Upload
volien
View
262
Download
5
Embed Size (px)
Citation preview
International Conference on Electricity Distribution September 22, 23 and 24, 2014, Hotel Panamericano, CIDEL 2014 Buenos Aires, Argentine
Trends in electricity distribution for a sustainable future _________________________________________________________________________________________________
Full Paper Presentation
TTHHEE RRCCCC GGRROOUUNNDD FFAAUULLTT NNEEUUTTRRAALLIIZZEERR –– AA NNOOVVEELL SSMMAARRTT GGRRIIDD PPRROOTTEECCTTIIOONN
Klaus WINTER
Swedish Neutral AB, Stockholm Sweden
INTRODUCTION
In utilizing the inherent - but so far unused – zero
sequence properties of the 3-phase system, the RCC
Ground Fault Neutralizer (GFN) elevates grid
protection to new levels of performance and takes all
the benchmarks of good protection – namely speed,
selectivity and last but not least detection sensitivity.
Moreover, the GFN action is smart in the way that
voltage injection and fault current can be cancelled out
completely without interrupting the power supply – a
truly smart grid solution. Instead of feeder tripping
“fault surgery” with lots of outages, the GFN now
offers “smart medication”. The “antidote” – a current
equal but opposite to the fault current - is simply
injected into the neutral. No immediate interruption of
any power supply is required.
The GFN protects all parts of an interconnected grid –
from the power transformer over the bus bar and the
outgoing feeders down to the last corner of the grid – a
truly overall protection scheme. This overall action is
accomplished in a very cost efficient way from one
point – the neutral.
Figure 1 GFN basic approach to earth fault protection
A PARADIGM SHIFT IN PROTECTION BY
SMART NEUTRAL TREATMENT
Protection is about safety and minimizing risks to
people and property. The risk with an electrical fault is
generally described as proportional to the energy
injected into the fault site..
Figure 2 GFN benchmarks for earth fault protection
by neutral treatment
Therefor the IEC standard defines the risk to be
proportional to fault current and interception time – the
well-known I2t criteria. Everybody understands -
protection must be fast. But fault current levels
included by their square are even more decisive to
minimize consequential damages. The good news is -
both fault current and interception time can be
influenced from the neutral.
A benchmarking for different types of system
grounding and neutral treatment with respect to fault
current levels and interception time clearly proofs the
superiority of the Ground Fault Neutralizer. Even
better - almost all existing grids can be converted to
GFN grounding. This conversion offers one of most
cost efficient investments in grid performance,
improved SAIDI figures (9) and, last but not least
safety. .
International Conference on Electricity Distribution September 22, 23 and 24, 2014, Hotel Panamericano, CIDEL 2014 Buenos Aires, Argentine
Trends in electricity distribution for a sustainable future _________________________________________________________________________________________________
Full Paper Presentation
THE GFN GROUND FAULT NEUTRALIZER
The Ground Fault Neutralizer is normally connected to the
neutral of the supplying power transformer (Y-winding) or a
separate grounding transformer (Z-winding). A complete
GFN-system is composed of a modern solid core arc
suppression coil (ASC), see Figure 4, a cabinet with power
electronics for voltage/current injection (RCC - Residual
Current Compensator) and the GFN control cabinet.
Beside the controls for the RCC voltage/current injection
the GFN also provides automatic retuning for the arc
suppression coil and a new twin-scheme fault locator with
superior detection capabilities. Distance-to-fault information
can be obtained by feeder looping.
The arc suppression coil forms a parallel resonant circuit
with the phase-to-ground capacitive leakage (Co) of the
network. By this resonant circuit the source impedance for
single phase-to-ground faults increases in the order of ten to
twenty times, sufficient to quench single-phase flashover
faults on overhead lines. But it was still necessary to trip the
faulty feeder, in order to minimize the risk for fire and
personal hazards due to the remaining active current.
The GFN Ground Fault Neutralizer now provides fast and
complete compensation of all remaining earth fault currents
– both fundamental and harmonics – by injecting a 180
degree opposite current into the neutral. This is beneficial
especially in industry- and urban cable grids where almost
all faults start single phase-to-ground (cable screen). If not
properly compensated, a re-striking cable fault quickly
develops into a multi-phase or cross-country fault with
subsequent long term outages.
Figure 3 GFN adaptive zero sequence admittance scheme
Figure 4 Modern dry-type fast tuning arc suppression coils,
forming the high voltage part of the GFN system.
Also with respect to personal safety and fire prevention the
GFN offers premium protection [3]. A fault interception in
less than three cycles in praxis can never be reached by
traditional protection schemes working on breakers.
FAULT FINDING - A MATTER OF MINUTES
Even though the GFN immediately eliminates voltage
injection and fault current - independent of the location of
the fault - the actual fault site must be located for further
inspection or repair.
The integrated GFN fault locating is based on two superior
detection schemes – a very fast transient detection mainly
for re-striking cable faults and a highly sensitive adaptive
zero sequence admittance scheme to detect both low and
high impedance faults on overhead lines and cables.
International Conference on Electricity Distribution September 22, 23 and 24, 2014, Hotel Panamericano, CIDEL 2014 Buenos Aires, Argentine
Trends in electricity distribution for a sustainable future _________________________________________________________________________________________________
Full Paper Presentation
Figure 5 GFN fault interception in less than 3 cycles
In urban grids distribution feeders are normally arranged in
open rings with ring main units to provide safe power
supply. For these grids the GFN works with its well proven
distance-to-fault scheme. After closing the NOP - normally-
open-point – the fault site can be pin pointed with high
accuracy.
Figure 6 GFN Cabinet – Everything at your fingertips
Rural distributions generally have radial structures with
many lateral spurs. Earth fault locating in these grids is a
kind of difficult and often based on either time consuming
trial & error methods or overcurrent fault passing indicators
with insufficient sensitivity.
The new GFN FPI working with access to modern internet
communication technology provides a substantial
improvement. Due to its adaptive scheme, the GFN FPI can
detect much more sensitive than traditional FPI’s. This is an
important step ahead, as many of the line faults in overhead
grids are high impedance mid-span faults with poor ground
contact.
The GFN FPI can be combined with any type of
sectionalizing equipment. All fault confirmation and
sectionalizing controls are available at the central GFN
terminal, but can also be transmitted to a dispatch center or
a handheld field monitor.
GFN PD-MONITORING & CONTROL – THE
NEXT STEP IN GRID PROTECTION
The GFN Ground Fault Neutralizer, originally developed to
solve the problem with re-striking cable faults in resonant
grounded networks, offers combined with state of the art on-
line PD measurement a new powerful tool for grid
insulation monitoring and pre-fault protection. By means of
voltage/current injection into the neutral, the GFN controls
all phase-to-ground voltages and - if necessary - quickly
quenches discharge activities by lowering the voltage in the
suspected phase, thus preventing further development into a
full dielectric breakdown.
Furthermore the full control of phase-to-ground voltages
during plant operation also admits for new online PD testing
methods at levels above normal operating voltages, thus
enabling systematic fore-checking strategies for the early
detection of defective components. This is done without
affecting the power supply to end-users.
Distribution network owners and operators looking for new
and cost efficient means to monitor the condition of their
aging cable grids may benefit from this novel tool to
support their ongoing CBM activities. The GFN enhanced
monitoring works on all type of plant - rotating machines as
well as transformers, switchgears and cable feeders. The
method can also be used before, during and after
commissioning of new plant to verify the quality of
workmanship on cable joints and terminations.
International Conference on Electricity Distribution September 22, 23 and 24, 2014, Hotel Panamericano, CIDEL 2014 Buenos Aires, Argentine
Trends in electricity distribution for a sustainable future _________________________________________________________________________________________________
Full Paper Presentation
Figure 7 GFN PD monitoring and control - a novel pre-
fault protection and “Early Warning System”
CONCLUSIONS
Upgrading the traditional arc suppression coil to a full
scheme Ground Fault Neutralizer means that Waldemar
Petersen’s superior protection concept of resonance
grounding will survive the ongoing cabling in many MV
grids. (1) (2) (3) The Ground Fault Neutralizer also
provides for the first time truly fire and personal safe
operation of sustained faults (6).
As many injury files and bush fire investigations indicate,
speed is still the most essential aspect of protection. With a
total response time of less than 3 cycles (Figure 5) –
independent of the actual fault location the Ground Fault
Neutralizer is substantially faster than traditional protection
schemes (4) (6). A first Brazilian Pilot installation was
presented at the PAC World Conference in Florianopolis
/Brazil (8).
Finally, the possibility to improve already existing PD
online detection methods into true “Early Warning Systems”
adds another strong argument for GFN resonance grounding
as the superior grounding concept (5) (7). Enhanced GFN
PD online monitoring in the ageing cable grids of the large
cities in the word is considered to bring about a major step
in CBM – condition based maintenance.
___________________________
Reference list
(1) Wilheim R. and Waters M. “Neutral Grounding
in High Voltage Transmission Networks”,
Elsevier Publishing, New York 1956
(2) Winter K. “Swedish Distribution networks –
A new method for Earth-fault Protection in
Cable- and Overhead Systems” 5th International
Conference in Power System Protection, IEE
conference publication No 368, York/UK 1993
(3) Koetzold B., Gauger V. and Winter K.et al.
“Erdschluss-Vollschutzsystem mit Reststrom-
kompensation – ein Weg zur höheren Ver-
sorgungsqualität in erdschlusskompensierten
Verteilungsnetzen” ETG Fachbericht Nr 66,
ETG/PSE Summer Meeting, Berlin/Germany
1997
(4) Winter K. “The RCC Ground Fault Neutralizer –
a Novel Scheme for Fast Earth Fault Protection,
Proceedings of the 18th
Internat. Conference on
Electricity Distribution, CIRED, Turin/Italy
2005
(5) Winter K. et al “ The RCC Ground Fault
Neutralizer – a Novel Scheme for Pre- and
Post-Fault Protection”, Key note address at the
Australasian Power Engineering Conference
AUPEC, Melbourne/Victoria 2006
(6) Victorian Bushfires Royal Commission,
Powerline Bushfire Safety Taskforce, Final
Report Chapter 3.4.1. GFN Rapid Earth Fault
Current Limiter, Melbourne /Victoria 2011
(7) M. Seltzer-Grant, et al “On-line Partial
Discharge Detection on MV cable networks
with Ground Fault Neutralizer” CIRED
Stockholm/ Sweden, June 2013
(8) Mauro Silveira, et al “The RCC Ground Fault
Neutralizer – First Brazilian Pilot Installation”
PAC World Conference Latin America, Paper
No OP005, Florianopolis/Brazil, Nov 2012
(9) SHM Othman et al “The Pilot Project of a
Ground Fault Neutralizer at Sibu Sarawak”
CIRED South East Asia, Kuala Lumpur,
Malaysia, May 2014
____________________________