TCY3-T0121R

Embed Size (px)

Citation preview

  • TCY3-T0121R

    Doc: 70-000002 V1.0, 20100420 Vector Controls GmbH, Switzerland Page 1 Subject to alteration

    TCY3-T0121R Series Intelligent Compact Controller Features Temperature control for 2-pipe, 4-pipe HVAC

    systems. -H version: Humidity control with integrated

    humidity sensor Universal PID and binary control for any

    analog input/output signal and range 4 independent PID sequences, 12

    independent binary sequences 1 modulating output for DC 0...10V or 020

    mA actuators with 10 bit resolution. 1 Input for DC 05V, 010V or 020 mA

    sensors with 10 bit resolution 1 internal temperature sensor and 1 external

    sensor input Multiple functions on external input: auto

    changeover, remote control Monitoring of low and high limits on all inputs.

    Programmable reaction in case of alarm. Feedback function for internal sensors and

    set points. Special functions for dehumidifying, set point

    shift and VAV control Transformation of display value according to

    analog sensor range Password protected programmable user and

    control parameters Blue backlight Deluxe Version only: o Power Cap protected real time clock with 24h

    power backup o 16 switching times, grouped in 4 time

    schedules. o Infrared remote control

    Applications Air Only Systems: Constant or Variable Air Volume systems for single or dual duct systems with options of:

    o up to two reheat stages o supply air, extract air cascade control o humidity control o Control for variable speed fans

    Air/Water Systems:

    o Fan Coil units for 2-pipe or 4-pipe systems with options of: Humidity control Pressure control

    o radiator control, chilled ceiling

    Water Only Systems: Radiator, floor heating or chilled ceilings

    Individual room control for hotel rooms, meeting rooms, etc. General Description The TCY3 is a stand-alone electronic universal controller with two autonomous control loops. Each control loop may use up to 2 PID sequences and 6 binary sequences. The TCY3-T0121R features 1 NTC temperature sensor and 1 analog input, 2 binary outputs and one analog output. The outputs need to be assigned to the control sequences by parameters. A detailed configuration is possible by following a simple setup routine. The TCY3 can be configured using the standard operation terminal. No special tool or software is required.

  • TCY3-T0121R Technical Data

    Doc: 70-000002 V1.0, 20100420 Vector Controls GmbH, Switzerland Page 2 Subject to alteration

    Name

    C YT T 0 1 2 1 H(- ) U(- ) D(- )-3 R

    Ordering Model Stock code Variant Mounting size Type Key-data TCY3-T0121R 40-10 0021 Standard 88mm x 88mm

    No humidity sensor

    Compact PI controller with: 1 TI int or ext 1 AI 2 DO (Relay) 1 AO

    TCY3-T0121R-D 40-10 0022 Deluxe TCY3-T0121R-U 40-10 0023 Standard 2 x 4 TCY3-T0121R-U-D 40-10 0024 Deluxe TCY3-T0121R-H 40-10 0025 Standard 88mm x 88mm

    With humidity sensor

    TCY3-T0121R-H-D 40-10 0026 Deluxe TCY3-T0121R-H-U 40-10 0027 Standard 2 x 4 TCY3-T0121R-H-U-D 40-10 0028 Deluxe

    Dimensions [mm] (inch)

    Deluxe version 2 x 4 housing Integrated Humidity sensor Relays for binary outputs Number of analog outputs (AO) = 1 Number of binary output (DO) = 2 Number of analog inputs (AI) = 1 Number of binary inputs (DI) = 0 With external temperature input (RT) Series (TCY3)

    88 (3.5) 32 (1.2)21

    (0.8)

    88 (3

    .5)

    58 (2

    .3)

    58 (2

    .3)

    112

    (4.4

    )

    73 (2.9) 32 (1.2) 15 (0.6)

  • TCY3-T0121R Technical Data

    Doc: 70-000002 V1.0, 20100420 Vector Controls GmbH, Switzerland Page 3 Subject to alteration

    Technical specifications Power Supply Operating Voltage 24 V AC/DC 10 %, 5060 Hz

    Power Consumption Max. 3 VA Electrical Connection Terminal Connectors,

    wire 0.342.5 mm2 (AWG 2412)

    Internal rectification: Signal ground = power ground

    Half wave rectified Security transformer required

    Clock backup 24 hours (Deluxe version only) Signal inputs Analog Input

    Input Signal Resolution

    AI1 0...10 V or 0...20 mA 9.76 mV or 0.019 mA (10 bit)

    Temperature Input Range Int. NTC: 050 C (32122 F)

    Ext. NTC (Sxx-Tn10 sensor): -40140 C (-40284 F) Accuracy -400 C (-4032 F): 0.5 K

    050 C (32122 F): 0.2 K 50100 C (122212 F): 0.5 K > 100 C (> 212 F): 1 K

    Humidity Input: (-H Version only) Range Accuracy at 55 % r.H. Hysteresis Repeatability Stability

    H1 Thermoset Polymer-Based Capacity 0100 % r.H. 3.0 % at 25 C (77 F) 3 % between 1590 % r.H. 0.5 % 0.5 % / year if used within 050 C (32122 F)

    Signal outputs Analog Outputs Output Signal Resolution Maximum Load in voltage mode

    AO1 DC 0...10 V or 0...20 mA (250 max.) 9.76 mV resp. 0.019 mA (10 bit) 10 mA

    Relays Outputs AC Voltage DC Voltage

    DO1, DO2 048 VAC, 2 (1.2) A max. each output 030 VDC, 2 (1.2) A max. each output

    Environment Operation Climatic Conditions Temperature Humidity

    To IEC 721-3-3 class 3 K5 050 C (32122 F)

  • TCY3-T0121R Technical Data

    Doc: 70-000002 V1.0, 20100420 Vector Controls GmbH, Switzerland Page 4 Subject to alteration

    Selection of actuators and sensors

    Temperature Sensors: Use only our approved NTC sensors to achieve maximum accuracy. Recommended is SDB-Tn10-20 as Duct sensor, SRA-Tn10 as Room sensor and SDB-Tn10-20 with AMI-S10 as immersion sensor.

    Modulating Actuators: Choose actuators with an input signal type of 0-10 V DC or 4-20 mA. Minimum and maximum signal limitations may be set in software.

    Floating Actuators: Actuators with constant running time are recommended. Observe power limits on binary devices.

    Binary auxiliary devices: E.g. pumps, fans, on/off valves, humidifiers, etc. Do not directly connect devices that exceed 48 VAC, 2(1.2) A. Observe startup current on inductive loads.

    Connection diagram

    YB1 YB2 YM1 XA1 RT

    2 3

    1 4 5 6 7 8

    TCY3-T0121..

    24V AC/DC 10%

    0...48 VAC0...30 VDC

    0V (GND)

    0V

    Description:

    YB1 Binary output 1: 048 VAC or 030 VDC YB2 Binary output 2: 048 VAC or 030 VDC XA1 Analog input 1: 05 V, 010 V or* 020 mA YM1 Analog output 1: 010 V or* 020 mA RT Temperature input 1: NTC 10k @ 25C (77F)

    *) selectable by jumper

    U WARNING:

    Power supply is half-wave rectified: Signal ground = Power ground

    Connect through a safety isolation transformer

    !