ALL FIRE SPRINKLER PIPING SHALL BE CONCEALED ABOVE CEILING OR IN
SPRINKLER CONTRACTOR SHALL COORDINATE SPRINKLER HEAD INSTALLATION
WITH NEW LIGHTING AND DIFFUSER LOCATIONS.
ALL SPRINKLER HEADS SHALL BE PLACED IN THE CENTER OF ALL CEILING
TILES WHERE NEW CEILING TILES ARE LOCATED.
ALL DIMENSIONS AND EXISTING CONDITIONS SHALL BE CHECKED AND VERIFIED
BY CONTRACTOR AT THE SITE.
REQUIREMENTS. PIPE SIZING SHALL BE BY HYDRAULIC CALCULATION.
INSTALLATIONS SHALL CONFORM TO NFPA AND INSURANCE UNDERWRITER
OF WORK AND SPECIFICATIONS. ALL SPRINKLER SYSTEM COMPONENT
WALLS, WHERE POSSIBLE.
3.
5.
4.
2.
SUPPRESSION INSTALLATION AS PER THE INTENT OF THE PROJECT SCOPE
RESPONSIBLE TO PROVIDE ALL COMPONENTS FOR A COMPLETE FIRE
REVIEW AND INFORMATIONAL PURPOSES ONLY. THE CONTRACTOR IS
SPRINKLER SYSTEM COMPONENTS ARE INDICATED ON THE DRAWING FOR
FIRE PROTECTION GENERAL NOTES
1.
QUICK RESPONSE UPRIGHT SPRINKLER HEAD (SP)
ON DRAWING AND NOTE NUMBER
INDICATES NOTE LOCATED ELSEWHERE
QUICK RESPONSE DRY PIPE SPRINKLER HEAD (SP)
FUNNEL DRAIN
GENERAL CONTRACTOR
HEATING CONTRACTORHC
CAP OR PLUG
CHECK VALVE
GATE OR GLOBE VALVE
BALANCING COCK
OS & Y SUPERVISED VALVE
FNL DR
GC
CLG
BLW
ABV
CEILING
BELOW
ABOVE
QUICK RESPONSE SEMI-RECESSED PENDENT
FIRE PROTECTION SYMBOL AND ABBREVIATION SCHEDULE
FIRE STANDPIPE LINE (F)F
FIRE SPRINKLER LINE (FS)FS
SPRINKLER HEAD (SP)
QUICK RESPONSE SIDEWALL SPRINKLER HEAD (SP)
QUICK RESPONSE UPRIGHT SPRINKLER HEAD BELOW OBSTRUCTION (SP)
FIRE DEPARTMENT CONNECTION
XX
FIRE SPRINKLER WATER DEMAND
SEE SCHEDULE
.10 GPM/SQ FT
SEE SCHEDULE
CATEGORY 2
GUEST ROOMS AND PUBLIC AREAS
SPRINKLER TEMPERATURE RATING:
SEE SCHEDULE
SPRINKLER SCHEDULE:
EXCEPT AS INDICATED BELOW:
ROOM/SPACE
ALL SPRINKLER HEADS SHALL BE QUICK-RESPONSE, 155° F TO 165° F, SEMI-RECESSED TYPE
QUICK RESPONSE, CORROSION RESISTANT
SPRINKLER TYPE
MECHANICAL/ELECTRICAL ROOMS
ELEVATOR MACHINERY
SWIMMING POOLS
QUICK RESPONSE
QUICK RESPONSE
TEMPERATURE RATING
212° F
155° F TO 165° F
212° F
1. FIRE SPRINKLER WATER DEMAND INDICATED ABOVE PENDING INSURANCE UNDERWRITER
NOTE:
AND AUTHORITY HAVING JURISDICTION APPROVAL.
HOSE STREAM ALLOWANCE:
SPRINKLER HEAD TYPE:
SPRINKLER 'K' FACTOR:
250 GPM
K=5.6
SEE SCHEDULE
100 GPM
K=5.6
BACK OF HOUSE AREAS
DESIGN AREA OF WATER APPLICATION:
TYPE OF SPRINKLER SYSTEM:
OCCUPANCY CLASSIFICATION:
MINIMUM DENSITY:
.15 GPM/SQ FT
1500 SQ FT
ORDINARY GROUP 1
WET
WET
LIGHT
1
CATEGORY 1
SEE SCHEDULE
250 GPM
SEE SCHEDULE
K=5.6
2
ORDINARY GROUP I
.15 GPM/SQ FT
1500 SQ FT
WET
KITCHEN AND KITCHEN STORAGE
CATEGORY 33
WITH SHALLOW (1/2" D) ESCUTCHEONS (IF VISIBLE)
QUICK RESPONSE PENDENT TYPE IN GUEST LAUNDRY, ADMIN AREA, AND BACK-OF-HOUSE AREAS.
WHITE FINISH
QUICK RESPONSE SEMI-RECESSED IN GUEST SUITES AND PUBLIC SPACES.
CAGE-TYPE COVERS IN SERVICE AND UTILITY AREAS.3.
2.
1.
SPRINKLER APPLICATION CRITERIA:
1500 SQ FT
DATE OF TEST:
04/24/13
WATER TEST INFORMATION
TEST HYDRANT ELEVATION:
STATIC PRESSURE:
RESIDUAL PRESSURE:
SOURCE OF INFORMATION:
FLOW RATE:
TEST HYDRANT: BAUM & VINTAGEB1480, BAUM B747
---
75 PSI
72 PSI
1280 GPM
RYCO FIRE PROTECTION
CONCEALED PENDENT SPRINKLER HEADS ARE NOT PERMITTED.4.
STAINLESS STEEL, WAX COATED
REFER TO MARRIOTT MODULE 14 AND THE PROJECT SPECIFICATIONS FOR
ADDITIONAL INFORMATION REGARDING FIRE SPRINKLER SYSTEM REQUIREMENTS.
SPRINKLER CONTRACTOR SHALL COORDINATE BRANCH PIPING INSTALLATIONS
TO AVOID PIPING INSTALLATIONS IN BEARING WALLS.
6.
7.
QUICK RESPONSE EXTENDED COVERAGE SIDEWALL SPRINKLER HEAD (SP)
SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLETE COMPLIANCE
WITH MARRIOTT MODULE 14.
8.POOL EQUIPMENT
THE RESULTS OF A WATER FLOW TEST FROM THE LOCAL WATER AUTHORITY.
THE TEST MUST BE DATED LESS THAN ONE (1) YEAR FROM THE PRESENT DATE
TO BE CONSIDERED AN ACCEPTABLE TEST. IF THE WATER AUTHORITY CANNOT
PROVIDE THIS INFORMATION, THEN THE FIRE SPRINKLER CONTRACTOR SHALL
CONDUCT A NEW WATER FLOW TEST. THE CONTRACTOR WILL BE RESPONSIBLE
FOR ANY COSTS INCURRED TO DO THE NEW WATER FLOW TEST, AND WILL
CONDUCT THE TEST WITH THE OWNER, ENGINEER AND INSURANCE COMPANY
PRESENT AS WITNESSES. ANY NEW WATER FLOW TEST SHALL BE COORDINATED
WITH THE LOCAL WATER AUTHORITY.
9.
QUICK RESPONSE DRY SIDEWALL SPRINKLER HEAD (SP)
ELEVATOR HOISTWAY QUICK RESPONSE 250° F
F0.01
SYMBOLS, ABBREVIATIONSAND GENERAL NOTESFIRE PROTECTION
SUPERVISED VALVE
FLOW SWITCH
INSPECTOR'S TEST VALVE - SEE DETAIL ON DRAWING
FP5.1
2 1/2" FIRE DEPARTMENT VALVE W/ 2 1/2" X 1 1/2" REDUCER IN RECESSED
CABINET
4" FIRE STANDPIPE
4" SPRINKLER RISER
2" SPRINKLER TEST DRAIN
TERMINATE 2" SPRINKLER TEST DRAIN OVER CONCRETE SPLASH BLOCK
WITH INSECT SCREEN.
INSTALL FIRE SPRINKLER IN LAUNDRY CHUTE AS REQUIRED TO MEET NFPA
13 REQUIREMENTS.
ALL FIRE SPRINKLER PIPING LOCATED IN THE POOL AREA SHALL BE
GALVANIZED PIPING, WITH STAINLESS STEEL WAX COATED SPRINKLER
HEADS.
HIGH TEMPERATURE UPRIGHT QUICK RESPONSE UPRIGHT SPRINKLER
HEAD.
COORDINATE SPRINKLER HEAD LOCATIONS WITH INTERIOR DESIGN
DRAWINGS.
4" FIRE STANDPIPE
KEYNOTES:
2
3
4
5
6
7
8
9
10
11
12
1
13
MA
TC
HL
IN
E
MA
TC
HL
IN
E
STORAGE
017a
MECHANICAL/ELECTRICAL
020
SITE STORAGE
019
COR.
016
KITCHEN
017
BUFFET
009
MENS
014
WOMENS
015
BILLIARDS
013
DINING AREA
012
COMMUNAL AREA
011
DEN
010
SOCIAL SEATING AREA
008
1
1
1
2
F
SP SP
9'-0" CLG. HT.
9'-3" CLG. HT.
9'-0" CLG. HT.
11'-8" CLG. HT.
12'-4" CLG. HT.
10'-0" CLG. HT.
10'-0" CLG. HT.
OPEN TO
STRUCTURE
OPEN TO
STRUCTURE
OPEN TO
STRUCTURE
7'-6" CLG. HT.
7'-6" CLG. HT.
9'-0" CLG. HT.
9'-0" CLG. HT.
11'-0" CLG. HT.
9'-6" CLG. HT.
9'-0" CLG. HT.
9'-6" CLG. HT.
11'-0" CLG. HT.
10'-0" CLG. HT.
10
8'-6" CLG. HT.
8'-6" CLG. HT.
9'-6" CLG. HT.
SPRAY-APPLIED
ACOUSTICAL
INSULATION
SPRAY-APPLIED
ACOUSTICAL
INSULATION
SPRAY-APPLIED
ACOUSTICAL
INSULATION
4
5
6
2
1
3
TERMINATE 2" SPRINKLER TEST
DRAIN WITH INSECT SCREEN
COORDINATE SPRINKLER HEAD LOCATIONS
WITH INTERIOR DESIGN DRAWINGS.
NOTE:
13
CHECK VALVE
F1.01A
PARTIAL GROUND FLOORFIRE PROTECTION
01 FIRE PROTECTIONSCALE: 1/8" = 1'-0"
PARTIAL GROUND FLOOR PLAN
SUPERVISED VALVE
FLOW SWITCH
INSPECTOR'S TEST VALVE - SEE DETAIL ON DRAWING
FP5.1
2 1/2" FIRE DEPARTMENT VALVE W/ 2 1/2" X 1 1/2" REDUCER IN RECESSED
CABINET
4" FIRE STANDPIPE
4" SPRINKLER RISER
2" SPRINKLER TEST DRAIN
TERMINATE 2" SPRINKLER TEST DRAIN OVER CONCRETE SPLASH BLOCK
WITH INSECT SCREEN.
INSTALL FIRE SPRINKLER IN LAUNDRY CHUTE AS REQUIRED TO MEET NFPA
13 REQUIREMENTS.
ALL FIRE SPRINKLER PIPING LOCATED IN THE POOL AREA SHALL BE
GALVANIZED PIPING, WITH STAINLESS STEEL WAX COATED SPRINKLER
HEADS.
HIGH TEMPERATURE UPRIGHT QUICK RESPONSE UPRIGHT SPRINKLER
HEAD.
COORDINATE SPRINKLER HEAD LOCATIONS WITH INTERIOR DESIGN
DRAWINGS.
4" FIRE STANDPIPE
KEYNOTES:
2
3
4
5
6
7
8
9
10
11
12
1
13
MA
TC
HL
IN
E
MA
TC
HL
IN
E
CORRIDOR
035
REFUSE/
RECYCLE
052
CORRIDOR
051
PRE-FUNCTION
026
STORAGE
034
CORR.
028
GM OFFICE
027
COMPUTER
023
EMPLOYEE
LOUNGE
047
POOL TOILET
050
POOL EQUIPMENT
039
INDOOR POOL
049
CORRIDOR
048
CORRIDOR
038
FITNESS
040
ELEVATOR
LOBBY
025
OFFICE
044
LINEN
STORAGE
043
LAUNDRY
045
MEETING ROOM
STORAGE
042
CORRIDOR
030
SALES OFFICE
029
WORK AREA
022
MARKET
004
STORAGE
024
STAIR 2
054
F
1
1
F
Xref E:\HOSPITALITY\HOTELS\Concord Hospitality\Hyatt House Shadyside\Drawings\Plans\Ground Floor Plan.dwg
SP SP
11'-8" CLG. HT.
12'-4" CLG. HT.
8'-6" CLG. HT.
9'-0" CLG. HT.
11'-0" CLG. HT.
11'-0" CLG. HT.
9'-0" CLG. HT.
9'-0" CLG. HT.
10'-0" CLG. HT.
9'-8" CLG. HT.
9'-8" CLG. HT.
8'-0" CLG. HT.
7'-6" CLG. HT.
7'-6" CLG. HT.
9'-0" CLG. HT.
OPEN TO
STRUCTURE
9'-0" CLG. HT.
8'-0" CLG. HT.
9'-0" CLG. HT.
9'-0" CLG. HT.
8'-0" CLG. HT.
9'-0" CLG. HT.
OPEN TO
STRUCTURE
12'-4" CLG. HT.
CS CS
8'-0" CLG. HT.
OPEN TO
STRUCTURE
OPEN TO
STRUCTURE
OPEN TO
STRUCTURE
7'-0
" C
LG
. H
T.
9
7'-0
" C
LG
. H
T.
4
5
7
8
9
10
10
10
10
11
13
10
F1.01B
PARTIAL GROUND FLOORFIRE PROTECTION
01 FIRE PROTECTIONSCALE: 1/8" = 1'-0"
PARTIAL GROUND FLOOR PLAN
MA
TC
HL
IN
E
MA
TC
HL
IN
E
STAIR 1
253
CORRIDOR
241
CORRIDOR
240
STORAGE
237
ELECTRICAL
ROOM
236
217
KD
TYPE 2
216
TYPE 2
214
KS
215
KS
213
KDL
212
KD
TYPE 1
210
KS
211KS
209
QQA
208
KS
207
K
TYPE 2
206
K
TYPE 1
205
TYPE 1
201
TYPE 1
202
FSFS
F
S
1
2
4
5
6
7
10
QUICK RESPONSE SEMI-RECESSED
PENDENT SPRINKLER HEAD
AT TOP OF STAIR. FIETH LEVEL ONLY
QUICK RESPONSE SEMI-RECESSED
PENDENT SPRINKLER HEAD
(TYPICAL)
QUICK RESPONSE SEMI-RECESSED
PENDENT SPRINKLER HEAD
(TYPICAL)
F1.02A
PARTIAL TYPICAL 2ND-5THLEVEL - FIRE PROTECTION
01 FIRE PROTECTION
SCALE: 1/8" = 1'-0"
PARTIAL TYPICAL SECOND TO FIFTH LEVEL FLOOR PLAN
MA
TC
HL
IN
E
MA
TC
HL
IN
E
STAIR 2
254
CORRIDOR
243
CORRIDOR
HOUSE
KEEPING
235
ELEVATOR
LOBBY
234
KS
CORNER
229
KDA
228KD
TYPE 1
226
KD
TYPE 1
224
KS
225
KS
223
KS
221
KS
219
KS
217
TYPE 2
220
KD
TYPE 2
218
KD
TYPE 2
216
ELEV
2
ELEV
1
FSFS
F
S
SUPERVISED VALVE
FLOW SWITCH
INSPECTOR'S TEST VALVE - SEE DETAIL ON DRAWING FP5.1
2 1/2" FIRE DEPARTMENT VALVE W/ 2 1/2" X 1 1/2" REDUCER
2 1/2" FIRE DEPARTMENT VALVE W/ 2 1/2" X 1 1/2" REDUCER IN RECESSED
CABINET
4" FIRE STANDPIPE
4" FIRE SPRINKLER RISER
2" SPRINKLER TEST DRAIN
INSTALL FIRE SPRINKLER IN LAUNDRY CHUTE AS REQUIRED TO MEET NFPA
13 REQUIREMENTS.
4" FIRE STANDPIPE
KEYNOTES:1
2
3
4
5
6
7
8
9
FS
1
2
3
4
5
6
8
9
10
10
QUICK RESPONSE UPRIGHT
SPRINKLER HEAD AND
ASSOCIATED PIPING AT TOP
OF ELEVATOR SHAFT.
FIFTH LEVEL ONLY
QUICK RESPONSE SEMI-RECESSED
PENDENT SPRINKLER HEAD
AT TOP OF STAIR. FIETH LEVEL ONLY
QUICK RESPONSE SEMI-RECESSED
PENDENT SPRINKLER HEAD
(TYPICAL)
QUICK RESPONSE SEMI-RECESSED
PENDENT SPRINKLER HEAD
(TYPICAL)
F1.02B01 FIRE PROTECTION
SCALE: 1/8" = 1'-0"
PARTIAL TYPICAL SECOND TO FIFTH LEVEL FLOOR PLAN
PARTIAL TYPICAL 2ND-5THLEVEL - FIRE PROTECTION
MA
TC
HL
IN
E
MA
TC
HL
IN
E
F1.03A
PARTIAL TYPICAL 2ND-5THLEVELS ABOVE CEILING
01 FIRE PROTECTIONSCALE: 1/8" = 1'-0"
PARTIAL TYPICAL FLOOR PLAN - 2ND THRU 5TH LEVELS ABOVE CEILING
FIRE PROTECTION
MA
TC
HL
IN
E
MA
TC
HL
IN
E
F1.03B01 FIRE PROTECTION
SCALE: 1/8" = 1'-0"
PARTIAL TYPICAL FLOOR PLAN - 2ND THRU 5TH LEVELS ABOVE CEILING
PARTIAL TYPICAL 2ND-5THLEVELS ABOVE CEILINGFIRE PROTECTION
TERMINATE SLEEVE FLUSH
WITH FINISH WALL SURFACE
FINISHED WALL SURFACE
FIRE RATED PARTITION
RATED WALLS AND MAKE
FIREPROOF AND SMOKE TIGHT.
PIPE TO BE CENTERED IN
SLEEVE. DO NOT SUPPORT
PIPE FROM SLEEVE.
SEAL SLEEVE THRU FIRE
PIPE INSULATION SHALL
TERMINATE AT WALL.
FINISHED WALL SURFACE
PROVIDE FIREPROOFING MATERIAL
BETWEEN PIPE SLEEVE AND PIPE.
INTERIOR WALLS
C
L
PIPE
SCHEDULE 40 STEEL PIPE SLEEVE
OF SIZE TO PASS PIPE.
L
CC
L
FIRE STANDPIPE- SEE FIRE
2 1/2" NIPPLE
NEW FIRE STANDPIPE
PIPE CLAMP TIGHT TO FLOOR SLAB
SPANNER LUGS
PROTECTION FLOOR PLANS FOR
STANDPIPE LOCATIONS AND SIZES
PACK SPACE BETWEEN SLEEVE AND PIPE
WITH FIREPROOF AND WATERPROOF MATERIAL
TO MAKE AIR-TIGHT AND WATER-TIGHT. (NOT
PIPE SLEEVE (MINIMUM 8")
REQUIRED IN STAIRWELLS)
(4
'-0
") M
AX
IM
UM
INSTALL PRESSURE GAUGE
AT TOP OF EACH FIRE
STANDPIPE
FIRE DEPARTMENT
VERIFY THREAD ON VALVE WITH LOCAL
2 1/2" FIRE DEPARTMENT HOSE VALVE
W/2 1/2" x 1 1/2" REDUCER
PIPE SUPPORTS
FLOW SWITCH
TO BUILDING
6"
DRAIN VALVE PLUGGED AND
CHAINED CLOSED
EXTEND AND TERMINATE
OVER FUNNEL DRAIN
6" FIRE PROTECTION
WATER SUPPLY
REFER TO SITE UTILITY PLAN
WALL SLEEVE & SEAL
OR MECHANICAL
SLEEVE SEAL
EXTERIOR WALL
4"
A A
20 GAUGE STEEL
SPRINKLER SHIELD
SHEET METAL SCREWS 2" ON
CENTERS. SMOOTH SCREW
HEADS WITH FILE OR EMERY
PAPER. ATTACHMENT MAY BE
BY SPOT WELDING
FRONT ELEVATION
SECTION A-A
SIDE ELEVATION
18
"
3"
1"
C
H
U
T
E
W
A
L
L
6" RADIUS
5"x 6" INCREASER
WATER FLOW SWITCH
6" FIRE STANDPIPE-
SEE FLOOR PLANS
SUPERVISORY SWITCH
CONTROL VALVE WITH
INDICATING TYPE FLOOR
CHECK VALVE
PRESSURE GAUGE
TO FIRE SPRINKLERS
01 (SHOWN FROM RISER) NOT TO SCALE
02 LINE/CHUTE SPRINKLER DETAILNOT TO SCALE
05 FIRE DEPARTMENT VALVE DETAILNOT TO SCALE
04 PIPE SLEEVE THRU FIRE-RATED WALL DETAILNOT TO SCALE
03 FIRE PROTECTION WATER SERVICE DETAILNOT TO SCALE
SPRINKLER FLOOR CONTROL VALVE ASSEMBLY DETAIL
06DETAILED CORRIDOR SECTION FOR ELECTRICAL & MECHANICAL ITEMSNOT TO SCALE
6" DOUBLE DETECTOR
CHECK VALVE ASSEMBLY
6"
SITE GLASS
INSPECTORS TEST VALVE
EXTEND SPRINKLER TEST
DRAIN TO EXTERIOR. SEE
FLOOR PLAN FOR LOCATION
FROM END OF REMOTE BRANCH
LINE FOR EACH ZONE
4"Ø MAIN
SPRINKLER PIPE
8"W x 4"H EXH DUCT 8"W x 4"H SA DUCT
8" HIGH MAX SUPPLY AIR DUCT
WIDTH VARIES, REFER TO FLOOR PLANS
8" HIGH MAX EXHAUST AIR DUCT
WIDTH VARIES, REFER TO FLOOR PLANS
DOWN
LIGHT
BATHROOM
CORRIDOR
GUESTROOM TV COAX AND/OR TELE/DATA HOMERUNS
BUNDLED TOGETHER ABOVE THE CEILING WITH PLENUM
RATED TIE-WRAPS 5'-0" O.C. AND SUPPORTED FROM
THE STRUCTURE ABOVE THE BRIDAL RINGS 10'-0" OC (TYP)
1"C STUBS FOR TELEPHONE AND
CABLE TV WIRING IN EACH
GUESTROOM (TYPICAL).
1" SPRINKLER PIPING INTO EACH
GUEST ROOM
1" SPRINKLER PIPING INTO EACH
GUEST ROOM
NOTE:
HVAC, PLUMBING, AND ELECTRICAL CONTRACTORS
SHALL COORDINATE LOCATIONS OF ALL DUCTS,
PIPING, CONDUIT, ETC., IN THE CORRIDOR SPACE.
CORRIDOR WALL
CORRIDOR WALL
6x6 ERC
6x6 SDC
1" CONDUITS
WALL MOUNTED 5" STORZ FIRE
DEPARTMENT CONNECTION
F6.01
DETAILSFIRE PROTECTION