Mounting and Operating Instructions EB 6116 EN Translation of original instructions Edition October 2016 System 6000 Electropneumatic Converter for DC Signals Type 6116 i/p Converter Type 6116 i/p Converter

Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

  • Upload
    ngobao

  • View
    325

  • Download
    12

Embed Size (px)

Citation preview

Page 1: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

Mounting and Operating Instructions

EB 6116 EN

Tran

slatio

n of

orig

inal

instr

uctio

ns

Edition October 2016

System 6000

Electropneumatic Converter for DC SignalsType 6116 i/p Converter

Type 6116 i/p Converter

Page 2: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

2 EB 6116 EN

Note on these mounting and operating instructions

These mounting and operating instructions assist you in mounting and operating the device safely. The instructions are binding for handling SAMSON devices.

Î For the safe and proper use of these instructions, read them carefully and keep them for later reference.

Î If you have any questions about these instructions, contact SAMSON‘s After-sales Service Department ([email protected]).

The mounting and operating instructions for the devices are included in the scope of delivery. The latest documentation is available on our website (www.samson.de) > Product documentation. You can enter the document number or type number in the [Find:] field to look for a document.

Definition of signal words

DANGER!Hazardous situations which, if not avoided, will result in death or seri-ous injury

WARNING!Hazardous situations which, if not avoided, could result in death or seri-ous injury

NOTICEProperty damage message or mal-function

Note:Additional information

Tip:Recommended action

WARNING!Damage to health relating to the REACH regulation.If a SAMSON device contains a substance which is listed as being a substance of very high concern on the candidate list of the REACH regulation, this circumstance is indicated on the SAMSON delivery note.Information on safe use of the part affected, see u http://www.samson.de/reach-en.html.

Page 3: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

Contents

EB 6116 EN 3

1 General safety instructions .............................................................................42 Description ....................................................................................................52.1 Application ...................................................................................................52.2 Versions ........................................................................................................52.3 Principle of operation .....................................................................................73 Installation ....................................................................................................83.1 Mounting position ..........................................................................................83.2 Mounting ......................................................................................................83.3 Electrical connection .......................................................................................93.4 Pneumatic connection ...................................................................................104 Operation ...................................................................................................104.1 Checking zero and span ...............................................................................105 Maintenance ...............................................................................................125.1 Cleaning the restriction .................................................................................126 Servicing explosion-protected devices ..........................................................127 Positioner attachment ..................................................................................137.1 Principle of operation ...................................................................................137.2 Installation ...................................................................................................147.2.1 Mounting position of the converter ................................................................147.3 Electrical connection .....................................................................................147.4 Pneumatic connection ...................................................................................147.5 Operation ...................................................................................................158 Troubleshooting...........................................................................................199 Technical data .............................................................................................2010 Article code .................................................................................................2210.1 Accessories .................................................................................................2411 Dimensions .................................................................................................25

Page 4: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

4 EB 6116 EN

General safety instructions

1 General safety instructions − The device must be mounted, started up or serviced by fully trained and

qualified personnel only; the accepted industry codes and practices are to be observed. Make sure employees or third persons are not exposed to any danger.

− All safety instructions and warnings given in these mounting and operating instructions, particularly those concerning installation, start-up and mainte-nance, must be strictly observed.

− According to these mounting and operating instructions, trained personnel refers to individuals who are able to judge the work they are assigned to and recognize possible dangers due to their specialized training, their knowledge and experience as well as their knowledge of the applicable standards.

− The devices with a CE marking comply with the requirements of the Europe-an Pressure Equipment Directive 2014/30/EU. Devices with a CE marking have a declaration of conformity, which includes information about the ap-plied conformity assessment procedure. This declaration of conformity can be provided on request.

− To ensure appropriate use, only use the device in applications where the op-erating pressure and temperatures do not exceed the specifications used for sizing the device at the ordering stage.

− The manufacturer does not assume any responsibility for damage caused by external forces or any other external factors.

− Any hazards that could be caused in the valve by the process medium, op-erating pressure or by moving parts are to be prevented by taking appropri-ate precautions.

− Proper transport, storage, installation, operation and maintenance are as-sumed.

Page 5: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 5

Description

Further versions − Type 6116-x2xxxxxxxxx2… :

− Temperatures down to –45 °C − Type 6116-0… :

− AS-interface connection with Type 6150 Slave

− Voltage input (e.g. 0 to 10 V) with Type 6151 u/i Module

− Electropneumatic converter without booster or switch-off electronics:Converters can be combined with SAMSON Type 3760, Type 3766-000 (model index .02 and higher) and Type 4765 Pneumatic Positioners. See section 7 on page 13. − Type 6116-xx060111000xxxx for

attachment to p/p positioners (½ NPT connection)

− Type 6116-xx060112000xxxx for attachment to p/p positioners (M20 x 1.5 connection)

Fig. 1: Sample application

2 Description2.1 ApplicationThe devices (proportional valves) are used to convert a direct current input signal into a pneumatic output signal for measuring and control tasks. They are particularly suitable as an intermediate element between electric measuring devices and pneumatic controllers or between electric control devices and pneumatic control valves.The input is a load-independent direct cur-rent (e.g. 4 to 20 mA) and the output is a pneumatic signal, for example, 0.2 to 1 bar (3 to 15 psi) or signal ranges up to 8 bar (116 psi).

2.2 VersionsVersions for safe areas: − Type 6116-0 ...

Versions for hazardous areas: − Type 6116-1... Ex i according to ATEX

and GOST − Type 6116-2... Ex d according to ATEX,

IEC and GOST − Type 6116-3... Explosion-proof acc. to

CSA and FM standards − Type 6116-4... Intrinsically safe accord-

ing to CSA and FM standards − Type 6116-5... Explosion Proof/Austra-

lia/IEC/Korea − Type 6116-6... Intrinsically Safe/Austra-

lia/IEC − Type 6116-7… Ex d according to JIS

standard/Japan

TROVIS 6493

Type 3241-1

Type 6116

Supply air

p

e

Page 6: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

6 EB 6116 EN

General safety instructions

Fig. 2: Functional drawing

1 Balance beam2 Plunger coil3 Permanent magnet4 Zero point and span adjusters (not in

version without electronics)5 Switch-off electronics: slide switch (only

with 4 to 20 mA version with electronics)

6 Flapper7 Nozzle8 Volume booster8.2 Fixed restriction9 Sleeve10 Diaphragm

6

7

8

10

8.2

9

1

2

3

4

i

5

pA

pK

ZERO SPAN

SUPPLY 8

EXHAUST

OUTPUT 36

GAUGE (36)

Type 6109/Type 6112 i/p Module

− Type 6116-xx06011x000xxxx (for positioner attachment) 1)

Input: 4 to 20 mA, other signals on request, internal resistance approx. 200 Ω at 20 °COutput: 0.2 to 1 bar for positionerOther data same as standard version (see section 9 on page 20)1) With Type 6109 i/p Converter Module only

Page 7: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 7

General safety instructions

2.3 Principle of operationSee Fig. 2 on page 6.The device consists of an i/p converter mod-ule and a downstream volume booster.When operated, the supplied direct current i flows through the plunger coil (2) located in the field of a permanent magnet (3). At the balance beam (1), the force of the plunger coil, which is in proportion to the current, is balanced against the force of the dynamic backpressure. The backpressure is produced on the flapper plate (6) by the air jet leaving the nozzle (7).The supply air (SUPPLY 8) flows to the bot-tom chamber of the volume booster (8) and a certain amount of air determined by the diaphragm position flows past the sleeve (9) and leaves through the output (OUTPUT 36). As the input current and the forces acting on the plunger coil increase, the flapper (6) moves closer to the nozzle (7). This causes the backpressure and the cascade pressure pK upstream of the restriction (8.2) to in-crease until the cascade pressure corre-sponds with the input current.The increasing cascade pressure pushes the diaphragm (10) and the plug sleeve (9) downwards. As a result, the supply air caus-es the output pressure pA to increase until a new state of equilibrium is reached in the di-aphragm chambers.When the cascade pressure drops, the dia-phragm moves upwards, releasing the plug sleeve and thus allowing the output pressure pA to escape through the venting (EXHAUST) until the forces are equal again.

Switch-off electronics (see Fig. 3)Devices with an input range from 4 to 20 mA have a slide switch which activates the switch-off electronics. This function allows the input signal to be set to 0 mA when the signal falls below the switching point of 4.08 ± tolerance. This causes the pneumatic output to be vented to approximately 100 mbar. This guarantees, for example, the tight shut-off function of a valve.This function requires a characteristic which passes through the zero point, for example, for the version with 4 to 20 mA/0.2 to 1 bar.If the characteristic line does not pass through zero, for example, for an allocated output signal from 0.8 to 2.7 bar, then the pneumatic output is vented to a remaining pressure of approx. 0.3 bar when the switch-off electronics are activated.

4 8 12 16 20mA

0.2

0.4

0.6

0.81.0

bar

4 8 12 16 20mA

1

2

3bar

2.7

0.30.8

Fig. 3: Switch-off electronics and remaining pressure

Output 0.2 to 1 barRemaining pressure approx. 0.1 bar

Output 0.8 to 2.7 barRemaining pressure approx. 0.3 bar

Page 8: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

8 EB 6116 EN

Installation

3 Installation

3.1 Mounting positionThe converter is to be installed horizontally, with the pressure gauge (or screw plug) fac-ing upward. If a different mounting position is used, the zero point must be readjusted as described in section 4.1 on page 10.With degree of protection IP 54, the vent plug must always be installed facing down-ward to the floor.

3.2 MountingThe converter can be mounted to a wall, a pipe or directly to a control valve (Fig. 4).The following accessories are required:Order no. 1400-6216 − For wall and pipe mounting

Order no. 1400-6217 − For attachment to valve with cast yoke

Order no. 1400-6218 − For attachment to valve with rod-type

yokeSee section 10.1 on page 24 for further mounting parts.

Fig. 4: Mounting

2 Plate3 Rail4 M6 x 16 screw5 M6 x 25 screw6 Spring washer B67 A6.4 washer8 M8 nut9 A8.4 washer10 M8 x 25 screw11 Clamp13 Wall or pipe bracket

7 6 5

8 9 13 12

6 74

108 9 11

563 2

Wall and pipe mountingTop view

Top view

Valve with cast yoke/rod-type yoke mountingSide view

Rod-type yoke bracket

Yoke bracket

Clamp for attachment to 2” pipe

Page 9: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 9

Installation

3.3 Electrical connection

DANGER!Risk of electric shock and/or the for-mation of an explosive atmosphere.For electrical installation, observe the relevant electrotechnical regulations and the accident prevention regula-tions that apply in the country of use.

In Germany, these are the VDE regulations and the accident prevention regulations of the employers’ liability insurance.

DANGER!Adhere to the terminal assignment. Switching the assignment of the elec-trical terminals may cause the explo-sion protection to become ineffective.Do not loosen enameled screws in or on the enclosure.

The following regulations apply to installa-tion in hazardous areas: EN 60079-14 (VDE 0165, Part 1) and DIN EN 50281-1-2 (VDE 0165, Part 2).The maximum permissible values specified in the EC type examination certificates apply when interconnecting intrinsically safe elec-trical equipment (Ui or U0, li or I0, Pi or P0, Ci or C0 and Li or L0).

WARNING!Leakage to the terminal space leads to the degree of protection not being met.Only operate the device with sealed cable entries and locked cover.

11 12

+ –

Fig. 5: Electrical connection

1. Unscrew the enclosure cover and connect the wires for the input signal to the termi-nals 11 (+) and 12 (–) using suitable ca-ble glands or connectors.No additional voltage supply is required.Connect Ex d versions with an approved metal cable entry (certificate of conformi-ty) or a seal box pipe.Approved versions (certificate of confor-mity) are equipped with permanently sealed cable entries.

2. Secure grounding conductor at the ground terminal located either inside or outside the enclosure.

3. Check the O-ring for damage and re-place it, if necessary.

4 to 20 mA inputGreen/yellow grounding conductor

Page 10: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

10 EB 6116 EN

Operation

through and clean all air pipes and hoses thoroughly before connecting them.

NOTICERisk of property damage due to wa-ter entering the device when a pipe is used to extend the vent pipe.Make sure that no water can enter at the end of an extension pipe (mini-mum cross-section of 28 mm² = 6 mm inside diameter) connected to either vent elbow piece or directly to the G or NPT connection.

4 OperationSee Fig. 2 on page 6.

4.1 Checking zero and spanThe device converts the input signal propor-tionally into the output signal.The signal ranges are specified on the name-plate.In case of a mounting position that is not horizontal or when the pressure gauge/screw plug does not face upwards, zero and span can be corrected by approx. 10 % us-ing the electronics. To do this, proceed as follows:1. Unscrew the enclosure cover to access

the ZERO and SPAN potentiometers (4) on the circuit board.

2. Connect a pressure gauge (minimum ac-curacy class 1) to the converter output.

4. Screw on the cover as far as it will go. Unscrew the cover until the first possible safety position (notch) is reached.

5. Unscrew the fillister head screw to lock the cover.

NOTICELoss of Ex d protection due to dam-age to the cover's thread and/or the connecting thread. The enclosure cover must be firmly closed during operation.

3.4 Pneumatic connectionThe pneumatic connections for supply air (SUPPLY 8) and output (OUTPUT 36) are de-signed as threaded ports with G ¼ or ¼–18 NPT thread (see section 11 on page 25).Customary fittings for metal tubing or plastic hoses can be used.Supply air (see section 9 on page 20). − Min. + 0.4 bar above the upper signal

pressure range − Max. 10 bar · Type 6116-2: max. 6 bar

(see EC type examination certificate in Appendix)

Note:The supply air must be dry and free of oil and dust (see section 9 on page 20).

Read the maintenance instructions for up-stream pressure reducing stations. Blow

Page 11: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 11

Operation

The zero point can only be adjusted me-chanically at the zero screw (1.1) of the i/p module.

NOTICEDo not open devices with flameproof enclosures when the electrical power supply is connected.Do not damage the cover's thread and/or the connecting thread.Risk of explosion!Observe the explosion-protection regulations.

ZERO

SPAN

OFF

ON

Fig. 6: Zero and span correction

Terminals

Zero and span ad-justers

Switch to switch off electronics

3. Set the supply air to 0.4 bar above the upper output signal range and apply it to the device.

4. Deactivate the switch-off electronics at the slide switch (5).

Checking zero5. Set the input signal to the lower range

value using a suitable ammeter (e.g. set it to 4 mA for 4 to 20 mA range = 0.2 to 1 bar).The output signal of the pressure gauge should now indicate 0.2 bar. If this is not the case, readjust zero accordingly with the ZERO potentiometer (4).

Checking span6. Set the input signal to 20 mA (upper

range value) using a suitable ammeter.The output signal of the pressure gauge should now indicate 1.0 bar. If this is not the case, readjust the span accordingly with the SPAN potentiometer (4).

Note:As the adjustment of zero and span influence each other, recheck both values and correct them, if necessary.

Zero adjustment for special versions with 0 to 20 mA input signalThese versions do not have potentiometers to adjust zero or span nor switch-off electron-ics.

Page 12: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

12 EB 6116 EN

Maintenance

5 MaintenanceNo specific maintenance measures need to be carried out.To guarantee trouble-free operation of the converter, make sure that the supply air is al-ways clean (see section 9 on page 20 for air quality).Therefore, check the air filter and trap in-stalled in the upstream air reducing station regularly.

5.1 Cleaning the restrictionThe restriction (see Fig. 11) is located inside the enclosure. It can be accessed from the back of the device. It can be taken out after the screw plug (Ø10) has been removed.When the output signal is too small or when there is no output signal at all, the restriction might be blocked. To remove blockages, take the filter out of the restriction and clean or replace it.

Filter Order no.: 0550-0193Restriction including filter

Order no.: 1390-0186

In addition, the pneumatic connections have filters with plastic rims (order no. 0550-0213) which can be removed for cleaning.

6 Servicing explosion-protected devices

If a part of the device on which the explosion protection is based needs to be serviced, the device must not be put back into operation until a qualified inspector has assessed it ac-cording to explosion protection require-ments, has issued an inspection certificate or given the device a mark of conformity.Inspection by a qualified inspector is not re-quired if SAMSON performs a routine test on the device before putting it back into op-eration. Document the passing of the routine test by attaching a mark of conformity to the device.Replace explosion-protected components on-ly with original, routine-tested components from the manufacturer.Devices that have already been used outside hazardous areas and are intended for future use inside hazardous areas must comply with the safety requirements placed on ser-viced devices. Before being operated inside hazardous areas, test the devices according to the specifications for servicing explo-sion-protected devices.

Page 13: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 13

Positioner attachment

7 Positioner attachmentAnalog positioners with Ex d explosion pro-tection can be implemented by combining a p/p positioner with a Type 6116-2 (Ex d) Converter.In the Type 6116 Converter designed for po-sitioner attachment, the connection to the po-sitioner is used in place of the booster.Another application involves upgrading p/p positioners to electropneumatic positioners (current signal input instead of the pneumatic signal).Type 6116-xx010111000xxxx with ½ NPT electrical connection andType 6116-xx101012000xxxx with M20 x 1.5 electrical connection

7.1 Principle of operationWhen operated, the supplied direct current i flows through the plunger coil (2) located in the field of a permanent magnet (3). At the balance beam (1), the force of the plunger coil, which is in proportion to the current, is balanced against the force of the dynamic backpressure. The backpressure is produced on the flapper plate (6) by the air jet leaving the nozzle (7).The air supply for the nozzle is taken from the pneumatic positioner (connection to the pneumatic input signal – input signal 27).

Fig. 7: Functional diagram of version for positioner

1 Balance beam2 Plunger coil3 Permanent magnet6 Flapper

7 Nozzle8 Adapter (3766)9 Adapter10 O-ring

11 Vent plug13 Flame protection filter14 Restriction with air

supply

2

3

1 7 6 13 8(9) 11

14

10

Positioner

Input signal 27Supply air

Type 6116

Page 14: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

14 EB 6116 EN

Positioner attachment

7.2 InstallationThe following mounting accessories are re-quired for attachment of a positioner:Type 3766-000 Positioner(model index .02 and higher)Direct attachment to the positioner according to Fig. 8 (for positioner with M20 x 1.5 elec-trical connection): order no. 1400-6227For older positioner models with PG 13.5: order no. 1400-6222Type 4765 PositionerNAMUR attachment to the yoke of a control valve according to Fig. 9: order no. 1400-6223Type 3760 PositionerAttachment to the yoke of the Type 3510 Mi-cro-flow Valve according to Fig. 10 or to the NAMUR rib: order no. 1400-6224

7.2.1 Mounting position of the converter

The converter must be mounted horizontally using the adapter with the cable entry facing sideways away from the positioner or the control valve.Make sure the O-ring (10) to seal the enclo-sure is inserted correctly.

7.3 Electrical connectionConnect as described in section 3.3 and Fig. 5.

7.4 Pneumatic connection

Note:Generally, the pneumatic connection of the i/p converter is established by connecting it to the pneumatic input of the positioner.

For direct attachment to the Type 3766-000 Positioner (Fig. 8), the converter is connect-ed using the hollow screw with grommet (6) and threaded bushing (5). The second screw (7) is used to vent the converter over the po-sitioner housing.Before attaching the adapter (8) to the posi-tioner, remove the M20 screw plug and the connecting nipple (input signal).For Type 4765 and Type 3760 Positioners (Fig. 9 and Fig. 10) the 1/8 NPT threaded connection of the adapter (9) needs to be fit-ted with a suitable cable gland and must be connected to the input connection (input sig-nal 27) of the positioner using a pipe or hose. Try to keep the connection as short and small as possible, e.g. 6 x 1 mm cross-section.The second bore (G ¼) serves as vent and needs to be equipped with the vent plug (11) included in the accessories.For all positioners, the connecting plate (1) must be removed from the bottom of the housing together with the sealing element (1.1) and replaced with the parts delivered (accessories). Make sure that the sealing ele-ment is positioned correctly. The filter must

Page 15: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 15

Positioner attachment

be located in front of the restriction of the connecting plate.For Types 4765 and 3766, attach the sili-cone hose (4). For Type 3760, put on the cap (4) included in the accessories.Refer to the mounting and operating instruc-tions of the corresponding positioner con-cerning the connections for supply air (SUP-PLY 8) and output (OUTPUT 36).

7.5 OperationAny adjustments to assign the travel of the control valve to the electric input signal must be made at the positioner separately from the converter module. The necessary steps are described in the corresponding mounting and operating instructions.

Page 16: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

16 EB 6116 EN

Positioner attachment

Fig. 8: Direct attachment to Type 3766 Positioner

1 Connecting plate1.1 Sealing element1.2 M3 x 16 screws4 Hose5 Threaded bushing6 Screw with grommet

7 Screw8 Adapter8.1 M4 x 12 screw8.2 M4 x 40 screw10 O-ring

Accessories (1400-6227)

8.1 10 6 8 8.2 5

6

7 6 4 1 1.1 1.2

Page 17: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 17

Positioner attachment

Fig. 9: NAMUR attachment to valve with Type 4765 Positioner

9 9.1 11 9.3 10 9.2

4 1 1.1 1.2

Positioner

1 Connecting plate1.1 Sealing element1.2 M3 x 16 screws4 Hose9 Adapter

9.1 M4 x 12 screw9.2 M4 x 40 screw9.3 M4 x 55 screw10 O-ring11 Vent plug

Accessories (1400-6223)

i/p converters

Page 18: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

18 EB 6116 EN

Positioner attachment

Fig. 10: Attachment to micro-flow valve with Type 3760 Positioner

1 Connecting plate1.1 Sealing element1.2 M3 x 16 screws4 Cap9 Adapter9.1 M4 x 12 screw9.2 M4 x 40 screw9.3 M4 x 55 screw10 O-ring11 Vent plug12 Hex bar (not required for

mounting to a NAMUR rib)

Accessories (1400-6224)

Positioner (opened)

10

9 9.1 11

9.3 9.2 12

4

1.2

1

1.1

Page 19: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 19

Troubleshooting

8 Troubleshooting

Problem Possible reasons Corrective action to be taken Comments

No output signal despite changing the input signal

Supply air not connected Check supply air connec-tion. See section 3.3.

Incorrect terminal assign-ment

Connect + and – termi-nals correctly. See sec-tion 3.3.

NOTICE i/p converter does not need any extra voltage.

Incorrect input signal Connect correct signal. Read nameplate:0 to 20 mA or 4 to 20 mA.

i/p converter constantly vents off air loudly

Connections for supply air and output at the i/p con-verter mixed up

Check pneumatic con-nections. See sec-tion 3.4.

i/p converter does not reach 100 % output e.g. 20 mA input: output only 70 % instead of 100 %

Supply pressure too lowSupply air must be 0.4 bar greater than the max. output signal.

Read nameplate: output 0.2 to 1 bar → Supply air at least 1.4 bar

Input signal faulty

Check whether the input signal at the terminals reaches 100 % (100 % is e.g. 20 mA in standard version and 12 mA for split-range operation)

NOTICE i/p converter has a load of– max. 6 V (standard version)– max. 7 V (Ex ia version)Check specification concern-ing permissible load at the source of the input signal.

Page 20: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

20 EB 6116 EN

Technical data

9 Technical dataNo explosion protection Type 6116-0With explosion protection Types 6116-1/-2/-3/-4/-5/-6/-7

Input 5) 4 to 20 mA, other signals on requestMinimum current >3.6 mA, load impedance ≤6 V (corresponding to 300 Ω at 20 mA)Versions with explosion protection: load impedance 7 V (corresponding to 350 Ω at

20 mA)Versions without switch-off electronics: Ri = 200 Ω ± 7.5 %

Output 5) 0.2 to 1 bar (3 to 15 psi) (Type 6109 i/p Converter Module)0.4 to 2 bar (6 to 30 psi) (Type 6112 i/p Converter Module)

Special ranges adjustable according to customer specifications:Output range = Initial value 10) + Span ∆p with Type 6112 i/p Module

0.1 to 0.4 bar + 0.75 to 1.0 bar Module A0.1 to 0.4 bar + 1.0 to 1.35 bar Module B0.1 to 0.4 bar + 1.35 to 1.81 bar Module C0.1 to 0.8 bar + 1.81 to 2.44 bar Module D0.1 to 0.8 bar + 2.44 to 3.28 bar Module E0.1 to 0.8 bar + 3.28 to 4.42 bar Module F0.1 to 1.2 bar + 4.42 to 5.94 bar Module G0.1 to 1.2 bar + 5.94 to 8.0 bar Module H 9)

Max. air output capacity 3)

2.0 m³/h with an output of 0.6 bar (0.2 to 1.0 bar)2.5 m³/h with an output of 1.2 bar (0.4 to 2.0 bar)8.5 m³/h with an output of 5.0 bar (0.1 to 8.0 bar)

Supply air At least 0.4 bar above the upper signal pressure range value, max. 10 bar without sup-ply pressure regulator, max. 6 bar for Ex d version

Air quality acc. to ISO 8573-1: 2001

Max. particle size and density: Class 4 · Oil content: Class 3 · Pressure dew point: Class 3 or at least 10 K below the lowest ambient temperature to be expected

Air consumption 2)0.08 mn³/h at 1.4 bar0.1 mn³/h at 2.4 bar

Max. 0.26 mn³/h at 10 bar

Characteristic Characteristic: Output linear to input

Hysteresis ≤0.3 % of upper range valueDeviation from terminal-based conformity

≤1 % of upper range value (for upper range values up to 5 bar); more exact values on request

≤1.5 % of upper range value (for upper range values above 5 bar)

Effect in % of the upper range value

Supply air: 0.1 %/0.1 bar 2)

Alternating load, supply air failure, interruption of the input current: < 0.3 %Ambient temperature: lower range value < 0.03 %/K, span < 0.03 %/K

Page 21: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 21

Technical data

1) Details (including electric specifications and installation instructions) can be found in the EC type ex-amination certificate

2) Measured with average output pressure3) Measured with 2 m hose with 4 mm inside diameter4) Observe recommended mounting position5) See section 2.2 on page 5 when combined with a positioner6) Devices without explosion protection7) Special versions down to –45 °C available on request8) Possible by using accessories9) Max. possible output pressure 8 bar10) Initial value raised up to 3.0 bar (special version)11) Metal cable glands and vent plugs are required for temperatures below –20 °C.

Technical data (continued)Dynamic responseLimiting frequency 5.3 HzPhase shift –130°

Variable position Max. 3.5 % depending on attachment: ±1 % in horizontal position (Type 6109)Max. 1 % depending on attachment: ±0.3 % in horizontal position (Type 6112)

Ambient conditions, degree of protection, compliance and weights

Storage temperature –45 to 80 °C

Ambient temperature 11)

With Type 6109 –30 to 70 °C 6) · –30 to 60 °C 1)

With Type 6112 –40 to 70 °C 6) 7) · –40 to 60 °C 1) 7)

Degree of protection IP 54 4), IP 65 8), NEMA 4

Compliance ·

Weight, approx. 0.85 kg

Explosion protection

ATEX, IECEx, ... See test certificates (Appendix)

Materials

Enclosure Die-cast aluminum, chromated and plastic coated

Cable gland (standard) Black polyamide (6 to 12 mm clamping range, –20 to 80 °C)

Page 22: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

22 EB 6116 EN

Article code

10 Article codeOrder no. Type 6116- ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...

Explosion protection

Without 0Intrinsically safe    II 2G Ex ia IIC T6 acc. to ATEX and GOST 1) 2)

1

Flameproof enclosure      II 2G Ex d IIC T6 acc. to ATEX and GOST 3) 2

Explosion-proof acc. to CSA and FM standards 5) 12) 3Intrinsically safe according to CSA and FM standards 1) 4 3Explosion proof Ex d IIC T6 acc. to IECEx TSA (Australia) 4) 6) 5Intrinsically safe Ex ia/Ex n IIC T6 acc. to IECEx TSA (Australia) 1) 6 2 2

Ex d IIC T6 acc. to JIS standard (Japan) 4) 7i/p converter module

Type 6109 4) 1 0 1 1Type 6112 2

Input

4 to 20 mA 0 14 to 12 mA 1) 11) 2 0 312 to 20 mA, without switch-off electronics 1) 7) 11) 2 0 40 to 20 mA, without switch-off electronics 7) 2 0 54 to 20 mA, without switch-off electronics 7) for positioner attachment 0 6

Output

0.2 to 1.0 bar 0 13 to 15 psi 0 20.4 to 2.0 bar 2 0 46 to 30 psi 2 0 5

Special ranges 8)

Initial value 0.1 to 0.4 bar; span 0.75 to 1.00 bar 2 1 1Initial value 0.1 to 0.4 bar; span 1.00 to 1.35 bar 2 1 2Initial value 0.1 to 0.4 bar; span 1.35 to 1.81 bar 2 1 3Initial value 0.1 to 0.8 bar; span 1.81 to 2.44 bar 2 1 4Initial value 0.1 to 0.8 bar; span 2.44 to 3.28 bar 2 1 5Initial value 0.1 to 0.8 bar; span 3.28 to 4.42 bar 2 1 6Initial value 0.1 to 1.2 bar; span 4.42 to 5.94 bar 2 1 7Initial value 0.1 to 1.2 bar; span 5.94 to 8.00 bar 2 1 8

Direction of action

Increasing/increasing 1Increasing/decreasing 1) 2

Electrical connection

½ - 14 NPT 1M 20 x 1.5 2

Pneumatic connection

Positioner attachment (without booster) 9) 0 6 0 1 1 0 0 0¼ -18 NPT 1ISO-228/1 - G ¼ 2

Degree of protection

Without (vent for positioner attachment) 0 6 0 1 1 0 0 0IP 54 1IP 65 2NEMA 4 10) 3

Output pressure gauge

Without 0

With 1) 1

Page 23: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 23

Article code

Order no. Type 6116- ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...

Temperature range

Tmin ≥ –25 °C (Type 6109 standard) 1 0Tmin ≥ –45 °C (Type 6112 subjected to routine test, metal cable gland) 2 1

Tmin ≥ –40 °C (Type 6112 standard) 2 2

Special version

Without 0 0 0IECEx approval, Ex d IIC T4/T5/T6 Gb (Type 6116-2) 2 5 1GOST approval, Ex ia or Ex d (Type 6116-1 or Type 6116-2) 2 5 2KCS approval, Korea (Type 6116-5) 2 6 2

1) Not for positioner attachment2) With degree of protection IP 54/IP 65 only3) Supply pressure max. 6 bar; output 5.6 bar4) Only with 0.2 to 1 bar/3 to 15 psi5) With ½ NPT electrical connection, degree of

protection NEMA 4 or positioner attachment6) With ½ NPT electrical connection, degree of

protection IP 65 or positioner attachment7) Without switch-off electronics and without

potentiometers for zero point and span correction

8) Specify setting range, e.g. set to 0.1 to 4 bar; output pressure max. 8 bar. Initial value raised up to 3.0 bar (special version)

9) Only with Ex d or explosion-proof according to CSA and FM standards

10) Only explosion-proof or intrinsically safe ac-cording to CSA and FM standards

11) 4 to 12 mA and 12 to 20 mA input only up to 4.0 bar span

12) Only with 0.2 to 1 bar (3 to 15 psi) and 0.4 to 2 bar (6 to 30 psi) output

Page 24: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

24 EB 6116 EN

Article code

Pressure gauge retrofit Order no. − Pressure gauge: 0.2 to 1.2 bar pressure range 0080-0185 − Pressure gauge: 0 to 6 bar pressure range 0080-0186 − Pressure gauge: 0 to 10 bar pressure range 8520-0032 − Pressure gauge: 0 to 6.6 MPa/0 to 6 kg/cm² pressure range 0800-0204 − For all pressure gauges: screw fitting 0250-1090

10.1 AccessoriesOrder no.

– Wall and pipe mounting 1400-6216– Mounting bracket (1.4301) for wall mounting 1400-7432– Mounting unit for Type 6116 in various versions M6116– Attachment to Type 3766 1) 1400-6227– Attachment to Type 4765 1) 1400-6223– Attachment to Type 3760 1) 1400-6224– Mounting on cast yoke according to NAMUR 1) 1400-6217– Mounting on rod-type yoke according to NAMUR 1) 1400-6218– G ¼ male connector to hose

4 mm inside diameter and 6 mm outside diameter, brass 8582-1452

– ¼ NPT male connector to hose4 mm inside diameter and 6 mm outside diameter, brass 8582-1523

– Cable gland M20 x 1.5, blue polyamide (6 to 12 mm clamping range) 8808-1012– Cable gland M20 x 1.5, nickel-plated brass

(6 to 12 mm clamping range) 1890-4875

– Cable gland M20 x 1.5, stainless steel 1.4305(8 to 14.5 mm clamping range) 8808-0160

– Vent plug G ¼, stainless steel 1.4305, IP 66 (–45 to +80 °C) 1790-7253– Vent plug G ¼, stainless steel 1.4305, NEMA 4 (–45 to +80 °C) 1790-96461) Only mounting part without assembly and without any possibly required piping. Order together with mounting unit

(M6116).

Page 25: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 25

Dimensions

11 Dimensions

Fig. 11: Wall and pipe mounting · Rear view including booster

Wall and pipe mounting · Order no. 1400-6216Ø40

88

127

75 220

Ø2" pipe

OUTPUT

Clamp for mounting on 2" pipe

M20 x 1.5/½-14 NPT for electrical connection

Pressure gauge

EXHAUST (venting/IP 65)

Wall mounting

30

Restriction

EXHAUST (venting/IP 54)

OUTPUTM6, 10 deep

All dimensions in mm

Rear view · i/p converter with booster

Page 26: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

26 EB 6116 EN

Dimensions

Fig. 12: Attachment to valve with cast yoke and rod-type yoke · Type 6116-xx06011x000xxxx with-out booster for positioner attachment

230113

200

40 95

117

Ø84 8

Attachment to a valve with cast yokeOrder no.: 1400-6217

Attachment to a valve with rod-type yokeOrder no.: 1400-6218

SUPPLY ¼-18 NPT or G ¼

All dimensions in mm

Type 6116-xx06011x000xxxx without booster for positioner attachment

120

93

92129

Attachment according to NAMUR with Type 4765/3760Accessories order numbersType 4765: 1400-6223Type 3760: 1400-6224

Combined with Type 3766-000 PositionerAccessories order no.: 1400-6227

Page 27: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 27

Page 28: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

28 EB 6116 EN

Page 29: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 29

Page 30: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

30 EB 6116 EN

Page 31: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 31

Page 32: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

32 EB 6116 EN

Page 33: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 33

Page 34: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

34 EB 6116 EN

Page 35: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 35

Page 36: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

36 EB 6116 EN

Page 37: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 37

Page 38: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

38 EB 6116 EN

Page 39: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

EB 6116 EN 39

Page 40: Type 6116 i/p Converter - SAMSON · PDF fileType 6116 i/p Converter. 2 EB 6116 EN Note on these mounting and operating instructions These mounting and operating instructions assist

SAMSON AG · MESS- UND REGELTECHNIKWeismüllerstraße 3 · 60314 Frankfurt am Main, GermanyPhone: +49 69 4009-0 · Fax: +49 69 [email protected] · www.samson.de EB 6116 EN 20

16-1

2-01

· En

glish