    The expansion vessel

    When we talked about storage tanks in thermal plants we meant of course open tanks.

    Storage tanks also function as expansion vessels. The expansion tank has a dual function: thermal and

    hydraulic.

    From a thermal point of view its function is to allow water, which is an incompressible fluid, to expand or contract.

    In order for this to be possible it is necessary for the fluid to be in contact with a gas that can compensate for the

    expansions and contractions of the fluid.

    There are three possible configurations:

    open atmosphere vessel;closed vessel, containing water and air (or other inert gas) without any for of separation (self-pressurization or pressurization with air or gas that is inserted from the outside);closed vessel with a separating membrane between the water and an inert gas (nitrogen)

    The volume of the expansion vessels can be calculated by using the following expressions:

    for a vessel that is open to the atmosphere:

    for a closed vessel without a diaphragm:

    for a closed vessel with diaphragm:

    where:

    Vv= the volume of the expansion vessel (L)

    Vw= the volume of the inside the plant (L)

    v1 = the specific volume of the cold water at a lowest temperature t1 (m3 / kg)

    v2 = the specific volume of the water at the highest temperature t2 (m3 / kg)

    = the coefficient of the expansion of metals (see table)

    - per steel = 1,2 . 10-5 (1/K)

    - per copper = 1,65 10-5 (1/K)

    http://www.tempcoblog.com/3432/the-expansion-vessel/http://it.wikipedia.org/wiki/Vaso_di_espansionehttp://www.tempcoblog.com/?p=1558http://www.tempcoblog.com/3432/the-expansion-vessel/
  • 7/27/2019 The Expansion Vessel _ Tempco Blog

    2/10

    8/20/13 The expansion vessel : Tempco Blog

    www.tempcoblog.com/3432/the-expansion-vessel/?doing_wp_cron=1376980215.5700790882110595703125 2/10

    t= t2 t1(C)

    Pa = absolute atmospheric pressure (bar)

    Pi= initial absolute pressure at the lowest temperature t1 (bar)

    Pf= absolute pressure while functioning at the highest temperature t2 (bar)

    The expression:

    Vw[(v2/v1) 1] 3 t(L)

    represents the volume variation.

    In hot water systems the reference temperatures are predominantly:

    t1 = the temperature during filling, 10 C

    t2= the waters maximum flow temperature 85 : 90 C

    In superheated water systems the temperature t2 can reach up to 130 C and beyond.

    Instead in cooling water circuits:

    t1 = the maximum water temperature that can be reached when the system is not functioning, 35C;

    t2 = the minimum functioning temperature, 7C, for example.

    The waters specific volumes are shown in the following table.

    http://www.tempcoblog.it/wp-content/uploads/2009/09/tabella-massa-volumica3.JPG
  • 7/27/2019 The Expansion Vessel _ Tempco Blog

    3/10

    8/20/13 The expansion vessel : Tempco Blog

    www.tempcoblog.com/3432/the-expansion-vessel/?doing_wp_cron=1376980215.5700790882110595703125 3/10

    From a hydraulic point of view the expansion tank determines and sets the systems pressure reference. At the

    point in which the vessel is inserted in the circuit, the pressure is equal to the vessels air pressure which is

    increased or decreased by the liquid located above or below.

    Pressure values at the insertion point of different types of expansion vessels.

    Open expansion vessel

    As can be see by its expression, the vessels capacity must be at least twice the waters expansion volume in

    order to prevent water from leaking due to possible overflow during the heating phase and is fed back into the

    vessel again during the cooling phase. The illustration shows the accessories that the vessel must be equipped

    with.

    Open expansion vessel

    The vessel and the safety tubes must be protected from freezing temperatures. As far as systems using many

    boilers is concerned it is good practice to provide each with its own boiler expansion vessel, thus making it

    possible to eliminate one or more boilers.

  • 7/27/2019 The Expansion Vessel _ Tempco Blog

    4/10

    8/20/13 The expansion vessel : Tempco Blog

    www.tempcoblog.com/3432/the-expansion-vessel/?doing_wp_cron=1376980215.5700790882110595703125 4/10

    Expansion vessels for three specific generators.

    The hot water heating systems that use open expansion vessels, with a functioning pressure that does not exceed

    5 bar, should be provided with:

    - a safety pipe between the vessel and the generator that has a diameter equal to its virtual length and to the

    generators thermal power (see; Safety standards for appliances containing hot liquids under pressure);

    - automatic adjusting thermal switch;

    - automatic blocking thermal switch;

    - a thermometer with an inlay for the checking thermometer

    - a pressure gauge with flange for the checking pressure gauge.

    The illustrations below show some possible connection diagrams; the illustration of theconnection of the expansion

    tank with filler and safety pipes is typically used in the German DIN standard and the diameters of the tubes, as a

    result of this standard, can be calculated by using the following expressions:

    - in the event of overheating, the safety pipe must be able to vent any vapor produced in the boiler.

    - for the expansion or loading pipe which must enable the speedy filling of the boiler using water from the vessel.

    - where P is the power of the generator or generators expressed in kW.

  • 7/27/2019 The Expansion Vessel _ Tempco Blog

    5/10

    8/20/13 The expansion vessel : Tempco Blog

    www.tempcoblog.com/3432/the-expansion-vessel/?doing_wp_cron=1376980215.5700790882110595703125 5/10

    Connecting the open expansion vessel to a boiler.

    Connecting the expansion vessel with loading and safety tubes.

    Should there be many heat generators which run the same plant, a safety pipe that is sized for the nominal

    capacity of all the generators can be used; only the connections of each generator to the normal safety tube can

    be sized for the single power. Should it be necessary to separate the generators from the expansion vessel, the

    pipes that connect each generator to the safety pipes must be installed with three-way valves using a passage

    cross section that is not smaller than the valves on the generators security tube. This ensures the connection

    between the generator and the atmosphere either via the safety pipe or via the vent tube.

  • 7/27/2019 The Expansion Vessel _ Tempco Blog

    6/10

    8/20/13 The expansion vessel : Tempco Blog

    www.tempcoblog.com/3432/the-expansion-vessel/?doing_wp_cron=1376980215.5700790882110595703125 6/10

    Connecting two heating generators to only one safety tube.

    The vent tube must be conveyed in order to prevent it from causing to persons in case there is water discharge.

    Systems with a functioning pressure exceeding 5 bar must have a secondary automatic blocking thermal switch

    independent from the other switch. As far as the position of the circulation pump is concerned, with respect to the

    vessels circuit connection point, we should pay close attention because the circulation pumps must be installed in

    the water distribution network in a way that both physical and technical functions can be carried out. It should be

    noted, above all, that tube throttling should not be carried out on the open vessel plants two safety pipes:

    therefore, a pump, whatever type it may be, is considered a choking device and must consequently be installed in

    areas away from the connections with the vessel. Another important aspect that should be taken into

    consideration is installing the pump with respect to the boiler: suction (when sending) or under pressure (when

    returning).

    There are no safety requirements regarding this issue: the problem is solved by taking into consideration that no

    point in the network should be in depression. The piping networks, in fact, are never perfectly sealed against air,

    which can penetrate, for example, if a heating body goes into depression, through the control valves stuffing box.

    In order to verify the pressure of the piping networks critical points it is necessary to check the diagram of the

    pressures along the circuit and to check the installation instructions. Lets look at the following two examples of a

    start pump and a return pump.

    Start pump. Installation instructions and pressure diagram.

  • 7/27/2019 The Expansion Vessel _ Tempco Blog

    7/10

    8/20/13 The expansion vessel : Tempco Blog

    www.tempcoblog.com/3432/the-expansion-vessel/?doing_wp_cron=1376980215.5700790882110595703125 7/10

    Return pump. Installation instructions and pressure diagram.

    The A H static pressure prevails on the starting pump at point A, where the expansion vessel is connected. At the

    pumps exit the pressure value increases in proportion to the pumps manometric height, then as the water flows

    in the circuit, the pressure decreases to the pumps suction value. Items 1.2.3.4.5.1. are a graphical

    representation of the pressure variations along the circuit. Point 4 represents the pressure in radiator M. When the

    water circulates, the pressure is positive; however if the valve is closed the pressure in the radiator is the same

    as the return pressure, represented by point 5, whose ordinate is, however greater by than the static pressure

    HA , defined uniquely by the water level in the expansion vessel. At point 5, pressure HA + prevails.

    A closer look at the problem shows how the lowest radiator is not at risk. The highest one is in danger because the

    pressure is less than HN compared to the lower radiator. This pressures value is:

    HA + - HN = (HA HN) +

    The term (HA HN) is the difference between the vessels water height and the radiator N height. In this scenario

    too the pressure is positive.

    Lets now examine the return pump.

    The line that goes from here too represents the pressure flow between the radiator M and the pump, however it is

    placed below the line of the static pressure between the radiator M and the pump. We can also note that it is

    placed below the line of the static pressure of a value equal to the height of the manometric pump.

    The pressure in 5 is worth HA HP + . The pressure in the radiator at risk, or lets say the highest radiator, is:

    HA HP + HN = (HA HN) HP +

    In order to avoid this value from becoming negative (depression in the highest radiator) it is necessary (lets

    neglect to be on the safe side) for HA HN , or rather the level difference between the vessel and the highest

    radiator, to be greater than the pumps prevalence. In some buildings where HA HN is 3 : 5m it is quite

    probable to see a pump, which has slightly less prevalence, ensure the circuits water circulation without any form

    of depression.

    It is therefore necessary to evaluate each scenario and to appropriately position the pumps flow, whether it be

    start or return flow. The start pump ensures that no point of the network goes into depression. The possible

    disadvantages are that water at high temperatures could get into the pump and as a result there could be high

    pressure in the network.

    The illustration below gives details of the equipment required by IPESL regulations for an open vessel system.

  • 7/27/2019 The Expansion Vessel _ Tempco Blog

    8/10

    8/20/13 The expansion vessel : Tempco Blog

    www.tempcoblog.com/3432/the-expansion-vessel/?doing_wp_cron=1376980215.5700790882110595703125 8/10

    Security equipment required by ISPESL regulations open vessel.

    Closed expansion vessel

    We have already seen at the beginning of the chapter how to calculate the capacity of a closed vessel, in the

    expression which is valid for a closed vessel without the diaphragm, the absolute pressures to consider are:

    Pi= absolute initial pressure corresponding to the hydrostatic pressure at the point where the vessel is installed

    measured in bar (kg/cm2), increased by an amount determined by the designer and, however, not less than 0.15

    bar;

    Pf= maximum absolute functioning pressure, in bar, equal to the calibration pressure of the safety valve,

    increased by the excess pressure of the valve and decreased by an amount corresponding to the difference inheight between the expansion vessel and that safety valve, if the latter is placed lower or in other words increased

    if placed higher.

    A closed vessel system without a diaphragm.

    For closed vessels with a diaphragm, assuming the definition is Pf, the Pipressure to place in the the closed vessel

    with a diaphragm is:

    Pi= absolute pressure in bar to which the gas cushion is precarious, a pressure which cannot be less than the

    hydrostatic pressure at the point where the vessel is connected.

  • 7/27/2019 The Expansion Vessel _ Tempco Blog

    9/10

    8/20/13 The expansion vessel : Tempco Blog

    www.tempcoblog.com/3432/the-expansion-vessel/?doing_wp_cron=1376980215.5700790882110595703125 9/10

    Closed vessel system with diaphragm.

    The expression of vessels without a diaphragm can only be applied to self-pressurized vessels where the pressure

    prior to filling is equal to the atmospheric pressure. For pressurized vessels, for example where the pressure

    before filling is greater than the atmospheric pressure, and has a variable pressure while functioning, the formula

    to be used for testing is the same used for the closed vessel with a diaphragm, and even for vessels without a

    diaphragm, increasing the volume resulting from the calculation of a quantity equal to the initial volume of water

    contained in the cold system vessel; in which case the system designer must indicate, in addition to the pre-

    charge pressure and the total vessel volume, the volume occupied by the gas when the system is cold.

    For pre-pressurized vessels at constant pressure and variable pressure level during functioning, the tank volume

    must be calculated the same as for open vessels. For pre-pressurized vessels that have a constant level and

    pressure while functioning, the volume of the vessel must be sufficient enough to contain the excursions

    necessary for the devices needed when discharging and water re-integrating is necessary.

    In closed vessel heating systems with a power up to 350 kW and a working pressure that doesnt exceed 5 bar,

    you must have:

    - a safety valve which enables the discharge of a quantity of steam per hour (kg/h) of not less than P/0.58 (where

    P is the power of the generator in kW);- automatic thermal regulating switch;

    - automatic thermal blocking switch;

    - blocking control device;

    - thermometer with small well for the checking thermometer;

    - a pressure gauge with flange for the checking pressure gauge.

    Even with closed expansion vessels it is possible to exclude heat generators provided that the pipe connected to

    the vessels generator is installed using a three-way valve with the same open vessel characteristics. It must

    ensure the generators connection either with the expansion vessel or with the atmosphere. With closed vessel,

    circulation pump heating systems the heat input must be automatically interrupted should the pump stop

    functioning and this can be implemented with an electric burning pump or via a flow switch.

    Closed vessel pressurized systems that run on constant pressure and at a variable level must be protected by a

    fuel shut-off valve or a temperature relief valve because there is no correlation between increased temperature

    and pressure. For systems with a pressure exceeding 5 bar a second blocking thermostat must be installed which

    is independent from the first one.

    The illustration below shows the instrumentation required for closed vessel systems.

    In addition to what has already been written please note:

    - automatic filling unit which reduces the aqueducts supply pressure and reintegrates any losses of water in the

    cold state; the filling unit is made up of the pressure reducing valve, the filling valve and the restraint and filtervalve.

    - air separator with automatic vent valve and float.

    Safety and control instrumentation for a heating system with a closed vessel (the symbols used are those used by

    the regulating standards).

    1 burner

  • 7/27/2019 The Expansion Vessel _ Tempco Blog

    10/10

    8/20/13 The expansion vessel : Tempco Blog

    bl /3432/ h i l/?d i 13 698021 00 90882110 9 0312 10/10

    2 boiler3 safety valve4 fuel shut off valve;5 expansion vessel with membrane;6 automatic regulating thermal switch;7 automatic blocking switch;8 pressure control device;9 pressure indicator;10 temperature indicator;11 little well;12 accessible and visible discharge;

    13 circuit pump;14 pressure reducer;15 non-return valve;

    16 water counter (possible)