DESIGN TEAM CITY OF LAREDO HIGH SERVICE PUMP VFD AND POWER FACTOR CORRECTION DRAWING INDEX 8 FEBRUARY, 2019 C0.0 COVER SHEET E1.1 ELECTRICAL GENERAL NOTES AND LEGENDS E1.2 OVERALL SITE PLAN E2.1 ELECTRICAL SCHEDULES AND DETAIL (UCRM 1 & 2) E3.1 ELECTRICAL DEMO (UCRM 1) E4.1 VFD ADDITIONS (UCRM 1) T1818- CITY OF LAREDO - HIGH SERVICE PUMP VFD AND POWER FACTOR CORRECTION. 2519 Jefferson St., Laredo, TX 78040 TEESI Engineering AUSTIN, TEXAS 78745 (512) 328-2533 TBPE #F-3502 www.teesi.com 1301 S. CAPITAL OF TX HWY. SUITE B-325 JEFFERSON STREET WATER TREATMENT PLANT 5816 DAUGHERTY AVE. LAREDO, TEXAS 78041 CITY COUNCIL Rudy Gonzalez, Jr. - District 1 Vidal Rodriguez - District 2 Mercurio Martinez, III. - District 3 Alberto Torres, Jr. - District 4 Nelly Vielma - District 5 Marte A. Martinez - District 6 George J. Altgelt - District 7 Roberto Balli - District 8 Mayor Pete Saenz UTILITIES DIRECTOR Riazul I. Mia, P.E. M.S.E.E. Robert A. Eads CO-INTERIM CITY MANAGERS Rosario Cabello N:\T18\T1818 - Laredo Loanstar VFD - PFC\2D - Design Phase\CAD\MEP\C0.0.dwg, C0.0, 2/14/2019 10:20:23 AM, Thomas, AutoCAD PDF (General Documentation).pc3 02/14/2019

TEESI · degrees celsius degrees fahrenheit dat ddc det dia dis dn do dp dps dpt dsp dx °c °f galvanize ground green grounding electrode conductor galv grd grn gec pounds local

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: TEESI · degrees celsius degrees fahrenheit dat ddc det dia dis dn do dp dps dpt dsp dx °c °f galvanize ground green grounding electrode conductor galv grd grn gec pounds local

DESIGN TEAM

CITY OF LAREDO

HIGH SERVICE PUMP VFD AND POWER FACTOR CORRECTION

DRAWING INDEX

8

FEBRUARY, 2019

C0.0 COVER SHEET

E1.1 ELECTRICAL GENERAL NOTES AND LEGENDS

E1.2 OVERALL SITE PLAN

E2.1 ELECTRICAL SCHEDULES AND DETAIL (UCRM 1 & 2)

E3.1 ELECTRICAL DEMO (UCRM 1)

E4.1 VFD ADDITIONS (UCRM 1)

T1

81

8- C

IT

Y O

F L

AR

ED

O - H

IG

H S

ER

VIC

E P

UM

P V

FD

A

ND

P

OW

ER

F

AC

TO

R C

OR

RE

CT

IO

N.

2519 Jefferson St., Laredo, TX 78040

TEESIEngineering

AUSTIN, TEXAS 78745(512) 328-2533

TBPE #F-3502www.teesi.com

1301 S. CAPITAL OF TX HWY.SUITE B-325

JEFFERSON STREET WATER TREATMENT PLANT

5816 DAUGHERTY AVE.

LAREDO, TEXAS 78041

CITY COUNCIL

Rudy Gonzalez, Jr. - District 1

Vidal Rodriguez - District 2

Mercurio Martinez, III. - District 3

Alberto Torres, Jr. - District 4

Nelly Vielma - District 5

Marte A. Martinez - District 6

George J. Altgelt - District 7

Roberto Balli - District 8

Mayor Pete Saenz

UTILITIES DIRECTOR

Riazul I. Mia, P.E. M.S.E.E.

Robert A. Eads

CO-INTERIM CITY MANAGERS

Rosario Cabello

N:\T18\T1818 - Laredo Loanstar VFD - PFC\2D - Design Phase\CAD\MEP\C0.0.dwg, C0.0, 2/14/2019 10:20:23 AM, Thomas, AutoCAD PDF (General Documentation).pc3

02/14/2019

Page 2: TEESI · degrees celsius degrees fahrenheit dat ddc det dia dis dn do dp dps dpt dsp dx °c °f galvanize ground green grounding electrode conductor galv grd grn gec pounds local

E1.1

EL

EC

TR

IC

AL

G

EN

ER

AL

NO

TE

S &

L

EG

EN

DS

TEESIENGINEERING

AUSTIN PH. (512) 328-2533LAREDO PH. (956) 724-1600

www.teesi.com

#B-325, AUSTIN, TEXAS 787461301 S. CPTL. OF TX. HWY.

TBPE #F-3502

CIT

Y O

F L

AR

ED

O

HIG

H S

ER

VIC

E P

UM

P V

FD

A

ND

P

OW

ER

F

AC

TO

R C

OR

RE

CT

IO

N

JE

FF

ER

SO

N S

TR

EE

T W

AT

ER

T

RE

AT

ME

NT

P

LA

NT

25

19

JE

FF

ER

SO

N S

TR

EE

T.

LA

RE

DO

, T

X 7

80

40

REVISION CLOUD & MARKER

BOUNDARY MARKS

BREAK MARK

NEW TO EXISTING

POINT OF CONNECTION

DRAWING

SHEET

REFERENCE

REFERENCE

DEMOLITION KEYED NOTE

NEW WORK KEYED NOTE

MATCHLINE

(N) - NEW WORK

(E) - EXISTING, REMAINS

(X) - DEMOLITION

AREA " "

AREA " "

GENERAL LEGEND

DETAIL KEYED NOTE

MISC. KEYED NOTE

SRV/HUB

TV/TEL

TV OUTLET BOX

MANUAL SWITCH, CALL OUTS; 'K'-INDICATES KEYED SWITCH; 2-DOUBLE POLE, 3-3-WAY SWITCH; 4-4-WAY

SWITCH; M-DOUBLE THROW, MOMENTARY CONTACT; F-CAPACITOR TYPE, 4 SPEED FAN CONTROL;

OS-OCCUPANCY SENSOR RM. COVERAGE CONTROLLER; D-DIMMER; SC-SPEED CONTROL.

DATA OUTLET; FLUSH FLOOR DATA OUTLET

COMB DATA & TELEPHONE OUTLET; FLUSH FLOOR COMB. DATA & TELEPHONE OUTLET

TELEPHONE OUTLET; FLUSH FLOOR TELEPHONE

OUTLET

ELECTRICAL LEGEND

LIGHTING/POWER CKT. ARROW INDICATES HOME RUN, TICS INDICATE NUMBER OF CONDUCTORS

EXCLUDING GROUNDS.

PHOTO-CONTROL RELAY

POWER/COMM POLE, NUMBER OF CHANNELS &/OR DEVICES AS INDICATED. WIREMOLD OR APPROVED

EQUAL

FLUSH MOUNTED FLOOR DUPLEX RECEPTACLE WITH COVER AS INDICATED

DISCONNECT SWITCH, SIZE & TYPE AS INDICATED OR REQUIRED

MOMENTARY CONTACT, PUSHBUTTON, MUSHROOM HEAD

MOMENTARY CONTACT, PUSHBUTTON

XX

XX

XX

SYMBOL DESCRIPTION

CIRCUIT RELATED

POWER OUTLETS

TELEPHONE/DATA

MISC. DEVICES

DUPLEX RECEPTACLE, NEMA 5-20R

FOURPLEX RECEPTACLE, NEMA 5-20R

DUPLEX RECEPTACLE & DATA RECEPTACLE IN DUAL CHANNEL, SURFACE RACEWAY

FOUR-PLEX RECEPTACLE & DATA RECEPTACLE IN DUAL CHANNEL, SURFACE RACEWAY

POWER EQUIPMENT

SINGLE RECEPTACLE, NEMA 5-20R, UNLESS OTHERWISE NOTED

XX

COMMON NOTATIONS: X-XXR = NEMA CONFIGURATION; IG = ISOLATED GROUND; GFI = GROUND

FAULT CIRCUIT INTERRUPTER; WP = WEATHERPROOF

COMBINATION STARTER / DISCONNECT SWITCH

MOTOR STARTER

PANELBOARD

PANELBOARD - FLUSH MOUNTED

SERVER/HUB

VARIABLE FREQUENCY DRIVE

THERMOSTAT; MARK INDICATES UNIT OR ZONE CONTROLLED

PHOTO SENSOR (A=ANOLOG, S=SWITCH)BOR)

SWITCHING &/OR DIMMING STATION (K=KEYED ACCESS)

MOTION SENSOR, ARROWS INDICATE DIRECTION OF SENSING FIELD

CONDUIT STUBBED OR ROUTED UP

CONDUIT STUBBED OR ROUTED DOWN

CONNECT TO EQUIPMENT

TRANSFORMER; THICK LINE DENOTES FRONT

SWITCHGEAR; THICK LINE DENOTES FRONT

GROUND BAR

LOW VOLTAGE CONTROL

T

X

VFD

JUNCTION BOX, MOUNTED AS INDICATED

TV OR TELEPHONE TERMINAL BOARD; 3/4"THK x 8' HT TYPE AC PLYWD.

XX

RELAY MODULE W/ LOW VOLTAGE POWER SUPPLY

LOW VOLTAGE SIGNAL WIRING

BRANCH CIRCUIT SIZING TABLE

NOTES:

1. ALLOWABLE CIRCUIT LENGTH (AL) MAY BE ADJUSTED FROM TABLE LENGTH (TL) BY

LOAD FACTOR (LF=AMPS/MAX CKT AMPS) AND VOLTAGE FACTOR (VF) USING THE

FORMULA: AL = TL x VF / LF

2. FOR THIS PURPOSE, ASSUME THAT ANY CIRCUIT SERVING ANY UNDESIGNATED

RECEPTACLE IS LOADED AT ITS PROTECTION RATING.

3. IF CIRCUIT CONDUCTOR SIZE IS INCREASED FOR VOLTAGE DROP, INCREASE

EQUIPMENT GROUNDING CONDUCTOR BY SAME NUMBER OF AWG SIZES (SAME

CIRCULAR MILLS RATIO).

LENGTH (FT) FOR 3% DROP AT 120V, 1 PH

MAX CKT

AMPS

BASE WIRE

SIZE (AWG)

BASE SIZE NEXT SIZE NEXT SIZE NEXT SIZE

20

30

50

65

85

100

115

130

150

175

200

225

12

10

8

6

4

3

2

1

1/0

2/0

3/0

4/0

45

45

45

55

65

70

75

80

90

90

95

100

70

70

70

85

80

85

90

100

110

110

115

110

110

110

110

100

110

115

125

140

140

180

180

140

135

130

140

150

160

180

VOLTS,

PHASE

VOLTAGE

FACTOR

120V, 1PH

208V, 1PH

277V, 1PH

480V, 1PH

208V, 3PH

480V, 3PH

1.00

1.73

2.31

4.00

2.00

4.62

EGC WIRE

SIZE (AWG)

12

10

10

10

6

4

6

6

6

8

8

6

· EGC = EQUIPMENT GROUNDING CONUDCTOR

GENERAL ELECTRICAL NOTES:

--M

--N

--O

--P

--Q

--R

--T

--U

--V

--L

--K

--I

--H

--G

--F

--E

--D

--C

--B

--A

VOLTS ALTERNATING CURRENT

VOLTS DIRECT CURRENT

VARIABLE FREQUENCY DRIVE

TELEPHONE

TYPICAL

TOWER

UNDERGROUND

UNDERGROUND ELECTRICAL

UNLESS OTHERWISE NOTED

UNDERGROUND PRIMARY ELECTRICAL

UNDERGROUND SECONDARY

ELECTRICAL

DATA

DIRECT DIGITAL CONTROL

DETECTOR

DIAMETER

DISCRETE INPUT, DIGITAL IN

DOWN

DISCRETE OUT, DIGITAL OUT

DIFFERENTIAL PRESSURE

DIFFERENTIAL PRESSURE SWITCH

DIFFERENTIAL PRESSURE TRANSDUCER

DISCHARGE STATIC PRESSURE

DIRECT EXPANSION

DEGREES CELSIUS

DEGREES FAHRENHEIT

DAT

DDC

DET

DIA

DIS

DN

DO

DP

DPS

DPT

DSP

DX

°C

°F

GALVANIZE

GROUND

GREEN

GROUNDING ELECTRODE CONDUCTOR

GALV

GRD

GRN

GEC

POUNDS

LOCAL AREA NETWORK

LARGE

LOW LIMIT THERMOSTAT

LOCAL OPERATING NETWORK

LBS

LAN

LG

LLT

LON

KVA

KW

K

KILOVOLT-AMPS

KILOWATTS

KILO

IN

HL

HP

HRU

HRV

HTG

HZ

INCHES

FCU

FT

FSD

FLEX

FLR

FPMB

FRZ

EA

EWC

EWH

EXT

EDH

EF

EMS

ENA

ENCL

ENET

ERH

ERW

ERV

ETR

EGC

CHILLER

CHILLED WATER PUMP

CEILING

COMMUNICATIONS

CURRENT STATUS SWITCH

COOLING TOWER

COOLING TOWER FAN

CONTROL

CONDENSING UNIT

CONDENSER WATER PUMP

BUILDING AUTOMATION SYSTEM

BELOW FINISHED FLOOR

BELOW FINISHED GRADE

BUILDING

BOILER

BRITISH THERMAL UNIT

BRITISH THERMAL UNIT PER HOUR

BREAK ON RISE

ABOVE FINISHED FLOOR

ABOVE FINISHED CEILING

ABOVE FINISHED GRADE

ACCESS DOOR

ACCESS PANEL

AIR CONDITIONING

APPROXIMATE

ACTUATOR

AIR COOLED CONDENSING UNIT

AIR HANDLING UNIT

ANALOG IN

ALARM

ANALOG OUT

AUXILIARY

BAS

BFF

BFG

BLDG

BLR

BTU

BTUH

BOR

CH

CHWP

CLG

COM

CS

CT

CTF

CTRL

CU

CWP

AFF

AFC

AFG

AD

AP

A/C

APPROX

ACT

ACCU

AHU

AI

ALM

AO

AUX

EACH

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

EXTERNAL

ELECTRIC DUCT HEATER

EXHAUST FAN

ENERGY MANAGEMENT SYSTEMS

ENABLE

ENCLOSURE

ETHERNET

ELECTRIC RE-HEAT

ENERGY RECOVERY WHEEL

ENERGY RECOVERY VENTILATOR

EXISTING TO REMAIN

EQUIP. GROUNDING CONDUCTOR

FAN COIL UNIT

FEET/FOOT

FIRE/SMOKE DAMPER

FLEXIBLE

FLOOR

FAN POWERED MIXING BOX

FREEZER

HIGH LIMIT THERMOSTAT

HORSEPOWER

HEAT RECOVERY UNIT

HEAT RECOVERY VENTILATOR

HEATING

HERTZ

MAX

MIN

MVA

MOR

MAXIMUM

MINIMUM

MEGAVOLT-AMPS

MAKE ON RISE

NA

NU

NC

NO

NOT APPLICABLE

NUMBER

NORMALLY CLOSED

NORMALLY OPEN

PWM PULSE WIDTH MODULATION

QTY QUANTITY

VAC

VDC

VFD

UG

UGE

UON

UPE

USE

TEL

TYP

TWR

--W

WATTS

WEATHERPROOF

WATER DETECTOR

WITH

W

WP

WD

W/

--X

--Z

ZONE

ZONE RELAY

TRANSFORMER

ZN

ZR

XFMR

REC

REF

R

RM

RTU

RECEPTACLE

REFERENCE

RELAY

ROOM

ROOFTOP UNIT

--S

SMOKE DETECTOR

SUPPLY FAN

SOLENOID

START/STOP

STATUS

STAGE

SD

SF

SOL

S/S

STAS

STG

ELECTRICAL ABBREVIATIONS

1. ELECTRICAL CONTRACTOR SHALL VERIFY EXACT LOCATION OF ALL FLOOR MOUNTED

BOXES W/ OWNER/ARCHITECT.

2. ELECTRICAL CONTRACTOR SHALL MARK ALL DATA CONDUITS & BOXES W/ PERMANENT

MARKER TO ENSURE THAT THEY ARE NOT USED FOR OTHER WIRING.

3. ELECTRICAL CONTRACTOR SHALL COORDINATE W/ OTHER TRADES TO MINIMIZE

CONFLICTS.

4. ALL NEW WIRE & CABLE SIZES ARE FOR COPPER. ALUMINUM WILL NOT BE ALLOWED.

5. CONFIRM W/ LOCAL CODES, MECHANICAL CONTRACTOR & EQUIPMENT VENDORS ON THE

LOCATION & MOUNTING METHOD FOR DISCONNECT SWITCHES, MANUAL MOTOR STARTERS,

COMBINATION STARTER/DISCONNECTS, ETC. PRIOR TO ELECTRICAL ROUGH-IN &

INSTALLATION.

6. ELECTRICAL CONTRACTOR SHALL DOUBLE CHECK ALL FEEDER CONDUCTOR & CONDUIT

SIZES W/ NEC & LOCAL CODES PRIOR TO ORDERING OR CUTTING CONDUCTORS.

7. ELECTRICAL CONTRACTOR SHALL COORDINATE WORK W/ ARCHITECTURAL DRAWINGS &

REPORT ANY DISCREPANCIES TO ARCHITECT/ENGINEER IMMEDIATELY.

8. UNLESS OTHERWISE NOTED, BRANCH CIRCUIT CONDUCTORS & EQUIPMENT GROUNDING

CONDUCTORS SHALL BE COPPER, THWN-2, SIZED PER BRANCH CIRCUIT SIZING TABLE, THIS

SHEET.

9. ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED & BONDED PER THE NEC. ISOLATED

GROUND RECEPTACLES SHALL HAVE SEPARATE GROUND CONDUCTOR OF EQUIVALENT

SIZE.

10. ELECTRICAL CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS TO OWNER-PROVIDED

EQUIPMENT.

11. ALL J-BOXES SHALL BE ACCESSIBLE FOR FUTURE SERVICE PER NEC.

12. CONDUITS SHALL NOT BE ROUTED EXPOSED IN FINISHED AREAS UNLESS NOTED.

13. ALL INTERIOR CONDUIT SHALL BE EMT OR RGSC.

14. EQUIPMENT OR MATERIAL SUBSTITUTED AS APPROVED EQUAL TO THAT SHOWN ON PLANS

& SPECIFIED SHALL BE COMPATIBLE IN ALL RESPECTS. ANY CHANGES OR MODIFICATIONS

REQUIRED TO ACCOMMODATE THE SUBSTITUTED ITEMS SHALL BE MADE BY THE

CONTRACTOR WITH APPROVAL FROM & AT NO EXTRA COST TO THE OWNER.

15. MOUNTING HEIGHTS FOR ALL OUTLETS, SWITCHES & CONTROLS SHALL BE IN COMPLIANCE

W/ TEXAS ACCESSIBILITY STANDARDS.

16. ELECTRICAL CONTRACTOR SHALL PROVIDE ROUGH-IN & POWER FOR OTHER TRADES,

INCLUDING DATA SYSTEMS, TELEPHONE SYSTEMS, SECURITY SYSTEMS. REFER TO E4 & E8

SERIES FOR ADDITIONAL INFORMATION.

17. ALL PANELBOARDS NOT LOCATED IN MECHANICAL OR ELECTRICAL EQUIPMENT ROOMS

SHALL BE FLUSH MOUNTED, UNLESS NOTED OTHERWISE. FROM FLUSH MOUNTED PANELS,

PROVIDE AT LEAST ONE 3/4" CONDUIT TO ABOVE ACCESSIBLE CEILING FOR EACH THREE

POLES WITHOUT WIRE CONNECTED.

16. ALL 15A AND 20A RECEPTACLES IN RESTROOMS, OUTDOORS OR WITHIN 6' OR AN OUTSIDE

DOOR, WITHIN 6 FEET OF THE OUTSIDE EDGE OF SINK(S); OR SERVING WATER

DISPENSERS, KITCHEN EQUIPMENT OR LAUNDRY EQUIPMENT; SHALL BE GFI PROTECTED.

SEE NEC AND LOCAL CODES FOR SIMILAR REQUIREMENTS. THESE REQUIREMENTS APPLY

WHETHER OR NOT RECEPTACLES ARE MARKED AS GFI RECEPTACLES ON THE POWER

PLAN. THE GFI PROTECTIVE DEVICE MUST BE READILY ACCESSIBLE FOR TESTING, EITHER

AT THE RECEPTACLE ITSELF OR IN A CLEARLY IDENTIFIED OUTLET BOX NEARBY.

17. ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE THE ROUGH-IN W/ ALL OTHER

TRADES & SUBCONTRACTORS FOR THE EXACT MOUNTING HEIGHT REQUIREMENTS. NOTIFY

THE OWNER/ENGINEER OF ANY CONFLICT PRIOR TO ROUGH-IN.

18. CONTRACTOR SHALL COORDINATE W/ THE OWNER FOR THE REMOVAL OF OWNER'S

MATERIALS IN THE WORK AREA.

19. ALL OCCUPIED WORK AREAS SHALL BE LEFT IN A WIPED-CLEAN CONDITION EACH TIME THE

CONTRACTOR LEAVES THE WORK AREA.

20. CONTRACTOR SHALL USE A DUST COLLECTING VACUUM DURING ANY DRILLING OR

HAMMER-DRILLING TO HELP MAINTAIN A CLEAN WORK ENVIRONMENT. COORDINATE W/

OWNER FOR APPROPRIATE TIMES FOR DRILLING.

21. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL DEVICES REQUIRED TO MEET

CODE REQUIREMENTS WHETHER SHOWN OR NOT.

22. ALL WORK SHALL COMPLY WITH APPLICABLE LOCAL, STATE AND FEDERAL CODES AND

ORDINANCES. FOLLOW RECOMMENDED PRACTICES AS DEFINED BY ASME, SMACNA,

ASHRAE, NFPA, APPLICABLE BUILDING CODES, APPLICABLE ELECTRICAL CODE, NATIONAL

ELECTRICAL CODE, AGAG, ADA AND OSHA.

23. UPDATE LABELING OF RACEWAYS, SWITCHES, PANELS AND PANEL DIRECTORIES

TO REFLECT CHANGES.

1/2

MOTOR CONNECTION, NUMBER IN CIRCLE

INDICATES HORSEPOWER

RELAY WITH POWER SUPPLY

RELAY WITHOUT POWER SUPPLY

NOT ALL LEGEND SYMBOLS SHOWN

MAYBE APPLICABLE TO THIS PROJECT

CIRCUIT BREAKER

NORMALLY OPEN (NO) CONTACT

NORMALLY CLOSED (NC) CONTACT

SINGLE POLE SINGLE THROW (SPST) SWITCH

SINGLE POLE DOUBLE THROW (SPDT) SWITCH

HAND - OFF - AUTO (HOA) SELECTOR SWITCH

GROUNDING ELECTRODE

ONE-LINE WIRING LEGEND

TRANSFORMER

1. FIELD VERIFY ALL EXISTING CONDITIONS, INCLUDING EQUIPMENT & UTILITY SERVICES

LOCATIONS, PRIOR TO START OF ANY WORK. VISIT JOB SITE PRIOR TO BIDDING TO VERIFY

EXISTING CONDITIONS. NOTIFY GC & ENGINEER IMMEDIATELY IF ANY DISCREPANCIES ARE

FOUND.

2. PERFORM ALL WORK & DISPOSALS/RECYCLING IN COMPLIANCE WITH APPLICABLE FEDERAL,

STATE & LOCAL LAWS, CODES & ORDINANCES.

3. KEEP THE CONSTRUCTION AREA CLEAN AT ALL TIMES. RESTORE ANY WORK SPACE TO

WIPED-CLEAN STATUS BEFORE SCHEDULED OCCUPANCY BY OWNER.

4. COORDINATE WITH APPROPRIATE TRADES TO DISCONNECT RELATED SERVICES BEFORE

DEMOLITION OF ANY ITEM.CLOSE & TAG OUT WATER & GAS VALVES. TAG & LOCK OUT

ELECTRICAL POWER. DISABLE & DOCUMENT STATUS OF FIRE ALARM, SECURITY & CONTROL

POINTS.

5. COORDINATE WITH OTHER TRADES TO PERFORM DEMOLITION WORK IN THE PROPER TIME

FRAME.

6. WHERE PIPING OR CONDUIT IS REMOVED, REMOVE ALL ANCILLARY SUPPORTS, VALVES,

DEVICES & CONNECTORS NOT TO BE REUSED.

7. CAP & SEAL ANY PIPE/CONDUIT TO REMAIN & LEFT OPEN-ENDED BY DEMOLITION.

8. PRIOR TO START OF WORK, OBTAIN ANY AVAILABLE ASBESTOS SURVEYS FROM THE OWNER.

DO NOT PROCEED WITH ANY WORK THAT MAY DISTURB ASBESTOS UNTIL ANY & ALL

REQUIRED ABATEMENT HAS BEEN COMPLETED.

9. PRIOR TO DEMOLITION, BAS CONTRACTOR SHALL DECOMMISSION, DISCONNECT & REMOVE

ALL REQUIRED CONTROL ITEMS BEFORE DEMOLITION STARTS. OTHERWISE THE PRIME

CONTRACTOR WILL BE FINANCIALLY RESPONSIBLE FOR THE REPAIR/REPLACEMENT OF THE

DAMAGED OR LOST CONTROL ITEMS.

10. DISPOSE OF WATER DRAINED FROM ANY EXISTING CHEMICALLY TREATED SYSTEMS &

WATER USED IN FLUSHING &/OR PASSIVATION OF ANY NEW PIPING SYSTEM PER CODE.

11. UPDATE LABELING OF RACEWAYS, SWITCHES, PANELS AND PANEL DIRECTORIES

TO REFLECT CHANGES.

GENERAL DEMOLITION NOTES:

BID PACKAGES AND ALTERNATES

[BB] BASE BID; ALL THREE VFDs WITH ALL INDICATED AND IMPLIED

WORK.

[D1] DEDUCTIVE ALTERNATE #1; BASE BID, EXCLUDING

REPLACEMENT OF MCC-62, NEW VFD-833, NEW AC-833 AND

RELATED WORK.

[D2] DEDUCTIVE ALTERNATE #2; BASE BID, EXCLUDING

RENOVATION OF MCC-61, NEW VFDs 831 & 832, NEW ACs 831 &

832 AND RELATED WORK.

ALTERNATES ARE INDEPENDENT OF EACH OTHER. PROJECT COULD

INCLUDE ONE, TWO OR THREE VFDs:

[BB] = ALL 3 VFDs

[BB] + [D1] = VFDs 831 & 832 (NO WORK AT MCC-62)

[BB] + [D2] = VFD 833 (NO WORK AT MCC-61)

PROVIDE SEPARATE PRICE FOR HVAC AND RELATED ELECTRICAL

WORK IN EACH BID CONFIGURATION.

CONTRACTOR SHALL VERIFY EXISTING

CONDITIONS AND DIMENSIONS ON SITE

PRIOR TO BIDDING.

N:\T18\T1818 - Laredo Loanstar VFD - PFC\2D - Design Phase\CAD\MEP\E1.1.dwg, E1.1, 2/14/2019 10:20:27 AM, Thomas, AutoCAD PDF (General Documentation).pc3

02/14/2019

Page 3: TEESI · degrees celsius degrees fahrenheit dat ddc det dia dis dn do dp dps dpt dsp dx °c °f galvanize ground green grounding electrode conductor galv grd grn gec pounds local

E1.2

OV

ER

AL

L S

IT

E P

LA

N

OVERALL VIEW

TEESIENGINEERING

AUSTIN PH. (512) 328-2533LAREDO PH. (956) 724-1600

www.teesi.com

#B-325, AUSTIN, TEXAS 787461301 S. CPTL. OF TX. HWY.

TBPE #F-3502

CIT

Y O

F L

AR

ED

O

HIG

H S

ER

VIC

E P

UM

P V

FD

A

ND

P

OW

ER

F

AC

TO

R C

OR

RE

CT

IO

N

JE

FF

ER

SO

N S

TR

EE

T W

AT

ER

T

RE

AT

ME

NT

P

LA

NT

25

19

JE

FF

ER

SO

N S

TR

EE

T.

LA

RE

DO

, T

X 7

80

40

RE: 2/E1.2MCC-12

MCC-61

MCC-62

SW

GR

-5, 6

HSP-833

HSP-833

HSP-833

BWP-471

BWP-472

VALVE

VALVE

VALVE

MANHOLE

1102 (E)

MANHOLE

1099 (E)

EAST HIGH SERVICE PUMP AREA

REF: E3.1, E4.1

ROUTE OF [FR2]. SEE KEYED

NOTE [26] ON SHEET E4.1

ROUTE OF [FR3] (3 THUS).

SEE KEYED NOTE [26]

ON SHEET E4.1

MC

C-41

MCC-41PF

CONTRACTOR SHALL VERIFY EXISTING

CONDITIONS AND DIMENSIONS ON SITE

PRIOR TO BIDDING.

TYPICAL EXISTING

UNDERGROUND

DUCTBANK.

N:\T18\T1818 - Laredo Loanstar VFD - PFC\2D - Design Phase\CAD\MEP\E1.2.dwg, E1.2, 2/14/2019 10:20:31 AM, Thomas, AutoCAD PDF (General Documentation).pc3

02/14/2019

Page 4: TEESI · degrees celsius degrees fahrenheit dat ddc det dia dis dn do dp dps dpt dsp dx °c °f galvanize ground green grounding electrode conductor galv grd grn gec pounds local

E2.1

EL

EC

TR

IC

AL

S

CH

ED

UL

ES

A

ND

D

ET

AIL

(U

CR

M 1

&

2

)

TEESIENGINEERING

AUSTIN PH. (512) 328-2533LAREDO PH. (956) 724-1600

www.teesi.com

#B-325, AUSTIN, TEXAS 787461301 S. CPTL. OF TX. HWY.

TBPE #F-3502

CIT

Y O

F L

AR

ED

O

HIG

H S

ER

VIC

E P

UM

P V

FD

A

ND

P

OW

ER

F

AC

TO

R C

OR

RE

CT

IO

N

JE

FF

ER

SO

N S

TR

EE

T W

AT

ER

T

RE

AT

ME

NT

P

LA

NT

25

19

JE

FF

ER

SO

N S

TR

EE

T.

LA

RE

DO

, T

X 7

80

40

VARIABLE FREQUENCY DRIVE SCHEDULE

MARK

VFD-831

VFD-832

VFD-832

GENERAL NOTES FOR VFD SCHEDULE:

G1

G2

G3

G4

G5

G6

G7

G8

G9

G10

G11

G12

G13

G14

VFD SCHEDULE FOOTNOTES:

1

IN THIS PROJECT, VARIABLE FREQUENCY DRIVE (VFD) MEANS THE SAME AS VARIABLE SPEED DRIVE (VSD).

PROVIDE SCHEDULED MODEL OR APPROVED EQUAL BY ABB OR YASKAWA. REFER TO DIVISION 1 OF SPECIFICATIONS FOR PRODUCT

SUBSTITUTION LIMITATIONS AND PROCEDURES. ANY DEVIATION FROM THE SCHEDULED PRODUCT IN DIMENSIONAL, THERMAL,

ELECTRICAL, ACCESS OR OTHER REQUIREMENTS MUST BE DECLARED AND RESOLVED AT THE CONTRACTOR'S EXPENSE BEFORE

PRODUCT SUBMITTAL CAN BE ACCEPTED.

PROVIDE UNIT RATED FOR CONTINUOUS OPERATION AT SCHEDULED HORSEPOWER AND AMBIENT TEMPERATURE.

UNLESS OTHERWISE NOTED, DRIVE SHALL BE FOR VARIABLE TORQUE APPLICATIONS.

EQUIP DRIVE WITH INTERNAL SAFETIES TO PREVENT DAMAGE FROM LOAD DISCONNECTION, WINDMILLING, OVERLOAD, UNDER- OR

OVER-VOLTAGE, PHASE LOSS OR REVERSAL, OR UL 1449 "CATEGORY A" SURGE.

EQUIP DRIVE WITH INTERFACE FOR USER'S NETWORK CONNECTION. DRIVE OUTPUTS MUST INCLUDE AT LEAST OUTPUT FREQUENCY

(HZ OR % OF MOTOR NAMEPLATE HZ), OUTPUT POWER (KW), OUTPUT CURRENT (AMPS), OPERATIONAL STATUS AND FAULTS.

INPUTS MUST INCLUDE AT LEAST FREQ. SETPOINT (HZ OR % OF MOTOR NAMEPLATE HZ), AND ENABLE/DISABLE.

PROVIDE WITH HARDWIRED EMERGENCY SHUTDOWN CIRCUIT THAT RESULTS IN SHUTDOWN UPON LOSS OF CONTINUITY.

PROVIDE START-UP BY FACTORY-CERTIFIED TECHNICIAN. SUBMIT TECH'S SIGNED REPORT.

PROVIDE TRAINING BY FACTORY-CERTIFIED INSTRUCTOR. OWNER SHALL HAVE THE OPTION OF VIDEOTAPING THE TRAINING.

REFER TO SPECIFICATIONS DIVISION 26 FOR ADDITIONAL VFD SPECIFICATIONS, INCLUDING CONTROL SEQUENCE.

PROVIDE WITH ON-BOARD PID LOOP FOR USER-PROGRAMMED CONTROL FROM LOCAL HEADER PRESSURE SENSOR. SEE SPECIFICATIONS

FOR OTHER REQUIRED CONTROL CAPABILITIES.

BEFORE ORDERING, FIELD-VERIFY THAT ALL NECESSARY CONDUITS WILL BE ABLE TO CONNECT TO EACH VFD WHERE AND AS REQUIRED.

REFER TO ALTERNATE BID DESCRIPTIONS. SOME VFD'S MAY BE INVOLVED IN DEDUCTIVE ALTERNATES.

VFD MUST FIT IN THE AVAILABLE FOOTPRINT AND MUST BE SUITABLE FOR INSTALLATION AND SERVICE WITHIN A PAD-TO-CEILING HEIGHT

LIMIT OF 126".

PROVIDE WITH NEAR-SINE-WAVE OUTPUT SUITABLE FOR USE WITH MOTOR NOT LABELED FOR USE ON INVERTER DRIVE.

SERVES

PUMP HSP-831

PUMP HSP-833

PUMP HSP-833

HP

600

600

600

MOTOR

FLA

131.0

131.0

131.0

V/Ph/Hz

2300/3/60

2300/3/60

2300/3/60

POLES

6

6

6

SW

200

200

200

INPUT (AMPS)

FU

175

175

175

KAIC

22

22

22

FLA

132

132

132

RECT.

STEPS

18

18

18

NEMA

ENCL.

1

1

1

MAX AMB TEMP

°C

50

50

50

°F

122

122

122

MAX LOSS

(BTUH)

78,000

78,000

78,000

MAKE & SERIES

YASKAWA MV1000

YASKAWA MV1000

YASKAWA MV1000

FOOT-

NOTES

1

1

1

PANEL PP-611VOLTS:

SYSTEM:

MAIN TYPE:

MAIN RATING:

UL KAIC:

FED FROM:

CKT.

NO.

1

3

5

7

9

11

13

15

17

19

21

23

2

4

6

8

10

12

14

16

18

20

22

24

FOOTNOTES FOR THIS PANEL:

[F1]

[F2][F3]

[F4]

[xx]

BRANCH

CB

TM

---

---

TM

---

---

TM

---

---

TM------

TM------TM------TM---TM---TM---

[F2]

DETERMINE ACTUAL CB PLACEMENTS AND CIRCUIT NUMBERS ON

SITE.

REPLACE EXISTING 60A/3P MCB WITH NEW 90A/3P MCB.REPLACE EXISTING 50A/3P MCB IN ADJACENT PANEL LP-611 WITH NEW 45A/3P MCB TO PROTECT SECONDARY OF T.LP6111.FEED CPT PROVIDED IN VFD BY MANUFACTURER.

FOR ABBREVIATIONS AND OTHER BRACKETED NOTES, SEE

"ABBREVIATIONS AND NOTES FOR PANELBOARD SCHEDULES"

480

3

TM CB

9014

45 KVA XFMR IN MCC-61

AMPS

15

3P

3P

15

3P

3P

30

3P

3P

203P3P

153P3P203P3P152P152P152P

903P

3P

90

n.CB

L-L

PH

AMPS

WIRE SIZES

PH

12

12

12

12

12

12

10

10

10

121212

121212121212121212121212

2

2

2

115

WSA

277

4

NEU

---

12

12

12

2

L-N

WIRE

[F2]

EGC

12

12

10

12

12

12

12

12

12

6

(EXISTING)

MAKE:

STYLE:

MOUNT:

SPACE LIMITS:

BUSSES:

ENCLOSURE:

MIN.

CNDT

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1/2"

1-1/4"

LOAD SERVED

ACU-WEST

---

---

ACU-EAST

---

---

PANEL LP-6111

--

--

PACU-833------

PACU-831------PACU-832------VFD-831 FAN & CTRL---VFD-832 FAN & CTRL---VFD-833 FAN & CTRL---

PANEL PP-611

--

--

VIA T.LP-6111

15 kVA

Existing

Ltg+Appl

Surface

Existing

Existing

NEMA 1

MCA=

MOCP=

MCA=

MOCP=

MCA=MOCP=

MCA=MOCP=

MCA=MOCP=

[F1]

NOTE

11

15

11

15

[F3]12.5

20

1115

12.520

[F4]

[F4]

[F4]

89%

L.F.

AMPS

NEC

11.0

11.0

11.0

11.0

11.0

11.0

21.7

21.7

21.7

12.5 12.5 12.5

11.0 11.0 11.0 12.5 12.5 12.5 3.6 3.6 3.6 3.6 3.6 3.6

80.1

80.1

80.1

1.2

S.F.

PH

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

A

B

C

ABBREVIATIONS AND NOTES FOR PANELBOARD SCHEDULES:

CB

CNDT

EGC

NEU

PH

TM

TMST

ET

SS

IL

GFI

GFE

SW/F

FR/TR

HPOU

HPIU

GEC

XBS

G1

G2

G3

G4

ABREVIATIONSCIRCUIT BREAKER

CONDUIT

EQUIPMENT GROUNDING CONDUCTOR

NEUTRAL

PHASE

THERMAL-MAGNETIC

THERMAL-MAGNETIC WITH SHUNT TRIP

ELECTRONIC TRIP

SOLID STATE

CURRENT LIMITING

GROUND FAULT INTERRUPTER (5 mA)

GROUND FAULT EQUIPMENT PROTECTION (1/2 NOM. RATING, 0.2 SEC. UON)

SWITCH/FUSE

FRAME/TRIP

HEAT PUMP OUTDOOR UNIT

HEAT PUMP INDOOR UNIT

GROUNDING ELECTRODE CONDUCTOR

AUXILIARY BUS SECTION

GENERAL NOTES

WIRE SIZES ARE EXPRESSED IN AWG UP TO 4/0 AND IN KCM FOR LARGER

CONDUCTORS. SIZES SHOWN ARE MINIMUM, AND MUST BE INCREASED

FOR TEMPERATURE DERATING AND VOLTAGE DROP. SEE VOLTAGE

DROP CORRECTION TABLE ON SHEET E1.1 FOR CIRCUITS BELOW 400 A.

CONFIRM CIRCUIT CHARACTERISTICS WITH EQUIPMENT SUPPLIERS

BEFORE ORDERING IF POSSIBLE. COORDINATE WITH ENGINEER TO

RESOLVE CIRCUIT, WIRE, RECEPTACLE AND LOAD DISCREPANCIES.

LABEL EACH DISCONNECT SWITCH WITH THE NAME OF THE EQUIPMENT

AND THE CIRCUIT NUMBER.

LABEL THE FACE OF EACH RECEPTACLE OUTLET COVER PLATE AND THE

INSIDE OF EACH SWITCH COVER PLATE WITH THE CIRCUIT NUMBER(S).

(E)

(N)

(R)

(X)

EXISTING

NEW

RENOVATE

REMOVE

MCC-62 SUMMARYSECT

1(X)

2(X)

3(X)

4(X)

1(N)

GENERAL NOTES

G1

G2

FOOTNOTES

(E) = EXISTING

[1]

CONTENT

MAIN

AUX. BUSS SECT.

ISLOATION SW.

RVSS STARTER

ISO. SW W/ FUSES &

CONTACTOR

EXISTING 2400V/3PH/1200A SWITCHBOARD IS A SQUARE D

PRODUCT. REPLACE WITH PRODUCT HAVING DIMENSIONS THAT

FIT. LAYOUT IS BASED ON GE LIMITAMP MCC.

REFER TO "MISC. EQUIP. SCHED." THIS SHEET AND MV MOTOR

CONTROLLER SPECIFICATION.

SEE ALSO SPECIFICATIONS FOR MV MCC.

(N) = NEW

WORK

REMOVE SECTION

REMOVE SECTION

REMOVE SECTION

REMOVE SECTION

FEED VFD-833

(X) = DEMO

NOTES

[1]

MISCELANEOUS ELEC. EQUIPMENT SCHEDULEMARK

T.611 (N)

IN MCC-61

IS831 &

IS832

IN MCC-61

MCC-62

1

2

DESCRIPTION

TRANSFORMER: 75 KVA DRY TYPE, 3 PH, 2400-480/277, IN NEW SWGR

SECTION; DIMENSIONS ~ 40"W x 31"D x 90"H. REPLACE EXISTING 45 KVA

TRANSFORMER IN MCC-61 (GE LIMITAMP). PROVIDE DRIVE ISOLATION

STYLE TRANSFORMER. MATCH EXISTING T.611 EXCEPT FOR KVA RATING.

DISCONNECT, REPLACE SECTION AND RECONNECT.

NEW 2400V/3PH SWITCHGEAR SECTION COMPOSED OF TWO-HIGH 400A

BOLTED PRESSURE SWITCHES W/ 200A E-RATED FUSES,

AND VACUUM CONTACTORS, EACH SUITABLE FOR FEEDING A VFD.

CONNECT INPUTS BY BUS TO MCC-61. RE:NOTES [23] & [24] ON E4.1.

SIMILAR TO IS832, BUT MOUNTED IN LOWER HALF OF SECTION WITH

VOLT AND AMP METERS IN UPPER HALF. CONFIGURE AND PROVIDE

ACCESSORIES TO MAKE SECTION SUITABLE AS BUILDING DISCON-

NECTING MEANS PER NEC 225.51. RE: NOTES [21], [23] & [24] ON E4.1.

FOOTNOTES:

PROVIDE SIGNAGE AT EACH BUILDING DISONNECTING MEANS (MCC-51, MCC-61 &

MCC-62) IDENTIFYING LOCATIONS OF ALL BUILDING DISCONNECTING MEANS.

REFER TO NEC 225.52 F.

REFER ALSO TO SPECIFICATIONS SECTION 261839.

FOOTNOTES

2

1,2

MISCELANEOUS FEEDER SCHEDULEFDR

MARK

[F1]

[F2]

[F3]

[F4]

GENERAL NOTES

G1

G2

G3

FOOTNOTES

(E) = EXISTING

[1]

VOLT

CLASS

5 KV

5 KV

5 KV

5 KV

VERIFY ALL EXISTING FEEDER DATA ON SITE. DATA IS TAKEN FROM RECORDS OF UNCERTAIN

RELIABILITY.

REUSE EXISTING BURIED CONDUIT AND EXISTING RGSC COUNDUIT FOR NEW WIRING. ANY NEW

CONDUIT REQUIRED SHALL BE RGSC.

REMOVE DEMO'D WIRING AND RELATED EXPOSED CONDUIT. CAP OR PLUG BURIED CONDUIT THAT

SO THAT IT IS NOT AN OBSTRUCTION TO NEW WORK.

SHIELDED MV CONDUCTORS (IN RGSC WHERE NEW NEW CONDUIT IS REQUIRED)

FOR ABBREVIATIONS AND GENERAL RELATED NOTES, SEE

"ABBREVIATIONS AND NOTES FOR PANELBOARD SCHEDULES"

NOM.

AMPS

630

280

240

55

(N) = NEW

PARA'L

SETS

2

1

1

1

CONDUCTOR SIZES

A

250

4/0

3/0

8

(X) = DEMO

B

250

4/0

3/0

8

C

250

4/0

3/0

8

NEU GR

2

4

3

8

MIN.

CNDT

3"

3"

LOAD SERVED

MCC-61

MCC-62

600 HP PUMP OR VFD

150 KVAR PFCC

FOOT-

NOTES

(E)

(E)

(E),(N),[1]

(X)

POWER FACTOR CORRECTION CAPACITOR SCHEDULE

EQUIPMENT

DIRECT REPLACEMENTS (IN STARTERS OR AT PUMPS)

HSP-821

HSP-822

HSP-823

HSP-831

HSP-832

HSP-833

RWP-041

RWP-044

ADDITIONS IN STARTERS

RWP-042

RWP-043

GENERAL NOTES

G1

G2

G3

G4

G5

FOOTNOTES:

1

2

3

4

5

6

UNLESS OTHERWISE NOTED, PROVIDE PFCC UNITS WITH EXTERNAL BUSHINGS AND FUSES.

VERIFY THAT EACH REPLACEMENT PFCC IS PROTECTED BY A SURGE ARRESTER ON EACH PHASE.

WHERE APPLIED TO MOTORS ON REDUCED VOLTAGE STARTERS, ENSURE THAT PFCC IS ONLY ENERGIZED AFTER MOTOR IS

CONNECTED TO FULL VOLTAGE.

IN DIRECT REPLACEMENTS, BIDS MAY ASSUME THAT ONLY THE PFCC UNIT AND FUSES ARE NEEDED. IF MISSING PARTS ARE

ENCOUNTERED, SUCH AS CONTACTOR, FUSE PROVISIONS, TERMINALS, OR SURGE ARRESTERS, POSTPONE INSTALLATION AND

SUBMIT ITEMIZED PRICING FOR CORRECTIONS TO ENGINEER AND OWNER. (OWNER MAY ELECT TO PRE-AUTHORIZE CERTAIN

IMMEDIATE REPAIRS UP TO AN AGREED COST LIMIT.)

PROVIDE INDIVIDUAL DEDUCTIVE ALTERNATE PRICE FOR EACH PFCC IN CASE FIELD CONDITIONS OR BUDGET DICTATE ITS EXCLUSION.

INCLUDE THIS FORM WITH DEDUCTIVE PRICING FILLED IN AS PART OF BID PACKAGE.

PROVIDE WITH EXTERNAL BUSHINGS AND FUSES IF SPACE ALLOWS.

THIS PFCC MAY BE PROTECTED BY MOTOR OVERLOAD PROTECTION ONLY IF SPACE IS NOT AVAILABLE

FOR EXTERNAL FUSES. FOR BIDDING, ASSUME FUSES ARE REQUIRED.

PROVIDE SURGE ARRESTER PER PHASE.

NOTE NOT USED.

REPLACE ONLY IF HSP-83x IS NOT PROVIDED WITH A VFD IN THIS PROJECT. SEE ALTERNATE BID INFORMATION ON SHEET E4.1.

DESIRED SIZE IS SCHEDULED. IF IT IS NOT AVAILABLE IN THE NEEDED CONFIGURATION, THE NEXT SMALLER SIZE AND/OR A UNIT

PROTECTED BY MOTOR OVERLOAD PROTECTION ONLY WILL BE ACCEPTABLE.

HP

600

600

600

600

600

600

300

300

150

200

VOLTS

2300

2300

2300

2300

2300

2300

2300

2300

2300

2300

PH.

3

3

3

3

3

3

3

3

3

3

HZ.

60

60

60

60

60

60

60

60

60

60

KVAR

150

150

150

150

150

150

50

50

35

50

MCA

48.7

48.7

48.7

48.7

48.7

48.7

16.2

16.2

11.4

16.2

FUSE

50

50

50

50

50

50

20

20

15

20

LOCATION

MCC-51

MCC-51

MCC-51

AT PUMP

AT PUMP

AT PUMP

MCC-12

MCC-12

MCC-12

MCC-12

ACTION

REPLACE

REPLACE

REPLACE

REPLACE

REPLACE

REPLACE

REPLACE

REPLACE

ADD NEW

ADD NEW

[G5]

DEDUCT FOOTNOTES

2,5

2,5

2,5

2,5

2,5

1,3,6

1,3,6

MCC-61 SUMMARYSECT

1(E)

2(E)

3(E)

4(X)

5(X)

6(X)

7(X)

8(X)

4(N)

5(N)

6(N)

GENERAL NOTES

G1

G2

FOOTNOTES

(E) = EXISTING

[1]

[2]

[3]

CONTENT

IN-FEED

MAIN

BRANCH

45 KVA XFMR

ISLOATION SW.

RVAT STARTER

ISLOATION SW.

RVAT STARTER

75 KVA XFMR

HORIZ BUS BEHIND

BARRIER

2 SWs W/ FUSES &

CONTACTORS

EXISTING GE 2400V/3PH/1200A LIMITAMP MCC, WITH SECTIONS

MODIFIED, REMOVED AND ADDED PER SHT. E4.1. ALL MODIFICA-

TIONS MUST BE BY GE-APPROVED PERSONNEL.

REFER TO "MISC. EQUIP. SCHED." THIS SHEET AND MV MOTOR

CONTROLLER SPECIFICATION.

SEE ALSO SPECIFICATIONS FOR MV MCC.

NOTE NOT USED.

SECTION MAY BE FULLY ENCLOSED OR JUST AN ENCLOSED BUS. THE

SECTION'S FUNCTIONS ARE TO CONVEY POWER TO SECTION 6 AND TO

ALLOW 2.4 kV POWER AND LV CONTROL AND SIGNAL WIRING TO ACCESS

CONDUITS IN THE FLOOR BELOW THIS SECTION.

(N) = NEW

WORK

REPLACE MAIN FUSE

VERIFY FUSE

REMOVE SECTION

REMOVE SECTION

REMOVE SECTION

REMOVE SECTION

REMOVE SECTION

REPLACEMENT, SAME SIZE (44" W)

USE VACANT SPACE TO ACCESS CONDUITS

(PWR & CONTROL) TO HSP-831. (12" TO 16" W)

FEED VFDs 831, 832

(X) = DEMO

NOTES

[3]

[1]

N:\T18\T1818 - Laredo Loanstar VFD - PFC\2D - Design Phase\CAD\MEP\E2.1.dwg, E2.1, 2/14/2019 10:42:33 AM, Thomas, AutoCAD PDF (General Documentation).pc3

02/14/2019

Page 5: TEESI · degrees celsius degrees fahrenheit dat ddc det dia dis dn do dp dps dpt dsp dx °c °f galvanize ground green grounding electrode conductor galv grd grn gec pounds local

1200 A

(52-61)

1200A.

390A

[X][10]

MCC-61 (GE)

SWBD-6

30A

25A

45 KVA

60A MCB (X)

2300V

480V

480V

208V/120V

50A MCB (X)

1200 A

(52-62) [11]

PNL 611

HS

P-8

31

HS

P-8

32

HS

P-8

33

LP-6111

SS SS

MCC-62 (X)

[FR1] (E)

SS

1200A.

900A

15 KVA

T.6111

T.611 (X)

[FR2] [26]

[FR3]

[26]

[FR4]

(X)

[FR3]

[26]

[FR4]

(X)

[FR3]

[26]

(E) (X)

2400V, 3PH, 3-W

5'-1"

IS-833

(X)

RVAT-831

(X)

IS-831

(X)

RVAT-832

(X)

IS-832

(X)

RVSS-833

(X)

PCM-HS2

(XR)

IS-823RVSS-823IS-822RVSS-822IS-821RVSS-821

PCM-HS

PP-611

T.6111

LP-6111

MCC-61

MAIN

IS-T.611

MCC-62

MAIN (X)

MCC-51

MAIN

RE: E1.2

[1][3]

[3][2]

[6][8]

[9]

[10]

RE:[41]

[51]

J-BOX

T.611

(X)

[7]

RE [25]

[9]

RE [23]

[8]

[13]

[5]

[D1][D2]

(HIGH)

[12]

[4][4](RE: [6])

[12] [12]

[14]

[15]

E3.1

EL

EC

TR

IC

AL

D

EM

O

(U

CR

M 1

)

TEESIENGINEERING

AUSTIN PH. (512) 328-2533LAREDO PH. (956) 724-1600

www.teesi.com

#B-325, AUSTIN, TEXAS 787461301 S. CPTL. OF TX. HWY.

TBPE #F-3502

CIT

Y O

F L

AR

ED

O

HIG

H S

ER

VIC

E P

UM

P V

FD

A

ND

P

OW

ER

F

AC

TO

R C

OR

RE

CT

IO

N

JE

FF

ER

SO

N S

TR

EE

T W

AT

ER

T

RE

AT

ME

NT

P

LA

NT

25

19

JE

FF

ER

SO

N S

TR

EE

T.

LA

RE

DO

, T

X 7

80

40

SWBD-6

PARTIAL DEMO SINGLE LINE OF

ELECTRICAL BUILDING

DEMO: PLAN VIEW - HIGH SERVICE PUMP

GENERAL NOTES FOR THIS SHT.

1. BEFORE ANY DEMOLITION, COOPERATE WITH OWNER'S SCADA

MANAGER TO LABEL ALL CONTROL AND MONITORING WIRING

CONNECTED TO COMPONENTS TO BE DEMOLISHED OR MOVED.

OBTAIN DIRECTION FROM SCADA MANAGER FOR HANDLING

AND PROTECTION OF CONDUCTORS.

2. VERIFY CONDUIT STUB-UP LOCATIONS AND RESOLVE ANY

CONFLICT WITH NEW EQUIPMENT LOCATI0NS OR CONDUIT

ENTRY POINTS.

3. INSTALL CONTROL AND MONITORING CONDUCTORS PER

MANUFACTURER'S INSTRUCTIONS AND IN COORDINATION WITH

SCADA MANAGER.

4. EXISTING CONDUIT FROM WHICH CAPACITOR LEADS WERE

REMOVED MAY BE UTILIZED FOR CONTROL WIRING IF

PRACTICABLE.

5. UPDATE LABELING OF RACEWAYS, SWITCHES, PANELS AND

PANEL DIRECTORIES TO REFLECT CHANGES.

6. AT LEAST ONE OF THE HSP'S MUST REMAIN IN SERVICE AT ALL

TIMES. IN SUMMER PEAK DEMAND TIMES, OWNER MAY REQUIRE

THAT TWO (2) HSP'S BE AVAILABLE AND BE READY TO OPERATE

EXCEPT IN NEGOTIATED WINDOWS OF EXPECTED LOW

DEMAND.

KEYED NOTES FOR THIS SHEET

[1] DISCONNECT FEEDER CONDUCTORS FROM SWBD-6 AT MCC-62.

REMOVE CONDUIT BACK TO OVERHEAD PULLBOX. RETAIN

CONDUCTORS FOR SPLICING AND RE-USE. REMOVE MAIN

SWITCH SECTION OF MCC-62.

[2] DISCONNECT CONDUCTORS TO MOTOR OF HSP-833 FROM

MOTOR STARTER. RETAIN AND PROTECT CONDUCTORS.

REMOVE MOTOR STARTER.

[3] REMOVE ISOLATION SWITCH AND BUS TRANSITION SECTIONS.

[4] EXISTING SCADA CONDUIT RISER IN THIS AREA. RE: [6].

[5] LOCATION OF CONDUIT RISER FROM EXISTING SWBD-6 (RE: [1]

& E1.2) THAT SERVED EXISTING MCC-62 AND WILL SERVE NEW

MCC-62.

[6] EXISTING SCADA PANEL TO BE RELOCATED BY OWNER. RE: [4].

COORDINATE WORK SCHEDULE TO MINIMIZE INTERFERENCE.

[7] SUB-CONTRACT WORK ON MSB-61 TO ABB (GE NOW MERGED

WITH ABB) TO ANY EXTENT NECESSARY TO RETAIN UL LISTING.

CONTACT KEVIN BRADLEY, (281)-254-0982,

[email protected]. RE: SHT. E2.1 FOR SUMMARY OF

MCC-61 WORK.

[8] IN PREPARATION FOR WORK ON MCC-61 (RE: [7]), REMOVE

CONDUCTORS FROM MOTOR STARTERS TO MOTORS AND

POWER FACTOR CORRECTION CAPACITORS (PFCCs) OF

HSP-831 & HSP-832 (RE: E1.2). RETAIN MOTOR CONTROL AND

SENSOR CONDUCTORS. REMOVE PFCCs AT MOTORS.

[9] AS PART OF MCC-61 RENOVATION, UPGRADE TRANSFORMER

T.611 FROM 45 KVA TO 75 KVA. DISCONNECT AND

RE-CONNNECT PRIMARY AND SECONDARY FEEDERS. VERIFY

THAT PRIMARY IS PROTECTED BY 25 A FUSES.

[10] REPLACE EXISTING 390 A BOLT-IN MOTOR PROTECTION FUSE IN

MAIN SWITCH OF MCC-61 WITH NEW 400 A E-RATED FUSE.

VERIFY THAT UPSTREAM PROTECTION IN SWBD-6 IS

APPROPRIATE FOR THE FEEDER CONDUCTORS AND NOT LESS

THAN 450 A. REPORT TO DESIGN TEAM IF NOT.

[11] VERIFY THAT THE FUSES IN SWBD-6 THAT SERVES THE FEEDER

TO MCC-62 ARE RATED 400A, TYPE "E". REPORT TO DESIGN

TEAM IF NOT.

[12] MARK AND PROTECT EXISTING CONDUITS FROM STARTERS TO

HSP-831, 832 AND 833. SEE ALSO KEYED NOTE 26 ON SHT. E4.1.

[13] REMOVE EXISTING EMPTY CONDUITS DOWN TO FLOOR AND

PLUG.

[14] REMOVE EXISTING CONDUIT IN PREPARATION FOR

INSTALLATION OF VFD-831.

[15] EXISTING GROUNDING CONDUCTORS (~#

3

0

AWG BARE COPPER)

STUBBED UP ABOVE FLOOR. PRESERVE FOR GROUNDING PER

[31] ON SHT E4.1.

[16] THRU 50 REFER TO SHEET E4.1 KEYED NOTES.

SUPPLEMENTAL LEGEND

[E] EXISTING TO REMAIN. (OTHER INDICATORS FOR THIS ARE

LIGHT, SOLID LINES ON BOTH DEMO AND NEW PLANS.

[X] EXISTING TO BE REMOVED. (OTHER INDICATORS FOR

DEMOLITION ARE DASHED LINES ON THE DEMO PLAN,

SHADING ON DEMO DIAGRAM OR ITEM MISSING TOTALLY FROM

THE NEW PLAN.)

[N] NEW ITEM IN THIS PROJECT.

[XR] EXISTING TO BE RELOCATED.

[NR] NEW LOCATION FOR RELOCATED ITEM.

[FR1] FEEDER SIZE #1; SEE MISC. FEEDER SCHEDULE

[ED-X] ELECTRICAL DUCTBANK

[BB] BASE BID

[D1] DEDUCTIVE ALTERNATE BID #1 (FEWER VFD'S)

[A1] ADDITIVE ALTERNATE BID #1 (MORE HVAC UNITS)

RE: E1.2

N:\T18\T1818 - Laredo Loanstar VFD - PFC\2D - Design Phase\CAD\MEP\E3.1.dwg, E3.1, 2/14/2019 10:20:38 AM, Thomas, AutoCAD PDF (General Documentation).pc3

02/14/2019

Page 6: TEESI · degrees celsius degrees fahrenheit dat ddc det dia dis dn do dp dps dpt dsp dx °c °f galvanize ground green grounding electrode conductor galv grd grn gec pounds local

(ER)

PCM-HS2

IS-823RVSS-823IS-822RVSS-822IS-821RVSS-821

MCC-61

MAIN (E)

IS-T.611

(E)

MCC-51

MAIN

AC-832

T.611 (N)

IS-831 (N) [23]

VFD-831

(N)

AC-831AC-833

VFD-833

[42][42]

[42]

RE: [4]

[41]

[22] & [32]

[41]

[43]

[43]

RE: [6]

RE: [9]

RE: [4]

RE: [9],[29]

WP

PP-611-2 PP-611-8 PP-611-19

12.5"

IS-832 (N) [23]

VFD-832

(N)

[25]

[24]

[FR3]

[21]

[FR2]

[FR3]

[D2]

[D1]

[26.3] & [32]

[A2] [A3]

PCM-HS

PP-611

T.6111

LP-6111

(HIGH)

MCC-62

MAIN (N)

J-BOX

[24]

[24]

LP-6111-X[30]

[43]

[27]

[26.2], [32], [33]

[26.1], [32], [33]

[28]

[A1]

[31]

PP-611-18

PP-611-14

PP-611-22

207.05"

30" 18"

12.5"

4.05"20"

[31]

59.63"

21"

9.5"

60.31

"

[4], RE:[6]

62.2"50.92

"

MCC-61 (G.E.)

SWBD-6

30A

25A

75 KVA

2300V

480V

15 KVA

480V

208V/120V

45A MCB (N)

1200 A

(52-62)

PNL 611

HS

P-8

33

[FR2](E)[22]

LP-6111

90 A MCB (N)

1200 A

(52-61)

1200A M.S.

400A M.F.

(N) [10]

[FR1]

T.6111

T.611

200A

175A

VFD

833

[FR3] [26]

[29]

200A [11]

[25]

HS

P-8

31

VFD

831

200A

175A

HS

P-8

32

VFD

832

200A

175A

[FR3] (N)

[FR3] [26]

[FR3](N)

(E)

(N)

MCC-62 (N)

J-BOX[22]

2400V, 3PH, 3-W

E4.1

VF

D A

DD

IT

IO

NS

(U

CR

M 1

)

TEESIENGINEERING

AUSTIN PH. (512) 328-2533LAREDO PH. (956) 724-1600

www.teesi.com

#B-325, AUSTIN, TEXAS 787461301 S. CPTL. OF TX. HWY.

TBPE #F-3502

CIT

Y O

F L

AR

ED

O

HIG

H S

ER

VIC

E P

UM

P V

FD

A

ND

P

OW

ER

F

AC

TO

R C

OR

RE

CT

IO

N

JE

FF

ER

SO

N S

TR

EE

T W

AT

ER

T

RE

AT

ME

NT

P

LA

NT

25

19

JE

FF

ER

SO

N S

TR

EE

T.

LA

RE

DO

, T

X 7

80

40

SWBD-6

PARTIAL REVISED SINGLE LINE OF

ELECTRICAL BUILDING

PLAN VIEW - HIGH SERVICE PUMP

GENERAL NOTES FOR THIS SHT.

1. BEFORE ANY DEMOLITION, COOPERATE WITH OWNER'S SCADA

MANAGER TO LABEL ALL CONTROL AND MONITORING WIRING

CONNECTED TO COMPONENTS TO BE DEMOLISHED OR

MOVED. OBTAIN DIRECTION FROM SCADA MANAGER FOR

HANDLING AND PROTECTION OF CONDUCTORS.

2. VERIFY CONDUIT STUB-UP LOCATIONS AND RESOLVE ANY

CONFLICT WITH NEW EQUIPMENT LOCATI0NS OR CONDUIT

ENTRY POINTS.

3. INSTALL CONTROL AND MONITORING CONDUCTORS PER

MANUFACTURER'S INSTRUCTIONS AND IN COORDINATION

WITH SCADA MANAGER.

4. EXISTING CONDUIT FROM WHICH CAPACITOR LEADS WERE

REMOVED MAY BE UTILIZED FOR CONTROL WIRING IF

PRACTICABLE.

5. UPDATE LABELING OF RACEWAYS, SWITCHES, PANELS AND

PANEL DIRECTORIES TO REFLECT CHANGES.

6. REFER TO VFD SPECIFICATIONS FOR VFD CONTROL

SEQUENCE AND INTERFACE WITH OWNER'S CONTROL

SYSTEM.

7. AT LEAST ONE OF THE THREE HSP'S (831, 832 OR 833) MUST

REMAIN IN SERVICE AT ALL TIMES. IN SUMMER PEAK DEMAND

TIMES, OWNER MAY REQUIRE THAT TWO (2) HSP'S BE

AVAILABLE AND BE READY TO OPERATE EXCEPT IN

NEGOTIATED WINDOWS OF EXPECTED LOW DEMAND.

8. ALL NEW CONDUITS SHALL BE ROUTED OVERHEAD. NOTE

THAT CONDUITS CANNOT BE ROUTED OVER THE VFD COOLING

FANS OR WITHIN ABOUT 4' IN FRONT OF THEM TO ENSURE

THAT FAN COVERS CAN BE INSTALLED AND REMOVED.

KEYED NOTES FOR THIS SHEET

[1] THRU [20] REFER TO SHEET E3.1 KEYED NOTES.

[21] PROVIDE NEW MCC-62 TO SERVE VFD-833. USE FEEDER THAT

SERVED EXISTING MCC-62. SEE ALSO [33] BELOW.

[22] APPROX. LOCATION WHERE FEEDER SERVING EXISTING

MCC-62 EMERGES FROM FLOOR. EXTEND CONDUIT TO NEW

MCC-62.

[23] VFD ISOLATION SWITCH. ROUTE OUTPUT OVERHEAD TO VFD.

[24] INSTALL NEW VFD. RE: VFD SCHEDULE AND SPECIFICATION.

VFD'S ARE TALL; WORK OUT CONDUIT ROUTING AND SUPPORT

BEFORE INSTALLING VFD'S. IT WILL BE NECESSARY TO MOUNT

THE FAN ASSEMBLIES AFTER THE VFD'S ARE INDOORS AND

PERHAPS EVEN AFTER THEY ARE SET IN PLACE.

[25] RE-CONNECT EXISTING SECONDARY FEEDER TO T.611. (RE: [9]

& [28].)

[26] APPROXIMATE LOCATIONS WHERE EXISTING MOTOR FEEDER

AND CONTROL CONDUITS EXIT THROUGH FLOOR SLAB. VERIFY

THESE LOCATIONS PRECISELY BEFORE ANY DEMOLITION.

CONDUCTORS MAY BE SPLICED IF SUITABLE SPACE IS

AVAILABLE ABOVE FLOOR. EACH VFD REQUIRES 5 KV POWER

FEEDER [FR3] IN AND OUT, PLUS TWO 2" CONDUIT FOR

CONTROLS (MIN 6- #12 XHHW) PLUS 2" CONDUIT FOR ANALOG

SIGNALS (MIN 24-#16 TWISTED, SHIELDED PAIR (TSP)

INCLUDING 2-TSP FOR PRESSURE SENSORS, AND 8-TSP FOR

WINDING TEMPERATURE SENSORS). CONNECT PER VFD

MANUFACTURER'S INSTRUCTIONS, WITH OWNER INPUT. SEE

ALSO [32] & [33].

[1.1] FROM VFD-831: ROUTE THROUGH 12" WIDE SECTION

PROVIDED IN MCC-61. (RE: [28].) KEEP VOLTAGE CLASSES

SEPARATED, BY PHYSICAL BARRIERS WHERE FEASIBLE.

[1.2] FROM VFD-832: ENSURE THAT VFD WIRING

COMPARTMENT IS LOCATED ABOVE CONDUIT STUB-UP.

[1.3] FROM VFD-833: EXTEND CONDUITS TO ABOVE VFD-833

BEFORE INSTALLING THE VFD. SEE ALSO [32].

[27] EXTEND CONCRETE PAD TO 2" BEYOND FRONT OF MCC-62.

[28] INCLUDE NEW 12" WIDE SECTION IN MCC-62 WITH THRU-BUS IN

BACK AND PULL SECTION IN FRONT. FIELD VERIFY THAT

SECTION WILL SIT OVER THE CONDUITS TO HSP-831.USE PULL

SECTION FOR POWER AND CONTROL WIRING (SEPARATED BY

PHYSICAL BARRIER TO EXTENT FEASIBLE) FOR VFD-821.

[29] REPLACE EXISTING 60A/3P MAIN BREAKER IN PANEL P611 WITH

90A/3P CB [RE:29]. VERIFY THAT EXISTING CONDUCTORS ARE

LARGE ENOUGH FOR THE AMPERAGE. NOTIFY ENGINEER IF

NOT.

[30] INSTALL NEW 20A/1P BREAKER IN PANEL LP-6111.

[31] USE EXISTING GROUNDING CONDUCTORS TO GROUND

ENCLOSURES OF VFDs 1, 2 & 3 AND OF MCC-62. USE #3/0 BARE

COPPER AND GROUNDING-RATED COMPRESSION

CONNECTORS.

[32] IF EXISTING CONDUCTORS WILL NOT REACH NEW

TERMINATION POINTS, PROVIDE NEW J-BOX ON WALL OR

CEILING AND SPLICE CONDUCTORS. FOR MV CONDUCTORS,

USE ONLY SPLICING METHODS RECOMMENDED BY CABLE

MANUFACTURER AND APPROVED BY THE FACILITY ENGINEER.

[33] FOR CONTROL AND SIGNAL CONDUCTORS ROUTED THROUGH

COMPARTMENTS OR MANHOLES THAT INCLUDE 2.4 KV WIRING,

ENCLOSE THEM IN PVC COATED FLEXIBLE STEEL CONDUIT

(LFMC) GROUNDED TO THE ENCLOSURE (OR MANHOLE

GROUND). SECURE IN PLACE. (INTENT IS TO PROVIDE ADDED

CABLE PROTECTION, PERSONNEL SAFETY AND EMI

SHIELDING.)

[34] THRU [40] NOT USED.

[41] RELOCATE THERMOSTAT FOR EXISTING HVAC UNIT TO 12"

BELOW ROOF SLAB. ROUTE WIRING IN EMT.

[42] PROVIDE NEW HVAC UNIT AS SCHEDULED. PROVIDE OPENING

IN CMU WALL. SUPPORT, ANCHOR AND WEATHERPROOF PER

MANUFACTURER'S INSTRUCTIONS AND GOOD PRACTICE.

ELEVATE EQUIPMENT SO THAT TOP OF AIR DISCHARGE IS

APPROXIMATELY 16" TO 32" BELOW BOTTOM OF ROOF DECK,

AS DIRECTED BY ENGINEER AND/OR OWNER SO THAT AIR

DISCHARGE IS ABOVE TOP OF EQUIPMENT. PROVIDE 4"X4"X1/4"

GALVANIZED ANGLE AS HEADER FOR MASONRY OPENING.

GROUT ANGLE INTO MASONRY JOINT TO AT LEAST 12" BEYOND

OPENING EACH SIDE. INSTALL WITH VERTICAL FLANGE UP AND

ON INSIDE. ADJUST DISCHARGE LOUVERS FOR WIDE

DISTRIBUTION.

[43] PROVIDE REMOTE THERMOSTAT 12" BELOW ROOF SLAB. SET

ALL THERMOSTATS AT TEMPERATURES REQUESTED BY

OWNER. ENGINEER SUGGESTS SETTING AT 1°F INTERVALS

BETWEEN 78°F AND 82°F.

[44] THRU [50] NOT USED.

SUPPLEMENTAL LEGEND

[E] EXISTING TO REMAIN. (OTHER INDICATORS FOR THIS ARE

LIGHT, SOLID LINES ON BOTH DEMO AND NEW PLANS.

[X] EXISTING TO BE REMOVED. (OTHER INDICATORS FOR

DEMOLITION ARE DASHED LINES ON THE DEMO PLAN,

SHADING ON DEMO DIAGRAM OR ITEM MISSING TOTALLY FROM

THE NEW PLAN.)

[N] NEW ITEM IN THIS PROJECT.

[XR] EXISTING TO BE RELOCATED.

[NR] NEW LOCATION FOR RELOCATED ITEM.

[FR1] FEEDER SIZE #1; SEE MISC. FEEDER SCHEDULE

[BB] BASE BID

[D1] DEDUCTIVE ALTERNATE BID #1

[A1] ADDITIVE ALTERNATE BID #1

RE: E1.2

N:\T18\T1818 - Laredo Loanstar VFD - PFC\2D - Design Phase\CAD\MEP\E4.1.dwg, E4.1, 2/14/2019 10:20:42 AM, Thomas, AutoCAD PDF (General Documentation).pc3

02/14/2019