Upload
others
View
7
Download
0
Embed Size (px)
Citation preview
Sheet 1 of 1 B01-0300.xls - Front sheet
02
Originator / Contractor Code
Short Requisition No / PO Identifier Sheet Rev
FC EL0016-A01 02
Alternative Document No: (if applicable):
Rev Orig. Chk'd App'd
02 IT GR NCR
01 GR GR IT
Code
1
2
3
4
5
6
Purchaser Review of Supplier Document
Cancelled / Superseded
As-Built
Purchaser Document Number
Sequence no.
0300
SDDR code
B01
Project ID
CLB
Equipment Tag No(s):
Supplier Document No:
Document Title:
Z-89903
N/A
GENERAL ARRANGEMENT - LQ TEMPORARY SUBSTATION
Supplier Document Revision No.
SUPPLIER DOCUMENT FRONT SHEET
Supplier Name: ABB Ltd
For Information
1-Oct-13
20-Nov-13
Rejected, Do Not start work (Comments to be incorporated and resubmitted)
Description of Code
DateDescription
INITIAL SUBMISSION
Signature of Purchaser'sResponsible Engineer Date
UPDATED SUBMISSION
Accepted (Reviewed and Agreed)
Comments to Incorporated and Resubmitted
7500
4000
7500
3200100
REMOVABLEEND PANELS
7500
4000
7500
750
95 155
100
2800 1400
4300 1002900100
100
LADDER RACK CARRYINGSERVICE CABLES
890
1000
1230
266
414
1430 885585
100
100
525 990 1385
1800
STR
UTUR
AL O
PENI
NG18
00 S
TRUT
URAL
OPE
NING
INTERNAL PLAN VIEW
INTERNAL PLAN VIEW SHOWING FLOOR APERTURES
400
501
400
501
470790
620
1437.5 100325 APER525 APERTURE525 APERTURE525 APERTURE525 APERTURE
137.5 75 75 75 75
725 APERTURE
282.5 APERTURE
525 APERTURE717.5
75
1137.5
137.5
2800
3200
100
100
100
2200 kVATRANSFORMER
1200 kVATRANSFORMER
STAIR & LANDING:
STAIRS & LANDINGS ARE TO THE BRADGATE STANDARD STEEL CONSTRUCTION DESIGN CONFORMING TO THESTANDARDS OUTLINED IN EEMUA PUBLICATION 105 SEVENTH EDITION ' FACTORY STAIRWAYS, LADDERS ANDHANDRAILS'. LANDING GRATING IS SERRATED & STAIR TREAD NOSING IS NON-SLIP. ALL STAIRS & LANDINGSCOMPONETS ARE SUPPLIED WITH EARTH BONDING TAPPING POINTS. ALL STAIRS & LANDINGS COMPONENTS AREFINISHED 'HOT DIP GALVANISED' IN ACCORDANCE WITH BS EN ISO 1461:2009NOTE, THAT STAIRS & LANDINGS ARE DESIGNED FOR PERSONNEL ACCESS USE ONLY!I.E. NO EQUIPMENT IS TO BE PLACED ON THE LANDINGS.
UNDERSTRUCTURE:
THE UNDERSTRUCTURE IS DESIGNED AS A BOLT TOGETHER SET OF FRAMES.THERE ARE A TOTAL OF SIX FRAMES, TWO ALONG EACH SIDE & ONE EITHER END.THE MODULE WILL BE CONNECTED TO THE UNDERSTRUCTURE USING BRADGATE DESIGNED CLAMPS.THE UNDERSTRUCTURE WILL BE SUPPLIED WITH ADDITIONAL BRADGATE DESIGNED CLAMPS ALLOW THE WHOLESTRUCTURE & MODULE TO BE SECURELY FASTENED DOWN WHEN INSTALLED AT SITE.THE CLAMPS WILL BE FASTENED DOWN AT SITE BY USING MECHANICAL FIXINGS INTO THE CIVILS FOUNDATION /CONCORSE AREA. NOTE IT IS THE RESPONSIBILITY OF OTHERS TO SELECT & SUPPLY THE CORRECT MECHANICALFIXINGS FOR THE CLAMPING DOWN.THERE IS PROVISION PROVIDED TO FIT EARTH BONDING BETWEEN THE MODULE & THE UNDERSTRUCTURE FRAME& PROVISION TO EARTH BOND BETWEEN EACH OF THE UNDERSTRUCTURE FRAMES.THE UNDERSTRUCTURE WIL BE 'HOT DIP GALVANISED' IN ACCORDANCE WITH BS EN ISO 1461:2009
MODULE PAINT SPECIFICATION:
PAINT SYSTEM BRADGATE STD SPEC 005 (OFF SHORE).EXTERNAL DFT 220 MICRONS.INTERNAL DFT 150 MICRONS.
OUTSIDE BS 4800 10-A-05 GOOSEWING GREYINSIDE BRADGATE STANDARD WHITE.FLOOR BRADGATE STANDARD BLACK.UNDERSIDE BRADGATE STANDARD BLACK UNDERSEAL.
TRANSPORT & STORAGE:
ALL BUILDING DOORS WILL BE SECURED WITH A SCREWED RETAINING PLATE.ALL EXTERNAL LOUVERS WILL BE TEMPORARILY BOARDED WITH PLYWOOD SHEET C/W PLASTIC MEMBRANE.DURING TRANSPORTATION.TEMPORARY PLYWOOD BOARDING OF THE HVAC EXTERNAL CONDENSER.DURING LENGTHY SEA TRANSIT & ANY STORAGE, IT IS RECOMENDED THAT TEMPORARY BACK GROUND HEATINGIS USED TO ALLEVIATE THE ONSET OF A DAMP ATMOSPHERE.THE UNDERSTRUCTURE SUPPORT FRAMES, STAIRS & LANDINGS WILL BE SHIPPED IN STANDARD ISO CONTAINERS.
APPROXIMATE WEIGHTS AS SUPPLIED BY BRADGATE CONTAINERS LTD:
EMPTY MODULE ------------------------------------------------------------------- = TBC kgINSTALLED EQUIPMENT SUB TOTAL ---------------------------------------- = 11058 kgBRADGATE ELECTRICAL EQUIPMENT (ESTIMATED.) ---------------- = TBC kg
TOTAL CALCULATED WEIGHT = TBC kg
PLEASE NOTE THAT THE EQUIPMENT INDIVIDUAL WEIGHTS SHOWN HAVE BEEN TAKEN FROMINFORMATION/DRAWINGS SUPPLIED TO BRADGATE CONTAINERS LTD. CUSTOMER TO ADVISE IF ANY OF THEEQUIPMENT WEIGHTS ARE INCORRECT PRIOR TO MANUFACTURE OF THE MODULE.
LIFTING & RIGGING OF MODULE:
4 OFF TOP LIFTING LUG POINTS ARE PROVIDED, NOTING THAT THESE LIFTING LUGS ARE ONLY TO BE USED FORLIFTING A FULLY FITTED OUT MODULE ONLY! THE UNDERSTRUCTURE OR STAIRS & LANDINGS MUST BE LIFTEDSEPERATLY. SEE LIFTING & RIGGING DRAWING 13240-1-5 FOR DETAILS.
REFERENCE TABLE OF EQUIPMENT FOR LQ TEMPORARY SUBSTATION MODULE (TAG No. Z-89903)
REF EQUIPMENT TAG DESCRIPTION QTY. WIDTH. (mm) DEPTH (mm) HEIGHT (mm) WEIGHT (kg) HEAT LOSS (kW) SUPPLIER COMMENTS
01 ETR-89903 2200 kVA TRANSFORMER 1 1980 1230 2306 4485 24.15 ABB
02 ETR-89904 1200 kVA TRANSFORMER 1 1700 939 1973 2543 14.6 ABB
03 ESW-89903 690V SWITCHBOARD 1 2850 800 2300 1600 2.11 ABB04 ESW-89904 400V SWITCHBOARD 1 3250 800 2300 1900 2.7 ABB05 ECP-89903 SWITCHBOARD REMOTE CONTROL 1 400 250 600 - NIL ABB
06 EJB-89903 CABLE / SPLITTER BOX 1 1050 550 1200 105 NIL ABB
07 EIN-89903 TRIP & CLOSE UPS 1 750 455 1255 210 - ABB08 HCN-89903 HVAC EXTERNAL CONDENSER UNIT 1 970 450 845 83 NIL GAT09 HAH-89903 HVAC INTERNAL AIR HANDLING UNIT 1 950 950 333 81 NIL GAT10 HCP-89903 HVAC CONTROL PANEL 1 - - - - NIL GAT11 DRP-89903 FIRE PANEL 1 - - - - NIL CFS12 DSA-89903-01 SMOKE DETECTOR 2 - - - - NIL CFS13 DSA-89903-02 SMOKE DETECTOR 2 - - - - NIL CFS14 DHR-89903-01 RoR HEAT DETECTORS (WEATHERPROOF) 2 - - - - NIL CFS15 DHR-89903-02 RoR HEAT DETECTORS (WEATHERPROOF) 2 - - - - NIL CFS16 MAC-89903 FIRE MANUAL CALL POINT 1 - - - - NIL CFS17 DAL-89903-01 FIRE SOUNDER BEACON IP65 (RED) - INTERNAL 1 - - - - NIL CFS18 DAL-89903-02 FIRE SOUNDER BEACON IP65 (RED) - EXTERNAL 1 - - - - NIL CFS19 SFC-89903 CO2 FIRE EXTINGUISHER & ID SIGN 1 - - - - NIL CFS20 EME-89903 STAIRS & LANDINGS 1 - - - 860 NIL BRADGATE21 ES3-89903-01 DOMESTIC ELECTRICAL TWIN SOCKET 230V 60 Hz 16A 2 - - - - NIL BRADGATE 3 PIN (RCD PROT.)
22 ES3-89903-02 DOMESTIC ELECTRICAL TWIN SOCKET 230V 60 Hz 16A 2 - - - - NIL BRADGATE 3 PIN (RCD PROT.)
23 EFL-89903-01 FLOURESCENT LUMINAIRE C/W EMERGENCY BACK-UP 4 - - - - NIL BRADGATE
24 EFL-89903-02 FLOURESCENT LUMINAIRE C/W EMERGENCY BACK-UP 4 - - - - NIL BRADGATE
25 EFL-89903-03 FLOURESCENT LUMINAIRE C/W EMERGENCY BACK-UP 4 - - - - NIL BRADGATE
26 EFL-89903-04 FLOURESCENT LUMINAIRE C/W EMERGENCY BACK-UP 4 - - - - NIL BRADGATE
27 EIS-89903 ELECTRICAL LIGHT SWITCH ISOLATOR 1 - - - - NIL BRADGATE
28 EDB-89903 LIGHTING & SMALL POWER DIST. BOARD 1 - - - - NIL BRADGATE
29 EFL-89903-05 LIT EMERGENCY EXIT SIGN 1 - - - - NIL BRADGATE
30 ETR-89923 15 kVA 3 PHASE AUTOTRANSFORMER 1 350 242 353 25 0.175 BRADGATE HVAC SUPPLY
31 EWL-89903 COMMON FAULT WARNING LIGHT 1 - - - - NIL BRADGATE
32 SEIK-89903 ELECTRICAL INTERVENTION KIT (LIFE SAVING KIT) 1 840 754 270 20 NIL ABB
33 EEL-89903 KEY BOX/SAFE 1 190 50 250 4 NIL BRADGATE
34 RSL-89903 PORTABLE EMERGENCY HAND LAMP 1 110 180 190 1.75 NIL BRADGATE
NOTES:
ALL EXTERNAL HINGES AND REMOVABLE PANELS ARE FIXED WITH M8 STAINLESS STEEL TORX SECURITYSCREWS.
ALL REMOVABLE PANELS ARE FIXED WITH M10 STAINLESS STEEL TORX SECURITY SCREWS.
ALL DOORS AND REMOVABLE PANELS ARE 'EARTH BONDED'.
ALL ELECTRICAL ITEMS AS SPECIFICATION.
NON-DESTRUCTIVE TESTING (NDT):
ALL LIFTING LUG WELDS AND LIFT PATH WELDS ARE TO BE MAGNETIC PARTICLE TESTED TO BRADGATE WORKSPROCEDURE 010.INSPECTION / TEST RESULTS ARE TO BE RECORDED.
MATERIAL SPECIFICATION:
STRUCTURAL:ALL RHS AND SHS SECTIONS TO BS EN 10210 S355J2HALL PLATE MATERIAL OVER 5mm THK. TO BS EN 10025 S355J2ALL PLATE MATERIAL 5mm AND UNDER TO BS EN 10025 S275JRALL ALUMINIUM GLAND PLATES 6mm MARINE GRADE, 5083 - H111
CERTIFICATES FOR ALL STRUCTURAL MATERIALS WILL BE ISSUED IN PROJECT DOCUMENTATION.
ROOF:OUTER SKIN 14swg (2.0mm) ZINTEC SHEET.INNER SKIN 16swg (1.6mm) ZINTEC SHEET.TREATMENT 100mm RWA45 MINERAL WOOL.
WALL:OUTER SKIN 14swg (2.0mm) STEEL CORRUGATED SHEET.INNER SKIN 18swg (1.2mm) ZINTEC SHEET.TREATMENT 100mm RWA45 MINERAL WOOL.
FLOOR:STRUCTURE 300x100x46 UKPFC PERIMETER BEAMS.STRUCTURE 260x90x35 UKPFC CROSS BEAMS.STRUCTURE 200x75x23 UKPFC CROSS BEAMS.TRIMMERS 10swg FOLDED CHANNEL.FLOOR PLATE 5mm PLAIN STEEL PLATE.GLAND PLATES 6mm THK. MARINE GRADE ALUMINIUM PLATE.TREATMENT 100mm RWA45 MINERAL WOOL.
EARTH BAR 50x6 THK.FLAT NON INSULATED COPPER
DOOR FURNITURE DETAILS:
DOOR FURNITURE:EXTERNAL STAINLESS STEEL DOOR HANDLE EXIDOR (0210081005) LEVER OPERATED C/W EURO-PROFILECYLINDER & THREE KEYS.INTERNAL EXIDOR (0210180324) 3 POINT LATCHING EMERGENCY PANIC BAR & DOOR GEAR.INTERNAL & EXTERNAL PULL HANDLES (HENDERSON 436)DOOR STAY, BRADGATE STANDARD BCL-DS-01
HINGES:FURGOCAR 304 STAINLESS STEEL MAINTENANCE FREE .
WEATHER LOUVERS (TRANSFORMER ROOM):
EXTERNAL WEATHER LOUVERS COMBINED WITH INTERNAL MESH GIVE AN IP33 PROTECTION RATING.
EARTH BAR:
INTERNAL HIGH LEVEL PERIMETER EARTH BAR, 50x6 thk. UN-INSULATED PLAIN COPPER MOUNTED ON TOP HATFOLDED SECTIONS. WITH DROPPERS & THROUGH WALL EXTERNAL CONNECTION POINTS. NOTE THAT ONLY THEHORIZONTAL CABLE CONNECTION EARTH BAR LENGTH WILL BE MOUNTED ON INSULATION BOBBINS. BOLTEDDISCONNECT LINK AT LOW LEVEL.
630 A
PERT
URE
620 A
PERT
URE
36941
075
75
800
800
100
RUBBER MAT IN FRONT OF SWITCHBOARDS
RUBBER MAT IN FRONT OF SWITCHBOARDS
32
33
01
02
1401
02 15
LADDER RACK CARRYINGSERVICE CABLES
06
23 24
25 26
12 13
09
08
10
30
08
05
28
11
16
27
19
28
11
16
27
19
29
17
18
31
250 mm² APERTURE THRO' BASE C/WMARINE GRADE ALUM. GLAND PLATE TO U/SIDE.
(ACCESS FOR TRANSFORMER EARTH CABLE)
250 mm² APERTURE THRO' BASE C/WMARINE GRADE ALUM. GLAND PLATE TO U/SIDE.
(ACCESS FOR TRANSFORMER EARTH CABLE)
APERTURE THRO' BASE C/W MARINEGRADE ALUM. GLAND PLATE TO U/SIDE.
(EARTH CABLE ACCESS TO CABLE BOX/SPLITTER PANEL)
200
280
5 OFF CABLE APERTURES THROUGHBASE FRAME & FLOOR PLATE.C/W MARINE GRADE ALUMINIUM GLANDPLATES TO UNDERSIDE
4 OFF CABLE APERTURES THROUGHBASE FRAME & FLOOR PLATE.C/W MARINE GRADE ALUMINIUM GLANDPLATES TO UNDERSIDE
725 APERTURE
75
03
04
34
34
1325 LOUVERS 1325 LOUVERS
1325 LOUVERS 1325 LOUVERS
06
07
07
THIS DRAWING IS THE SOLE PROPERTY OF 'BRADGATE CONTAINERS LTD' AND MAY NOTBE COPIED OR USED FOR ANY PURPOSE OTHER THAN THAT FOR WHICH IT IS SUPPLIEDWITHOUT THE EXPRESS WRITTEN PERMISSION OF 'BRADGATE CONTAINERS LTD' (©2013)
BRADGATE CONTAINERS LTD. LEICESTER ROAD,
SHEPSHED, LEICS.
LE12 9EG
ISSUE SHEET SIZE
A0
BQ/
THIRD ANGLE PROJECTION
IF IN DOUBT ASK - DO NOT SCALE GENERAL FABRICATING TOLERANCES
ALL DIMENSIONS UP TO & INCLUDING 300 ±1 IN MILLIMETRES 301 UP TO 1500 ±2UNLESS STATED ABOVE 1500 ±3
DESCRIPTION
ORIGINAL ISSUE
ABB Ltd.
17/9/13G.N. Rogers17433
1:20
N/A NCR
DH 17/9/13
17/9/13
Equipment Layout of Living Quarters Substation Module(690V/400V) for BP Clair Ridge Temporary Substations
13240-1-1 B 1
SUPPLIER DRAWING DECAL
ProjectID
Alternative Document No.
1- Accepted (Reviewed andAgreed)
2- Comments to be Incorporatedand Resubmitted
Signature Date
3- Rejected, Do Not Start Work(Comments to beIncorporated andresubmitted)
4- For Information
Review Status
Short RequisitionNo/PO Identifier
Sequence Sheet. Rev
5- Cancelled/Superseded
6- As Built
Purchaser Document Number
Originator/ContractorCode
SDDRCode
CLB- AA- AANNNN-ANN ANN- NNNN- (NN) NN
B 6CUPDATED INLINE WITH COMMENTS
BY AMEC REC'D ON 17/10/13. 19.11.13
4040
408
PLAN VIEW ON MODULE ROOF
Y
7500
3000
300
1500
3708
5208
SIDE ELEVATION
END VIEW
HVAC SERVICES PASSTHROUGH TRANSIT
END VIEW
7500
ARROW 'Y' - SIDE ELEVATION
2255
CLE
ARAN
CE H
T.
2555
3400
845
751
8251 O/A LENGTH
1100 1100 STRUT. OPENING 1800 20 REF20 REF1665.5
9165.5 REF
1800
6134 APPROX.
40002134 APPROX.
DOOR GUTTER
4 OFF LIFTING LUGS
7350 LIFT LUG CRS.75 75
M12 PERIMETER EARTHBAR EXTERNALCONNECTION
M12 PERIMETEREARTH BAR EXTERNAL
CONNECTION
EARTH BOSS TAPPED M12(EXTERNAL BUILDING EARTH CONNECTION)
UNDERSTRUCTURE BOLT TOGETHER FRAMESSEE NOTES & DRAWING 13240-1-6 SHEET 1
RETANGULAR BASE EYE PLATESFULLY WELDED TO SIDE & END RAILS
FOR LASHING DURING TRANSPORTATION(6 POSITIONS EACH SIDE & 4 POSITIONS EACH END)
2795
STR
UCTU
RAL O
PENI
NG
1800 STRUCTURAL OPENING1800 STRUCTURAL OPENING
2 OFF BOLT-ON UN-LINNED CORRUGATEDREMOVABLE END PANELS. C/W A PAIR OFM20 EYEBOLTS TO BS 4278 POSITIONED ATTHE TOP CORNERS. SEALED WITH NEOPRENE STRIPALL ROUND TO PREVENT WATER INGRESS.ALL FIXINGS ARE STAINLESS STEEL SECURITY TYPE.BOTH PANELS ARE EARTH BONDED TO MODULE.2 APERTURES WITH THE STRUCTURAL OPENINGSSHOWN ARE THE ONLY ACCESS INTO THE TRANSFORMERROOM & ALLOW TRANSFORMER INSTALLATION OR REMOVAL.BOTTOM THRESHOLDS ARE REMOVABLE.
REMOVABLE BOTTOM THREASOLDTO ALLOW TRANSFORMER INSTALLATIONOR REMOVAL I.E. GIVING CLEAR ACCESSTO AT FLOOR LEVEL (TYP. 2 POS.)
2750
5 FLO
OR P
LT.
1800
100 3800 100
3400 200200
2370
REF
(SW
. BOA
RD C
ABIN
ET)
2370
REF
(SW
. BOA
RD C
ABIN
ET)
5 FLO
OR P
LT.
610 APER. 630 APER.185 1852190 REF.
1675
125
M16 SAFETY HARNESS BOSSES(TYPICAL 8 POSITIONS)
HVAC AHU CONDENSATEDRAIN PASSES OUT THRO'THE FLOOR
2587
APP
ROX.
LADDER RACK CARRYINGSERVICE CABLES
LADDER RACKCARRYING
SERVICE CABLES
LADDER RACK CARRYINGSERVICE CABLES
100 3800 100
370
5 FLO
OR P
LT.
2205
.5
1884
.55 F
LOOR
PLT
.
490
490
500 1510A
A
C
C
SECTION C-C THROUGH TRANSFORMER ROOMSECTION A-A THROUGH SWITCH ROOM
86654
5
LV S
IDE
HV S
IDE
LV S
IDE
HV S
IDE
LADDER RACKCARRYINGPOWER CABLES
LADDER RACK CARRYINGPOWER CABLES
4040
3708
.1
1100 1100 1800 2020
2600
DOOR GUTTER
300
1700
1700
END VIEW (HVAC SYSTEM, STAIRS, LANDING & UNDERSTRUCTURE OMMITTED FOR CLARITY)
1700
SMALLPOWER
DIST.BOARD
0307
2804
20
20 20
20
08
08
08
3118 29
3118 29
30
10
05
34
16
27
11
19
21
100 3800 100
SECTION B-B (UNDER-STRUCTURE OMMITTED FOR CLARITY)
1000
1300
B
B
32 22 33
0304
STAINLESS STEEL TRANSITFRAME FOR POWER CABLES
(S.S. TYPE - TO STOP EDDY CURRENTS)
STEEL TRANSIT FRAME FOREARTH CABLES
STEEL TRANSIT FRAMEFOR SIGNAL CABLES
STAINLESS STEEL TRANSITFRAME FOR POWER CABLES(S.S. TYPE - TO STOP EDDY CURRENTS)
STEEL TRANSIT FRAME FOREARTH CABLES
STEEL TRANSIT FRAMEFOR SIGNAL CABLES
UNDERSTRUCTURE BOLT TOGETHER FRAMESSEE NOTES & DRAWING 13240-1-6 SHEET 1
370500
LADDER RACKCARRYING
POWER CABLES
02
01
M12 PERIMETEREARTH BAREXTERNAL
CONNECTION
EARTH BARFOR EARTH
CABLECONNECTIONS
06
09
CABLE TRAY FORSIGNAL CABLES
03
04
08
TRANSFORMER ROOM VENTILATIONWEATHER LOUVERS WITH MESHPANEL TO INSIDE (SEE NOTES).
TRANSFORMER ROOM VENTILATIONWEATHER LOUVERS WITH MESHPANEL TO INSIDE (SEE NOTES).
40004000
75THK PERSONNEL / EQUIPMENT ACCESS DOOR C/W 300 x 300 mm DOUBLE GLAZEDWINDOW FITTED WITH GEORGIAN WIRED SAFETY GLASS.
LINED WITH 45 kg/m³ DENSITY MINERAL WOOL.DOOR STAY: St.St. BSL-DS01. COMPRESSION SEAL ALL ROUND.
ALL FIXINGS ARE SECURITY TYPE. HENDERSON 436 PULLHANDLES (INSIDE AND OUT), EARTH BONDED AND J-SECTION
GUTTER STRIP TO HEADER. EXTERNAL DOOR FURNITURE: EXIDOR (021 008 1005)STAINLESS LEVER HANDLE C/W EURO-PROFILE CYLINDER. INTERNAL
DOOR FURNITURE: EXIDOR (021 018 0324) 3-POINT LATCHING EMERGENCYPANIC BAR. HINGES: 3 OFF FURGOCAR 304 STAINLESS STEEL
MAINTENANCE FREE HINGE. INOX COD. 1015-0619A
09
EARTH BOSS TAPPED M12(EXTERNAL BUILDING EARTH CONNECTION)
EARTH BOSS TAPPED M12(EXTERNAL BUILDING EARTH CONNECTION
FOR STAIRS & LANDINGS EARTH BRAID)
M12 PERIMETER EARTHBAR EXTERNALCONNECTION FROMTRANSFORMER ROOM
!Warning
No Equipment is tobe placed or wheeledonto the landing area
WARNING SIGN SHOWN, FITTEDTO INSIDE OF DOOR
THIS DRAWING IS THE SOLE PROPERTY OF 'BRADGATE CONTAINERS LTD' AND MAY NOTBE COPIED OR USED FOR ANY PURPOSE OTHER THAN THAT FOR WHICH IT IS SUPPLIEDWITHOUT THE EXPRESS WRITTEN PERMISSION OF 'BRADGATE CONTAINERS LTD' (©2013)
BRADGATE CONTAINERS LTD. LEICESTER ROAD,
SHEPSHED, LEICS.
LE12 9EG
ISSUE SHEET SIZE
A0
BQ/
THIRD ANGLE PROJECTION
IF IN DOUBT ASK - DO NOT SCALE GENERAL FABRICATING TOLERANCES
ALL DIMENSIONS UP TO & INCLUDING 300 ±1 IN MILLIMETRES 301 UP TO 1500 ±2UNLESS STATED ABOVE 1500 ±3
DESCRIPTION
ORIGINAL ISSUE
ABB Ltd.
26/6/13G.N. Rogers17433
1:30
N/A NCR
DH 30/9/13
30/9/13
G.A. of Living Quarters Substation Module (690V/400V)for BP Clair Ridge Temporary Substations
13240-1-1 B 2
SUPPLIER DRAWING DECAL
ProjectID
Alternative Document No.
1- Accepted (Reviewed andAgreed)
2- Comments to be Incorporatedand Resubmitted
Signature Date
3- Rejected, Do Not Start Work(Comments to beIncorporated andresubmitted)
4- For Information
Review Status
Short RequisitionNo/PO Identifier
Sequence Sheet. Rev
5- Cancelled/Superseded
6- As Built
Purchaser Document Number
Originator/ContractorCode
SDDRCode
CLB- AA- AANNNN-ANN ANN- NNNN- (NN) NN
DRAWING TO BE READ IN CONJUNCTION WITH SHEET 1
B 6E'LANDING AREA' WARNING SIGN ADDED
TO INSIDE OF DOOR 19.11.13