6 r' SMS 010 - Substation Monitoring System (PC DOS/MS WindowsTM based) 1MAK 511 014-BEN P"ne 1 ABB Network Partner local communication link .Time synchronisation via fibre optic loop or i via galvanic minute pulse i .Utilising public switched telephone network (according to CCITT) or packet switched network (X.25) for remote communication .Possibility to connect to a single unit via the front connector, or local and/or remote work place accessing several terminals interconnected with a loop G .Modular and flexible system with easy installation and step-by-step upgrading .Excellent commissioning tool and possibil- ity to prepare settings off-line in advance r: -settings and configuration of all para- meters -reading/resetting of all indications -measured values at fault -service values from analogue and digital inputs -self supervision results .Password protection when changing sl~ttings .Setting calculation program for line dis- tance protection terminals .Automatic or on-request collection of data from disturbance recorders .Powerful disturbance evaluation too I run- ning under MS WindowsTM .Expert system for automatic disturbance evaluation and database handling All information available in the protection termi- nals in the SPACOM series, the REx 100 series and the REx 500 series can be accessed from a PC in the station or via telephone modems. For the RE. 216/316 series the disturbance recordings can be transferred to the SMS PC. For the protection terminals in the SPACOM series and in the REx 500 series a temporary connection to one terminal at a time, utilising the front connector, is also possible. A Substation Monitoring System (SMS) is an information system for handling, storing and presentation of the information stored in pro- tection terminals and disturbance recorders. SMS 010 is intended for medium and hIgh volt~ age applications with high performance requirements. Protection tertrlinals, alarm annunciators and stand alone djSturbahce recorders can be combined using the same communication hardware and software. Application g November 1995 Changed since March 1995 Replaces 1MRK501 0O2-BEN Dala subject lo change wilhoul nolice

Substation Monitoring System (PC DOS/MS … · Substation Monitoring System (PC DOS/MS WindowsTM based) 1 MAK 511 014-BEN P"ne 1 ABB Network Partner ... sponding protection and controi

  • Upload
    vomien

  • View
    242

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Substation Monitoring System (PC DOS/MS … · Substation Monitoring System (PC DOS/MS WindowsTM based) 1 MAK 511 014-BEN P"ne 1 ABB Network Partner ... sponding protection and controi

6r' SMS 010 -

Substation Monitoring System(PC DOS/MS WindowsTM based)

1 MAK 511 014-BENP"ne 1

ABB Network Partner

local communication link.Time synchronisation via fibre optic loop or ivia galvanic minute pulse i

.Utilising public switched telephone network(according to CCITT) or packet switchednetwork (X.25) for remote communication

.Possibility to connect to a single unit viathe front connector, or local and/or remotework place accessing several terminalsinterconnected with a loop

G.Modular and flexible system with easyinstallation and step-by-step upgrading

.Excellent commissioning tool and possibil-ity to prepare settings off-line in advance r:

-settings and configuration of all para-meters

-reading/resetting of all indications

-measured values at fault-service values from analogue and digital

inputs-self supervision results

.Password protection when changing sl~ttings

.Setting calculation program for line dis-tance protection terminals

.Automatic or on-request collection of datafrom disturbance recorders

.Powerful disturbance evaluation too I run-ning under MS WindowsTM

.Expert system for automatic disturbanceevaluation and database handling

All information available in the protection termi-nals in the SPACOM series, the REx 100 seriesand the REx 500 series can be accessed froma PC in the station or via telephone modems.For the RE. 216/316 series the disturbancerecordings can be transferred to the SMS PC.

For the protection terminals in the SPACOMseries and in the REx 500 series a temporaryconnection to one terminal at a time, utilisingthe front connector, is also possible.

A Substation Monitoring System (SMS) is aninformation system for handling, storing andpresentation of the information stored in pro-tection terminals and disturbance recorders.SMS 010 is intended for medium and hIgh volt~age applications with high performancerequirements. Protection tertrlinals, alarmannunciators and stand alone djSturbahcerecorders can be combined using the samecommunication hardware and software.

Application

g

November 1995Changed since March 1995Replaces 1MRK501 0O2-BENDala subject lo change wilhoul nolice

Page 2: Substation Monitoring System (PC DOS/MS … · Substation Monitoring System (PC DOS/MS WindowsTM based) 1 MAK 511 014-BEN P"ne 1 ABB Network Partner ... sponding protection and controi

Application (confd) SMS is intended for:

-the relay engineer

-the mairitena:riöepersötiiiel

-the commissioning engineers

With the use of SMS when commissioning,parameters can be prepared in the office anddown loaded to the protection in the station.the use of a PC as a local MMI gives animprovedoverviewof.all parameters and func-tions, and also an informative hel p text foreach parameter for improved understanding.

The information includes parameters, indica-tions and internai self-diagnosis. Disturbancefiles collected manuallyor automaticaUy byJhePC are evaluated with an MS WindowsTMbased progtam (REVAL). Automatic analys isof the disturbance files in hi,gh voltage appfica-tions is performed by an expert system(RESDA).SMS is above all to beused as a w~ytp tran$-fer information from the stations, directiy to thecentral relay office where the fault. evaluationtakes place. It also provides an improved localMMI on a PC in the station.

Design AJI terminals includes the possibility to syn-chtonise the internai clock via the SPA-bus,using a data communicator, e.g. a SAID, asmaster sending out time messages on theloop, or an existing controi system (SCS). Timesynchronisation can also be performed bymeans of a galvanic minute pulse connected

tö the protection terminals in the

The design of SMS is modular, consisting ofhardware and software building blocks. Themodular structure makes future extensionsand step-by-step implementation easily done.

HardwareThe hardware requirements for a complete moni-toring system are minimal and to a high extentbased on commercially available equipment.

by allSPA-bus version 2.4.

These bus connector units are then connectedto afibre optic loop. The loop consists of glassand/or plastic fibres depending on the lengthbetween the different units. The fibre opticloop ends up in an opto/electrical converter,with an RS232 electrical interface which isconnected directly to the serial port of an IBMcompatible PC. The converter can also beconnected directly to a telephone modem, andthe PC placed at a remote location.

Several optical loops can be connected to thePC via a data communicator, e.g. a SRIO.. orother opto/electrical devices, e.g. SPA-ZC22.thus forming a star configuration. This configu-ration gives higher availability but is not ascost-effective as the loop configuration.

It is also possible to have a PC both locally inthe station and at a remote location communi-cating via telephone modems. This configura-tion requires RECOM in the local station-PC,equipped with two serial (COM) ports. Thelocal PC is connected to the opto/electriealconverter via one of the serial ports and to thetelephone modem via the other serial port.

-the telephone modem handling (Hayes com-

patible modems)

-the setting of communication parameters

-the password functions

-a terminal emulator for communication trou-ble shooting

-the error correction for the communication

To the SMS-BASE software platform, the fol-lowing software modules are added accordingto the actual application.

SM/SPASM/SPA--is the software module for parametersettlng and supervision of the protection termi-nals in the SPACOM series.

SM/SACOSM/SACO is the software module for parame-ter setting and supervision of the SACOannunciators in the SPACOM series.

SM/SPTOSM/SPTO is the software module for configura-tion of the controi modules in the SPACOM series.

SM/SPCRSM/SPCR is the software module for parame-ter setting and supervision of the SPCR typedisturbance recorders in the SPACOM series.

Page 3: Substation Monitoring System (PC DOS/MS … · Substation Monitoring System (PC DOS/MS WindowsTM based) 1 MAK 511 014-BEN P"ne 1 ABB Network Partner ... sponding protection and controi

ABB Network Partner 1MRK511014-BENPage 3

SMS 010Substation Monitoring System

SM/REL 501, SM/REL 511, SM/REL 521,SM/REL 531, SM/REL 551, SM/REL 561,SM/REB 551, SM/REC 561SM/REx 5xx are the software modules forparameter setting and supervision of the corre-sponding protection and controi terminal in theREx 500 series. These modules also include aprogram called FrontRECOM, which is a part ofRECOM, for collection of the disturbances, butonly via the front port. For disturbance collec-tion via the rear port RECOM must be used.

SM/REL 100SM/REL 100 is the software module for param-eter setting and supervision of the line protec-tion terminal REL 100 versions 2.3 and 3.0.SM/REL 100 with SMS-BASE is a completereplacement of RDIAL 1 and RDIAL 3.

SM/REG 100SM/REG 100 is the software module for param-eter setting and supervision of the generatorprotection terminals REG 100, REG 110 andREG 150, versions 3.X. SM/REG 100 with SMS-BASE is a complete replacement of RDIAL 2.

SM/REOR 100SM/REOR 100 is the software module forparameter setting and supervision of the distur-banGe recorders REOR 100/RCRA 100 ver. 3.0.

SM/REL 012SM/REL 012 is the software module for param-eter setting and supervision of the 4-step earthfault protection REL 012.

RCALCRCALC is a stand alone simulation and calcu-lation program running under MS WindowsTM,used to check the reach of a distance relay,especially for high resistance earth faults whenthe power transferred on the line is high.

The network configuration is a two-machinesystem with up to three lines -two with mutualcoupling and one without. Different faults likephase to earth, phase to phase, two phase toearth and three phase faults can be applied.

A drawing function is included which gives a pos-sibility to check the size of the operating area in aR-X diagram when the relay setting is changed.

The RCALC includes the characteristics for thefollowing distance relays: RAZFE, RAZOA,REZ 1, REL 100, REL 511, and REL 521.

RECOMRECOM is a communication program for man-ual or automatic collection of disturbance filesto a PC from REOR 100 / RCRA 100 (versions2.2 and 3.0) and terminals in the REx 500series equipped with optional disturbancerecorder. When installed, the program is inte-grated in the SMS-BASE structure. When thedisturbance recordings are collected byRECOM they can be evaluated by REVAL.

The automatic function in RECOM is a MS Win-dOWSTM based universal Scheduler programpolling the stations the number of times perday specified by the user. When new distur-bance recordings are available they will auto-matically be transferred to the PC.

The RECOM Scheduler also makes the use oflocal and central PC possible since, beinginstalled in the local PC, this PC will be transparentfor SPA-messages coming from the central PC.

DRCOMDRCOM is a communication program for man-ual or automatic collection of the disturbancefiles to a PC from the disturbance recorders inthe SPACOM series. The program can be usedas a stand alone program or it can be usedwith the REPORT program.

The automatic function is polling the distur-banGe recorders periodically according to settime interval. If new disturbances are availablethey will automatically be transferred to the PC.

The DRCOM includes a simple presentation of thesignals. When the disturbance recording is col-lected the files are converted to the COMTRADEformat and can then be evaluated by REVAL.

EVECOMEVECOM is a communication program formanual or automatic collection of the distur-banGe files to a PC from the terminals in theRE. 216/316 series equipped with optional dis-turbance recorder, and also the SPCR distur-banGe recorder modules in the SPACOM series.The program is to be used as a stand aloneprogram, running under MS WindowsTM.

When the disturbance recording is collectedthe files are stored on the PC and can the n beevaluated by REVAL.

REVALREVAL is a disturbance evaluation program forevaluation of files collected from REOR 100/RCRA 100, REx 500 series, SPCR 8C27, RE. 316series, and other recorders complying to any ofthe formats handled by REVAL.

It is a MS WindowsTM application, which meansGmouse based interaction and easy handling. It

includes extensive functionality such as:

-measuring of instantaneous amplitude, RMS-value, time and phase angle

-individual or equal scaling

-individual line type and colouring of signalsas weil as grouping of signals

-merging of up to three disturbances

-handling of up to 33 analogue and 144 digitalsignals in one window

-printout on WindowsTM system printer

Page 4: Substation Monitoring System (PC DOS/MS … · Substation Monitoring System (PC DOS/MS WindowsTM based) 1 MAK 511 014-BEN P"ne 1 ABB Network Partner ... sponding protection and controi

1MRK 511 014-BENPage 4

ABB Network Partner

Design (cont'd) file, RESDA does the analysis automatically.The result file is then transferred via the publictelephone network to the central PC byRECOM where the central part of RESDA isinstalled. The station part is installed in everystation where information is collected.

RESDA Central is installed at the office wherethe central database is accessed. The data-base is built up with data from the distur-bances. The information in the database isused for reports, fault statistics and mainte-nance planning. It is possible to export thereport files to MS ExcelTM and MS WordTM.

REPORTREPORT is a program for alarm and eventhandling, and polling of measured values, reg-isters and other values. The program is auto-matically with in user defined time intervalspolling selected events, alarms and other val-ues from the terminals. Events and alarms areshown in time order on the screen.

The events, alarms and other polled valuescan be stored on thehard drive or printed to aprinter. REPORT always requires a data commu-nicator, i.e. SAla or SACO 148D, in the station.

The REPORT program can be used with all ter-minals .in the SPACOM series and also theREL 100, REG 100, and the protection termi-nals in the REx 500 series have been inte-

grated.

The selecting of the events to be included is apart of each SM/... module respectively. Thismeans that a SM/... module for each terminaltype in the system must be installed in the PCin order to achieve the REPORT functfonality.

REVAL can read and convert files of the follow-ing formats:

-REVAL (REOR 100/RCRA 100 version 3.0and the REx 500 series terminals)

-EVE (REOR 100/RCRA 100 version 2.2 andthe RE. 216/316 series terminals)

-COMTRADE which is an IEEE standard

REVAL can convert files to the following for-mats:

-DADiSP@ (Mathematical signal analys is tool)

-MATLAB@ (Mathematical signal analysis too/)

-User defined ASCII format

REVAL is available in several language ver-sions, e.g. English, Swedish, Spanish, Germanand Italiano

RESDARESDA is an expert system for disturbanceanalysis. It is a MS WindowsTM application,which means mouse based interaction andeasy handling. It is used for automatic fault anal-ysis and statistics. It also performs an accuratecalculation of the fault location using an algo-rithm including load compensation. RESDA is tobe used together with REOR 100 1 RCRA 100and terminals in the REx 500 series with anoptional disturbance recorder. RESDA can onlybe used in solidly earthed networks since rela-tively high fault currents are required for the

analysis.

The program is divided in a station part and acentral part. Both parts are needed for thefunctionality. The station part of the program isto be installed in a PC located in the station.When RECOM has collected a disturbance

Technical data

Page 5: Substation Monitoring System (PC DOS/MS … · Substation Monitoring System (PC DOS/MS WindowsTM based) 1 MAK 511 014-BEN P"ne 1 ABB Network Partner ... sponding protection and controi

ABB Network Partner 1MRK 511 014-BENPage 5

SMS 010

Substation Monitoring System

Table 4: Recommendation for the PCThe PC shall comply to the following recommended requirements:-100% IBM compatible running DOS 5.0 (DOS 3.3 is sufficient when running SMS-BASE and SM/SP.. only).-640 kb RAM or more (at lesst 450 kb available).-VGA screen and 31/2" floppy disk drive (1,44 Mb).-one serial port available (two ports on the station PC if it is communicating with a central PC).

I

DRCOM

EVECOM

R~~~=~:~~

SM8-BASEI4Mb; MS WindowsTM 3.1

or higherMS WindowsTM 3.1or higherMSWindowsTM3.1or higherMS WindowsTM 3.1

-.?~~}gher

I REVAL i

~2Mb

I RECOMI RESDA Central

'r-4863Mb**

I RECOMI RESDA Station

~2Mb

I SMS-BASE II REPORT*** 1386 12Mb T2Mb

Page 6: Substation Monitoring System (PC DOS/MS … · Substation Monitoring System (PC DOS/MS WindowsTM based) 1 MAK 511 014-BEN P"ne 1 ABB Network Partner ... sponding protection and controi

Diagrams Fig. 1 The use of SMS-BASE with the differ-ent SM/... modulesvery much simplifiesthe setting and con-figuration of the pro-tection terminals.Furthermore, thesystem overview andunderstanding ofthe function isenhanced.

Fig. 2 Correctly set protec-live relays is a must inorder to maintainselectivity in the net-work. With the RCALCsetting calculationand simulation pro-gram the setting cal-culat!on process forthe line distance pro-tection terminals is

considerably simpli-tied.

Fig.3 Events at differentlevels can beaccessed depend-ing on the task athand. With theREPORT programevents on the stationleve I can beacquired either man-ually or automati-cally.

Fig. 4 The REVAL distur-bance evaluationprogram includesextensive functional-ity including file con-version to userdefined ASCIIbased format. Thismakes REVAL thekey in building up apowerful signal anal-ysis world station.

Page 7: Substation Monitoring System (PC DOS/MS … · Substation Monitoring System (PC DOS/MS WindowsTM based) 1 MAK 511 014-BEN P"ne 1 ABB Network Partner ... sponding protection and controi

1 MRK 511 014-BENPage 7

ABB Network Partner SMS 010Substation Monitoring System

Fibre optic loop

Fig. 5 SMS configuration with monitoring of the protection terminals. disturbance collection anddisturbance evaluation in a PC located in a central office. communicating via telephonemodems. The central PC can elsa be used for monitoring of other stations. (Note that forRE. 316 only disturbance collection is possible. i.e. not parameter setting.)

Fig. 6 SMS configuration with monitoring of the protection terminals and event reporting functionsin a PC located in a central office communicating via telephone modems. The central PCcan also be used for monitoring of other stations.

Fig. 7 SMS configuration example with both a station PC and a central PC. The RESDA Station per-forms an automatic analysis of the disturbances which is presented in the central PC. Alsodirect access to the terminals from the central PC can be established since RECOM makesthe station PC transparent for communication. Aminute pulse connected to a galvanic input

synchronises the terminals.

Page 8: Substation Monitoring System (PC DOS/MS … · Substation Monitoring System (PC DOS/MS WindowsTM based) 1 MAK 511 014-BEN P"ne 1 ABB Network Partner ... sponding protection and controi

1MRK 511 014-BENPage 8

ABB Network Partner SMS 010Substation Monitoring System

Ordering Specify:

.Type designations and ordering numbers

.Quantity

.End user of the software: Name, Company and Address

Programs and software modules

Type designatlon OrderIng No.

SMS-BASE English AS 881 007-AA

SM/SPA- English AS 881 008-AA

SM/SACO English AS 881 009-AA

SM/SPTO English AS 881 01D-AA

SM/SPCA English AS 881 015-AA

DACOM English AS 881 016-AA

AEPOAT English AS 881 011-AA

SMS-BASE Swedish AS 881 007-AB

SM/SPA- Swedish AS 881 008-AB

SM/SACO Swedish AS 881 009-AB

SM/SPTO Swedish AS 881 010-AB

SM/SPCASwedish AS881015-AB,..

DRCOM Swedish AS 881 016-AB

AEPOAT Swedish AS 881 011-AB

EVECOM English HESG 448411 A2

EVECOM German HESG 448411 A1

SM/REL 100 English 1MAKOO0077-A

SM/REG 100 English 1MAKOOOO77-B

SM/REOA 100 English 1MAKOOO077-C

Type designation Ordering No.I §~~~~~.;~'~~~;i~h ~~-R-~B~~"i;-E'SM/REL 501 English 1MRKOOO314-A

SM/REL 511 English 1MRKOOO314-BA

SM/REL 521 English 1MRKOOO314-C

SM/REL 531 English 1MRKOOO314-GA!

SM/REL551 English 1MRK000314-FA

SM/REL 561 English 1MRKOOO314-DA

SM/REB 551 English 1MRKOOO314-EA

SM/REC 561 English 1 MRKOOO314-HA

RCALC English 1 MRKOOO589-AAIRECOM English 1 MRKOOOO77 -DA

REVAL English 1 MRKOOOO78-AA, "

REVAL Swedish' 1 MRKOOOO78-BA

REVAL Italian 1 MRKOOOO78-CA

REVAL German 1 MRKOOOO78-DA

REVAL Spanish 1MRKOOOO78-EA

RESDA Station English 1 MRKOOOO79-A

RESDA Central English 1 MRKOOOO79-B

,Cable for connection to front of the terminals in the REx 500 series.To be connected to PC GOM port (RS232, DB9)

Type designatlon OrderIng No.

Front cable 1MKC950001-1\"

Opto/electrical converter (make FIBERDATA)

Flbre connectors Electrical contact Aux. supply Ordering No.

(RS232)Plastic I Male .220 V ac 5716 099-B

Plastic Male 110 V ac 5716 099-BA

Glass Male 220 V ac 5716 100-B

Glass Male 110 V ac 5716100-BA

PIastic fIbres cablesConnector type HP-connector of HFBR type (snap-in)Types One-core fibrecable and two-core fibre cable

Lengths Available in lengths between 1 and 30 metres

Connector type ST-connector (bayonet)Types One-core fibre cable. two-core fibre cable, and two-core fibre cable for

outdoors or rough environmentLengths Available in lenQths between 1 and 500 meters

Page 9: Substation Monitoring System (PC DOS/MS … · Substation Monitoring System (PC DOS/MS WindowsTM based) 1 MAK 511 014-BEN P"ne 1 ABB Network Partner ... sponding protection and controi

1 MAK 511 014-BENPage 9

ABB Network Partner SMS 010Substation Monitoring System

Sample specification The monitoring system shall be of modulardesign with distributed databases in the pro-tection terminals and fibre optic communica-tian for interference free transmission withinthe station. The system shall support commu-nication with telephone modems, and no sta-tion computer or other central unit. other thanthe telephone modem, shall be required forthis communication.

The hardware shall to the highest possibleextent consist of commercially availableequipment, and both disturbance recordersand protection terminalsshall be incorporatedin the same hardware configuration. Possibilityto have both a station and a remote PC shallbe supported.

The software of the monitoring system shallconsist of a flexible software package, han-dling both disturbance recorders and protec-tian terminals. All programs shall be PC OOS/MS WindowsTM based.

Reading and setting of all parameters in theprotection terminals and changing betweencomplete groups of parameters or changing ofsingle parameters sh all be possible, and theediting of the parameters shall be done off-line.

A communication program for manual or auto-matic collection of disturbance files to a PCsh all be available. The automatic function shallpoll the station the number of times per dayspecified by the user. When new disturbancerecordings are available they shall automati-cally be transferred to the PC.

The disturbance evaluation software shall rununder MS WindowsTM and include functionssuch as time, amplitude and angle measure-ment. Also zooming in the time scale and inde-pendent magnitude scaling of each signal shallbe included. Merging of disturbance files shallbe possible and the software sh all be able tohandle 33 analogue and 144 digital signals inone window. Furthermore sh all the evaluationsoftware accept the standard disturbance fileformat COMTRADE (IEEE standard) and per-form conversion between different formats.

An expert system for automatic evaluation ofdisturbances shall also be available for highvoltage applications and include functions forhandling of statistics and accurate fault locatorcalculation using an algorithm including load

compensation.

An event, alarm and logging program shall beavailable with automatic polling of one or sev-eral stations.

PYRAMID SubstationAutomation

References1 MRK 500 O 16-BEN

See the Buyer's Guide for each protection ter-minal in SPACOM series, REx 100 series,REx 500 series and RE. 216/316 seriesrespectively.