Upload
ramki-ramakrishnan
View
230
Download
0
Embed Size (px)
Citation preview
7/29/2019 System Protection in Rurla Transmission lines
1/56
Dr Campbell BoothUniversity of Strathclyde
Review of ConventionalDistribution System Protection
EES-UETP Course title
University of ManchesterMarch 2011
7/29/2019 System Protection in Rurla Transmission lines
2/56
Distribution System Protection: Overview
Typical distribution network architectures
Protection basics and requirements (review)
Brief review of protection philosophies and
schemes: Unit/non-unit
Differential/distance/overcurrent
Reclosers/Sectionalisers/Fuses
Summary of operation and
setting of distribution protection
Practical considerations
University of Strathclyde, 2011http://www.flickr.com/photos/10223809@N02/847602455/
7/29/2019 System Protection in Rurla Transmission lines
3/56
Gers and HolmesProtection of Electricity Distribution Networks,IEE Power & Energy Series 47
Transmission& DistributionArchitecture
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
4/56
ProtectionZones
Gers and Holmes
Protection of Electricity Distribution Networks,IEE Power & Energy Series 47
7/29/2019 System Protection in Rurla Transmission lines
5/56
Electrical Arc
Pressure Waves
Copper Vapor:
Solid to VaporExpands by67,000 times
Molten Metal
Intense Light
Hot Air-Rapid Expansion
20,000 C
Shrapnel
Sound Waves
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
6/56
Faults on power systems
Faults on power systems
(Usually) characterised by large fault currents
Fault current level usually drops with distanceaway from source due to impedance oflines/transformers in the network
Large voltage depression around the point of
fault (load impedances shorted)
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
7/56
SourceLoad
(High Z)Load
(High Z)
Line(Low Z)
Line
(Low Z)
Line(Low Z)
Line(Low Z)
Typical section of power system one line diagram
Power System Protection - How?
Load(High Z)
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
8/56
SourceLoad
(High Z)Load
(High Z)
Line(Low Z)
Line(Low Z)
Line(Low Z)
Line(Low Z)
Typical section of power system one line diagram
v v v v
V V V
Power System Protection - How?
Load(High Z)
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
9/56
SourceLoad
(High Z)Load
(High Z)
Line(Low Z)
Line(Low Z)
Line(Low Z)
Line(Low Z)
Typical section of power system one line diagram
v v v v
V V V
Fault 1
Power System Protection - How?
Load(High Z)
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
10/56
SourceLoad
(High Z)Load
(High Z)Load
(High Z)
Line(Low Z)
Line(Low Z)
Line(Low Z)
Line(Low Z)
Typical section of power system one line diagram
v v v v
V V V
Fault 1
Power System Protection - How?
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
11/56
SourceLoad
(High Z)Load
(High Z)Load
(High Z)
Line(Low Z)
Line(Low Z)
Line(Low Z)
Line(Low Z)
Typical section of power system one line diagram
v v v v
V V V
Current much higher than load currentVoltage at fault = 0
Fault 1
Voltagehere?
Voltagehere?
Power System Protection - How?
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
12/56
Measurement of current (and often voltage)at many locations:
Fault current flow usually lessens in magnitude as
fault distance from source increases Voltage at a measurement point usually increases
as fault distance from measurement pointincreases
Power System Protection - How?
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
13/56
SourceLoad
(High Z)Load
(High Z)Load
(High Z)
Line(Low Z)
Line(Low Z)
Line(Low Z)
Line(Low Z)
Typical section of power system one line diagram
v v v v
V V V
Current much higher than load currentVoltage at fault = 0
Fault 1
Voltageand current measured
here?
Power System Protection - How?
P
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
14/56
Source
Line(Low Z)
Line(Low Z)
Line(Low Z)
Line(Low Z)
Typical section of power system one line diagram
v v v v
Current much higher than load current
(but not as high as fault at position 1)Voltage at fault = 0
Fault 2
Power System Protection - How?
Voltageand current measured
here?
P
V V
Much reduced
current due to
line voltage
depression
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
15/56
Factors affecting fault severity
Magnitude of fault current How much and what nature of generation is
on the system
How close generation is to fault position impedance to fault
Power system configuration
Nature of fault
Earthing arrangements (only applicable forparticular types of fault)
Duration of fault
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
16/56
Protection System Requirements (1)
The protection systems must:
rapidly and automatically disconnect the
faulty item(s) of plant or section of thepower network;
minimise the disconnection of healthy
plant, thus ensuring maximum security ofsupply to consumers.
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
17/56
Protection System Requirements (2)
The degree to which any protectionsystem satisfies the aforementioned
requirements can be described by fourinter-related parameters -
discrimination, sensitivity, operating
time and stability.
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
18/56
Protection System Requirements (3)
Discrimination is the degree of ability of theprotection system to select whether or not to
operate for a given measured system state. Sensitivityis a measure of the ability of the
protection system to identify the presence of a
fault or other undesirable condition, eventhough that condition may be only slightlydifferent from an apparently healthy condition.
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
19/56
Protection System Requirements (4)
Operating time is the total time taken fromthe onset of the fault to the protection relay
sending a trip signal to the circuit breaker(s). Stability is a measure of the ability of the
protection system to remain inoperative
under certain fault conditions, because thefault is of such a nature that some otherprotection system is intended to effecttripping.
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
20/56
Protection Philosophies
Two major protection philosophies unit schemes should only detect and
react to primary system faults within thezone of protection, while remaining
inoperative for external faults;
non-unit schemes do not independentlyprotect one clearly defined part (or zone)
of the system - adjacent non-unitprotection schemes on an interconnectedpower system have an element ofoverlap with respect to their respective
zones of protection. University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
21/56
Unit Protection Schemes
Measurements/comparisons of
quantities
React only to faults inside protectedzone
Employs communications - expensive
Remain stable for external faults No backup for neighbouring system
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
22/56
Unit Protection: Normal Conditions
Communications
I1 I2
Irelay1= Irelay2Relay 1 Relay 2
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
23/56
Unit Protection: Internal Fault
Communications
I1 I2
Irelay1 Irelay2Relay 1 Relay 2
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
24/56
Unit Protection: Internal Fault
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
25/56
Unit Protection: External Fault
Communications
I1 I2
Irelay1= Irelay2Relay 1 Relay 2
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
26/56
Unit Protection Schemes
Examples:
Current differential protection
Phase comparison protection
Balanced voltage protection
Fault-generated noise protection
Distance protection with zone 1 inter-tripping
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
27/56
Non-Unit Protection Schemes
Do not independently protect one clearlydefined part (or zone) of the system
Non-unit protection schemes overlap withrespect to their zones of protection -provides backup
Settings are important to ensure
discrimination and stability Communications sometimes used to
enhance operation
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
28/56
Sub 2Sub 1
I
Decreasing Fault Current
I
Fault 1
Fault 1t
Fault 2tFault 2t
Fault 2
Relay 1 Relay 2
Non-Unit Protection
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
29/56
Non-Unit Protection Schemes
Examples:
Overcurrent schemes
Measure current
Distance/impedance measuring schemes
Measure voltage and current
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
30/56
Non-unit set to operatewith a time delay in this
region
Unit/non-unit
protection
Main transformerunit Protection
sub1
sub2
Back-upnon-unit protection
t
I
Fault 2
Fault 3
Fault 1
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
31/56
SourceLoad
(High Z)Load
(High Z)Load
(High Z)
Line(Low Z)
Line(Low Z)
Line(Low Z)
Line(Low Z)
v v v v
V V V
Current much higher than load currentVoltage at fault = 0
Fault 1
Assuming all line Zs are equalVoltage at P = 0.5VsourceFault current = X
Voltagehere?
Distance Protection
P
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
32/56
Source
Line(Low Z)
Line(Low Z)
Line(Low Z)
Line(Low Z)
v v v v
Current much higher than load current
(but not as high as fault at position 1)Voltage at fault = 0
Fault 2
Voltageand current measured
here?
P
Assuming all line Zs are equalVoltage at P = 0.75VsourceFault current = 0.5X
Distance Protection
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
33/56
Distance Protection
Measures voltage and current Faults further away from measurement point
V relatively high
I relatively low Faults nearer to measurement point
V relatively low
I relatively high
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
34/56
Distance Protection
System is set to operate for certain ratios of V, I
Can react with different time delays (e.g. as fast aspossible for close faults, slower (backup) for furtheraway faults
www.protectionrelaytest.com
O P i
http://www.protectionrelaytest.com/http://www.protectionrelaytest.com/7/29/2019 System Protection in Rurla Transmission lines
35/56
Overcurrent Protection
Inverse characteristic
Used as main protection
in distribution networks,backup in transmission
networks
Provides different time of operation
depending on level of fault current University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
36/56
Timesetting
Restrainingspring
Disc
Plugsetting
Core
(carriesflux)
Relay
contacts
Shadingrings
(introducephase shift)
Contactmaker
Induction Disc Relay
7/29/2019 System Protection in Rurla Transmission lines
37/56
Coil withmultiple tapping
points(results in more
or less flux forsame input current).
Tapping useddictated
by plug setting.
Induction Disc Relay
View from Rear
7/29/2019 System Protection in Rurla Transmission lines
38/56
Overcurrent Protection - Operation
BA
t
I
t
Decreasing Fault Current
I
Fault 1
Fault 1tF1
Fault 2tF2
Fault 2tF2
Fault 2
Relay 1 Relay 2
Source
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
39/56
Effect on curve positionof modifying
Time Multiplier Setting
Effect on curve positionof modifyingPlug Setting
Overcurrent Protection - Operation
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
40/56
Relays Standard Types
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
41/56
http://www.youtube.com/watch?v=kU6NSh7hr7Q
Video that describes magnetic fields, induced eddy currents andforces:
http://www.youtube.com/watch?v=TgzkA3fo-D8&feature=relate
Video showing induction disc relay operation (1:25), marginaloperation, or creep just before 2 minutes:
Induction disc relay operation
University of Strathclyde, 2011
http://www.youtube.com/watch?v=kU6NSh7hr7Qhttp://www.youtube.com/watch?v=TgzkA3fo-D8&feature=relatedhttp://www.youtube.com/watch?v=TgzkA3fo-D8&feature=relatedhttp://www.youtube.com/watch?v=TgzkA3fo-D8&feature=relatedhttp://www.youtube.com/watch?v=TgzkA3fo-D8&feature=relatedhttp://www.youtube.com/watch?v=kU6NSh7hr7Q7/29/2019 System Protection in Rurla Transmission lines
42/56
Alternative methods exist
One method:
Start at furthest downstream relay Progress upstream
Each relay is set with the objective of providing
backup to next downstream relay with a time delay Important to ensure that upstream relays will not
begin to operate before downstream relays for any
current
Setting of overcurrent relays
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
43/56
BA C
Source(Grid)
Load Load Load
I1 I2 I3 I4
IL1 IL2 IL3
I1=I2+IL1
Normal Operation
University of Strathclyde, 2011
O
7/29/2019 System Protection in Rurla Transmission lines
44/56
BA
Decreasing Fault Current
C
Source(Grid)
Load Load Load
Operate (quickly)Operate
(after a delay)Dont operate
Operation During Fault
University of Strathclyde, 2011
S i /G di f O R l
7/29/2019 System Protection in Rurla Transmission lines
45/56
Summary of procedure for each relay Calculate (or get from previous study) fault current, CT
ratio, relay rating, desired grading margin
Calculate plug setting (PS) must result in operating
current threshold greater than (130%?) of max loadcurrent check current discrimination withdownstream relay(s)
Get characteristic operating time (for TSM=1) for fault
current Use (or calculate) desired operating time to calculate
required TSM Desired operating time is known for furthest downstream relay, or is
downstream relays operating time for a fault at the downstream
location+grading margin)
Setting/Grading of Overcurrent Relays
University of Strathclyde, 2011
Overcurrent Protection Practical
7/29/2019 System Protection in Rurla Transmission lines
46/56
Overcurrent Protection PracticalConsiderations
Maximum/minimum fault levels
Motor starting
Embedded generation Meshed networks
Instantaneous/delayed operation
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
47/56
Use of directional relaysto provide correct protectionoperation on parallel feeders
From NPAG: - chapter 9www.deadsmall/2VA
University of Strathclyde, 2011
http://www.deadsmall/2VAhttp://www.deadsmall/2VA7/29/2019 System Protection in Rurla Transmission lines
48/56
Use of overcurrentrelays
for protection of ringmains
From NPAG: - chapter 9www.deadsmall/2VA
University of Strathclyde, 2011
Gradingexample with
http://www.deadsmall/2VAhttp://www.deadsmall/2VA7/29/2019 System Protection in Rurla Transmission lines
49/56
example withinstantaneous
& inverserelays (1A)
From ArevaNPAG
3000A125%125%
125%
PS(%)
7/29/2019 System Protection in Rurla Transmission lines
50/56
Protection of Distribution Networks
132/33kV Distance, differential (some), overcurrent
11kV/415V Overcurrent, reclosers, sectionalisers, fuses, RCDs
Remember, majority of faults transient fuses shouldonly operate if fault is permanent
Typically, faults are isolated very quickly by reclosers,multiple reclose attempts are attempted, and if fault is
permanent and downstream of fuses, fuses ultimatelymelt while system is in reclosed state
Reclose is then successful
If permanent fault between recloser and fuse, then
recloser will lock-out after pre-defined number of attempts
7/29/2019 System Protection in Rurla Transmission lines
51/56
Protection of distribution networks
Distribution network protection is
based on overcurrent protection
reclosers, sectionalisers and and
fuses
In rural distribution networks,>80% of faults are temporary and
auto reclose schemes are
adopted.
CBT1-11
CBT1-33
CBT2-11
CBT2-33B33kV
B11kV
SpurA1
SpurA2
SpurA3
SpurA4
SpurA5
SpurA6
SpurA7
SpurA8
SpurB1
SpurB2
SpurB3
SpurB4
SpurB5
R-A R-B
PMAR-A
PMAR-B
Feeder
A
Feeder
B
SpurA9
SpurA10
SpurA1
University of Strathclyde, 2011
7/29/2019 System Protection in Rurla Transmission lines
52/56
Protection of Distribution Networks
Transient fault
Recloser willsuccessfully reclose
Permanent fault
Recloser will reclosemultiple times (withvariable delays beforere-opening) and fuse
will melt before maxreclosures attempted
Sectionalisers/smartlinks may be used to
save fuses
Gers and HolmesProtection of
Electricity
DistributionNetworks,IEE Power &Energy Series 47
P i f Di ib i N k
7/29/2019 System Protection in Rurla Transmission lines
53/56
Protection of Distribution Networks
Gers and HolmesProtection of Electricity
Distribution Networks,
IEE Power & Energy Series 47
P i f Di ib i N k
7/29/2019 System Protection in Rurla Transmission lines
54/56
BA C
Load
Protection of Distribution Networks
PMAR Sectionaliser
Fuse
IDMT
PMAR
Sectionaliser
Fuse
IDMT StartOpen
Count 1
1 shot
ResetOpen
Count 1
1 shot
ResetClose
Count 1
2 shots
StartOpen
Count 2
2 shots
ResetOpen
Count 2
2 shots
ResetClose
Count 2
melt
ResetClose
Reset
melted
tFault inception
120
P i f Di ib i N k
7/29/2019 System Protection in Rurla Transmission lines
55/56
BA C
Load
Protection of Distribution Networks
PMAR Sectionaliser
Fuse
IDMT
PMAR
Sectionaliser
Fuse
IDMT StartOpen
Count 1
ResetOpen
Count 1
ResetClose
Count 1
ResetClose
Reset
tFault inception
10
Distribution System Protection: Summary
7/29/2019 System Protection in Rurla Transmission lines
56/56
Distribution System Protection: Summary
Typical distribution network architectures
Protection basics and requirements (review)
Brief review of protection philosophies and
schemes: Unit/non-unit Differential/distance/overcurrent
Reclosers/Sectionalisers/Fuses
Summary of operation andsetting of distribution protection
Practical considerations