CAT.200.01.T.E For more information contact Cutler-Hammer: www.ch.cutler-hammer.com/catalog
9-111January 2001
Transformers
9
Industrial Control TransformersType AP
Vol. 1, Ref. No. [0395]
Product SelectionAdditional Product Selection information begins on Page 9-120.
Table 9-135. Type AP
1 See Page 9-83 for Wiring Diagrams.Note: For additional information refer to Cutler-Hammer Industrial Control Transformer Binder B1228A.
kVA Mounting Dimensions (Inches) WeightLbs.
Dimensions (mm) WeightKg
Frame WiringDiagram 1
CatalogNumber
PriceU.S. $H W D H W D
240/480 Volts to 120/240 Volts, 60 Hz357.510
BottomBottomBottomBottom
8-5/1610-3/410-3/410-3/4
9-9/1610-3/410-3/410-3/4
8-13/16 8 -11/1610-3/1611-3/8
65104129148
227273273273
243273273273
224221259289
29.547.258.667.2
13399100101
5555
C0003P7GBC0005P7GBC0007P7GBC0010P7GB
1,360.1,695.2,330.2,905.
1535
BottomSide/WallSide/Wall
129-3/411-5/8
13-3/16 8-13/16 8-11/16
10-7/16 9-9/1610-3/4
19765104
305248295
335224221
265243273
89.429.547.2
134292256
555
C0015P7GBC0003P7GSC0005P7GS
3,940.1,360.1,695.
7.51015
Side/WallSide/WallSide/Wall
11-5/811-5/812-7/8
10-13/1611-3/810-7/16
10-3/410-3/413-3/16
129148197
295295327
275289265
273273335
58.667.289.4
257258259
555
C0007P7GSC0010P7GSC0015P7GS
2,330.2,905.3,940.
For other ratings or styles not shown, or for special enclosure types (including stainless steel) refer to Cutler-Hammer. Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1
472_09.fm Page 111 Monday, November 20, 2000 9:37 AM
9-124
For more information contact Cutler-Hammer: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E
January 2001
Transformers
9
Vol. 1, Ref. No. [0408]
Catalog Numbering SystemTable 9-154. Industrial Control Transformers, CE Marked Control Transformers — Example: CE0250G2FES
Note: For the Cutler-Hammer Dry Type Transformers Catalog Numbering System see Page 9-122 and 9-123.Note: Contact your local Cutler-Hammer sales office for voltage combinations not shown. Use table for catalog number breakdown only.
Type
C = Industrial Control Transformer
CE= CE Marked Control Transformer
VA Rating
0025 = 250050 = 500075 = 750100 = 1000150 = 1500200 = 2000250 = 2500300 = 3000350 = 3500500 = 5000750 = 7501000 = 10001500 = 15002000 = 20003000 = 30005000 = 5000
Type AP Only:0003 = 30000005 = 50000007 = 75000010 = 100000015 = 15000
Transformer Design
A= MTAC = MTCE = MTEG= MTGK = MTKP = AP
Voltage
Primary Secondary
1B =2A =
2B =2C =2F =2G =2U =
2V =2W =3A =3B =3C =3D =4C =4D =4H =
4W =5E =
6U =
7G =(Type AP
Only)
120 x 240240 x 480,
230 x 460,220 x 440
240 x 480240 x 480230/460230/460220/380/440/550,
230/400/460/575,240/416/480/600
208/230/400/460/575208/230/400/460/575208/277115230/460/575208/380/416550/575/600380/400/415380/400/415550/575/600200/220/440,
208/230/460, 240/480
240/416/480/600,230/400/460/575,220/380/440/550,208/500
240 x 480
24120/115/110
24120 x 240115115/23023/110, 24/115,
25/120
24/115/230115/23012024115/95115/95110/115/120110 x 22022/23/2422/23/2423/110, 24/115,
25/120
99/120/130,95/115/125,91/110/120,85/100/110
120/240
Modifications
Type MTE/MTG/MTKFB = Factory mounted 2-pole primary fuse block for
rejection type fusesFBN = Factory mounted 2-pole primary fuse block for
non-rejection type fusesQ = Secondary fuse clips for 1/4 x 1-1/4 inch fusesXX = No Secondary fuse clipsRT = Ring type terminals for connection to fuseblockES = Electrostatic shieldFS = Factory mounted finger safe terminal shields
Type APB = Bottom mountedS = Side/wall mountedES = Electrostatic shieldCU = Copper windings
Type MTA/MTCFB = Factory mounted 3-pole fuseblock (2-pole
primary rejection type with 1-pole secondary non-rejection type)
ES = Electrostatic shieldL = Lead terminations
CE 0250 G 2F ES
472_09.fm Page 124 Monday, November 20, 2000 9:37 AM
9-110
For more information contact Cutler-Hammer: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E
January 2001
Transformers
9
Industrial Control TransformersType AP
Vol. 1, Ref. No. [0394]
Type AP
Type AP Transformer
Product Description■ Resin-encapsulated designs
Application DescriptionTransformers provide stepped down voltages to machine tool control devices enabling control circuits to be isolated from all power and lighting circuits. This allows the use of grounded or ungrounded circuits that are independent of the power or light-ing grounds; greater safety is afforded the operator. The control transformer line is particularly adaptable on appli-cations where compact construction is demanded.
Features, Benefits and Functions■ UL recognized ■ Resin encapsulated■ 60 Hz operation■ 115°C winding rise■ Convenient screw-type terminal
board■ Bottom or side/wall mounting
designs■ Performance meets/exceeds
requirements of ANSI/NEMA ST-1■ Regulation exceeds ANSI/NEMA
requirements for all ratings
Standards and CertificationsIndustry StandardsAll Cutler-Hammer dry type distribution and control transformers are built and tested in accordance with applicable NEMA, ANSI, and IEEE Standards.
Product SpecificationsOverload CapabilityShort-term overload is designed into transformers as required by ANSI. Dry type distribution transformers will deliver 200% nameplate load for one-half hour; 150% load for one-hour; and 125% load for four-hours without being damaged provided that a con-stant 50% load precedes and follows the overload. See ANSI C57.96-01.250 for additional limitations.
Continuous overload capacity is not deliberately designed into a trans-former because the design objective is to be within the allowed winding tem-perature rise with nameplate loading.
Insulation System and Temperature RiseIndustry standards classify insulation systems and rise as shown below:
Table 9-133. Insulation System Classification
The design life of transformers having different insulation systems is the same — the lower temperature systems are designed for the same life as the higher temperature systems.
Sound LevelsAll Cutler-Hammer 600 volt class general purpose dry type distribution transformers are designed to meet NEMA ST-20 levels listed here.
Table 9-134. Sound Levels
1 Applies to general purpose transformers only.
Winding Terminations
Cutler-Hammer recommends external cables be rated 90ºC (sized at 75°C ampacity) for encapsulated designs.
Series-Multiple WindingsSeries-multiple windings consist of 2 similar coils in each winding which can be connected in series or parallel (multiple). Transformers with series-multiple windings are designated with an “X” or “/” between the voltage ratings, such as voltages of “120/240” or “240 X 480.” If the series-multiple winding is designated by an “X,” the winding can be connected only for a series or parallel. With the “/” designa-tion, a mid-point also becomes avail-able in addition to the series or parallel connection. As an example, a 120 X 240 winding can be connected for either 120 (parallel) or 240 (series), but a 120/240 winding can be connected for 120 (parallel), or 240 (series), or 240 with a 120 mid-point.
Technical Data and SpecificationsPlease refer to Page 9-114.
Ambient + WindingRise
+HotSpot
=Temp. Class
40°C40°C40°C40°C
55°C80°C115°C150°C
10°C30°C30°C30°C
105°C150°C185°C220°C
kVA NEMA Average 1
Sound Level in dB
0 – 910 – 5051 – 150151 – 300
40455055
301 – 500501 – 700701 – 10001001 – 1500
60626465