10/01(9832-728) A-900 8 2001 FABRAL T-Rib Roofing System Installation Manual 3449 Hempland Road Lancaster, PA 17601 (717) 397-2741 308 Alabama Blvd. Jackson, GA 30233 (770) 775-4484 World Wide Web: www.fabral.com E-Mail: [email protected]

T-Rib Roofing System - Florida Building

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: T-Rib Roofing System - Florida Building

10/01(9832-728) A-900 8 2001 FABRAL

T-Rib

Roofing System

Installation Manual

3449 Hempland Road Lancaster, PA 17601 (717) 397-2741

308 Alabama Blvd. Jackson, GA 30233 (770) 775-4484

World Wide Web: www.fabral.com

E-Mail: [email protected]

Page 2: T-Rib Roofing System - Florida Building

General NotesHem LengthsThermal Movement TableAccessoriesT-Rib SpecificationsProduct ApplicationEndlap DetailDetailsDormer Details

4555

6-89-10

1112-1920-22

Table of Contents

VALLEY

PITCH BREAKWITHOUT FASCIA

EAVE WITHOUTGUTTER

FASCIA (INSIDE CORNER)

GABLE

RIDGE

EAVE WITH GUTTER

FASCIA (OUTSIDECORNER)

GABLE

ROOF/FASCIA TRANSITION

PEAK

HEAVY EQUIP-MENT CURB VENT PIPE

(LIGHT EQUIP-MENT CURB)

SIDEWALL

3

Page 3: T-Rib Roofing System - Florida Building

T-Rib Architectural Roofing

4

T-RIB SSR SYSTEM General Notes and Installation Recommendations

A. GENERAL NOTES

1. This booklet has been prepared to assist the designer and installer with various recommended details and installation procedures. Each project usually requires its own specially designed details. The details included can be used as a guide in designing project details.

2. Each roof panel is manufactured with four (4) minor stiffening ribs in the flat area to minimize oil-canning. However, due to the limitations of commercially available metals, some oil-canning should be anticipated and is not cause for rejection.

3. The erection of the T-Rib roof system can begin at either end of the building.

4. Whenever possible, workers should walk on the panel ribs rather than the flat of the panel. Boards or plywood should be placed over panels in areas which receive excessive foot traffic (such as roof top equipment, skylights, etc.).

5. Flashings must lap a minimum of 6". Treat flashing endlaps similar to a panel endlap detail using two rows of sealant tape with stitch screws 4" o.c. maximum.

6. Sealants: (a) Quality long-life butyl sealants work best as a gasket

sandwiched between two pieces of metal. (b) One part polyurethane sealants are recommended

when voids must be filled. 9. Jobsite handling:

(a) Panel crates must be lifted at bundle block locations. (b) Do NOT lift material with ropes or wires. (c) Do NOT lift panels greater than 25'-0" long without a

spreader bar. (d) Do NOT lift panels from ends while flat. DO lift panels

on edge. B. PROPER STORAGE

If the material is not to be used immediately, it should be stored in a dry place where little moisture can contact it. Moisture (from rain, snow, condensation, etc.) trapped between pieces of material may cause water stains or white rust which can affect the service life of the material and will detract from its appearance. To avoid staining or white rust, store the material in a well ventilated, dry area. Break the steel strapping bands used for shipment and store the material stacks material in an inclined position. If outdoor storage cannot be avoided, protect the material with a canvas or waterproof paper cover. Do not use plastic which can cause condensation. Keep the material off the ground in an inclined position with an insulator such as wood. It is the responsibility of the contractor to insure that all materials are properly stored at the jobsite.

C. INSTALLATION PROCEDURES 1. Check the structural support system to be sure it is straight

and square and that the tops of all members are in the same plane. Vertical camber in roof supports can cause water to pool on low pitched roofs. Misaligned structures can greatly increase the amount and degree of oil-canning.

2. Fasten each clip to the roof support member with the appropriate screw fastener. Clips are furnished pre-drilled to accept #12 screws.

3. For applications requiring endlaps, install the first panel (down-slope panel) like a normal panel. Prior to installing the upslope panel, place the back-up plate onto the

installed downslope panel. Position the endlap sealant tape and place the upslope panel into position. Install the upslope panel as outlined in the endlap details. Secure the endlap with four (4) self-drilling, self-tapping screws, as shown on the detail. Connect all beads of sealant prior to placement of the cap-lock at panel endlaps. For ease of installation, install the clip at the endlap prior to installing the remaining clips on the upslope panel.

D. FINAL CAP STRIP SEAMING 1. The cap strip seaming with the electric closure machine is begun after all other erection sequences are complete.

2. Remove closure machine from shipping box. 3. Install handle in position on motor mount stanchion. Insert clevis pin with washer through pivot holes. Insert retaining washer and spring pin.

4. To operate, use an approved electrical cord and plug into a 115 volt A.C. source. 5. Determine direction of operation and starting location on roof panel assembly. 6. Open seaming dies by moving lock lever to “unlock” position. At same time, raise handle of closing mechanism opening seaming dies to fully open position, approximately 30 degrees to each side of closure machine. 7. Lift closure machine and place in position where cap strip has been hand seamed. Insure front and rear guide blocks are aligned with panel ribs, are properly seated, and cam followers are along the sides of the cap strip. 8. Close seaming dies by moving lock lever into “lock” position. 9. Turn electric switch on, machine will begin seaming cap strip. 10.Operator should maintain alignment to panel ribs at same time applying slight forward pressure to assist movement along roof panel rib. 11. Upon reaching end of panel ribs, turn power switch off. Never install or remove closure machine while running. 12. Open seaming dies by moving lock lever to “unlock” position, releasing lock on left side of base platform, at same time raise handle of closing mechanism. 13. Position closure machine on next area of ribs to be seamed. Do not let closure machine sit directly on top of panels or it may mar the finish. 14. It is suggested that the closure machine be placed approximately 3 feet from the ridge and faced toward it and then seamed. Machine is then turned 180 degrees and seaming to the eave is completed. 15. The closure machine is not self-propelled but requires some pushing. A slightly firmer push may be needed at clip locations. 16. Inspect each seam after completion. Machine may be re-run over seam if required.

Page 4: T-Rib Roofing System - Florida Building

X

2X + 1/4"OVERALL

HEM LENGTH

ACCESSORIES

AC 3 ROOF CLIP, 1/4" STAND OFF, 18GA., TWO HOLES, UL 90 RATED.

FASTENERS

CLOSURECLIPS ARE AVAILABLE IN STAINLESS STEEL AND GALVANIZED STEEL.

USE STAINLESS STEEL CLIPS FOR EITHER STEEL OR ALUMINUM PANELS. USE GALVANIZED STEEL CLIPS FOR STEEL PANELS ONLY.

# 10-16 x 1" PHILLIPS PANCAKE HEAD, TYPE "A", SELF-TAPPING.

CLIPS

AC 5 ROOF CLIP, 1 1/4" STAND OFF, 18 GA., TWO HOLES, UL 90 RATED.

METAL TOP CLOSURE, GAUGE, COLOR AND WIDTH TO MATCH PANEL.

TOOLS

HAND CRIMPING TOOL

ELECTRIC SEAMER

TOUCH-UP PAINT

END DAMMING TOOL

HEM LENGTHSThe length of the hem at the end of a panel will vary with the change in temperature that the panel experiences and the length of the panel. Unless a more exact analysis of the temperature during installation compared to the maximum and minimum anticipated temperature is conducted, use the following equation and Thermal Movement Table. When installing panels, be sure to leave room at the end of the panel that will experience movement for the "starting gap" which is the required air space (X) between the panel and cleat.

THERMAL MOVEMENT TABLEPanel movement (in.) with a 100∞F temperature change in the panel

and a 50∞F temperature change in the substrate.

PANEL

MATERIAL

SUBSTRATE

MATERIAL

PANEL LENGTH(FT.)

steel

aluminum

rigid insulation

wood

steel

concrete

rigid insulation

wood

steel

concrete

10' 50' 100'

25/32"13/32"3/32"

5/8"3/8"1/16"

13/32"3/8"1/16"

15/32"3/8"1/16"

1 9/16"25/32"5/32"

1 3/8"11/16"5/32"

1 5/32"19/32"1/8"

1 7/32"5/8"1/8"

MISC.

PLATES

BEARING PLATE, 4" x 4", 20 GA.(USED FOR CLIPS INSTALLED OVER RIGID INSULATION)

BACK UP PLATE, 16 GA. (USED AT END LAPS OR RIDGES FOR EXTRA SUPPORT)

FILTER PLATE, "KNEE CAP", GAUGE AND COLOR TO MATCH PANEL.

THERMAL BLOCK, 1" x 4" x 17 1/2" POLYSTYRENE BLOCK.

# 10-16 x 1" PHILLIPS PANCAKE HEAD, SELF-DRILLING, SELF-TAPPING.

#12-14 x 1" PHILLIPS PANCAKE HEAD, TYPE "A", SELF TAPPING.

#12-14 x 1" PHILLIPS PANCAKE HEAD, SELF-DRILLING.

5

Page 5: T-Rib Roofing System - Florida Building

T-Rib Architectural Roofing

6

12", 16", OR 18"

1/16"

SEAM WITH CLIP BEFORE SEAMING

1 1/2"

2 7/16" 2 7/16"

SEAM WITH CLIP AFTER SEAMING

1 1/2"

5/8"

1 1/2"

2 3/8"

CAP STRIP

ALLOWABLE WIND UPLIFT LOAD (PSF) substrate

width

3.0'

3.5'

4.0'

4.5'

5.0'

24 ga. steel

12"

75

65

57

50

45

24 ga. steel

18"

57

48

42

38

34

22 ga. steel

12"

94

81

71

63

56

22 ga. steel

18"

71

60

53

48

43

.032" alum.

12"

55

52

49

46

42

.032" alum.

18"

42

39

37

34

32

Notes: 1. Allowable loads are based on 1980 edition of AISI specifications. 2. Deflection is limited to L/240 of span. 3. Loads are based on spans of 3 or more. 4. FY = 50 ksi for steel panels. 5. Uplift values based on attachment to 16 ga. purlins with 2 #10-16 SD ST screws. DESIGN INFORMATION The T-Rib panels can be custom tapered to a minimum width of 23" and a maximum width of 18". The maximum length of tapered panels is 40'. The maximum purlin spacing for the T-Rib panels is 4'. Minimum roof slope is 2:12. Panel can be curved in the field to a minimum radius of 200'. Maximum panel length is 65'. Minimum panel length is 6'.

TEST REPORT SUMMARIES

AIR INFILTRATION: had 0.015 cfm/sq ft leakage with 6.24 psf pressure differential per ASTM E283. WATER RESISTANCE: No water penetration under 5 gal./hr. spray at 6.24 psf pressure differential per ASTM E 331. UL90 UPLIFT RATING: 18" wide, 24 ga. panels on 16 ga. purlins (50 ksi yield strength) spaced 4' o.c. with two screws per clip and up to 6" of insulation between the panels and purlins (Construction No. 103). UL90 UPLIFT RATING: like Construction No. 103 (above) but with optional foamed plastic insulation (13" to 12" thickness) between panels and purlins and with butts occurring over purlins (Construction No. 139). UL90 UPLIFT RATING: 18" wide, 24 ga. panels on 2" plywood with clips spaced 2' o.c. and two #12-14 screws per clip (Construction No. 415). UL90 UPLIFT RATING: 18" wide, 24 ga. panels on 22 ga. deck (33 ksi yield strength) with clips spaced 2' o.c. Clips are fastened to deck with two #14 truss-head, No. 3 Phillips drive, self-drilling screws per clip. Bearing plates (42" x 6" x 24 ga.) are required under each clip. One to 4" of rigid insulation (2 pcf density) is optional between the panel and deck (Construction No. 416).

Page 6: T-Rib Roofing System - Florida Building

T-Rib Architectural Roofing

7

T-Rib Metal Roofing Suggested Specification PART 1: GENERAL 1.01 SUMMARY

A. Section includes: Prefinished, prefabricated, mechanically seamed, structural standing seam roof system and accessories.

B. Related Sections 1. Metal decking 2. Rough carpentry, plywood, and underlayment 3. Insulation 4. Membrane roofing 5. Flashing and sheet metal 6. Joint sealers: sealants and caulk 7. Structural framing.

1.02 REFERENCES A. American Society for Testing and Materials (ASTM)

1. ASTM A 653: Steel Sheet, Zinc-Coated by the Hot Dip Process

2. ASTM A 792: Steel Sheet, Aluminum -Zinc Alloy Coated by the Hot Dip Process.

3. ASTM B 209: Aluminum and Aluminum Alloy Sheet and Plate.

4. ASTM E 283: Air leakage 5. ASTM E 331: Water penetration

B. Underwriters Laboratory 1. UL Building Materials Directory C. Sheet Metal and Air Condition Contractors National

Association, Inc. (SMACNA) 1. SMACNA Architectural Sheet Metal Manual, 1993 Edition.

D. American Iron and Steel Institute (AISI) 1. AISI Cold Formed Steel Design Manual

E. Metal Construction Association (MCA) 1. Preformed Metal Wall Guidelines

F. Code references 1. ASCE, Minimum Loads for Buildings and Other

Structures 2. BOCA National Building Code 3. UBC Uniform Building Code 4. SBC Standard Building Code

1.03 SYSTEM DESCRIPTION A. Performance Requirements: Provide factory formed,

prefinished, mechanically seamed, concealed clip, structural standing seam metal roof system, that has been pretested and certified by manufacturer to comply with specified requirements under installed conditions. 1. Provide UL90 rated roofing system that has been tested in

accordance with UL 580 test procedure. 2. Resistance to air leakage: 0.015 cfm/ft. of joint leakage

when tested in accordance with ASTM E 283 at static pressure differential of 6.24 psf.

3. Resistance to water penetration: No leakage through panel joints when tested in accordance with ASTM E 331 at static pressure differential of 6.24 psf.

B. Structural Requirements: Engineer panels for structural properties in accordance with latest edition of American Iron and Steel Institute=s Cold Formed Steel Design Manual using Aeffective width" concept and Aluminum Association=s Aluminum Design Manual.

C. Maximum clip spacing shall be 4' o.c. 1.04 SUBMITTALS

A. Product Data: submit manufacturer's specifications, standard profile sheet, product data brochure and finish warranty.

B. Shop Drawings: shop drawings showing roof plan with layout of panels, clips, clip attachment, underlayment and sections of each flashing/trim condition shall be submitted for approval prior to fabrication. Drawings shall contain material type, metal thickness and finish. Drawings shall distinguish between factory and field fabrication.

C. Samples: 1. Submit sample 12" long x full width panel, showing

proposed metal gauge, seam profile and specified finish.

2. Submit manufacturers standard colors for Architect's selection.

D. Test Reports: 1. Submit the test reports prepared by Underwriters

Laboratory indicating wind uplift rating of proposed roof system. The manufacturer must be listed by name in the UL Directory.

2. Air leakage per ASTM E 283 and Water penetration per AST M E 331. (Actual independent laboratory certified test results must be submitted).

E. Certification: Submit manufacturer's certification that materials and finishes meet specification requirements.

1.05 QUALITY ASSURANCE A. Panel manufacturer shall have a minimum of ten (10) years of

experience in manufacturing architectural roofing in a permanent stationary indoor facility.

B. Panel installer shall have a minimum of two (2) years experience in the installation of concealed clip architectural standing seam metal roofing and show evidence of successful completion of at least three (3) projects of similar size, scope, and complexity.

1.06 DELIVERY, STORAGE, and HANDLING A. Panels shall be protected and properly packaged to protect

against transportation damage in transit to the jobsite. B. Upon delivery, exercise care in unloading, stacking, moving,

storing, and erecting panels to prevent twisting, bending, scratching, or denting.

C. Store panels in a safe, dry environment under a waterproof covering to prevent water damage. Allow for adequate ventilation to prevent condensation. Panels and flashings with strippable film shall not be stored in direct sunlight.

D. Upon installation immediately remove strippable film from panels and flashings. Protect panels and flashings from foot traffic and from all other trades.

1.07 PROJECT CONDITIONS A. Field dimensions shall be taken prior to fabrication to verify

jobsite conditions. 1.08 WARRANTIES

A. Panel manufacturer shall provide a twenty (20) year warranty on the paint finish covering chalking, cracking, checking, chipping, blistering, peeling, flaking, and fading.

B. Applicator shall furnish written warranty for a two (2) year period from date of substantial completion of building covering repairs required to maintain roof and flashings in watertight conditions.

Part 2 PRODUCTS 2.01 PRODUCT DESCRIPTION

A. T-Rib structural standing seam roof system as manufactured by Fabral, 3449 Hempland Road, Lancaster, PA 17601, ph.: 800-477-2741; fax: 800-283-4289.

B. Panels: The T-Rib panel shall have a width of 12", 16", or 18" wide. Seams shall be 22" high with a 2" top flange angled at 90 degrees from the seam to facilitate the seaming of the panel and cap. The panels shall have 1/16" x 1" stiffening ribs in the pan of the panel.

C. Roof panels shall use a one-piece roof clip allowing for thermal movement of the panel system.

D. The panel shall have a factory applied mastic and be mechanically seamed with a field operated electric seaming machine provided by the manufacturer.

E. The panel system shall be as a true standing seam shape requiring no trapezoidal foam closures, plugs, or fillers at eaves.

F. The maximum cap length shall be 30'. 2.02 PRODUCT SUBSTITUTIONS

A. Requests to use alternate systems shall be submitted in writing to the project designer at least ten (10) days prior to bid date. Request shall demonstrate proposed substitution meets or exceeds specified performance requirements. Certified

Page 7: T-Rib Roofing System - Florida Building

T-Rib Architectural Roofing

8

statements, samples and descriptive data shall be included in this submittal request.

B. Manufacturers listed in this section are prequalified manufacturers. Substitution of manufacturer's products for those specified shall not be allowed at anytime during construction.

2.03 MATERIALS AND FINISHES A. Panel materials

1. 24 or 22 gauge, Grade 50 (50 ksi yield strength) structural steel with G90 (0.90 oz./ft.2) hot dipped galvanized coating, both conforming to ASTM A 653.

2. 24 or 22 gauge, Grade 50 (50 ksi yield strength) structural steel with AZ50 (0.50 oz./ft.2) aluminum-zinc alloy coating, both conforming to ASTM A 792.

3. 0.032" or 0.040", 3105-H14 or equal (20 ksi yield strength) aluminum alloy conforming to ASTM B 209.

B. Texture: panels shall be smooth C. Finish: paint shall be full strength 70% polyvinylidene fluoride

(Kynar/Hylar* fluorocarbon) baked-on coating, factory applied prior to roll forming. The treatment shall be a two-coat system consisting of a single coat of 0.2 mil. primer followed by a finish coat of 0.8 mil. Kynar topcoat with a total dry film thickness of 1.0 mil ∀ 0.2 mil. The reverse side of the panels shall be treated with a back coat system consisting of a 0.2 mil. primer with a 0.3 mil. topcoat for a total dry film thickness 0.5 mil.

2.04 ACCESSORIES A. Concealed clips:

1. AC3 roof clip: a one piece, 18 ga. galvanized steel or (stainless steel), 3" stand-off, used on purlins (with or without up to 4" vinyl faced batt insulation) or light gauge framing and metal decking (with or without rigid insulation board and a bearing plate).

2. AC4 roof clip: a one piece, 18 ga. galvanized steel ( or stainless steel), 3" stand-off used on bar joist (with or without up to 4" vinyl faced batt insulation).

3. AC5 roof clip: a one piece, 18 ga. galvanized steel (or stainless steel), 1 3" stand-off used on purlins (with 4" t o 8" batt insulation).

4. Deck style roof clip: a one piece, 22 ga. galvanized steel used on plywood underlayment.

B. Flashing and Trim 1. All flashing and trim shall be of the same material, gauge,

finish, and color as the roof panels and fabricated in accordance with standard SMACNA procedure and details.

2. Provide transition rib covers where roofing changes pitch. 3. Fabricate gutters and downspouts in the same gauge,

material, finish, and color as the roof panels. C. Fasteners

1. Clips to substrate: screw shall be #12-14, self tapping type, zinc-plated steel.

2. Flashings to panels: exposed screws shall be zinc plated with a #14 x f" combination steel and neoprene washer, color to match panel.

3. Pop rivets: #43 stainless steel, color finish to match panel. D. Sealants

1. Shall not contain oil, asbestos, or asphalt. 2. Factory applied weatherstripping shall be applied in the

seam cap and designed for metal to metal concealed joints.

3. Field applied panel end sealant shall be mastic tape sealant.

4. Exposed sealant shall be one-part polyurethane joint sealant. Coordinate color with roof panels.

E. Closures 1. Ridge and hip closures shall be protected and supported by

a formed metal closure manufactured from the same material, color, and finish as the panels.

2. Metal closures shall be factory fabricated and field-cut as needed.

F. Thermal blocks 1. Thermal blocks shall be:

a. Non-treated wood as per manufacturer=s recommendation.

b. Extruded polystyrene block. c. EPDM membrane.

G. Vapor Retarder: 1. Retarder with a permeance of 0.05 or less as determined

by ASTM E 98. 2.05 RELATED MATERIALS

A. Refer to other sections listed in Related Sections paragraph for related materials.

2.06 FABRICATION A. Roof panels shall be formed in continuous lengths. End laps will

not be allowed. B. Panels shall be roll formed on a stationary industrial type rolling

mill to gradually shape the sheet metal. Portable rollformers, rented or owned by the installer, are not acceptable.

C. Fabricate flashings from the same material as the roof system. 2.07 SOURCE QUALITY

A. Source Quality: obtain metal panels and accessories from a single manufacturer.

B. Fabrication tolerances: follow tolerances in MCA=s Preformed Metal Wall Guidelines.

C. Tests and inspections D. Verification of performance

PART 3 EXECUTION 3.01 MANUFACTURER=S INSTRUCTIONS

A. Compliance: Comply with manufacturer=s product data, including product technical bulletins, product catalog installation instructions, and product cartons for installation.

3.02 EXAMINATION A. Installer shall:

1. Inspect roof deck and/or purlins to verify that it complies with shop drawings and is smooth, even, sound, and free of depressions.

2. Report variations and potential problems in writing to the architect.

3.03 INSTALLATION A. Conform to the standard set forth in the SMACNA architectural

sheet metal manuals and the approved shop drawings detailed for the project.

B. Install panels plumb, level, and straight with the seams parallel, conforming to the design as indicated.

C. Install panel system so it is watertight, without waves, warps, buckles or distortions, and allow for thermal movement considerations.

D. Abrasive devices shall not be used to cut on or near roof panel system.

E. Apply sealant tape or caulking as necessary at flashing and panel joints to prevent water penetration.

F. Remove any strippable film immediately upon installation. G. Hand-crimp battens at each clip or mechanically seam before

workers stand on panels. H. Seam panels together with electric-powered seaming machine

supplied by the panel manufacturer for a weathertight seam. I. Vapor retarder: The joints, perimeter, and all openings shall be

sealed per the manufacturer's instructions to provide a continuous vapor retarder.

J. Underlayment (solid substrat e): 1. Provide one layer of 30# felt with horizontal overlaps and

endlaps staggered between layers. 2. Provide ice and water shield membrane at all valley and

eave conditions as well as any area at less than a 3:12 slope.

3. Lay parallel to ridge line with 22" horizontal laps and 6" vertical laps

3.04 CLEANING A. Dispose of excess materials and debris from jobsite. B. Remove filings, grease, stains, marks, or excess sealants from

roof panel system to prevent staining. C. Protect work from damage from other trades until final

acceptance.

Page 8: T-Rib Roofing System - Florida Building

T-Rib Architectural Roofing

9

* Kynar7 500 is a registered trademark of Elf Atochem North America, Inc.

* Hylar7 5000 is a registered trademark of Ausimont USA, Inc.

Page 9: T-Rib Roofing System - Florida Building

BOX END DETAILBENDING TOOLBOX END OR HEMMED END

(AT RIDGES, HIPS, PEAKS, ETC.)METAL TOP CLOSURE

T-RIB PANEL PROFILE

1 1/2" 12", 16", & 18" COVERAGE

2 3/8"

1/16" x 1" STANDARD RIBS

(AT RIDGES, HIPS, PEAKS, ETC.)

FIELD BEND BOTTOM OFPANEL UP WITH BENDINGTOOL. BE CAREFUL NOTTO TEAR THE PANELNEAR THE SEAMS.

VARIESAS REQ'D

1" x 1" TUBING

2-2" x 2" x 1/4"ANGLES WELDED ASSHOWN.

1 1/2"

GUN GRADE MASTIC

T-RIB PANEL

5-#14x7/8"FASTENERS

1"x3/32" MASTIC.CONT. ALONG TOPOF CLOSURE

PRODUCT APPLICATION

9

Page 10: T-Rib Roofing System - Florida Building

(BEFORE)

HAND CRIMPING TOOL

(AFTER)

PUSH OUT

1" LAP

PANEL RIBS

UPSLOPE CAP STRIP.HAND CRIMP OVERLOWER CAP.

DOWNSLOPE CAPSTRIP. HANDCRIMP END.

HAND CRIMP ATROOF CLIPS.

10

Page 11: T-Rib Roofing System - Florida Building

LAP

#12x1 1/4"CLIP

PURLIN

BACK PLATE

(2) ROWS TAPE MASTIC(1) ROW GUN GRADE MASTIC

2 1/2

6"

9 1/2

1 1/2 "

FOLD MASTICOVER LAPPEDPANEL FLANGE

6"

#12x 1 1/4" FASTENERSTHRU PREPUNCHED HOLES.

BACK PLATE SLIDEUNDER PANEL.

TAPE MASTIC

GUN GRADE MASTIC

MASTIC MUST BESNUG IN CORNERS

END LAP DETAIL

11

Page 12: T-Rib Roofing System - Florida Building

OPEN FRAMING

AND METAL DECKRIGID INSULATION

PLYWOOD

HAT CHANNELS

AND WOOD DECKINGRIGID INSULATION

TUBE STEEL

T-RIB PANEL CLIP

T-RIB PANEL

AND WOOD DECK

HAT SECTION PURLIN

VINYL FACED BATT INSULATION

T-RIB PANEL CLIP

T-RIB PANEL

-TWO (2) PER CLIP

ZEE PURLIN

FASTENERS

-TWO (2) PER CLIPFASTENERS

ON BEARING PLATET-RIB PANEL CLIP

T-RIB PANEL

30lb. SATURATED FELTSON RIGID INSULATION

-TWO (2) PER CLIP

AND METAL DECK

FASTENERS

ON BEARING PLATET-RIB PANEL CLIP

T-RIB PANEL

FASTENERS

30lb. SATURATED FELTSON RIGID INSULATION

-TWO (2) PER CLIP

ON PLYWOOD SUBSTRATE30lb. SATURATED FELTS

-TWO (2) PER CLIPFASTENERS

T-RIB PANEL CLIP

T-RIB PANEL

TUBE STEEL

-TWO (2) PER CLIPFASTENERS

T-RIB PANEL CLIP

T-RIB PANEL

T-Rib panels can be installed over a variety of substrates and can accomodate most insulation requirements. Continuoushorizontal members are required for roof clip attachment and must be spaced to meet loading requirements. The horizontal members must have a flat surface at least as wide as the clip. Two fasteners per clip are required. Because T-Rib is atype of standing seam roof that accommodates thermal movement, the roof panels will not act as a diaphragm for winddesign. Therefore, bracing is required to resist wind loads.

12

Page 13: T-Rib Roofing System - Florida Building

SLIDING EAVE DETAIL (USE WITH SLIDING VALLEY AND FIXED RIDGE, HIP, AND

END WALL DETAILS)

SLIDING EAVE WITH GUTTER DETAIL (USE WITH FIXED RIDGE, HIP, AND END WALL DETAILS)

FASTENERSSEALANT TAPE

EAVE TRIM

HEM PANEL END

HOLD-DOWN STRIPFASTENERS @ 6" o.c.

-TWO (2) PER CLIP

ZEE PURLIN

EAVE STRUT

SEALANT IN SEAM

SEALANT TAPE

HOLD DOWN CLEAT SET ON3/16" x 1" "CHEMSCO"

3/16" x 1" "CHEMSCO"

T-RIB PANEL CLIP

T-RIB PANEL

HOLD-DOWN STRIP

FASTENERS @ 6" o.c.

EAVE TRIM w' CLEAT

SEALANT TAPE

HEM PANEL END

3/16" x 1" "CHEMSCO"

SEALANT IN SEAM

-TWO (2) PER CLIP

ZEE PURLIN

EAVE STRUT

FASTENERS

T-RIB PANEL CLIP

T-RIB PANEL

-TWO (2) PER CLIP

BOX GUTTER

FASTENERS @ 6" o.c.

EAVE TRIM w' CLEAT

FASTENER @ 24" o.c.

SEALANT TAPE

GUTTER STRAP @ 24" o.c.

3/16" x 1" "CHEMSCO"

HEM PANEL END

EAVE STRUT

ZEE PURLIN

FASTENERS

T-RIB PANEL CLIP

T-RIB PANEL

SLIDING EAVE DETAIL (USE WITH SLIDING VALLEY AND FIXED RIDGE, HIP, AND

END WALL DETAILS)

T-RIB PANEL

HOLD-DOWN STRIP

3/16" x 1" "CHEMSCO"

3/16" x 1" "CHEMSCO"HOLD DOWN CLEAT SET ON

SEALANT TAPE

SEALANT TAPE

EAVE TRIM

SEALANT IN SEAM

EAVE STRUT

FASTENERS @ 6" o.c.

-TWO (2) PER CLIP

ZEE PURLIN

FASTENERS

EAVE TRIM w' CLEAT

HOLD-DOWN STRIP

SEALANT IN SEAM

3/16" x 1" "CHEMSCO"SEALANT TAPE

FASTENERS @ 6" o.c.

EAVE STRUT

-TWO (2) PER CLIP

ZEE PURLIN

FASTENERS

T-RIB PANEL

SEALANT TAPE

BOX GUTTER

EAVE TRIM w' CLEAT

FASTENER @ 24" o.c.

GUTTER STRAP @ 24" o.c.

3/16" x 1" "CHEMSCO"

T-RIB PANEL

FASTENERS @ 6" o.c.

ZEE PURLIN

EAVE STRUT

-TWO (2) PER CLIPFASTENERS

FIXED EAVE WITH GUTTER DETAIL(USE WITH SLIDING RIDGE, HIP, AND END WALL

DETAILS)

FIXED EAVE DETAIL (USE WITH SLIDING RIDGE, HIP, AND END WALL DETAILS)

FIXED EAVE DETAIL (USE WITH SLIDING RIDGE, HIP, AND END WALL DETAILS)

1 1/2 "

POP-RIVET

1 1/2 "

13

Page 14: T-Rib Roofing System - Florida Building

T-RIB PANEL CLIP

T-RIB PANEL

CLEAT

#12 FASTENERS

FASTENERS @ 3" o.c.

-TWO (2) PER CLIP

METAL TOP CLOSURE

SEALANT TAPESET ON 3/16"x 1" "CHEMSCO"

VENT DRIP

RIDGE TRIM

8" x 8" RIDGE/HIP PLATE

ZEE PURLIN

20 ga. STEEL

T-RIB PANEL CLIP

T-RIB PANEL

SET @ 3" o.c.

SEALANT TAPESET ON 3/16" x 1" "CHEMSCO"METAL TOP CLOSURE

RIDGE/HIP TRIM

STAKING FASTENER(1) PER PANEL

PAN PANEL END

#12 x 1" FASTENERS

3/16"x 1" "CHEMSCO"

FASTENERS @ 12" o.c.

T-RIB PANEL CLIP

T-RIB PANEL

SEALANT TAPE

#12 FASTENERS

FASTENERS @ 3" o.c.

-TWO (2) PER CLIP

SEALANT TAPE

METAL TOP CLOSURESET ON 3/16"x 1" "CHEMSCO"

RIDGE TRIM

* CLIP SCREWS MUST HAVE LOW-PROFILE HEADS. PURCHASE FROM FABRAL ONLY.

FIXED RIDGE/HIP DETAIL (USE WITH SLIDING EAVE AND VALLEY DETAILS)

SLIDING RIDGE/HIP DETAIL (USE WITH SLIDING EAVE AND VALLEY DETAILS)

VENTED, FIXED RIDGE/HIP DETAIL (USE WITH SLIDING EAVE AND VALLEY

DETAILS)

2"

2"12"

7"

2"

2"

12"

14

Page 15: T-Rib Roofing System - Florida Building

NOTE:

AND HEM PANEL END UNDER.INSTALLER TO FIELD NOTCH

* CLIP SCREWS MUST HAVE LOW-PROFILE HEADS. PURCHASE FROM FABRAL ONLY.

FIXED VALLEY DETAIL (USE WITH FIXED EAVE AND SLIDING RIDGE, HIP, AND END WALL

DETAILS)

SLIDING VALLEY DETAIL (USE WITH SLIDING EAVE AND FIXED RIDGE, HIP, AND

END WALL DETAILS)

ICE & WATER SHIELDON 16ga. STEEL BACKER

-TWO (2) PER CLIPFASTENERS

-TWO (2) PER CLIP

FASTENERS @ 6" o.c.

FASTENERS

SEALANT TAPE

VALLEY TRIM

1 1/2 "

HOLD-DOWN CLEAT ON3/16" x 1" "CHEMSCO"

3/8

5"

ICE & WATER SHIELDON 16" x 16" VALLEY BACKER

MIN.

T-RIB PANEL

T-RIB PANEL CLIP

3/16" x 1" "CHEMSCO"SEALANT TAPE

ZEE PURLIN

SEALANT IN SEAM

T-RIB PANEL

SEALANT TAPE

VALLEY TRIM

3/16"x 1" "CHEMSCO"

#14 FASTENER @ 6" o.c.W' NEOPRENE WASHER

SEALANT IN SEAM

T-RIB PANEL CLIP

15

* CLIP SCREWS MUST HAVE LOW-PROFILE HEADS. PURCHASE FROM FABRAL ONLY.

Page 16: T-Rib Roofing System - Florida Building

GABLE FLASHING

WALL PANEL

SCREW

SEALANT TAPE

CONTINUOUS SUPPORT(UNNECESSARY FOR

INSTALLATIONS OVERDECK)

RIVET

CONTINUOUS SUP-PORT (UNNECES-SARY FOR INSTAL-LATIONS OVERDECK)

WALL PANEL

GABLE FLASHING

FIELD-BENDPANEL UP ATLEAST 2 1/2"

SCREW

END GABLESTART GABLE

CONTINUOUS ZEE

SEALANT

CONTINUOUS HEM; FILL W/ BUTYL CAULK

PURLIN

SIDEWALL DETAIL

TYPICAL REGLET

T-RIB PANEL

RIVET (12" O.C.)

SCREW (12" O.C.)

BEND UP PANEL 2 1/2";CAULK SEAM W/ BUTYL

CONTINUOUS SUPPORT (UNNECESSARYFOR INSTALLATIONS OVER DECK

RUBBER MEMBRANE

HOLD-DOWN CLEAT

CONTINUOUS ANGLE

EXPANSION JOINT CAP

BUTYL CAULK OR SEALANT TAPE

CONTINUOUS ANGLE

RIVET

E 2EE

SEALANT TAPE

CONTINUOUS SUPPORT (UNNECESSARY FOR INSTALLATIONS OVER DECK)

PURLIN PURLIN

EXPANSION JOINT DETAIL

E = CALCULATED THERMAL MOVEMENT

CONTINUOUS ANGLE

CAULK W/ BUTYL

16

CONTINUOUSHOLD-DOWN CLEAT

Page 17: T-Rib Roofing System - Florida Building

T-RIB PANEL

T-RIB PANEL CLIP

ZEE PURLIN

PEAK STRUT

HOLD-DOWN STRIP

#12 x 1" FASTENERSSET @ 12" o.c.

(1) PER PANEL

SET ON 3/16" x 1"

PEAK TRIM

PAN PANEL END

#12 x 1" FASTENERSSET @ 3" o.c.STAKING FASTENER

METAL TOP CLOSURE

"CHEMSCO" SEALANT

T-RIB PANEL CLIP

T-RIB PANEL

RIB COVER

POP-RIVET

LOW FIXED CLIPURETHANE SEALANTUNDER COVER

PLYWOOD SUBSTRATE30lb. FELTS ON

T-RIB PANEL CLIP

T-RIB PANEL

COUNTERFLASHING

PITCHBREAK TRIM

SET ON 3/16" x 1"

#12 x 1" FASTENERS

ZEE PURLIN

SET @ 3" o.c.

PEAK STRUT

STAKING FASTENER

(1) PER PANEL

"CHEMSCO" SEALANT

METAL TOP CLOSURE

TAPE

ROOF/FASCIA TRANSITION (FIXED AT TRANSITION; USE WITH SLIDING RIDGE, HIP, AND PEAK DETAILS AND SLIDING DETAIL AT FASCIA

BOTTOM)

FIXED PEAK DETAIL(USE WITH FIXED RIDGE, HIP, AND END WALL DETAILS AND SLIDING EAVE AND

VALLEY DETAILS)

FIXED END WALL DETAIL WITH SURFACE-MOUNTED REGLET (USE WITH SLIDING EAVE

AND VALLEY DETAILS)

7"

6"

17

Page 18: T-Rib Roofing System - Florida Building

ROOF PANELCURB

3/16"x 1" "CHEMSCO"

CURB JAMB FLASHING

SEALANT TAPE

RIGID INSULATIONAND METAL DECK

30lb. FELTS ON

3/16"x 1" "CHEMSCO"SEALANT TAPE

TURN PANEL EDGE UP

POP-RIVET TO PANELCURB TRIM

CURB FLASHING(by others) typ.

SECTION A-A

DOWNSLOPE

A A

PRE-FAB ROOF CURB

6"

6"

18

Page 19: T-Rib Roofing System - Florida Building

FASCIA INSIDE CORNER

FOR VERTICAL FASCIA PANELS LESS THAN 10' LONG, MAKING THE FIRST FOLD ONLY OF THE SEAM IS PERMISSIBLE.

FASCIA OUTSIDE CORNER

VENT PIPE FLASHING(ALSO APPLIES TO LIGHT

EQUIPMENT CURBS)

PANCAKEHEAD SCREW

(12" O.C.)FILL HEM W/BUTYL CAULK

NOT TO EXCEED 10"

NOT TO EXCEED 10"

NOT TO EXCEED 10"

PANCAKE HEADSCREW (12" O.C.)

FASCIA EDGE

OUTSIDECORNER

FLASHING

NO

T T

O E

XC

EE

D 10"

INSIDECORNER

FLASHING

FIELD-CUT AND HEMPANEL; FILL HEM

WITH BUTYL SEALANT

FILL HEMS W/BUTYL CAULK

PANCAKE HEADSCREW (12" O.C.)

CONTINUOUS CLEAT

FOR ATTACHING PIPE BOOTS TO PANELS ON PURLINS, DO NOT PENETRATE PURLINS WITH SCREWS AND KEEP SCREWS AND PIPE AT LEAST 1" FROM PURLINS.

2"

LEAVE CLEARANCE OF2" AROUND PIPE.

SET IN SEALANT

SCREW FASTENER@ 3" o.c.

VENT PIPE

PIPE BOOT

2"

CL CL CL

NO

T T

O E

XC

EE

D 10"

19

FIELD-CUTPANEL

Page 20: T-Rib Roofing System - Florida Building

LAP 6", START AT EAVE2 SET 30# FELTS,

1 SET 36" WIDEICE & WATER SHEILD

20

Page 21: T-Rib Roofing System - Florida Building

WITH CLEATSSET VALLEY TRIM4

WITH J-CLEATSET RAKEWALL TRIM3

21

Page 22: T-Rib Roofing System - Florida Building

PITCHBREAK

RAKEWALL

ROOF TO FASCIA

GABLE

RIDGE

5 PANELS IN PLACE

LAP PANELS 12"

VALLEY

22

Page 23: T-Rib Roofing System - Florida Building

10/01(9832-728) A-900 8 2001 FABRAL

3449 Hempland Road, Lancaster, PA 17601 (800) 477-2741 Route 24 West, Gridley, IL 71744 (800) 451-3974

308 Alabama Blvd., Jackson, GA 30233 (800) 884-4484 Route 3, Box 632, Idabel, OK 74745 (800) 926-8509

2402 Industry Way, Cedar City, UT 84720 (800) 432-2725 658 Boekel Road, Rathdrum, ID 83858 (888) 432-2725

1820 East 26th St., Marshfield, WI 54449 (800) 528-0878 Highway 41 South & 55 Lamb Loop Road, Tifton, GA 31793 (800) 749-8144

World Wide Web address: www.fabral.com

e-mail address: [email protected]