Contents Description Page Catalog Number Selection 3 Digitrip 310+ Electronic Trip Unit Types LGE, LGS, LGH, LGC, LGU, LGX Long Delay Response and Short Delay with Flat Response Curve (LSI, LSIG, ALSI, ALSIG) TC01207004E 5 Long Delay Response and Short Delay with I 2 t Response Curve (LS, LSG) TC01207005E 6 Ground Fault Delay Response Curve (LSG, LSIG, ALSIG) TC01207006E 7 Maintenance Mode / Instantaneous Setting (ALSI, ALSIG) TC01207014E 8 Thermal/Magnetic Trip Unit LGE, LGS, LGH, LGC, LGU, and LGX Circuit Breakers TC01208002E 9 LHH High Instantaneous Circuit Breaker TC01206004E 10 Peak Let-Through (IP) and Clearing (I 2 T) Curves LG, JG, EG, and EG CL (with Current Limiter), Molded-Case Circuit Breakers—240V TC01200001E-A 11 LG, JG CL, JG, EG, and EG CL (with Current Limiter), Molded-Case Circuit Breakers—480V TC01200001E-B 12 LG, JG CL, JG, EG, and EG CL (with Current Limiter), Molded-Case Circuit Breakers—600V TC01200001E-C 13 LGU and JGU Molded-Case Circuit Breakers—240V TC01200001E-D 14 LGU and JGU Molded-Case Circuit Breakers—480V TC01200001E-E 15 LGU and JGU Molded-Case Circuit Breakers—600V TC01200001E-F 16 LGX and JGX Molded-Case Circuit Breakers—240V TC01200001E-G 17 LGX and JGX Molded-Case Circuit Breakers—480V TC01200001E-H 18 LGX, JG CL, and JGX Molded-Case Circuit Breakers—600V TC01200001E-I 19 Peak Let-Through Currents (Ip) and Clearing (I 2 t) Summary Tables 20 Earth Leakage Module Curves UL LG Circuit Breaker Earth Leakage Module, Three- and Four-Pole, 110–480V TC01212009E 21 IEC LG Circuit Breaker Earth Leakage Module, Three- and Four-Pole, 110–480V TC01212008E 22 ote N The following curves meet the requirements of UL, T CSA, T IEC, CCC, and CE The following circuit breakers are derived from Eaton, Westinghouse, T or Cutler-Hammer T brand Series G L-Frame 100–630A, 220–690V Time Current Curves TD012019EN Effective March 2014

Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

Embed Size (px)

Citation preview

Page 1: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

ContentsDescription Page

Catalog Number Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Digitrip 310+ Electronic Trip Unit Types LGE, LGS, LGH, LGC, LGU, LGXLong Delay Response and Short Delay with Flat Response Curve

(LSI, LSIG, ALSI, ALSIG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01207004E . . . . . 5Long Delay Response and Short Delay with I2t Response Curve (LS, LSG) . . . . . . TC01207005E . . . . . 6Ground Fault Delay Response Curve (LSG, LSIG, ALSIG) . . . . . . . . . . . . . . . . . . . . . TC01207006E . . . . . 7Maintenance Mode / Instantaneous Setting (ALSI, ALSIG) . . . . . . . . . . . . . . . . . . . TC01207014E . . . . . . 8

Thermal/Magnetic Trip UnitLGE, LGS, LGH, LGC, LGU, and LGX Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . TC01208002E . . . . . 9LHH High Instantaneous Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01206004E . . . . 10

Peak Let-Through (IP) and Clearing (I2T) CurvesLG, JG, EG, and EG CL (with Current Limiter), Molded-Case

Circuit Breakers—240V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-A . . . 11LG, JG CL, JG, EG, and EG CL (with Current Limiter), Molded-Case

Circuit Breakers—480V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-B . . . 12LG, JG CL, JG, EG, and EG CL (with Current Limiter), Molded-Case

Circuit Breakers—600V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-C . . . 13LGU and JGU Molded-Case Circuit Breakers—240V . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-D . . . 14LGU and JGU Molded-Case Circuit Breakers—480V . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-E . . . 15LGU and JGU Molded-Case Circuit Breakers—600V . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-F . . . 16LGX and JGX Molded-Case Circuit Breakers—240V . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-G . . . 17LGX and JGX Molded-Case Circuit Breakers—480V . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-H . . . 18LGX, JG CL, and JGX Molded-Case Circuit Breakers—600V . . . . . . . . . . . . . . . . . TC01200001E-I . . . 19Peak Let-Through Currents (Ip) and Clearing (I2t) Summary Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Earth Leakage Module CurvesUL LG Circuit Breaker Earth Leakage Module, Three- and Four-Pole, 110–480V . . . TC01212009E . . . . 21IEC LG Circuit Breaker Earth Leakage Module, Three- and Four-Pole, 110–480V . . . TC01212008E . . . . 22

otee:N The following curves meet the requirements of UL,T CSA,T IEC, CCC, and CE . The following circuit breakers are derived from Eaton, Westinghouse,T or Cutler-HammerT brand .

Series G L-Frame100–630A, 220–690V

Time Current Curves TD012019EN Effective March 2014

Page 2: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

2

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

otee:N Unless noted below, all curves remain unchanged from their prior revision .

Revision Curve Number Page Date

Page 3: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

3

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

Catalog number SelectionThis information is presented only as an aid to understanding catalog numbers . It is not to be used to build catalog numbers for circuit breakers or trip units .

Table 1. Series G—LG-Frame (250–630A)

L G S 3 600 FA G C

Frame

L

Standard/Application

G = IEC/CE/UL/CSA

Number of Poles

3 = Three4 = Four—Neutral 0% protected6 = Four—Neutral 60% protected7 = Four—Neutral 100% protected8 = Four—Neutral 0–60% protected9 = Four—Neutral 0–100 protected

Performance

600 480 415 240

E 18 35 35 65S 25 50 50 85H 35 65 70 100C 50 100 100 200U 65 150 150 200X 65 200 200 200K Molded-case switch

Rating

Blank = 80% ratedC = 100% rated

Amperes

250300350400500600630

Terminations/Hardware

Terminals Mounting Hardware

M = Metric end capsE = Imperial end capsG = Line/load standardW = Without terminals

MetricImperialMetric

Trip Unit

AA = Adj. adj.FA = Fixed adj.KS = Molded-case switch33 = 310+ electronic LS32 = 310+ electronic LSI35 = 310+ electronic LSG36 = 310+ electronic LSIG38 = 310+ electronic ALSI39 = 310+ electronic ALSIGNN = Frame only (no trip)

Table 2. Trip Unit

Trip Unit

AA = Adj. adj., thermal-magneticFA = Fixed adj., thermal-magneticKS = Molded case switch33 = 310+ electronic LS32 = 310+ electronic LSI35 = 310+ electronic LSG36 = 310+ electronic LSIG38 = 310+ electronic ALSI39 = 310+ electronic ALSIG

Amperes

250300350400500600630

Number of Poles

3 = Three4 = Four—neutral 0% protected8 = Four—neutral 0–60% protected9 = Four—neutral 0–100 protected

Frame

LT

LT 3 600 FA

Table 3. Earth Leakage Modules

Trip Unit

W = Without terminalsAmperes

400600630

Number of Poles

3 = Three4 = Four

Frame

ELLB

ELLB N 3 400 W

Rating

N = UL ratedE = IEC rated

Page 4: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

4

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

ALSIG (With Maintenance Mode)

ALSI (With Maintenance Mode)

LSIG

E

GF

HA

B

DC

RI12

2015

242

4

107

6

87

102

3

54

.8 1.0

.2.3

.6.4

N

PO

QJ

K

ML

12 I

sd

i

I (x )IRSHORT

gI (xIn)GND

R

tR (s)LONG

sdt / gt (ms)SHORT / GND*

TEST /ALARM STATUS

Push to Tript

t

g

sd

(ms)

(ms)

120KNQ

300LOR

* Inst.JMP

Inst.120300

Settings68C 4580 H01

~

LSG

E

GF

HA

B

DC

RI12

2015

242

4

107

6

87

102

3

54

.8 1.0

.2.3

.6.4

12 I

sd

i

I (x )IRSHORT

gI (xIn)GND

tR (s)LONG

TEST /ALARM STATUS

Push to Trip

68C 4580 H02

120

300Inst.

tg (ms)GND~

E

GF

HA

B

DC

IR∑12

2015

242

4

107

6

87

102

3

54

12

Isd (xIR)SHORT

tR (s)LONG

TEST /ALARM STATUS

Push to Trip

68C 4580 H18

120

30050

tsd (ms)SHORT

8

1210

2.5

76

Ii (xIn)INST

4

Maintenance Mode

Remote MM

E

GF

HA

B

DC

IR∑12

2015

242

4

107

6

87

102

3

54

.8 1.0

.2.3

.6.4

N

PO

QJ

K

ML

12

Isd (xIR)SHORT

Ig (xIn)GND

R

tR (s)LONG

tsd / tg (ms)SHORT / GND*

TEST /ALARM STATUS

Push to Triptg (ms)

tsd(ms)

120KNQ

300LOR

* 50JMP

50120300

Settings68C 4580 H17

8

1210

2.5

76

Ii (xIn)INST

4

Maintenance Mode

Remote MM

E

GF

HA

B

DC

IR∑12

2015

242

4

107

6

87

102

3

54

12 Ii

Isd (xIR)SHORT

tR (s)LONG

TEST /ALARM STATUS

Push to Trip

68C 4580 H03

120

300Inst.

tsd (ms)SHORT

E

GF

HA

B

DC

IR∑12

2015

242

4

107

6

87

102

3

54

12 Ii

Isd (xIR)SHORT

tR (s)LONG

TEST /ALARM STATUS

Push to Trip

68C 4580 H04

LSI

LS

Figure 1. Digitrip 310+ Faceplates

Page 5: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

5

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

.

.

.

.

.

1 2 3 4 5 7 10 20 300.5 0.7 12

1000900800

2000

3000

50006000700080009000

10,000

30

405060708090

100

700600500400

300

200

4000

1 M

inu

te2

Ho

urs

1 H

ou

r

0.01

2

0.02

0.03

0.040.050.060.070.080.090.1

0.2

0.3

0.40.50.60.70.80.9

3

456789

10

20

Tim

e in

Sec

on

ds

Maximum TotalClearing Time

1.15

Available Long Delay Time

(Seconds +0/–30%):2*, 4*, 7*, 10, 12, 15*, 20, 24*

*Shown below at 6x

MinimumTotalClearingTime

Available ShortDelay PickupSettings 2–8,

10, 12 x Ir ±5%(See Note 7)

300 ms(P, Q, R)

120 ms(M, N, O)

Inst.(J, K, L)

1

Current in Multiples of (Ir)

Current in Multiples of (Ir)

Current in Multiples of (In)1 2 3 4 5 7 10 20.5 0.7

Adjustable Flat Trip Style (LSI, LSIG, ALSI, ALSIG)

12 53 4 7 10 20 30 40 50 70 1000.01

0.02

0.03

0.040.050.060.070.080.090.1

0.2

0.3

0.40.5

Tim

e in S

econ

ds

ApplicationDetermines

End of Curve

InstantaneousOverride (See Note 8)

28X

12X

20 30 40 50 70 100

7

10

2 4

3

5

6

8

2

4

7

12

15

24

Figure 2. Digitrip 310+ Long Delay Response and Short Delay with Flat Response Curve (LSI, LSIG, ALSI, ALSIG)— Curve Number TC01207004E, May 2008

DigitripE 310+ Circuit Breaker time/Current Curves (Phase Current)

Series G® L-Frame Circuit BreakersCatalog Typese: LGE, LGS, LGH, LGC, LGU, LGX, GLE, GLS, GLH, GLC, GLU, and GLX circuit breakers, three- and four-pole .

Trip Unit Types: 32 (LSI), 36 (LSIG), 38 (ALSI), and 39 (ALSIG) .

Available Sensors (In)e: 250A, 400A, 600A, and 630A .

Long Delay and Short Delay with Flat Response

available Sensors(Ir) / (In)

Rated amperes

250 400 600 630

A 100 160 250 250B 125 200 300 300C 150 225 315 315D 160 250 350 350E 175 300 400 400F 200 315 450 500G 225 350 500 600H 250 400 600 630

otese:N

1 . Curve accuracy applies from –20°C to +55°C ambient . For possible continuous Ampere derating for ambient above +40°C, refer to Eaton . Temperatures above +85°C cause an overtemperature protection trip .

2 . Application frequency is 50/60 Hz .3 . There is a memory effect that can act to shorten the Long Delay . If the breaker trips on a

Long Delay overload and is quickly reset, the memory capacitor will still have charge and a subsequent overload will cause the breaker to trip in a shorter time than normal . The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload . Approximately five minutes is required between overloads to completely reset memory .

4 . The right portion of the curve is determined by the interrupting rating of the circuit breaker .5 . The left portion of the curve is shown as a multiple of the Long Delay Setting

(Long Delay Pickup = 115% of Ir) . Range is 110–120% .6 . Total clearing times shown include the response times of the trip unit, the breaker opening,

and the interruption of the current .7 . The Short Delay Pickup has nine settings/positions: 2–8, 10, and 12 .For high fault current levels, an additional fixed Instantaneous Override is provided .

Instantaneous Override tolerance is +/– 20% . The Instantaneous Override pickup value (Ii) is a multiple of the breaker sensor rating (In) . The Instantaneous Override has precedence over a SDPU . When Rated Amps (Ir) is set to the maximum (position H), then both the SDPU and the Instantaneous Override pickup are equivalent . Therefore, the breaker will trip on Instantaneous Override . In = 250A Instantaneous Override (Ii) = 28X(In) In = 400A, 600A, 630A Instantaneous Override (Ii) = 12X(In)

E

GF

HA

B

DC

IR∑12

2015

242

4

107

6

87

102

3

54

12 Ii

Isd (xIR)SHORT

tR (s)LONG

TEST /ALARM STATUS

Push to Trip

68C 4580 H03

120

300Inst.

tsd (ms)SHORT

E

GF

HA

B

DC

IR∑12

2015

242

4

107

6

87

102

3

54

.8 1.0

.2.3

.6.4

N

PO

QJ

K

ML

12 Ii

Isd (xIR)SHORT

Ig (xIn)GND

R

tR (s)LONG

tsd / tg (ms)SHORT / GND*

TEST /ALARM STATUS

Push to Triptg (ms)

tsd(ms)

120KNQ

300LOR

* Inst.JMP

Inst.120300

Settings68C 4580 H01

LSI LSIG

E

GF

HA

B

DC

IR∑12

2015

242

4

107

6

87

102

3

54

.8 1.0

.2.3

.6.4

N

PO

QJ

K

ML

12

Isd (xIR)SHORT

Ig (xIn)GND

R

tR (s)LONG

tsd / tg (ms)SHORT / GND*

TEST /ALARM STATUS

Push to Triptg (ms)

tsd(ms)

120KNQ

300LOR

* 50JMP

50120300

Settings68C 4580 H17

8

1210

2.5

76

Ii (xIn)INST

4

Maintenance Mode

Remote MM

aLSIG (With Maintenance Mode)

E

GF

HA

B

DC

IR∑12

2015

242

4

107

6

87

102

3

54

12

Isd (xIR)SHORT

tR (s)LONG

TEST /ALARM STATUS

Push to Trip

68C 4580 H18

120

30050

tsd (ms)SHORT

8

1210

2.5

76

Ii (xIn)INST

4

Maintenance Mode

Remote MM

aLSI (With Maintenance Mode)

Page 6: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

6

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

.

.

.

.

.

.

0.01

2

10

20

30

405060708090

100

1000900800700600500400

300

200

2000

3000

400050006000700080009000

10,000

0.02

0.03

0.040.050.060.070.080.090.1

0.2

0.3

0.40.50.60.70.80.9

1 M

inu

te2

Ho

urs

Tim

e in

Sec

on

ds

1 H

ou

r

Current in Multiples of (Ir)1 2 3 4 5 7 10 20 300.5 0.7

Current in Multiples of (In)Current in Multiples of (Ir)I 2t Trip Style (LS and LSG)

12

1 2 3 4 5 7 10 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 1000.5 0.7 12

Available Short DelayPickup Settings

2–8, 10 and 12 x Ir ±5%(See Notes 7 and 10)

ApplicationDetermines

End of Curve

InstantaneousOverride

(See Note 10)

I 2t Short Delay(See Note 8)

67 ms

See Note 9 28X

12X

0.01

0.02

0.03

0.040.050.060.070.080.090.1

0.2

0.3

Tim

e in S

econ

ds

3

456789

Maximum TotalClearing Time

Minimum TotalClearing Time

1.15

Available Long Delay Time(Seconds +0/–30%):

2*, 4*, 7*, 10, 12, 15*, 20, 24**Shown below at 6x

15

24

1

7

4

2

2 4

3

5

7

8

6

12

10

Figure 3. Digitrip 310+ Long Delay Response and Short Delay with I2t Response Curve (LS, LSG)— Curve Number TC01207005E, May 2008

Digitrip 310+ Circuit Breaker time/Current Curves (Phase Current)

Series G® L-Frame Circuit BreakersCatalog Typese: LGE, LGS, LGH, LGC, LGU, LGX, GLE, GLS, GLH, GLC, GLU, and GLX circuit breakers, three- and four-pole .

Trip Unit Types: 33 (LS) and 35 (LSG) .

Available Sensors (In)e: 250A, 400A, 600A, and 630A .

Long Delay and Short Delay with I2T Response

available Sensors(Ir) / (In)

Rated amperes

250 400 600 630

A 100 160 250 250B 125 200 300 300C 150 225 315 315D 160 250 350 350E 175 300 400 400F 200 315 450 500G 225 350 500 600H 250 400 600 630

otese:N

1 . Curve accuracy applies from –20°C to +55°C ambient . For possible continuous Ampere derating for ambient above +40°C, refer to Eaton . Temperatures above +85°C cause an overtemperature protection trip .

2 . Application frequency is 50/60 Hz .3 . There is a memory effect that can act to shorten the Long Delay . If the breaker trips on a

Long Delay overload and is quickly reset, the memory capacitor will still have charge and a subsequent overload will cause the breaker to trip in a shorter time than normal . The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload . Approximately five minutes is required between overloads to completely reset memory .

4 . The right portion of the curve is determined by the interrupting rating of the circuit breaker .5 . The left portion of the curve is shown as a multiple of the Long Delay Setting

(Long Delay Pickup = 115% of Ir) . Range is 110–120% .6 . Total clearing times shown include the response times of the trip unit, the breaker opening,

and the interruption of the current .7 . The Short Delay Pickup has nine settings/positions: 2–8, 10, and 12 .8 . Short Delay I2t band has a tolerance of ±15% .9 . Breakpoint back to FLAT response occurs at 8X Ir for upper line of the I2t curve .10 . For high fault current levels, an additional fixed Instantaneous Override is provided .

Instantaneous Override tolerance is +/– 20% . The Instantaneous Override pickup value (Ii) is a multiple of the breaker sensor rating (In) . The Instantaneous Override has precedence over a SDPU . When Rated Amps (Ir) is set to the maximum (position H), then both the SDPU and the Instantaneous Override pickup are equivalent . Therefore, the breaker will trip on Instantaneous Override . In = 250A Instantaneous Override (Ii) = 28X(In) In = 400A, 600A, 630A Instantaneous Override (Ii) = 12X(In)

E

GF

HA

B

DC

RI12

2015

242

4

107

6

87

102

3

54

12 I

sd

i

I (x )IRSHORT

tR (s)LONG

TEST /ALARM STATUS

Push to Trip

68C 4580 H04

~

LS

E

GF

HA

B

DC

RI12

2015

242

4

107

6

87

102

3

54

.8 1.0

.2.3

.6.4

12 I

sd

i

I (x )IRSHORT

gI (xIn)GND

tR (s)LONG

TEST /ALARM STATUS

Push to Trip

68C 4580 H02

120

300Inst.

tg (ms)GND~

LSG

Page 7: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

7

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

0.01

2

3

4

56

8

10

20

30

40

5060708090

100

1000900800700600500

400

300

200

0.02

0.03

0.04

0.050.060.070.080.090.1

0.2

0.3

0.40.50.60.70.80.9

1

7

9

2000

3000

4000

50006000700080009000

10,0001

Min

ute

Ground Current in Multiple of (In)0.1 0.2 0.3 0.4 0.5 0.7 1 2

0.1 0.2 0.3 0.4 0.5 0.7 1 2

Ground Fault Pickup Settings(Tolerance ±10%)

0.4X

0.3X

0.2X 1X0.6X

0.8X

Inst.(J, M, P)

120 ms(K, N, Q)

300 ms(L, O, R)

Tim

e in

Sec

on

ds

Figure 4. Ground Fault Delay Response Curve (LSG, LSIG, ALSIG)—Curve Number TC01207006E, May 2008

Digitrip 310+ Circuit Breaker time/Current Curves (Ground Current)

Series G® L-Frame Circuit BreakersCatalog Typese: LGE, LGS, LGH, LGC, LGU, LGX, GLE, GLS, GLH, GLC, GLU, and GLX circuit breakers, three- and four-pole .

LSG

E

GF

HA

B

DC

RI12

2015

242

4

107

6

87

102

3

54

.8 1.0

.2.3

.6.4

12 I

sd

i

I (x )IRSHORT

gI (xIn)GND

tR (s)LONG

TEST /ALARM STATUS

Push to Trip

68C 4580 H02

120

300Inst.

tg (ms)GND~

LSIG

E

GF

HA

B

DC

RI12

2015

242

4

107

6

87

102

3

54

.8 1.0

.2.3

.6.4

N

PO

QJ

K

ML

12 I

sd

i

I (x )IRSHORT

gI (xIn)GND

R

tR (s)LONG

sdt / gt (ms)SHORT / GND*

TEST /ALARM STATUS

Push to Tript

t

g

sd

(ms)

(ms)

120KNQ

300LOR

* Inst.JMP

Inst.120300

Settings68C 4580 H01

~

aLSIG (With Maintenance Mode)

E

GF

HA

B

DC

IR∑12

2015

242

4

107

6

87

102

3

54

.8 1.0

.2.3

.6.4

N

PO

QJ

K

ML

12

Isd (xIR)SHORT

Ig (xIn)GND

R

tR (s)LONG

tsd / tg (ms)SHORT / GND*

TEST /ALARM STATUS

Push to Triptg (ms)

tsd(ms)

120KNQ

300LOR

* 50JMP

50120300

Settings68C 4580 H17

8

1210

2.5

76

Ii (xIn)INST

4

Maintenance Mode

Remote MM

otee:N Refer to table below for variations .

Available Sensors (In)e: 250A, 400A, 600A, and 630A .

SD/GF Delay Settings table

t

t

g

sd

(ms)

(ms)

120KNQ

300LOR

* Inst.JMP

120300

Settings

Inst.

Ground Fault Delay Response notes:

1 . Curve accuracy applies from –20°C to +55°C ambient . For possible continuous Ampere derating for ambient above +40°C, refer to Eaton . Temperatures above +85°C cause an overtemperature protection trip .

2 . Application frequency is 50/60 Hz .3 . Trip units are suitable for functional field testing with test kit style #70C1056G52 .4 . For LD Response and SD with Flat Response curve, see TC01207004E .5 . For LD Response and SD with I2t Response curve, see TC01207005E .6 . For testing information, please contact Eaton .

Page 8: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

8

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

Current in Multiples of Rating (In)

0.01

2

0.02

0.03

0.040.050.060.070.080.090.1

0.2

0.3

0.4

0.50.60.70.80.9

1

3

4

56789

10

7

8

10

12 28

6

Tim

e in

Sec

on

ds T

ime in

Seco

nd

s

4

ApplicationDetermines

End of Curve

Maintenance Mode Trip Instantaneous Mode Trip

0.50.6

0.70.8

0.91 2 3 4 5 6 7 8 9

1020 30 40 50 1 10 100

0.01

2

0.02

0.03

0.04

0.050.060.070.080.090.1

0.2

0.3

0.40.50.60.70.80.91

3

45678910

2.5

ApplicationDetermines

End of Curve

Figure 5. Maintenance Mode / Instantaneous Setting (ALSI, ALSIG)—Curve Number TC01207014E, May 2008

Digitrip 310+ Circuit Breaker time/Current Curves

Maintenance Mode / Instantaneous Setting

Series G® L-Frame trip Unit nameplates

aLSI (With Maintenance Mode)

E

GF

HA

B

DC

IR∑12

2015

242

4

107

6

87

102

3

54

12

Isd (xIR)SHORT

tR (s)LONG

TEST /ALARM STATUS

Push to Trip

68C 4580 H18

120

30050

tsd (ms)SHORT

8

1210

2.5

76

Ii (xIn)INST

4

Maintenance Mode

Remote MM

aLSIG (With Maintenance Mode)

E

GF

HA

B

DC

IR∑12

2015

242

4

107

6

87

102

3

54

.8 1.0

.2.3

.6.4

N

PO

QJ

K

ML

12

Isd (xIR)SHORT

Ig (xIn)GND

R

tR (s)LONG

tsd / tg (ms)SHORT / GND*

TEST /ALARM STATUS

Push to Triptg (ms)

tsd(ms)

120KNQ

300LOR

* 50JMP

50120300

Settings68C 4580 H17

8

1210

2.5

76

Ii (xIn)INST

4

Maintenance Mode

Remote MM

otese:N

1 . The Maintenance Mode feature must be ENABLED for these curves to apply, when in Maintenance Mode .

2 . The Maintenance Mode is Enabled locally by turning the Maintenance Mode/INST dial to the 2 .5X or 4X position, or via remote signal . Enabling the Maintenance Mode via remote signal sets the pickup to 2 .5X regardless of Maintenance Mode/INST dial position .

3 . The end of the curve is determined by the interrupting rating of the circuit breaker .4 . Total clearing times shown include the response times of the trip unit,the breaker opening,

and the interruption of the current .5 . Nominal Values (Pickup) (Tolerance is ±15%) 2 .5X In, 4X In, 6X In, 7X In, 8X In, 10X In, 12X In .6 . These curves are comprehensive for the complete family of Series G L-Frame electronic

breakers, including all frame sizes, ratings, and constructions . The total clearing times shown are conservative and consider the maximum response times of the trip unit, the circuit breaker opening, and the interruption of the current in worst case conditions, such as maximum rated voltages, single-phase interruption, and minimum power factor . Faster clearing times are possible depending on the specific system conditions .

7 . For L-Frame breakers with 250A sensors (In = 250A), an INST setting of 12 is equal to 28X (7000A) .

8 . Contact Eaton for additional information .

This feature allows enabling of the maintenance mode remotely by applying 24 Vdc to the yellow (+) and black (–) wires that exit the left hand side of the breaker . The maintenance mode settings that is enabled is the 2 .5X setting .

There are two indicators that can verify that the trip unit has been remotely activated/enabled into the maintenance mode feature:

A . The blue LED (MM) located on the top left side of the trip unit will light .

AND/OR

B . The relay output is provided by three wires exiting the left hand side of the breaker: blue = C, red = NO, black = NC . The relay will change state when the maintenance mode is remotely enabled .

Left Side of Breaker

YellowBlack

BlackBlue

Red

24 Vdc

Relay Wiring

NONC

Page 9: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

9

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

0.001

0.01

0.1

1

10

100

1000

10,000

10,0001000100101Current in Multiples of Rating (In)

Tim

e in

Sec

on

ds

0.001

0.01

0.1

1

10

100

1000

10,000

5X±20%

Adjustable Magnetic Trip

10X ±10%

Maximum

Minimum

Interrupting Rating Determines End of Curve

Maximum Clearing Time

Figure 6. Thermal-Magnetic LGE, LGS, LGH, LGC, LGU, and LGX Circuit Breakers—Curve Number TC01208002E, January 2010

thermal-Magnetic Circuit Breaker time/Current Curves

Series G® LG-Frame Circuit BreakersCatalog Typese: LGE, LGS, LGH, LGC, LGU, and LGX circuit breakers, three- and four-pole .

For application and coordination purposes only . Thermal calibration based on +40°C ambient, cold start . Connected with four feet of rated wire (+75°C) per terminal . Tested in open air with current in all poles . Instantaneous calibration based on single-pole tests .

Maximum Voltagee: 690 Vac (50/60 Hz)—250 Vdc .

Breaker Rating

Rated amperes (In)

Instantaneous trip amperes

250–630 500 to 1000% of trip unit rating (DC values are approximately 40% higher)

Interrupting Rating

Breaker typeUL/CSa rms Sym. ka, 50/60 Hz ka, DC240V 480V 600V 250V

LGE 65 35 18 22LGS 85 50 25 22LGH 100 65 35 42LGC 200 100 50 42LGU 200 150 65 50LGX 200 200 65 50

IeC 60947-2 rms Sym. ka, 50/60 Hz ka, DCBreaker type 240V, (Ue) 415V, (Ue) 690V, (Ue) 250V, (Ue)

Icu Ics Icu Ics Icu Ics Icu IcsLGE 65 65 35 35 12 6 22 22LGS 85 65 50 50 20 10 22 22LGH 100 100 70 70 25 13 42 42LGC 200 200 100 100 30 15 42 42LGU 200 200 150 150 35 18 50 50LGX 300 200 200 200 65 35 50 50

Page 10: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

10

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

Current in Multiples of Rating (In)

0.001

0.01

0.1

1

100 1000 10,000 100,000 1,000,000

Current in Amperes (I)

Tim

e in

Sec

on

ds

10

100

1000

10,000

1 1

10 100 1000 10,000

Tim

e in

Sec

on

ds

Interrupting Rating Determines End of Curve

2500A

4000A

6000A

Magnetic Pickup

Thermal Curve

Maximum

Minimum

Maximum Interruption

Time

±20%

Figure 7. Thermal-Magnetic LHH High Instantaneous Circuit Breaker—Curve Number TC01206004E, September 2009

thermal-Magnetic Circuit Breaker time/Current Curves

Series G® LG-Frame Circuit BreakersCatalog Typese: LHH circuit breakers, three-pole .

For application and coordination purposes only . Thermal calibration based on 40°C ambient, cold start . Connected with four (feet of rated wire (+75°C) per terminal . Tested in open air with current in all poles . Instantaneous calibration based on single-pole tests .

Maximum Voltagee: 690 Vac (50/60 Hz)—250 Vdc (2 poles in series) .

Breaker Rating

Rated amperes (In)

Magnetic trip Point a

approx. Continuous Current Multiplier

Instantaneous trip amperes

125 2500 20XSee curve below (DC values are approx.40% higher)

Note: Magnetic pickup tolerance is ±20%

150 2500 17X175 4000 22X200 4000 20X225 6000 26X250 6000 24X300 6000 20X350 6000 17X400 6000 15X

Interrupting Rating

UL/CSa rms Sym. ka, 50/60 Hz ka, DCBreaker type 240V 480V 600V 250V

LHH 100 65 35 42

IeC 60947-2 rms Sym. ka, 50/60 Hz ka, DCBreaker type 240V, (Ue) 415V, (Ue) 690V, (Ue) 250V, (Ue)

Icu Ics Icu Ics Icu Ics Icu IcsLHH 100 100 70 70 25 13 42 42a Magnetic trip point tolerance is ±20%.

Page 11: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

11

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

Peak Let-Through Current, kA

100

kA

50 k

A

10 k

A

5 kA

1 kA

1 kA

100

kA50

kA

10 k

A5

kA

1000

kA

200

kA

Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

Ava

ilab

le Ip

fo

r 1s

t sy

mm

. 1/2

cyc

le

LG36

00

JG32

50

EG

3125

EG

CL1

00A

Figure 8. Peak Let-Through Current Series G Types LG, JG, EG, and EG CL (with Current Limiter), Molded-Case Circuit Breakers—240V—Curve Number TC01200001E-A, April 2012

LG36

00

JG32

50

EG

3125

EG

CL

100A

Peak Let-Through I2t, A2 sec

10,0

00,0

00

5,00

0,00

0

1,00

0,00

0

500,

000

100,

000

10,0

00

1 kA

100

kA50

kA

10 k

A5

kA

1000

kA

200

kA

Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

Figure 9. Peak Let-Through I2t Series G Types LG, JG, EG, and EG CL (with Current Limiter), Molded-Case Circuit Breakers— 240V—Curve Number TC01200001E-A, April 2012

otee:N All values are typical .

Page 12: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

12

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

Peak Let-Through Current, kA

Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

LG36

00

JG C

L 25

0A

JG32

50

EG

3125

EG

CL

100A

10 k

A

100

kA

50 k

A

5 kA

1 kA

10 k

A

100

kA

50 k

A

5 kA

1

kA

500

kA

1000

kA

Ava

ilab

le lp

fo

r 1s

tsy

mm

. 1/2

cyc

le

Figure 10. Peak Let-Through Current Series G Types LG, JG CL, JG, EG, and EG CL (with Current Limiter), Molded-Case Circuit Breakers—480V—Curve Number TC01200001E-B, April 2012

Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

JG C

L 25

0A

LG36

00

JG32

50

EG

3125

EG

CL

100A

10 k

A

100

kA

50 k

A

5 kA

1

kA

500

kA

1000

kA

10,0

00,0

00

100,

000

500,

000

1,00

0,00

0

500,

000

Peak Let-Through I2t, A2 sec

Figure 11. Peak Let-Through I2t Series G Types LG, JG, JG CL, EG, and EG CL (with Current Limiter), Molded-Case Circuit Breakers—480V—Curve Number TC01200001E-B, April 2012

otee:N All values are typical .

Page 13: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

13

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

JG C

L 25

0A

LG36

00

JG32

50

10 k

A

100

kA

50 k

A

5 kA

1

kA

500

kA

1000

kA

10 k

A

100

kA

50 k

A

5 kA

1 kA

Ava

ilab

le Ip

fo

r 1s

tsy

mm

. 1/2

cyc

le

Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

Peak Let-Through Current, kA

EG

3125

E

G C

L 10

0A

Figure 12. Peak Let-Through Current Series G Types LG, JG CL, JG, EG, and EG CL (with Current Limiter), Molded-Case Circuit Breakers—600V—Curve Number TC01200001E-C, April 2012

10,0

00,0

00

5,00

0,00

0

1,00

0,00

0

500,

000

100,

000

1 kA

5

kA

10 k

A

1000

kA

50

0 kA

10

0 kA

50

kA

Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

Peak Let-Through I2t, A2 sec

JG C

L 25

0A

LG36

00

JG32

50

EG

3125

EG

CL

100A

Figure 13. Peak Let-Through I2t Series G Types LG, JG, JG CL, EG, and EG CL (with Current Limiter), Molded-Case Circuit Breakers—600V—Curve Number TC01200001E-C, April 2012

otee:N All values are typical .

Page 14: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

14

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

1 kA

100

kA50

kA

10 k

A5

kA

Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

100

kA

50 k

A

10 k

A

5 kA

1 kA

LGU

3600

JGU

3250

Peak Let-Through Current, kA

Ava

ilab

le Ip

fo

r 1s

tsy

mm

. 1/2

cyc

le

500

kA 1000

kA

Figure 14. Peak Let-Through Current Series G Types LGU and JGU Molded-Case Circuit Breakers—240V—Curve Number TC01200001E-D, April 2012

1 kA

100

kA50

kA

10 k

A5

kA Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

10,0

00,0

00

5,00

0,00

0

1,00

0,00

0

500,

000

10,0

0050

0 kA 10

00 k

A

100,

000

Peak Let-Through I2t, A2 sec

LGU

3600

JGU

3250

Figure 15. Peak Let-Through I2t Series G Types LGU and JGU Molded-Case Circuit Breakers—240V—Curve Number TC01200001E-D, April 2012

otee:N All values are typical .

Page 15: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

15

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

1 kA

100

kA50

kA

10 k

A5

kA Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

100

kA

50 k

A

10 k

A

5 kA

LGU

3600

JGU

3250

Peak Let-Through Current, kA

500

kA 1000

kA

1 kA

Ava

ilab

le Ip

fo

r 1s

t sy

mm

. 1/2

cyc

le

Figure 16. Peak Let-Through Current Series G Types LGU and JGU Molded-Case Circuit Breakers—480V—Curve Number TC01200001E-E, April 2012

1 kA

100

kA50

kA

10 k

A5

kA Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

10,0

00,0

00

5,00

0,00

0

1,00

0,00

0

500,

000

LGU

3600

JGU

3250 50

0 kA 10

00 k

A

100,

000

Peak Let-Through I2t, A2 sec

Figure 17. Peak Let-Through I2t Series G Types LGU and JGU Molded-Case Circuit Breakers—480V—Curve Number TC01200001E-E, April 2012

otee:N All values are typical .

Page 16: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

16

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

1 kA

10 k

A5

kA

Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

100

kA

50 k

A

10 k

A

5 kA

LGU

3600

JGU

3250

Peak Let-Through Current, kA

50 k

A

100

kA

1 kA

Ava

ilab

le Ip

fo

r 1s

t sy

mm

. 1/2

cyc

le

Figure 18. Peak Let-Through Current Series G Types LGU and JGU Molded-Case Circuit Breakers—600V—Curve Number TC01200001E-F, April 2012

1 kA

10 k

A5

kA

Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

10,0

00,0

00

5,00

0,00

0

1,00

0,00

0

500,

000

LGU

3600

JGU

3250

50 k

A

100

kA

100,

000

Peak Let-Through I2t, A2 sec

Figure 19. Peak Let-Through I2t Series G Types LGU and JGU Molded-Case Circuit Breakers—600V—Curve Number TC01200001E-F, April 2012

otee:N All values are typical .

Page 17: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

17

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

1 kA

10 k

A5

kA Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

100

kA

50 k

A

10 k

A

5 kA

LGX

3600

JGX

3250

500

kA

1000

kA

1 kA

Peak Let-Through Current, kA

Ava

ilab

le Ip

fo

r 1s

t sy

mm

. 1/2

cyc

le

50 k

A10

0 kA

Figure 20. Peak Let-Through Current Series G Types LGX and JGX Molded-Case Circuit Breakers—240V—Curve Number TC01200001E-G, April 2012

1 kA

10 k

A5

kA Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

10,0

00,0

00

5,00

0,00

0

1,00

0,00

0

500,

000

LGX

3600

JGX

3250

500

kA 1000

kA

100,

000

Peak Let-Through I2t, A2 sec

50 k

A10

0 kA

10,0

00

Figure 21. Peak Let-Through I2t Series G Types LGX and JGX Molded-Case Circuit Breakers—240V—Curve Number TC01200001E-G, April 2012

otee:N All values are typical .

Page 18: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

18

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

1 kA

10 k

A5

kA

Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

100

kA

50 k

A

10 k

A

5 kA

500

kA 1000

kA

1 kA

Peak Let-Through Current, kA

50 k

A10

0 kA

Ava

ilab

le Ip

fo

r 1s

tsy

mm

. 1/2

cyc

le

LGX

3600

JGX

3250

Figure 22. Peak Let-Through Current Series G Types LGX and JGX Molded-Case Circuit Breakers—480V—Curve Number TC01200001E-H, April 2012

1 kA

10 k

A5

kA Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

500

kA 1000

kA

50 k

A10

0 kA

10,0

00,0

00

5,00

0,00

0

1,00

0,00

0

500,

000

100,

000

Peak Let-Through I2t, A2 sec

LGX

3600

JGX

3250

Figure 23. Peak Let-Through I2t Series G Types LGX and JGX Molded-Case Circuit Breakers—480V—Curve Number TC01200001E-H, April 2012

otee:N All values are typical .

Page 19: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

19

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

JG C

L 25

0A

LGX

3600

JGX

3250

10 k

A

100

kA

50 k

A

5 kA

1

kA

500

kA

1000

kA

10 k

A

100

kA

50 k

A

5 kA

1 kA

Ava

ilab

le Ip

fo

r 1s

tsy

mm

. 1/2

cyc

le

Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

Peak Let-Through Current, kA

Figure 24. Peak Let-Through Current Series G Types LGX, JG CL and JGX Molded-Case Circuit Breakers—600V—Curve Number TC01200001E-I, April 2012

LGX

3600

JGX

3250

10,0

00,0

00

5,00

0,00

0

1,00

0,00

0

500,

000

100,

000

1 kA

5

kA

10 k

A

1000

kA

500

kA

100

kA

50 k

A

Ava

ilab

le S

ho

rt-C

ircu

it C

urr

ent,

kA

rm

s

Peak Let-Through I2t, A2 sec

JG C

L 25

0A

Figure 25. Peak Let-Through I2t Series G Types LGX, JG CL and JGX Molded-Case Circuit Breakers—600V—Curve Number TC01200001E-I, April 2012

otee:N All values are typical .

Page 20: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

20

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

Table 4. 240V Peak Let-Through (Ip) and Clearing (I2t) Values for Series G High-Performance Breakers

Frame/Max. amperes (UL)

Maximum available Fault Current

35 ka 42 ka 65 ka 100 ka 150 ka 200 ka

Ip (ka) I2t (a2 sec) Ip (ka) I2t (a2 sec) Ip (ka) I2t (a2 sec) Ip (ka) I2t (a2 sec) Ip (ka) I2t (a2 sec) Ip (ka) I2t (a2 sec)

LGC/600A 30 2,000,000 33 2,100,000 38 2,300,000 45 2,600,000 N/A N/A N/A N/ALGU/600A 30 2,000,000 33 2,100,000 38 2,300,000 45 2,600,000 48 2,800,000 N/A N/ALGX/600A 30 2,000,000 33 2,100,000 38 2,300,000 45 2,600,000 48 2,800,000 52 2,900,000

Table 5. 480V Peak Let-Through (Ip) and Clearing (I2t) Values for Series G High-Performance Breakers

Frame/Max. amperes (UL)

Maximum available Fault Current

35 ka 50 ka 65 ka 100 ka 150 ka 200 ka

Ip (ka) I2t (a2 sec) Ip (ka) I2t (a2 sec) Ip (ka) I2t (a2 sec) Ip (ka) I2t (a2 sec) Ip (ka) I2t (a2 sec) Ip (ka) I2t (a2 sec)

LGC/600A 37 4,300,000 42 5,000,000 48 5,500,000 55 6,000,000 N/A N/A N/A N/ALGU/600A 37 4,300,000 42 5,000,000 48 5,500,000 55 6,000,000 62 6,800,000 N/A N/ALGX/600A 37 4,300,000 42 5,000,000 48 5,500,000 55 6,000,000 62 6,800,000 69 7,000,000

Table 6. 600V Peak Let-Through (Ip) and Clearing (I2t) Values for Series G High-Performance Breakers

Frame/Max. amperes (UL)

Maximum available Fault Current

35 ka 50 ka 65 ka

Ip (ka) I2t (a2 sec) Ip (ka) I2t (a2 sec) Ip (ka) I2t (a2 sec)

LGC/600A 39 6,400,000 46 7,200,000 N/A N/ALGU/600A 39 6,400,000 46 7,200,000 50 8,000,000LGX/600A 39 6,400,000 46 7,200,000 50 8,000,000

Page 21: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

21

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

Ig (A)

Settings

1S

500 ms

300 ms

150 ms

60 ms

Inst.

0.01 0.02 0.03 0.04 0.1 0.20.070.05

0.3 0.4 10.70.5 7 10 20 50 80

Tim

e in S

econ

ds

0.01 0.02 0.03 0.04 0.1 0.2 0.30.070.05

2.00.4 1.00.70.5 7.0 10.0 20.0 50.0 80.01000

0.001

0.002

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.090.1

0.2

0.3

0.4

0.50.60.70.80.9

1

2

3

4

56789

10

1009080706050

40

30

20

200

300

400

500600700800900

Tim

e in

Sec

on

ds

3.0 4.0 5.01000

0.001

0.002

0.003

0.004

0.0050.0060.0070.0080.0090.01

0.02

0.03

0.04

0.050.060.070.080.090.1

0.2

0.3

0.4

0.50.60.70.80.91

2

3

4

5678910

1009080706050

40

30

20

200

300

400

500600700800900

2 3 4 5

620.50.10.03Available Ig (A) 30

Figure 26. UL LG Circuit Breaker Earth Leakage Module, Three- and Four-Pole, 110–480V—Curve Number TC01212009E, September 2005

Circuit Breaker time/Current Curves

earth Leakage LG Circuit Breakers—ULCatalog Typese: ELLBN circuit breakers, three- and four-pole .

otese:N

1 . LG Circuit Breaker Earth Leakage Module, three- and four-pole,110–480V 60 Hz .2 . For application and coordination purposes only . –20ºC to +55ºC ambient .3 . Total clearing times include the response time of the Earth Leakage Module, the opening

time of the circuit breaker, and the interruption of the current .4 . For additional curve tolerances, contact Eaton .

Page 22: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

22

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

1000

0.001

0.002

0.003

0.0040.0050.0060.0070.0080.0090.01

0.02

0.03

0.040.050.060.070.080.090.1

0.2

0.3

0.40.50.60.70.80.9

1

2

3

456789

10

100908070605040

30

20

200

300

400

500600700800900

I∆n (Amperes)

0.01 0.02 0.03 0.04 0.1 0.2 0.3 0.4 0.50.070.05

1.0 2.0 3.0 4.0 5.00.7 7.0 10.0 20.0 50.0 80.0

Available I∆n Settings

Tim

e in

Sec

on

ds T

ime in

Seco

nd

s

0.01 0.02 0.03 0.04 0.1 0.2 0.3 0.4 0.50.070.05

1 2 3 4 50.7 7 10 20 50 80

1000

0.001

0.002

0.003

0.0040.0050.0060.0070.0080.0090.01

0.02

0.03

0.040.050.060.070.080.090.1

0.2

0.3

0.40.50.60.70.80.91

2

3

45678910

100908070605040

30

20

200

300

400

500600700800900

1S

500 ms

300 ms

150 ms

60 ms

Inst.

310.30.10.03 10

Figure 27. IEC LG Circuit Breaker Earth Leakage Module, Three- and Four-Pole, 110–480V—Curve Number TC01212008E, September 2005

Circuit Breaker time/Current Curves

earth Leakage LG Circuit Breakers—IeCCatalog Typese: ELLBE circuit breakers, three- and four-pole .

otese:N

1 . LG Circuit Breaker Earth Leakage Module, three- and four-pole,110–480V 60 Hz .2 . For application and coordination purposes only . –20ºC to +55ºC ambient .3 . Total clearing times include the response time of the Earth Leakage Module, the opening

time of the circuit breaker, and the interruption of the current .4 . For additional curve tolerances, contact Eaton .

Page 23: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

23

Time Current Curves TD012019ENEffective March 2014

Series G L-Frame

eaton www.eaton.com

Page 24: Time Current Curves TD012019EN Series G L-Frame · N = UL rated E = IEC rated. 4 Time Current Curves TD012019EN Effective March 2014 Series G L-Frame eaton ... Time Current Curves

Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton .com

© 2014 EatonAll Rights ReservedPrinted in USAPublication No . TD012019EN / Z14584March 2014