WIRING DEVICESJUNCTION BOX, WALL MOUNTED, +18" UON.
JUNCTION BOX, MOUNTED IN FLUSH FLOOR BOX.
JUNCTION BOX, MOUNTED FLUSH IN CEILING.
JUNCTION BOX, SURFACE OR PENDANT MOUNTED TO STRUCTURE IN ACCESSIBLE CEILING SPACE.
JUNCTION BOX, MOUNTED ON CONDUIT STANCHION FLOOR PENETRATION, +12" UON.
SINGLE-PLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON.
DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, WALL MOUNTED, +18" UON.
DENOTES WALL MOUNTED OVER COUNTER, 6" ABOVE BACK SPLASH UON. BUT NO HIGHER THAN ADA REQUIREMENTS.
'G' DENOTES GROUND FAULT CURRENT INTERRUPTER (GFCI), 'A' DENOTES ARC FAULT CURRENT INTERRUPTER (AFCI).
DUPLEX CONVENIENCE RECEPTACLE DEVICE WITH INTEGRAL USB PORTS, WALL MOUNTED,+ 18" UON.
DUPLEX RECEPTACLE, WEATHER RESISTANT WITH GROUND FAULT CURRENT INTERRUPTER 'GFCI', WITH WEATHERPROOF COVER, WALL MOUNTED, +18" UON.
SHADING DENOTES SPLIT WIRED DEVICE.
SHADING DENOTES DEVICE CONNECTED TO EMERGENCY POWER CIRCUIT.
SHADING DENOTES DEVICE CONTROLLED PER CA T24 130.5(d).
HORIZONTALL MOUNTED DUPLEX RECEPTACLE, +18" UON.
SHADING DENOTES SPECIALTY DEVICE, TYPE AS NOTED ON PLANS.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLUSH FLOOR BOX.
DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLUSH FLOOR BOX.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FIRE-RATED POKE-THRU FLOOR FITTING.
DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FIRE-RATED POKE-THRU FLOOR FITTING.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED FLUSH IN CEILING.
DOUBLE DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED FLUSH IN CEILING.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED ON CONDUIT STANCHION FLOOR PENETRATION, +12" UON.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, MOUNTED IN FLOOR MONUMENT.
COMBINATION POWER/TELECOMMUNICATION DEVICE, MOUNTED IN FLUSH FLOOR BOX. TYPE AS NOTED ON PLANS OR IN SPECIFICATIONS.
DUPLEX CONVENIENCE RECEPTACLE DEVICE, CORD OR REEL HUNG FROM STRUCTURE ABOVE. TYPE AS NOTED ON PLANS.
ELECTRIFIED FURNITURE PARTITION POWER FEED, WALL MOUNTED, +18" UON. CONSISTS OF 4 11/16" SQ. X 2 1/8" DEEP JUNCTION BOX, SINGLE GANG RING, AND STAINLESS STEEL COVER PLATE WITH KO TO ACCEPT FURNITURE WHIP.
ELECTRIFIED FURNITURE PARTITION COMBINATION POWER/TELECOMMUNICATION FEEDS, MOUNTED IN FLUSH FLOOR BOX WITH KO'S IN COVER TO ACCEPT FURNITURE WHIPS
ELECTRIFIED FURNITURE PARTITION POWER FEED, MOUNTED IN FIRE-RATED POKE-THRU FLOOR FITTING WITH KO IN COVER TO ACCEPT FURNITURE WHIP.
POWER/TELECOMMUNICATION POLE, MOUNTED TO EXTEND FROM FLOOR TO CEILING. TYPE AS NOTED ON PLANS.
SINGLE-POLE, SINGLE-THROW SWITCH, WALL MOUNTED, +42" UON.
THREE-WAY SWITCH, WALL MOUNTED, +42" UON.
FOUR-WAY SWITCH, WALL MOUNTED, +42" UON.
KEY-OPERATED, SINGLE-POLE, SINGLE-THROW SWITCH, WALL MOUNTED, +42" UON.
PILOT LIGHT, SINGLE-POLE, SINGLE-THROW SWITCH, WALL MOUNTED, +42" UON.
MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD ELEMENT, MOUNTED ADJACENT TO MOTOR.
MANUAL MOTOR STARTER/DISCONNECT SWITCH, MOUNTED ADJACENT TO MOTOR.
SWITCH FURNISHED UNDER ANOTHER DIVISION, BUT INSTALLED AND WIRED UNDER THIS DIVISION, WALL MOUNTED, +42" UON.
WALLBOX DIMMER SWITCH, +42" UON. SIZED PER CONNECTED LOAD ON PLANS AND FURNISHED FOR LAMP SOURCE SERVED. PROVIDED FOR DERATING WHEN INSTALLED GANGED LOCATIONS.
SINGLE-POLE, TIMER CONTROLLED SWITCH, WALL MOUNTED, +42" UON.
SINGLE-POLE, SINGLE-THROW, EXPLOSION PROOF SWITCH, WALL MOUNTED, +42" UON.
LINE VOLTAGE SINGLE RELAY VACANCY SENSOR, WALL MOUNTED, +42" UON.
SINGLE-POLE SWITCH WITH WEATHERPROOF COVER, WALL MOUNTED, +42" UON.
LINE-VOLTAGE MULTIPLE GANG SWITCHING STATION, WALL MOUNTED, 42" UON. REFER TO PLANS FOR DEVICE QUANTITIES AND TYPES.
LOW-VOLTAGE LIGHTING CONTROL SWITCHING STATION, WALL MOUNTED, +42" UON. REFER TO PLANS AND SCHEDULES FOR DEVICE QUANTITIES AND RELAYS CONTROLLED
LIGHTING CONTROL OCCUPANCY SENSOR WITH DUAL LEVEL SWITCHING, WALL MOUNTED, +42" UON.
LIGHTING CONTROL OCCUPANCY SENSOR WITH SINGLE LEVEL SWITCHING, WALL MOUNTED, +42" UON.
LIGHTING CONTROL OCCUPANCY SENSOR, CEILING MOUNTED FOR AREA COVERAGE.
PRESET SCENE CONTROL LIGHTING STATION WITH DIMMING CAPABILITIES, WALL MOUNTED, +42" UON. REFER TO PLANS AND SCHEDULES FOR CONTROL.
EGRESS LIGHTING TRANSFER DEVICE
CONTROL STATION, WALL MOUNTED, +42" UON.
PHOTOELECTRIC CELL
DAYLIGHT SENSOR
SMOKE ALARM FOR RESIDENTIAL DWELLING UNITS, CEILING MOUNTED.
SMOKE ALARM FOR RESIDENTIAL DWELLING UNITS, WALL MOUNTED, +6" BELOW CEILING.
COMBINATION SMOKE AND CARBON MONOXIDE ALARM FOR RESIDENTIAL DWELLING UNITS, CEILING MOUNTED.
COMBINATION SMOKE AND CARBON MONOXIDE ALARM FOR RESIDENTIAL DWELLING UNITS, WALL MOUNTED, +6" BELOW CEILING.
REMOTE 2-WAY COMMUNICATION STATION, MOUNTED +42" AFF.
J
J
J
J
J
G
P
P T
P
S
S
S
S
S
S
S
S
S
S
S
S
3
4
K
P
T
M
F
D
TC
EP
L
M
M1
M
D
ETD
PC
DS
WP
U
S
SEP
V
S
S
S/C
S/C
RACEWAYSCONDUIT RUN EXPOSED ON WALL OR CEILING.
CONDUIT RUN CONCEALED IN SLAB, UNDER SLAB OR UNDERGROUND.
CONDUIT RUN CONCEALED IN WALL OR ABOVE CEILING.
CONDUIT HOMERUN, CONTINUOUS RUN TO PANEL OR EQUIPMENT CABINET.
CONDUIT
FLEXIBLE METALLIC CONDUIT.
CONDUIT TURNED UP
CONDUIT TURNED DOWN.
CONDUIT CAPPED OR STUBBED WITH INSULATED BUSHINGS.
CONDUIT SLEEVE, WITH INSULATING BUSHINGS.
CROSSMARKS ON BRANCH CIRCUIT CONDUIT RUNS INDICATE THE QUANTITY OF CONDUCTORS AS FOLLOWS (GROUND CONDUCTORS ARE NOT NOTED, BUT SHOULD BE INCLUDED IN EVERY CONDUIT WITH POWER CONDUCTORS):
1. NO CROSSMARKS INDICATES TWO #12 AWG CONDUCTORS, UON.2. THREE TO SIX CROSSMARKS INDICATES THE QUANTITY OF #12 AWG CONDUCTORS, UON.3. SEVEN OR MORE CROSSMARKS INDICATES THE QUANTITY OF #10 AWG CONDUCTORS, UON.
SYMBOLS LIST
NUMBERED NOTE, APPLIES TO ALL DRAWINGS.
NUMBERED SHEET NOTE, APPLIES TO DRAWING CONTAINING NOTES ONLY.
OVERCURRENT PROTECTIVE DEVICE SPACE IDENTIFICATION TAG. REFERS TO LOCATION OF PROTECTIVE OR CONTROL DEVICE WITHIN SWITCHBOARDS, DISTRIBUTION BOARDS, MOTOR CONTROL CENTERS, ETC.
EQUIPMENT IDENTIFICATION TAG: ITEM FURNISHED AND INSTALLED UNDER ANOTHER SECTION AND WIRED UNDER THIS SECTION.
CABLE AND/OR RACEWAY TAG, FUNCTION AS NOTED BELOW:
P = POWER T = TELEPHONE C = COMMUNICATION
FEEDER SIZE. REFER TO FEEDER SCHEDULE.
DETAIL REFERENCE:
SHEET NUMBERDETAIL DESIGNATION
FIXTURE IDENTIFICATION TAG:
FIXTURE TYPEQUANTITY
1
1
1
NAME
2004
E-801
A
2-F3
P2
CONVENTIONS A AMPERES
AFI ARC FAULT CIRCUIT INTERRUPTER
AF AMPERE OVERCURRENT FRAME SIZE (WHEN APPLIED TO CIRCUIT BREAKERS) OR AMPERE FUSE SIZE (WHEN APPLIED TO FUSES)
AFF ABOVE FINISHED FLOOR
AIC ASYMMETRIC INTERRUPTING CURRENT
AL ALUMINUM
AT AMPERE OVERCURRENT TRIP (WHEN APPLIED TO CIRCUIT BREAKERS)
ATS AUTOMATIC TRANSFER SWITCH
BAS BUILDING AUTOMATION SYSTEM
BPS BOLTED PRESSURE CONTACT SWITCH
C CONDUIT
CCTV CLOSED CIRCUIT TELEVISION
CEC CALIFORNIA ELECTRICAL CODE
CL CURRENT LIMITING CIRCUIT BREAKER OR FUSE
CP CIRCULATION PUMP
CT CURRENT TRANSFORMER
CU COPPER
DF DRINKING FOUNTAIN
DW DISH WASHER
(E) EXISTING TO REMAIN
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EP EXPLOSION PROOF
EPO EMERGENCY POWER OFF
EMCS ENERGY MANAGEMENT CONTROLS SYSTEM
EMT ELECTRICAL METALLIC TUBING
ETD EMERGENCY TRANSFER DEVICE
EWH ELECTRIC WATER HEATER
F FUSED
(F) FUTURE
FACP FIRE ALARM CONTROL PANEL
FFCP FIREMAN'S FAN CONTROL PANEL
FLA FULL LOAD AMPERES
FMC FLEXIBLE METAL CONDUIT
FSD FIRE/SMOKE DAMPER
FRAP FIREMAN'S REMOTE ANNUNCIATOR PANEL
G GROUND
GB GROUND BUS
GD GARBAGE DISPOSAL
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRAP GENERATOR REMOTE ANNUNCIATOR PANEL
HNC HOME NETWORK CABINET
HPC HIGH PRESSURE CONTACT SWITCH
IMC INTERMEDIATE METAL CONDUIT
IWH INSTANTANEOUS OR POINT OF USE WATER HEATER
LCP LIGHTING CONTROL PANEL
MBGB MAIN BUILDING GROUND BUS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MLO MAIN LUGS ONLY
MT EMPTY
MTC EMPTY CONDUIT
MTS MANUAL TRANSFER SWITCH
MW MIRCOWAVE
(N) NEW
NC NORMALLY CLOSED
NF NON-FUSED
NIEC NOT IN ELECTRICAL CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
PDZ PRIMARY DAYLIGHT ZONE
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
RF REFRIGERATOR
(R) EXISTING TO BE REMOVED
(RR) REMOVE AND RELOCATE
RGB REFERENCE GROUND BUS
RSC RIGID STEEL CONDUIT
SAD SEE ARCHITECTURAL DRAWINGS
TC TIME CLOCK
TP TWISTED-PAIR
SDZ SECONDARY DAYLIGHT ZONE
SPD SURGE PROTECTION DEVICE
TX TRANSFORMER
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UR UNDERCOUNTER REFRIGERATOR
V VOLTS
VA VOLTS-AMPS
VFD VARIABLE FREQUENCY DRIVE
VM VENDING MACHINE
WAP WIRELESS ACCESS POINT
WP WEATHERPROOF
2SP TWO SPEED
1Ø 1 PHASE
3Ø 3 PHASE
1P 1 POLE
2P 2 POLE
3P 3 POLE
3W 3 WIRE
4W 4 WIRE
ABBREVIATIONSSOME OF THE SYMBOLS SHOWN MAY NOT BE USED ON THIS PROJECT
POWER DISTRIBUTIONSWITCHBOARD, DISTRIBUTION BOARD, SUBSTATION OR MOTOR CONTROL CENTER, FLOOR MOUNTED.
PANELBOARD, 277/480V, SURFACE MOUNTED ON WALL.
PANELBOARD, 277/480V, FLUSH MOUNTED IN WALL.
PANELBOARD, 120/208V, SURFACE MOUNTED ON WALL.
PANELBOARD, 120/208V, FLUSH MOUNTED IN WALL.
DRY-TYPE STEP-DOWN TRANSFORMER, FLOOR MOUNTED 3θ,480-120/208V, UON.
ELECTRIC MOTOR, NIEC. MAKE POWER CONNECTIONS ONLY AS NOTED ON PLANS.
INDOOR EXHAUST FAN MOTOR, SINGLE PHASE. MAKE POWER CONNECTIONS TO INCLUDE JUNCTION BOX MOUNTED MANUAL MOTOR STARTER AND DISCONNECT ADJACENT TO FAN WITH 2 #12 CONDUCTORS PLUS GROUND IN 1/2" FLEXIBLE CONDUIT BETWEEN STARTER AND MOTOR.
INDOOR FAN POWERED VAV BOX MOTOR, SINGLE PHASE, MOUNTED FROM STRUCTURE ABOVE, NIEC. MAKE POWER CONNECTIONS TO INCLUDE JUNCTION BOX MOUNTEDMANUAL MOTOR STARTER AND DISCONNECT ADJACENT TO VAV BOX WITH 2 #12CONDUCTORS PLUS GROUND IN 1/2" FLEXIBLE CONDUIT BETWEEN STARTER AND MOTOR.
PULLBOX OR HANDHOLE, SIZE AND TYPE AS NOTED ON PLANS.
SAFETY DISCONNECT SWITCH, 3 POLE, UON. ADJACENT NUMBER INDICATES FUSE SIZE WHEN APPLICABLE. LABELING CONVENTION AS FOLLOWS:A: 30A, NON-FUSED AF: 30A, FUSEDB: 60A, NON-FUSED BF: 60A, FUSEDC: 100A, NON-FUSED CF: 100A, FUSEDD: 200A, NON-FUSED DF: 200A, FUSEDE: 400A, NON-FUSED EF: 400A, FUSEDF: 600A, NON-FUSED FF: 600A, FUSEDG: 800A, NON-FUSED GF: 800A, FUSED
MAGNETIC MOTOR STARTER. ADJACENT NUMBER INDICATES NEMA SIZE OF STARTER.
COMBINATION MAGNETIC MOTOR STARTER/SAFETY DISCONNECT SWITCH. ADJACENT NUMBER INDICATES NEMA SIZE OF STARTER.
PACKAGE MOTOR CONTROLLER OR STARTER FURNISHED AND INSTALLED UNDERANOTHER DIVISION WITH EQUIPMENT CONTROLLED. PROVIDE SINGLE-POINT POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS.
VARIABLE FREQUENCY DRIVE FURNISHED AND INSTALLED UNDER ANOTHER DIVISION. PROVIDE POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS.
VARIABLE FREQUENCY DRIVE WITH INTEGRAL DISCONNECT FURNISHED AND INSTALLED UNDER ANOTHER DIVISION. PROVIDE POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS.
ELECTRONICALLY COMMUTATED MOTOR CONTROLLER FURNISHED AND INSTALLED UNDER ANOTHER DIVISION. PROVIDE POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS.
ELECTRONICALLY COMMUTATED MOTOR CONTROLLER WITH INTEGRAL CIRCUIT BREAKER FURNISHED AND INSTALLED UNDER ANOTHER DIVISION. PROVIDE POWER SERVICE CONNECTION UNDER THIS DIVISION AS NOTED ON PLANS.
DRIVEN GROUND ROD.
DRIVENG ROUND ROD IN GROUND WELL WITH COVER.
ELECTRICAL VEHICLE CHARGING STATION, WALL MOUNTED.
ELECTRICAL VEHICLE CHARGING STATION, PEDESTAL MOUNTED.
INDICATES TERMINATION POINT FOR POWER CABLE & BUS.
BOLTED PRESSURE OR HIGH PRESSURE CONTACT SWITCH OR FUSED SWITCH.
MEDIUM-VOLTAGE LOAD INTERRUPTER SWITCH.
GROUP MOUNTED MOLDED CASE CIRCUIT BREAKER.
INDIVIDUALLY FIXED MOUNTED INSULATED-CASE OR POWER CIRCUIT BREAKER.
INDIVIDUALLY DRAW-OUT MOUNTED INSULATED-CASE OR POWER CIRCUIT BREAKER.
MEDIUM-VOLTAGE, INDIVIDUALLY DRAW-OUT MOUNTED VACUUM CIRCUIT BREAKER.
INDICATES INTEGRAL GROUND FAULT RELAY WHEN ASSOCIATED WITH CIRCUIT BREAKER.
INDICATES COMMUNICATION NETWORK WIRING WHEN ASSOCIATED WITH CIRCUIT BREAKER.
INDICATES ELECTRICALLY OPERATED WHEN ASSOCIATED WITH CIRCUIT BREAKER.
INDICATES SHUNT TRIP WHEN ASSOCIATED WITH OVERCURRENT PROTECTION DEVICES.
INDICATES KIRK-KEY INTERLOCK WHEN ASSOCIATED WITH OVERCURRENT PROTECTION DEVICES. ADJACENT NUMBER CORRESPONDS WITH DEVICE INTERLOCK.
GROUND FAULT RELAY WITH SHUNT TRIP.
GROUND FAULT ALARM, NO SHUNT TRIP.
UTILITY METER.
PRIVATE METER.
TRANSFORMER.
CONNECTION TO GROUND.
CURRENT TRANSFORMERS.
POTENTIAL TRANSFORMERS.
AUTOMATIC OR MANUAL TRANSFER SWITCH.
AUTOMATIC TRANSFER/BY-PASS ISOLATION SWITCH.
EMERGENCY GENERATOR.
BATTERIES.
NEUTRAL SERVICE DISCONNECT LINK.
SURGE PROTECTION DEVICE, 'SPD'.
CONTROL CONTACTOR.
NORMALLY OPEN CONTACT.
NORMALLY CLOSED CONTACT.
DIGITAL METERING UNIT.
GROUND BUS.
WATT HOUR METER.
NEUTRAL BUS.
F
V
P
AFA
1
1
VFD
VFD
WHM
NEU
DMU
GND
C
SPD
G
M
GFA
GFR
1K
ST
EO
C
52
G
M
ECM
ECM
Sheet Index
SHEET NO. SHEET NAME SC
HE
MA
TIC
DE
SIG
N
DE
SIG
N D
EV
EL
OP
ME
NT
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
SU
BM
ITT
AL 0
4
E001 SYMBOLS, ABBREVIATIONS AND SHEET INDEX
E002 SCHEDULES & PROJECT NOTES
E100 ELECTRICAL SITE PLAN
E200 POWER ONE-LINE
E300 ROOM/AREA DETAILS
R
S
REGIS
TERED
PROFESS I ONAL
ENGINEE
ATATE OF CAL I FORN IELECTRICAL
CONSULTING ENGINEERS
REVISIONS
DESIGNER:
SCALE:
DATE:
TITLE:
DRAWING NO.
1125 HIGH STREETAUBURN, CA 95603(530) 886-8556
#E015491Exp. 06/30/21
SCOTT WHEELER
Designer
06-15-2020
SYMBOLS,ABBREVIATIONS
AND SHEET INDEX
E001
NE
VA
DA
UN
ION
HIG
H S
CH
OO
LC
AM
PU
S P
OW
ER
ON
E L
INE
AN
D S
ITE
DIS
TR
IBU
TIO
N P
HA
SE
-2
FEEDER SCHEDULEFEEDER SCHEDULE GENERAL NOTES
1. COPPER FEEDER SIZES SHOWN IN THIS SCHEDULE ARE BASED ON CONDUCTORS WITH THHN/THWN-2 INSULATION IN EMT CONDUIT.
2. ALUMINUM FEEDER SIZES SHOWN IN THIS SCHEDULE ARE BASED ON CONDUCTORS WITH XHHW-2 INSULATION IN EMT CONDUIT.
3. FEEDER SIZES SHOWN IN THIS SCHEDULE ARE BASED ON AN AMBIENT TEMPERATURE OF 30 DEGREES C (86 DEGREES F).
4. FEEDERS CONSISTING OF MULTIPLE SETS OF CONDUCTORS AND CONDUITS ARE TO BE PROVIDED WITH THE INDICATED SIZE GROUND CONDUCTOR
IN EACH CONDUIT.
5. PER CEC ARTICLE 110.14, ALL FEEDERS SIZED AT #2 AWG OR LESS ARE CALCULATED PER 60 DEGREE TABLE. FEEDERS GREATER THAN #2 AWG
ARE RATED 75 DEGREE.
FEEDER SCHEDULE REMARKS
A. OVERSIZED 150% NEUTRAL, SUITABLE FOR SERVICE FROM K-13 RATED TRANSFORMERS.
B. FEEDER APPROVED FOR USE WITH SEPARATELY DERIVED SYSTEM; GROUNDING AS REQUIRED BY CEC ARTICLES 240 AND 250.
C. FEEDER GROUND AND BONDING JUMPER SHALL HAVE AN AREA NOT LESS THAN 12.5% OF THE AREA OF THE LARGEST PHASE CONDUCTOR.
D. INCREASE CONDUIT TO THE NEXT LARGER TRADE SIZE WHEN USING SCHEDULE 40 OR 80 PVC CONDUIT.
E. PER CEC SECTION 240.4(B), THE NEXT HIGHER STANDARD OVERCURRENT DEVICE RATING (ABOVE THE AMPACITY OF THE CONDUCTORS) CAN BE USED.
RULE CAN NOT BE APPLIED IF 100% RATED BREAKERS ARE USED.
F. PER CEC 240.21(C), THE PROVISIONS OF 240.4(B) SHALL NOT BE PERMITTED FOR TRANSFORMER SECONDARY CONDUCTORS.
FEEDERTAG
FEEDERDESCRIPTION
CONDUITCONDUCTORS
SEPARATELY DERIVEDSYSTEM
REMARKS
PHASE/NEUTRAL GROUNDGROUNDINGELECTRODE
BONDINGJUMPER
153 15 AMP, 3 PHASE, 3 WIRE 1-0.75" 3 #12 CU 1 #12 CU - - -
203 20 AMP, 3 PHASE, 3 WIRE 1-0.75" 3 #12 CU 1 #12 CU - - -
204 20 AMP, 3 PHASE, 4 WIRE 1-0.75" 4 #12 CU 1 #12 CU - -
403 40 AMP, 3 PHASE, 3 WIRE 1-0.75" 3 #8 CU 1 #10 CU - - -
504 50 AMP, 3 PHASE, 4 WIRE 1-1.00" 4 #6 CU 1 #8 CU #8 CU IN 0.75" C. #8 CU B
703 70 AMP, 3 PHASE, 3 WIRE 1-1.00" 3 #4 CU 1 #8 CU - - D
704 70 AMP, 3 PHASE, 4 WIRE 1-1.25" 4 #4 CU 1 #10 CU - - -
904 90 AMP, 3 PHASE, 4 WIRE 1-1.25" 4 #3 CU 1 #8 CU - - -
1004 100 AMP, 3 PHASE, 4 WIRE 1-1.50" 4 #2 CU 1 #8 CU - - E
1254 125 AMP, 3 PHASE, 4 WIRE 1-1.50" 4 #1 CU 1 #6 CU - - -
1503 150 AMP, 3 PHASE, 3 WIRE 1-1.50" 3 #1/0 CU 1 #6 CU - - -
1504 150 AMP, 3 PHASE, 4 WIRE 1-2.00" 4 #1/0 CU 1 #6 CU - - D
1754 175 AMP, 3 PHASE, 4 WIRE 1-2.00" 4 #2/0 CU 1 #6 CU - - -
2004 200 AMP, 3 PHASE, 4 WIRE 1-2.00" 4 #3/0 CU 1 #6 CU - - -
2254 225 AMP, 3 PHASE, 4 WIRE 1-2.50" 4 #4/0 CU 1 #4 CU - - -
2504 250 AMP, 3 PHASE, 4 WIRE 1-2.50" 4 #250 KCMIL CU 1 #4 CU - - D
3004 300 AMP, 3 PHASE, 4 WIRE 1-3.00" 4 #350 KCMIL CU 1 #4 CU - - D
4003 400 AMP, 3 PHASE, 3 WIRE 1-3.00" 3 #500 KCMIL CU 1 #2 CU - - D
4004 400 AMP, 3 PHASE, 4 WIRE 1-4.00" 4 #500 KCMIL CU 1 #2 CU - - D
4503 450 AMP, 3 PHASE, 3 WIRE 2-2.50" 2 SETS OF 3 #4/0 CU 1 #2 CU/SET - - -
6004 600 AMP, 3 PHASE, 4 WIRE 2-3.00" 2 SETS OF 4 #350 KCMIL CU 1 #1 CU/SET - - D
8004 800 AMP, 3 PHASE, 4 WIRE 2-3.50" 2 SETS OF 4 #600 KCMIL CU 1 #1/0 CU/SET - - D
T4004 400 AMP, 3 PHASE, 4 WIRE 2-2.00" 2 SETS OF 4 #4/0 CU 1 #1/0 CU/SET #1/0 CU IN 0.75" C. #1/0 CU B,F
T10004 1032 AMP, 3 PHASE, 4 WIRE 3-3.00"3 SETS OF 3 #500 KCMIL CU, 2#300 KCMIL CU NEU./SET
#3/0 CU/SET #3/0 CU IN 1.00" C. #3/0 CU A,B,C,D,F
# DESCRIPTION DATE
PROJECT GENERAL NOTES*EXISTING CONDITIONS
1. THE EXISTING CONDITIONS INDICATED IN THIS DRAWING SET WERE DEVELOPED FROM VARIOUS SOURCESWHICH WERE NOT ALL FIELD VERIFIED AND NOT ALL CONDITIONS ARE SHOWN. LOCATIONS, ROUTING,ELEVATIONS, SIZES, ETC. ARE SHOWN SCHEMATICALLY. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS
PRIOR TO CONSTRUCTION.
2. DRAWINGS INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK. FOLLOW DRAWINGS IN LAYING OUT
WORK AND CHECK DRAWINGS OF OTHER TRADES TO VERIFY SPACE CONDITIONS. FINAL LOCATIONS SHALLBE ADJUSTED TO MEET FIELD CONDITIONS.
*DEMO & GENERAL CONDITIONS3. CONTRACTOR SHALL REMOVE ALL LEFT OVER CONDUIT, WIRE, SCRAPS, ETC. AND LEAVE PREMISES CLEAN
AND FREE OF TRASH OR DEBRIS RESULTING FROM THEIR WORK.
4. CONTRACTOR SHALL DISCONNECT AND REMOVE ALL DEMOLISHED DEVICES AND FIXTURES AS SHOWN ON
DEMOLITION PLAN. TURN OVER TO OWNER EXISTING DEVICES AND FIXTURES THAT ARE NOT REUSED.PROPERLY DISCARD IF THE OWNER DOES NOT WANT.
5.
6.
*SITE
7.
THERE SHALL BE A MINIMUM OF 18" OF COVER OVER UNDERGROUND CONDUITS, UON. INCLUDE A MINIMUM12" SEPARATION BETWEEN ALL LOW VOLTAGE AND LINE VOLTAGE RACEWAYS. INSTALL A WARNING/MARKER
TAPE 12 INCHES OVER THE CONDUIT.
8.
9.
CONTRACTOR SHALL SIZE ALL EXTERIOR JUNCTION/PULLBOXES PER THE MINIMUM CODE REQUIREMENTS
OF CEC ARTICLE 314, WHEN NOT INDICATED ON THE PLANS.
*EQUIPMENT, CONDUIT, WIRE, BOXES & DEVICES
PROVIDE INDIVIDUAL GFCI RECEPTACLES AT EACH LOCATION SHOWN, DO NOT USE FEED-THRU GFCI TYPE
RECEPTACLES. LOCATE RECEPTACLE AT END OF A BRANCH CIRCUIT WIRE.
14.
WHERE RECEPTACLES ARE LOCATED OUTSIDE OR IN WET/DAMP LOCATIONS PROVIDE WEATHER RESISTANT
TYPE, UON.
15.
CONDUIT SIZE SHALL BE 0.75 MINIMUM, U.O.N.
16.
ALL CONDUCTORS ON THIS PROJECT SHALL BE COPPER.
17.
18.
INSTALL AND CONNECT A CODE SIZED INSULATED OR BARE COPPER GROUNDING CONDUCTOR IN ALL BRANCHCIRCUITS AND FEEDERS.
19.
ALL DEVICES SHALL HAVE TYPE ON TAPE LABELS INDICATING THE PANELBOARD AND CIRCUIT SERVING EACHDEVICE, TYPICAL OF ALL DEVICES INCLUDED ON THIS PROJECT.
20.
PROVIDE INSULATING BUSHINGS OR INSULATED THROAT ON THE ENDS OF ALL EMPTY CONDUIT SLEEVES ANDINSTALL A POLYETHYLENE PULLING ROPE.
21.
WHERE CIRCUITS ARE SHOWN ON THE DRAWINGS WITH HOMERUNS THAT SHARE NEUTRAL CONDUCTORS THECONTRACTOR SHALL PROVIDE HANDLE TIES BETWEEN ALL BRANCH CIRCUIT BREAKER LOADS WHICH SHARE A
NEUTRAL.
22.
ALL OUTDOOR ELECTRICAL EQUIPMENT SHALL BE WEATHER-PROTECTED AND LISTED FOR EXTERIOR USE.
23.
PROVIDE TYPE WRITTEN PANEL SCHEDULES UPDATED TO INCLUDE ALL FIELD MODIFICATIONS AND SCOPEITEMS ASSOCIATED WITH THIS PROJECT.
24.
PROVIDE ENGRAVED NAMEPLATES FOR ELECTRICAL BOARDS, DISCONNECTS, AND SWITCHGEAR.
*CODE REQUIREMENTS & ELEC. CLEARANCES
25.
ALL ELECTRICAL WORK SHALL COMPLY WITH THE LATEST EDITION OF THE CALIFORNIA ELECTRICAL CODE(CEC).
26.
CONTRACTOR IS RESPONSIBLE TO SUBMIT REVISED LAYOUT OF EQUIPMENT IN ELECTRICAL SPACES FORWRITTEN APPROVAL BY ENGINEER IF PROPOSED INSTALLATION LAYOUT DIFFERS FROM CONSTRUCTIONDOCUMENTS. SUBMISSION MUST BE APPROVED PRIOR TO RELEASE OF ORDER FOR EQUIPMENT AND PRIOR
TO INSTALLATION.
27.
REQUIRED ELECTRICAL EQUIPMENT WORKING SPACE DEPTH SHALL NOT BE LESS THAN THAT INDICATED IN
CEC TABLE 110.26. THE WIDTH OF THE WORKING SPACE IN FRONT OF THE ELECTRICAL EQUIPMENT SHALL BETHE WIDTH OF THE EQUIPMENT OR 30", WHICHEVER IS GREATER. THIS REQUIREMENT ALSO APPLIES TODISCONNECT SWITCHES.
28.
ALL ELECTRICAL MATERIALS AND EQUIPMENT SHALL BE LISTED BY UNDERWRITERS LABORATORIES AND BEARTHEIR LABEL, OR ETL.
29.
WIRING SPACE IN PANELBOARDS, DISTRIBUTION PANES AND SWITCHBOARDS SHALL BE DEDICATED TOCONDUCTORS TERMINATED IN THAT ENCLOSURE. PANELBOARDS, DISTRIBUTION PANELS ANDSWITCHBOARDS SHALL NOT BE USED AS PULL AND/OR SPLICE BOXES FOR CONDUCTORS THAT TERMINATE IN
OTHER ENCLOSURES. DO NOT SPLICE CONDUCTORS IN EQUIPMENT.
30.
NEW CIRCUIT BREAKERS INSTALLED IN EXISTING EQUIPMENT SHALL BE PROVIDED TO MATCH THE kAIC
RATINGS AND THE MANUFACTURER OF THE EXISTING.
PROVIDE CLEAR SIGNAGE ON ALL ELECTRICAL EQUIPMENT PER CEC TO INDICATE THE ARC FLASH HAZARD
WARNING, AND THE MAXIMUM AVAILABLE FAULT CURRENT. WHEN MODIFICATIONS OCCUR THAT AFFECT THEMAXIMUM FAULT CURRENT THE CONTRACTOR SHALL RECALCULATE AS NECESSARY AND REMARK THEEQUIPMENT.
*COORDINATION
PROVIDE FUSES IN DISCONNECTS FOR MECHANICAL EQUIPMENT AS COORDINATED WITH THE UNITSNAMEPLATE AND MANUFACTURERS INSTALLATION INSTRUCTIONS. FUSES SHALL BE CURRENT LIMITING TYPE.
PROVIDE A GFCI TYPE DEVICE WITH WEATHER PROOF WHILE IN USE COVER WITHIN 25' OF ALL EXTERIORHVAC/PLUMBING EQUIPMENT.
WORK PERFORMED FROM THESE DRAWINGS SHALL ALSO COMPLY WITH THE PROJECT SPECIFICATIONS. INTHE EVENT THAT THERE IS A CONFLICT BETWEEN THE DRAWINGS AND SPECIFICATIONS, THE MORE
STRINGENT REQUIREMENT SHALL TAKE PRECEDENT.
*MISC.35. CONTRACTOR SHALL PREPARE RED LINED AS-BUILT DOCUMENTS REPRESENTING THE ACTUAL FIELD
ROUTINGS AND INSTALLATION LOCATIONS FOR ALL ITEMS ON THIS PROJECT.
36. SURFACE MOUNTED CONDUIT WHERE APPROVED, AND INSTALLED, SHALL BE PAINTED TO MATCH THEARCHITECTURAL FINISHES IN THAT AREA.
37. CONDUIT ROUTING (WHERE SHOWN) IS ESSENTIALLY DIAGRAMMATIC. CONTRACTOR SHALL LAYOUT RUNS TOSUIT FILED CONDITIONS AND THE COORDINATION REQUIREMENTS OF OTHER TRADES.
38. DRAWINGS INDICATE JUNCTION BOXES WITH HOMERUNS ON THE PLANS, BUT THE CONTRACTOR SHALLPROVIDE ALL INTERMEDIATE RACEWAY WORK AND CONDUCTORS/CABLING BETWEEN THE DEVICES,
FIXTURES, AND JUNCTION BOXES AS COORDINATED WITH ALL FIELD CONDITIONS AND TRADES.
10.
USE RIGID STEEL CONDUIT WRAPPED IN 10 MIL TAPE FOR ALL UNDERGROUND 90'S EXTENDING TO 6" ABOVE
THE GROUND.
11.
USE SCHEDULE 40 PVC FOR ALL UNDERGROUND CONDUITS, UON.
12.
USE RIGID STEEL CONDUIT FOR ALL EXPOSED INSTALLATIONS.
13.
NUMBERED SHEET NOTES#
3
1.
2. #4 REINFORCING BARS AT 12" MAXIMUM SPACING IN EACH DIRECTION. BARS SHALL BE AS PER ASTMA615, GRADE 40 MINIMUM.
3.
4.
5/8" DIAMETER X 8'-0" LONG COPPER GROUND ROD WITH GROUND ROD CLAMP.
SOLID BARE COPPER GROUND CONDUCTOR.
PLAN VIEW
SECTION A-A
10"
6"
12
"
8"
3"
3"
10"
FRONT
A A
4
1
2
CONCRETE PAD SHALL BE DESIGNED TO ATTAIN A STRENGTH OF 3000 PSI IN 28 DAYS. SURFACE SHALL HAVE A LIGHT BROOM OR WOOD FLOAT FINISH. ALL EXPOSED EDGES SHALL HAVE A 3/4" CHAMFER OR RADIUS. PAD DIMEMENSIONS SHALL BE DETERMINED BY EQUIPMENT DIMENSIONS AND LAYOUT ON E300. PAD SHALL EXTEND A 8" ON SIDES, FRONT AND BACK OF EQUIPMENT.
1/2" ∅ HILTI KWIK-BOLT TZ,INSTALL PER ICC ESR-1917MIN. 3.25" EMBED
EQUIPMENT ENCLOSURE
SPACING TO SUIT EQUIP. DIMENSION
BOTTOM OF PAD
2" MIN.
DISTRIBUTION BOARD: 2 PER SIDE PER CUBICLE, MAX WEIGHT 900#TRANSFORMER : 2 PER SIDE PER CUBICLE, MAX WEIGHT 1,250#
CONCRETEPAD/SLAB. REFERTO 1/E002.
R
S
REGIS
TERED
PROFESS I ONAL
ENGINEE
ATATE OF CAL I FORN IELECTRICAL
CONSULTING ENGINEERS
REVISIONS
DESIGNER:
SCALE:
DATE:
TITLE:
DRAWING NO.
1125 HIGH STREETAUBURN, CA 95603(530) 886-8556
#E015491Exp. 06/30/21
SCOTT WHEELER
Designer
06-15-2020
SCHEDULES &PROJECT NOTES
E002
NE
VA
DA
UN
ION
HIG
H S
CH
OO
LC
AM
PU
S P
OW
ER
ON
E L
INE
AN
D S
ITE
DIS
TR
IBU
TIO
N P
HA
SE
-2
SCALE:NTS1
EQUIPMENT PAD DETAIL
Notes:
Total Est. Demand: 397 A
Total Conn.: 397 A
Total Est. Demand: 330.00 kVA
Other 330 kVA 100.00% 330 kVA Total Conn. Load: 330.00 kVA
Load Classification Connected... Demand Factor Estimated... Panel Totals
Total... 397 A 397 A 397 A
Total Load: 110.00 kVA 110.00 110.00
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
--- -- -- 11 0.00 0.00 12 -- -- ---
--- -- -- 9 0.00 0.00 10 -- -- ---
space -- -- 7 0.00 0.00 8 -- -- space
-- -- -- 5 66.67 43.33 6 -- -- --
-- -- -- 3 66.67 43.33 4 -- -- --
TX-C 450 A 3 1 66.67 43.33 2 3 175 A (F) CHILLER
LOAD SERVED Amp P... # A (kVA) B (kVA) C (kVA) # P... Amp LOAD SERVED
Mounting: PAD Volts: 480V Wires 3 Main Type: MCB Main Rating: 500 A
Location: Southwest Pad Serv... MSB-2 Phases 3 A.I.C. Rating: 42KAIC Bus Rating 600 A
DISTRIBUTION BOARD: HDA
SCALE:NTS2
EQUIPMENT ATTACHMENT AT PAD
# DESCRIPTION DATE
(E)
P P
P
P
P
P
P
P
P
P
P
PP
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
PP
P
P
P
P
P
P
P
P
(E)3-2" MTC
(E)2-2" MTC
(E)2-2" MTC
(E)2-2" MTC
(E)1-2" MTC
(E)2-2" MTC
(E)3-4" MTC
(E)2-4" MTC
(E)2-4" MTC
2-2" COM
2710
BLDG. 'A'
MUSIC BLDG. L
BUS LOADING ZONE
MA
TH
/ A
RT
S B
LD
G. 'J
'
BLDG. 'G' -
BOYS GYM
CLASSROOM BLDG. 'D'
CLASSROOM BLDG. 'E'
CLASSROOM BLDG. 'C'
SCIENCE /
LIBRARY
"S"
BLDG. 'B'
THEATER
BLDG. 'K'
INDUSTRIAL
ARTS
AGRICULTURE. 'F'
DANCE
POOL
WRESTLING
SHOP BLDG.
MAINT.
SH
OW
ER
S
STADIUM
BLDG. 'A'
BLDG. I -
LANGUAGE
BLDG. 'B'
THEATER
BLDG. 'K'
8 .5'
1 7'
1 2.5'
1 2'
1 2'
1 2'
1 2'
1 2.5'
1 2.5'
1 2.5'
1 2'
1 2'
1 2'
1 2'
1 2.5'
1 2.5'
1 8'
9 '
8 '
3
A
A
A
A
AF
AF
AF
AFAF
AF
AF
T
T
A
T
F
18'-4"
13'-4"
5'-0"
13'-4"
16'-8"
16'-8"
16'-8"
16'-8"
16'-8"
16'-8"
8'-4"
16'-8"
16'-8"
16'-8"
CUT AN
D FLAT TE
N (E) SL
AB
NEW FL
OOR DR
AIN
NEW FL
OOR DR
AIN
BENCH
WD
ICE
2
6
N
G1
G2
G3
G4
G5
G6
G7
G8
G9
G10
G11
G12
G13
G16
G18A
G19
G18
G15
G17
G21
G203
G22
G26
G25
G23G24
G27
G15A
LOCKER
ROOM
CORRIDO
R
VESTIBU
LE
COACH-
1
COACH-
2
LOCKER
S
SHOWER
S
COACH-
3
EQUIPME
NT
DRYING
ROOM
SHOWER
EQUIP.
LAUNDR
Y
TOILET
WEIGHT
ROOM
BOILER
ROOM
WEIGHT
ROOM
CORRIDO
R
VESTIBU
LE
SNACK
BAR
STOR.
LOBBY
STORAG
E
GIRLS
TOILET
JANITORBOY
S
TOILET
GYMNAS
IUM
JAN.
J
S
J
S
J
S
(E) MSB-E
(E) MSB-4
(E) PANEL-E
(E) 5TX-U
(E) MSB-1
(E) #T1122
(E) LDA
(E) 5TX-C
(E) MSB-3
(E) #T1192
MSB-2#T0005
(E) DIST BOARD
PANEL-EK HOUSE DIMMER D1 PANEL-K3
PANEL-K1
PANEL-K2
PANEL-L2
PANEL-L1
PANEL-F1
PANEL-F2
PANEL-F3
PANEL-H1
PANEL-H2
PANEL-H3
PANEL-H4
EXIT LTG SWX PANEL
PANEL-G2
PANEL-D6
PANEL-D4
PANEL-D5
PANEL-D2
PANEL-D3
PANEL-D1
EMERGENCY CONTROL PANEL
PANEL-EMI
EMERGECNY DIST. PANEL
PANEL-B3
PANEL-B2
PANEL-B1
DIST. PANEL-A5
PANEL-A3
PANEL-A2
PANEL-C3
PANEL-C2
PANEL-C1
PANEL-E1PANEL-E6
PANEL-E7PANEL-E3
PANEL-E4
PANEL-E8
PANEL-E5
PANEL-E2
PANEL-E9
PANEL-J1PANEL-J2
DIST. PANEL
PANEL-J3PANEL-J4
P
E3001
E3002
E3003
P(E)
2
4
3
HDATX-C
2
(E) VAULT
Work to be completed under phase 1
Work to be completed under phase 2
R
S
REGIS
TERED
PROFESS I ONAL
ENGINEE
ATATE OF CAL I FORN IELECTRICAL
CONSULTING ENGINEERS
REVISIONS
DESIGNER:
SCALE:
DATE:
TITLE:
DRAWING NO.
1125 HIGH STREETAUBURN, CA 95603(530) 886-8556
#E015491Exp. 06/30/21
SCOTT WHEELER
Designer
06-15-2020
ELECTRICAL SITEPLAN
E100
NE
VA
DA
UN
ION
HIG
H S
CH
OO
LC
AM
PU
S P
OW
ER
ON
E L
INE
AN
D S
ITE
DIS
TR
IBU
TIO
N P
HA
SE
-2
SCALE: 1" = 60'-0"1
OVERALL SITE PLAN
LOCATE AND INTERCEPT EXISTING FEEDER WITH A 4’ X 6’ PULLBOX. EXTEND FEEDER ASSHOWN. REFER TO POWER ONE LINE DIAGRAM (E200) FOR ADDITIONAL INFORMATION.
1
EXTEND CONDUIT FROM EXISTING PULLBOX TO ELECTRICAL EQUIPMENT AND PROVIDE NEWWIRE. REFER TO POWER ONE LINE DIAGRAM (E200) FOR ADDITIONAL INFORMATION.
2
PROVIDE NEW UNDERGROUND FEEDER. REFER TO POWER ONE LINE DIAGRAM (E200) FORADDITIONAL INFORMATION. SAWCUT EXISTING CONRETE AND PATCH TO MATCH EXISTING.
3
PROVIDE NEW WIRE IN EXISTING CONDUIT. REFER TO POWER ONE LINE DIAGRAM (E200) FORADDITIONAL INFORMATION.
4
NUMBERED SHEET NOTES
1" = 60'-0"
1
ALL CONCRETE PULL BOXES SHALL BE PROVIDED WITH TRAFFIC RATED LID AND TAMPERPROOF HARDWARE.
1.
GENERAL SHEET NOTES
# DESCRIPTION DATE
XXX
APANEL
BPANEL
CPANEL
DPANEL
EPANEL
FPANEL
BOARD
LEDMESS
M
PG&E XFMR75kVA
#T-1351
904 1004 904 904 904 904
1,2,3BLDG
4,5,6BLDG
(?)PARF
9,10,11BLDG
13,14,15BLDG
M
XXX
??
PG&E XFMR75kVA
#T-1192
1004 1254 2254 2254 4004
E-2PANEL
E-3PANEL
E-4PANEL
E-5PANEL
E-1PANEL
M
#T-6717-7381PG&E XFMR, POLE MOUNTED
50kVA x 3
E-3PANEL
E-5PANEL
E-1PANEL
J1PANEL
J2PANEL
J3PANEL
J4PANEL
J5PANEL
JMPANEL
ERTERINV-
1004 1254 2254 2254 4004
1004 1254 1004 1254 1004 1004 204
LIGHTSPARKING
BOXPRESS
BOXPRESS
PANEL
SNACKBAR
CLASS
PORT-ABLE
BOARDSCORE-
XXX
HOUSEGREEN
SOUTH
POLELIGHTS
NORTH
POLELIGHTS
GYMWRESTLING
PG&E TRANSFORMERT-5
M
203 153 153 703 403 1503 703 2004 2254
PANELE-WING
PANELMCC-2
PANELJ-WING
LIGHTS
THEATERPARKING
PANELTHEATER
#2CHILLER
#1CHILLER
M
PG&E XFMR1000kVA
#T-1122
??
PANELS-WING
NPANEL
D-4PANEL
B-2PANEL
B-3PANEL
B-1PANEL
D-2PANEL
A-1PANEL
D-3PANEL
D-1PANEL
B-2PANEL
#137
PANELLB RM
#207
PANELLD RM
#205
PANELLF RM
#122
PANELLF RM
#223
PANELLL RM
#209
PANELS2 RM
#202
PANELS1 RM
#137
PANELHA RM
#207
PANELHC RM
A-4PANEL
STAGEPANEL
D-4PANEL
D-4PANEL
C-2PANEL
C-1PANEL
A-3PANEL
C-3PANEL
A-2PANEL
H1PANEL
H2PANEL
H3PANEL
HH1PANEL
4003
8004
G3PANEL
T4004
T10004
MAINPANEL
1PANEL
2PANEL
7PANEL
8PANEL
13PANEL
14PANEL
6004 2504 2254 4004 704 204 3004 4003 4004 8004 6004 6004
2004 2004
1004 504 504 504204 204 204
2004 2004 2004 2004 2004
1004 4004 1754 1004 1004 10041504 8004 3004 1254 8004
4503
4003
90A3P
100A3P
90A3P
90A3P
90A3P
90A3P
0A1P
MSB-4Northpoint
400A,120/208V,3Φ,4W Meter # 1006727937Load: 61kW, 169A
400A3P
100A3P
125A3P
225A3P
225A3P
400A3P
0A3P
MSB-3G-Wing
1000A,120/208V,3Φ,4WMeter# 1009985101Load: 20KW, 56A
PG&E PRIMARY
400A3P
225A3P
225A3P
125A3P
100A3P
MSB-EShop
800A,120/240V,3Φ,4W
20A3P
100A3P
100A3P
125A3P
100A3P
125A3P
100A3P
400A3P
PANEL J
120/240V,3Φ,4W
400A3P
Meter# 1003716856Load: XXKW, XXA
PG&E PRIMARY
225A3P
200A3P
70A2P
150A2P
40A2P
70A2P
15A2P
15A1P
20A1P
MSB-2Stadium
1200A, 277/480V,3Φ,4W, 65KAIC Meter# 1009510316Load: 118kW, 142A
1200A3P
PG&E PRIMARY
(N)500A
3P1
(N)5
250A3P
225A3P
20A3P
300A3P
400A3P
400A3P
MSB-1Upper Parking
3000A,277/480V,3Φ,4W
800A3P
600A3P
600A3P
100A3P
400A3P
175A3P
100A3P
150A3P
100A3P
800A3P
300A3P
100A3P
125A3P
800A3P
LDAC-Wing
1600A,120/208V,3Φ,4W
400A3P
70A3P
ALI GYM
200A3P
200A3P
200A3P
600A,277/480V,3Φ,4W
DPL
200A3P
200A3P
600A3P
MUSICBUILDING
200A3P
200A3P
300A3P
600A,277/480V,3Φ,4W
DPH
600A3P
PANEL A-5
225kVA XMFR 208/480V
Meter# 1010080211Load: 622kW, 748A
2500A3P
800A3P
225A3P
225A3P
225A3P
400A3P
225A3P
225A3P
225A3P
225A3P
225A3P
225A3P
225A3P
225A3P
225A3P
225A3P
600A3P
5TX-G112.5KVA
4160V Δ - 120/208V Y
5TX-C300KVA XMFR
4160V Δ - 120/208V Y
5TX-U500KVA XMFR
4160V Δ - 277/480V Y
112.5KVA4160V Δ - 120/208V Y
AG BLDG
TESTPOWER
PG&E PRIMARY
(N) TX-G112.5 KVA
480V Δ - 120/208V Y
2
3
3
(N) TX-C300KVA
480V Δ - 120/208V Y
(N)
2
(N)
SPARE(GREEN HOUSE)
SPARE(PORTABLES)
225KVA
1000A3P
100A3P
50A3P
50A3P
20A3P
50A3P
20A3P
EMERGENCY PANEL (AG)Upper Parking
20A3P
100A,277/480V,3Φ,4W
WORK TO BE COMPLETED UNDER THE AG SHOP PROJECT
(E) VAULT
5
P
6
(N)DIST
BOARDHDA
4(N)
(N)
400A3P
7
(N)
(N)
(E) VAULT
Work to be completed under phase 1
Work to be completed under phase 2
3
3
R
S
REGIS
TERED
PROFESS I ONAL
ENGINEE
ATATE OF CAL I FORN IELECTRICAL
CONSULTING ENGINEERS
REVISIONS
DESIGNER:
SCALE:
DATE:
TITLE:
DRAWING NO.
1125 HIGH STREETAUBURN, CA 95603(530) 886-8556
#E015491Exp. 06/30/21
SCOTT WHEELER
Designer
06-15-2020
POWER ONE-LINE
E200
NE
VA
DA
UN
ION
HIG
H S
CH
OO
LC
AM
PU
S P
OW
ER
ON
E L
INE
AN
D S
ITE
DIS
TR
IBU
TIO
N P
HA
SE
-2
1POWER ONE LINE - NORTHPOINT
3POWER ONE LINE - PORTABLES/G WING
2POWER ONE LINE - SHOPS/J WING
4POWER ONE LINE - STADIUM
5POWER ONE LINE - UPPER PARKING/MAIN CAMPUS
PROVIDE NEW BREAKER IN EXISTING BOARD. BREAKER SHALL BE LISTED FOR USE IN EXISTINGEQUIPMENT, WHICH IS CUTLER-HAMMER POW-R-LINE C.
1
PROVIDE NEW TRANSFORMER AS SHOWN.2
DISCONNECT AND REMOVE EXISTING PAD MOUNTED, OIL FILLED TRANSFORMER. DISPOSE OFEQUIPMENT. DISCONNECT AND SAFE OFF WIRE. LEAVE WIRE ABANDONED IN CONDUIT.COORDINATE DEMOLITION AND REMOVAL WITH DISTRICT, OTHER CONTRACTORS, PVCONTRACTORS, ETC. THE CONTRACTOR IS RESPONSIBLE TO DISPOSE OF TRANSFORMERS INACCORDACE WITH ALL APPROPRIATE LAWS AND REGULATIONS.
3
PROVIDE THREE SETS OF 3 #750KCMIL CU AND 1 #2/0 CU GROUND IN THE EXISTING 4"CONDUITS.
4
PROVIDE THREE SETS OF 3 #750KCMIL CU AND 1 #2/0 CU GROUND IN NEW 4" CONDUITS.5
CHILLER TO BE REMOVED UNDER ANOTHER PROJECT.6
PROVIDE INTEGRAL SECONDARY CIRCUIT BREAKER TRANSFORMER.7
NUMBERED SHEET NOTES
ALL EQUIPMENT, FEEDERS, ETC. IS EXISTING UNLESS NOTED OTHERWISE.1.
GENERAL SHEET NOTES
# DESCRIPTION DATE
A
A
A
A
A
I
J
H
G
CHP-2
CH-1
CH-2
CHP-5
CHP-3
CHP-4
(E)MCC
-2(E)
PANEL 'L
CY'
7.5HP,48
0V,3∅
7.5HP,48
0V,3∅
5HP,480
V,3∅
5HP,480
V,3∅CHP-1
LCV-1
J
AF
AF
AF
AFAF
AF
AF
T
T
T
1.5 HP,
230V, 3∅
1.5 HP,
230V, 3∅
1.5 HP,
230V, 3∅
3 HP, 2
30V, 3∅
3 HP, 2
30V, 3∅
1.5 HP,
208V, 3∅
1.5 HP,
208V, 3∅
N
HWP-G3
B/G1FAN
B/G2FAN
HWP-G2
HWP-G1
HWP-J2
HWP-J1
G3A-21
G3A-15
G3A-27
G3A-39
G3A-33
G3A-3
G3A-9
(N)PANE
L G3A
G3A-2
G19
BOILER
ROOM
J
S
J
S
S
P
P
(E)
(E)
(E)
(E)
(E)
(E)
(E)
3
5
REFER TO E100 FOR CONTINUATION
(N) TX-G
5TX-G
1
6
7
(E) PNL G4
(E) PNL G3
(E) 5TX-C
TX-C
(F) CHILLER LOCATION
(E) VAULT
(E) LDA
3
3
1HDA
REFER TO E100 FOR CONTINUATION
8
2
R
S
REGIS
TERED
PROFESS I ONAL
ENGINEE
ATATE OF CAL I FORN IELECTRICAL
CONSULTING ENGINEERS
REVISIONS
DESIGNER:
SCALE:
DATE:
TITLE:
DRAWING NO.
1125 HIGH STREETAUBURN, CA 95603(530) 886-8556
#E015491Exp. 06/30/21
SCOTT WHEELER
Designer
06-15-2020
ROOM/AREADETAILS
E300
NE
VA
DA
UN
ION
HIG
H S
CH
OO
LC
AM
PU
S P
OW
ER
ON
E L
INE
AN
D S
ITE
DIS
TR
IBU
TIO
N P
HA
SE
-2
SCALE: 1/4" = 1'-0"1
North 'G' Equipment YardSCALE: 1/4" = 1'-0"
2South 'G' Boiler RM
SCALE: 1/4" = 1'-0"3
Southwest Campus Pad
REMOVE EXISTING EQUIPMENT. REFER TO E200 FOR ADDITIONAL INFORMATION.1
PROVIDE NEW CONCRETE PAD. REFER TO DETAIL 1/E002. PAD SHALL FILL IN THE AREA WITHCONCRETE TO CREATE ONE CONTIGUOUS CONCRETE MAINTENANCE PAD.
2
PROVIDE NEW UNDERGROUND FEEDER TO EXISTING DISTRIBUTION BOARD LDA. RISE UP ANDTERMINATE INTO THE BOARD AT 6" ABOVE GRADE. AS AN ALTERNATE, INTERCEPT EXISTINGFEEDER ENTERING THE GEAR, REMOVE WIRE AND PULL NEW WIRE INTO THE EQUIPMENT.
3
PROVIDE NEW UNDEGROUND FEEDER.4
PROVIDE NEW N36 PULLBOX TO INTERCEPT EXISTING FEEDER AS SHOWN ON E100.5
PROVIDE 90 UP AT WALL AND PENETRATE WALL AT +8" ABOVE GRADE. CORE WALL ANDPENETRATE WALL WITH LB'S. EXTEND FEEDER TO TRANSFORMER AS SHOWN.
6
PROVIDE A TRANSFORMER WITH AN INTEGRAL SECONDARY CIRCUIT BREAKER.7
RAISE VAULT LID TO MATCH GRADE OF FINISHED CONCRETE PAD.8
NUMBERED SHEET NOTES
# DESCRIPTION DATE
PHASE 2
PHASE 2
PHASE 1