TP48200A. External Alarms. Special for Vodafone Project Total 15 Pages Cabinet TP48200A. External Alarms 1

Tp48200a External Alarms v1 0(Corregido)

Embed Size (px)

Citation preview

Page 1: Tp48200a External Alarms v1 0(Corregido)

TP48200A. External Alarms.

Special for Vodafone ProjectTotal 13 Pages

Cabinet TP48200A.

External Alarms

Huawei Technologies Co., Ltd.

Website:http://support.huawei.com

E-MAIL:[email protected]

All Rights Reserved.Address:Huawei Technologies Co., Ltd.,

Postal Code:

1

Page 2: Tp48200a External Alarms v1 0(Corregido)

TP48200A. External Alarms.

Table of Contents1. External Alarms Description:……………………………………….…………………5

2. External Alarms Connections (4x Ethernet cable (RJ45)): …………….……………..6

3. External Alarms Integration:…………………………………………..………………9

4. Reference Pictures:…………………………………………………………………..13

2

Page 3: Tp48200a External Alarms v1 0(Corregido)

TP48200A. External Alarms.

List of FiguresFigure 1. UIM 02A.................................................................................................................................................5

Figure 2. Terminal Block........................................................................................................................................5Figure 3. Layout Connection All External Alarms.................................................................................................6Figure 4. Ethernet Cable Conexion from UPEU_0 to UIM 02A............................................................................7Figure 5. Ethernet Cable Conexion from UPEU_1 to Terminal Block..................................................................8Figure 7. Example of External Alarm Integration................................................................................................10Figure 8. M2000 Alarm Definition.......................................................................................................................11

3

Page 4: Tp48200a External Alarms v1 0(Corregido)

TP48200A. External Alarms.

List of TablesTable 1. Alarm Information to be Commissioned in LMT and M2000..............................................................12

4

Page 5: Tp48200a External Alarms v1 0(Corregido)

TP48200A. External Alarms.

1. External Alarms Description:

External Alarms by Default corresponding to PMU (UIM 02A):

ALM1 Smoke Alarm ALM2 Door Open ALM3 Rect Fault ; Rect Com Fault ALM4 Load Fuse Trip; Batt Fuse Trip ALM5 Batt Temp Alarm ALM6 NULL (Not Configured)

ALM7 Main Fault ALM8 Head Lamp

ALM9 SPD Fault

Figure 1. UIM 02A

External Alarms from outside the cabinet:

ALM10 Alternative power source ALM11 AC main failure

ALM12 Beacon failure ALM13 Low level gas

ALM14 Grupo en Marcha ALM15 Reserved

ALM16 Reserved ALM17 Reserved

5

Page 6: Tp48200a External Alarms v1 0(Corregido)

TP48200A. External Alarms.

Figure 2. Terminal Block

2. External Alarms Connections (4x Ethernet cable (RJ45)):

6

Page 7: Tp48200a External Alarms v1 0(Corregido)

TP48200A. External Alarms.

Figure 3. Layout Connection All External Alarms

Note: Red cable connects ALM_9 (UIM 02A) to Port_0 (Terminal Block) in order to take ALM9 to the first position in UPEU_1.

2.1. UPEU_0 UIM 02A

ALM1 ALM2 ALM3 ALM4

7

Page 8: Tp48200a External Alarms v1 0(Corregido)

TP48200A. External Alarms.

UIM 02A

Board+ - + - + - + -

DRY PIN

Orange&White Orange Green&White Green Blue&White Blue Brown&White Brown

UPEU_0 Board

EXT_ALM0

UIM 02A

Board

ALM5 ALM7 ALM8 ALM9

+ - + - + - + -

DRY PIN

Orange&White Orange Green&White Green Blue&White Blue Brown&White Brown

UPEU_0 Board

EXT-ALM1

Figure 4. Ethernet Cable Conexion from UPEU_0 to UIM 02A

2.2 UPEU_1 Terminal Block

8

Page 9: Tp48200a External Alarms v1 0(Corregido)

TP48200A. External Alarms.

Terminal

Block

Port_0 Port_1 Port_2 Port_3

+ - + - + - + -

DRY PIN Orange&White Orange Green&White Green Blue&White Blue Brown&White Brown

UPEU_1 Board

EXT_ALM0

Terminal Block

Port_4 Port_5 Port_6 Port_7

+ - + - + - + -

DRY PIN Orange&White Orange Green&White Green Blue&White Blue Brown&White Brown

UPEU_1 Board

EXT-ALM1

Figure 5. Ethernet Cable Conexion from UPEU_1 to Terminal Block.

Note: For further details, please refer to Reference Pictures

3. External Alarms Integration:

1 st Step : Ethernet Cable Connection: UPEU_0 UIM 02A

9

Page 10: Tp48200a External Alarms v1 0(Corregido)

TP48200A. External Alarms.

UPEU_1 Terminal Block

Note: Refer to External Alarm Connections to check connection configuration details.

2 nd Step: Add External Alarm in UPEU Board:

Note: Refer to External Alarm Description to check Alarm ID for each external alarm.

Example:

Normally the configuration will be done on the 2G BTS as follow ,

SET BTSENVALMPORT: IDTYPE=BYID, BTSID=222, CN=0, SRN=0, SN=18, PN=0, SW=OPEN, AID=65133, PT=BOOL, AVOL=HIGH;SET BTSENVALMPORT: IDTYPE=BYID, BTSID=222, CN=0, SRN=0, SN=18, PN=1, SW=OPEN, AID=65134, PT=BOOL, AVOL=HIGH;....

Or From 3G NodeB

10

Page 11: Tp48200a External Alarms v1 0(Corregido)

TP48200A. External Alarms.

SET ALMPORT: CN=0, SRN=0, SN=18, PN=0, SW=ON, AID=65133, PT=BOOL, AVOL=HIGH;SET ALMPORT: CN=0, SRN=0, SN=18, PN=, SW=ON, AID=65133, PT=BOOL, AVOL=HIGH;Example:

SET ALMPORT: CN=0, SRN=0, SN=18, PN=0, SW=ON, AID=65033, PT=BOOL, AVOL=HIGH;

Figure 6. Example of External Alarm Integration

3 rd Step : M2000 External Alarm Definition: Assign Alarm Name to Alarm ID.

Note: Refer to External Alarm Description to check Alarm Name associated to Alarm ID.

Enter M2000 Server:Monitor / Alarm Setting / NE Alarm Setting Add

11

Page 12: Tp48200a External Alarms v1 0(Corregido)

TP48200A. External Alarms.

Figure 7. M2000 Alarm Definition.

ALARM

Cabinet No

Subrack No Slot No Port No Switch

Alarm ID

Port Type

Alarm Voltage

Alarm Name

Alarm Severity

Level (Configure

d from M2000)

(Configured from

M2000)

ALM1 0 0 18 0 ON 65133 BOOL HIGH Fuego / Major

ALM2 0 0 18 1 ON 65134 BOOL HIGH Intrusión Major

ALM3 0 0 18 2 ON 65135 BOOL HIGHFallo menor

Continua Major

ALM4 0 0 18 3 ON 65136 BOOL HIGHDistribución

Continua Major

ALM5 0 0 18 4 ON 65137 BOOL HIGHTemperatur

a Alta Major

ALM6 NULL NULL NULL NULL NULL NULL NULL NULL NULL NULL

12

Page 13: Tp48200a External Alarms v1 0(Corregido)

TP48200A. External Alarms.

ALM7 0 0 18 5 ON 65138 BOOL HIGHFallo

Alterna Major

ALM8 0 0 18 6 ON 65139 BOOL HIGHFallo Mayor

Continua Major

ALM9 0 0 18 7 ON 65140 BOOL HIGH

Fallo Prot. Sobretensió

n Major

ALM10 0 0 19 0 ON 65141 BOOL HIGHSuministro Alternativo Major

ALM11 0 0 19 1 ON 65142 BOOL HIGHFallo

Alterna Major

ALM12 0 0 19 2 ON 65143 BOOL HIGH Baliza Major

ALM13 0 0 19 3 ON 65144 BOOL HIGHBajo Nivel

Gasóleo Major

ALM14 0 0 19 4 ON 65145 BOOL HIGHGrupo en Marcha Major

ALM15 0 0 19 5 ON 65146 BOOL HIGH Reserva Major

ALM16 0 0 19 6 ON 65147 BOOL HIGH Reserva Major

ALM17 0 0 19 7 ON 65148 BOOL HIGH Reserva Major

Table 1. Alarm Information to be Commissioned in LMT and M2000.

4. Reference Pictures:

13