated Floor System with Cabinet of 5 Hz Frequency and Isolation Period of2.5 secs in Pacoima Dam Ground Motion 5-37

5-27 Analytical Response of Isolated Floor System with Cabinet of 5 Hz Frequency and Isolation Period of3.0 secs in Pacoima Dam Ground Motion 5-38

5-28 Analytical Response of Isolated Floor System with Cabinet of 10Hz Frequency and Isolation Period of2.5 secs in Pacoima Dam Ground Motion 5-39

5-29 Analytical Response of Isolated Floor System with Cabinet of 10Hz Frequency and Isolation Period of3.0 secs in Pacoima Dam Ground Motion 5-40

5-30 Analytical Response of Isolated Floor System with Cabinet of 20 Hz Frequency and Isolation Period of2.5 secs in Pacoima Dam Ground Motion 5-41

5-31 Analytical Response of Isolated Floor System with Cabinet of 20 Hz Frequency and Isolation Period of 3.0 secs in Pacoima Dam Ground Motion 5-42

5-32 Comparison of Response of Floor System by High Friction and by a Combination of Low Friction and High Viscous damping Isolation Systems 5-43

XVI

Page 19: Study of Seismic Isolation Systems for Computer Floors

LIST OF TABLES

TAB. TITLE PAGE

3-1 Frictional Properties of FPS Bearings and Viscous Damping Ratio of Isolation System 3-11

3-II Earthquake Motions Used in Test Program and Peak Motion Characteristics in Prototype Scale 3-20

3-III Length Scales in Testing Program and Corresponding Isolation System Properties 3-23

3-IV List of Channels (with reference to Figures 3-24 to 3-27) 3-37

5-1 Parameters in Analytical Model of Tested Isolated Floor System

5-II Parameters in Analytical Parametric Study

A-I Recorded Quantity and Corresponding Instrument(s)

XVll

5-6

5-21

A-I

Page 20: Study of Seismic Isolation Systems for Computer Floors
Page 21: Study of Seismic Isolation Systems for Computer Floors

SECTION 1

INTRODUCTION

Provisions for the design of buildings intend to provide protection against major structural

failure and loss of life. They are not intended to limit damage, maintain function, or

provide for easy repair (SEAOC, 1990). Yet, structures house equipment, such as

computers and data processing systems, on which businesses and industries rely.

Interruption or failure of these systems in an earthquake may result in chaos and

substantial economic loss.

Moreover, the safety of computers and other equipment is a concern when they perform

life saving operations such as in hospitals. Also, the protection of invaluable artifacts in

museums is important.

Protection of important equipment and artifacts in buildings may be accomplished in a

variety of ways, with varying degrees of success:

(a) Seismic Isolation of Building.

Seismic isolation of the entire building offers the benefits of reduction or elimination of

damage to the structural system, nonstructural components and housed equipment and

artifacts. In this construction technique the entire structure is supported on horizontally

flexible bearings (may be elastomeric or sliding bearings) so that its fundamental period

increases to values beyond the predominant one in the seismic excitation. Effectively,

seismic energy is deflected, leading to reduced inertia forces on the structure. The

1-1

Page 22: Study of Seismic Isolation Systems for Computer Floors

approach is particularly attractive for new construction. It has been used in the United

States and Japan in a number of critical facilities, such as hospitals, fire command centers

and computer manufacturing facilities (Kelly 1993, Soong and Constantinou 1994).

(b) Innovative Installation Procedures for Equipment.

These installation procedures may take the form of seismic isolation systems or a form of

combined limited isolation and energy dissipation systems. Typically, seismic isolation of

equipment is confronted with a number of problems, such as extreme difficulty to achieve

the desired long period and large displacements in comparison to the dimensions of

equipment.

For example, consider the problem of providing effective isolation for a motion such as the

1940 EI Centro earthquake, of which the response spectrum is given by Figure 3-14

herein. For bearings with a damping ratio of 5 % of critical and isolation period of 2 secs

will result in an acceleration of 0.2 g with bearing displacement of about 200 mm.

Bearings for these requirements are easily designed for buildings, but are very difficult or

impossible to meet for equipment, which have small weight.

Furthermore, equipment in the upper floors of a building experience motions which are

amplified in acceleration and contain strong components at long periods. Figure 3-16

herein presents the response spectrum of motion at the 7th floor of a building excited at

its base by the same 1940 EI Centro motion. For an isolated equipment at the 7th floor

to achieve an acceleration of 0.2 g , it requires an isolation period of 2.8 secs , for which

the bearing displacement is about 390 mm. Apart from the extreme difficulty in achieving

1-2

Page 23: Study of Seismic Isolation Systems for Computer Floors

this period (most types of bearings will be unstable under the gravity load), the required

displacement capacity of the isolation system is of the same order as that of the equipment

itself. Typically, to achieve effective isolation of single equipment under these conditions

it is required to use either spherically shaped sliding bearings, or multi-stage rubber

bearings, or pneumatic isolators. In any case, the cost is prohibitively high.

Alternatively, systems consisting of locked casters and restoring force/damping devices,

such as wire rope springs and viscoelastic elements, and stiff helical spring-viscous damper

systems were respectively tested by Demetriades 1992 , Kosar 1993 and Makris 1992.

The systems were found to improve the seismic response of single equipment either by

reducing accelerations at the expense of limited displacements or by maintaining

accelerations at the same level and substantially reducing the sliding displacements of

conventionally mounted equipment. However, the systems required the use of rather

complex arrangements of elements, which could constrain normal operations in a

computer room.

( c) Seismic Isolation of Computer Floors.

Problems with seismic isolation or innovative installation procedures of single equipment

can be alleviated by providing seismic isolation to entire computer floors. In this way, the

seismic forces may be substantially reduced while normal operations in the computer room

are not affected.

The Japanese construction industry developed a number of such computer floor systems

by utilizing combinations of devices, such as sliding bearings, springs, dampers,

1-3

Page 24: Study of Seismic Isolation Systems for Computer Floors

multi-stage rubber bearings, pneumatic isolators and even active components (Fujita

1991).

The work described in this report concentrated on the development and testing of

computer floor seismic isolation systems by utilizing devices of established effectiveness in

the seismic isolation of buildings and shock isolation of military equipment. A computer

floor system with raised floor and a generic slender equipment cabinet was constructed. It

was isolated by spherically shaped sliding bearings and was highly damped either by

utilizing high friction in the bearings or by installing fluid viscous dampers. The

spherically shaped bearings provided, in our opinion, the simplest means of achieving long

period in the isolation system under low gravity load.

The isolation system prevented rocking of the cabinet on top of the isolated floor and

substantially reduced its acceleration response in comparison to that of a conventional

computer floor. An analytical study was also conducted in order to extend the results to a

range of parameters which could not be tested.

1-4

Page 25: Study of Seismic Isolation Systems for Computer Floors

SECTION 2

DESCRIPTION OF COMPONENTS OF FLOOR ISOLATION SYSTEM

2.1 Introduction

The behavior of three isolation systems was investigated during these series of tests. All

three systems had as a basic isolation device the Friction Pendulum System (FPS) bearing,

a form of spherical sliding bearing. This bearing was selected because it can be designed

to deliver a large isolation period and accommodate large displacements under low gravity

load without any instability problems. In one tested configuration, only FPS bearings of

high friction were used. In two other configurations, better performance was sought by

utilizing lower friction bearings and by enhancing the ability of the isolation system to

dissipate energy through the use of fluid viscous dampers. The various components of the

isolation system are described in the following sections.

2.2 Friction Pendulum System Bearings (FPS)

A cross section view of a FPS bearing used in testing is shown in Figure 2-1. The bearing

consists of a spherical sliding surface and an articulated slider which is faced with a high

pressure capacity bearing material. The bearing is constructed of steel with the articulated

slider and the spherical surface made of stainless steel. Specifically, the spherical sliding

surface consists of highly polished austenitic, type 316 stainless steel. All sliding

interfaces, that is those of the articulated slider with the spherical surface and the

2-1

Page 26: Study of Seismic Isolation Systems for Computer Floors

supporting column, are faced with a high bearing capacity, self lubricating, PTFE-based

composite material.

The bearing used in testing of the floor isolation system (Figure 2-1) is identical to the one

used in testing of an isolated bridge model (Constantinou 1993). This bearing was

designed for vertical loads in excess of 50 kN. The load carried by the bearing in the floor

system tests was only 7 kN.

units:mm

112~ 82.£'

~

27'3

22'3

'---- CONCAVE SPHERICAL SURFACE FACED 'WITH STAINLESS STEEL OVERLAY

CONCAVE PLATE ------ PLATE 279_279_25

___ --CIRCULAR RETAINER

\-------- SEAL

Figure 2-1 Construction of Friction Pendulum System (FPS) Bearing

2-2

Page 27: Study of Seismic Isolation Systems for Computer Floors

2.2.1 Principles of Operation

The FPS isolation bearings produce the isolation effect by introducing flexibility and

energy absorption capability at an interface between the structure (or raised floor system

in this case) and the moving ground (or floor in this case). The principles of operation of

the FPS bearing have been established by Zayas 1987 and Mokha 1990, and more recently

described in a more general form by Constantinou 1993. As illustrated in Figure 2-2, a

structure on FPS bearings behaves as a pendulum of length R, where R is the radius of

curvature of the spherical sliding surface.

F or a typical design of this bearing the displacement capacity is less than 0.2R, so that

angle e (see Figure 2-2) is small. Under this condition the lateral force, F, at displacement

U IS

F= ~U+).1Wsgn(u) (2-1)

where W = load on bearing, j..l = coefficient of friction and u = velocity. The form of

equation (2-1) reveals the following unique properties of this isolation system:

(1) The period of vibration of the isolated structure is

(2-2)

This is independent of the supported mass and dependent only on the geometry of

the bearings.

(2) The lateral force is directly proportional to the weight they carry and, thus, the

isolation system force always develops at the center of mass of the supported

2-3

Page 28: Study of Seismic Isolation Systems for Computer Floors

structure. This property minimizes adverse torsional motions. This is important in

computer floor systems where equipment can be moved to arbitrary locations on

the floor without affecting the behavior of the isolation system.

(3) The bearings provide rigidity to service and minor earthquake loads. This is

accomplished by the friction in the bearings which does not allow motion until the

static friction limit is exceeded.

(4) The bearings have high vertical load capacity and stability. Owing to their unique

construction they do not exhibit P-~ effects at large displacements.

(5) Their properties of flexibility and energy absorption capability are not interrelated.

The first is entirely controlled by geometry (radius R) and the second is controlled

by friction at the sliding interface. This property allows for optimum design of the

isolation system.

In Figure 2-3 an open FPS bearing can be seen. During these series of tests the bearings

were installed with their spherical surface facing down. The radius of curvature of the

spherical sliding surface was R = 558.8 mm (22 inches) providing a period of vibration to

the isolation system of 1.5 sec. The maximum displacement to be accommodated by

these bearings was 89 mm (3.5 inches) in all directions.

2-4

Page 29: Study of Seismic Isolation Systems for Computer Floors

~

\ " / " /'

........ _---- /'

~ \

PENDULUM MOTION

MOTION OF STRUCTURE ON FPS BEARINGS

ARTICULATED SLIDER

F

R

u=Rsin e

Rcose

SPHERICAL SURFACE

v=R( l-cos e)

Figure 2-2 Basic Principle of Operation of FPS Bearing

2-5

Page 30: Study of Seismic Isolation Systems for Computer Floors

Figure 2-3 View of FPS Bearing

2.3 Fluid Viscous Dampers

Fluid viscous dampers operate on the principle of fluid flow through orifices. The

particular device used in these tests has been previously used in the testing of a steel model

structure (Constantinou 1992) and an isolated bridge model (Tsopelas 1994). The

construction of these devices is shown in Figure 2-4. It consists of a stainless steel piston,

with a bronze orifice head and an accumulator. It is filled with silicone oil.

2-6

Page 31: Study of Seismic Isolation Systems for Computer Floors

2.3.1 Operation of Fluid Dampers

The force that is generated by the fluid damper is due to a pressure differential across the

piston head. Consider that the piston head moves from left to right in Figure 2-4 (device

subjected to compressive force). Fluid flows from chamber 2 towards chamber 1.

Accordingly, the damping force is proportional to the pressure differential in these two

chambers. However, the fluid volume is reduced by the product of travel and piston rod

area. Since the fluid is compressible, this reduction in fluid volume is accompanied by the

development of a restoring (spring like) force. This is prevented by the use of the

accumulator.

The force generated by the differential of pressure is proportional to a power of the piston

rod velocity. Typical designs with cylindrical orifices produce force proportional to

velocity squared. This is usually unacceptable performance. A variety of designs have

been produced, which can alter the flow characteristics in order to produce acceptable

performance. Details of these designs may be found in Soong and Constantinou, 1994.

The particular damper used in these tests has been fitted with a fluidic control orifice, a

design which can produce force proportional to powers of velocity in the range of 0.4 to

2.0.

In these tests, the dampers were designed to have linear viscous behavior, that is

(2-3)

where P = force, it = velocity, and Co = damping constant. The damping constant was

experimentally determined to be equal to 14 Ns/mm at room temperature. Typically,

2-7

Page 32: Study of Seismic Isolation Systems for Computer Floors

these dampers are insensitive to variations of ambient temperature (Constantinou 1992,

Soong and Constantinou, 1994).

SEAL RETAINER

PISTON ROO PISTON HEAD WITH ORIFICES

CYLINDER

COMPRESSIBLE SILICONE FLUID

ACCUMULATOR HOUSING

ROO MAKE-UP ACCUMULATOR

_S€CONJARY INTAKE

STAGNATION 01AM8ER

-ACCELEHA I or:r­CIRCUIT

Fluidic Control Orifice

Figure 2-4 Construction of Fluid Viscous Damper

2-8

Page 33: Study of Seismic Isolation Systems for Computer Floors

SECTION 3

TESTED SYSTEM

3.1 Description of Tested System

The tested system consisted of an electronic equipment cabinet (termed the Cabinet) on

top of a raised floor system (termed the Raised Floor). The columns of the Raised Floor

were supported by beams, which formed the Base Floor. The isolation system was placed

between the Base Floor and the shake table, as it would have been installed on a typical

floor of a building. Figure 3 -1 presents a view of the tested system on the shake table.

Figure 3-1 View of Tested System on Shake Table

3-1

Page 34: Study of Seismic Isolation Systems for Computer Floors

The Raised Floor had plan dimensions of 1.83 m by 3.05 m (6 by 10 feet). Typically,

computer floors are crowded with equipment with total load of about 100 psf (48 kN/m2).

To properly simulate the load on the bearings, extra weights have been added at the Base

Floor to reach a total weight (Base Floor plus Raised Floor plus Cabinet) of 27.59 kN

(6.2 kips).

3.2 Description of Cabinet

The tested Cabinet is shown in Figure 3-2, whereas Figure 3-3 presents a schematic of the

Cabinet. It was placed on the Raised Floor having its center of mass at a distance of

0.9Im (3 feet) from the south side and 2.13m (7 feet) from the north side of the Raised

Floor. It was stranded with standard bungee cords on the Base Floor. The bungee cords

were attached to the frame of the Cabinet, run through holes in the tiles of the Raised

Floor and were attached to holes in the beams of the Base Floor. This arrangement allows

for easy relocation of the equipment, a typical requirement in computer floor systems. It

also allows for sliding and rocking of the equipment in seismic excitation but prevents

overturning of the equipment.

The Cabinet is 1.88m (74 in) in height and 0.56m by 0.76m (22 in by 30 in) in plan. It

consists of four horizontal diaphragms (levels 1, 2, 3 and top). These diaphragms are

connected together by side walls, which extend only in the longitudinal direction. At level

1, where the center of mass is located, alII N (25 lbs) weight was rigidly mounted on the

diaphragm. At levels 2 and 3, weights of 116 Nand 178 N (26 and 40 lbs) were

respectively mounted on trays which were supported by wire rope springs on top of the

3-2

Page 35: Study of Seismic Isolation Systems for Computer Floors

Figure 3-2 View of Cabinet on Raised Floor

3-3

Page 36: Study of Seismic Isolation Systems for Computer Floors

0.70

f--__ ----".iLEVEL 3

~_----7ILEVEL 2

0.16

1.88 0.10

0.92

CONNECTED TO

t .. BEAMS OF BASE FLOOR ..

TESTING DIRECTIONS

Figure 3-3 Tested Equipment Cabinet (Units: m)

3-4

Page 37: Study of Seismic Isolation Systems for Computer Floors

diaphragms. These arrangements represented flexible internal components of an

equipment cabinet. The arrangements may be seen in Figure 3-2.

Identification tests were conducted to establish the dynamic characteristics of the Cabinet

itself and of the two flexible internal arrangements. The Cabinet had a total weight of

1780 N (400 lbs), and its center of mass was at height of 920 mm from its base, and at the

level 1 diaphragm. From transfer functions, obtained in low level white noise excitation

and using the acceleration records at level 1 (center of mass), it was determined that the

Cabinet, in its fixed base condition, had a frequency of 40 Hz and damping ratio of about

2%.

The two flexible internal oscillators exhibited highly non-linear behavior due to the

hysteretic nature of the wire rope springs (Demetriades 1992). The dynamic

characteristics were determined in pull release tests from records of acceleration of the

masses. For level 2 (stiff system), its fundamental frequency was found to be 6.7 Hz for

acceleration of about 0.5 g, and 9.4 Hz for accelerations less than 0.1 g. For level 3 (soft

system), its fundamental frequency was found to be 4.8 Hz for accelerations greater than

0.5 g, and 8 Hz for accelerations less than 0.1 g. Due to the highly non-linear behavior of

the internal systems, and the interaction of all the connected parts of the Cabinet, the

damping ratio of the internal oscillators could not be accurately determined. It was

estimated to be of the order of 20 % of critical.

3-5

Page 38: Study of Seismic Isolation Systems for Computer Floors

3.3 Description of Base Floor

The Base Floor consisted of two AlSC W6x9 sections which spanned 3.05 m (10 feet).

These beams were transversely connected by AlSC W4x13 sections at centers of 0.61 m

(2 feet), which spanned 1.88 m (6 feet). In order to facilitate the addition of extra weight

on the Base Floor, two steel plates 12.7 mm thick were welded at the two edge bays. On

these steel plates lead bricks were added to reach the total weight of27.59 kN (6.2 kips)

of the floor system. Care was taken in detailing and manufacturing of the connections of

the Base Floor to the FPS bearings. At the four corners of the Base Floor, steel plates,

19.05 mm thick and 406.4 by 406.4 mm in plan, were attached. The surface in contact

with the FPS bearings (bottom side) was machined flat so that a perfect fit could be

achieved without the need for grouting.

F or the attachment of the Fluid Dampers, four steel brackets were welded at the bottom of

the W6x9 sections.

The total weight of the Base Floor was 23.94 kN (5.38 kips).

3.4 Description of Raised Floor

At the top of the Base Floor, the Raised Floor was erected. Aluminum pedestals were

welded to form a 609.6 by 609.6 mm (24 by 24 in) grid. The Raised Floor was assembled

together as a "bolted stringer system", according to the manufacturer's specifications. The

pedestals were connected with aluminum stringers and at the top "all steel computer floor

panels" with hard surface coverings were placed. The finished height of the Raised

3-6

Page 39: Study of Seismic Isolation Systems for Computer Floors

Computer Floor was 355.6 mm (14 in), and had plan dimensions of 1.83 by 3.05 m (6 by

10 feet). Standard seismic braces, provided by the manufacturer, were used to support the

pedestals of the Raised Floor (see Figure 3-1).

The total weight of the Raised Floor was 1.875 kN (0.422 kips). Identification tests

showed that the first frequency of the Raised Floor was 31.2 Hz, and the damping ratio

was 3.6%.

3.5 Tested Configurations

Three different isolation configurations were tested. The Friction Pendulum System (FPS)

bearing was the basic component in all three. Four FPS bearings were placed on the top

of load cells and supported the Base Floor. The bearings were installed with the spherical

surface facing down. The schematic of the floor system is shown in Figure 3-4.

The frictional properties of the material attached on the articulated slider were determined

in identification tests prior to and following the seismic testing. The coefficient of friction

was extracted from recorded loops of force vs bearing displacement. The coefficient of

friction followed the relation proposed by Constantinou 1990:

!J. = fmax - (fmax - fmin) exp (-a I trl) (3-1)

where f max is the coefficient of friction at high velocity of sliding, f min is the coefficient of

friction at essentially zero velocity of sliding and a is a parameter controlling the variation

of the coefficient with velocity of sliding.

3-7

Page 40: Study of Seismic Isolation Systems for Computer Floors

W

I 00

Q,7

6

__

_ CA

BIN

ET

(1.7

8

kN)

RA

ISED

FL

OO

R (1

.87

5 k

N)

4 !

_ TE

STIN

G

DIR

ECTI

ON

S

l.B

B

1.:

00

Fig

ure

3-4

Sche

mat

ic o

f Tes

ted

Isol

atio

n F

loor

Sys

tem

(U

nits

: m

)

NORT

H

J. TA

BLE

Page 41: Study of Seismic Isolation Systems for Computer Floors

0,56

-----

---------- 1. 88

BASE FLOOR

(23,8~ kN)l~~~~~l_~~~~~~~~~~ ~ AISC "'4x13

1><:1 r~-I

-0.17

=0,08 1.00

I ~. LOCATION OF DAMPERS ~1 I /

FOR ISOL,3 " '\~ "/J~ 0, 8

l 0.27 l l 0,27 l

1. 85

'WEST EAST

Figure 3-4 Continued

3-9

Page 42: Study of Seismic Isolation Systems for Computer Floors

In the identification tests the Cabinet was removed from the Raised Floor and the shake

table was driven at sinusoidal motion of specified frequency and amplitude. The

essentially rigid isolated structure responded in harmonic motion of the same amplitude.

The coefficient of friction was then extracted from recorded force-displacement loops of

the FPS bearings.

Furthermore, recorded force-displacement loops of the bearings during seismic testing

were used to obtain values of the coefficient of friction. These values were related to the

peak velocity at the sliding interface, which was determined from the recorded time history

of bearing displacement by numerical differentiation. Moreover, static push tests were

conducted in order to determine the coefficient of friction at initiation of motion. The

results are presented in Figure 3-5 together with those of the calibrated model of equation

(3-1). The parameters of the model of friction are presented in Table 3-I.

Of interest is to note in Figure 3-5 that the minimum value of the coefficient of friction in

the static push test is equal to 0.035 for the lower friction bearings. The static value of

friction is actually higher because the bearings were tested just after installation, and not

after sufficient load dwell (see Soong and Constantinou, 1994 for discussion on this

phenomenon). Typically, the static value of friction for these bearings is larger than 1m;n

but less than 1max' If we use the value of 0.035 we conservatively calculate the resistance

of the isolation system against service loads as 0.035W (W= total weight= 27.59 kN or

6.2 kips) or about 1 kN (220 lbs). This is sufficient to prevent any motion during normal

use of the computer floor.

3-10

Page 43: Study of Seismic Isolation Systems for Computer Floors

Table 3-1: Frictional Properties of FPS Bearings and Viscous Damping Ratio of Isolation System

Z 0 f= ()

a: LL LL 0 ~ Z W U u::: LL w 0 ()

(!) Z 15 ::J CJJ

Z 0 f= ()

a: LL LL 0 ~ Z w U u::: LL w 0 ()

(!) Z 15 ::J CJJ

ISOLATION fave f_ a Viscous

SYSTEM (sec/mm) Damping Ratio

0.22

0.20

0.18

0.16

0.14

0.12

0.10

0.08

0.06

0.04

0.02

0.00 0

0.22

0.20

0.18

0.16

0.14

0.12

0.10

0.08

0.06

0.04

0.02

0.00 0

1 0.19

2 0.13

3 0.13

Properties for Isolation System 1. (High Friction)

• o

0.07

0.03

0.03

0.015

0.015

O.oI5

• o

fmax=0.19 fmin=0.07 0=0.015 sec/mm

(%)

0.00

0.60

0.35

• Seismic Test, Pressure 3.45 MPa (0.50 ksi)

o Sinusoidal Test, Pressure 3.10 MPa (0.45 ksi)

• Static Push Test, Pressure 3.10 MPa (0.45 ksi

50 100 150 200 250 300 350 400 VELOCITY (mm/sec)

450 500 550

Properties for Isolation Systems 2 & 3. (Lower Friction)

50 100 150

o

fmax=0.13 fmin=0.03 0=0.015 sec/mm

o Sinusoidal Test (Without Dampers)

• Static Push Test

/!,. Sinusoidal Test (With Dampers)

200 250 300 350 400 VELOCITY (mm/sec)

450 500 550

600

600

Figure 3-5 Coefficient of Sliding Friction as a Function of Bearing Pressure and Sliding Velocity

3-11

Page 44: Study of Seismic Isolation Systems for Computer Floors

3.5.1 Isolation System 1

This system consisted of the four FPS bearings. The pressure on the bearings was

3.45MPa during seismic tests and 3.1 OMPa during sinusoidal tests. Isolation System 1

is characterized as "High Friction" with f max = 19 % and f min = 7 %. Figure 3-6 shows

recorded isolation force-displacement loops (combined, as recorded from the four

bearings) of the system in an identification test with harmonic motion of 1 Hz frequency.

The "thickness" of the hysteresis loop is equal to 2!l W, where W = weight of 25.8 kN

(Cabinet removed) and!l = coefficient of sliding friction. It is equal to 0.187.

3.5.2 Isolation System 2

In order to reduce the friction coefficient of the FPS bearings, small backing plates were

inserted between the articulated slider and the bearing material. Therefore, the pressure

would increase resulting in a lower coefficient of friction. These "Lower Friction"

bearings were used in Isolation Systems 2 and 3. The low load on the bearings prevented

the FPS to behave as expected to. The presence of backing plates was not fully utilized

and the "Lower Friction" bearings gave a friction coefficient higher than expected

ifmax =0.13). In combination with FPS bearings, two fluid dampers were used. They

connected the Base Floor to the shaking table at an angle of 45° to the vertical. A view of

Isolation System 2 on the shake table is shown in Figure 3-7. By having the dampers in an

angle, the damping constant was reduced by a factor of cos245° (=0.5). The damping

constant of each damper was 14 N s/mm. Therefore, the effective damping constant for

Isolation System 2 was 14 Ns/mm (2 dampers at 45° angle).

3-12

Page 45: Study of Seismic Isolation Systems for Computer Floors

10

8 6 4 2 - z ~ w

0

U

t....l

a:

I

0 -'

t....l

u.

-2

-4

-6

-8

-1~100

WE

IGH

T W

=2S

.8 k

N

-75

Fig

ure

3-6

-50

-25

0 25

50

B

EA

RIN

G D

ISP

LA

CE

ME

NT

(m

m)

Rec

orde

d Is

olat

ion

Sys

tem

1 F

orce

-Dis

plac

emen

t Loo

ps i

n Id

enti

fica

tion

Tes

t at

1 H

z F

requ

ency

21lW

75

10

0

Page 46: Study of Seismic Isolation Systems for Computer Floors

Figure 3-7 View of Isolation System 2

The viscous damping ratio of the isolation system is determined from

P=~=~JRg 2mro 2W

(3-2)

where m == mass (Wig), C == effective damping constant from the two dampers and

ro == natural frequency. For C == 14 Ns/mm, P == 0.6. This value is listed in Table 3-I.

Figure 3-8 shows recorded force-displacement loops of Isolation System 2 in a test with

harmonic motion of 1 Hz frequency. The top figure shows the combined loops from the

four FPS bearings. The next figure shows loops from the two fluid dampers (see Figure

3-4), whereas the bottom figure shows the total isolation system force-displacement loop.

It has been obtained by adding the horizontal component of the fluid damper forces to the

forces in the four FPS bearings and plotting the total force vs the bearing displacement.

3-14

Page 47: Study of Seismic Isolation Systems for Computer Floors

-Z ..:.:: ....... w () a: f2

-Z C w ()

5

o

-5

FORCE IN 4 FPS BEARINGS

-40

FORCE IN WEST SIDE

FLUID DAMPER

-20 0 20 BEARING DISPLACEMENT (mm)

w ()

FORCE IN EAST SIDE

FLUID DAMPER

40 60

~ 0 NA ~ 0 u.. ....J « X «

-Z ..:.:: ....... w () a: f2

u.. ....J « X «

-5 ~~~~~~~~~~~ -5~~~~~-L~~~~~

-40 -20 0 20 40 -40 -20 0 20 40 AXIAL DAMPER DISPL. (mm) AXIAL DAMPER DISPL. (mm)

5

TOTAL FORCE IN HORIZONT~AL~D~IR~E;C~TI;;O;.;.N=",=~~~~

o

-5

-40 -20 0 20 40 60 BEARING DISPLACEMENT (mm)

Figure 3-8 Recorded Isolation System 2 Force-Displacement Loops in Identification Test at 1 Hz Frequency

3-15

Page 48: Study of Seismic Isolation Systems for Computer Floors

3.5.3 Isolation System 3

The only difference between this system and Isolation System 2 is in the placement of the

dampers. They were placed so that their axis formed approximately equal angles with

respect to vertical, longitudinal and transverse directions. Using the direction cosines rule

of analytic geometry, and calculating the angle between two lines, the reduction factor of

the coefficient of damping was cos257.5° (=0.289). Therefore, the effective damping

constant of the isolation system was 8.09 Ns/mm. This corresponds to a viscous damping

ratio of 0.35. Thus systems 2 and 3 differed only in the viscous damping ratio. A view of

Isolation System 3 on the shake table is shown in Figure 3-9.

Recorded force-displacement loops of Isolation System 3 in a test with harmonic motion

of 1 Hz frequency are shown in Figure 3-10.

Figure 3-9 View of Isolation System 3

3-16

Page 49: Study of Seismic Isolation Systems for Computer Floors

Z :::=.. UJ () a: 0 LL

..--... z e. UJ ()

10

5

0

-5

-10 -60

FORCE IN 4 FPS BEARINGS

-40

FORCE IN WEST SIDE

FLUID DAMPER

-20 0 20 BEARING DISPLACEMENT (mm)

FORCE IN EAST SIDE

FLUID DAMPER

40 60

~ 0 LL ...J « X «

..--... z ~ '-"

UJ () a: o LL

-5 ~~~~~-L~~~~~ -5 '-----'-~_____.1.~~__'_~~~~~ -40 -20 0 20 40 -40 -20 0 20 40

AXIAL DAMPER DISPL. (mm) AXIAL DAMPER DISPL. (mm)

5

TOTAL FORCE IN HORIZONTA~L~D:IR~E~C~TI~O~N::::::~~~~~=:::::"

o

-5

-40 -20 0 20 40 60 BEARING DISPLACEMENT (mm)

Figure 3-10 Recorded Isolation System 3 Force-Displacement Loops in Identification Test at 1 Hz Frequency

3-17

Page 50: Study of Seismic Isolation Systems for Computer Floors

3.6 Experimental Program

The computer floor was tested in four different configurations: Non-isolated and isolated

with systems 1, 2 and 3. The test program was as follows:

(1) The bearings were locked by side plates to represent a non-isolated floor.

Identification tests with banded white noise in the frequency range of 0 - 50 Hz,

without the Cabinet, were performed. This established the properties of the Raised

Floor.

(2) The FPS bearings were released and the Isolation System 1 was in effect.

Sinusoidal tests with 1 Hz frequency, without the Cabinet on the floor, were

conducted to determine the properties of the isolation system. Furthermore, static

pull tests were performed to determine imin0 The Cabinet was then placed on the

Raised Floor and seismic tests were performed.

(3) The bearings were locked agam (non-isolated configuration) and a number of

seismic tests was performed.

(4) The bearings were unlocked and static pull tests were conducted. Then the

bearing material was replaced with the "Lower Friction" one. Static pull tests with

this material were performed. These tests established the coefficient of friction of

the bearings under static conditions (fmin).

(5) Sinusoidal tests with 1 Hz frequency, without the Cabinet, were conducted. These

tests revealed the frictional properties of the "Lower Friction" FPS bearings.

3-18

Page 51: Study of Seismic Isolation Systems for Computer Floors

(6) Isolation System 3 was put in effect. Fluid dampers were attached to the Base

Floor. Sinusoidal and seismic tests were performed.

(7) Isolation System 2 was established by reconfiguring the fluid dampers. Sinusoidal

and seismic tests were conducted.

The seismic tests were conducted with only horizontal input and with combined horizontal

and vertical input. The earthquake signals and their characteristics are listed in Table 3-11

The earthquake signals consisted of historic earthquakes and artificial motions. The

historic earthquakes were applied as recorded (termed ground motions) and after filtering

through an actual RIC 7 -story structure in order to generate floor motions. Details for

the generation of these floor motions are given in Demetriades 1992. The generated

motions at the 5th and 7th floors of the 7 -story structure were used in the tests. The

vertical component of motion over the height of the 7 -story building was assumed to

remain the same as at the ground level.

Table 3-II contains the peak values of recorded table motion in the tests at length scale of

1 (prototype). Nearly identical peak values of acceleration and velocity, when

extrapolated to prototype scale, were obtained in tests at length scale of 2, 3 and 4 (see

Appendix A). The shake table simulated peak horizontal accelerations and velocities are

comparable with those of the actual (target) motions. However, the shake table simulated

displacements were lower than those of the target motions. The discrepancy is significant

at length scale of 1 , but it is less at the larger length scales (see Appendix A for values in

each test).

3-19

Page 52: Study of Seismic Isolation Systems for Computer Floors

W

I tv

o

Tab

le 3

-11

: E

arth

qu

ake

Mot

ion

s U

sed

in T

est

Pro

gram

an

d P

eak

Mot

ion

Cha

ract

eris

tics

in P

roto

type

Sca

le

NO

TA

TIO

N

RE

CO

RD

S

HA

KE

TA

BL

E S

IMU

LA

TE

D M

OT

ION

A

CT

UA

L M

OT

ION

HO

RIZ

ON

TA

L

VE

RT

ICA

L

HO

RIZ

ON

TA

L

VE

RT

ICA

L

AC

C

VE

L

DIS

A

CC

V

EL

D

IS

AC

C

VE

L

DIS

A

CC

V

EL

D

IS

(g)

(mm

/s)

(mm

) (g

) (m

mls

) (m

m)

(g)

(mm

/s)

(mm

) (g

) (m

mls

) (m

m)

EL

CE

NT

RO

SO

OE

Impe

rial

Val

ley,

May

18,

194

0. H

or.C

omp.

SO

OE

0.37

29

5.9

59.4

0.

33

74.1

l3

.5

0.34

33

4.5

108.

7 0.

21

108.

5 55

.6

TA

FT

N2

1E

K

ern

Cou

nty,

Jul

y 21

, 19

52.

Hor

.Com

p. N

21E

0.

16

148.

3 3

l.3

0.

12

53.3

12

.2

0.16

15

7.2

67.1

0.

11

66.8

50

.3

PA

CO

IMA

S74

W

San

Fer

nand

o, F

ebru

ary

9, 1

971.

Hor

.Com

p. S

74W

1.

01

586.

1 10

3.4

1.60

35

4.5

72.0

1.

08

568.

2 10

8.2

0.71

58

3.1

193.

2

BE

LL

CO

RE

A

rtif

icia

l Mot

ion

0.88

56

3.9

58.7

0.

33

237.

5 18

.1

IBM

LE

VE

L -

1

Art

ific

ial M

otio

n 0.

43

456.

9 55

.6

0.21

12

8.9

17.1

N

OT

AP

PL

ICA

BL

E

IBM

LE

VE

L -

2

Art

ific

ial M

otio

n 0.

98

720.

1 91

.4

0.59

26

8.0

32.5

-

----

-------

Page 53: Study of Seismic Isolation Systems for Computer Floors

It should be noted in Table 3-II that the simulated motion by the shake table had

significantly stronger vertical components than the actual (target) motions. For example,

the simulated vertical component of the Pacoima Dam record had a peak acceleration of

1.6 g , whereas it should have only 0.71 g .

The artificial earthquakes were compatible with a proposed test input by Bellcore 1988 for

upper stories in Zone 4 earthquakes and two IBM developed inputs (IBM 1992). The

IBM inputs, denoted by IBM Level 1 and IBM Level 2, represent two functional test

levels. At the first level, a machine is expected to operate normally, and at the second

level, also referred to as the structure/safety level, gross structural failures should not

occur although the machine may not remain functional (Kosar 1993). The vertical

components of motion were taken as equal to 113 of the simulated horizontal component.

The motions were identical to those used in the tests of Demetriades 1992 and Kosar

1993.

Figures 3-11 to 3-23 present time histories of acceleration, velocity and displacement in

prototype time scale and response spectra of the seismic motions. The acceleration and

displacement histories were obtained from the tests at length scale of one, whereas the

velocity history was obtained by numerical differentiation of the displacement record.

Evidently, the horizontal components of these records contain long period components, as

expected to be the case of floor seismic motions (Singh 1988, Lin 1985). However, it

should be noted that the simulated motions for the Bellcore and IBM inputs do not contain

any significant components at periods above 2 secs.

3-21

Page 54: Study of Seismic Isolation Systems for Computer Floors

It may be observed in Figures 3-11 to 3-23 that the response spectra of the table

motions are in good agreement with the spectra of the actual (target) motions, except for

the vertical spectral components in the low period range, This unfaithful reproduction by

the table of the target vertical motions affected the outcome of the experiments.

Particularly, in the Pacoima motion tests the vertical table acceleration substantially

exceeded 1 g , resulting in uplift of the bearings and Cabinet.

Testing was conducted at four different length scales SL (prototype/model) equal to 1,2, 3

and 4. The tests were conducted by compressing time by factor equal to !&. The

recorded results were thus valid for four different isolation system periods (in prototype

scale): 1.5,2.12,2.60 and 3.0 seconds, as listed in Table 3-Ill.

3-22

Page 55: Study of Seismic Isolation Systems for Computer Floors

Table 3-111 : Length Scales in Testing Program and Corresponding Isolation System Properties

Properties in Isolation System Isolation System Isolation System Prototype Scale 1 2 3

Length Scale 4

Coef. of Friction 0.19 0.13 0.13 fmax

Viscous Damping 0.00 0.60 0.35 Ratio

Isolation System 3.00 3.00 3.00 Period (sees)

Length Scale 3

Coef. of Friction 0.19 0.13 0.13 fmox

Viscous Damping 0.00 0.60 0.35 Ratio

Isolation System 2.60 2.60 2.60 Period (sees)

Length Scale 2

Coef. of Friction 0.19 0.13 0.13 fmax

Viscous Damping 0.00 0.60 0.35 Ratio

Isolation System 2.12 2.12 2.12 Period (sees)

Length Scale 1

Coef. of Friction 0.19 0.13 0.13 fmax

Viscous Damping 0.00 0.60 0.35 Ratio

Isolation System 1.50 1.50 1.50 Period (sees)

3-23

Page 56: Study of Seismic Isolation Systems for Computer Floors

0.2

-~ 0.1 z

0 i= < a: 0.0 w ...J W U u -0.1 <

-0.2 a 5 10 15 20 25 30 35

50 150 DISPLACEMENT

E . VELOCITY

.s 25 75 ~ z w :E 0 w U < ...J n.. rn -25 0

-75 :i

-50 -150 0 5 10 15 20 25 30 35

TIME (sec)

§ 0.7

z 0.6 5% DAMPING 0 i= TABLE MOTION < 0.5 . ACTUAL a: w ...J 0.4 w () () 0.3 < ...J

0.2 < a: ~

0.1 u w n.. --._.-.----en 0.0

a 1 2 3 4 5 PERIOD (sec)

Figure 3-11 Acceleration, Velocity and Displacement Histories and Response Spectrum of Taft (Horizontal) - Ground in Prototype Scale

3-24

-0 Q) (IJ ..... E

..s >-~ (3 0 ...J w >

Page 57: Study of Seismic Isolation Systems for Computer Floors

0.5 ..

-.!?J z 0 t= < a: 0.0 w .J W 0 0 <

-0.5 0 5 10 15 20 25 30 35

50 300 DISPLACEMENT

E --- VELOCITY -0 E 25 150 m - ..... l- E z E w :::i: 0 >-W I-0 {5 < .J 0 a. , . .J en -25 -150 w 0 >

-50 -300 0 5 10 15 20 25 30 35

TIME (sec)

C, 1.5 -z 5% DAMPING 0 T ABLE MOTION i= < -- ACTUAL a: 1.0 w .J W 0 0 < .J 0.5 < a: I-0 W a. en 0.0

0 1 2 3 4 5 PERIOD (sec)

Figure 3-12 Acceleration, Velocity and Displacement Histories and Response Spectrum of Taft (Horizontal) - 5th Floor in Prototype Scale

3-25

Page 58: Study of Seismic Isolation Systems for Computer Floors

0.6

- 0.4 !?J z 0 0.2 i= 0( a: 0.0 w ...J W 0 -0.2 0 0(

-0.4

-0.6 0 5 10 15 20 25 30 35

75 600 DISPLACEMENT

E 50 --- VELOCITY 400 -0 E II) - UJ ... 25 200 E z w E

:::E -w 0 >-0 ... 0( (3 ...J -25 -2000 a.. ...J en w a -50 -400 >

-75 -600 0 5 10 15 20 25 30 35

TIME (sec)

Ci 2.5 -z 5% DAMPING 0 2.0 T ABLE MOTION i= 0( ---- ACTUAL a: w 1.5 ...J w 0 0 1.0 0( ...J 0( a: 0.5 ... 0 W 0-W 0.0

0 1 2 3 4 5 PERIOD (sec)

Figure 3-13 Acceleration, Velocity and Displacement Histories and Response Spectrum of Taft (Horizontal) - 7th Floor in Prototype Scale

3-26

Page 59: Study of Seismic Isolation Systems for Computer Floors

0.5

-~ z 0 ~ < a: 0.0 w ....I W U U <

-0.5 0 5 10 15 20 25 30 35

100 400 DISPLACEMENT

E -- VELOCITY -0 E 50 200 Q)

I/) - ...... l- E z ..s w ::::!: 0 >-w I-() (3 < ....I 0 D.. ....I en -50 -200w 15

-100 -400 0 5 10 15 20 25 30 35

TIME (sec)

§ 1.0

z 5% DAMPING 0 T ABLE MOTION ~ - ACTUAL < a: w I ~ ....I ;.

w 0.5 u ()

< ....I < a: I-U w D.. ---------.-. CIJ 0.0

0 1 2 3 4 5 PERIOD (sec)

Figure 3-14 Acceleration, Velocity and Displacement Histories and Response Spectrum of El Centro (Horizontal) - Ground in Prototype Scale

3-27

>

Page 60: Study of Seismic Isolation Systems for Computer Floors

0.5

-.!?) z 0 i= < a: 0.0 w ..J W () ()

<

-0.5 0 5 10 15 20 25 30 35

150 600 DISPLACEMENT

E 100 ..... _--_ .. VELOCITY 400 '0 .' .

E CD - " m .... 50 "

200 E z E w -::E 0 0 ~ w U ~: : (5 < ..J -50 -2000 a. ..J en w a -100 -400 >

-150 -600 0 5 10 15 20 25 30 35

TIME (sec)

- 2.0 OJ -z 5% DAMPING 0 T ABLE MOTION i= 1.5 < . ACTUAL a: w ..J W

1.0 () ()

< ..J < 0.5 a: .... u '. -w a. en 0.0

0 1 2 3 4 5 PERIOD (sec)

Figure 3-15 Acceleration, Velocity and Displacement Histories and Response Spectrum of EI Centro (Horizontal) - 5th Floor in Prototype Scale

3-28

Page 61: Study of Seismic Isolation Systems for Computer Floors

1.0

-2 0.5 z

0 i= c( a: 0.0 w ...J W 0 0 -0.5 c(

-1.0 0 5 10 15 20 25 30 35

150 750 DISPLACEMENT

E 100 . VELOCITY 5000-E CD - 11)

~ 50 250 E z E w -::::iE 0 >-w ~ 0 5 c( ...J -50 -2500 a.. ...J rn w Ci -100 -500 >

-150 -750 0 5 10 15 20 25 30 35

TIME (sec)

:§ 3

z 5% DAMPING 0 T ABLE MOTION i= c( ........ - .. ACTUAL a: 2 w ...J W 0 0 c(

...J 1 c( a: ~ 0 w a.. rn 0

0 1 2 3 4 5 PERIOD (sec)

Figure 3-16 Acceleration, Velocity and Displacement Histories and Response Spectrum of EI Centro (Horizontal) - 7th Floor in Prototype Scale

3-29

Page 62: Study of Seismic Isolation Systems for Computer Floors

1.0

-..9 0.5 z

0 t= < II: 0.0 W ....J W 0 0 -0.5 <

-1.0 0 5 10 15 20 25 30 35

150 600 DISPLACEMENT

E 100 VELOCITY 400 0 E CD - en I- 50 200 E z E w -::E 0 .". 0 > w -,.-, 0 I-

< (3 ....J -50 -2000 a. ....J en w is -100 -400 >

-150 -600 0 5 10 15 20 25 30 35

TIME (sec)

- 3 ..9 z 5% DAMPING 0 T ABLE MOTION t= < ........... ACTUAL II: 2 w ....J W 0 0 < ....J 1 < II: I-0 W a.

0 en 0 1 2 3 4 5

PERIOD (sec)

Figure 3-17 Acceleration, Velocity and Displacement Histories and Response Spectrum of Pacoima Dam (Horizontal) - Ground in Prototype Scale

3-30

Page 63: Study of Seismic Isolation Systems for Computer Floors

1.0

-.!!! z 0.5 0

.~~ i=

~~~~ ~ 1, , < a: 0.0 w -l W 0 0 < -0.5

-1.0 0 5 10 15 20 25 30 35

100 600 DISPLACEMENT - .. : ..... -. - VELOCITY

E -0

5 50 ..

300 ~ ..... .......

z E w E :::?: a -w 0 >-0 I-

< (3 -l 0 D.. : "

en -50 ..J

is : :: -300w

>

-100 -600 a 5 10 15 20 25 30 35

TIME (sec)

§ 3 ,

z 5% DAMPING 0 l-e:( a: 2 w ..J W 0 0 « ..J 1 < a: I-0 W D.. en a

0 1 2 3 4 5 PERIOD (sec)

Figure 3-18 Acceleration, Velocity and Displacement Histories and Response Spectrum of Bellcore (Horizontal) in Prototype Scale

3-31

Page 64: Study of Seismic Isolation Systems for Computer Floors

-~ z o ~ < ffi 0.0 -J W () ()

<

10 15 20 25 30 35

75~~~~~~~~~~~~~~~~~~~~~600

E 50 E -.... Z W ~ W ()

<

25

a

it -25 en a -50

--- DISPLACEMENT ------ VELOCITY 400 0'

(1) II)

200 E E -o > .... (3

-2000 -1 w

-400 >

-7 5 L-..L-..-----....~-'---'-__'___'___'_..L.......----'---'___'_.J........J...~--'-...I..._J..~~..L_J._'__"__'__L...J.__'_~ -600

z o ~ < 1.5 a: w -J W 8 1.0 < -J < a: .... () w a. en

0.5

o 5 1 a 1 5 20 25 30 35 TIME (sec)

5% DAMPING

1 2 3 4 5 PERIOD (sec)

Figure 3-19 Acceleration, Velocity and Displacement Histories and Response Spectrum of mM 1 (Horizontal) in Prototype Scale

3-32

Page 65: Study of Seismic Isolation Systems for Computer Floors

1.0

-!?J z 0.5 0 t= <

~ c:r: 0.0 W ...J W () ()

-0.5 <

-1.0 0 5 10 15 20 25 30 35

100 800 DISPLACEMENT

E , . ........... VELOCITY 0'

..s 50 ' :

400 CD I/J

~ -z E w E ~

... 0

:: ,. .' -w · . I 0 > ()

: '.;:; · ., .. . . ', · . ~

< ' . , . . , (3 ...J

' .

a.. 0 en -50 . '.

...J

a -400w >

-100 -800 0 5 10 15 20 25 30 35

TIME (sec)

:§ 3 z 5% DAMPING 0 t= < c:r: 2 w ...J W () ()

< ...J 1 < c:r: ~ () w a.. en 0

0 1 2 3 4 5 PERIOD (sec)

Figure 3-20 Acceleration, Velocity and Displacement Histories and Response Spectrum of mM 2 (Horizontal) in Prototype Scale

3-33

Page 66: Study of Seismic Isolation Systems for Computer Floors

0.2

-!?J 0.1 z

0 ~ < a: 0.0 w ...J W 0 0 -0.1 <

-0.2 0 5 10 15 20 25 30 35

15 60

E 10 -,0 E CD - UJ I- 5 -z E w E ~ -w 0 > u !::: < 0 ...J -5 -20 0 D.. ...J (J) W a -10 -40 >

-15 -60 0 5 10 15 20 25 30 35

TIME (sec)

- 0.4 C) -z 5% DAMPING 0

TABLE MOTION ~ 0.3 < ..... _---_. ACTUAL a: w ...J w 0.2 u u < ...J < 0.1 a: I-u --w --- -.---.-D.. "--.

0.0 --'-._- ... -

(J)

0 1 2 3 4 5 PERIOD (sec)

Figure 3-21 Acceleration, Velocity and Displacement Histories and Response Spectrum of Taft (Vertical) - Ground in Prototype Scale

3-34

Page 67: Study of Seismic Isolation Systems for Computer Floors

0.4

-.E) 0.2 z

0 i= < a: 0.0 w ..J W () ()

-0.2 <

-0.4 0 5 10 15 20 25 30 35

15 75 DISPLACEMENT

E 10 ...... VELOCITY 50 E - :", : ... 5 25 z w ~ 0 0 w ()

< ..J -5 -25 D.. en C -10 -50

-15 -75 0 5 10 15 20 25 30 35

TIME (sec)

§ 1.6

z 5% DAMPING 0 TABLE MOTION i= 1.2 < . ACTUAL a: w ..J w 0.8 (,) (,)

< ..J < 0.4 a: ... () W D..

0.0 _ ... _ .. -- --- ---- .. --en 0 1 2 3 4 5

PERIOD (sec)

Figure 3-22 Acceleration, Velocity and Displacement Histories and Response Spectrum ofEI Centro (Vertical) - Ground in Prototype Scale

3-35

-0 CJ) en ....... E E ->-... (5 0 ...J w >

Page 68: Study of Seismic Isolation Systems for Computer Floors

2

-2 z 1 0 ~ e( a: 0 w ...J W 0 0 -1 e(

-2 0 5 10 15 20 25 30 35

80 400 DISPLACEMENT

e- . VELOCITY -,', 0 E ,',

200 CD 40 .... - ::: ~ t/)

I- ...... z E w E ::E -w 0 .... '. 0 >-0 : ~: l-e( :;;: (3 ...J ,',' 0 ,., D.. ...J C/) -40 -200w £5 >

-80 -400 0 5 10 15 20 25 30 35

TIME (sec)

- 3.5 2 z 3.0 5% DAMPING 0 ~ T ABLE MOTION e( 2.5 ....... ACTUAL a: w ...J 2.0 w 0 0 1.5 e(

...J 1.0 e(

a: I-

0.5 0 w D.. C/) 0.0

_ ... -._- _ ..... _---, .. - .

0 1 2 3 4 5 PERIOD (sec)

Figure 3-23 Acceleration, Velocity and Displacement Histories and Response Spectrum of Pacoima Dam (Vertical) - Ground in Prototype Scale

3-36

Page 69: Study of Seismic Isolation Systems for Computer Floors

3.7 Instrumentation

The behavior of the Floor System and the Cabinet was monitored by load cells,

accelerometers and displacement transducers. The instrumentation is shown in Figures

3-24 to 3-27. The 47 monitored channels are listed in Table 3-IY.

Table 3-IV : List of Channels (with reference to Figures 3-24 to 3-27)

CHANNEL NOTATION INSTRUMENT RESPONSE MEASURED

1 ALAT ACCL Table Horizontal Accel.

2 AVRT ACCL Table Vertical Accel.

3 ABLH ACCL Deck Horizontal Accel.- South Side Center

4 ABLV ACCL Deck Vertical Accel.- South Side Center

5 AVLS ACCL Load Cell Vertical Accel.- South East

6 AVLN ACCL Load Cell Vertical Acce1.- North East

7 AWFE ACCL Base Floor Horizontal Accel.- South East

8 AWFW ACCL Base Floor Horizontal Accel.- North East

9 ARFH ACCL Raised Floor Horizontal Accel.- South Side Center

10 ARFV ACCL Raised Floor Vertical Accel.- South Side Center

11 ACBH ACCL Base of Cabinet Horizontal Accel.- North Center

12 ACMH ACCL C.M. of Cabinet Horizontal Accel.- North Center

13 AC2H ACCL 2nd Level of Cabinet Horizontal Accel.- North Center

14 AC3H ACCL 3rd Level of Cabinet Horizontal Accel.- North Center

15 ACTH ACCL Top of Cabinet Horizontal Accel.- North Center

16 ACSV ACCL Top of Cabinet Vertical Accel.- South Center

17 ACNV ACCL Top of Cabinet Vertical Accel.- North Center

18 ACOP ACCL Top of Cabinet out of Plane Hor. Acce1.-East Center

19 DLAT DT Table Horizontal Displ.

20 DVRT DT Table Vertical Displ.

21 DBLC DT Deck Total Horizontal Displ.-South Side Center

22 DBSW DT Bearing Horizontal Displ.- South West

23 DBSE DT Bearing Horizontal Displ. - South East

24 DBNW DT Bearing Horizontal Displ.- North West

25 DBNE DT Bearing Horizontal Displ.- North East

3-37

Page 70: Study of Seismic Isolation Systems for Computer Floors

Table 3-IV : List of Channels (with reference to Figures 3-24 to 3-27)

CHANNEL NOTATION INSTRUMENT RESPONSE MEASURED

26 DWFW DT Base Floor Total Horizontal Displ.- South West

27 DRFW DT Raised Floor Total Horizontal Displ.- South West

28 DCBW DT Base of Cabinet Total Horizontal Displ.- South West

29 DCMW DT C.M. of Cabinet Total Horizontal Displ.- South West

30 DCTW DT Top of Cabinet Total Horizontal Displ.- South West

31 DCTE DT Top of Cabinet Total Horizontal Displ.- South East

32 DTDW DT Axial Damper Displ.- West Side

33 DTDE DT Axial Damper Displ.- East Side

34 LCIN LOAD CELL Axial Bearing Force- North East

35 LC2N LOAD CELL Axial Bearing Force- North West

36 LC3N LOAD CELL Axial Bearing Force- South West

37 LC4N LOAD CELL Axial Bearing Force- South East

38 LCISX LOAD CELL Shear Bearing Force in South-North Dir.- North East

39 LC2SX LOAD CELL Shear Bearing Force in South-North Dir.- North West

40 LC3SX LOAD CELL Shear Bearing Force in South-North Dir.- South West

41 LC4SX LOAD CELL Shear Bearing Force in South-North Dir.- South East

42 LCISY LOAD CELL Shear Bearing Force in West-East Dir.- North East

43 LC2SY LOAD CELL Shear Bearing Force in West-East Dir.- North West

44 LC3SY LOAD CELL Shear Bearing Force in West-East Dir.- South West

45 LC4SY LOAD CELL Shear Bearing Force in West-East Dir.- South East

46 LCDW LOAD CELL Axial Force in Damper- West Side

47 LCDE LOAD CELL Axial Force in Damper- East Side

ACCEL= Accelerometer, DT= Displacement Transducer

3-38

Page 71: Study of Seismic Isolation Systems for Computer Floors

W

I W

10

• TR

ANSV

ERSE

D

IREC

TIO

N

ACCE

LERO

MET

ER

t VER

TICA

L D

IREC

TIO

N

ACCE

LERO

MET

ER

___ H

ORI

ZON

TAL

DIR

ECTI

ON

AC

CELE

ROM

ETER

0.7

6

r---

1 AC

SVI

I AC

NV

ACOP

i'

ACTH

___ A

C3H

___ A

C2H

---A

CMH

tARFV

ARFH

h

:J

i...

AC

BH

11K

~~~5--

!fooo:

::::::

:::::a

=ifA\l

ft'

\I,

AU

' ..

. ;

....

....

:::::>

','

AVRT

LA

LA

T

I 1.88

SOUT

H NO

RTH

0.6

0

3.0

0

6.0

0

. t

_ TE

STIN

G

DIR

ECTI

ON

S

I j6

0

• HO

RIZO

NTAL

D

IREC

TIO

N

ACCE

LERO

MET

ER

I V

ERTI

CAL

DIR

ECTI

ON

AC

CELE

ROM

ETER

__

_ TRA

NSVE

RSE

DIR

ECTI

ON

AC

CELE

ROM

ETER

ACSV

tCNV

~--.£ICOP

~C.3!:!

AC o2H

. AC

MH

I 1.88 I

0.36

,n:

::Jru~

~I:~JO

I7 1.

00

10.0~

0.3

8

I r=

-=-'

""1

" ! "~I

1 I

ABLH

I

1.85

-:r

WES

T EA

ST

Fig

ure

3-24

Loc

atio

n of

Acc

eler

omet

ers

(Uni

ts:

m)

Page 72: Study of Seismic Isolation Systems for Computer Floors

W

I .l>.

o SO

UTH

~HORIZONTAL

DIR

ECTI

ON

D

ISP,

TR

ANSD

UCER

DCTE

D

CT\

I

DC

MII

_

0,7

6

1.

I , .. I

,.. ..,,

" 6

,00

_ t

. TE

STIN

G

DIR

ECTI

ON

S

-:1.

~

• HO

RIZO

NTAL

D

IREC

TIO

N

DIS

P,

TRAN

SDUC

ER

DCT

II,

,DCT

E

DCM

II 1.

IlB

0~6

J~2

SLDBNE

-J~:~~

l:OD

' nB

SE 1

0

,3B

/

c'--

--=-

J 1

C~'::

J J'

IIE

ST

EAST

Fig

ure

3-25

Loc

atio

n o

f Dis

plac

emen

t T

rans

duce

rs (

Uni

ts:

m)

Page 73: Study of Seismic Isolation Systems for Computer Floors

l70 1.88

OCTW

OCMW

i I I

DCBW

1 WEST

ACSV ACNV

... ACTH

"..

( ) AC3H ( )

AC2H

AatH

A~H ... 0.56

ACOP -OCTE

LEVEL 3

LEVEL 2

LEVEL 1 (C.t.4.)

I.. 1 EAST

ACSV

DCTE I -DCTW

OCt.4W -

DCBW -I..

1 SOUTH

ACOP -

...<=!==.

\\\\\\ ~

0.76

.. t

ACNV

I - ACTH

\\\\\\ - r-----:: AC3H

- f---...t AC2H

- ACMH

ACBH -1 NORTH

TESTING DIRECTIONS

Figure 3-26 Instrumentation on Cabinet (Units: m)

3-41

Page 74: Study of Seismic Isolation Systems for Computer Floors

ACNV

ACSV

t ~CTW..,..,-______ -+-_~

DCTE TOP LEVEL -.--~---~~~~~~

ACOP

0.70

LEVEL "')L----~+_---_v

0.16

1.88 0.10

0.92

SOUTH

DCBN ---/­

/'

0.76 ~v _________ ~v 1 1

! TESTING DIRECTIONS

NORTH

ACTH

AC3H

AC2H

ACMH

Figure 3-27 Three Dimensional View of Instrumentation on Cabinet (Units: m)

3-42

Page 75: Study of Seismic Isolation Systems for Computer Floors

SECTION 4

TEST RESULTS AND INTERPRETATION

4.1 Test Results

The recorded peak response in each test is presented in Appendix A. This appendix

contains tables, each one of which corresponds to a specific input motion and length scale

of experiment. Each table compares the response of the system with the three isolation

systems and without isolation. The tables contain the recorded peak table motion and the

following recorded peak values of response:

(1) Horizontal and vertical acceleration of Raised Floor.

(2) Horizontal acceleration of center of mass (level 1) of Cabinet.

(3) Horizontal acceleration of flexible internal components at levels 2 and 3 (see

Figure 3-26)

(4) Horizontal and vertical acceleration of top of Cabinet.

(5) FPS bearing horizontal displacement.

(6) Total horizontal displacement of Raised Floor (that is, displacement of Raised

Floor with respect to a stationary frame).

(7) Horizontal displacement of Raised Floor and top of Cabinet with respect to the

Raised Floor.

4-1

Page 76: Study of Seismic Isolation Systems for Computer Floors

4.2 Comparison of Behavior of Isolated and Non-isolated Computer Floor

The results of Appendix A demonstrate that seismic isolation offers significant benefits. In

all cases of strong excitation (Taft 7th floor, EI Centro 7th floor, Pacoima, Bellcore and

IBM inputs) the non-isolated Cabinet underwent rocking motion, resulting in large

accelerations. These accelerations were of the order of 2 to 4 g, thus sufficiently strong to

cause interruption of operation in computers and damage to equipment.

Rocking of the Cabinet was also observed in tests of the isolated floor system in the

Bellcore input at length scale of 1. This case corresponds to an isolation system period in

prototype scale of 1.5 sees which is apparently not long enough to provide effective

isolation in long period motions. For example, an inspection of the response spectra of

Figures 3 -17 to 3 -19 reveals large spectral values at period of about 1 sec. Furthermore,

uplift and rocking of the Cabinet on the isolated Raised Floor was observed in the

Pacoima input with vertical component. This has been the result of the vertical table

motion, which exceeded 1 g in peak value (see Appendix A). The actual earthquake had

vertical acceleration of 0.71 g (see Table 3-11), however the shake table could not

accurately simulate this component. This was clearly evident during testing when the

Cabinet and Base Floor could be seen to momentarily separate from the Raised Floor and

isolation bearings, respectively.

We proceed to present a comprehensive comparison of isolated and non-isolated Cabinet

response at length scales of 2 ,3 and 4 and excluding the unsuccessfully run tests with

the vertical component of Pacoima input. Figures 4-1 to 4-10 present profiles of

4-2

Page 77: Study of Seismic Isolation Systems for Computer Floors

recorded peak acceleration of the Cabinet for all tested isolation systems. The profiles

show the recorded acceleration at the shake table, Raised Floor, center of mass (level 1) of

Cabinet and top of Cabinet. It should be noted that the three length scales correspond, in

prototype scale, to three different isolation system periods (see Table 3-III). The profiles

clearly demonstrate that the isolation systems achieve substantial reductions of

acceleration in comparison to the non-isolated floor system.

Figures 4-1 to 4-10 provide also information to compare the behavior of the three

isolation systems. The peak acceleration response of the Cabinet with isolation system 3

(that is the system with friction coefficient fmax = 0.13 and damping ratio of 0.35)

appears to be the least among the three isolation systems, although the differences are

relatively small.

A more enlightening comparison of the behavior of the three isolation systems is presented

in Figures 4-11 to 4-30, where "floor spectra" for the recorded motions at the center of

mass and top of Cabinet are shown. The spectra show the peak acceleration response of a

small weight (so that interaction with the Cabinet is negligible), lightly damped oscillator

(damping ratio = 2 %) with frequency up to 100 Hz if it were attached to various parts of

the Cabinet. Thus, the spectra present information on the response of small internal

components of the Cabinet, as for example in electronic components of a computer. The

figures included also, for comparison, the floor spectra of the non-isolated Cabinet and of

shake table.

4-3

Page 78: Study of Seismic Isolation Systems for Computer Floors

All floor spectra contain peaks at the frequency of 10Hz. The origin of this frequency

could not be determined. Concentrating first on the results for length scale of 2

(isolation system period in prototype scale equal to 2.12 secs) we observe:

(1) In weak seismic excitation (such as Taft input and EI Centro - ground input) the

high friction in isolation system 1 generates higher spectral accelerations than the

lower friction, viscously damped isolation systems 2 and 3.

(2) In strong seismic excitation the three isolation systems exhibit similar behavior and

general conclusions are difficult to arrive at. However, it is clear that in the

artificial Bellcore and IBM inputs the floor spectra for the isolated Cabinet are

substantially lower than those of the non-isolated Cabinet and that isolation system

3 exhibits best performance.

For length scale of 4 (isolation system period in prototype scale equal to 3 secs) we

observe:

(1) In weak seismic excitation (Taft input and EI Centro - ground input) the three

isolation systems have comparable performance.

(2) In strong seismic excitation all isolation systems show a substantial reduction of

spectral response in comparison with the non-isolated system. Particularly, the

lower friction, viscously damped isolation system 3 shows a better performance

than the higher friction isolation system 1.

4-4

Page 79: Study of Seismic Isolation Systems for Computer Floors

This behavior of the long period (3 sees in prototype scale) isolation systems is easily

interpreted. The isolation system period is sufficiently long to avoid the long period

strong components of the simulated floor motions (see spectra of Figures 3-16 to 3-20).

All tested isolation systems have very large energy dissipation capability, so that they

appear ineffective in weak excitation. Under these conditions, the presence of high

damping (either frictional or viscous) is detrimental to the isolation mechanism. However,

in strong excitation the isolation systems undergo larger displacements and isolation

becomes effective. As expected, isolation system 3 shows better performance than

isolation system 1 because high frictional damping has been exchanged for a combination

of lower frictional damping and viscous damping. At zero velocity, where the frictional

force abruptly changes direction,high frequency motion is generated in the structure

above the isolation system. System 3 has friction force at zero velocity ([min W , where

W=weight) equal to about one half of that of system 1 (see Figure 3-5). Thus, less high

frequency response is generated, leading to lower floor spectral values.

The better performance of isolation system 3 is further illustrated in Figure 4-31 which

presents the recorded peak acceleration of the flexible internal component at level 3 (see

Section 3.2 , Figure 3-2) for various earthquakes. The results for length scales of 2 and

4 are presented. Had been possible to test with lower friction than achieved in isolation

systems 2 and 3, even better performance could be achieved. This is analytically

demonstrated in Section 5 .

4-5

Page 80: Study of Seismic Isolation Systems for Computer Floors

4.3 Displacement Demand in Isolation System

Having determined that effective isolation requires isolation system period, in prototype

scale, of the order of 3 secs, it is important to establish the displacement demand in the

isolation bearings. It might be expected to be large because of the long isolation system

period.

An inspection of the results of Appendix A reveals that the peak bearing displacement, in

prototype scale occurs for the EI Centro 7th floor input for length scale of 4 and isolation

system 3. It is only 134 mm. This is small and, apparently, the result of the high energy

dissipation capacity of the tested systems. FPS bearings to accommodate this

displacement demand would be approximately 400 mm by 400 mm in plan dimension.

A more detailed presentation of bearing displacement demand is given in Figures 4-32 to

4-34. Here the recorded bearing displacement in all tests has been extrapolated to

prototype scale and plotted as function of length scale. It should be noted that length

scale corresponds to isolation system period as noted in the figure captions. Clearly,

increases in isolation system period are not accompanied by corresponding increases in

bearing displacement. Rather, bearing displacements appear only marginally affected by

the isolation system period. This is the result of high energy dissipation capability of the

tested isolation systems.

4-6

Page 81: Study of Seismic Isolation Systems for Computer Floors

z o f= Ci5 o CL

Z o f=

~ CL

CAB. TOP

CAB. C.O.t.!.

R. FLOOR

CAB. TOP

CAB.C.O.t.!.

R. FLOOR

Figure 4-1

0.0 0.1 02 0.3 0.4

MAX. HORIZONTAL ACCELERATION (g)

0.0 0.1 02 0.3 0.4

MAX. HORIZONTAL ACCELERATION (g)

* FIXED

B ISOL.l

-I's ISOL.2

e ISOL.3

Length Scale=2

0.5

* FIXED

B ISOL.1

e ISOl.3

Length Scale=4

0.5

0.6

0.6

Profiles of Peak Acceleration Along Height of Cabinet in Taft N21E Ground Horizontal -Vertical Input

4-7

Page 82: Study of Seismic Isolation Systems for Computer Floors

Z 0 f= (jj 0 c..

z o f= (jj o c..

Z o f= (jj o c..

CAB. TOP r I

CAB.C.O.M. I I

'~t TABLE

0.0 0.1

CAB. TOP

CAB.C.O.M.

R. FLOOR

02 0.3 0.4

MAX. HORIZONTAL ACCELERATION (g)

* FIXED

a ISOL.l

-tr ISOL. 2

~ ISOL.3

Length Scale=2

0.5

* FIXED

a ISOL.l

-tr ISOL.2

Length Scale=3

0.6

l B ISOL.3

TABLE ~ L-~~-L~ __ L-~~-L-L~ __ ~~~-L~ __ L-~~-L~~ __ ~

0.0 0.1

CAB. TOP

CAB.C.O.M.

R. FLOOR

0.0 0.1

02 0.3 0.4

MAX. HORIZONTAL ACCELERATION (g)

02 0.3 0.4

MAX. HORIZONTAL ACCELERATION (g)

0.5

* FIXED

a ISOL.l

~ ISOL.3

Length Scale=4

0.5

0.6

0.6

Figure 4-2 Profiles of Peak Acceleration Along Height of Cabinet in Taft N21E 5th Floor Horizontal -Vertical Input

4-8

Page 83: Study of Seismic Isolation Systems for Computer Floors

Z o i=

~

z o i= Ci5 o a.

z o i= Ci5 o a.

CAB. TOP

CAB.C.O.M.

R. FLOOR

CAB. TOP

CAB.C.O.M.

R. FLOOR

CAB. TOP

CAB.C.O.M.

R. FLOOR

Figure 4-3

0.0 0.4 0.8 12

MAX. HORIZONTAL ACCELERATION (g)

0.0 0.4 0.8 12

MAX. HORIZONTAL ACCELERATION (g)

0.4

MAX. HORIZONTAL ACCELERATION (g)

"" FIXED

B ISOL.1

-t" ISOL.2

B ISOL.3

Length Scale=2

1.6

"" AXED

B1SOL.l

-t"ISOL.2

BlSOL.3

Length Scale=3

1.6

"* AXED

B 1SOL1

e 1SOL3

Length Scale=4

2.0

2.0

Profiles of Peak Acceleration Along Height of Cabinet in Taft N21E 7th Floor Horizontal -Vertical Input

4-9

Page 84: Study of Seismic Isolation Systems for Computer Floors

z o i= iii o a.

z o i= iii o a.

CAB. TOP

CAB.C.O.M.

R. FLOOR

CAB. TOP

CAB.C.O.M.

R. FLOOR

0.0 02 0.4 0.6

MAX. HORIZONTAL ACCELERATION (g)

* FIXED

S ISOL.1

-tr ISOL. 2

B ISOL.3

Length Scale=2

0.8

"* FIXED

S ISOL.1

-tr ISOL. 2

B ISOL.3

Length Scale=3

1.0

TABLE L~--,_~--'-_~~~~-'--~_...i......--'-_-'----~_~.....L-----'_~--,_-'----1

z o i= iii o a.

CAB. TOP

CAB.C.O.M.

R.FLooR

Figure 4-4

0.0 02 0.4 0.6

MAX. HORIZONTAL ACCELERATION (g)

0.0 02 0.4 0.6

MAX. HORIZONTAL ACCELERATION (g)

0.8 1.0

* FIXED

S ISOL.1

B ISOL.3

Length Scale=4

0.8

Profiles of Peak Acceleration Along Height of Cabinet in EI Centro SOOE Ground Horizontal -Vertical Input

4-10

Page 85: Study of Seismic Isolation Systems for Computer Floors

z o F ii5 o 0..

CAB. TOP

CAB. C.O.M.

R. FLOOR

CAB. TOP

CAB.C.O.M.

R. FLOOR

Figure 4-5

0.0 0.5 1.0 1.5

MAX. HORIZONTAL ACCELERATION (g)

0.0 0.5 1.0 1.5

MAX. HORIZONTAL ACCELERATION (g)

0.0 0.5 l~ l~

MAX. HORIZONTAL ACCELERATION (9)

"* FIXED

8 ISOL.l

-tr ISOL. 2

B ISOL.3

Length Scale=3

2.0

"* FIXED

81S0L.l

B ISOL.3

Length Scale=4

2.0

2.5

2.5

Profiles of Peak Acceleration Along Height of Cabinet in EI Centro SOOE 5th Floor Horizontal-Vertical Input

4-11

Page 86: Study of Seismic Isolation Systems for Computer Floors

Z o i=

~ Cl.

Z o i=

~ Cl.

z o i=

~ Cl.

CAB. TOP

CAB.C.O.M.

R. FLOOR

CAB. TOP

CAB.C.O.M.

. R. FLOOR

CAB. TOP

CAB.C.O.M.

R.FLooR

Figure 4-6

0.0 0.5 1.0 1.5 2.0

MAX. HORIZONTAL ACCELERATION (g)

0.0 0.5 1.0 1.5 2.0

MAX. HORIZONTAL ACCELERATION (g)

0.0 0.5 1.0 1.5 2.0

MAX. HORIZONTAL ACCELERATION (g)

'* FIXED

e ISOl.l

-f:sISOL2

e ISOI..3

Length Scale=2

2.5

'* FIXED

e ISOL.l

-tr ISOL.2

e ISOL.3

Length Scale=3

2.5

'* FIXED

e ISOL.l

e ISOL3

Length Scale=4

2.5

3.0

3.0

3.0

Profiles of Peak Acceleration Along Height of Cabinet in EI Centro SOOE 7th Floor Horizontal-Vertical Input

4-12

Page 87: Study of Seismic Isolation Systems for Computer Floors

z o i= Cii o (L

z o i= Cii o (L

z o i=

~ (L

CAB. TOP

CAB. C.O.M.

R. FLOOR

CAB. TOP

CAB.C.O.M.

R. FLOOR

CAB. TOP

CAB.C.O.M.

R. FLOOR

Figure 4-7

0.0 0.5 1.0 1.5 2.0

MAX. HORIZONTAL ACCELERATION (g)

0.0 0.5 1.0 1.5 2.0

MAX. HORIZONTAL ACCELERATION (g)

0.0 0.5 1.0 1.5 2.0

MAX. HORIZONTAL ACCELERATION (g)

:lK: FIXED

e ISOLI

-ts ISOl. 2

~ ISOL.3

Length Scale=2

2.5

:lK: FIXED

e ISOLI

-ts 1501..2

~ 1501..3

Length Scale=3

2.5

:lK: AXED

e 1501..1

~ ISOL.3

Length Scale=4

2.5

3.0

3.0

3.0

Profiles of Peak Acceleration Along Height of Cabinet in Pacoima Dam S74W Ground Horizontal Input

4-13

Page 88: Study of Seismic Isolation Systems for Computer Floors

Z o f= ii.i o a..

z o f= ii.i o a..

z o f= ii.i o a..

CAB. TOP

CAB. C.O.lA.

R. FlOOR

CAB. TOP

CAB.C.O.lA.

R. FLOOR

TABLE

CAB. TOP

CAB.C.O.lA.

R. FLOOR

TABLE

Figure 4-8

0.0 0.5 1.0 1.5 2.0

MAX. HORIZONTAL ACCELERATION (g)

0.0 0.5 1.0 1.5 2.0

MAX. HORIZONTAL ACCELERATION (g)

0.0 0.5 1.0 1.5 2.0

MAX. HORIZONTAL ACCELERATION (g)

"* FIXED

B ISDL.l

-ts ISOL.2

B ISOL.3

Length Scale=2

2.5

"* FIXED

B ISOL.l

-ts ISOL. 2

B ISOL.3

Length Scale=3

2.5

"* FIXED

B ISOL.l

B ISOL.3

Length Scale=4

2.5

3.0

3.0

3.0

Profiles of Peak Acceleration Along Height of Cabinet in Bellcore Horizontal -Vertical Input

4-14

Page 89: Study of Seismic Isolation Systems for Computer Floors

Z o t= iii o CL

Z o t= iii o CL

CAB. TOP

CAB. C.O.M.

R. FlOOR

CAB. TOP

CAB.C.O.M.

R. FlOOR

0.0 0.5 1.0 1.5

MAX. HORIZONTAL ACCELERATION (g)

I

"* FIXED

B ISOl.l

-ft ISOl. 2

B ISOl.3

Length Scale=2

"* FIXED

B ISOl.l

-ft ISOl.2

B ISOl.3

I Length Scale=3

TABLE Lt~~ __ L-~~~-L~~ __ L-~~~-L~~ __ L-~~~-L~~ __ '~

z o t= iii o CL

CAB. TOP

CAB. C.O.M.

R. FlOOR

Figure 4-9

0.0 0.5 1.0 1.5 2.0 2.5

MAX. HORIZONTAL ACCELERATION (g)

0.0 0.5 1.0 1.5

MAX. HORIZONTAL ACCELERATION (g)

"* FIXED

B ISOl.l

B ISOL.3

Length Scale=4

2.0 2.5

Profiles of Peak Acceleration Along Height of Cabinet in mM Level-l Horizontal-Vertical Input

4-15

Page 90: Study of Seismic Isolation Systems for Computer Floors

~ l= Cii o a..

z o l=

~ a..

~ l=

~ a..

CAB. TOP

CAB.C.O.M.

R. FLOOR

TABLE

CAB. TOP

CAB.C.O.M.

R. FLOOR

CAB. TOP

CAB.C.O.M.

R. FLOOR

0.0 0.5

0.0 0.5

0.0 0.5

1.0 1.5 2.0 2.5

MAX. HORIZONTAL ACCELERATION (g)

1.0 1.5 2.0 2.5

MAX. HORIZONTAL ACCELERATION (g)

1.0 1.5 2.0 2.5

MAX. HORIZONTAL ACCELERATION (g)

71< FIXED

B ISOL.l

-f:r ISOL.2

B ISOL.3

Length Scale=2

3.0

71< FIXED

B ISOL.l

-f:r ISOL.2

B ISOL.3

Length Scale=3

3.0

71< FIXED

B ISOL.l

B ISOL.3

Length Scale=4

3.0

3.5

3.5

3.5

Figure 4-10 Profiles of Peak Acceleration Along Height of Cabinet in mM Level-2 Horizontal-Vertical Input

4-16

Page 91: Study of Seismic Isolation Systems for Computer Floors

FREQUENCY (Hz)

CENTER OF MASS OF CABINET DAMPING=2%

___ 2.5 - - FIXED ~ - ISOL.1 Z ...... ISOL.2 o - - ISOL.3

~ 2.0

II ill ....J ill o 1.5 () <{ ....J <{ II 1.0 I-() ill a.. _TABLE (f) 0.5

FREQUENCY (Hz)

10 100

------

10 100

Figure 4-11 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Taft N21E Ground Horizontal-Vertical Input and Length Scale of2

4-17

Page 92: Study of Seismic Isolation Systems for Computer Floors

7.0 ,----------.-.--,---.-r-rrr-,------,---.--,--,-----,-,-rn,------,---.----,.--,-----,-,-"l

6.5

6.0

9 5.5 Z o 5.0 i= « 4.5 a: ~ 4.0 LU o 3.5 o « 3.0 ...J

~ 2.5

t; 2.0 LU

TOP OF CABINET DAMPING=2%

- - FIXED - ISOL.l ······ISOL2 - - ISOL.3

Cl.. 1.5 -TABLE (f)

1.0

0.5

3.5

Z 3.0 o i= « a: 2.5 LU ...J LU o 2.0 o « ...J « 1.5 a: I­o LU 1.0 Cl..

FREQUENCY (Hz)

CENTER OF MASS OF CABINET DAMPING=2%

- - FIXED - ISOL.l ...... ISOL.2 - - ISOL.3

(f) _TABLE

0.5

FREQUENCY (Hz)

I I

I ~ I

------

Figure 4-12 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Taft N21E 5th Floor Horizontal-Vertical Input and Length Scale of2

4-18

Page 93: Study of Seismic Isolation Systems for Computer Floors

10.0

9.0

§ 8.0

Z 0 i=

7.0

« a: 6.0 W --1 W () 5.0 () « --1 4.0 « a: I- 3.0 () W 0.. 2.0 (f)

1.0

0.0 0

5.5

.--.. 5.0 9 Z 4.5

~ 4.0 ~ a: w 3.5 --1 W () 3.0 ()

« 2.5 --1 « a: 2.0 I-() W 1.5 0.. (f) 1.0

0.5

TOP OF CABINET DAMPING=2%

- - FIXED -ISOL.l ...... ISOL.2 - - ISOL.3

, II II

I I \ Ihl

I' I~

-TABLE

FREQUENCY (Hz)

CENTER OF MASS OF CABINET DAMPING=2%

- - FIXED -ISOL.l

ISOL.2 - - ISOL.3

__ TABLE

FREQUENCY (Hz)

11 II II II II I I

I

I I j

II I II I J I I I ~ II

(

10

10

,'- 1 I I I

.. / \

I \

\ , .....

0....:... ~_. ______

..... ,

100

100

Figure 4-13 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Taft N21E 7th Floor Horizontal-Vertical Input and Length Scale of2

4-19

Page 94: Study of Seismic Isolation Systems for Computer Floors

3.5

Z 3.0 o ~ a: 2.5 W ...J W o 2.0 o « ...J « 1.5 a: I­o W 1.0 a.. (f)

0.5

2.5

z o i= 2.0 L « a: w ...J W U 1.5 U « ...J « g: 1.0

U w a.. (f)

0.5

TOP OF CABINET DAMPING=2%

- - FIXED - ISOL.1 ...... ISOL.2 - - ISOL.3

-TABLE

I I ,

FREQUENCY (Hz)

CENTER OF MASS OF CABINET DAMPING=2%

- - FIXED - ISOL.1 ------ ISOL.2 - - ISOL.3

_TABLE

I ft II II II /I ,," Ii' I I I I, , I

l' " J ,', ,

FREQUENCY (Hz)

, , ~, "-

\'.:...:-:-:--------=1

- _ .. ..;,.;: ......... --...

Figure 4-14 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in EI Centro SOOE Ground Horizontal-Vertical Input and Length Scale of 2

4-20

Page 95: Study of Seismic Isolation Systems for Computer Floors

5.0

4.5

§4.0

Z Q 3.5 I-« ffi 3.0 ....J W () 2.5 () « ....J 2.0 « a: I- 1.5 () w a.. 1.0 U)

0.5

0.0

-.2.5 0> ---z o ~ 2.0

a: W ....J W () 1.5 () « ....J « a: 1.0 I-() W a.. U) 0.5

0

TOP OF CABINET II DAMPING=2% I \ II

- - FIXED I \ 'I

- ISOl.l I \ '\ ...... ISOl.2 ' \ ~ , ( \ - - ISOl.3

I \ \ I I I

_TABLE

FREQUENCY (Hz)

CENTER OF MASS OF CABINET' I DAMPING=2% I I

- - FIXED - ISOL.l ...... ISOL.2 - - ISOL.3

I I I \

FREQUENCY (Hz)

~ :, \ . \ E I

'\ \ III I I \',1 I'!! I '( Ii I \

~ I Il I

'\ I i I I

" I i I I I \ I 1 l \ I I I I

\ \

\ , , " --

10 100

10 100

Figure 4-15 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in EI Centro SOOE 5th Floor Horizontal-Vertical Input and Length Scale of 2

4-21

Page 96: Study of Seismic Isolation Systems for Computer Floors

8.0 ,---------,,---,.----..----r-,--,..,...,----,-----,-----.----r-,---,---.-r---,-------,--------,,--,-r-T---.-"l

7.5

7.0

0 6.5

Z 6.0 o i= 5.5

« ex: 5.0

~ 4.5 W 0 4 .0 o « 3.5 ....J « 3.0 ex: I- 2.5 o W 2.0 a.. C/) 1.5

1.0

0.5

TOP OF CABINET DAMPING=2%

- - FIXED - ISOL.1 ...... ISOL.2 - - ISOL.3

-TABLE

I~

I \ \ \

~ II I I I I \ I I 1\

I i '\ \ 1 \ 1/1

/ 1:\1 \

I {! \ , , ,

\ , , ./ ./

0.0 0l..---'---~=------.t-----'----'--'---L.l-------'----'--'----'-----L-I---'---W10----'----'---L--'--'-.L..L-'-'1 00

5.5

__ 5.0

-9 Z 4.5 o ~ 4.0

ex: W 3.5 ....J W 0 3.0 U « 2.5 ....J « ex: 2.0 I-U W 1.5 (L

U) 1.0

0.5

FREQUENCY (Hz)

CENTER OF MASS OF CABINET DAMPING=2%

- - FIXED - ISOL.1 ...... ISOL.2 - - ISOL.3

\ ,I

__ TABLE

FREQUENCY (Hz)

Figure 4-16 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in EI Centro SOOE 7th Floor Horizontal-Vertical Input and Length Scale of 2

4-22

Page 97: Study of Seismic Isolation Systems for Computer Floors

8.5 ,-----,-------r----.----,---.--,-,-,-,..------r--.----.-.--.-,.,-,.--,.--,---,----,.-,r-r'"

8.0

7.5

05 7.0

~ 6.5

o 6.0 i= « 5.5 a: W 5.0 -...l W 4.5 () 0 4.0 « -...l 3.5

~ 3.0 o 2.5

g: 2.0

if) 1.5

1.0

0.5

TOP OF CABINET DAMPING=2%

- - FIXED - ISOl.1 .. '''. ISOL.2 - - ISOL.3

-TABLE

I ~ " ,I " ,I

" " , "I , , II. I , :':' , :,' I ;: , ;".: '

'I I ::: , , : "

; , : .J"-) ;

/ . ' 1', .. "

I "

~

" " 1\ 'I 'I ,

\ '\ \ '\ \ , \

\ I \ I I \ I, \ \ \

\

---

0.0 '--_~'__ ___ ~=-l-.l.--'--.L __ ~_---'---'------'---'--L..Ll..--L __ ---'-_-'---'----'---L-"-..L.LJ

o FREQUENCY (Hz)

CENTER OF MASS OF CABINET 4.5 DAMPING=2%

94.0

Z Q 3.5 I-« a: w 3.0 -...l W () 2.5 o « -...l 2.0 « a: 5 1.5

W

fu 1.0

0.5

- - FIXED -ISOL.1 ...... 'SOL.2 - - ISOL.3

--TABLE

\

'I

" " " " , '

" , , ,;' , ,:\

,I ,: ; " ,! '

_ ' ~ '1 /. .... I

, 1\

I

FREQUENCY (Hz)

10 100

10 100

Figure 4-17 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Pacoima Dam S74W Ground Horizontal Input and Length Scale of2

4-23

Page 98: Study of Seismic Isolation Systems for Computer Floors

9.0

§ B.O

z o 7.0

~ ffi 6.0 ...J W U 5.0 U « ...J 4.0 « 0: I- 3.0 o w &3 2.0

1.0

5.5

_5.0 9 Z 4.5 o ~ 4.0

0: W 3.5 ...J W U 3.0 o « 2.5 ...J « 0: 2.0 I-U W 1.5 a.. C/) 1.0

0.5

TOP OF CABINET DAMPING=2%

- - FIXED - ISOl.1 ...... ISOL.2 - - ISOL.3

-TABLE I

I

I ~ I' I' I \ ,

'r I I 'I' , 1\ : \

~ , 1\ \ I

I, I \ I' I, I I, I' I, I I II, , ~ , I'

I \I ~ n ~I I ~ ;:\ I\~U I .: ~ " I I .... I ii ::: I I I ,

",(,111 I' I I ,\ ,

'I ~ I," I, I \ ~"\

, , , , !\ \ ; .... ' .' ,

'- =--=-----------:j

FREQUENCY (Hz)

CENTER OF MASS OF CABINET DAMPING=2%

- - FIXED - ISOL.1 ...... ISOL.2 - - ISOL.3

--TABLE

I ,

H '/ 11 1 j

~ I, I I I I,

'l ~, : I : I i I i I .

I I I

I

FREQUENCY (Hz) 10

I, 1./ \ ,

\ \

' ......

100

Figure 4-18 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Bellcore Horizontal-Vertical Input and Length Scale of2

4-24

Page 99: Study of Seismic Isolation Systems for Computer Floors

10.0

9.0

§ 8.0

Z 0 7.0 i= « a::: 6.0 W ..-I W () 5.0 () « ..-I 4.0 « a::: I- 3.0 () w a.. 2.0 (f)

1.0

0.0

5.5

........ 5.0 -9 Z 4.5 o ~ 4.0

a::: W 3.5 ..-I ill () 3.0 ()

« 2.5 ...J « a::: 2.0 I-() W 1.5 a.. (f) 1.0

0.5

0

TOP OF CABINET ~

DAMPING=2% "

" - - FIXED ," - ISOl.1 Ii , ...... ISOL.2 , ' - - ISOL.3 , , I ,

" I " , ~~I 'n " ~ I ~ , , " t '" j I' ,',', , ' , \,. , VII \, /III, \ \ "

/V, \ \' I, , , ,'\' " , " ,,' , l' , I III,

~

_TABLE I I

I ,,-

10 FREQUENCY (Hz)

CENTER OF MASS OF CABINET DAMPING=2%

- - FIXED - ISOL.1

ISOL.2 - - ISOL.3

-TABLE

-, , \

\ \

\ , ---

100

l

---...... " -" ;.,:..:.:.--... : ... :-..:.,:-:..:.--...:....---

10 100 FREQUENCY (Hz)

Figure 4-19 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in mM Level-1 Horizontal-Vertical Input and Length Scale of2

4-25

Page 100: Study of Seismic Isolation Systems for Computer Floors

10.0

9.0

§ Z 8.0

o ~ 7.0

a: ~ 6.0 W a () 5.0 .ex: ;i 4.0

a: I-a 3.0 w a.. Cf) 2.0

1.0

5.5

..--.5.0 OJ

'--"

Z 4.5 o ~ 4.0

a: w 3.5 --I W () 3.0 o .ex: 2.5 --I .ex: a: 2.0 I-o W 1.5 a.. Cf) 1.0

0.5

TOP OF CABINET DAMPING=2%

- - FIXED - ISOl.1 ...... ISOl.2 - - ISOl.3

-TABLE "I

J

I ~ I

II ~ 11"1 II~II ,.11, I -,~ I VI

I I I I

~

FREQUENCY (Hz)

CENTER OF MASS OF CABINET DAMPING=2% , - - FIXED - ISOl.l ...... ISOl.2 - - ISOl.3

-TABLE

,.

~ 'I 'I I I

" I I I I I I I I I f

11/ f ~

/\1

FREQUENCY (Hz)

10

/1 I \

I \ I I

I I \ \

, ,

\ ,

, '--

100

10 100

Figure 4-20 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in mM Level-2 Horizontal-Vertical Input and Length Scale of2

4-26

Page 101: Study of Seismic Isolation Systems for Computer Floors

_2.5 ~ Z o ~ 2.0

a: W ....J W o 1.5 o <{ ....J <{ a: 1.0

TOP OF CABINET DAMPING=2%

- - FIXED - ISOL.1 - - ISOL.3

I- -TABLE o W a.. (f) 0.5

- - --

0.0 L_~_~=~~rr::._----'_-'---'--...l.-L--'--.I.-L-1-__ ..L...-----'----'--'--...l..-L~

_2.5 ~ Z o ~ 2.0

a: W ....J W o 1.5 () <{ ....J <{ a: 1.0 I-o w a.. C/) 0.5

o 10 100 FREQUENCY (Hz)

CENTER OF MASS OF CABINET DAMPING=2%

- - FIXED - ISOL.1 - - ISOL.3

_TABLE

FREQUENCY (Hz)

1 '1\ \ \ I'

" ' 1 \ \

\

- - - --

100

Figure 4-21 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Taft N21E Ground Horizontal-Vertical Input and Length Scale of 4

4-27

Page 102: Study of Seismic Isolation Systems for Computer Floors

3.5 -. .9 z 3.0 o ~ a:: 2.5 W ...J W () 2.0 () « ...J « 1.5 a:: I­o W 1.0 CL U)

0.5

TOP OF CABINET DAMPING=2%

- - FIXED - ISOL.l - - ISOL.3

-TABLE

- --

FREQUENCY (Hz)

3.0 ,.....---,--,--,--,-..,--,--,-,..---,---,---,-,--,-.... ,,--...,--,-..,--.,--,--,-,.,-

-.2.5 .9 z o ~ 2.0

a:: W ...J W o 1.5 () « ...J « a:: 1.0 I-o w CL (J) 0.5

CENTER OF MASS OF CABINET DAMPING=2%

- - FIXED - ISOL.l - - ISOL.3

-TABLE

I " , /1

II " I II

I

,~ I 1/ I

1/ ' I

FREQUENCY (Hz)

~

" I I I I

i I \ • II I \ ,\

1\ I " \ I \ I \ /1\ , \ \

1\ \ \j \

.... ----

Figure 4-22 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Taft N21E 5th Floor Horizontal-Vertical Input and Length Scale of 4

4-28

Page 103: Study of Seismic Isolation Systems for Computer Floors

8.0 ,-----,--,--r-,-,--..,..,,..---,-.--,--,-,....,...,,----.--,--,-,,.....,-..,

7.5

7.0

:9 6.5

Z 6.0 o 1= 5.5 « a: 5.0

~ 4.5 W () 4.0 () « 3.5 ....J « 3.0 a: I- 2.5 () W 2.0 0.. (J) 1.5

1.0

0.5

TOP OF CABINET DAMPING=2%

- - FIXED - ISOl.l - - ISOL.3

-TABLE

I " "

" , " " " " J ,

,11, ' , ''', ~ , ," /' ft,', 1\ I " ,

II, , / " AI, " " ",', fI.; 1\ 1 , , , , " ~ , ~ ',... ,I , , " " I,' 1\ , , t I I \ ,

~, \ , , \ \ , , , ---

'I I

-, O.OL--__ ~~~ __ ~~~~~-L_~~~~_uw-__ ~_~~~~~

4.5

:94.0

Z Q 3.5

~ ffi 3.0 ....J W o 2.5 o « ....J 2.0 « a: I- 1.5 () W g, 1.0

0.5

o 10 FREQUENCY (Hz)

CENTER OF MASS OF CABINET DAMPING=2%

- - FIXED -ISOl.l - - ISOL.3

_TABLE

~ ~

" " " " " " ~'I "'1 I

,," I I 'Ai, I,\.( , 1 II,. , : ' I',r "~ , ,~ I, ~'" '" , 'I , ( V , ,

I ' , , ' ,,' , ~ ,

FREQUENCY (Hz)

/, ,\ " , , " , ' ,

" , I' , , , , , , , ,

100

, ,

Figure 4-23 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Taft N21E 7th Floor Horizontal-Vertical Input and Length Scale of 4

4-29

Page 104: Study of Seismic Isolation Systems for Computer Floors

3.5

Z 3.0 o ~ a: 2.5 W -.J W U 2.0 U c::t: -.J c::t: 1.5 a: ..... u W 1.0 a... Cf)

0.5

_2.5 0> -z ~ 20 L c::t:' a: w --l W U 1.5 U c::t: -.J c::t: a: 1.0 ..... U w a... (J) 0.5

TOP OF CABINET DAMPING=2%

- - FIXED - ISOL.l - - ISOL.3

-TABLE

FREQUENCY (Hz)

CENTER OF MASS OF CABINET DAMPING=2%

- - FIXED - ISOL.1 - - ISOL.3

-TABLE

FREQUENCY (Hz)

I I 1\ ,I I ~ I

I

VI I I I I.

" " .... _-- - --

.... .... _-

Figure 4-24 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in EI Centro SOOE Ground Horizontal-Vertical Input and Length Scale of 4

4-30

Page 105: Study of Seismic Isolation Systems for Computer Floors

7.0 ,----,--........,..--,----,---,-,...,....".----r-....--.......,..,......,-,--,rr---,--,-,--,..., ..... T"T"l

6.5 TOP OF CABINET DAMPING=2%

6.0

:3 5.5 Z o 5.0 i= « 4.5 a: ~ 4.0 W () 3.5 () « 3.0 ....J

~ 2.5

G 2.0 W Il.. 1.5 C/)

1.0

0.5

6.0

- - FIXED - ISOL.1 - - ISOL.3

-TABLE

I I

I

FREQUENCY (Hz) 10

5.5 CENTER OF MASS OF CABINET DAMPING=2%

.--.. 5.0 - - FIXED

.9 - ISOL.1

Z 4.5 - - ISOL.3

0 I ( ~

~ 4.0 I I

~ I a: , W 3.5 'I " '\ ' ....J I, , ,,',' W 0 3.0 , I ',t " " () r ,,"\' ii' « 2.5 ~, \ I ....J J « y a: 2.0 ~ 0

1.5 W Il..

__ TABLE

(f) 1.0

FREQUENCY (Hz)

- - --

100

~ ,I ,I , I

I I I I I I \ \ \ \ \

"' "' ..... .... "

Figure 4-25 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in El Centro SOOE 5th Floor Horizontal-Vertical Input and Length Scale of 4

4-31

Page 106: Study of Seismic Isolation Systems for Computer Floors

8.0.----.---.-.-r.-"n-----.--.--~-.~"-----,--.-.-,,-.,,

7.5

7.0

§6.5

Z 6.0 o ~ 5.5 ~ II: 5.0

~ 4.5 W 0 4.0 o ~ 3.5 ....J ~ 3.0 II: ..... 2.5 o W 2.0 (L CI) 1.5

1.0

0.5

TOP OF CABINET DAMPING=2%

- - FIXED - ISOL.l - - ISOL.3

-TABLE

, , , , , /' ,

I

~

I, I, , I , , ,

I , , ,I , ,I \, I \ , , ,,It

I, 1/

/I II ~ , ,

" / , 'I I , I ,

,I I' " , , It' I I ,

r , 1'1' ,1 'I , I , 1'1 , , , , "I , ,

\ I " f , \ \ I ,

\ ---

O.OL---~----~~~LLLL ____ ~~--~-L~~-----L--~~~-L~ o 10 100

FREQUENCY (Hz)

6.0 .----.---,--,--r-....--, ...... .-----__ ~ __ -.-.~~----~I------~-,-~

5.5

---.5.0 Cl -Z 4.5 o ~ 4.0

a: W 3.5 -I W 0 3.0 o ~ 2.5 ....J ~ II: 2.0 ..... o W 1.5 (L

CI) 1.0

0.5

CENTER OF MASS OF CABINET DAMPING=2%

- - FIXED - ISOL.l - - ISOL.3

-TABLE

,.

" / I I I , , , ,

,I , I ,I' , , I' I

1 ,I' , ~ j .. I' ,

\. ,,'" I' I 11/1~1 f , , , ,

l ,

FREQUENCY (Hz)

.... .... ........ -

Figure 4-26 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in EI Centro SOOE 7th Floor Horizontal-Vertical Input and Length Scale of 4

4-32

Page 107: Study of Seismic Isolation Systems for Computer Floors

8.0 .----,---r----r---r--,.-,..-,---ro---.,----,---,.---.-,---,C"'T'",,--.----.------.-...,-;r-r""l

7.5

7.0

C5 6.5 -Z 6.0 o i= 5.5

Ci 5.0

~ 4.5 W () 4.0 () « 3.5 -l « 3.0 a: I- 2.5 () W 2.0 0.... C/) 1.5

1.0

0.5

TOP OF CABINET DAMPING=2%

- - FIXED - ISOL.1 - - ISOL.3

_TABLE

"

" 1 I " j I ' ,

" \ " , I I' ',,I ~ ,\ '1 ,y ~ ,ft , I , , I

, \ fI'l,l I, \ , , I I \'1,' '11 '\

, ~

I \ " I " \ I '

,I " I , I \ I I ;

,I I I, , I , " , , I , " , 'V

~ ,

1\ , , \ ,

, \ I I I ,

\ \ ,

\ "".- -

O.OL-___ ~~~~~~~ ____ ~ __ ~-L-L~LLLL ____ ~ __ L-~~~~

5.5

_5.0 .9 Z 4.5 o ~ 4.0

a: W 3.5 -l W () 3.0 ()

« 2.5 -l « a: 2.0 I-() W 1.5 0.... C/) 1.0

0.5

o 10 FREQUENCY (Hz)

CENTER OF MASS OF CABINET DAMPING=2%

- - FIXED - ISOL.1 - - ISOL.3

_TABLE

" I " ~ , ,

I Ii ' , ,1 '" , , """ '\ , \ , 'I", '" , I ,,' , "', ,

I , \ , \ , ' , ,

,\ 1 ) , ,,," , " \

I \ .... " ,

100

......... -

0.0 ~ __ ~---._==~:Ll--L.l ____ ~ __ ~-L-'--~LLLL ____ ~ __ L-~~~~

o 10 100 FREQUENCY (Hz)

Figure 4-27 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Pacoima Dam S74W Ground Horizontal Input and Length Scale of 4

4-33

Page 108: Study of Seismic Isolation Systems for Computer Floors

10.0

9.0

§ 8.0

Z 0 7.0 ~ « cr: 6.0 UJ ...J UJ () 5.0 () « ...J 4.0 « cr: .-()

3.0

UJ c... 2.0 en

1.0

0.0

5.5

_5.0 en -Z 4.5 o

0

~ 4.0 r­cr: UJ 3.5 ...J UJ 0 3.0 o « 2.5 ...J « cr: 2.0 I-() UJ 1.5 c... C/) 1.0

0.5

TOP OF CABINET DAMPING=2%

I , - - FIXED I) j

- ISOL.1 I,ll - - ISOL.3 I .. ill

" 1\

"l' I ,~

!,~ (, r \ " ,. t , , I q , , " I \ I \

I ," • " .........

" ,

I , I \ , , , , , \

I , _TABLE I ,

'" ..-_ .... 10

FREQUENCY (Hz)

CENTER OF MASS OF CABINET DAMPING=2%

- - FIXED - ISOL.1 - - ISOL.3

-TABLE

~ I' ~ ,I j" ,,~ ~

\ " I

," L "I.,. .,

"I " I " " '",i I, I', V , , ,., i', , A \1 ,

, , ", ,~N" , I Y "," , ", ,

J" , ~, " , , , , \ ~ ,

,T, , t ,

'I \ /' I 1 I I It' ,I.

I ,,111,1 I I • \ 11\1

I II II

10

, , , ,

FREQUENCY (Hz)

\

\

I.,. ..... ,

---- - - --

, , .....

.............

100

100

Figure 4-28 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in Bellcore Horizontal-Vertical Input and Length Scale of 4

4-34

Page 109: Study of Seismic Isolation Systems for Computer Floors

11.0 t

10.0 TOP OF CABINET ~ DAMPING=2%

" " § 9.0 - - FIXED

" - ISOl.1 Z - - ISOL.3

II

0 8.0 " ~ II

« 7.0 ,I a:: \11 UJ I ....J 6.0 'I' UJ II () I I ~

'I J~ \ II () 5.0 I _

I', J « I '1 II }

1\) I I I ~ ....J I \ P "\ 1 ~ I « 4.0 I ,\ 1

a:: I 1/\ I' \' II ' I \I \

~ 1 \ ~,' \1/ I () 3.0 I , ... \ UJ

, " c....

1\' \

(j) 2.0 _TABLE " ---I

1.0

0.0 0 10 100

FREQUENCY (Hz)

7.5 r----r----,----r---.--r-...,.,.-.-r---r-~~~~~_r_--~-r__~~_r~

7.0

6.5

§6.0

Z o 5.5

~ 5.0

ffi 4.5 ....J UJ 4.0 () () 3.5 « ....J 3.0 « a:: 2.5 ~ () 2.0 UJ g, 1.5

1.0

0.5

CENTER OF MASS OF CABINET DAMPING=2%

- - FIXED - ISOL.l - - ISOL.3

-- TABLE

\ \

..... .... _-

0.0 L-_---''--......... ..-.I. ____ ..,;;;;~~_--'-_ _'____"___"_..L...l.....L.J....L __ _'__'___'__.L.....J__'_.L..LJ

o 10 100 FREQUENCY (Hz)

Figure 4-29 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in mM Level-l Horizontal-Vertical Input and Length Scale of4

4-35

Page 110: Study of Seismic Isolation Systems for Computer Floors

11.0

10.0

§ 9.0

Z o 8.0

~ II 7.0 W ....J W 6.0 () () « 5.0 ....J « II 4.0 I-trl 3.0 a.. C/) 2.0

1.0

6.5

6.0

§5.5 Z o 5.0 ~ « 4.5 II ~ 4.0 W () 3.5 () « 3.0 ....J

~ 2.5

b 2.0 W a.. 1.5 C/)

1.0

0.5

TOP OF CABINET DAMPING=2%

- - FIXED - ISOL.l - - ISOL.3

_TABLE

1'1

I " , I f

I I ,

I I

I

\

\ \ , \ ,

\

FREQUENCY (Hz)

CENTER OF MASS OF CABINET DAMPING=2%

- - FIXED - ISOL.1 - - ISOL.3

-TABLE

r I I I.

A II" III

" ' , I I I

" I I ,1

I , I I ,

A II , , I , I ,

I " ~ ',/\ I , , '1/, r ,

J" I" I , ,I II' I ~" ,

"',," " , I .. ~ I ~ I , , , , ,

FREQUENCY (Hz)

, \

, , ,

........ -

Figure 4-30 Floor Spectra for Recorded Motions at Center of Mass and Top of Cabinet in mM Level-2 Horizontal-Vertical Input and Length Scale of4

4-36

Page 111: Study of Seismic Isolation Systems for Computer Floors

1.4 SL=2

1.2 r LEVEL 3

~ 1.0 ~ Z 0 0.8 i= « a: w

0.6 ...I W () () « 0.4

0.2

0.0 2 3

3

4

EARTHQUAKE

4

EARTHQUAKE

5

5

6

6

"" FIXED

B ISOL.1

flISOL.2

e ISOl.3

"" FIXED

B ISOU

fl ISOL.2

e ISOL.3

7

7

1: Taft Ground+Vert. 2: Taft 5th+Vert. 3: Taft 7th+Vert. 4: EI Centro Ground+Vert. 5: EI Centro 5th+Vert. 6: EI Centro 7th+Vert. 7: Pacoima Ground

Figure 4-31 Comparison of Response of Internal Flexible Component (Level 3) for Various Excitations.

4-37

Page 112: Study of Seismic Isolation Systems for Computer Floors

14

16 ~

I 12 ~ f­Z W ::; 10 W U :) 8 a. CI)

o 6 (!l Z a: 4

i1i 00

TAFT N21E GROUND+VERTICAL

EXTRAPOLATED TO PROTOTYPE SCALE

~I 3

LENGTH SCALE

TAFT N21 E 5th FLOOR+ VERTICAL

SISOL.1

1!r ISOl.2

e ISOl.3

30 .----------------------------------------------------,

E 25

.s ~ w 20 ::; w

~ 15 a. CI)

o (!l 10 Z a: « lil 5

,

S ISOL.1

1!r ISOL.2

e ISOL.3

OLI ~ ______________________ ~L_ ______________________ -L~

50

45

E 40 .s f- 35 Z W ::;

30 W U :) 25 a. CI)

0 20

(!l Z 15 a: « 10 W 00

3

LENGTH SCALE

TAFT N21E 7th FLOOR+VERTICAL

3

LENGTH SCALE

S ISOL.1

1!r ISOl.2

e ISOl.3

Figure 4-32 Peak Bearing Displacement in Prototype Scale for the Taft Input.Length Scale of 2 Corresponds to Isolation Period of 2.12 sees, Length Scale of 3 Corresponds to 2.60 sees, and Length Scale of 4 Corresponds to 3.00 sees

4-38

Page 113: Study of Seismic Isolation Systems for Computer Floors

EL-CENTRO SOOE GROUND+VERTICAL 40 ,----------------------------------------------------,

3S L EXTRAPOLATED TO PROTOTYPE SCALE ~

! 3Q ~ ~==~!t:::===--=======::;

125 ~' ~ :5 20 a. (J)

Ci 15 <!l Z a: 10 c( W m

B ISOL.1

-6IS0L2

e ISOL3

B ISOL.1

-.!r ISOL2

e ISOL.3

B ISOL.1

-6IS0L2

e ISOL.3

Figure 4-33 Peak Bearing Displacement in Prototype Scale for the EI Centro Input.Length Scale of 2 Corresponds to Isolation Period of 2.12 sees, Length Scale of 3 Corresponds to 2.60 sees, and Length Scale of 4 Corresponds to 3.00 sees

4-39

Page 114: Study of Seismic Isolation Systems for Computer Floors

BELLCORE+ VERTICAL 120,---------------------------------------------------,

110 ~ EXTRAPOLATED TO PROTOTYPE SCALE

E 100 0 o

.s 90 8-I-

~ 80to __ ----------------------eo----------------------~O ~ 70 6------------------____ ~6

j 60 a. C/l 50 o (!) 40 Z a: 30

i1i m 20

10

3

LENGTH SCALE

IBM LEVEL-1+VERTICAL

B ISOU

~ ISOL2

e ISOU

1oo,---------------------------------------------------~

90

E .s 80 !z 70 w ~ 60

j 50 a. C/l o (!) z a: « w m

:: ~ 20

10

B ISOU

~ ISOL.2

e ISOU

OLI ~ ______________________ ~ ________________________ ~

3

LENGTH SCALE

IBM LEVEL-2+VERTICAL

175 ~=================I E 150 F- ro---

.s ___ ------------~O~----------------!z 125 G- -0 w ~ 100 6...--___________________ ---,6

j a. C/l 75 o (!)

Z 50 a: « w m 25

3

LENGTH SCALE

B ISOU

~ ISOL2

e ISOL3

Figure 4-34 Peak Bearing Displacement in Prototype Scale for the Artificial Inputs.Length Scale of 2 Corresponds to Isolation Period of 2.12 sees, Length Scale of 3 Corresponds to 2.60 sees, and Length Scale of 4 Corresponds to 3.00 sees

4-40

Page 115: Study of Seismic Isolation Systems for Computer Floors

SECTION 5

ANALYTICAL PREDICTION OF RESPONSE

5.1 Introduction

A simple analytical model of the isolated floor system is developed and calibrated. The

model is used for the analytical prediction of the response of the tested system. The model

is subsequently used to extend the results of the experimental study OVer a range of

isolation system parameters which could not be experimentally evaluated.

5.2 Analytical Model

The analytical model, as shown in Figure 5-1, is a three degree of freedom representation

of the floor system and Cabinet. The selected degrees of freedom were: The

displacement at the center of mass of the Cabinet with respect to the Raised Floor, Uc ' the

Raised Floor displacement with respect to the Base Floor, UR , and the Base Floor

displacement with respect to the shake table, UB .

The Cabinet was assumed to be fixed on the Raised Floor, a condition which is valid only

when sliding or rocking of the Cabinet does not occur.

5-1

Page 116: Study of Seismic Isolation Systems for Computer Floors

CABINET

==;==-i __ -----., __ uc (\I,R,T, RAISED FLOOR)

C,M, OF CABINET

fii'22'i22Si5=~==~222!~=~RSiSAiSZSI12SSZiiED~F~LSZiioiSZSoR=S1S1!iI---.. -UR (\I, R, T, BASE FLOOR)

Ug -

~ (W,R,T, TABLE) ----FPS BEARING AND FLUID DAMPER ELEMENT

SHAKE TABLE

Figure 5-1 Longitudinal Direction Model of Isolated Floor System

.. .. Fe

( II '\, ---t .. _FR

II L II)

Figure 5-2 Free Body Diagram of Floor System Model

5-2

Page 117: Study of Seismic Isolation Systems for Computer Floors

A free body diagram of the model is shown in Figure 5-2. The equations of motion were

derived by consideration of dynamic equilibrium of the Cabinet, Raised Floor and Base

Floor in the horizontal direction:

mc(UB + UR + Ue + Ug ) +Fe = 0

mR(UB+ UR + Ug ) +FR -Fe = 0

(5-1)

(5-2)

(5-3)

where Fe and FR are, respectively, the restoring and damping (assumed viscous) forces

of the Cabinet and Raised Floor. Furthermore, F is is the isolation system force, which

consists of a component contributed by the FPS bearings and another contributed by the

fluid dampers. That is,

Fe=KeUe+CeUe

W* . F is = R+/.lW*Z+CoUB

where /.l = coefficient of friction, R= radius of curvature of FPS bearings,

(5-4)

(5-5)

(5-6)

W= instantaneous normal load on FPS bearings and Co= effective damping constant (in

horizontal direction) offluid dampers.

The instantaneous load on the bearings was obtained as

W* = W(1 + UV) g (5-7)

where W= gravity load on bearings (27595 N) and Uv = vertical table acceleration.

Equation (5-7) should actually include a modified vertical acceleration to account for the

5-3

Page 118: Study of Seismic Isolation Systems for Computer Floors

vertical flexibility of the floor system and distribution of mass. This modified vertical

acceleration has the general form

L

Uvm(t) = ~ J m(X)URv(X, t)dx o

(5-8)

where L= distance between bearings, m= mass distribution over distance Land

URv= vertical acceleration of Raised Floor. Noting that in the tested system most of the

mass was located in the vicinity of the bearings, for which URv = Uv

(FPS bearings are vertically rigid), it is concluded that Uvm "" Uv . Thus, Equation (5-7)

is valid.

The coefficient of friction in the FPS bearings was described by

Jl = fmax - (jmax - fmin) exp (-a 1 UB I) (5-9)

where f min and a were assumed independent of instantaneous bearing pressure, whereas

f max was assumed to depend on the instantaneous bearing pressure, p :

fmax =fmaxo-Dfp (5-10)

(5-11)

where Pw= bearing pressure due to gravity load. Equation (5-10) is not generally valid

(see Soong and Constantinou, 1994 for details), but rather it is valid for low pressures in

the range of 0 to about 10 MPa.

5-4

Page 119: Study of Seismic Isolation Systems for Computer Floors

Furthermore, variable Z in Equation (5-6) was used to describe rigid plastic behavior. It

is governed by the following equation (Constantinou 1990):

(5-12)

where Y= "yield" displacement and ~ and y = parameters satisfying the condition

~+y= 1.

Table 5-I lists values of the parameters in the analytical model of Equations (5-1) to

(5-12). Solution of these equations was obtained by reducing the equations to first order

form and integrating using a predictor-corrector adaptive integration scheme

(IMSL, 1987).

5-5

Page 120: Study of Seismic Isolation Systems for Computer Floors

Table 5-1 : Parameters in Analytical Model of Tested Isolated Floor System

Quantity Isolation System 1 Isolation System 2 Isolation System 3

Wc=mcg (N) 1780 1780 1780

WR=mRg (N) 1875 1875 1875

WB=me1J (N) 23940 23940 23940

(oc = JKe me (rls) 251.3 251.3 251.3

(0 =~ R mR (rls) 196.0 196.0 196.0

~c= Cc 2mcffi c

0.020 0.020 0.020

~R= CR 2mRffiR

0.036 0.036 0.036

R (rrun) 558.8 558.8 558.8

fmaxo 0.24 0.24 0.24

-fmin

0.07 0.03 0.03

Df (MPa)'l 0.0143 0.0143 0.0143

Y (rrun) 0.25 0.25 0.25

a (sec/rrun) 0.015 0.015 0.015

Co (Ns/rrun) 0.0 14.0 8.1

Pw (MPa) 3.5 7.7 7.7

5-6

Page 121: Study of Seismic Isolation Systems for Computer Floors

5.3 Comparison of Analytical and Experimental Results

Figures 5-3 to 5-10 compare analytical and experimental results for the isolated floor

system in the EI Centro 7th floor plus vertical input. Results are compared for the three

isolation systems and for the three length scales: 2 ,3 and 4. The compared results

include:

(a) Time histories ofFPS bearing displacement.

(b) Time histories of horizontal acceleration of the Raised Floor and center of mass of

Cabinet.

(c) Loops of horizontal isolation system force (force from bearings and VlSCOUS

dampers) versus bearing displacement.

Evidently, the analytically calculated bearing displacements and accelerations are in good

agreement with the experimental results. However, it may be noted that the recorded

acceleration histories contain spikes which are not captured by the analytical model.

These spikes are more pronounced in the acceleration histories of the Raised Floor. They

may have been caused by movement and impact (rattling) of the tiles of Raised Floor in

the vicinity of the instruments.

5-7

Page 122: Study of Seismic Isolation Systems for Computer Floors

75.0

e-50.0 .s

..J 25.0 Cl. (/) W B 0.0

CJ Z -25.0 a: ~ -50.0 W CD

-75.0 0.50

§ ..J u. 0.25 0 w (/)

<t: a: 0.00 ..J w () () ~ -0.25 a: 0 J:

-0.50 0.50

§ cD ~

0.25 () (/) (/) ~ ~

0.00 (j ..J w () () -0.25 ~ a: 0 J:

-0.50 0

I- 0.50 J: CJ iIi

~ 0.25

() a:

0.00 0 u. t-= (/)

-0.25 >-(/)

..J 0 -0.50 !:!? -75

Figure 5-3

- EXPERIMENTAL

M ~. ,.",' .

-_ ... - ANALYTICAL

. : .......................... -.............. -........ -............................ " .......... _-..

W

15 20 25 TIME (secs)

-50 -25 0 25 50 75 BEARING DISPLACEMENT (mm)

Comparison of Analytical and Experimental Results of Floor System with Isolation System 1 in EI Centro 7th Floor plus Vertical Input at Length Scale of 2.

5-8

Page 123: Study of Seismic Isolation Systems for Computer Floors

50.0

E S 25.0 -i 0-

W C/)

Q 0.0 .. <!J z a: -25.0 ~ W CO

-50.0 0.50

§ -i u.. 0.25 0 W C/)

« a: 0.00 -i w () () ~ -0.25 ci 0 :c

..Q.50 0.50

§ cO ~

0.25 () C/) C/) ~ ::E

0.00 0 -i w () () ..Q.25 <r; a: 0 :c

-0.50 0

I- 0.50 :c <!J iIi

~ 0.25

() a:

0.00 0 u.. .....: C/)

-0.25 >-C/)

-i 0

-0.50 ~ -50

Figure 5-4

- EXPERIMENTAL

..... . ANALYTICAL

N~" ............................................... -... .

5 10 15 20 25 TIME (secs)

~ 0 ~ 50 BEARING DISPLACEMENT (mm)

Comparison of Analytical and Experimental Results of Floor System with Isolation System 1 in EI Centro 7th Floor plus Vertical Input at Length Scale of 3.

5-9

Page 124: Study of Seismic Isolation Systems for Computer Floors

40.0

E .s 20.0 .J a.. , (J)

~ 15 0.0 (!) z 0: -20.0 < w CO

-40.0 0.50

:§ .J u. 0.25 0 W (J)

« a:: 0.00 .J w () () < -0.25 a: 0 I

-0.50 0.50

:§ cO < 0.25 () (J) (J)

< ~

0,00 0 .J w () ()

-0.25 < a: 0 I

-0.50 0

r- 0.50 I (!) ijj

~ 0.25

() a::

0.00 0 u. t-= (J)

-0.25 >-(J)

.J 0 -0.50 q,2 -40

Figure 5-5

, - EXPERIMENTAL

.... .. ANALYTICAL "

N~ ':<"" , ,r· .. ,······,··,··, .... , .. ·· .. " .. , .. · .... ,,·· .. · .. , .

5 10 15 20 25 TIME (secs)

~ 0 ~ 40 BEARING DISPLACEMENT (mm)

Comparison of Analytical and Experimental Results of Floor System with Isolation System 1 in EI Centro 7th Floor plus Vertical Input at Length Scale of 4.

5-10

Page 125: Study of Seismic Isolation Systems for Computer Floors

so.o E .s .J

25.0

Cl.. CJ)

C5 0.0 <.'J z a: -25.0 « W CO

-50.0 0.50

§ .J u. 0.25 0 W CJ)

< a: 0.00 .J w () () « -0.25 a: 0 I

-0.50 0.50

§ cD «

0.25 () CJ) CJ) « ~

0.00 0 .J w () ()

-0.25 « ex: 0 I

-0.50 0

I- 0.50 I <.'J iii

~ 0.25

() a:

0.00 0 u. .....: CJ)

-0.25 >-CJ)

.J 0

-0.50 ~ -50

Figure 5-6

5

- EXPERIMENTAL

. _... . ANALYTICAL

. , ........ . .- .. ' ._ .. " ........ .

10 15 TIME (sees)

20

~ 0 ~

BEARING DISPLACEMENT (mm)

25 30

50

Comparison of Analytical and Experimental Results of Floor System with Isolation System 2 in EI Centro 7th Floor plus Vertical Input at Length Scale of 2.

5-11

Page 126: Study of Seismic Isolation Systems for Computer Floors

E .s -.i 0... C/)

(5 (!) z a: « w co

20.0

0.0

·20.0

- EXPERIMENTAL

..... . ANALYTICAL

-- .. _---.--_.-- .. -

-40.0 L--~~~~__'_~~_~~-'--~~~~---'-~_~~~_"_~~~~___' 0.50 r---------r------_,__-------.-----_____ _

§ -.i u. 0.25 o W C/)

« a: 0.00 -.i w o o « -0.25 ex:: o I

-0.50 L--~.L-~~_'_~~~_~.L_~~~~--'-~_~~~_'__~~~~___'

0.50 ------,-----------------------§ IIi « o C/) C/) « ~ <.:i -.i w o o « ex:: o I

l­I (!) W

~ o a: o u.

0.25

0.00

-0.25

0.25

0.00

~ >- -0.25 C/)

..J

5 10 15 20 25 TIME (sees)

o C/) -0.50 L....~~~~~~.L.....~~~~~~.L.....~~~~~~'___~~~~~~

-40 -20 0 20 40

Figure 5-7

BEARING DISPLACEMENT (mm)

Comparison of Analytical and Experimental Results of Floor System with Isolation System 2 in EI Centro 7th Floor plus Vertical Input at Length Scale of 3.

5-12

Page 127: Study of Seismic Isolation Systems for Computer Floors

40.0

~ 20.0 (J)

B 0.0 CJ Z -20.0 cr lii -40.0 CD

§ ~ LL o W (J)

< a: ~ w () () « c::: o I

0.25

0.00

-0.25

- EXPERIMENTAL

. ... .. ANALYTICAL

-0.50 '-----~~~..-J..~~~~--"-~~~~_L_~~ _ __'_~~~~_'___~~~~

0.50 ,--~~~--.-~~~~-.-~~~~-,------~~~~~~~~-.-~~~-.----,

§ a:i « () 0.25 (J) (J) « ~ cj 0.00 .J w ()

~ -0.25 c::: o I

-0.50 '-----~~~..-J..~~~~--"-~~~~_L_~~~__'_~~~~_'_~~~~

l­I CJ iIi

~ () a: o LL ..,.:

o 5 10 15 20 25 30 TIME (sees)

0.25

0.00

~ -0.25 (J)

~ o ~

-0.50 L.....~~~....L~~~~~~~~~-'----'-~~~---"-'-~~~~'-'--'-~~~~ ~ ~ ~ 0 ~ ~ 00

Figure 5-8

BEARING DISPLACEMENT (mm)

Comparison of Analytical and Experimental Results of Floor System with Isolation System 3 in EI Centro 7th Floor plus Vertical Input at Length Scale of 2.

5-13

Page 128: Study of Seismic Isolation Systems for Computer Floors

E .s .J a.. rJ)

(5 (!j z

20.0

0.0

a: -20.0 ~ w CO

§ .J LL

o W rJ)

:;{ 0: .J w ()

0.25

0.00

~ -0.25 a: o :::r:

§ cri ~ () 0.25 rJ)

~ ~ cj 0.00 .J w ()

~ -0.25 a: o :::r:

I­:::r: (!j jjj

~ () a:

0.25

0.00 ~ ~ >- -0.25 rJ)

.J o S!2

Figure 5-9

- EXPERIMENTAL

------ ANALYTICAL

5 10 15 20 25 TIME (secs)

~ 0 M 40 BEARING DISPLACEMENT (mm)

Comparison of Analytical and Experimental Results of Floor System with Isolation System 3 in EI Centro 7th Floor plus Vertical Input at Length Scale of 3.

5-14

Page 129: Study of Seismic Isolation Systems for Computer Floors

E .§. ..J CL en

20.0

Ci 0.0

c::J z a: -20.0 <t: w CD

- EXPERIMENTAL

-- ---- ANALYTICAL

-40.0 L-..~~~_~-'--~~_~~......J....~_~~~_'--~~~_~-L-~--' 0.50 ,--~-~-~-,--~--~~--.--~~--,---,--~--~-,-----,

§ ..J LL 0.25 o W en < a: 0.00 ..J w () () <t: -0.25 a: o I

..Q.50 '--~~..J.-.,._~-'--~~_~~......J....~_~~~_'--~~~_~-'-~--' 0.50 .-~~--~-.----~--.---~---r--'---'--~-,-~--'

§ cri <t: ()

en en <t: :E

0.25

0.00 <.5 ..J w () () « ..Q.25. a: o I

l­I (!J

W

~ () a:

0.25

0.00 fi: ~ >- -0.25 en ..J o en

5 10 15 20 TIME (secs)

~ 0 ~ 40 BEARING DISPLACEMENT (mm)

Figure 5-10 Comparison of Analytical and Experimental Results of Floor System with Isolation System 3 in EI Centro 7th Floor plus Vertical Input at Length Scale of 4.

5-15

Page 130: Study of Seismic Isolation Systems for Computer Floors

Analyses have also been performed for the case of isolation 1 by utilizing a model in

which the dependency of the coefficient of friction on bearing pressure was neglected.

That is, pressure p in Equation (5-11) was set equal to Pw . Results are compared to

experimental results in Figures 5-11 to 5-13. It is evident that neglect of the bearing

pressure dependency of the coefficient of friction does not lead to any significant

difference. For this compare Figures 5-11 to 5-13 to Figures 5-3 to 5-5.

5-16

Page 131: Study of Seismic Isolation Systems for Computer Floors

50.0

~ 25.0

6 o.oW (!) Z ·25.0 a: U5 -50.0 0)

~ ~~~"""" .~J: ................................. . - EXPERIMENTAL

. .. _. - ANALYTICAL

," ........... , ...... , : .......................... -.

-75.0 '---~~~~--'-~~_~~-'---~~~~----L~~_~~--L..-~~~~---' 0.50 ,---------r---,-----,--~------r-------,-----__,

§ ..J u. o w en ::( a: ..J w ()

~ ci o I

0.25

0.00

-0.25

§ cO <{ () 0.25 en en <{ :::;jE o 0.00 ..J w ()

~ -0.25 a: o I

l­I c:l W

~ () a: o u. ~

5

0.25

0.00

10 15 20 25 TIME (secs)

~ -0.25 en .J o en -0.50 L--~~~-----L~~~~~~~~~~~~~----L~~~~-'--~~~"___'

-75 -50 -25 0 25 50 75 BEARING DISPLACEMENT (mm)

Figure 5-11 Comparison of Analytical and Experimental Response of Floor System with Isolation System 1 in EI Centro 7th Floor plus Vertical Input at Length Scale 2 . Analysis Performed without Accounting for Dependence of Coefficient of Friction on Instantaneous Bearing Pressure.

5-17

Page 132: Study of Seismic Isolation Systems for Computer Floors

E 5 ...i a.. (f)

is (!) z 0: « W ID

§ ...i u. Cl w (f) ;;;: a: ...i w () () « a: 0 I

§ cD « ()

(f) (f) « :2 cj ...i w () () « a: 0 I

I-I (!)

W

~ () a: 0 u. ....: (f)

>-(f)

...i 0 ~

50.0

25.0

W ~ 0.0

\J -25.0

-50.0 0.50

0.25

0.00

..Q.25

..Q.50 0.50

0.25

0.00

-0.25

-0.50 0

0.50

0.25

0.00

-0.25

-0.50 -50

~ ....

5

- EXPERIMENTAL

.. .. .. ANALYTICAL

- ................ -................................................. : .......................................... -........ .

10 15 20 25 TIME (secs)

~ 0 ~ 50 BEARING DISPLACEMENT (mm)

Figure 5-12 Comparison of Analytical and Experimental Response of Floor System with Isolation System 1 in EI Centro 7th Floor plus Vertical Input at Length Scale 3 . Analysis Performed without Accounting for Dependence of Coefficient of Friction on Instantaneous Bearing Pressure.

5-18

Page 133: Study of Seismic Isolation Systems for Computer Floors

E S ..J a.. C/)

(5 o z

20.0

o.o~· . ~" .. :,"" ........................................... '.

- EXPERIMENTAL

...... ANALYTICAL

~ -20.0 « W (])

§ ..J u.. 0 W C/)

« II ..J w <.) <.) « Ii 0 :z:

§ cD « <.) C/) C/) « ~ 0 ..J w <.) <.) « Ii 0 :z:

I-:z: 0 W ~ W <.) II 0 u.. ....,: C/)

>-C/)

..J 0 ~

0.25

0.00

-0.25

-0.50 0.50

0.25

0.00

-0.25

-0.50 0 5 15 20 25

TIME (sees)

0.50

0.25

0.00

-0.25

-0.50 -40 ~ 0 ~ 40

BEARING DISPLACEMENT (mm)

Figure 5-13 Comparison of Analytical and Experimental Response of Floor System with Isolation System 1 in EI Centro 7th Floor plus Vertical Input at Length Scale 4 . Analysis Performed without Accounting for Dependence of Coefficient of Friction on Instantaneous Bearing Pressure.

5-19

Page 134: Study of Seismic Isolation Systems for Computer Floors

5.4 Analytical Parametric Study

The analytical model of the tested floor isolation system is sufficiently accurate to allow

for an extension of the experimental study to a range of parameters which could not be

experimentally studied. Particularly, experimental results were not obtained at low values

of friction.

The analytical study concentrated on the response of the isolated floor system in the Taft,

EI Centro and Pacoima Dam records, using the actual records and not those of the shake

table (recall that the table did not reproduce properly the vertical ground motion).

Furthermore, the parametric study was conducted in prototype scale (that is, length scale

of 1).

Table 5-11 lists the range of parameters of the analytical study. All parameters of the

Cabinet and Raised Floor are those of the tested system except for the fundamental

frequency of the Cabinet. The isolation system is described by the radius of curvature of

the FPS bearings (R= 1553 and 2236 mm , which correspond to periods-Equation (2-2)­

of 2.5 and 3. 0 sees), the frictional properties of the bearings and the damping ratio as

determined from Equation (3-2). The dependency of parameter f max on the instantaneous

bearing pressure is neglected. The governing equations of motion are those of Equations

(5-1) to (5-7) , (5-9) and (5-12).

5-20

Page 135: Study of Seismic Isolation Systems for Computer Floors

Table 5-ll : Parameters in Analytical Parametric Study

Quantity Range of Values

Weight of We (N) 1780 Cabinet

Weight of WR (N) 1875 Raised Floor

Weight of Base WE (N) 23940 Floor

Frequency of Ie (Hz) 5 10 20 Cabinet

Frequency of k (Hz) 31.2 Raised Floor

Damping Ratio ~e 0.020 of Cabinet

Damping Ratio ~R 0.036 of Raised Floor

Radius of R (mm) 1553 2236 Curvature of [Period(secs)] [2.5] [3.0] FPS Bearing

Parameters in lmax 0.05 0.10 0.15 0.20 Friction Model

fmin 0.03 0.04 0.06 0.08

a (sec/mm) 0.015

Damping Ratio ~ 0.00 0.15 0.30 0.50 of Isolation

System (Eq.3-2)

5-21

Page 136: Study of Seismic Isolation Systems for Computer Floors

It should be noted that the analytical study was conducted with fundamental frequency of

Cabinet equal to 5 , 10 and 20 Hz. The experimental results at length scale of SL = 4

(corresponding time scale ST= 2 and frequency scale SF= 0.5) may be extrapolated to

prototype scale to obtain an additional set of results, which is valid for Cabinet frequency

of 20 Hz and radius of curvature ofFPS bearings R= 2236 mm (thus, period of 3 secs).

F or the extrapolation, the recorded displacements should be multiplied by a factor of 4 ,

whereas accelerations are the same as in the model scale.

The analytically determined peak response of the isolated floor system is presented in

Figures 5-14 to 5-31. The results demonstrate a number of significant features which

could not be observed in the testing program:

( a) The flexibility of the Cabinet is significant in establishing the effectiveness of the

isolation system. For a flexible Cabinet (say 5 Hz frequency), a high friction

system, with or without dampers, will generate unacceptably large accelerations at

the Cabinet level. It may be observed in the figures that the Cabinet accelerations

in the high friction systems are large and at the level which would cause rocking of

the Cabinet.

(b) A combination of very low friction ifmax= 0.05) and high viscous damping (~=0.50)

results in an acceleration response which is only marginally affected by the

flexibility of the Cabinet on top of the isolated floor. This is illustrated in Figure

5-32 which compares the acceleration response at the center of mass of the

Cabinet in various analyzed configurations for the EI Centro and Taft motions.

5-22

Page 137: Study of Seismic Isolation Systems for Computer Floors

The figure demonstrates the sensitivity of Cabinet response of the high friction

system on the flexibility of the Cabinet.

(c) The combination of low friction and high viscous damping isolation system

produces significant reduction of Cabinet acceleration in comparison to a high

friction system. This significant benefit is achieved at the expense of some small

increase in bearing displacement. This is also illustrated in Figure 5-32 for the

Taft and EI Centro motions.

Of interest is to note the ease in achieving high damping ratio values in the isolation

system. For an isolation system with R= 2236 mm (period of 3 secs) on a 6 m by 6 m

floor (20 ft by 20 ft), a damping ratio ~= 0.50 can be achieved with two dampers in each

principal direction, placed at an angle of 45° with respect to the vertical. From Equation

(3-2) , each damper should have a damping constant Co such that

(5-13)

Considering a weight of 178 kN (40 kips or 100 pst), we obtain Co= 38 Ns/mm

(217 lb-s/in). Based on the calculated displacement in the EI Centro 7th floor motion for

the system with fmax = 0.05 and ~= 0.50 ,the bearing displacement demand is about 120

mm. Thus, the dampers should have a displacement capacity of at least 120xcos45° or

85mm.

5-23

Page 138: Study of Seismic Isolation Systems for Computer Floors

Fluid viscous dampers with damping constant of 38 N s/mm , displacement capacity of ±

100 mm and force capacity of 25,000 N (sufficient for this application) should have

length of about 600 mm and diameter of about 75 mm.

5-24

Page 139: Study of Seismic Isolation Systems for Computer Floors

80

75

E 70

.s I- 65 Z UJ 80 ~ UJ 0 55 :5 0.. 50 CIJ Ci

45 (!) Z c: 40

i1i 35 00

30

25

0,35

~ 0,30 .9 II: 0 0 0.25 ...J U. CI UJ CIJ 0,20 ;;: II: u. 0 ....i

0,15

UJ 0 0 « 0,10

0,05

0,95

~ 0,95 .9 I-UJ Z 0,75 iii « 0 u. 0,65 0 ~ ci 0,55

u. 0 ....i 0.45 UJ 0

~ 0,35

0,25

TAFT N21 E 7th FLOOR+VERTICAL

R=1553mm (PERIOD=2.5secs) CABINET FREQ. fc=5Hz

0.05

0,05

0.05

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0,15

COEFFICIENT OF FRICTION, fmax

O~ 0~5

COEFFICIENT OF FRICTION, fmax

0,2

0,2

02

Figure 5-14 Analytical Response of Isolated Floor System with Cabinet of 5 Hz Frequency and Isolation Period of 2.5 secs in Taft 7th Floor Motion.

5-25

Page 140: Study of Seismic Isolation Systems for Computer Floors

TAFT N21E 7th FLOOR+VERTICAL

80

75 R=2236mm (PERIOD=3secs) CABINET FREQ. fe=SHz

E 70 .§. I-Z W :;; W ()

:5 a..

~~ 60

55

50

-e- 13--0

13- 13--0.15

-9- 13--0.30

+ 1\=0.50

en 15 45 Cl Z cc 40

L5 35 co 30

25 0.05 0.1 0.15

COEFFICIENT OF FRICTION, fmax 0.2

0.35 ,--------------------------------;

§ 0.30

a:

~ 0.25

a w en 0.20

~ u. 0

0.15 .J W () u « 0.10

0.05

0.95

~ 0.85 E! I-W Z 0.75 iii « ()

u. 0.65 0 ::i c..i 0.55

U. 0 .J 0.45 W () () « 0.35

0.25

0.05

0.05

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.2

0.2

Figure 5-15 Analytical Response of Isolated Floor System with Cabinet of 5 Hz Frequency and Isolation Period of 3.0 secs in Taft 7th Floor Motion.

5-26

Page 141: Study of Seismic Isolation Systems for Computer Floors

TAFT N21E 7th FLOOR+VERTICAL

00 ,-----------------------------------------------------------

75

E 70

oS fo- 65 Z UJ 60 ::::; UJ (J

:5 c.. rJJ 15 45 <!l z a: 40

US 35 CD

30

25

0.35

~ 0.30 .9 a: 0 0 0.25 -' u. Cl UJ rJJ 0.20 ~ a: u. 0

0.15 .J UJ (J (J <{ 0.10

0.05

0.95

~ 0.85 .9 fo-UJ Z 0.75 iii <{ (J

u. 0.65 0 ~ (j 0.55

u. 0 .J 0.45 UJ (J (J <{ 0.35

0.25

R=1553mm (PERIOD=2.5secs) CABINET FREQ. fe=10Hz

-e-~=O

B~--{)·15

0.05 0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.05

0.05

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

02

0.2

0.2

Figure 5-16 Analytical Response of Isolated Floor System with Cabinet of 10 Hz Frequency and Isolation Period of 2.5 secs in Taft 7th Floor Motion.

5-27

Page 142: Study of Seismic Isolation Systems for Computer Floors

80

75

E 70 §. ~ 65 Z UJ 60 ::; UJ l) 55 ::s 0.. 50 (fJ

0 45

(!) Z a: 40 ~ UJ 35 III

30

25

0.35

~ 0.30 .9 a: 0 0 0.25 ...J u. Cl UJ (fJ 0.20 < a: u. 0

0.15 ,..j UJ l) l) ~ 0.10

0.05

0.95

~ 0.85 .9 ~ UJ Z 0.75 i'ii ~ l)

u. 0.65 0 ~ 0 0.55

u. 0 ,..j 0.45 W l) l) ~ 0.35

0.25

TAFT N21 E 7th FLOOR+VERTICAL

R=2236mm (PERIOD=3secs)

0.05

0.05

0.05

0.1 0.15

COEFFICIENT OF FRICTION, fmax

CABINET FREQ. fe=10Hz

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.2

0.2

0.2

Figure 5-17 Analytical Response of Isolated Floor System with Cabinet of 10 Hz Frequency and Isolation Period of 3.0 secs in Taft 7th Floor Motion.

5-28

Page 143: Study of Seismic Isolation Systems for Computer Floors

80

75

E 70

..s I- 65 Z w 60 :2 w 0 :s 55

a. 50 en Ci 45 CJ z a: 40 « w 35 CD

30

25

TAFT N21E 7th FLOOR+VERTICAL

R=1553mm (PERIOD=2.5secs)

0.05 0.1 0.15

COEFFICIENT OF FRICTION, fmax

CABINET FREQ. fc=20Hz

0.2

0.30 r--------------------------------,

§ 0.25 c:: o ~ Cl 0.20 w en ~ c:: LL 0.15 o --i w o ~ 0.10

0.05 '---'--________ '--________ -'--________ ...L....-J

0.70

~ 0.80 -9 I-w Z 0.50 10 « 0 LL 0.40 0 ~ 0 0.30

LL 0 --i 0.20 LU ()

~ 0.10

0.00

0.05

0.05

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.2

0.2

Figure 5-18 Analytical Response of Isolated Floor System with Cabinet of 20 Hz Frequency and Isolation Period of 2.5 secs in Taft 7th Floor Motion.

5-29

Page 144: Study of Seismic Isolation Systems for Computer Floors

280

260

E 240 g f- 220 Z W 200 :::; W u 180 :5 a.. 160 (J)

Ci 140 <!) z a: 120

U) !O 100

80

60

0.42

0.38

§ a: 0.34 0 0 ...J

0.30 LL Cl W (J) 0.26 :;:;: a: LL

0.22 0 .J w U 0.18 U «

0.14

0.10

1.20

1.10

§ f- 1.00 W z iIi 0.90 « () LL 0.80 0 ~ 0.70 (.) LL 0 0.60 .J W U 0.50 U «

0.40

0.30

EL CENTRO SOOE 7th FLOOR+VERTICAL

R=2236mm (PERIOD=3secs) CABINET FREQ. fc=5Hz

~ 0.05

0.05

0.05

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

01 ~5

COEFFICIENT OF FRICTION, fmax

-e- J3--{}

B (3=0.15

..,.,.. J3--{}.30

~ (3=0.50

~ 0.2

0.2

0.2

Figure 5-21 Analytical Response of Isolated Floor System with Cabinet of 5 Hz Frequency and Isolation Period of 3.0 secs in EI Centro 7th Floor Motion.

5-32

Page 145: Study of Seismic Isolation Systems for Computer Floors

280

260

E 240

.s """

220 Z W 200 :::;; W <..> 180 :5 a. 160 en 0 140 <!l z a: 120

~ 100 OJ

80

60

0.42

0.38

§ a: 0.34 0 0 ...J

0.30 U.

a w en 0:26 < a: u. 0.22 0 .J w <..> 0.18 <..> co:

0.14

0.10

0.90

0.80

§

""" 0.70

W Z iIi 0.60 co: <..> u. 0.50 0

~ 0.40 (j U. 0 0.30 .J w <..> 0.20 <..> co:

0.10

0.00

El CENTRO SOOE 7th FlOOR+VERTlCAl

R=1553mm (PERIOD=2.5secs) CABINET FREQ. fe=10Hz

-e-fI=O -B- ~-o.15

.,... ~-o.30

+ fI=O.50

~--: ----..:~~ 0.05

0.05

0.05

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

01 ~5

COEFFICIENT OF FRICTION, fmax

0.2

0.2

0.2

Figure 5-22 Analytical Response of Isolated Floor System with Cabinet of 10 Hz Frequency and Isolation Period of 2.5 secs in EI Centro 7th Floor Motion.

5-33

Page 146: Study of Seismic Isolation Systems for Computer Floors

280

260

E 240

S I- 220 Z UJ 200 ~ UJ U 180 :5 Q. 160 UJ Ci

140 <!l Z if 120

iti 100 CD

80

60

EL CENTRO SOOE 7th FLOOR+VERTICAL

R=2236mm (PERIOD=3secs)

0.05 ru o.~

COEFFICIENT OF FRICTION. !max

CABINET FREQ. fe=10Hz

0.2

0.42 r----------------------------~

0.38

II: 0.34

§ lL 0.30 o W !Q 026 « II:

~ 022

..J W U 0.18

~ 0.14

0.10 L-L-_______ --'-________ -L-________ L......l

0.90

0.80

§ 1- 0.70 W Z iIi 0.60 « U lL 0.50 0 ~ 0.40 0 lL 0 0.30 ..J UJ U 0.20 U «

0.10

0.00

0.05

0.05

~ ~5

COEFFICIENT OF FRICTION, !max

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.2

0.2

Figure 5-23 Analytical Response of Isolated Floor System with Cabinet of 10 Hz Frequency and Isolation Period of 3.0 secs in EI Centro 7th Floor Motion.

5-34

Page 147: Study of Seismic Isolation Systems for Computer Floors

EL CENTRO SOOE 7th FLOOR+VERTICAL

280

260 R=1553mm (PERIOD=2.5secs) CABINET FREQ. fc=20Hz

E 240

S I-Z W :::;: W <..l :5 c.. (fJ

15 (!) Z a: L5 tIl

§ II:

8 -' U. a w (fJ ;;: II: u.. 0 .J w <..l <..l «

§ I-W Z iii « <..l u. 0 ~ <.:i u.. 0 .J w <..l <..l «

220

200 ~ 180 r-160 ~ 140

120

100

80

60 0.05

0.42

0.38

0.34

0.30

0.26

0.22

0.18

0.14 ~ 0.10 '--.l-

0.05

0.90

0.80

0.70

0.60

0.50

0.40

0.30

~ 0.20

0.10

0.00 0.05

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15 COEFFICIENT OF FRICTION, fmax

~13=0

.g. 13=0.15

~ 13=030 ~ /3=050

0.2

0.2

0.2

Figure 5-24 Analytical Response of Isolated Floor System with Cabinet of 20 Hz Frequency and Isolation Period of 2.5 secs in EI Centro 7th Floor Motion.

5-35

Page 148: Study of Seismic Isolation Systems for Computer Floors

280

260

E 240

.s I- 220 Z W 200 ::E w () 180 ~ a. 160 en 0

140 <!l z a: 120

U) 100 In

80

60

0.42

0.38

§ a: 0.34 0 0 ..J

0.30 u. 0 w en 0.26 « a: u. 0.22 0 ...i w () 0.18 ()

< 0.14

0.10

0.90

0.80

§ I- 0.70 W Z iii 0.60 < () u. 0.50 0 ~ 0.40 0 U. 0 0.30 ...i W () 0.20

~ 0.10

0.00

EL CENTRO SOOE 7th FLOOR+VERTICAL

R=2236mm (PERIOD=3secs) CABINET FREQ. fe=20Hz

0.05

0.05

~

0.05

~

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

~ ~5

COEFFICIENT OF FRICTION, fmax

0.2

0.2

0.2

Figure 5-25 Analytical Response of Isolated Floor System with Cabinet of 20 Hz Frequency and Isolation Period of 3.0 secs in EI Centro 7th Floor Motion.

5-36

Page 149: Study of Seismic Isolation Systems for Computer Floors

260

240

E 220

.s I- 200 Z LU 180 ~ LU ()

:s 160

a. 140 (J)

6 120 (!J Z a: 100 « LU 80 CD

60

40

0.42

0.38

§ a: 0.34 0 0 --' 0.30 u. a LU (J) 0.26 ;:;: a: u. 0.22 0 ~ LU () 0.18 () «

0.14

0.10

0.05

0.05

PACOIMA S74W GROUND+VERTICAL

R=1553mm (PERIOD=2.Ssecs) CABINET FREO. fe=SHz

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.2

0.2

1.70 r-------------------------------::~

1.60

§ 1.50

tu 1.40 z iIi 1.30 « ~ 1.20

o 1.10 :::;:

<.i u. o ~ LU ()

~

1.00

0.90

0.80

0.70

0.60

0.50 0.05 Ql ~5

COEFFICIENT OF FRICTION, fmax 0.2

Figure 5-26 Analytical Response of Isolated Floor System with Cabinet of 5 Hz Frequency and Isolation Period of 2.5 secs in Pacoima Dam Ground Motion.

5-37

Page 150: Study of Seismic Isolation Systems for Computer Floors

260

240

E 220

.s I- 200 Z LU 180 :::; LU () 160 :5 0.. 140 Ul 0 Cl

120

Z ex: 100

US 80 CD

60

40

0.42

0.38

§ a: 0.34

~ u. 0.30 0 LU Ul 0.26 :;;: a: u.

0.22 0 ..J W () 0.18 () «

0.14

0.10

PACOIMA S74W GROUND+VERTICAL

R=2236mm (PERIOD=3secs)

0.05

0.05

CABINET FREQ. fe=SHz

0.1 0.15 COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.2

0.2

1.70 ,..-----------------------------::;;oiT-"l

1.60

§ 1.50

tu 1.40 Z 1ii 1.30 « ~ 1.20

o 1.10

~ <5 u. o ..J LU ()

~

1.00

0.90

0.80

0.70

0.60

0.50 0.05 0.1 0.15

COEFFICIENT OF FRICTION, fmax 0.2

Figure 5-27 Analytical Response ofIsolated Floor System with Cabinet of 5 Hz Frequency and Isolation Period of 3.0 secs in Pacoima Dam Ground Motion.

5-38

Page 151: Study of Seismic Isolation Systems for Computer Floors

PACOIMA S74W GROUND+VERTICAL

2W ,---------------------------------------------------------,

240

E 220 E ;:- 200 Z UJ 180 ::!! UJ <.l 160 ~ 0- 140 (fJ

15 120

Cl z cr: 100 ..: UJ 80 !D

60

40

0.44

0.40

§ a: 0.36 0 0 ...J

0.32 lI. 0 UJ (fJ 0.28 ;;: a: lI. 0.24 0 ..J UJ <.l 0.20 <.l ..:

0.16

0.12

0.90

0.80

§ I- 0.70 UJ Z CD 0.60 ..: <.l lI. 0.50 0 ~ 0.40 t.i lI. 0 0.30 ..J UJ <.l 020 <.l ..:

0.10

0.00

0.05

0.05

0.05

R=1553mm (PERIOD=2.5secs) CABINET FREQ. fe=10Hz

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

~I\=O

.g. ~-o.15

~ 1\=0.30

+ 1\=0.50

0.2

0.2

0.2

Figure 5-28 Analytical Response of Isolated Floor System with Cabinet of 10 Hz Frequency and Isolation Period of 2.5 secs in Pacoima Dam Ground Motion.

5-39

Page 152: Study of Seismic Isolation Systems for Computer Floors

260

240

E 220

.s I- 200 Z UJ 180 :::: UJ (J 160 ~ a. 140 en is (!)

120

Z a: 100 « UJ 80 III

60

40

0.44

0.40

:§ a: 0.36 0 0 ...J

0.32 u. Cl UJ en 0.28 < a: u. 0.24 0 ..J UJ () 0.20 (J «

0.16

0.12

0.90

0.80

:§ I- 0.70 UJ Z iii 0.60 « (J

u. 0.50 0 :::i 0.40 0 u. 0 0.30 ..J UJ () 0.20 (J «

0.10

0.00

PACOIMA S74W GROUND+VERTICAL

R=2236mm (PERIOO=3secs)

0.05

0.05

0.05

CABINET FREQ. fe=10Hz

0.1 0.15

COEFFICIENT OF FRICTION, fmax

·0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.2

0.2

0.2

Figure 5-29 Analytical Response of Isolated Floor System with Cabinet of 10 Hz Frequency and Isolation Period of 3.0 secs in Pacoima Dam Ground Motion.

5-40

Page 153: Study of Seismic Isolation Systems for Computer Floors

E .s I-Z UJ ~ UJ <..l :5 a.. C/)

C5 <!J z a: U) III

§ 0: 0 0 ~ LL

0 UJ C/)

« 0: LL 0 ..J UJ <..l <..l ..:

§ I-UJ Z iii ~ LL 0 :::E c.i LL 0 ..J UJ <..l <..l ..:

PACOIMA S74W GROUND+VERTICAL

200 ,---------------------------------------------------------,

240

220

200

180

160

140

120

100

80

00

40 0.05

0.44

0.40

0.36

0.32

0.28

0.24

0.20

0.16

0.12 0.05

0.90

0.80

0.70

0.60

0.50

0.40

0.30

0.20

0.10

0.00 0.05

R=1553mm (PERIOD=2.5secs) CABINET FREQ. fc=20Hz

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

~I3=O

B 13=0 15

.,... 13=0.30

+ ~-o50

0.2

0.2

0.2

Figure 5-30 Analytical Response of Isolated Floor System with Cabinet of 20 Hz Frequency and Isolation Period of 2.5 secs in Pacoima Dam Ground Motion.

5-41

Page 154: Study of Seismic Isolation Systems for Computer Floors

260

240

E 220

.s I- 200 Z W 180 :::; W () 160

:5 0.. 140 If)

15 120

<!l Z CC 100

US 80 CD

60

40

0.44

0.40

§ a: 0.36 0 0 --' u.. 0.32 a w If) 0.28 ;;: a: u..

0.24 0 -i w () 0.20 () «

0.16

0.12

0.90

0.80

§ I- 0.70 W Z m 0.60 « ()

u.. 0.50 0 ~ 0.40 cj u.. 0 0.30 -i W () 0.20 () «

0.10

0.00

PACOIMA S74W GROUND+VERTICAL

R=2236mm (PERIOD=3secs)

0.05

0.05

0.05

CABINET FREQ. fe=20Hz

~~-o

B ~-o.15

-9- ~-o.30

4- ~-o5O

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.1 0.15

COEFFICIENT OF FRICTION, fmax

0.2

0.2

0.2

Figure 5-31 Analytical Response of Isolated Floor System with Cabinet of 20 Hz Frequency and Isolation Period of 3.0 secs in Pacoima Dam Ground Motion.

5-42

Page 155: Study of Seismic Isolation Systems for Computer Floors

1.4 r------------------------------,

:§ 1.2

t­lJ.J Z 1.0 ili « o u. 0.8 o ~ cj 0.6 U. o

R= 2236 mm (PERIOD= 3 sees)

G- ________ _

------

o fmax=0.05.j3;O.5

o fmax=0.20.j3;O

-- EL CENTRO SOOE 7th+VERT

- - - -. TAFT N21 E 7th+VERT

.J 0.4 ~ lJ.J

8 G- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -:Q ____ _ ------ --- ---------:8 « 0.2

0.0 '---!--------------'---------------"--'

5 10 20

FREQUENCY OF CABINET (Hz)

~ ::: f E tG~---------------~O~------------------~O .s L ~ 100 !- Df------------------ED3--------------------10 lJ.J ~ t5 80 « ....J 0-(j) 60 o CJ Z a: 40

« lJ.J !D 20

8-------------------------------0-------------------------------0

G - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - B - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - EJ

o '---! _____________ L-____________ -L~

5 10 20 FREQUENCY OF CABINET (Hz)

Figure 5-32 Comparison of Response of Floor System Isolated by High Friction and by a Combination of Low Friction and High Viscous Damping Isolation Systems.

5-43

Page 156: Study of Seismic Isolation Systems for Computer Floors
Page 157: Study of Seismic Isolation Systems for Computer Floors

SECTION 6

SUMMARY AND CONCLUSIONS

Interruption or failure of data processing systems in an earthquake may result in chaos and

substantial economic loss. Seismic design provisions for buildings do not intend to limit

damage or maintain function of such systems. Available options for the owner are seismic

isolation of the entire building, innovative installation of single equipment or seismic

isolation of computer floors. The first two have been the subject of many studies. This

study concentrated on the development and testing of a computer floor system.

The studied system consisted of spherically shaped sliding bearings and fluid viscous

dampers. The spherically shaped bearings provided the simplest means of achieving long

isolation period without bearing instability problems. For the testing, Friction Pendulum

(or FPS) bearings were used. In one tested configuration, only high friction FPS bearings

were used. In two other configurations, lower friction FPS bearings and fluid viscous

dampers were used. All configurations were characterized by substantial ability to

dissipate energy. However, in the two configurations with fluid viscous dampers, high

frictional damping was exchanged by a combination of lower frictional damping and

viscous damping in an attempt to further reduce the acceleration response.

An analytical model of the tested system was developed and shown to be capable of

predicting the experimental results with good accuracy. The model was then utilized to

extend the experimental results over a range of parameters which could not be

experimentally evaluated.

6-1

Page 158: Study of Seismic Isolation Systems for Computer Floors

The experimental and analytical results demonstrated substantial reductions in the

response of a generic computer cabinet on top of the isolated floor. Under non-isolated

conditions the tested cabinet underwent rocking and developed accelerations which could

cause either interruption of operation or failure. In contrast, the cabinet on the isolated

floor with long isolation period (about 3 secs) did not experience rocking and developed

substantially less acceleration.

It was concluded that a floor isolation system with spherically shaped bearings of isolation

period of about 3 secs and, dynamic coefficient of friction of about 0.05 and fluid

viscous dampers providing damping ratio of 50 % of critical was the most effective. This

system resulted in the lowest acceleration response of the computer cabinet, which was

also insensitive to the dynamic characteristics of the cabinet. In contrast, a high friction

system resulted in high accelerations, which were also dependent on the dynamic

characteristics of the cabinet.

Bearing displacements were found to be small. For the most successful long period - low

friction - high viscous damping system, this displacement did not exceed 120 mm for the

used seismic motions. This low value has been the result of high energy dissipation

capability of the isolation system.

6-2

Page 159: Study of Seismic Isolation Systems for Computer Floors

SECTION 7

REFERENCES

Bellcore (1988), Network Equipment-Building Systems (NEBS), "Generic Equipment Requirements." Report TR-EOP-000063, Issue 3, Whippany, NJ, March.

Constantinou, M.C., Mokha, A and Reinhorn, AM. (1990). "Teflon Bearings in Base Isolation II: Modeling." J. Struct. Engrg., ASCE, 116(2), 455-474.

Constantinou, M.C. and Symans M.D. (1992). "Experimental and Analytical Investigation of Seismic Response of Structures with Supplemental Fluid Viscous Dampers." Report No. NCEER-92-0032, Nat. Ctr. for Earthquake Engrg. Res., State Univ. of New York, Buffalo, NY.

Constantinou, M.C., Tsopelas, P., Kim, Y-S. and Okamoto, S. (1993). "NCEER-TAISEI Corporation Research Program on Sliding Seismic Isolation Systems for Bridges-Experimental and Analytical Study of Friction Pendulum System (FPS)." Report No. NCEER-93-0020, Nat. Ctr. for Earthquake Engrg. Res., State Univ. of New York, Buffalo, NY.

Demetriades, G.F., Constantinou, M.C., Reinhorn, AM. (1992). "Study of Wire Rope Systems for Seismic Protection of Equipment in Buildings." Report No. NCEER-92-0012, Nat. Ctr. for Earthquake Engrg. Res., State Univ. of New York, Buffalo, NY.

Fujita, T. (1991), editor. "Seismic Isolation and Response Control for Nuclear and Non-nuclear Structures." Special Issue for the Exhibition of the 11th International Conference (SMiRT 11), August 18-23, Tokyo, Japan.

IBM (1992), "Earthquake resistance for IBM Hardware Products", Corporate Bulletin C-B 1-9711-009, Purchase, NY.

IMSL Mathematical Library (1987). "Fortran Library for Mathematical Applications."

Kelly, J.M. (1993). "State-of-the-Art and State-of-the-Practice in Base Isolation." Proc. ATC-17-1 Seminar on Seismic Isolation, Passive Energy Dissipation, and Active Control, March 11-12 , San Francisco, CA

Kosar, K, Soong, T.T., Shen, KL., HoLung, lA. and Lin, YK (1993). "Seismic Testing of Installation Methods for Computers and Data Processing Equipment. " NCEER-93-0007, Nat. Ctr. for Earthquake Engrg. Res., State Univ. of New York, Buffalo, NY.

Lin, J. and Mahin, S.A (1985). "Seismic Response of Light Subsystems on Inelastic Structures." J. Struct. Engrg., ASCE, 111(2),400-417.

7-1

Page 160: Study of Seismic Isolation Systems for Computer Floors

Makris, N. and Constantinou, M.e. (1992). "Spring-viscous Damper Systems for Combined Seismic and Vibration Isolation." Earthq. Engrg. Struct. Dyn., 21, 649-664.

Mokha, A, Constantinou, M.e. and Reinhom AM. (1990). "Experimental Study and Analytical Prediction of Earthquake Response of a Sliding Isolation System with a Spherical Surface." Report No. NCEER-90-0020, Nat. Ctr. for Earthquake Engrg. Res., State Univ. of New York, Buffalo, NY.

Singh, M.P. (1988). "Seismic Design of Secondary Systems." Prob. Engrg. Mech., 3(3), 151-158

Soong, T.T. and Constantinou M.e., (1994), editors. "Passive and Active Structural Vibration Control in Civil Engineering." Springer-Verlag, Wien.

Structural Engineers Association of California (SEAOC), Seismology Committee·(1990), "Recommended Lateral Force Requirements and Commentary", 5th Edition, Sacramento, CA

Tsopelas, P., Okamoto, S., Constantinou, M.C., Ozaki, D. and Fujii, S. (1994). "NCEER-TAISEI Corporation Research Program on Sliding Seismic Isolation Systems for Bridges-Experimental and Analytical Study of Systems Consisting of Sliding Bearings, Rubber Restoring Force Devices and Fluid Dampers." Report No. NCEER-94-0002, Nat. Ctr. for Earthquake Engrg. Res., State Univ. of New York, Buffalo, NY.

Zayas, V, Low, S.S. and Mahin, S.A (1987). "The FPS Earthquake Resisting System, Experimental Report." Report No. UCBI EERC-87/01, Earthquake Engineering Research Center, University of California, Berkeley, CA, June.

7-2

Page 161: Study of Seismic Isolation Systems for Computer Floors

APPENDIX A

EXPERIMENTAL RESULTS

This Appendix contains the peak recorded response of the isolated and nonisolated floor

system in each test. The reported quantities were obtained from the measurements of the

instruments listed in the following table.

Table A-I: Recorded Quantity and Corresponding Instrument(s).

Acceleration Instrument( s ) Displacement Instrument( s) Quantity Quantity

Table Horizontal ABLH Table Horizontal DBLC

Raised Floor ARFH Bearing Horizontal average(DBSW,DBSE,DBNW,DBNE) Horizontal

Cabinet Level 1 ACMH Raised Floor DRFW (C.M.) Horizontal Horizontal

Cabinet Level 2 AC2H Cabinet C.M. DCMW-DRFW Horizontal Horizontal W.R. T.

Raised Floor

Cabinet Level 3 AC3H Cabinet Top DCTW-DRFW Horizontal Horizontal W.R.T.

Raised Floor

Cabinet Top ACTH Horizontal

Table Vertical ABLV

Raised Floor ARFV Vertical

Cabinet Top max(ACSV,ACNV)

Vertical

A-I

Page 162: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

TAFT N2lE GROUND LENGTH SCALE = 1

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal -- -- 0.157 0.157 ( --) ( --) (0.163) ( --)

Raised Floor -- -- 0.136 0.205

Horizontal (--) ( --) (0.154) (--)

Cabinet Level 1 -- -- 0.171 0.273

(C.M.) Horizontal ( --) (--) (0.144) ( --)

Cabinet Level 2 -- -- 0.235 0.242

Horizontal (--) ( --) (0.188) (--)

Cabinet Level 3 -- -- 0.255 0.363

Horizontal (--) (--) (0.256) (--)

Cabinet Top -- -- 0.248 0.303

Horizontal (--) (--) (0.191) ( --)

Table Vertical -- -- 0.034 0.020 ( --) (--) (0.125) ( --)

Raised Floor -- -- 0.046 0.026

Vertical ( --) ( --) (0.144) (--)

Cabinet Top -- -- 0.075 0.063

Vertical ( --) (--) (0.166) (--)

DISPLACEMENT (rom)

Table Horizontal -- -- 31.318 3l.902 ( --) (--) (3l.852) ( --)

Bearing Horizontal -- -- 5.309 N/A (--) (--) (5.486) (N/A)

Raised Floor -- -- 32.963 31.712

Horizontal (--) (--) (32.506) ( --)

Cabinet C.M. -- -- l.702 l.510

Horizontal W.R.T. ( --) (--) (l.005) (--)

Raised Floor

Cabinet Top -- -- 2.210 2.235

Horizontal W.R.T. ( --) (--) (l.956) ( --)

Raised Floor

A-2

Page 163: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion.

TAFT N21E GROUND LENGTH SCALE = 2

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.160 0.175 0.157 0.159 (0.169) (0.163) (0.153) (0.164)

Raised Floor 0.147 0.135 0.130 0.272

Horizontal (0.182) (0.182) (0.178) (0.269)

Cabinet Level 1 0.183 0.146 0.149 0.303

(C.M.) Horizontal (0.204) (0.138) (0.141) (0.262)

Cabinet Level 2 0.212 0.179 0.186 0.268

Horizontal (0.255) (0.200) (0.233) (0.292)

Cabinet Level 3 0.298 0.233 0.247 0.361

Horizontal (0.312) (0.244) (0.245) (0.347)

Cabinet Top 0.246 0.222 0.231 0.411

Horizontal (0.307) (0.210) (0.213) (0.365)

Table Vertical 0.033 0.028 0.030 0.034 (0.148) (0.116) (0.118) (0.151)

Raised Floor 0.033 0.029 0.030 0.030

Vertical (0.146) (0.115) (0.124) (0.167)

Cabinet Top 0.073 0.069 0.058 0.117

Vertical (0.188) (0.196) (0.218) (0.202)

DISPLACEMENT (nun)

Table Horizontal 22.225 22.047 22.631 22.200 (22.377) (22.276) (22.250) (22.352)

Bearing Horizontal 6.452 3.734 3.404 N/A (3.175) (5.131) (3.277) (N/A)

Raised Floor 22.257 22.524 23.406 22.174

Horizontal (22.314) (22.720) (22.511) (22.270)

Cabinet C.M. 0.784 0.824 0.633 1.500

Horizontal W.R.T. (1.094) (0.905) (0.892) (1.607)

Raised Floor

Cabinet Top 1.448 1.118 1.194 2.337

Horizontal W.R.T. (2.819) (1.651) (1.778) (2.997)

Raised Floor

A-3

Page 164: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response ofIsolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

TAFT N21E GROUND LENGTH SCALE = 3

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.159 0.158 0.152 0.154 (0.171) (0.155) (0.147) (0.162)

Raised Floor 0.229 0.122 0.116 0.237

Horizontal (0.230) (0.133) (0.152) (0.279)

Cabinet Level 1 0.236 0.154 0.196 0.257

(C.M.) Horizontal (0.218) (0.159) (0.190) (0.269)

Cabinet Level 2 0.267 0.194 0.237 0.248

Horizontal (0.241) (0.196) (0.257) (0.292)

Cabinet Level 3 0.368 0.268 0.253 0.402

Horizontal (0.387) (0.258) (0.261) (0.414)

Cabinet Top 0.295 0.230 0.296 0.353

Horizontal (0.302) (0.222) (0.302) (0.375)

Table Vertical 0.035 0.036 0.033 0.049 (0.142) (0.115) (0.124) (0.133)

Raised Floor 0.046 0.039 0.028 0.036

Vertical (0.136) (0.139) (0.137) (0.136)

Cabinet Top 0.077 0.081 0.060 0.130

Vertical (0.231) (0.237) (0.274) (0.226)

DISPLACEMENT (mm)

Table Horizontal 17.374 17.348 17.323 17.399 (17.526) (17.424) (17.450) (17.450)

Bearing Horizontal 1.702 3.099 2.515 N/A (2.565) (4.648) (2.362) (N/A)

Raised Floor 17.482 18.028 17.837 17.336

Horizontal (17.361) (17.729) (17.571) (17.278)

Cabinet C.M. 1.194 0.656 0.548 1.456

Horizontal W.R.T. (1.287) (0.938) (0.932) (1.638)

Raised Floor

Cabinet Top 1.178 1.168 1.219 2.184

Horizontal W.R.T. (2.413) (1.905) (1.956) (2.489)

Raised Floor

A-4

Page 165: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

TAFT N2lE GROUND LENGTH SCALE == 4

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM I SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.149 -- 0.155 0.153 (0.162) ( --) (0.161) (0.158)

Raised Floor 0.203 -- 0.121 0.251

Horizontal (0.263) (--) (0.162) (0.268)

Cabinet Level I 0.218 -- 0.190 0.275

(C.M.) Horizontal (0.204) ( --) (0.191) (0.298)

Cabinet Level 2 0.260 -- 0.233 0.209

Horizontal (0.276) (--) (0.293) (0.232)

Cabinet Level 3 0.344 -- 0.328 0.389

Horizontal (0.384) (--) (0.331) (0.416)

Cabinet Top 0.312 -- 0.280 0.376

Horizontal (0.322) ( --) (0.326) (0.353)

Table Vertical 0.048 -- -- 0.046 (0.137) (--) (--) (0.137)

Raised Floor -- -- 0.028 0.042

Vertical (--) ( --) (0.154) (0.127)

Cabinet Top 0.116 -- 0.076 0.117

Vertical (0.301) ( --) (0.284) (0.185)

DISPLACEMENT (rnm)

Table Horizontal 14.427 -- 14.199 13.919 (14.427) (--) (14.249) (14.300)

Bearing Horizontal 0.914 -- 1.397 N/A (3.048) ( --) (1.524) (N/A)

Raised Floor 14.421 -- 14.580 14.300

Horizontal (14.345) ( --) (14.389) (14.319)

Cabinet C.M. 0.857 -- 0.614 1.989

Horizontal W.RT. (1.119) ( --) (1.049) (1.254)

Raised Floor

Cabinet Top 1.549 -- 1.372 2.692

Horizontal W.RT. (2.286) (--) (1.778) (2.667)

Raised Floor

A-5

Page 166: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response ofIsolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

TAFT N2lE 5th FLOOR LENGTH SCALE = 1

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal -- -- 0.303 0.295 ( --) (0.295) (0.295) ( --)

Raised Floor -- -- 0.230 0.402

Horizontal (--) (0.248) (0.246) (--)

Cabinet Level 1 -- -- 0.245 0.418

(C.M.) Horizontal ( --) (0.247) (0.253) ( --)

Cabinet Level 2 -- -- 0.260 0.348

Horizontal ( --) (0.278) (0.333) ( --)

Cabinet Level 3 -- -- 0.303 0.463

Horizontal (--) (0.337) (0.293) (--)

Cabinet Top -- -- 0.307 0.494

Horizontal (--) (0.281) (0.314) (--)

Table Vertical -- -- 0.072 0.083 ( --) (0.140) (0.148) ( --)

Raised Floor -- -- 0.148 0.095

Vertical ( --) (0.171) (0.171) ( --)

Cabinet Top -- -- 0.137 0.174

Vertical (--) (0.249) (0.236) ( --)

DISPLACEMENT (rrun)

Table Horizontal -- -- 42.672 42.723 ( --) (42.697) (42.520) ( --)

Bearing Horizontal -- -- 19.304 N/A ( --) (18.237) (20.574) (N/A)

Raised Floor -- -- 41.764 42.659

Horizontal ( --) (42.056) (41.929) (--)

Cabinet C.M. -- -- 1.351 3.312

Horizontal W.R.T. (--) (1.788) (1.597) ( --)

Raised Floor

Cabinet Top -- -- 1.854 4.394

Horizontal W.R.T. (--) (2.667) (2.413) (--)

Raised Floor

A-6

Page 167: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response ofIsolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion.

TAFT N2lE 5th FLOOR LENGTH SCALE = 2

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.268 0.265 0.262 0.275 (0.269) (0.256) (0.257) (0.281)

Raised Floor 0.238 0.228 0.201 0.344

Horizontal (0.281) (0.245) (0.216) (0.369)

Cabinet Level 1 0.303 0.238 0.215 0.395

(C.M.) Horizontal (0.310) (0.228) (0.217) (0.356)

Cabinet Level 2 0.352 0.281 0.269 0.360

Horizontal (0.393) (0.320) (0.335) (0.454)

Cabinet Level 3 0.378 0.346 0.311 0.572

Horizontal (0.392) (0.367) (0.338) (0.502)

Cab met Top 0.438 0.315 0.278 0.440 Horizontal (0.465) (0.370) (0.378) (0.442)

Table Vertical 0.098 0.090 0.103 0.103 (0.151) (0.143) (0.153) (0.146)

Raised Floor 0.070 0.046 0.045 0.067

Vertical (0.142) (0.116) (0.126) (0.132)

Cabinet Top 0.148 0.109 0.111 0.142

Vertical (0.327) (0.242) (0.294) (0.259)

DISPLACEMENT (mm)

Table Horizontal 23.851 23.749 23.774 23.952 (23.952) (23.851) (23.851) (23.851)

Bearing Horizontal 8.611 11.481 12.192 N/A (7.925) (11.760) (11.811) (N/A)

Raised Floor 24.048 24.162 23.946 23.838

Horizontal (23.705) (23.876) (23.870) (23.844)

Cabinet C.M. 1.629 1.367 1.080 3.026 Horizontal W.R.T. (1.697) (1.400) (1.367) (2.597)

Raised Floor

Cabinet Top 2.743 1.880 1.727 4.394 Horizontal W.R.T. (3.683) (2.337) (2.083) (4.775)

Raised Floor

A-7

Page 168: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

TAFT N21E 5th FLOOR LENGTH SCALE = 3

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.273 0.277 0.267 0.268 (0.273) (0.284) (0.278) (0.263)

Raised Floor 0.328 0.224 0.213 0.456

Horizontal (0.341) (0.251) (0.253) (0.367)

Cabinet Level 1 0.318 0.228 0.219 0.504

(C.M.) Horizontal (0.338) (0.227) (0.235) (0.381)

Cabinet Level 2 0.367 0.317 0.291 0.384

Horizontal (0.410) (0.307) (0.323) (0.443)

Cabinet Level 3 0.508 0.383 0.348 0.739

Horizontal (0.538) (0.380) (0.355) (0.747)

Cabinet Top 0.455 0.342 0.336 0.647

Horizontal (0.432) (0.304) (0.358) (0.457)

Table Vertical 0.095 0.083 0.080 0.094 (0.152) (0.139) (0.133) (0.163)

Raised Floor 0.076 0.062 0.054 0.191

Vertical (0.494) (0.134) (0.147) (0.163)

Cabinet Top 0.159 0.143 0.136 0.270

Vertical (0.282) (0.263) (0.329) (0.248)

. DISPLACEMENT (mm)

Table Horizontal 18.288 18.390 18.186 18.263 (18.364) (18.339) (18.263) (18.237)

Bearing Horizontal 6.350 9.0l7 7.620 N/A (6.401) (9.220) (7.772) (N/A)

Raised Floor 18.256 18.637 18.466 18.167

Horizontal (18.155) (18.587) (18.364) (11.722)

Cabinet C.M. 2.332 1.557 1.072 3.934

Horizontal W.R.T. (2.364) (1.608) (1.294) (3.281)

Raised Floor

Cabinet Top 3.658 2.489 2.032 6.299

Horizontal W.R.T. (4.470) (2.870) (2.184) (4.877)

Raised Floor

A-8

Page 169: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

TAFT N21E 5th FLOOR LENGTH SCALE = 4

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.276 -- 0.283 0.275 (0.277) ( --) (0.286) (0.273)

Raised Floor 0.273 -- 0.242 0.496

Horizontal (0.286) ( --) (0.272) (0.452)

Cabinet Level 1 0.312 -- 0.251 0.570

(C.M.) Horizontal (0.345) (--) (0.255) (0.534)

Cabinet Level 2 0.353 -- 0.3l3 0.398

Horizontal (0.425) (--) (0.341) (0.405)

Cabinet Level 3 0.658 -- 0.426 0.988

Horizontal (0.768) (--) (0.436) (0.997)

Cabinet Top 0.400 -- 0.340 0.646

Horizontal (0.447) (--) (0.378) (0.588)

Table Vertical 0.082 -- -- 0.142 (0.145) (--) (--) (0.223)

Raised Floor -- -- 0.046 0.144

Vertical (--) ( --) (0.148) (0.220)

Cabinet Top 0.144 -- 0.111 0.300

Vertical (0.340) (--) (0.298) (0.406)

DISPLACEMENT (rum)

Table Horizontal 14.935 -- 14.884 15.011 (15.l38) (--) (14.834) (14.910)

Bearing Horizontal 4.801 -- 5.867 N/A (5.791) ( --) (5.740) (N/A)

Raised Floor 15.005 -- 15.107 14.961

Horizontal (14.897) ( --) (14.986) (14.942)

Cabinet C.M. 2.2l3 -- 1.359 4.440

Horizontal W.R.T. (2.611) (--) (1.405) (3.923)

Raised Floor

Cabinet Top 3.327 -- 2.210 7.290

Horizontal W.RT. (4.597) ( --) (2.769) (6.604)

Raised Floor

A-9

Page 170: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

TAFT N21E 7th FLOOR LENGTH SCALE = I

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM I SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal -- -- 0.525 0.542 (--) (0.527) (0.527) (0.554)

Raised Floor -- -- 0.317 0.789

Horizontal (--) (0.371) (0.312) (0.870)

Cabinet Level I -- -- 0.335 0.544

(C.M.) Horizontal ( --) (0.341) (0.318) (0.548)

Cabinet Level 2 -- -- 0.396 0.942

Horizontal ( --) (0.418) (0.424) (0.933)

Cabinet Level 3 -- -- 0.462 0.923

Horizontal ( --) (0.446) (0.443) (0.972)

Cabinet Top -- -- 0.449 0.930

Horizontal ( --) (0.408) (0.454) (1.035)

Table Vertical -- -- 0.101 0.117 ( --) (0.146) (0.144) (0.188)

Raised Floor -- -- 0.130 0.671

Vertical ( --) (0.224) (0.172) (0.607)

Cabinet Top -- -- 0.145 0.653

Vertical ( --) (0.243) (0.219) (0.648)

DISPLACEMENT (mm)

Table Horizontal -- -- 53.518 53.797 ( --) (53.823) (53.594) (53.823)

Bearing Horizontal -- -- 34.569 N/A (--) (31.293) (36.068) (N/A)

Raised Floor -- -- 49.492 53.594

Horizontal (--) (51.257) (48.463) (53.531)

Cabinet C.M. -- -- 1.910 9.600

Horizontal W.R.T. ( --) (3.377) (2.181) (9.735)

Raised Floor

Cabinet Top -- -- 2.667 15.367

Horizontal W.R.T. (--) (4.648) (3.023) (16.256)

Raised Floor

A-IO

Page 171: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion.

TAFT N21E 7th FLOOR LENGTH SCALE = 2

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.477 0.456 0.452 0.490* (0.487) (0.464) (0.452) (0.498)*

Raised Floor 0.271 0.323 0.295 1.150

Horizontal (0.303) (0.369) (0.347) (1.409)

Cabinet Level 1 0.317 0.319 0.274 0.570

(C.M.) Horizontal (0.311) (0.324) (0.270) (0.585)

Cabinet Level 2 0.443 0.350 0.333 1.168

Horizontal (0.463) (0.369) (0.381) (1.248)

Cabinet Level 3 0.500 0.489 0.402 l.035

Horizontal (0.505) (0.477) (0.379) (l.030)

Cabinet Top 0.499 0.326 0.295 l.617

Horizontal (0.518) (0.391) (0.376) (l.608)

Table Vertical 0.178 0.094 0.103 0.239 (0.199) (0.175) (0.168) (0.256)

Raised Floor 0.108 0.081 0.117 0.342

Vertical (0.173) (0.143) (0.140) (0.329)

Cabinet Top 0.275 0.209 0.158 l.498

Vertical (0.417) (0.264) (0.289) (1.564)

DISPLACEMENT (nun)

Table Horizontal 29.464 29.337 29.235 29.439 (29.489) (29.362) (29.312) (29.515)

Bearing Horizontal 14.834 18.085 19.787 N/A (14.834) (18.110) (19.431) (N/A)

Raised Floor 25.356 25.984 26.994 29.483

Horizontal (25.749) (26.022) (25.025) (29.477)

Cabinet C.M. 2.210 2.053 l.634 39.307

Horizontal W.R.T. (2.078) (2.208) (l.491) (26.816)

Raised Floor

Cabinet Top 3.581 2.794 2.286 4l.504

Horizontal W.R.T. (4.166) (2.997) (2.362) (38.329)

Raised Floor

* = Cabinet Rocking Observed

A-ll

Page 172: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

TAFT N2lE 7th FLOOR LENGTH SCALE = 3

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.368 0.379 0.367 0.353* (0.384) (0.376) (0.369) (0.357)*

Raised Floor 0.368 0.314 0.264 0.934

Horizontal (0.376) (0.318) (0.303) (0.996)

Cabinet Level 1 0.348 0.289 0.286 0.653 (C.M.) Horizontal (0.363) (0.291) (0.274) (0.616)

Cabinet Level 2 0.437 0.329 0.355 1.193

Horizontal (0.474) (0.383) (0.368) (1.091)

Cabinet Level 3 0.854 0.535 0.481 1.298

Horizontal (0.945) (0.587) (0.495) (1.287)

Cabinet Top 0.468 0.387 0.372 1.461

Horizontal (0.485) (0.354) (0.380) (1.490)

Table Vertical 0.114 0.091 0.098 0.226 (0.174) (0.l34) (0.168) (0.309)

Raised Floor 0.110 0.1l3 0.080 0.272

Vertical (0.533) (0.173) (0.146) (0.308)

Cabinet Top 0.314 0.249 0.244 1.693

Vertical (0.475) (0.361) (0.377) (1.616)

DISPLACEMENT (mm)

Table Horizontal 19.939 19.964 19.990 19.888 (19.863) (19.939) (19.990) (19.787)

Bearing Horizontal 11.735 l3.360 12.878 N/A (11.862) (13.437) (12.802) (N/A)

Raised Floor 18.758 19.190 19.107 19.888

Horizontal (18.625) (19.241) (19.101) (19.825)

Cabinet C.M. 3.356 2.624 1.735 23.101

Horizontal W.R.T. (3.127) (2.303) (1.518) (22.830)

Raised Floor

Cabinet Top 4.928 3.785 2.286 38.862

Horizontal W.R.T. (5.359) (3.810) (2.413) (38.024)

Raised Floor

* = Cabinet Rocking Observed

A-12

Page 173: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

TAFT N21E 7th FLOOR LENGTH SCALE = 4

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.414 -- 0.422 0.418* (0.424) ( --) (0.412) (0.421)*

Raised Floor 0.361 -- 0.350 0.915

Horizontal (0.375) (--) (0.407) (0.948)

Cabinet Level 1 0.361 -- 0.273 1.211

(C.M.) Horizontal (0.373) (--) (0.294) (1.116)

Cabinet Level 2 0.408 -- 0.349 0.574

Horizontal (0.482) (--) (0.494) (0.632)

Cabinet Level 3 0.847 -- 0.627 1.192

Horizontal (0.893) ( --) (0.660) (1.276)

Cabinet Top 0.461 -- 0.378 1.646

Horizontal (0.523) ( --) (0.495) (1.560)

Table Vertical 0.144 -- -- 0.394 (0.226) ( --) ( --) (0.424)

Raised Floor -- -- -- 0.514

Vertical ( --) (--) (0.247) (0.616)

Cabinet Top 0.278 -- 0.215 1.767

Vertical (0.488) (--) (0.436) (1.608)

DISPLACEMENT (mm)

Table Horizontal 15.240 -- 15.138 15.189 (15.316) ( --) (15.113) (15.164)

Bearing Horizontal 9.169 -- 8.992 N/A (9.423) (--) (8.788) (N/A)

Raised Floor 15.399 -- 15.608 15.246

Horizontal (15.278) ( --) (15.437) (15.158)

Cabinet C.M. 2.923 -- 1.834 23.160

Horizontal W.R.T. (3.280) ( --) (1. 783) (23.689)

Raised Floor

Cabinet Top 4.394 -- 3.327 41.173

Horizontal W.R.T. (4.470) ( --) (2.997) (41.148)

Raised Floor

* = Cabinet Rocking Observed

A-13

Page 174: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

EL-CENTRO SOOE GROUND LENGTH SCALE = 1

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal -- -- 0.365 0.388 (--) (--) (0.366) ( --)

Raised Floor -- -- 0.265 0.730

Horizontal (--) ( --) (0.332) ( --)

Cabinet Level I -- -- 0.253 0.853

(C.M.) Horizontal ( --) (--) (0.342) ( --)

Cabinet Level 2 -- -- 0.292 0.526

Horizontal ( --) (--) (0.440) ( --)

Cabinet Level 3 -- -- 0.395 1.040

Horizontal ( --) ( --) (0.383) ( --)

Cabinet Top -- -- 0.309 0.973

Horizontal ( --) ( --) (0.445) ( --)

Table Vertical -- -- 0.093 0.191 ( --) (--) (0.331) ( --)

Raised Floor -- -- 0.122 0.390

Vertical ( --) ( --) (0.387) (--)

Cabinet Top -- -- 0.119 0.839

Vertical ( --) (--) (0.747) ( --)

DISPLACEMENT (mm)

Table Horizontal -- -- 59.360 59.665 (--) (--) (59.588) (--)

Bearing Horizontal -- -- 24.714 N/A (--) (--) (24.333) (N/A)

Raised Floor -- -- 64.021 59.233

Horizontal ( --) (--) (63.983) ( --)

Cabinet C.M. -- -- 1.541 10.249

Horizontal W.R.T. (--) (--) (1.975) ( --)

Raised Floor

Cabinet Top -- -- 2.l34 16.688 Horizontal W.R.T. (--) (--) (3.581) ( --)

Raised Floor

A-14

Page 175: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

EL-CENTRO SOOE GROUND LENGTH SCALE = 2

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM I SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.305 0.322 0.316 0.369 (0.329) (0.321) (0.318) (0.352)#

Raised Floor 0.293 0.253 0.218 0.728

Horizontal (0.343) (0.355) (0.338) (0.774)

Cabinet Level I 0.288 0.256 0.222 0.727

(C.M.) Horizontal (0.325) (0.308) (0.292) (0.501)

Cabinet Level 2 0.364 0.365 0.288 0.529

Horizontal (0.420) (0.415) (0.434) (0.587)

Cabinet Level 3 0.418 0.391 0.308 0.717

Horizontal (0.475) (0.431) (0.390) (0.686)

Cabinet Top 0.443 0.360 0.287 0.964

Horizontal (0.477) (0.393) (0.355) (0.765)

Table Vertical 0.189 0.120 0.126 0.199 (0.234) (0.238) (0.244) (0.341)

Raised Floor 0.108 0.091 0.090 0.261

Vertical (0.253) (0.270) (0.261) (0.363)

Cabinet Top 0.208 0.207 0.209 0.551

Vertical (0.638) (0.559) (0.687) (0.593)

DISPLACEMENT (rum)

Table Horizontal 42.342 42.189 42.240 42.266 (42.393) (42.189) (42.215) (42.469)

Bearing Horizontal 11.125 10.744 14.199 N/A (13.868) (10.541) (14.021) (N/A)

Raised Floor 42.183 42.482 40.437 42.259

Horizontal (38.049) (41.269) (39.872) (42.450)

Cabinet C.M. 1.875 1.583 1.319 7.814

Horizontal W.R.T. (2.175) (1.965) (1.697) (7.053)

Raised Floor

Cabinet Top 2.972 2.032 1.803 13.106

Horizontal W.R.T. (5.258) (2.997) (3.124) (13.157)

Raised Floor

# = Cabinet Sliding Observed

A-IS

Page 176: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response ofIsolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

EL-CENTRO SOOE GROUND LENGTH SCALE = 3

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.308 0.296 0.288 0.314 (0.298) (0.291) (0.286) (0.314)

Raised Floor 0.321 0.234 0.240 0.829

Horizontal (0.335) (0.262) (0.307) (0.710)

Cabinet Level 1 0.342 0.205 0.212 0.640

(C.M.) Horizontal (0.348) (0.255) (0.222) (0.503)

Cabinet Level 2 0.477 0.313 0.328 0.490

Horizontal (0.512) (0.406) (0.400) (0.705)

Cabinet Level 3 0.553 0.341 0.326 0.874

Horizontal (0.575) (0.403) (0.363) (0.767)

Cabinet Top 0.574 0.328 0.320 0.778

Horizontal (0.555) (0.327) (0.343) (0.888)

Table Vertical 0.139 0.103 0.109 0.156 (0.208) (0.175) (0.179) (0.233)

Raised Floor 0.457 0.094 0.078 0.224

Vertical (0.500) (0.308) (0.221) (0.255)

Cabinet Top 0.238 0.121 0.135 0.595

Vertical (0.477) (0.407) (0.530) (0.573)

DISPLACEMENT (mm)

Table Horizontal 33.274 33.147 33.223 33.249 (33.274) (33.096) (33.249) (33.147)

Bearing Horizontal 9.347 8.890 11.151 N/A (10.719) (8.966) (10.236) (N/A)

Raised Floor 33.198 33.903 31.153 33.052

Horizontal (31.540) (33.376) (32.487) (33.033)

Cabinet C.M. 2.457 1.505 1.229 6.455

Horizontal W.R.T. (2.665) (l.949) (l.826) (5.636)

Raised Floor

Cabinet Top 3.708 2.286 l.753 10.414

Horizontal W.R.T. (4.343) (3.124) (2.489) (9.423)

Raised Floor

A-16

Page 177: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion.

EL-CENTRO SOOE GROUND LENGTH SCALE = 4

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.283 -- 0.280 0.286 (0.287) (--) (0.278) (0.287)

Raised Floor 0.304 -- 0.239 0.738

Horizontal (0.307) ( --) (0.261) (0.774)

Cabinet Level 1 0.338 -- 0.248 0.713

(C.M.) Horizontal (0.331) ( --) (0.238) (0.692)

Cabinet Level 2 0.440 -- 0.371 0.465

Horizontal (0.485) (--) (0.414) (0.437)

Cabinet Level 3 0.643 -- 0.388 0.954

Horizontal (0.632) (--) (0.408) (0.907)

Cabinet Top 0.584 -- 0.373 0.706

Horizontal (0.575) (--) (0.343) (0.782)

Table Vertical 0.188 -- -- 0.184 (0.215) (--) (--) (0.258)

Raised Floor -- -- 0.092 0.236

Vertical (--) (--) (0.192) (0.260)

Cabinet Top 0.236 -- 0.173 0.551

Vertical (0.428) (--) (0.501) (0.603)

DISPLACEMENT (nun)

Table Horizontal 27.483 -- 27.280 27.483 (27.280) ( --) (27.051) (27.356)

Bearing Horizontal 7.417 -- 8.331 N/A (8.001) ( --) (8.484) (N/A)

Raised Floor 27.750 -- 27.394 27.337

Horizontal (27.476) (--) (26.734) (27.508)

Cabinet C.M. 2.192 -- 1.400 5.912

Horizontal W.RT. (2.207) ( --) (1.826) (6.007)

Raised Floor

Cabinet Top 3.429 -- 2.007 10.236

Horizontal W.RT. (3.886) (--) (2.591) (10.922)

Raised Floor

A-I7

Page 178: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

EL-CENTRO SOOE 5th FLOOR LENGTH SCALE = 1

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal -- -- 0.430 0.429 (--) (0.430) (0.432) ( --)

Raised Floor -- -- 0.362 0.556

Horizontal (--) (0.374) (0.437) ( --)

Cabinet Level 1 -- -- 0.366 0.579

(C.M.) Horizontal (--) (0.403) (0.436) ( --)

Cabinet Level 2 -- -- 0.481 0.431

Horizontal ( --) (0.496) (0.538) ( --)

Cabinet Level 3 -- -- 0.415 0.738

Horizontal ( --) (0.452) (0.456) ( --)

Cabinet Top -- -- 0.441 0.629

Horizontal ( --) (0.513) (0.561) ( --)

Table Vertical -- -- 0.299 0.246 (--) (0.323) (0.319) (--)

Raised Floor -- -- 0.410 0.383

Vertical (--) (0.528) (0.499) ( --)

Cabinet Top -- -- 0.216 0.407

Vertical ( --) (0.667) (0.777) ( --)

DISPLACEMENT (mm)

Table Horizontal -- -- 107.340 107.772 (--) (107.772) (107.417) ( --)

Bearing Horizontal -- -- 65.888 N/A (--) (46.355) (65.303) (N/A)

Raised Floor -- -- 129.997 107.067

Horizontal ( --) (117.316) (129.578) ( --)

Cabinet C.M. -- -- 2.757 7.741

Horizontal W.R.T. (--) (3.369) (3.145) ( --)

Raised Floor

Cabinet Top -- -- 3.632 12.802

Horizontal W.R.T. (--) (5.385) (5.486) ( --)

Raised Floor

A-I8

Page 179: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

EL-CENTRO SOOE 5th FLOOR LENGTH SCALE = 2

Table Horizontal

Raised Floor Horizontal

Cabinet Level I (CM.) Horizontal

Cabinet Level 2 Horizontal

Cabinet Level 3 Horizontal

Cabinet Top Horizontal

Table Vertical

Raised Floor Vertical

Cabinet Top Vertical

Table Horizontal

Bearing Horizontal

Raised Floor Horizontal

Cabinet C.M. Horizontal W.RT.

Raised Floor

Cabinet Top Horizontal W.RT.

Raised Floor

ISOLATION ISOLATION ISOLATION SYSTEM I SYSTEM 2 SYSTEM 3

ACCELERATION (g)

0.421 0.424 0.406 (0.430) (0.409) (0.409)

0.322 0.405 0.362 (0.438) (0.404) (0.458)

0.291 0.347 0.311 (0.372) (0.398) (0.374)

0.479 0.488 0.496 (0.642) (0.555) (0.537)

0.458 0.451 0.390 (0.557) (0.464) (0.474)

0.459 0.478 0.431 (0.571) (0.513) (0.537)

0.347 0.320 0.324 (0.351) (0.329) (0.367)

0.209 0.380 0.420 (0.382) (0.469) (0.558)

0.252 0.280 0.201 (0.763) (0.494) (0.606)

DISPLACEMENT (mm)

56.286 56.109 56.159 (56.159) (55.931) (55.931)

36.297 29.185 39.446 (36.068) (29.235) (39.421)

50.933 53.467 53.562 (51.073) (53.086) (53.791)

2.259 2.540 2.103 (2.261) (2.613) (2.361)

2.997 3.023 2.565 (6.071) (4.775) (4.369)

* = Cabinet Rocking Observed # = Cabinet Sliding Observed

A-19

WITHOUT ISOLATION

0.416* (0.411)*#

1.574 (0.914)

1.565 (0.635)

0.865 (1.101)

1.168 (0.941)

2.453 (1.471)

0.315 (0.356)

0.475 (0.370)

3.292 (1.249)

56.261 (56.210)

N/A (N/A)

56.166 (56.267)

75.754 (75.575)

134.112 (82.956)

Page 180: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion.

EL-CENTRO SOOE 5th FLOOR LENGTH SCALE = 3

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM I SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.389 0.384 0.374 0.382* (0.398) (0.384) (0.383) (0.392)*

Raised Floor 0.331 0.287 0.273 1.525

Horizontal (0.363) (0.296) (0.337) (1.423)

Cabinet Level 1 0.304 0.300 0.274 1.577

(C.M.) Horizontal (0.339) (0.298) (0.288) (0.948)

Cabinet Level 2 0.457 0.440 0.377 0.915

Horizontal (0.530) (0.432) (0.450) (1.533)

Cabinet Level 3 0.472 0.438 0.378 1.067

Horizontal (0.526) (0.431) (0.361) (1.051)

Cabinet Top 0.444 0.340 0.342 2.860

Horizontal (0.513) (0.384) (0.380) (2.379)

Table Vertical 0.261 0.281 0.241 0.311 (0.325) (0.297) (0.307) (0.308)

Raised Floor 0.111 0.129 0.113 0.542

Vertical (0.508) (0.354) (0.272) (0.645)

Cabinet Top 0.239 0.253 0.208 3.557

Vertical (0.505) (0.434) (0.516) (2.601)

DISPLACEMENT (mru)

Table Horizontal 43.104 42.774 43.028 43.002 (42.850) (42.647) (42.697) (42.621)

Bearing Horizontal 21.107 23.800 29.032 N/A (26.772) (23.673) (29.058) (N/A)

Raised Floor 33.280 38.176 36.601 42.761

Horizontal (34.341) (38.513) (36.760) (42.596)

Cabinet C.M. 2.496 2.445 1.697 73.914

Horizontal W.R.T. (2.605) (2.329) (1.830) (63.275)

Raised Floor

Cabinet Top 3.353 3.200 2.286 127.457

Horizontal W.R.T. (4.547) (4.064) (3.404) (116.586)

Raised Floor

* = Cabinet Rocking Observed

A-20

Page 181: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

EL-CENTRO SOOE 5th FLOOR LENGTI-I SCALE = 4

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.399 -- 0.386 0.395* (0.397) (--) (0.392) (0.392)*

Raised Floor 0.358 -- 0.240 1.017

Horizontal (0.392) (--) (0.257) (1.160)

Cabinet Level 1 0.338 -- 0.267 1.694

(C.M.) Horizontal (0.356) (--) (0.288) (1.515)

Cabinet Level 2 0.461 -- 0.363 0.757

Horizontal (0.474) (--) (0.434) (0.780)

Cabinet Level 3 0.528 -- 0.421 1.081

Horizontal (0.595) (--) (0.434) (1.076)

Cabinet Top 0.484 -- 0.358 2.567

Horizontal (0.563) (--) (0.452) (2.453)

Table Vertical 0.244 -- -- 0.296 (0.304) ( --) (--) (0.320)

Raised Floor -- -- 0.116 0.466

Vertical (--) ( --) (0.156) (0.731)

Cabinet Top 0.186 -- 0.186 2.948

Vertical (0.457) (--) (0.439) (2.472)

DISPLACEMENT (mm)

Table Horizontal 34.823 -- 34.569 34.849 (34.849) (--) (34.519) (34.849)

Bearing Horizontal 21.387 -- 23.749 N/A (21.336) (--) (23.851) (N/A)

Raised Floor 29.128 -- 30.791 34.754

Horizontal (30.213) (--) (31.325) (34.849)

Cabinet C.M. 2.732 -- 1.719 62.770

Horizontal W.R.T. (2.858) ( --) (1.711) (64.140)

Raised Floor

Cabinet Top 4.166 -- 2.311 109.449

Horizontal W.R.T. (4.801) (--) (3.073) (110.668)

Raised Floor

* = Cabinet Rocking Observed

A-21

Page 182: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

EL-CENTRO SOOE 7th FLOOR LENGTH SCALE = 1

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal -- -- 0.753* 0.710* (--) ( --) ( --) (0.706)*

Raised Floor -- -- 3.729 1.882

Horizontal (--) (--) ( --) (1.888)

Cabinet Level 1 -- -- 1.043 0.825

(C.M.) Horizontal ( --) (--) ( --) (0.875)

Cabinet Level 2 -- -- 2.048 1.553 Horizontal (--) (--) ( --) (1.676)

Cabinet Level 3 -- -- 1.348 1.052

Horizontal ( --) (--) ( --) (1.094)

Cabinet Top -- -- 3.093 2.284

Horizontal (--) ( --) (--) (2.099)

Table Vertical -- -- 1.109 0.280 ( --) (--) (--) (0.287)

Raised Floor -- -- 1.322 0.694

Vertical ( --) ( --) ( --) (0.564)

Cabinet Top -- -- 3.933 3.091

Vertical (--) (--) ( --) (2.662)

DISPLACEMENT (nun)

Table Horizontal -- -- 131.928 131.953 ( --) (--) ( --) (132.080)

Bearing Horizontal -- -- 88.79++ N/A (--) (--) (--) (N/A)

Raised Floor -- -- 178.092 131.375

Horizontal (--) (--) ( --) (131.274)

Cabinet C.M. -- -- 183.937 179.557

Horizontal W.R.T. (--) c--) ( --) (205.816)

Raised Floor

Cabinet Top -- -- 248.895 208.534

Horizontal W.R.T. (--) ( --) ( --) (228.778)

Raised Floor

* = Cabinet Rocking Observed ++ = Bearing Displacement Capacity Exceeded

A-22

Page 183: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response oflsolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

EL-CENTRO SOOE 7th FLOOR LENGTH SCALE = 2

Table Horizontal

Raised Floor Horizontal

Cabinet Level 1 (C.M.) Horizontal

Cabinet Level 2 Horizontal

Cabinet Level 3 Horizontal

Cabinet Top Horizontal

Table Vertical

Raised Floor Vertical

Cabinet Top Vertical

Table Horizontal

Bearing Horizontal

Raised Floor Horizontal

Cabinet C.M. Horizontal W.R.T.

Raised Floor

Cabinet Top Horizontal W.R.T.

Raised Floor

ISOLATION ISOLATION ISOLATION SYSTEM 1 SYSTEM 2 SYSTEM 3

ACCELERATION (g)

0.839 0.817 0.849 (0.841) (0.816) (0.834)

0.328 0.631 0.474 (0.422) (0.736) (0.446)

0.380 0.494 0.530 (0.392) (0.606) (0.626)

0.490 0.657 0.365 (0.598) (0.743) (0.428)

0.476 0.910 0.465 (0.625) (0.999) (0.512)

0.538 0.815 0.487 (0.607) (0.790) (0.561)

0.210 0.237 0.233 (0.350) (0.323) (0.353)

0.238 0.499 0.272 (0.435) (0.494) (0.386)

0.301 0.408 0.322 (0.884) (0.618) (0.750)

DISPLACEMENT (mm)

72.949 71.552 71.577 (71.806) (71.577) (71.349)

59.157 43.967 60.452 (62.433) (50.597) (60.198)

73.419 66.231 71.374 (76.746) (66.491) (72.403)

2.499 7.033 3.423 (2.950) (66.491) (3.354)

4.267 10.718 4.445 (6.172) (66.294) (5.436)

* = Cabinet Rocking Observed # = Cabinet Sliding Observed

A-23

WITHOUT ISOLATION

0.846*# (0.818)*#

l.950 (l.837)

0.843 (1.042)

1.410 (l.456)

0.951 (0.996)

l.898 (l.908)

0.324 (0.441)

0.466 (0.587)

2.145 (2.168)

72.187 (72.009)

N/A (N/A)

72.028 (72.155)

133.306 (138.551)

137.922 (139.065)

Page 184: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

EL-CENTRO SOOE 7th FLOOR LENGTH SCALE = 3

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.842 0.814 0.808 0.801 * (0.826) (0.812) (0.804) (0.874)*

Raised Floor 0.403 0.611 0.404 1.693

Horizontal (0.399) (0.609) (0.382) (2.165)

Cabinet Level 1 0.384 0.512 0.447 0.900

(C.M.) Horizontal (0.387) (0.519) (0.482) (1.003)

Cabinet Level 2 0.472 0.583 0.315 1.537

Horizontal (0.548) (0.610) (0.354) (1.735)

Cabinet Level 3 0.553 0.807 0.460 1.270

Horizontal (0.556) (0.799) (0.475) (1.375)

Cabinet Top 0.522 0.528 0.394 2.356

Horizontal (0.521) (0.656) (0.398) (2.829)

Table Vertical 0.200 0.292 0.209 0.449 (0.264) (0.342) (0.319) (0.341)

Raised Floor 0.545 0.295 0.229 0.760

Vertical (0.583) (0.512) (0.351) (0.520)

Cabinet Top 0.378 0.365 0.368 4.106

Vertical (0.761) (0.594) (0.603) (3.958)

DISPLACEMENT (rum)

Table Horizontal 53.391 53.137 53.391 53.086 (53.315) (53.086) (53.086) (53.086)

Bearing Horizontal 41.250 32.741 42.596 N/A (41.681) (32.715) (42.520) (N/A)

Raised Floor 42.158 45.072 41.548 53.099

Horizontal (45.199) (45.142) (42.272) (53.289)

Cabinet C.M. 3.162 4.661 2.396 98.927

Horizontal W.R.T. (3.161) (4.466) (2.475) (104.697)

Raised Floor

Cabinet Top 4.648 6.299 3.175 171.602

Horizontal W.R.T. (5.309) (7.112) (4.166) (180.111)

Raised Floor

* = Cabinet Rocking Observed

A-24

Page 185: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response ofIsolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion.

EL-CENTRO SOOE 7th FLOOR LENGTH SCALE = 4

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.789 -- 0.755 0.713* (0.764) ( --) (0.761) (0.711)*

Raised Floor 0.428 -- 0.384 1.353

Horizontal (0.449) (--) (0.383) (1.377)

Cabinet Level 1 0.382 -- 0.410 1.506

(C.M.) Horizontal (0.417) (--) (0.383) (1.480)

Cabinet Level 2 0.450 -- 0.308 0.733

Horizontal (0.572) ( --) (0.493) (0.775)

Cabinet Level 3 0.640 -- 0.487 1.061

Horizontal (0.662) ( --) (0.531) (1.086)

Cabinet Top 0.503 -- 0.444 2.438

Horizontal (0.562) (--) (0.516) (2.424)

Table Vertical 0.183 -- 0.216 0.319 (0.232) ( --) (--) (0.357)

Raised Floor -- -- 0.190 0.662

Vertical (--) ( --) (0.279) (0.621)

Cabinet Top 0.325 -- 0.283 3.236

Vertical (0.449) ( --) (0.477) (3.402)

DISPLACEMENT (mm)

Table Horizontal 42.367 -- 42.316 42.316 (42.266) (--) (42.418) (42.367)

Bearing Horizontal 30.658 -- 33.299 N/A (32.080) (--) (33.426) (N/A)

Raised Floor 32.722 -- 35.192 42.456

Horizontal (33.045) (--) (34.677) (42.393)

Cabinet C.M. 3.423 -- 2.615 67.678

Horizontal W.R.T. (3.446) (--) (2.235) (67.678)

Raised Floor

Cabinet Top 5.055 -- 3.150 115.519

Horizontal W.R.T. (5.486) (--) (4.420) (117.297)

Raised Floor

* = Cabinet Rocking Observed

A-25

Page 186: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response ofIsolated Raised Floor and Cabinet. V I . P th" D C b' d H' tId V rf I I t M f auem aren eSls IS or om me onzon a an e lca npu o Ion.

PACOIMA DAM S74W GROUND LENGTH SCALE = 1

Table Horizontal

Raised Floor Horizontal

Cabinet Level I (C. M.) Horizontal

Cabinet Level 2 Horizontal

Cabinet Level 3 Horizontal

Cabinet Top Horizontal

Table Vertical

Raised Floor Vertical

Cabinet Top Vertical

Table Horizontal

Bearing Horizontal

Raised Floor Horizontal

Cabinet C.M. Horizontal W.R.T.

Raised Floor

Cabinet Top Horizontal W.R.T.

Raised Floor

ISOLATION ISOLATION ISOLATION SYSTEM 1 SYSTEM 2 SYSTEM 3

ACCELERATION (g)

-- -- 0.990 (--) (1.019)*+ (1.008)*+

-- -- 0.401 ( --) (1.297) (0.782)

-- -- 0.526 ( --) (0.812) (1.005)

-- -- 0.392 (--) (1.653) (0.670)

-- -- 0.596 (--) (1.163) (0.954)

-- -- 0.482 ( --) (2.402) (1.628)

-- -- 0.182 ( --) (1.673) (1.439)

-- -- 0.253 ( --) (1.056) (1.117)

-- -- 0.511 (--) (3.511) (2.559)

DISPLACEMENT (mm)

-- -- 103.683 (--) (104.369) (104.597)

-- -- 57.760 ( --) (41.427) (57.074)

-- -- 106.134 (--) (100.838) (105.461)

-- -- 3.323 ( --) (53.824) (10.128)

-- -- 4.953 (--) (66.243) (15.621)

* = Cabinet Rocking Observed + = Cabinet Uplift Observed

A-26

WITHOUT ISOLATION

--( --)

--( --)

--( --)

--( --)

--( --)

--( --)

--( --)

--( --)

--( --)

--(--)

--(--)

--( --)

--( --)

--(--)

Page 187: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response oflsolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion.

PACOIMA DAM S74W GROUND LENGTH SCALE = 2

Table Horizontal

Raised Floor Horizontal

Cabinet Level 1 (C.M.) Horizontal

Cabinet Level 2 Horizontal

Cabinet Level 3 Horizontal

Cabinet Top Horizontal

Table Vertical

Raised Floor Vertical

Cabinet Top Vertical

Table Horizontal

Bearing Horizontal

Raised Floor Horizontal

Cabinet C.M. Horizontal W.R.T.

Raised Floor

Cabinet Top Horizontal W.R.T.

Raised Floor

ISOLATION ISOLATION ISOLATION SYSTEM 1 SYSTEM 2 SYSTEM 3

ACCELERATION (g)

1.004 1.033* 1.028

(1.017)*+ (1.024)*+ (1.049)*+

0.566 1.000 0.471 (2.281) (1.073) (1.154)

0.425 0.685 0.564 (0.963) (0.680) (1.315)

0.605 1.179 0.393 (1.866) (1.314) (0.747)

0.732 0.968 0.829 (1.300) (1.196) (1.388)

0.647 1.258 0.628 (2.533) (1.947) (2.256)

0.328 0.279 0.365 (1.513) (1.677) (1.682)

0.315 0.628 0.480 (1.271) (1.067) (1.038)

0.429 l.246 0.494 (3.749) (2.911) (3.633)

DISPLACEMENT (nun)

55.016 54.915 55.169 (55.728) (55.677) (55.728)

34.823 29.566 39.776 (33.249) (30.683) (39.014)

57.341 54.521 57.868 (56.109) (54.115) (55.950)

3.150 14.051 4.283 (27.857) (54.123) (16.553)

4.724 23.851 6.452 (35.255) (54.102) (23.749)

* = Cabinet Rocking Observed + = Cabinet Uplift Observed

A-27

WITHOUT ISOLATION

1.045*

(1.043)*+

1.928 (2.217)

0.895 (1.054)

l.834 (l.680)

1.146 (1.913)

3.049 (2.669)

0.513 (l.426)

2.700 (l.133)

3.587 (2.983)

54.966 (55.702)

N/A (N/A)

54.839 (53.473)

39.805 (49.363)

56.617 (79.553)

Page 188: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response ofIsolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

PACOIMADAM S74W GROUND LENGTH SCALE = 3

Table Horizontal

Raised Floor Horizontal

Cabinet Level 1 (C.M.) Horizontal

Cabinet Level 2 Horizontal

Cabinet Level 3 Horizontal

Cabinet Top Horizontal

Table Vertical

Raised Floor Vertical

Cabinet Top Vertical

Table Horizontal

Bearing Horizontal

Raised Floor Horizontal

Cabinet C.M. Horizontal W.R.T.

Raised Floor

Cabinet Top Horizontal W.R. T.

Raised Floor

ISOLATION ISOLATION ISOLATION SYSTEM 1 SYSTEM 2 SYSTEM 3

ACCELERATION (g)

0.832 0.858 0.841 (0.860)*+ (0.877)*+ (0.868)*+

0.525 0.904 0.520 (1.200) (0.979) (0.863)

0.472 0.553 0.671 (0.856) (0.671) (1.179)

0.689 1.024 0.458 (1.591) (1.263) (0.620)

0.981 1.018 0.903 (1.754) (1.439) (1.383)

0.752 1.228 0.682 (2.017) (1.993) (1.713)

0.322 0.353 0.398 (1.218) (1.421) (1.341)

0.645 0.451 0.467 (1.457) (1.210) (1.323)

0.462 0.864 0.542 (2.754) (2.996) (2.849)

DISPLACEMENT (rom)

37.821 37.897 37.719 (38.481) (38.481) (38.379)

23.825 23.673 29.362 (22.047) (22.301) (29.083)

41.269 36.043 37.783 (37.433) (35.859) (37.230)

3.437 8.325 3.459 (24.436) (13.572) (9.981)

4.953 12.294 5.258 (35.281) (22.631) (18.491)

* = Cabinet Rocking Observed + = Cabinet Uplift Observed

A-28

WITHOUT ISOLATION

0.887* (0.895)*+

1.833 (2.305)

0.757 (1.020)

1.009 (1.809)

1.388 (1.712)

1.774 (2.700)

0.396 (1.453)

0.383 (1.681)

2.143 (3.477)

37.694 (38.202)

N/A (N/A)

37.586 (35.839)

28.764 (47.985)

44.272 (62.611)

Page 189: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

PACOIMADAM S74W GROUND LENGTH SCALE == 4

Table Horizontal

Raised Floor Horizontal

Cabinet Level 1 (C.M.) Horizontal

Cabinet Level 2 Horizontal

Cabinet Level 3 Horizontal

Cabinet Top Horizontal

Table Vertical

Raised Floor Vertical

Cabinet Top Vertical

Table Horizontal

Bearing Horizontal

Raised Floor Horizontal

Cabinet C.M. Horizontal W.R.T.

Raised Floor

Cabinet Top Horizontal W.R.T.

Raised Floor

ISOLATION ISOLATION ISOLATION SYSTEM 1 SYSTEM 2 SYSTEM 3

ACCELERATION (g)

0.842 -- 0.781

(0.827)*+ (--) (0.801)*+

0.548 -- 0.532 (1.304) ( --) (0.712)

0.434 -- 0.571 (0.867) ( --) (l.268)

0.736 -- 0.378 (l.651) ( --) (0.701)

0.825 -- 0.841 (l.484) (--) (1.184)

0.762 -- 0.514 (l.824) (--) (1.369)

0.314 -- 0.345 (1.192) (--) (1.041)

-- -- 0.286 (--) ( --) (0.963)

0.762 -- 0.530 (3.002) (--) (2.445)

DISPLACEMENT (rrun)

29.007 -- 29.032 (29.743) (--) (29.667)

17.145 -- 22.022 (18.847) (--) (21.768)

30.715 -- 25.781 (26.753) (--) (27.184)

3.199 -- 3.096 (18.450) (--) (9.300)

5.004 -- 4.140 (29.870) (--) (16.154)

* == Cabinet Rocking Observed + = Cabinet Uplift Observed

A-29

WITHOUT ISOLATION

0.785* (0.794)*+

1.542 (l.967)

1.577 (1.535)

0.833 (0.957)

1.256 (1.430)

1.997 (2.064)

0.477 (1.224)

0.703 (1.189)

2.034 (2.247)

29.134 (29.820)

N/A (N/A)

29.185 (28.099)

18.958 (21.020)

34.874 (33.604)

Page 190: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

BELLCORE LENGTH SCALE = 1

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal -- -- 0.869 --( --) (0.906)* (0.873) (--)

Raised Floor -- -- 0.456 --Horizontal (--) (1.065) (0.459) ( --)

Cabinet Level 1 -- -- 0.425 --(C.M.) Horizontal (--) (0.827) (0.383) ( --)

Cabinet Level 2 -- -- 0.395 --Horizontal (--) (1.521) (0.512) (--)

Cabinet Level 3 -- -- 0.629 --Horizontal ( --) (1.254) (0.605) (--)

Cabinet Top -- -- 0.485 --Horizontal (--) (2.218) (0.592) ( --)

Table Vertical -- -- 0.134 --( --) (0.325) (0.333) (--)

Raised Floor -- -- 0.178 --Vertical ( --) (0.542) (0.427) (--)

Cabinet Top -- -- 0.225 --Vertical (--) (2.454) (0.473) ( --)

DISPLACEMENT (mm)

Table Horizontal -- -- 58.903 --( --) (58.979) (58.979) (--)

Bearing Horizontal -- -- 73.787 --( --) (54.000) (72.695) ( --)

Raised Floor -- -- 56.159 --Horizontal (--) (56.629) (55.264) ( --)

Cabinet C.M. -- -- 4.764 --Horizontal W.R.T. ( --) (49.197) (6.244) (--)

Raised Floor

Cabinet Top -- -- 6.325 --Horizontal W.R.T. (--) (74.778) (9.068) ( --)

Raised Floor

* = Cabinet Rocking Observed

A-30

Page 191: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

Table Horizontal

Raised Floor Horizontal

Cabinet Level I (C.M.) Horizontal

Cabinet Level 2 Horizontal

Cabinet Level 3 Horizontal

Cabinet Top Horizontal

Table Vertical

Raised Floor Vertical

Cabinet Top Vertical

Table Horizontal

Bearing Horizontal

Raised Floor Horizontal

Cabinet C.M. Horizontal W.RT.

Raised Floor

Cabinet Top Horizontal W.RT.

Raised Floor

BELLCORE LENGTH SCALE = 2

ISOLATION ISOLATION ISOLATION SYSTEM I SYSTEM 2 SYSTEM 3

ACCELERATION (g)

1.025 1.069 1.042 (1.032) (1.057) (1.031)

0.433 0.750 0.360 (0.412) (0.693) (0.357)

0.420 0.718 0.394 (0.426) (0.701) (0.434)

0.486 0.971 0.317 (0.571) (0.903) (0.356)

0.752 1.164 0.544 (0.788) (1.181) (0.542)

0.560 1.228 0.385 (0.592) (1.069) (0.493)

0.179 0.221 0.203 (0.337) (0.373) (0.372)

0.163 0.510 0.239 (0.347) (0.464) (0.364)

0.316 0.869 0.279 (0.594) (0.943) (0.536)

DISPLACEMENT (mm)

30.734 30.607 30.683 (30.709) (30.505) (30.810)

46.457 28.296 36.525 (46.660) (36.601) (38.837)

31.668 25.616 24.949 (36.297) (25.495) (25.375)

3.910 13.873 3.167 (4.177) (25.487) (3.388)

5.385 24.232 4.140 (7.137) (25.502) (4.115)

* = Cabinet Rocking Observed # = Cabinet Sliding Observed

A-31

WITHOUT ISOLATION

1.069* (1.062)*#

2.208 (2.089)

0.809 (0.903)

1.568 (1.696)

1.215 (1.239)

2.263 (2.396)

0.283 (0.384)

0.622 (2.258)

2.613 (3.069)

30.886 (30.861)

N/A (N/A)

30.994 (31.071)

117.483 (97.198)

121.564 (110.744)

Page 192: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion.

Table Horizontal

Raised Floor Horizontal

Cabinet Level 1 (C.M.) Horizontal

Cabinet Level 2 Horizontal

Cabinet Level 3 Horizontal

Cabinet Top Horizontal

Table Vertical

Raised Floor Vertical

Cabinet Top Vertical

Table Horizontal

Bearing Horizontal

Raised Floor Horizontal

Cabinet C.M. Horizontal W.RT.

Raised Floor

Cabinet Top Horizontal W.RT.

Raised Floor

BELLCORE LENGTH SCALE = 3

ISOLATION ISOLATION ISOLATION SYSTEM 1 SYSTEM 2 SYSTEM 3

ACCELERATION (g)

1.009 1.055 1.005 (1.016) (1.039) (1.014)

0.467 0.652 0.412 (0.494) (0.519) (0.374)

0.463 0.592 0.416 (0.455) (0.579) (0.418)

0.659 0.779 0.327 (0.624) (0.732) (0.326)

0.805 0.889 0.638 (0.866) (0.973) (0.712)

0.668 0.927 0.430 (0.670) (0.823) (0.477)

0.164 0.187 0.142 (0.353) (0.363) (0.362)

0.533 0.224 0.260 (0.709) (0.535) (0.378)

0.321 0.658 0.273 (0.776) (0.592) (0.605)

DISPLACEMENT (mm)

20.498 20.523 20.371 (20.676) (20.777) (20.853)

31.648 21.590 25.349 (33.503) (23.089) (27.203)

19.158 16.256 16.186 (26.238) (18.256) (17.196)

3.891 7.342 3.334 (3.969) (6.812) (3.158)

5.334 11.405 4.597 (6.553) (10.262) (4.064)

* = Cabinet Rocking Observed # = Cabinet Sliding Observed

A-32

WITHOUT ISOLATION

1.031 * (1.041)*#

1.820 (1.921)

1.093 (0.987)

1.427 (1.399)

1.188 (1.235)

2.262 (2.181)

0.292 (0.399)

1.125 (0.881)

2.481 (2.649)

20.676 (20.955)

N/A (N/A)

2l.298 (21.152)

67.782 (55.491)

97.892 (98.069)

Page 193: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response ofIsolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

BELLCORE LENGTH SCALE = 4

ISOLATION ISOLATION ISOLATION WIlliOUT SYSTEM I SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.972 -- 1.005 1.077* (0.984) (--) (0.996) (1.070)*

Raised Floor 0.528 -- 0.425 1.946

Horizontal (0.601) (--) (0.435) (1.761)

Cabinet Level I 0.457 -- 0.414 1.305

(C.M.) Horizontal (0.507) (--) (0.439) (1.463)

Cabinet Level 2 0.733 -- 0.323 0.915

Horizontal (0.779) ( --) (0.317) (0.932)

Cabinet Level 3 0.914 -- 0.658 1.392

Horizontal (1.013) (--) (0.728) (1.239)

Cabinet Top 0.775 -- 0.429 2.364

Horizontal (0.805) ( --) (0.540) (2.140)

Table Vertical 0.153 -- 0.153 0.329 (0.359) (--) (0.372) (0.458)

Raised Floor -- -- 0.183 0.558

Vertical (--) (--) (0.377) (0.749)

Cabinet Top 0.407 -- 0.308 2.361

Vertical (0.753) ( --) (0.637) (2.317)

DISPLACEMENT (mm)

Table Horizontal 15.240 -- 15.240 15.494 (15.570) ( --) (15.570) (15.926)

Bearing Horizontal 24.917 -- 18.720 N/A (25.908) (--) (20.320) (N/A)

Raised Floor 15.850 -- 10.967 16.415

Horizontal (20.447) ( --) (12.878) (16.478)

Cabinet C.M. 4.394 -- 3.369 68.732

Horizontal W.R.T. (4.485) (--) (2.959) (36.614)

Raised Floor

Cabinet Top 6.401 -- 4.801 106.020

Horizontal W.R.T. (7.315) (--) (3.785) (66.167)

Raised Floor

* = Cabinet Rocking Obselved

A-33

Page 194: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response ofIsolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

IBM LEVEL -1 LENGTH SCALE = 1

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal -- -- 0.429 --( --) (0.424) (0.426) (--)

Raised Floor -- -- 0.356 --Horizontal (--) (0.380) (0.348) (--)

Cabinet Level 1 -- -- 0.351 --(c. M.) Horizontal (--) (0.374) (0.336) ( --)

Cabinet Level 2 -- -- 0.396 --Horizontal (--) (0.396) (0.370) ( --)

Cabinet Level 3 -- -- 0.422 --Horizontal ( --) (0.441) (0.411) (--)

Cabinet Top -- -- 0.380 --Horizontal ( --) (0.432) (0.366) ( --)

Table Vertical -- -- 0.075 --(--) (0.201) (0.214) ( --)

Raised Floor -- -- 0.123 --Vertical ( --) (0.179) (0.204) ( --)

Cabinet Top -- -- 0.180 --Vertical ( --) (0.209) (0.227) ( --)

DISPLACEMENT (rrun)

Table Horizontal -- -- 55.550 --( --) (55.626) (55.524) (--)

Bearing Horizontal -- -- 61.493 --(--) (40.996) (60.046) (--)

Raised Floor -- -- 55.016 --Horizontal (--) (54.223) (55.239) ( --)

Cabinet C.M. -- -- 2.597 --Horizontal W.R T. (--) (2.378) (2.319) ( --)

Raised Floor

Cabinet Top -- -- 3.581 --Horizontal W.RT. (--) (5.258) (5.207) ( --)

Raised Floor

A-34

Page 195: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

IBM LEVEL - I LENGTH SCALE = 2

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM I SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.426 0.427 0.426 0.432* (0.432) (0.425) (0.437) (0.423)*

Raised Floor 0.310 0.349 0.283 1.209

Horizontal (0.301) (0.367) (0.289) (1.208)

Cabinet Level I 0.350 0.316 0.257 0.848

(C.M.) Horizontal (0.355) (0.318) (0.265) (0.846)

Cabinet Level 2 0.399 0.363 0.291 1.576

Horizontal (0.408) (0.420) (0.326) (1.579)

Cabinet Level 3 0.561 0.514 0.373 1.117

Horizontal (0.567) (0.505) (0.358) (1.088)

Cabinet Top 0.485 0.352 0.307 2.184

Horizontal (0.466) (0.389) (0.350) (2.293)

Table Vertical 0.063 0.077 0.084 0.206 (0.170) (0.181) (0.177) (0.266)

Raised Floor 0.048 0.061 0.069 0.476

Vertical (0.154) (0.164) (0.151) (0.453)

Cabinet Top 0.108 0.151 0.117 2.773

Vertical (0.220) (0.237) (0.211) (2.992)

DISPLACEMENT (rom)

Table Horizontal 28.143 28.016 28.042 28.321 (28.245) (28.143) (28.143) (28.296)

Bearing Horizontal 31.394 24.790 30.988 N/A (29.4l3) (27.102) (29.489) (N/A)

Raised Floor 33.414 29.489 28.969 28.169

Horizontal (33.528) (30.067) (29.636) (28.251)

Cabinet C.M. 2.561 2.494 1.576 82.493

Horizontal W.RT. (2.550) (30.067) (l.543) (8l.280)

Raised Floor

Cabinet Top 3.810 3.302 2.108 l32.029

Horizontal W.R.T. (5.080) (30.048) (3.277) (l31.699)

Raised Floor

* = Cabinet Rocking Observed

A-35

Page 196: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

IBM LEVEL-l LENGTH SCALE = 3

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.440 0.417 0.417 0.445* (0.440) (0.423) (0.415) (0.445)*

Raised Floor 0.372 0.328 0.282 1.145

Horizontal (0.365) (0.326) (0.287) (1.082)

Cabinet Level 1 0.364 0.281 0.254 0.788

(C.M.) Horizontal (0.376) (0.269) (0.253) (0.761)

Cabinet Level 2 0.466 0.326 0.320 1.454

Horizontal (0.491) (0.344) (0.326) (1.478)

Cabinet Level 3 0.643 0.523 0.428 1.247

Horizontal (0.693) (0.516) (0.414) (1.296)

Cabinet Top 0.461 0.346 0.317 2.019

Horizontal (0.496) (0.331) (0.336) (2.173)

Table Vertical 0.055 0.071 0.066 0.167 (0.168) (0.179) (0.176) (0.259)

Raised Floor 0.421 0.132 0.086 0.733

Vertical (0.536) (0.220) (0.191) (0.814)

Cabinet Top 0.138 0.131 0.145 2.420

Vertical (0.231) (0.219) (0.220) (2.299)

DISPLACEMENT (mm)

Table Horizontal 18.974 18.872 18.771 18.796 (19.025) (18.898) (18.923) (18.923)

Bearing Horizontal 19.914 20.295 20.676 N/A (18.644) (20.726) (21.438) (N/A)

Raised Floor 20.993 20.504 20.053 18.777

Horizontal (21.768) (21.171) (20.873) (18.904)

Cabinet C.M. 3.499 2.592 1.473 44.064

Horizontal W.R.T. (3.594) (2.605) (1.557) (45.401)

Raised Floor

Cabinet Top 5.207 3.607 2.108 75.870

Horizontal W.R.T. (5.258) (3.734) (2.718) (77.800)

Raised Floor

* = Cabinet Rocking Observed

A-36

Page 197: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

IBM LEVEL -1 LENGTH SCALE = 4

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.456 -- 0.441 0.439* (0.461) ( --) (0.446) (0.451)*

Raised Floor 0.347 -- 0.292 1.073

Horizontal (0.374) ( --) (0.317) (1.066)

Cabinet Level 1 0.371 -- 0.273 1.281

(C.M.) Horizontal (0.388) ( --) (0.267) (1.369)

Cabinet Level 2 0.452 -- 0.330 0.634

Horizontal (0.536) ( --) (0.379) (0.648)

Cabinet Level 3 0.776 -- 0.489 1.111

Horizontal (0.774) (--) (0.490) (1.095)

Cabinet Top 0.463 -- 0.368 1.798

Horizontal (0.481) (--) (0.413) (1.851)

Table Vertical 0.066 -- -- 0.146 (0.168) (--) (--) (0.272)

Raised Floor -- -- 0.098 0.482

Vertical ( --) (--) (0.187) (0.482)

Cabinet Top 0.150 -- 0.160 1.951

Vertical (0.280) ( --) (0.262) (1.768)

DISPLACEMENT (mm)

Table Horizontal 14.275 -- 14.046 14.275 (14.148) ( --) (13.995) (14.122)

Bearing Horizontal 15.189 -- 16.383 N/A (14.656) ( --) (17.018) (N/A)

Raised Floor 15.596 -- 15.151 14.135

Horizontal (18.307) (--) (15.831) (14.218)

Cabinet C.M. 3.686 -- 1.640 33.350

Horizontal W.R.T. (3.181) ( --) (1.756) (36.467)

Raised Floor

Cabinet Top 5.690 -- 2.337 58.039

Horizontal W.R.T. (4.953) (--) (2.743) (60.401)

Raised Floor

* = Cabinet Rocking Observed

A-37

Page 198: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

IBM LEVEL-2 LENGTH SCALE = 2

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.910 0.911 0.963 0.950* (0.918) (0.920) (1.075) (0.963)*

Raised Floor 0.351 0.889 0.416 2.278

Horizontal (0.408) (0.737) (0.480) (2.043)

Cabinet Level 1 0.345 0.682 0.391 1.088

(C.M.) Horizontal (0.370) (0.640) (0.465) (1.169)

Cabinet Level 2 0.476 0.923 0.442 2.010

Horizontal (0.494) (0.937) (0.642) (2.048)

Cabinet Level 3 0.608 1.023 0.552 1.305

Horizontal (0.657) (1.108) (0.548) (1.4l3)

Cabinet Top 0.476 0.993 0.428 2.717

Horizontal (0.513) (1.045) (0.624) (3.194)

Table Vertical 0.152 0.187 0.199 0.341 (0.386) (0.378) (0.512) (0.395)

Raised Floor 0.151 0.350 0.227 --Vertical (0.327) (0.447) (0.545) (3.279)

Cabinet Top 0.267 0.742 0.506 3.935

Vertical (0.491) (0.808) (0.824) (3.779)

DISPLACEMENT (mm)

Table Horizontal 46.685 46.482 46.533 46.584 (46.888) (46.736) (46.584) (46.711)

Bearing Horizontal 75.895 51.156 63.805 N/A (73.482) (50.902) (64.973) (N/A)

Raised Floor 59.804 48.222 43.548 46.584

Horizontal (58.579) (45.333) (45.491) (46.698)

Cabinet C.M. 2.889 10.620 2.499 158.582

Horizontal W.R. T. (3.153) (8.471) (3.069) (151.798)

Raised Floor

Cabinet Top 4.953 17.043 3.810 190.348

Horizontal W.R. T. (7.544) (13.640) (4.191) (171.806)

Raised Floor

* = Cabinet Rocking Observed

A-38

Page 199: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

IBM LEVEL -2 LENGTH SCALE = 3

Table Horizontal

Raised Floor Horizontal

Cabinet Level I (C.M.) Horizontal

Cabinet Level 2 Horizontal

Cabinet Level 3 Horizontal

Cabinet Top Horizontal

Table Vertical

Raised Floor Vertical

Cabinet Top Vertical

Table Horizontal

Bearing Horizontal

Raised Floor Horizontal

Cabinet C.M. Horizontal W.RT.

Raised Floor

Cabinet Top Horizontal W.RT.

Raised Floor

ISOLATION ISOLATION ISOLATION SYSTEM 1 SYSTEM 2 SYSTEM 3

ACCELERATION (g)

0.934 0.946 0.929 (0.928) (0.945) (0.942)

0.346 0.648 0.423 (0.442) (0.662) (0.469)

0.380 0.565 0.350 (0.417) (0.718) (0.388)

0.459 0.756 0.473 (0.567) (0.954) (0.565)

0.656 0.951 0.575 (0.611) (1.068) (0.597)

0.473 0.815 0.405 (0.551) (0.889) (0.494)

0.198 0.208 0.198 (0.347) (0.379) (0.383)

0.507 0.327 0.213 (0.686) (0.761) (0.385)

0.317 0.543 0.254 (0.581) (0.776) (0.656)

DISPLACEMENT (mm)

31.496 3l.471 31.267 (3l.445) (3l.420) (31.318)

55.524 36.271 4l.707 (52.832) (35.509) (42.520)

42.761 30.258 28.702 (42.793) (29.445) (28.848)

3.100 7.249 2.057 (3.462) (7.545) (2.492)

4.394 11.252 2.769 (5.817) (10.490) (2.896)

* = Cabinet Rocking Observed # = Cabinet Sliding Observed

A-39

WITHOUT ISOLATION

0.968* (0.978)*#

2.243 (2.557)

0.955 (0.910)

1.642 (1.725)

1.242 (1.314)

2.685 (3.090)

0.372 (0.471)

1.667 (1.928)

3.348 (3.730)

31.344 (31.547)

N/A (N/A)

31.560 (31.528)

75.222 (88.165)

129.972 (149.428)

Page 200: Study of Seismic Isolation Systems for Computer Floors

Recorded Peak Response of Isolated Raised Floor and Cabinet. Value in Parenthesis is for Combined Horizontal and Vertical Input Motion

IBM LEVEL-2 LENGTH SCALE = 4

ISOLATION ISOLATION ISOLATION WITHOUT SYSTEM 1 SYSTEM 2 SYSTEM 3 ISOLATION

ACCELERATION (g)

Table Horizontal 0.897 -- 0.899 0.950* (0.880) ( --) (0.920) (0.948)*

Raised Floor 0.273 -- 0.460 2.751

Horizontal (0.482) (--) (0.551) (2.040)

Cabinet Level I 0.403 -- 0.340 l.485

(C.M.) Horizontal (0.407) (--) (0.404) (1.520)

Cabinet Level 2 0.590 -- 0.487 0.879

Horizontal (0.584) (--) (0.526) (0.863)

Cabinet Level 3 0.663 -- 0.659 1.278

Horizontal (0.768) ( --) (0.751) (1.395)

Cabinet Top 0.585 -- 0.463 2.504

Horizontal (0.591) (--) (0.564) (2.515)

Table Vertical 0.208 -- -- 0.338 (0.390) (--) (--) (0.603)

Raised Floor -- -- 0.164 0.594

Vertical (--) (--) (0.352) (0.756)

Cabinet Top 0.257 -- 0.231 2.785

Vertical (0.648) ( --) (0.529) (2.928)

DISPLACEMENT (mm)

Table Horizontal 23.749 -- 23.597 23.800 (24.130) (--) (23.952) (24.181)

Bearing Horizontal 44.475 -- 32.080 N/A (43.078) (--) (32.283) (N/A)

Raised Floor 33.077 -- 2l.844 24.054

Horizontal (35.090) ( --) (2l.838) (24.022)

Cabinet C.M. 3.454 -- 2.505 58.393

Horizontal W.R.T. (3.705) (--) (2.665) (56.372)

Raised Floor

Cabinet Top 5.182 -- 3.099 95.504

Horizontal W.R.T. (6.045) (--) (3.048) (95.910)

Raised Floor

* = Cabinet Rocking Observed

A-40

Page 201: Study of Seismic Isolation Systems for Computer Floors

NATIONAL CENTER FOR EARTHQUAKE ENGINEERING RESEARCH LIST OF TECHNICAL REPORTS

The National Center for Earthquake Engineering Research (NCEER) publishes technical reports on a variety of subjects related to earthquake engineering written by authors funded through NCEER. These reports are available from both NCEER's Publications Department and the National Technical Information Service (NTIS). Requests for reports should be directed to the Publications Department, National Center for Earthquake Engineering Research, State University of New York at Buffalo, Red Jacket Quadrangle, Buffalo, New York 14261. Reports can also be requested through NTIS, 5285 Port Royal Road, Springfield, Virginia 22161. NTIS accession numbers are shown in parenthesis, if available.

NCEER-87-0001 "First-Year Program in Research, Education and Technology Transfer," 3/5/87, (PB88-134275).

NCEER-87-0002 "Experimental Evaluation ofInstantaneous Optimal Algorithms for Structural Control," by R.C. Lin, T.T. Soong and A.M. Reinhorn, 4/20/87, (PB88-134341).

NCEER-87-0003 "Experimentation Using the Earthquake Simulation Facilities at University at Buffalo," by A.M. Reinhorn and R.L. Ketter, to be published.

NCEER-87-0004 "The System Characteristics and Performance of a Shaking Table," by J.S. Hwang, K.C. Chang and G.C. Lee, 6/1/87, (PB88-134259). This report is available only through NTIS (see address given above).

NCEER-87-0005 "A Finite Element Formulation for Nonlinear Viscoplastic Material Using a Q Model," by O. Gyebi and G. Dasgupta, 11/2/87, (PB88-213764).

NCEER-87-0006 "Symbolic Manipulation Program (SMP) - Algebraic Codes for Two and Three Dimensional Finite Element Formulations," by X. Lee and G. Dasgupta, 11/9/87, (PB88-218522).

NCEER-87-0007 "Instantaneous Optimal Control Laws for Tall Buildings Under Seismic Excitations," by J.N. Yang, A. Akbarpour and P. Ghaemmaghami, 6/10/87, (PB88-134333). This report is only available through NTIS (see address given above).

NCEER-87-0008 "IDARC: Inelastic Damage Analysis of Reinforced Concrete Frame - Shear-Wall Structures," by Y.J. Park, A.M. Reinhorn and S.K. Kunnath, 7120/87, (PB88-134325).

NCEER-87-0009 "Liquefaction Potential for New York State: A Preliminary Report on Sites in Manhattan and Buffalo," by M. Budhu, V. Vijayakumar, R.F. Giese and L. Baumgras, 8/31/87, (PB88-163704). This report is available only through NTIS (see address given above).

NCEER-87-001O "Vertical and Torsional Vibration of Foundations in Inhomogeneous Media," by A.S. Veletsos and K.W. Dotson, 6/1/87, (PB88-134291).

NCEER-87-0011 "Seismic Probabilistic Risk Assessment and Seismic Margins Studies for Nuclear Power Plants," by Howard H.M. Hwang, 6/15/87, (PB88-134267).

NCEER-87-0012 "Parametric Studies of Frequency Response of Secondary Systems Under Ground-Acceleration Excitations," by Y. Yong and Y.K. Lin, 6/10/87, (PB88-134309).

NCEER-87-0013 "Frequency Response of Secondary Systems Under Seismic Excitation," by J.A. HoLung, J. Cai and Y.K. Lin, 7/31/87, (PB88-134317).

NCEER-87-0014 "Modelling Earthquake Ground Motions in Seismically Active Regions Using Parametric Time Series Methods," by G.W. Ellis and A.S. Cakmak, 8/25/87, (PB88-134283).

NCEER-87-0015 "Detection and Assessment of Seismic Structural Damage," by E. DiPasquale and A.S. Cakrnak, 8/25/87, (PB88-163712) .

B-1

Page 202: Study of Seismic Isolation Systems for Computer Floors

NCEER-87-0016 "Pipeline Experiment at Parkfield, California," by 1. Isenberg and E. Richardson, 9/15/87, (PB88-163720). This report is available only through NTIS (see address given above).

NCEER-87-0017 "Digital Simulation of Seismic Ground Motion," by M. Shinozuka, G. Deodatis and T. Harada, 8/31/87, (PB88-155197). This report is available only through NTIS (see address given above).

NCEER-87-0018 "Practical Considerations for Structural Control: System Uncertainty, System Time Delay and Truncation of Small Control Forces," J.N. Yang and A. Akbarpour, 8/10/87, (PB88-163738).

NCEER-87-0019 "Modal Analysis of Nonclassically Damped Structural Systems Using Canonical Transformation," by J.N. Yang, S. Sarkani and F.X. Long, 9/27/87, (PB88-187851).

NCEER-87-0020 "A Nonstationary Solution in Random Vibration Theory," by J.R. Red-Horse and P.D. Spanos, 11/3/87, (PB88-163746).

NCEER-87-0021 "Horizontal Impedances for Radially Inhomogeneous Viscoelastic Soil Layers," by A.S. Veletsos and K.W. Dotson, 10/15/87, (PB88-150859).

NCEER-87-0022 "Seismic Damage Assessment of Reinforced Concrete Members," by Y.S. Chung, C. Meyer and M. Shinozuka, 10/9/87, (PB88-150867). This report is available only through NTIS (see address given above).

NCEER-87-0023 "Active Structural Control in Civil Engineering," by T.T. Soong, 11/11/87, (PB88-187778).

NCEER-87-0024 "Vertical and Torsional Impedances for Radially Inhomogeneous Viscoelastic Soil Layers," by K.W. Dotson and A.S. Veletsos, 12/87, (PB88-187786).

NCEER-87-0025 "Proceedings from the Symposium on Seismic Hazards, Ground Motions, Soil-Liquefaction and Engineering Practice in Eastern North America," October 20-22, 1987, edited by K.H. Jacob, 12/87, (PB88-188115).

NCEER-87-0026 "Report on the Whittier-Narrows, California, Earthquake of October I, 1987," by J. Pantelic and A. Reinhorn, 11/87, (PB88-187752). This report is available only through NTIS (see address given above).

NCEER-87-0027 "Design of a Modular Program for Transient Nonlinear Analysis of Large 3-D Building Structures," by S. Srivastav and J.F. Abel, 12/30/87, (PB88-187950).

NCEER-87-0028 "Second-Year Program in Research, Education and Technology Transfer," 3/8/88, (PB88-219480).

NCEER-88-0001 "Workshop on Seismic Computer Analysis and Design of Buildings With Interactive Graphics," by W. McGuire, J.F. Abel and C.H. Conley, 1118/88, (PB88-187760).

NCEER-88-0002 "Optimal Control of Nonlinear Flexible Structures," by J.N. Yang, F.X. Long and D. Wong, 1/22/88, (PB88-213772).

NCEER-88-0003 "Substructuring Techniques in the Time Domain for Primary-Secondary Structural Systems," by G.D. Manolis and G. Juhn, 2/10/88, (PB88-213780).

NCEER-88-0004 "Iterative Seismic Analysis of Primary-Secondary Systems," by A. Singhal, L.D. Lutes and P.D. Spanos, 2/23/88, (PB88-213798).

NCEER-88-0005 "Stochastic Finite Element Expansion for Random Media," by P.D. Spanos and R. Ghanem, 3/14/88, (PB88-213806).

NCEER-88-0006 "Combining Structural Optimization and Structural Control," by F.Y. Cheng and C.P. Pantelides, 1110/88, (PB88-213814).

B-2

Page 203: Study of Seismic Isolation Systems for Computer Floors

NCEER-88-0007 "Seismic Performance Assessment of Code-Designed Structures," by H.H-M. Hwang, J-W. Jaw and H-J. Shau, 3/20/88, (PB88-219423).

NCEER-88-0008 "Reliability Analysis of Code-Designed Structures Under Natural Hazards," by H.H-M. Hwang, H. Ushiba and M. Shinozuka, 2/29/88, (PB88-229471).

NCEER-88-0009 "Seismic Fragility Analysis of Shear Wall Structures," by J-W Jaw and H.H-M. Hwang, 4/30/88, (PB89-102867).

NCEER-88-0010 "Base Isolation of a Multi-Story Building Under a Harmonic Ground Motion - A Comparison of Performances of Various Systems," by F-G Fan, G. Ahmadi and LG. Tadjbakhsh, 5/18/88, (PB89-122238).

NCEER-88-00l1 "Seismic Floor Response Spectra for a Combined System by Green's Functions," by F.M. Lavelle, L.A. Bergman and P.D. Spanos, 5/1/88, (PB89-102875).

NCEER-88-0012 "A New Solution Technique for Randomly Excited Hysteretic Structures," by G.Q. Cai and Y.K. Lin, 5/16/88, (PB89-102883).

NCEER-88-0013 "A Study of Radiation Damping and Soil-Structure Interaction Effects in the Centrifuge," by K. Weissman, supervised by J.H. Prevost, 5/24/88, (PB89-144703).

NCEER-88-0014 "Parameter Identification and Implementation of a Kinematic Plasticity Model for Frictional Soils," by J.H. Prevost and D. V. Griffiths, to be published.

NCEER-88-0015 "Two- and Three- Dimensional Dynamic Finite Element Analyses of the Long Valley Dam," by D.V. Griffiths and J.H. Prevost, 6/17/88, (PB89-144711).

NCEER-88-0016 "Damage Assessment of Reinforced Concrete Structures in Eastern United States," by A.M. Reinhorn, M.J. Seidel, S.K. Kunnath and Y.J. Park, 6/15/88, (PB89-122220).

NCEER-88-0017 "Dynamic Compliance of Vertically Loaded Strip Foundations in Multilayered Viscoelastic Soils," by S. Ahmad and A.S.M. Israil, 6/17/88, (PB89-102891).

NCEER-88-0018 "An Experimental Study of Seismic Structural Response With Added Viscoelastic Dampers," by R.C. Lin, Z. Liang, T. T. Soong and R.H. Zhang, 6/30/88, (PB89-122212). This report is available only through NTIS (see address given above).

NCEER-88-0019 "Experimental Investigation of Primary - Secondary System Interaction," by G.D. Manolis, G. Juhn and A.M. Reinhorn, 5/27/88, (PB89-122204).

NCEER-88-0020 "A Response Spectrum Approach For Analysis of Nonc1assically Damped Structures," by J.N. Yang, S. Sarkani and F.X. Long, 4122/88, (PB89-102909).

NCEER-88-002l "Seismic Interaction of Structures and Soils: Stochastic Approach," by A.S. Veletsos and A.M. Prasad, 7/21/88, (PB89-122196).

NCEER-88-0022 "Identification of the Serviceability Limit State and Detection of Seismic Structural Damage," by E. DiPasquale and A.S. Cakmak, 6/15/88, (PB89-122188). This report is available only through NTIS (see address given above).

NCEER-88-0023 "Multi-Hazard Risk Analysis: Case of a Simple Offshore Structure," by B.K. Bhartia and E.H. Vanmarcke, 7/21/88, (PB89-145213).

NCEER-88-0024 "Automated Seismic Design of Reinforced Concrete Buildings," by Y.S. Chung, C. Meyer and M. Shinozuka, 7/5/88, (PB89-122170). This report is available only through NTIS (see address given above).

B-3

Page 204: Study of Seismic Isolation Systems for Computer Floors

NCEER-88-0025 "Experimental Study of Active Control of MDOF Structures Under Seismic Excitations," by L.L. Chung, R.C. Lin, T.T. Soong and A.M. Reinhorn, 7/10/88, (PB89-122600).

NCEER-88-0026 "Earthquake Simulation Tests of a Low-Rise Metal Structure," by I.S. Hwang, K.c. Chang, G.c. Lee and R.L. Ketter, 8/1/88, (PB89-102917).

NCEER-88-0027 "Systems Study of Urban Response and Reconstruction Due to Catastrophic Earthquakes," by F. Kozin and H.K. Zhou, 9/22/88, (PB90-162348).

NCEER-88-0028 "Seismic Fragility Analysis of Plane Frame Structures," by H.H-M. Hwang and Y.K. Low, 7/31/88, (PB89-131445).

NCEER-88-0029 "Response Analysis of Stochastic Structures," by A. Kardara, C. Bucher and M. Shinozuka, 9/22/88, (PB89-174429).

NCEER-88-0030 "Nonnormal Accelerations Due to Yielding in a Primary Structure," by D.C.K. Chen and L.D. Lutes, 9/19/88, (PB89-131437).

NCEER-88-0031 "Design Approaches for Soil-Structure Interaction," by A.S. Veletsos, A.M. Prasad and Y. Tang, 12/30/88, (PB89-174437). This report is available only through NTIS (see address given above).

NCEER-88-0032 "A Re-evaluation of Design Spectra for Seismic Damage Control," by C.L Turkstra and A.G. Tallin, 11/7/88, (PB89-145221).

NCEER-88-0033 "The Behavior and Design of Noncontact Lap Splices Subjected to Repeated Inelastic Tensile Loading," by V.E. Sagan, P. Gergely and R.N. White, 12/8/88, (PB89-163737).

NCEER-88-0034 "Seismic Response of Pile Foundations," by S.M. Mamoon, P.K. Banerjee and S. Ahmad, 11/1/88, (PB89-145239).

NCEER-88-0035 "Modeling of R/C Building Structures With Flexible Floor Diaphragms (IDARC2)," by A.M. Reinhorn, S.K. Kunnath and N. Panahshahi, 9/7/88, (PB89-207153).

NCEER-88-0036 "Solution of the Dam-Reservoir Interaction Problem Using a Combination of FEM, BEM with Particular Integrals, Modal Analysis, and Substructuring," by C-S. Tsai, G.C. Lee and R.L. Ketter, 12/31/88, (PB89-207146).

NCEER-88-0037 "Optimal Placement of Actuators for Structural Control," by F. Y. Cheng and C.P. Pantelides, 8/15/88, (PB89-162846).

NCEER-88-0038 "Teflon Bearings in Aseismic Base Isolation: Experimental Studies and Mathematical Modeling," by A. Mokha, M.C. Constantinou and A.M. Reinhorn, 12/5/88, (PB89-218457). This report is available only through NTIS (see address given above).

NCEER-88-0039 "Seismic Behavior of Flat Slab High-Rise Buildings in the New York City Area," by P. Weidlinger and M. Ettouney, 10/15/88, (PB90-145681).

NCEER-88-0040 "Evaluation of the Earthquake Resistance of Existing Buildings in New York City," by P. Weidlinger and M. Ettouney, 10/15/88, to be published.

NCEER-88-0041 "Small-Scale Modeling Techniques for Reinforced Concrete Structures Subjected to Seismic Loads," by W. Kim, A. El-Attar and R.N. White, 11/22/88, (PB89-189625).

NCEER-88-0042 "Modeling Strong Ground Motion from Multiple Event Earthquakes," by G.W. Ellis and A.S. Cakmak, 10/15/88, (PB89-174445).

B-4

Page 205: Study of Seismic Isolation Systems for Computer Floors

NCEER-88-0043 "Nonstationary Models of Seismic Ground Acceleration," by M. Grigoriu, S.E. Ruiz and E. Rosenblueth, 7/15/88, (PB89-189617).

NCEER-88-0044 "SARCF User's Guide: Seismic Analysis of Reinforced Concrete Frames," by Y.S. Chung, C. Meyer and M. Shinozuka, 11/9/88, (PB89-174452).

NCEER-88-0045 "First Expert Panel Meeting on Disaster Research and Planning," edited by J. Pantelic and J. Stoyle, 9/15/88, (PB89-174460).

NCEER-88-0046 "Preliminary Studies of the Effect of Degrading Infill Walls on the Nonlinear Seismic Response of Steel Frames," by C.Z. Chrysostomou, P. Gergely and J.F. Abel, 12/19/88, (PB89-208383).

NCEER-88-0047 "Reinforced Concrete Frame Component Testing Facility - Design, Construction, Instrumentation and Operation," by S.P. Pessiki, C. Conley, T. Bond, P. Gergely and R.N. White, 12/16/88, (PB89-174478).

NCEER-89-OOO1 "Effects of Protective Cushion and Soil Compliancy on the Response of Equipment Within a Seismically Excited Building," by J.A. HoLung, 2/16/89, (PB89-207179).

NCEER-89-0002 "Statistical Evaluation of Response Modification Factors for Reinforced Concrete Structures," by H.H-M. Hwang and J-W. Jaw, 2117/89, (PB89-207187).

NCEER-89-0003 "Hysteretic Columns Under Random Excitation," by G-Q. Cai and Y.K. Lin, 1/9/89, (PB89-196513).

NCEER-89-0004 "Experimental Study of 'Elephant Foot Bulge' Instability of Thin-Walled Metal Tanks," by Z-H. Jia and R.L. Ketter, 2/22/89, (PB89-207195).

NCEER-89-0005 "Experiment on Performance of Buried Pipelines Across San Andreas Fault," by J. Isenberg, E. Richardson and T.D. O'Rourke, 3110/89, (PB89-218440). This report is available only through NTIS (see address given above).

NCEER-89-0006 "A Knowledge-Based Approach to Structural Design of Earthquake-Resistant Buildings," by M. Subramani, P. Gergely, C.H. Conley, J.F. Abel and A.H. Zaghw, 1/15/89, (PB89-218465).

NCEER-89-0007 "Liquefaction Hazards and Their Effects on Buried Pipelines," by T.D. O'Rourke and P.A. Lane, 2/1/89, (PB89-218481).

NCEER-89-0008 "Fundamentals of System Identification in Structural Dynamics," by H. Imai, C-B. Yun, O. Maruyama and M. Shinozuka, 1/26/89, (PB89-2072 11).

NCEER-89-0009 "Effects of the 1985 Michoacan Earthquake on Water Systems and Other Buried Lifelines in Mexico," by A.G. Ayala and M.J. O'Rourke, 3/8/89, (PB89-207229).

NCEER-89-ROlO "NCEER Bibliography of Earthquake Education Materials," by K.E.K. Ross, Second Revision, 9/1/89, (PB90-125352) .

NCEER-89-0011 "Inelastic Three-Dimensional Response Analysis of Reinforced Concrete Building Structures (IDARC-3D), Part I - Modeling," by S.K. Kunnath and A.M. Reinhorn, 4117/89, (PB90-114612).

NCEER-89-0012 "Recommended Modifications to ATC-14," by C.D. Poland and J.O. Malley, 4/12/89, (PB90-108648).

NCEER-89-0013 "Repair and Strengthening of Beam-to-Column Connections Subjected to Earthquake Loading," by M. Corazao and A.J. Durrani, 2/28/89, (PB90-109885).

NCEER-89-0014 "Program EXKAL2 for Identification of Structural Dynamic Systems," by O. Maruyama, C-B. Yun, M. Hoshiya and M. Shinozuka, 5/19/89, (PB90-109877).

B-5

Page 206: Study of Seismic Isolation Systems for Computer Floors

NCEER-89-0015 "Response of Frames With Bolted Semi-Rigid Connections, Part I - Experimental Study and Analytical Predictions," by P.J. DiCorso, A.M. Reinhorn, J.R. Dickerson, J.B. Radziminski and W.L. Harper, 6/1/89, to be published.

NCEER-89-0016 "ARMA Monte Carlo Simulation III Probabilistic Structural Analysis," by P.D. Spanos and M.P. Mignolet, 7/10/89, (PB90-109893).

NCEER-89-P017 "Preliminary Proceedings from the Conference on Disaster Preparedness - The Place of Earthquake Education in Our Schools," Edited by K.E.K. Ross, 6/23/89, (PB90-108606).

NCEER-89-00l7 "Proceedings from the Conference on Disaster Preparedness - The Place of Earthquake Education in Our Schools," Edited by K.E.K. Ross, 12/31/89, (PB90-207895). This report is available only through NTIS (see address given above).

NCEER-89-0018 "Multidimensional Models of Hysteretic Material Behavior for Vibration Analysis of Shape Memory Energy Absorbing Devices, by E.J. Graesser and F.A. Cozzarelli, 6/7/89, (PB90-164146).

NCEER-89-0019 "Nonlinear Dynamic Analysis of Three-Dimensional Base Isolated Structures (3D-BASIS)," by S. Nagarajaiah, A.M. Reinhorn and M.e. Constantinou, 8/3/89, (PB90-161936). This report is available only through NTIS (see address given above).

NCEER-89-0020 "Structural Control Considering Time-Rate of Control Forces and Control Rate Constraints," by F.Y. Cheng and C.P. Pantel ides, 8/3/89, (PB90-120445).

NCEER-89-0021 "Subsurface Conditions of Memphis and Shelby County," by K.W. Ng, T-S. Chang and H-H.M. Hwang, 7/26/89, (PB90-120437).

NCEER-89-0022 "Seismic Wave Propagation Effects on Straight Jointed Buried Pipelines," by K. Elhmadi and M.L O'Rourke, 8/24/89, (PB90-162322).

NCEER-89-0023 "Workshop on Serviceability Analysis of Water Delivery Systems," edited by M. Grigoriu, 3/6/89, (PB90-127424).

NCEER-89-0024 "Shaking Table Study of a 1/5 Scale Steel Frame Composed of Tapered Members," by K.C. Chang, J.S. Hwang and G.C. Lee, 9/18/89, (PB90-160169).

NCEER-89-0025 "DYNAID: A Computer Program for Nonlinear Seismic Site Response Analysis - Technical Documentation," by Jean H. Prevost, 9/14/89, (PB90-161944). This report is available only through NTIS (see address given above).

NCEER-89-0026 "1:4 Scale Model Studies of Active Tendon Systems and Active Mass Dampers for Aseismic Protection," by A.M. Reinhorn, T.T. Soong, R.C. Lin, Y.P. Yang, Y. Fukao, H. Abe and M. Nakai, 9/15/89, (PB90-173246).

NCEER-89-0027 "Scattering of Waves by Inclusions in a Nonhomogeneous Elastic Half Space Solved by Boundary Element Methods," by P.K. Hadley, A. Askar and A.S. Cakmak, 6/15/89, (PB90-145699).

NCEER-89-0028 "Statistical Evaluation of Deflection Amplification Factors for Reinforced Concrete Structures," by H.H.M. Hwang, J-W. Jaw and A.L. Ch'ng, 8/31/89, (PB90-164633).

NCEER-89-0029 "Bedrock Accelerations in Memphis Area Due to Large New Madrid Earthquakes," by H.H.M. Hwang, e.H.S. Chen and G. Yu, 11/7/89, (PB90-162330).

NCEER-89-0030 "Seismic Behavior and Response Sensitivity of Secondary Structural Systems," by Y.Q. Chen and T.T. Soong, 10/23/89, (PB90-164658).

B-6

Page 207: Study of Seismic Isolation Systems for Computer Floors

NCEER-89-0031 "Random Vibration and Reliability Analysis of Primary-Secondary Structural Systems," by Y. Ibrahim, M. Grigoriu and T.T. Soong, 11/10/89, (PB90-16l951).

NCEER-89-0032 "Proceedings from the Second U.S. - Japan Workshop on Liquefaction, Large Ground Deformation and Their Effects on Lifelines, September 26-29, 1989," Edited by T.D. O'Rourke and M. Hamada, 12/1/89, (PB90-209388).

NCEER-89-0033 "Deterministic Model for Seismic Damage Evaluation of Reinforced Concrete Structures," by J .M. Bracci, A.M. Reinhorn, J.B. Mander and S.K. Kunnath, 9/27/89.

NCEER-89-0034 "On the Relation Between Local and Global Damage Indices," by E. DiPasquale and A.S. Cakmak, 8/15/89, (PB90-173865).

NCEER-89-0035 "Cyclic Undrained Behavior of Nonplastic and Low Plasticity Silts," by A.I. Walker and H.E. Stewart, 7/26/89, (PB90-l83518).

NCEER-89-0036 "Liquefaction Potential of Surficial Deposits in the City of Buffalo, New York," by M. Budhu, R. Giese and L. Baumgrass, 1/17/89, (PB90-208455).

NCEER-89-0037 "A Deterministic Assessment of Effects of Ground Motion Incoherence," by A.S. Veletsos and Y. Tang, 7/15/89, (PB90-164294).

NCEER-89-0038 "Workshop on Ground Motion Parameters for Seismic Hazard Mapping," July 17-18, 1989, edited by R.V. Whitman, 12/1/89, (PB90-173923).

NCEER-89-0039 "Seismic Effects on Elevated Transit Lines of the New York City Transit Authority," by C.J. Costantino, C.A. Miller and E. Heymsfield, 12/26/89, (PB90-207887).

NCEER-89-0040 "Centrifugal Modeling of Dynamic Soil-Structure Interaction," by K. Weissman, Supervised by J.H. Prevost, 5/10/89, (PB90-207879).

NCEER-89-0041 "Linearized Identification of Buildings With Cores for Seismic Vulnerability Assessment," by I-K. Ho and A.E. Aktan, 11/1/89, (PB90-251943).

NCEER-90-0001 "Geotechnical and Lifeline Aspects of the October 17, 1989 Lorna Prieta Earthquake in San Francisco," by T.D. O'Rourke, H.E. Stewart, F.T. Blackburn and T.S. Dickerman, 1/90, (PB90-208596).

NCEER-90-0002 "Nonnormal Secondary Response Due to Yielding in a Primary Structure," by D.C.K. Chen and L.D. Lutes, 2/28/90, (PB90-251976).

NCEER-90-0003 "Earthquake Education Materials for Grades K-12," by K.E.K. Ross, 4/16/90, (PB91-251984).

NCEER-90-0004 "Catalog of Strong Motion Stations in Eastern North America," by R.W. Busby, 4/3/90, (PB90-251984).

NCEER-90-0005 "NCEER Strong-Motion Data Base: A User Manual for the GeoBase Release (Version 1.0 for the Sun3)," by P. Friberg and K. Jacob, 3/31/90 (PB90-258062).

NCEER-90-0006 "Seismic Hazard Along a Crude Oil Pipeline in the Event of an 1811-1812 Type New Madrid Earthquake," by H.H.M. Hwang and C-H.S. Chen, 4/16/90(PB90-258054).

NCEER-90-0007 "Site-Specific Response Spectra for Memphis Sheahan Pumping Station," by H.H.M. Hwang and C.S. Lee, 5/15/90, (PB91-108811).

NCEER-90-0008 "Pilot Study on Seismic Vulnerability of Crude Oil Transmission Systems," by T. Ariman, R. Dobry, M. Grigoriu, F. Kozin, M. O'Rourke, T. O'Rourke and M. Shinozuka, 5/25/90, (PB91-108837).

B-7

Page 208: Study of Seismic Isolation Systems for Computer Floors

NCEER-90-0009 "A Program to Generate Site Dependent Time Histories: EQGEN, " by G.W. Ellis, M. Srinivasan and A.S. Cakmak, 1130/90, (PB91-108829).

NCEER-90-001O "Active Isolation for Seismic Protection of Operating Rooms," by M.E. Talbott, Supervised by M. Shinozuka, 6/8/9, (PB91-110205).

NCEER-90-0011 "Program LINEARID for Identification of Linear Structural Dynamic Systems," by C-B. Yun and M. Shinozuka, 6/25/90, (PB91-110312).

NCEER-90-0012 "Two-Dimensional Two-Phase Elasto-P1astic Seismic Response of Earth Dams," by A.N. Yiagos, Supervised by LH. Prevost, 6/20/90, (PB91-110197).

NCEER-90-0013 "Secondary Systems in Base-Isolated Structures: Experimental Investigation, Stochastic Response and Stochastic Sensitivity," by G.D. Manolis, G. Juhn, M.C. Constantinou and A.M. Reinhorn, 7/1/90, (PB91-110320).

NCEER-90-0014 "Seismic Behavior of Lightly-Reinforced Concrete Column and Beam-Column Joint Details," by S.P. Pessiki, C.H. Conley, P. Gergely and R.N. White, 8122/90, (PB91-108795).

NCEER-90-0015 "Two Hybrid Control Systems for Building Structures Under Strong Earthquakes," by J.N. Yang and A. Danielians, 6/29/90, (PB91-125393).

NCEER-90-0016 "Instantaneous Optimal Control with Acceleration and Velocity Feedback," by LN. Yang and Z. Li, 6/29/90, (PB91-125401).

NCEER-90-0017 "Reconnaissance Report on the Northern Iran Earthquake of June 21, 1990," by M. Mehrain, 10/4/90, (PB91-125377).

NCEER-90-0018 "Evaluation of Liquefaction Potential in Memphis and Shelby County," by T.S. Chang, P.S. Tang, C.S. Lee and H. Hwang, 8/10/90, (PB91-125427).

NCEER-90-0019 "Experimental and Analytical Study of a Combined Sliding Disc Bearing and Helical Steel Spring Isolation System," by M.C. Constantinou, A.S. Mokha and A.M. Reinhorn, 10/4/90, (PB91-125385).

NCEER-90-0020 "Experimental Study and Analytical Prediction of Earthquake Response of a Sliding Isolation System with a Spherical Surface," by A.S. Mokha, M.e. Constantinou and A.M. Reinhorn, 10/11/90, (PB91-125419).

NCEER-90-0021 "Dynamic Interaction Factors for Floating Pile Groups," by G. Gazetas, K. Fan, A. Kaynia and E. Kausel, 9/10/90, (PB91-170381).

NCEER-90-0022 "Evaluation of Seismic Damage Indices for Reinforced Concrete Structures," by S. Rodriguez-Gomez and A.S. Cakmak, 9/30/90, PB91-171322).

NCEER-90-0023 "Study of Site Response at a Selected Memphis Site," by H. Desai, S. Ahmad, E.S. Gazetas and M.R. Oh, 10/11/90, (PB91-196857).

NCEER-90-0024 "A User's Guide to Strongmo: Version 1.0 of NCEER's Strong-Motion Data Access Tool for PCs and Terminals," by P.A. Friberg and C.A.T. Susch, 11/15/90, (PB91-171272).

NCEER-90-0025 "A Three-Dimensional Analytical Study of Spatial Variability of Seismic Ground Motions," by L-L. Hong and A.H.-S. Ang, 10/30/90, (PB91-170399).

NCEER-90-0026 "MUMOID User's Guide - A Program for the Identification of Modal Parameters," by S. Rodriguez­Gomez and E. DiPasquale, 9/30/90, (PB91-171298).

NCEER-90-0027 "SARCF-II User's Guide - Seismic Analysis of Reinforced Concrete Frames," by S. Rodriguez-Gomez, Y.S. Chung and C. Meyer, 9/30/90, (PB91-171280).

B-8

Page 209: Study of Seismic Isolation Systems for Computer Floors

NCEER-90-0028 "Viscous Dampers: Testing, Modeling and Application in Vibration and Seismic Isolation," by N. Makris and M.C. Constantinou, 12/20/90 (PB91-190561).

NCEER-90-0029 "Soil Effects on Earthquake Ground Motions in the Memphis Area," by H. Hwang, C.S. Lee, K. W. Ng and T.S. Chang, 8/2/90, (PB91-190751).

NCEER-91-0001 "Proceedings from the Third Japan-U.S. Workshop on Earthquake Resistant Design of Lifeline Facilities and Countermeasures for Soil Liquefaction, December 17-19, 1990," edited by T.D. O'Rourke and M. Hamada, 2/1/91, (PB91-179259).

NCEER-91-0002 "Physical Space Solutions of Non-Proportionally Damped Systems," by M. Tong, Z. Liang and G.c. Lee, 1/15/91, (PB91-179242). .

NCEER-91-0003 "Seismic Response of Single Piles and Pile Groups," by K. Fan and G. Gazetas, 1/10/91, (PB92-174994).

NCEER-91-0004 "Damping of Structures: Part 1 - Theory of Complex Damping," by Z. Liang and G. Lee, 10/10/91, (PB92-197235) .

NCEER-91-0005 "3D-BASIS - Nonlinear Dynamic Analysis of Three Dimensional Base Isolated Structures: Part II," by S. Nagarajaiah, A.M. Reinhorn and M.C. Constantinou, 2/28/91, (PB91-190553).

NCEER-91-0006 "A Multidimensional Hysteretic Model for Plasticity Deforming Metals in Energy Absorbing Devices," by E.J. Graesser and F.A. CozzareIIi, 4/9/91, (PB92-108364).

NCEER-91-0007 "A Framework for Customizable Knowledge-Based Expert Systems with an Application to a KBES for Evaluating the Seismic Resistance of Existing Buildings," by E.G. Ibarra-Anaya and S.J. Fenves, 4/9/91, (PB91-210930).

NCEER-91-0008 "Nonlinear Analysis of Steel Frames with Semi-Rigid Connections Using the Capacity Spectrum Method," by G.G. Deierlein, S-H. Hsieh, Y-J. Shen and J.F. Abel, 7/2/91, (PB92-113828).

NCEER-91-0009 "Earthquake Education Materials for Grades K-12," by K.E.K. Ross, 4/30/91, (PB91-212142).

NCEER-91-001O "Phase Wave Velocities and Displacement Phase Differences in a Harmonically Oscillating Pile," by N. Makris and G. Gazetas, 7/8/91, (PB92-108356).

NCEER-91-0011 "Dynamic Characteristics of a Full-Size Five-Story Steel Structure and a 2/5 Scale Model," by K.C. Chang, G.C. Yao, G.C. Lee, D.S. Hao and Y.C. Yeh," 7/2/91, (PB93-116648).

NCEER-91-0012 "Seismic Response of a 2/5 Scale Steel Structure with Added Viscoelastic Dampers," by K.C. Chang, T.T. Soong, S-T. Oh and M.L. Lai, 5/17/91, (PB92-110816).

NCEER-91-0013 "Earthquake Response of Retaining Walls; Full-Scale Testing and Computational Modeling," by S. AlampaIli and A-W.M. Elgamal, 6/20/91, to be published.

NCEER-91-0014 "3D-BASIS-M: Nonlinear Dynamic Analysis of Multiple Building Base Isolated Structures," by P.C. Tsopelas, S. Nagarajaiah, M.C. Constantinou and A.M. Reinhorn, 5/28/91, (pB92-113885).

NCEER-91-0015 "Evaluation of SEAOC Design Requirements for Sliding Isolated Structures," by D. Theodossiou and M.C. Constantinou, 6/10/91, (PB92-1l4602).

NCEER-91-0016 "Closed-Loop Modal Testing of a 27-Story Reinforced Concrete Flat Plate-Core Building," by H.R. Somaprasad, T. Toksoy, H. Yoshiyuki and A.E. Aktan, 7/15/91, (PB92-129980).

NCEER-91-0017 "Shake Table Test of a 1/6 Scale Two-Story Lightly Reinforced Concrete Building," by A.G. El-Attar, R.N. White and P. Gergely, 2/28/91, (PB92-222447).

B-9

Page 210: Study of Seismic Isolation Systems for Computer Floors

NCEER-91-0018 "Shake Table Test of a 1/8 Scale Three-Story Lightly Reinforced Concrete Building," by A.G. El-Attar, R.N. White and P. Gergely, 2/28/91, (PB93-116630).

NCEER-91-0019 "Transfer Functions for Rigid Rectangular Foundations," by A.S. Veletsos, A.M. Prasad and W.H. Wu, 7/31/91.

NCEER-91-0020 "Hybrid Control of Seismic-Excited Nonlinear and Inelastic Structural Systems," by J.N. Yang, Z. Li and A. Danielians, 8/1/91, (PB92-143171).

NCEER-91-0021 "The NCEER-91 Earthquake Catalog: Improved Intensity-Based Magnitudes and Recurrence Relations for U.S. Earthquakes East of New Madrid," by L. Seeber and J.G. Armbruster, 8/28/91, (PB92-176742).

NCEER-91-0022 "Proceedings from the Implementation of Earthquake Planning and Education in Schools: The Need for Change - The Roles of the Changemakers," by K.E.K. Ross and F. Winslow, 7/23/91, (PB92-129998).

NCEER-91-0023 "A Study of Reliability-Based Criteria for Seismic Design of Reinforced Concrete Frame Buildings," by H.H.M. Hwang and H-M. Hsu, 8/10/91, (PB92-140235).

NCEER-91-0024 "Experimental Verification of a Number of Structural System Identification Algorithms," by R.G. Ghanem, H. Gavin and M. Shinozuka, 9/18/91, (PB92-176577).

NCEER-91-0025 "Probabilistic Evaluation of Liquefaction Potential," by H.H.M. Hwang and C.S. Lee," 11125/91, (PB92-143429).

NCEER-91-0026 "Instantaneous Optimal Control for Linear, Nonlinear and Hysteretic Structures - Stable Controllers," by J.N. Yang and Z. Li, 11/15/91, (PB92-163807).

NCEER-91-0027 "Experimental and Theoretical Study of a Sliding Isolation System for Bridges," by M.C. Constantinou, A. Kartoum, A.M. Reinhorn and P. Bradford, 11/15/91, (PB92-176973).

NCEER-92-0001 "Case Studies of Liquefaction and Lifeline Performance During Past Earthquakes, Volume 1: Japanese Case Studies," Edited by M. Hamada and T. O'Rourke, 2/17/92, (PB92-197243).

NCEER-92-0002 "Case Studies of Liquefaction and Lifeline Performance During Past Earthquakes, Volume 2: United States Case Studies," Edited by T. O'Rourke and M. Hamada, 2117/92, (PB92-197250).

NCEER-92-0003 "Issues in Earthquake Education," Edited by K. Ross, 2/3/92, (PB92-222389).

NCEER-92-0004 "Proceedings from the First U.S. - Japan Workshop on Earthquake Protective Systems for Bridges," Edited by I.G. Buckle, 2/4/92, (PB94-142239, A99, MF-A06).

NCEER-92-0005 "Seismic Ground Motion from a Haskell-Type Source in a Multiple-Layered Half-Space," A.P. Theoharis, G. Deodatis and M. Shinozuka, 112/92, to be published.

NCEER-92-0006 "Proceedings from the Site Effects Workshop," Edited by R. Whitman, 2/29/92, (PB92-197201).

NCEER-92-0007 "Engineering Evaluation of Permanent Ground Deformations Due to Seismically-Induced Liquefaction," by M.H. Baziar, R. Dobry and A-W.M. Elgamal, 3/24/92, (PB92-222421).

NCEER-92-0008 "A Procedure for the Seismic Evaluation of Buildings in the Central and Eastern United States," by C.D. Poland and J.O. Malley, 4/2/92, (PB92-222439).

NCEER-92-0009 "Experimental and Analytical Study of a Hybrid Isolation System Using Friction Controllable Sliding Bearings," by M.Q. Feng, S. Fujii and M. Shinozuka, 5/15/92, (PB93-150282).

NCEER-92-0010 "Seismic Resistance of Slab-Column Connections in Existing Non-Ductile Flat-Plate Buildings," by AJ. Durrani and Y. Du, 5/18/92.

B-lO

Page 211: Study of Seismic Isolation Systems for Computer Floors

NCEER-92-0011 "The Hysteretic and Dynamic Behavior of Brick Masonry Walls Upgraded by Ferrocement Coatings Under Cyclic Loading and Strong Simulated Ground Motion," by H. Lee and S.P. Prawel, 5/11192, to be published.

NCEER-92-0012 "Study of Wire Rope Systems for Seismic Protection of Equipment in Buildings," by G.F. Demetriades, M.C. Constantinou and A.M. Reinhorn, 5/20/92.

NCEER-92-0013 "Shape Memory Structural Dampers: Material Properties, Design and Seismic Testing," by P.R. Witting and F.A. Cozzarelli, 5/26/92.

NCEER-92-0014 "Longitudinal Permanent Ground Deformation Effects on Buried Continuous Pipelines," by M.J. O'Rourke, and C. Nordberg, 6/15/92.

NCEER-92-0015 "A Simulation Method for Stationary Gaussian Random Functions Based on the Sampling Theorem," by M. Grigoriu and S. Balopoulou, 6/11192, (PB93-127496).

NCEER-92-0016 "Gravity-Load-Designed Reinforced Concrete Buildings: Seismic Evaluation of Existing Construction and Detailing Strategies for Improved Seismic Resistance," by G.W. Hoffmann, S.K. Kunnath, A.M. Reinhorn and J.B. Mander, 7/15/92, (PB94-142007, A08, MF-A02).

NCEER-92-00l7 "Observations on Water System and Pipeline Performance in the Lim6n Area of Costa Rica Due to the April 22, 1991 Earthquake," by M. O'Rourke and D. Ballantyne, 6/30/92, (PB93-126811).

NCEER-92-0018 "Fourth Edition of Earthquake Education Materials for Grades K-12," Edited by K.E.K. Ross, 8/10/92.

NCEER-92-0019 "Proceedings from the Fourth Japan-U.S. Workshop on Earthquake Resistant Design of Lifeline Facilities and Countermeasures for Soil Liquefaction," Edited by M. Hamada and T.D. O'Rourke, 8/12/92, (PB93-163939).

NCEER-92-0020 "Active Bracing System: A Full Scale Implementation of Active Control," by A.M. Reinhorn, T.T. Soong, R.C. Lin, M.A. Riley, Y.P. Wang, S. Aizawa and M. Higashino, 8/14/92, (PB93-127512).

NCEER-92-0021 "Empirical Analysis of Horizontal Ground Displacement Generated by Liquefaction-Induced Lateral Spreads," by S.F. Bartlett and T.L. Youd, 8/17/92, (PB93-188241).

NCEER-92-0022 "IDARC Version 3.0: Inelastic Damage Analysis of Reinforced Concrete Structures," by S.K. Kunnath, A.M. Reinhorn and R.F. Lobo, 8/31/92, (PB93-227502, A07, MF-A02).

NCEER-92-0023 "A Semi-Empirical Analysis of Strong-Motion Peaks in Terms of Seismic Source, Propagation Path and Local Site Conditions, by M. Kamiyama, M.J. O'Rourke and R. Flores-Berrones, 9/9/92, (PB93-150266).

NCEER-92-0024 "Seismic Behavior of Reinforced Concrete Frame Structures with Nonductile Details, Part I: Summary of Experimental Findings of Full Scale Beam-Column Joint Tests," by A. Beres, R.N. White and P. Gergely, 9/30/92, (PB93-227783, A05, MF-AOl).

NCEER-92-0025 "Experimental Results of Repaired and Retrofitted Beam-Column Joint Tests in Lightly Reinforced Concrete Frame Buildings," by A. Beres, S. El-Borgi, R.N. White and P. Gergely, 10/29/92, (PB93-227791, A05, MF-A01).

NCEER-92-0026 "A Generalization of Optimal Control Theory: Linear and Nonlinear Structures," by J.N. Yang, Z. Li and S. Vongchavalitkul, 1112/92, (PB93-188621).

NCEER-92-0027 "Seismic Resistance of Reinforced Concrete Frame Structures Designed Only for Gravity Loads: Part I -Design and Properties of a One-Third Scale Model Structure," by J.M. Bracci, A.M. Reinhorn and LB. Mander, 12/1/92, (PB94-104502, A08, MF-A02).

B-l1

Page 212: Study of Seismic Isolation Systems for Computer Floors

NCEER-92-0028 "Seismic Resistance of Reinforced Concrete Frame Structures Designed Only for Gravity Loads: Part II -Experimental Performance of Subassemblages," by L.E. Aycardi, 1.B. Mander and A.M. Reinhorn, 12/1/92, (PB94-10451O, A08, MF-A02).

NCEER-92-0029 "Seismic Resistance of Reinforced Concrete Frame Structures Designed Only for Gravity Loads: Part III -Experimental Performance and Analytical Study of a Structural Model," by 1.M. Bracci, A.M. Reinhorn and J.B. Mander, 12/1/92, (PB93-227528, A09, MF-AOl).

NCEER-92-0030 "Evaluation of Seismic Retrofit of Reinforced Concrete Frame Structures: Part I - Experimental Performance of Retrofitted Subassemblages," by D. Choudhuri, J.B. Mander and A.M. Reinhorn, 12/8/92, (PB93-198307, A07, MF-A02).

NCEER-92-0031 "Evaluation of Seismic Retrofit of Reinforced Concrete Frame Structures: Part II - Experimental Performance and Analytical Study of a Retrofitted Structural Model," by J .M. Bracci, A.M. Reinhorn and J.B. Mander, 12/8/92, (PB93-198315, A09, MF-A03).

NCEER-92-0032 "Experimental and Analytical Investigation of Seismic Response of Structures with Supplemental Fluid Viscous Dampers," by M.C. Constantinou and M.D. Symans, 12/21/92, (PB93-191435).

NCEER-92-0033 "Reconnaissance Report on the Cairo, Egypt Earthquake of October 12, 1992," by M. Khater, 12/23/92, (PB93-188621).

NCEER-92-0034 "Low-Level Dynamic Characteristics of Four Tall Flat-Plate Buildings in New York City," by H. Gavin, S. Yuan, 1. Grossman, E. Pekelis and K. Jacob, 12/28/92, (PB93-188217).

NCEER-93-0001 "An Experimental Study on the Seismic Performance of Brick-Infilled Steel Frames With and Without Retrofit," by J.B. Mander, B. Nair, K. Wojtkowski and 1. Ma, 1129/93, (PB93-22751O, A07, MF-A02).

NCEER-93-0002 "Social Accounting for Disaster Preparedness and Recovery Planning," by S. Cole, E. Pantoja and V. Razak, 2/22/93, (PB94-142114, A12, MF-A03).

NCEER-93-0003 "Assessment of 1991 NEHRP Provisions for Nonstructural Components and Recommended Revisions," by T.T. Soong, G. Chen, Z. Wu, R-H. Zhang and M. Grigoriu, 3/1/93, (PB93-188639).

NCEER-93-0004 "Evaluation of Static and Response Spectrum Analysis Procedures of SEAOCIUBC for Seismic Isolated Structures," by C.W. Winters and M.C. Constantinou, 3/23/93, (PB93-198299).

NCEER-93-0005 "Earthquakes in the Northeast - Are We Ignoring the Hazard? A Workshop on Earthquake Science and Safety for Educators," edited by K.E.K. Ross, 4/2/93, (PB94-103066, A09, MF-A02).

NCEER-93-0006 "Inelastic Response of Reinforced Concrete Structures with Viscoelastic Braces," by R.F. Lobo, J.M. Bracci, K.L. Shen, A.M. Reinhorn and T.T. Soong, 4/5/93, (PB93-227486, A05, MF-A02).

NCEER-93-0007 "Seismic Testing of Installation Methods for Computers and Data Processing Equipment," by K. Kosar, T.T. Soong, K.L. Shen, J.A. HoLung and Y.K. Lin, 4/12/93, (PB93-198299).

NCEER-93-0008 "Retrofit of Reinforced Concrete Frames Using Added Dampers," by A. Reinhorn, M. Constantinou and C. Li, to be published.

NCEER-93-0009 "Seismic Behavior and Design Guidelines for Steel Frame Structures with Added Viscoelastic Dampers," by K.C. Chang, M.L. Lai, T.T. Soong, D.S. Hao and Y.C. Yeh, 5/1/93, (PB94-141959, A07, MF-A02).

NCEER-93-0010 "Seismic Performance of Shear-Critical Reinforced Concrete Bridge Piers," by 1.B. Mander, S.M. Waheed, M.T.A. Chaudhary and S.S. Chen, 5/12/93, (PB93-227494, A08, MF-A02).

B-12

Page 213: Study of Seismic Isolation Systems for Computer Floors

NCEER-93-0011 "3D-BASIS-TABS: Computer Program for Nonlinear Dynamic Analysis of Three Dimensional Base Isolated Structures," by S. Nagarajaiah, C. Li, A.M. Reinhom and M.C. Constantinou, 8/2/93, (PB94-141819, A09, MF-A02).

NCEER-93-0012 "Effects of Hydrocarbon Spills from an Oil Pipeline Break on Ground Water," by 0.1. Helweg and H.H.M. Hwang, 8/3/93, (PB94-141942, A06, MF-A02).

NCEER-93-0013 "Simplified Procedures for Seismic Design of Nonstructural Components and Assessment of Current Code Provisions," by M.P. Singh, L.E. Suarez, E.E. Matheu and G.O. Maldonado, 8/4/93, (PB94-141827, A09, MF-A02).

NCEER-93-0014 "An Energy Approach to Seismic Analysis and Design of Secondary Systems," by G. Chen and T.T. Soong, 8/6/93, (PB94-142767, All, MF-A03).

NCEER-93-0015 "Proceedings from School Sites: Becoming Prepared for Earthquakes - Commemorating the Third Anniversary of the Lorna Prieta Earthquake," Edited by F.E. Winslow and K.E.K. Ross, 8/16/93.

NCEER-93-0016 "Reconnaissance Report of Damage to Historic Monuments in Cairo, Egypt Following the October 12, 1992 Dahshur Earthquake," by D. Sykora, D. Look, G. Croci, E. Karaesmen and E. Karaesmen, 8/19/93, (PB94-142221, A08, MF-A02).

NCEER-93-0017 "The Island of Guam Earthquake of August 8, 1993," by S.W. Swan and S.K. Harris, 9/30/93, (PB94-141843, A04, MF-AOl).

NCEER-93-0018 "Engineering Aspects of the October 12, 1992 Egyptian Earthquake," by A.W. Elgamal, M. Amer, K. Adalier and A. Abul-Fadl, 1017193, (PB94-141983, A05, MF-AOl).

NCEER-93-0019 "Development of an Earthquake Motion Simulator and its Application in Dynamic Centrifuge Testing," by I. Krstelj, Supervised by J.H. Prevost, 10/23/93, (PB94-181773, A-lO, MF-A03).

NCEER-93-0020 "NCEER-Taisei Corporation Research Program on Sliding Seismic Isolation Systems for Bridges: Experimental and Analytical Study of a Friction Pendulum System (FPS)," by M.C. Constantinou, P. Tsopelas, V-So Kim and S. Okamoto, 11/1193, (PB94-142775, A08, MF-A02).

NCEER-93-0021 "Finite Element Modeling of Elastomeric Seismic Isolation Bearings," by L.J. Billings, Supervised by R. Shepherd, 11/8/93, to be published.

NCEER -93-0022 "Seismic Vulnerability of Equipment in Critical Facilities: Life-Safety and Operational Consequences," by K. Porter, G.S. Johnson, M.M. Zadeh, C. Scawthom and S. Eder, 11124/93, (PB94-181765, A16, MF­A03).

NCEER-93-0023 "Hokkaido Nansei-oki, Japan Earthquake of July 12, 1993, by P.I. Yanev and C.R. Scawthom, 12/23/93, (PB94-181500, A07, MF-A01).

NCEER-94-0001 "An Evaluation of Seismic Serviceability of Water Supply Networks with Application to the San Francisco Auxiliary Water Supply System," by I. Markov, Supervised by M. Grigoriu and T. O'Rourke, 1121/94.

NCEER-94-0002 "NCEER-Taisei Corporation Research Program on Sliding Seismic Isolation Systems for Bridges: Experimental and Analytical Study of Systems Consisting of Sliding Bearings, Rubber Restoring Force Devices and Fluid Dampers," Volumes I and II, by P. Tsopelas, S. Okamoto, M.C. Constantinou, D. Ozaki and S. Fujii, 2/4/94, (pB94-181740, A09, MF-A02 and PB94-181757, A12, MF-A03).

NCEER-94-0003 "A Markov Model for Local and Global Damage Indices in Seismic Analysis," by S. Rahman and M. Grigoriu, 2/18/94.

B-13

Page 214: Study of Seismic Isolation Systems for Computer Floors

NCEER-94-0004 "Proceedings from the NCEER Workshop on Seismic Response of Masonry Infills," edited by D.P. Abrams, 3/1/94, (PB94-180783, A07, MF-A02).

NCEER-94-0005 "The Northridge, California Earthquake of January 17, 1994: General Reconnaissance Report," edited by J.D. Goltz, 3/11/94.

NCEER-94-0006 "Seismic Energy Based Fatigue Damage Analysis of Bridge Columns: Part I - Evaluation of Seismic Capacity," by G.A. Chang and I.B. Mander, 3/14/94.

NCEER-94-0007 "Seismic Isolation of Multi-Story Frame Structures Using Spherical Sliding Isolation Systems," by T.M. AI-Hussaini, V.A. Zayas and M.C. Constantinou, 3/17/94.

NCEER-94-0008 "The Northridge, California Earthquake of January 17, 1994: Performance of Highway Bridges," edited by 1.G. Buckle, 3/24/94.

NCEER-94-0009 "Proceedings of the Third U.S.-Japan Workshop on Earthquake Protective Systems for Bridges," edited by 1.G. Buckle and 1. Friedland, 3/31/94.

NCEER-94-0010 "3D-BASIS-ME: Computer Program for Nonlinear Dynamic Analysis of Seismically Isolated Single and Multiple Structures and Liquid Storage Tanks," by P.e. Tsopelas, M.C. Constantinou and A.M. Reinhorn, 4/12/94.

NCEER-94-0011 "The Northridge, California Earthquake of January 17, 1994: Performance of Gas Transmission Pipelines," by T.D. O'Rourke and M.C. Palmer, 5/16/94.

NCEER-94-0012 "Feasibility Study of Replacement Procedures and Earthquake Performance Related to Gas Transmission Pipelines," by T.D. O'Rourke and M.C. Palmer, 5/25/94.

NCEER-94-0013 "Seismic Energy Based Fatigue Damage Analysis of Bridge Columns: Part II - Evaluation of Seismic Demand," by G.A. Chang and J.B. Mander, 6/1/94, to be published.

NCEER-94-0014 "NCEER-Taisei Corporation Research Program on Sliding Seismic Isolation Systems for Bridges: Experimental and Analytical Study of a System Consisting of Sliding Bearings and Fluid Restoring ForcelDamping Devices," by P. Tsopelas and M.C. Constantinou, 6/13/94.

NCEER-94-0015 "Generation of Hazard-Consistent Fragility Curves for Seismic Loss Estimation Studies," by H. Hwang and J-R. Huo, 6/14/94.

NCEER-94-0016 "Seismic Study of Building Frames with Added Energy-Absorbing Devices," by W.S. Pong, C.S. Tsai and G.C. Lee, 6/20/94.

NCEER-94-0017 "Sliding Mode Control for Seismic-Excited Linear and Nonlinear Civil Engineering Structures," by 1. Yang, J. Wu, A. Agrawal and Z. Li, 6/21/94.

NCEER-94-0018 "3D-BASIS-TABS: Computer Program for Nonlinear Dynamic Analysis of Three Diemnsional Base Isolated Structures (Version 1.1)," by S. Nagarajaiah, C. Li, A.M. Reinhorn and M.e. Constantinou, 6/22/94.

NCEER-94-0019 "Proceedings of the International Workshop on Civil Infrastructure Systems: Application of Intelligent Systems and Advanced Materials on Bridge Systems," Edited by G.C. Lee and K.C. Chang, 7/18/94, to be published.

NCEER-94-0020 "Study of Seismic Isolation Systems for Computer Floors," by V. Lambrou and M.C. Constantinou, 7/19/94.

B-14