ANGLE AT ABOVE FINISH FLOOR ALUMINUM ARCHITECTURAL BLOCKING BUILT- UP ROOF CENTERLINE CONTROL JOINT CEILING CENTER CONCRETE CONCRETE MASONRY UNIT CONTINUOUS DIAMETER DOWN SPOUT DRAWING EXTERIOR EXISTING EACH EXPANSION JOINT ELECTRICAL ELEVATION ELEVATOR EQUIPMENT ELECTRIC WATER COOLER FINISH FLOOR DRAIN FACE OF FINISH FACE OF STUD FIRE RETARDENT FIELD VERIFY GAUGE GYPSUM BOARD HOLLOW METAL HORIZONTAL HEIGHT HEATING VENTILATION AIR-CONDITIONING INSIDE DIAMETER INSULATION JOINT LAVATORY MAXIMUM MECHANICAL MANUFACTURER MINIMUM MASONRY OPENING NOT IN CONTRACT NOMINAL NOT TO SCALE ON CENTER OUTSIDE DIAMETER OPENING OPPOSITE PAINT PAIR PLATE, PROPERTY LINE PRESSURE TREATED RADIUS REQUIRED ROOF DRAIN ROUGH OPENING SQUARE FEET SIMILAR SPECIFICATIONS STAINLESS STEEL STANDARD STRUCTURAL SUSPENDED TOP OF STEEL TOP OF WALL TYPICAL UNLESS NOTED OTHERIWSE VERTICAL VINYL COMPOSITION TILE WITH WATER CLOSET WATER RESISTANT WELDED WIRE FABRIC WOOD @ AFF ALUM ARCH BLKG BU CJ CLG CTR CONC CMU CONT DIA DS DWG EXT EXIST EA EJ ELEC EL ELEV EQUIP EWC FIN FD FOF FOS FR FV GA GYP BD HM HORIZ HT HVAC ID INSUL JT LAV MAX MECH MFR MIN MO NIC NOM NTS OC OD OPNG OPP P PR PL PT R, RAD REQD RD RO SF SIM SPEC SS STD STR SUSP TOS TOW TYP UNO VERT VCT W/ WC WR WWF WD C L PLAN DETAIL REFERENCE ROOM TAG SYMBOL WALL SECTION / DETAIL SECTION REFERENCE DOOR SYMBOL ALTERNATE WALL SECTION REFERENCE BUILDING SECTION REFERENCE FIRE RATED WALL SYMBOLS REVISION SYMBOL DETAIL NUMBER WHERE DETAIL IS SHOWN DETAIL NUMBER WHERE DETAIL IS SHOWN WALL SECTION / DETAIL NUMBER WHERE WALL SECTION / DETAIL IS SHOWN ROOM NAME ROOM NUMBER DOOR NUMBER FRAME TYPE DOOR TYPE DIMENSION TO FACE OR EDGE DIMENSION TO CENTERLINE ELEVATION ABOVE SEA LEVEL ITEM IDENTIFIED WINDOW / STOREFRONT / CURTAIN WALL / LOUVER TYPE PARTITION TYPE FIRE EXTINGUISHER RECESSED IN WALL CABINET FIRE EXTINGUISHER MOUNTED ON WALL BRACKETS FD - FLOOR DRAIN BUILDING SECTION NUMBER WHERE BUILDING SECTION IS SHOWN WALL SECTION / DETAIL NUMBER WHERE WALL SECTION / DETAIL IS SHOWN TOP = TOP HALF OF WALL FOR PARTICULAR LEVEL BOT = BOTTOM HALF OF WALL FOR PARTICULAR LEVEL WALL SECTION / DETAIL NUMBER WHERE WALL SECTION / DETAIL IS SHOWN SIM = SIMILAR CONDITION OH = OPPOSITE HAND CONDITION OPP = OPPOSITE HAND CONDITION ROT = ROTATED CONDITION ONE-HOUR FIRE-RATED WALL ASSEMBLY TWO-HOUR FIRE-RATED WALL ASSEMBLY FOUR-HOUR FIRE-RATED WALL ASSEMBLY SEE PARTITION TYPES FOR UL DESIGN NO'S. BRICK VENEER / CMU CONTROL JOINT TOILET / LOCKER ROOM ACCESSORY SYMBOL GYPSUM BOARD CONTROL JOINT INDICATES A CHANGE IN ORIENTATION OF CUT PLANE (INTERIOR ELEVATION ONLY) CLOUD AROUND REVISION EXTERIOR WALL / ROOF CONSTRUCTION TYPE TITLE SCALE: 1'-0" = 1'-0" REF: 1/A1.1 1 A1.1 LOCATION OF DETAIL CUT (AS SHOWN) 1 A1.1 1 A1.1 1 BOT TOP SIM 001A DX FX S1 1A FE-C FE-C 100 RECEPTION 1 A1.1 1 A1.1 1 A1.1 1 A1.1 EXPANSION JOINT TYPE A 26 26 95 26 20 85 385 77 20 95 26 CAROLINA GEORGIA NORTH ATLANTIC OCEAN COLUMBIA STATE OF SOUTH CAROLINA MAP NORTH CLEARANCES TO COMPLY WITH LATEST VERSION OF ANSI A117.1 ADOPTED BY GOVERNING BODY NOTE: DIMENSIONS AND CLEARANCES SHOWN MUST BE PROVIDED AT ALL DOORS. CONTRACTOR SHALL REVIEW FIELD LAYOUT AND CONFIRM THAT ALL OF THE APPROPRIATE CLEARANCES ARE PROVIDED. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION. ANY REMEDIAL WORK THAT SHOULD HAVE BEEN AVOIDED BY BRINGING DISCREPANCIES TO THE ARCHITECT'S ATTENTION SHALL BE AT THE CONTRACTOR'S EXPENSE. TWO HINGED DOORS IN A SERIES HINGE SIDE APPROACHES FRONT APPROACHES LATCH SIDE APPROACHES PULL SIDE 36" MIN. 42" MIN. 60" MIN. PULL SIDE PUSH SIDE PUSH SIDE PUSH SIDE PULL SIDE 60" MIN. 18" MIN. 48" MIN. 24" MIN. 54" MIN. IF DOOR HAS CLOSER 24" MIN. 42" MIN. 48" MIN. IF DOOR HAS CLOSER 12" MIN. IF DOOR HAS BOTH CLOSER AND LATCH 52" MIN. 12" MIN. 42" MIN. 48" MIN. IF DOOR HAS IF BOTH CLOSER AND LATCH 48" MIN. 60" MIN. 48" MIN. 60" MIN. PUSH / PUSH PUSH / PULL 60" MIN. PULL / PUSH 64" MIN. (W/ 54" CLEAR) (W/ 60" CLEAR) IF BOTH CLOSER AND LATCH 22" MIN. 54" MIN. COMPACTED EARTH POROUS FILL (STONE OR GRAVEL) CONCRETE CONCRETE MASONRY UNIT (CMU) BRICK SAND, PLASTER, CEMENT, GROUT STEEL WOOD (ROUGH) WOOD (FINISHED) PLYWOOD BATT INSULATION GYPSUM BOARD RIGID INSULATION EXISTING BUILDING GENERAL CODE INFORMATION: (BASED ON DRAWINGS PROVIDED BY USC, INCLUDING RECENT RENOVATION DOCUMENTATION, AND SITE REVIEW) ORIGINALLY DESIGNED AND CONSTRUCTED IN 1967 UNDER CURRENT CODE AT THE TIME RENOVATIONS: 1991 (TO ACADEMIC CENTER) 2004 (REPLACEMENT OF FIRE-RETARDANT TREATED WOOD TRUSSES) 2010 (GENERAL RENOVATIONS) EXISTING BUILDING OCCUPANCY: BUSINESS (B) EXISTING CONSTRUCTION CLASSIFICATION: ASSUMED TYPE IIIB, UNPROTECTED - EXTERIOR WALLS AND INTERIOR CMU WALLS - NON-COMBUSTIBLE - WOOD ROOF TRUSSES - COMBUSTIBLE - BUILDING NON-SPRINKLERED, WITH FIRE ALARM - 1-HOUR FIRE RATED CORRIDORS EXISTING AND TO BE MAINTAINED - NEW 1-HOUR RATED PARTITION BASIS FOR DESIGN: UL DESIGN U465 WHERE INDICATED TO BE 1-HOUR FIRE-RATED ON PLANS PROJECT SCOPE RELEVANT CODE INFORMATION: SECOND FLOOR (OUTDOOR VOLLEYBALL TEAM SPACE) OVERALL BUILDING FLOOR AREA = 13,070 GSF OVERALL SECOND FLOOR AREA = 6,535 GSF VOLLEYBALL TEAM SPACE AREA AREA PER PERSON OCCUPANT LOAD BUSINESS 2,127 SF 100 GROSS 22 STORAGE 148 SF 300 GROSS 1 *ACCESSORY USE TOTAL: 2,275 SF 23 - DISTANCE BETWEEN EXITS = MIN. ONE-HALF LENGTH OF MAX. OVERALL DIAGONAL (NON-SPRINKLERED) (PER TABLE 1007.1.1) - MAX. COMMON PATH OF EGRESS TRAVEL DISTANCE = 100' (NON-SPRINKLERED, OCCUPANT LOAD < 30) (PER TABLE 1006.2.1) - MAX. EXIT ACCESS TRAVEL DISTANCE = 200' (NON-SPRINKLERED) (PER TABLE 1017.2) PROJECT DESIGNED IN ACCORDANCE WITH: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. INTERNATIONAL BUILDING CODE (IBC), 2015 EDITION INTERNATIONAL EXISTING BUILDING CODE (IEBC), 2015 EDITION INTERNATIONAL FIRE CODE (IFC), 2015 EDITION INTERNATIONAL ENERGY CONSERVATION CODE (IECC), 2009 Edition INTERNATIONAL FUEL GAS CODE (IFGC), 2015 EDITION INTERNATIONAL MECHANICAL CODE (IMC), 2015 EDITION INTERNATIONAL PLUMBING CODE (IPC), 2015 EDITION with the following insertions: 1. Section 305.4.1, insert “18” and insert “18” 2. Section 903.1, insert “8” INTERNATIONAL PRIVATE SEWAGE DISPOSAL CODE (IPSDC), 2015 EDITION INTERNATIONAL PROPERTY MAINTENANCE CODE (IPMC), 2015 EDITION NATIONAL ELECTRICAL CODE (NEC) [NFPA-70], 2014 EDITION NATIONAL ELECTRICAL SAFETY CODE, IEEE-C2-2012 EDITION AMERICAN NATIONAL STANDARDS INSTITUTE, INC. (ANSI) - A117.1 - 2017, ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES STATE FIRE MARSHAL RULES, REGULATIONS, AND POLICIES - LATEST EDITION STATE OF SC TELEPHONE EQUIPMENT ROOM AND COMMUNICATIONS/DATA SYSTEMS POLICY AS FORMULATED BY THE DSIT ARCHITECTURAL MECHANICAL PLUMBING ELECTRICAL T1.1 TITLE SHEET, CODE REVIEW & INDEX TO DRAWINGS X1.1 LIFE SAFETY PLAN A1.1 FIRST FLOOR PLANS A1.2 SECOND FLOOR PLANS A2.1 ENLARGED REFLECTED CEILING PLANS A2.2 ENLARGED CEILING DIMENSION PLAN & DETAILS A3.1 ENLARGED PLANS, PARTITION TYPES & DETAILS A4.1 INTERIOR ELEVATIONS A5.1 DOOR SCHEDULE, DOOR AND FRAME TYPES & PLAN DETAILS A5.2 CASEWORK & LOCKER DETAILS A6.1 ENLARGED FINISH PLANS & SCHEDULES M1.1 SECOND FLOOR PLANS M2.1 DETAILS, NOTES, SCHEDULES AND LEGEND P1.1 SECOND FLOOR PLANS P2.1 DETAILS, NOTES, SCHEDULE AND LEGEND E0.1 ELECTRICAL NOTES & LEGENDS E1.0 ELECTRICAL DEMOLITION PLANS E1.1 FIRST AND SECOND FLOOR LIGHTING PLANS E1.2 SECOND FLOOR POWER RENOVATION PLAN PROJECT NO. DATE DRAWING NO. DRAWN BY: CHECKED BY: THIS DRAWING AND THE DESIGN THEREON ARE THE PROPERTY OF THE GARVIN DESIGN GROUP, INC. THE REPRODUCTION, COPYING, OR USE OF THIS DRAWING W ITHOUT THE WRITTEN CONSENT OF THE GARVIN DESIGN GROUP IS PROHIBITED AND ANY INFRINGEMENT WILL BE SUBJECT TO LEGAL ACTION. @2003 GARVIN DESIGN GROUP, INC. PROJECT TITLE A/E SEAL A/E SEAL DRAWING TITLE 5/15/2018 3:05:46 PM T1.1 U479.18 05.15.18 TITLE SHEET, CODE REVIEW & INDEX TO DRAWINGS Author Checker OUTDOOR VOLLEYBALL LOCKER/FILM ROOM RENOVATION 107 South Marion Street Columbia, SC 29208 107 SOUTH MARION STREET COLUMBIA, SOUTH CAROLINA 29208 15 MAY 2018 BID DOCUMENTS ABBREVIATIONS ARCHITECTURAL SYMBOLS LOCATION MAP MANEUVERING CLEARANCES MATERIAL DESIGNATIONS Architect's Project Number: U479.18 USC Project Number: H27-Z378 OUTDOOR VOLLEYBALL LOCKER/FILM ROOM RENOVATION UNIVERSITY OF SOUTH CAROLINA CODE INFORMATION - OUTDOOR VOLLEYBALL CODE INFORMATION - GENERAL REVISIONS NO. NAME DATE INDEX TO DRAWINGS

UNIVERSITY OF SOUTH CAROLINA OUTDOOR VOLLEYBALL …

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

ANGLEATABOVE FINISH FLOORALUMINUMARCHITECTURALBLOCKINGBUILT- UP ROOFCENTERLINECONTROL JOINTCEILINGCENTERCONCRETECONCRETE MASONRY UNITCONTINUOUSDIAMETERDOWN SPOUTDRAWINGEXTERIOREXISTINGEACHEXPANSION JOINTELECTRICALELEVATIONELEVATOREQUIPMENTELECTRIC WATER COOLERFINISHFLOOR DRAINFACE OF FINISHFACE OF STUDFIRE RETARDENTFIELD VERIFYGAUGEGYPSUM BOARDHOLLOW METALHORIZONTALHEIGHTHEATING VENTILATION AIR-CONDITIONINGINSIDE DIAMETERINSULATIONJOINTLAVATORYMAXIMUMMECHANICALMANUFACTURERMINIMUMMASONRY OPENINGNOT IN CONTRACTNOMINALNOT TO SCALEON CENTEROUTSIDE DIAMETEROPENINGOPPOSITEPAINTPAIRPLATE, PROPERTY LINEPRESSURE TREATEDRADIUSREQUIREDROOF DRAINROUGH OPENING SQUARE FEETSIMILARSPECIFICATIONSSTAINLESS STEELSTANDARDSTRUCTURALSUSPENDEDTOP OF STEELTOP OF WALLTYPICALUNLESS NOTED OTHERIWSEVERTICALVINYL COMPOSITION TILEWITHWATER CLOSETWATER RESISTANTWELDED WIRE FABRICWOOD

@AFFALUMARCHBLKGBU

CJCLGCTRCONCCMUCONTDIADSDWGEXTEXISTEAEJELECELELEVEQUIPEWCFINFDFOFFOSFRFVGAGYP BDHMHORIZHTHVACIDINSULJTLAVMAXMECHMFRMINMONICNOMNTSOCODOPNGOPPPPRPLPTR, RADREQDRDRO SFSIMSPECSSSTDSTRSUSPTOSTOWTYPUNOVERTVCTW/WCWRWWFWD

CL

PLAN DETAIL REFERENCE

ROOM TAG SYMBOL

WALL SECTION / DETAIL SECTION REFERENCE

DOOR SYMBOL

ALTERNATE WALL SECTION REFERENCE

BUILDING SECTION REFERENCE

FIRE RATED WALL SYMBOLS

REVISION SYMBOL

DETAIL NUMBER

WHERE DETAIL IS SHOWN

DETAIL NUMBERWHERE DETAIL IS SHOWN

WALL SECTION / DETAIL NUMBERWHERE WALL SECTION / DETAIL IS SHOWN

ROOM NAME

ROOM NUMBER

DOOR NUMBER

FRAME TYPE

DOOR TYPE

DIMENSION TO FACE OR EDGE

DIMENSION TO CENTERLINE

ELEVATION ABOVE SEA LEVELITEM IDENTIFIED

WINDOW / STOREFRONT / CURTAIN WALL / LOUVER TYPE

PARTITION TYPE

FIRE EXTINGUISHER RECESSED IN WALL CABINET

FIRE EXTINGUISHER MOUNTED ON WALL BRACKETS

FD - FLOOR DRAIN

BUILDING SECTION NUMBERWHERE BUILDING SECTION IS SHOWN

WALL SECTION / DETAIL NUMBERWHERE WALL SECTION / DETAIL IS SHOWN

TOP = TOP HALF OF WALL FOR PARTICULAR LEVEL

BOT = BOTTOM HALF OF WALL FOR PARTICULAR LEVEL

WALL SECTION / DETAIL NUMBERWHERE WALL SECTION / DETAIL IS SHOWN

SIM = SIMILAR CONDITIONOH = OPPOSITE HAND CONDITIONOPP = OPPOSITE HAND CONDITIONROT = ROTATED CONDITION

ONE-HOUR FIRE-RATED WALL ASSEMBLY

TWO-HOUR FIRE-RATED WALL ASSEMBLY

FOUR-HOUR FIRE-RATED WALL ASSEMBLY

SEE PARTITION TYPES FOR UL DESIGN NO'S.

BRICK VENEER / CMU CONTROL JOINT

TOILET / LOCKER ROOM ACCESSORY SYMBOL

GYPSUM BOARD CONTROL JOINT

INDICATES A CHANGE IN ORIENTATION OF CUT PLANE(INTERIOR ELEVATION ONLY)

CLOUD AROUND REVISION

EXTERIOR WALL / ROOF CONSTRUCTION TYPE

TITLESCALE: 1'-0" = 1'-0" REF: 1/A1.1

1A1.1

LOCATION OF DETAIL CUT (AS SHOWN)

1A1.1

1A1.1

1

BOT

TOP

SIM

001ADX FX

S1

1A

FE-C FE-C

100RECEPTION

1A1.1

1A1.1

1A1.1

1A1.1

EXPANSION JOINT TYPEA

26

26

95

2620

85 38577

20

95

26 CAROLINA

GEORGIA

NORTH

ATLANTIC OCEAN

COLUMBIA

STATE OFSOUTH CAROLINA

MAPNORTH

CLEARANCES TO COMPLY WITH LATEST VERSION OF ANSI A117.1 ADOPTED BY GOVERNING BODY

NOTE: DIMENSIONS AND CLEARANCES SHOWN MUST BE PROVIDED AT ALL DOORS. CONTRACTOR SHALL REVIEW FIELD LAYOUT AND CONFIRM THAT ALL OF THE APPROPRIATE CLEARANCES ARE PROVIDED. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION. ANY REMEDIAL WORK THAT SHOULD HAVE BEEN AVOIDED BY BRINGING DISCREPANCIES TO THE ARCHITECT'S ATTENTION SHALL BE AT THE CONTRACTOR'S EXPENSE.

TWO HINGED DOORS IN A SERIES

HINGE SIDE APPROACHES

FRONT APPROACHES

LATCH SIDE APPROACHES

PULL SIDE

36" MIN.

42" MIN.

60" M

IN.

PULL SIDE

PUSH SIDE

PUSH SIDE

PUSH SIDE

PULL SIDE

60" M

IN.

18" MIN.

48" M

IN.

24" MIN.54" M

IN.

IF D

OOR

HAS

CLOS

ER

24" MIN.

42" M

IN.

48" M

IN.

IF D

OOR

HAS

CLOS

ER

12" MIN.IF DOOR HAS BOTHCLOSER AND LATCH

52" M

IN.

12" MIN.

42" M

IN.

48" M

IN. IF

DOO

R HA

SIF

BOT

H CL

OSER

AND

LATC

H

48" M

IN.

60" MIN.

48" M

IN.

60" MIN.

PUSH / PUSH

PUSH / PULL

60" MIN.

PULL / PUSH

64" M

IN.

(W/ 54" CLEAR)

(W/ 60" CLEAR)

IF BOTH CLOSER AND LATCH

22" MIN.54" M

IN.

COMPACTED EARTH

POROUS FILL (STONE OR GRAVEL)

CONCRETE

CONCRETE MASONRY UNIT (CMU)

BRICK

SAND, PLASTER, CEMENT, GROUT

STEEL

WOOD (ROUGH)

WOOD (FINISHED)

PLYWOOD

BATT INSULATION

GYPSUM BOARD

RIGID INSULATION

EXISTING BUILDING GENERAL CODE INFORMATION: (BASED ON DRAWINGS PROVIDED BY USC, INCLUDING RECENT RENOVATION DOCUMENTATION, AND SITE REVIEW)

ORIGINALLY DESIGNED AND CONSTRUCTED IN 1967 UNDER CURRENT CODE AT THE TIME

RENOVATIONS:1991 (TO ACADEMIC CENTER)2004 (REPLACEMENT OF FIRE-RETARDANT TREATED WOOD TRUSSES)2010 (GENERAL RENOVATIONS)

EXISTING BUILDING OCCUPANCY: BUSINESS (B)

EXISTING CONSTRUCTION CLASSIFICATION: ASSUMED TYPE IIIB, UNPROTECTED

- EXTERIOR WALLS AND INTERIOR CMU WALLS - NON-COMBUSTIBLE- WOOD ROOF TRUSSES - COMBUSTIBLE- BUILDING NON-SPRINKLERED, WITH FIRE ALARM - 1-HOUR FIRE RATED CORRIDORS EXISTING AND TO BE MAINTAINED - NEW 1-HOUR RATED PARTITION BASIS FOR DESIGN: UL DESIGN U465 WHERE INDICATED TO BE 1-HOUR FIRE-RATED ON PLANS

PROJECT SCOPE RELEVANT CODE INFORMATION: SECOND FLOOR (OUTDOOR VOLLEYBALL TEAM SPACE)

OVERALL BUILDING FLOOR AREA = 13,070 GSF

OVERALL SECOND FLOOR AREA = 6,535 GSF

VOLLEYBALL TEAM SPACE AREA AREA PER PERSON OCCUPANT LOAD

BUSINESS 2,127 SF 100 GROSS 22

STORAGE 148 SF 300 GROSS 1*ACCESSORY USE

TOTAL: 2,275 SF 23

- DISTANCE BETWEEN EXITS = MIN. ONE-HALF LENGTH OF MAX. OVERALL DIAGONAL (NON-SPRINKLERED) (PER TABLE 1007.1.1)- MAX. COMMON PATH OF EGRESS TRAVEL DISTANCE = 100' (NON-SPRINKLERED, OCCUPANT LOAD < 30) (PER TABLE 1006.2.1)- MAX. EXIT ACCESS TRAVEL DISTANCE = 200' (NON-SPRINKLERED) (PER TABLE 1017.2)

PROJECT DESIGNED IN ACCORDANCE WITH:

1.2.3.4.5.6.7.

8.9.10.11.12.

13.14.

INTERNATIONAL BUILDING CODE (IBC), 2015 EDITIONINTERNATIONAL EXISTING BUILDING CODE (IEBC), 2015 EDITIONINTERNATIONAL FIRE CODE (IFC), 2015 EDITIONINTERNATIONAL ENERGY CONSERVATION CODE (IECC), 2009 EditionINTERNATIONAL FUEL GAS CODE (IFGC), 2015 EDITIONINTERNATIONAL MECHANICAL CODE (IMC), 2015 EDITIONINTERNATIONAL PLUMBING CODE (IPC), 2015 EDITION with the following insertions:

1. Section 305.4.1, insert “18” and insert “18”2. Section 903.1, insert “8”

INTERNATIONAL PRIVATE SEWAGE DISPOSAL CODE (IPSDC), 2015 EDITIONINTERNATIONAL PROPERTY MAINTENANCE CODE (IPMC), 2015 EDITIONNATIONAL ELECTRICAL CODE (NEC) [NFPA-70], 2014 EDITIONNATIONAL ELECTRICAL SAFETY CODE, IEEE-C2-2012 EDITIONAMERICAN NATIONAL STANDARDS INSTITUTE, INC. (ANSI) - A117.1 - 2017, ACCESSIBLE AND USABLE BUILDINGS AND FACILITIESSTATE FIRE MARSHAL RULES, REGULATIONS, AND POLICIES - LATEST EDITIONSTATE OF SC TELEPHONE EQUIPMENT ROOM AND COMMUNICATIONS/DATA SYSTEMS POLICY AS FORMULATED BY THE DSIT

ARCHITECTURAL

MECHANICAL

PLUMBING

ELECTRICAL

T1.1 TITLE SHEET, CODE REVIEW & INDEX TO DRAWINGS

X1.1 LIFE SAFETY PLAN

A1.1 FIRST FLOOR PLANSA1.2 SECOND FLOOR PLANSA2.1 ENLARGED REFLECTED CEILING PLANSA2.2 ENLARGED CEILING DIMENSION PLAN & DETAILSA3.1 ENLARGED PLANS, PARTITION TYPES & DETAILSA4.1 INTERIOR ELEVATIONSA5.1 DOOR SCHEDULE, DOOR AND FRAME TYPES & PLAN DETAILSA5.2 CASEWORK & LOCKER DETAILSA6.1 ENLARGED FINISH PLANS & SCHEDULES

M1.1 SECOND FLOOR PLANSM2.1 DETAILS, NOTES, SCHEDULES AND LEGEND

P1.1 SECOND FLOOR PLANSP2.1 DETAILS, NOTES, SCHEDULE AND LEGEND

E0.1 ELECTRICAL NOTES & LEGENDSE1.0 ELECTRICAL DEMOLITION PLANSE1.1 FIRST AND SECOND FLOOR LIGHTING PLANSE1.2 SECOND FLOOR POWER RENOVATION PLAN

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

5/15

/201

8 3:

05:4

6 PM

T1.1U479

.18

05.1

5.18

TITLE

SHE

ET, C

ODE

REVI

EW &

INDE

X TO

DRA

WIN

GS

Auth

or

Chec

ker

OUTD

OOR

VOLL

EYBA

LL LO

CKER

/FILM

ROOM

REN

OVAT

ION

107

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

08

107 SOUTH MARION STREET COLUMBIA, SOUTH CAROLINA 29208

15 MAY 2018BID DOCUMENTS

ABBREVIATIONS ARCHITECTURAL SYMBOLS

LOCATION MAP MANEUVERING CLEARANCES

MATERIAL DESIGNATIONS

Architect's Project Number: U479.18USC Project Number: H27-Z378

OUTDOOR VOLLEYBALL LOCKER/FILM ROOM RENOVATIONUNIVERSITY OF SOUTH CAROLINA

CODE INFORMATION - OUTDOOR VOLLEYBALL

CODE INFORMATION - GENERAL

REVI

SIO

N S

NO.

NAM

EDA

TE

INDEX TO DRAWINGS

STAIR 2ND FLRST01

WOMEN'S RESTROOM202

FE-C

12

332

112' TO RATED STAIR

332

COMM./ELEC.215

STORAGE201B

WOMEN'S LOCKERROOM

203

STORAGE203B

TEAM LOUNGE201

CORRIDORH202

CORRIDORH204

58' OVERALL DIAGONAL

48' - 0 3/8" > 1/2 DIAGONAL

11

136' TO BOTTOM OF OPEN / NON-RATED STAIR

40' TO RATED STAIR

.

.

.

.

.

NOT IN PROJECT SCOPE

FURNITURE (N.I.C.)

FURNITURE (N.I.C.)

FURNITURE (N.I.C.)

1. SEE CODE RELATED INFORMATION ON SHEET T1.1

2. BUILDING NON-SPRINKLERED: SEE T1.1

3. MAXIMUM TRAVEL DISTANCE TO AN EXIT = 200 FEET

4. EXIT SIGNS ALSO SHOWN ON RCP AND ELECTRICAL DRAWINGS

FIRE EXTINGUISHER WALL CABINET, SEE SPECS.

ONE-HOUR FIRE-RATED WALL ASSEMBLY*SEE PARTITION TYPES FOR UL DESIGN NO'S.

FE-C

EXIT LIGHTS - SEE ELECTRICAL DRAWINGS FOR LOCATIONS

REQUIRED EGRESS WIDTH AT DOOR, IN INCHESEGRESS WIDTH PROVIDED AT DOOR, IN INCHES

EGRESS WIDTH SYMBOLS

534

4' - 0"(3'-8") REQUIRED EGRESS WIDTH AT PASSAGE

EGRESS WIDTH PROVIDED AT PASSAGE

23 # OF PEOPLE/DIRECTION OF TRAVEL

[9,960 SF = 50P] NET (OR GROSS) SQ. FT./# OF PEOPLE (OCCUPANCY OF SPACE)

TRAVEL DISTANCE LEGEND246'-1"

TRAVEL DIST.

200' TO EXIT FROM REMOTE CORNER

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

5/15

/201

8 3:

05:5

2 PM

X1.1U479

.18

05.1

5.18

LIFE

SAFE

TY P

LAN

Auth

or

Chec

ker

OUTD

OOR

VOLL

EYBA

LL LO

CKER

/FILM

ROOM

REN

OVAT

ION

107

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

08

REVI

SIO

N S

NO.

NAM

EDA

TE

REFERENCED ON:

1/4" = 1'-0"X1.1 A3.11 SECOND FLOOR LIFE SAFETY PLAN

GENERAL NOTES - LIFE SAFETY

LEGEND - LIFE SAFETY

UP

VESTIBULEV101

LOBBYV102

STAIR 1ST FLRST01

A1.13

A1.12

A6.12

NOT IN PROJECT SCOPE

NOT IN PROJECT SCOPE

EXTERIOR COURTYARD CORRIDORH101

FUTURE WALL GRAPHIC (N.I.C)

CORRIDORH101

LOBBYV102

VESTIBULEV101

FUTURE WALL GRAPHIC (N.I.C)

SEE FINISH PLAN AND SCHEDULE FOR NEW FINISHES

ELEC.113

STAIR 1ST FLRST01STAIR 1ST FLR

ST01

1

2

2

3

3

3

LOBBYV102

VESTIBULEV101

CORRIDORH101

ELEC.113

EXSITING WALL TO REMAIN

EXISTING WALL TO BE DEMOLISHED

EXISTING DOOR TO BE DEMOLISHED

EXISTING DOOR TO BE REMAIN

EXISTING WINDOW TO BE DEMOLISHED

EXISTING WINDOW TO REMAIN

GRAY SHADED AREA NOT IN PROJECT SCOPE

1

2

3

EXISTING DISPLAY & CASEWORK TO BE REMOVED

PREPARE ALL LOBBY WALLS TO BE REPAINTED / RE-COVERED

REPAIR/LEVEL/PATCH EXISTING VCT FLOORING AS REQUIRED FOR INSTALLATION AND ADHESION OF NEW FLOORING FINISHES

STAIR 1ST FLRST01

CORRIDORH101

LOBBYV102

VESTIBULEV101

1

1

1

2

ELEC.113

NOTE:REMOVAL AND REPLACEMENT OF CEILNG IN THIS AREA FOR WASTE PIPING ROUTING TO BE INCLUDED IN BASE BID. REFERENCE PLUMBING DWGS. FOR EXTENT.

1 REPLACE ALL CEILING TILE, GRID TO REMAIN. SEE SPECS AND FINISH SCHEDULE. ALL LIGHTING, EXIT DEVICES, AND OTHER ELECTRICAL AND MECHANICAL DEVICES TO REMAIN. REMOVE AND RE-SET IN NEW CEILING TILE AS REQUIRED. SEE ELEC. AND MECH. DWGS. FOR ADDITIONAL INFORMATION. CONTRACTOR TO SALVAGE AND SAVE ALL BATT INSULATION ON TOP OF CEILING TILES AND RE-INSTALL ON NEW CEILNG TILE AND GYPSUM BOARD SOFFITS AND CEILINGS. CONTRACTOR IS RESPONSIBLE FOR ADDING ADDITIONAL BATT INSULATION OF SAME TYPE, THICKNESS AND R-VALUE ABOVE CEILINGS TO CREATE A CONTINUOUS INSULATION LAYER OVER ENTIRE RENOVATION AREA.

REPAIR AND REPAINT EXISTING GWB SOFFIT AFTER REMOVAL OF EXISTING DISPLAY CASE.

2

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

5/15

/201

8 3:

04:5

9 PM

A1.1U479

.18

05.1

5.18

FIRST

FLOO

R PL

ANS

Auth

or

Chec

ker

OUTD

OOR

VOLL

EYBA

LL LO

CKER

/FILM

ROOM

REN

OVAT

ION

107

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

08

REVI

SIO

N S

NO.

NAM

EDA

TE

REFERENCED ON:

1/8" = 1'-0"A1.11 FIRST FLOOR REFERENCE PLAN

REFERENCED ON:

3/8" = 1'-0"A1.1 A1.13 FIRST FLOOR ENLARGED RENOVATION PLAN

REFERENCED ON:

3/8" = 1'-0"A1.1 A1.12 FIRST FLOOR ENLARGED DEMOLITION PLAN

LEGEND - DEMOLITION PLAN

KEYNOTES - DEMO PLAN FIRST FLOOR

REFERENCED ON:

1/4" = 1'-0"A1.14 FIRST FLOOR REFECTED CEILING PLAN

KEYNOTES - REFLECTED CEILING PLAN FIRST FLOOR

ALTERNATE NO. 1ALL FIRST FLOOR WORK REFERENCED ON THIS SHEET IS PART OF ALTERNATE NO. 1, UNLESS NOTED OTHERWISE

UP

UP

EXISTING STEP TO BE MOVED

NOT IN PROJECT SCOPE

NOT IN PROJECT SCOPE

NOT IN PROJECT SCOPE

2

2

4

4

1

1 1 1 11

1

3 3 3 3 3

46

7

222

2

6

7

DEMO TILE AND SETTING BED UP TO NEW STEP LOCATION

8

33

NOT IN PROJECT SCOPE

CORRIDORH202

STAIR 2ND FLRST01

CORRIDORH204

COMM./ELEC.215

DISASSEMBLE WING PARTITIONS AND SEAT AND STORE FOR RE-USE. RE-INSTALL TO NEW METAL STUD/GWB/CERAMIC TILE WALL AT SAME LOCATION

10

9

56 7

1211

13

13

A4.1 A4.1

2

3

COMM./ELEC.215

WOMEN'S RESTROOM202

STORAGE201B

STORAGE203B

23' - 0 3/8"

WOMEN'S LOCKERROOM

203

1' - 1 3/8"

110.00°

6

1

A4.1

9

12

11

12

12

6

3 3

4

4

8

4

4

3

2 2 2 27 7 7 7

5

9

7

NOT IN PROJECT SCOPE

NOT IN PROJECT SCOPE

NOT IN PROJECT SCOPE

A3.11

M3AM3A

M3C

M3A

M3A

M3A

204AD1 F1

201AD1 EX203A

D1 EX

M3C

M3C

M3C

M3C

202AD2 -

206AD1 F1

202BD1 F1

A4.1

4

5

7 8

R 10' - 0"

19' - 0" 7 3/4"

10

4A5.2

A3.12

9' - 2

"

3' - 7"

2A5.2

M2C

M2C

A5.13

STAIR 2ND FLRST01

A5.14

TYP.

10

10

10

A5.14

Sim

O.H. TYP.

REFRIGERATOR (N.I.C.)

6' - 3 1/4" 8' - 10 1/4"

10' - 6 5/8"

M3A

M3A

M2C

M2C

3' - 5 1/2" 1' - 3" 2' - 4"

2' - 1

"

M2CM2C

M3CM3C

M3CM3C

M2C

M2C

M2C

15' -

7"1'

- 1 7

/8"

M2C

M2C

M3C

6"

6' - 1

0"

A5.12 10

M3C

215AD1 EX

CORRIDORH204CORRIDOR

H202

1

77

4" 8' - 0" 4"

5

9

9

11

11

14' -

0"1'

- 0 1

/8"

1' - 1

" M2C

M3C

M3C7

13

1' - 0"

4

A2.2

M2C

M2C

M2C

A5.16

NOT IN PROJECT SCOPE

A5.15

M3C

M3B*

FURNITURE (N.I.C.)

FURNITURE (N.I.C.)

FURNITURE (N.I.C.)

FURNITURE (N.I.C.)

A5.17

A5.17

Sim

O.H.

SEE T1.1 FOR MINIMUM REQUIRED ADA MANEUVERING CLEARANCES. VERIFY EXACT FEB AND FEC LOCATIONS WITH ARCHITECT.

SEE T1.1 FOR REQUIRED UL ASSEMBLIES OF ALL BUILDING SYSTEMS. ALL PENETRATIONS THROUGH RATED WALL AND FLOOR ASSEMBLIES MUST COMPLY WITH UL DESIGN FOR PENETRATIONS.

DIMENSIONS INDICATED ON THESE DRAWINGS ARE TO FACE OF CMU WALL, FACE OF EXTERIOR VENEER, FACE OF STUD WALL, OR CENTERLINE OF COLUMN UNLESS OTHERWISE INDICATED. COORDINATE ALL DIMENSIONS WITH STRUCTURAL DIMENSION PLANS, ENLARGED PLANS, SECTION AND DETAIL DRAWINGS, AND STRUCTURAL DRAWINGS AND VERIFY EXACT LOCATIONS. COORDINATE ALL FLOOR SLAB PENETRATIONS WITH SYSTEM DRAWINGS (S'S, M'S, P'S, FP'S, AND E'S) AND ACTUAL PRODUCT TO BE INSTALLED AND VERIFY LOCATIONS WITH ARCHITECTURAL DRAWINGS PRIOR TO INSTALLATION.

SEE FINISH SCHEDULE AND PLAN FOR FLOOR PATTERNS AND FLOOR FINISH REFERENCES

EXISTING AND MASONRY OPENINGS TO RECEIVE CURTAIN WALL, DOORS, WINDOWS, LOUVERS, OR OTHER ELEMENTS SHALL BE FIELD VERIFIED PRIOR TO MANUFACTURE OF SYSTEM.

INTERIOR METAL STUD OPENINGS TO RECEIVE STOREFRONT, DOORS, GRILLES, LOUVERS, OR OTHER ELEMENTS SHALL BE FIELD VERIFIED PRIOR TO MANUFACTURE OF SYSTEM. LOCATION OF ALL RECESSED CABINETS AND EQUIPMENT WALL PENETRATIONS MUST BE VERIFIED PRIOR TO INSTALLATION OF CMU WALLS TO ENSURE INDICATED LOCATION AND EVEN COURSING. ANY CONFLICTS WITH INDICATED DIMENSIONS OR LOCATIONS SHALL BE COORDINATED WITH ARCHITECT PRIOR TO INSTALLATION..

CONTACT OWNER UPON DISCOVERY OF ANY SUSPECTED ASBESTOS-CONTAINING MATERIALS OR OTHER SUSPECTED HAZARDOUS MATERIALS NOT SHOWN TO BE REMOVED WITHIN THE PROJECT SCOPE.

1.

2.

3.

4.

5.

6

7.

1

2

3

4

5

6

ACCESS CONTROL - SEE ELEC. DWGS.

MANUAL ROLLER SHADES ADDED TO EXISTING WINDOWS

TRANSLUCENT FILM APPLIED TO EXISTING WINDOWS, SEE SPECS.

CUSTOM WOOD/LAMINATE LOCKERS

BUILT IN CASEWORK OR SHELVES

STORAGE SHELVING BY OWNER (N.I.C.)

EXISTING FAN COIL UNITS TO REMAIN, SAND AND REPAINT, SEE SCHEDULE OF INTERIOR FINISHES

FUTURE LARGE SCALE WALL GRAPHIC (N.I.C.)

SOLID SURFACE SILL

GLASS FIBER REINFORCED GYPSUM RADIUS END CAP

FLAT PANEL DISPLAY - BY OWNER (N.I.C.)

WRITE-ON WALL SURFACE - SEE SCHEDULE OF INTERIOR FINISHES, WB-1

AFTER DEMO OF COUNTER AND MIRRORS, PATCH AND REPAIR WALL AND PREP FOR PAINTING. INFILL MISSING WOOD CHAIR RAIL (MATCH PROFILE). REPAINT WALL AND CHAIR RAIL TO MATCH EXISTING COLORS THIS WALL EAST WALL OF CORRIDOR H202 ONLY.

7

8

9

10

11

12

13

EXSITING WALL TO REMAIN

EXISTING WALL TO BE DEMOLISHED

EXISTING DOOR TO BE DEMOLISHED

EXISTING DOOR TO BE REMAIN

EXISTING WINDOW TO BE DEMOLISHED

EXISTING WINDOW TO REMAIN

GRAY SHADED AREA NOT IN PROJECT SCOPE

FIRE EXTINGUISHER WALL CABINET, SEE SPECS.

ONE-HOUR FIRE-RATED WALL ASSEMBLY*SEE PARTITION TYPES FOR UL DESIGN NO'S.

FE-C

GRAY SHADED AREA NOT IN PROJECT SCOPE

1

2

3

4

5

6

DEMO AND DISPOSE OF LOCKERS IN THEIR ENTIRETY . UNDER NO CIRCUMSTANCE ARE LOCKERS TO BE REMOVED INTACT AND RESOLD, MAINTAINED BY THE GC, AND/OR GIVEN TO OTHER PARTIES.

DEMO EXISTING CMU WALLS

EXISTING FAN COIL UNITS TO REMAIN

DEMO EXISTING DOOR, REPLACE WITH NEW DOOR IN EXISTING FRAME. HOLLOW METAL FRAME TO REMAIN.

DEMO CERAMIC TILE AND WALL AS REQUIRED FOR INSTALLATION OF NEW COUNTER, SINKS AND WATER CLOSETS. SEE PLUMBING DWGS. RECONSTRUCT WALL/CHASE AS REQUIRED. SEE FINISH PLANS AND ELEVATIONS FOR NEW WALL FINISHES.

DEMO EXISTING COUNTER TOP, PATCH AND REPAIR WALL IN CORRIDOR H202

REMOVE EXISTING MIRRORS FROM WALL, PATCH AND REPAIR WALL IN CORRIDOR H202

REMOVE CARPET ONLY TO DOOR JAMB, SEE FINISH PLAN FOR EXTENT OF NEW CARPET THIS AREA. CREATE CLEAN FLUSH TRANSITION BETWEEN NEW AND EXISTING CARPET

DEMO EXISTING TILE AND SETTING BED THIS AREA ONLY

EXISTING FLOOR TILE TO REMAIN. NEW TILE TO BE INSTALLED OVER EXISTING.

DEMO DRINKING FOUNTAIN, SEE PLUMBING DWGS.

DEMO FIRE EXTINGUISHER CABINET

DEMO EXISTING CASEWORK AND SHELVES

7

8

9

10

11

12

13

1. FIELD VERIRY EXISTING CONDITIONS PRIOR TO COMMENCEMENT OF DEMOLITION AND NEW WORK. EXISTING BUILDING INFORMATION SHOWN IS BASED ON THE EXISTING DRAWINGS PROVIDED BY THE OWNER AND SELECTIVE FIELD MEASUREMENTS. GENERAL CONTRACTOR AND SUB-CONTRACTORS ARE TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO BID AND PRIOR TO CONSTRUCTION.

2. PROVIDE AND INSTALL ALL SHORING AND SUPPORT SYSTEMS NECESSARY TO ENSURE EXISTING STRUCTURE TO REMAIN STABLE THROUGHOUT DEMOLITION AND NEW CONSTRUCTION.

3. WHERE APPLICABLE, REFERENCE ABATEMENT SPECIFICATIONS FOR KNOWN AREAS CONTAINING HAZARDOUS MATERIALS. CONTACT OWNER UPON DISCOVERY OF ANY SUSPECTED ASBESTOS-CONTAINING MATERIALS OR OTHER SUSPECTED HAZARDOUS MATERIALS NOT SHOWN TO BE REMOVED IN THE PROJECT SCOPE.

4. CONTRACTOR SHALL PHOTOGRAPH ALL EXISTING CONDITIONS PRIOR TO COMMENCEMENT OF DEMOLITION OR NEW WORK TO DOCUMENT PRE-CONSTRUCTION CONDITIONS. PROVIDE ARCHITECT AND OWNER WITH ELECTRONIC COPY OF PHOTOGRAPHS.

5. ITEMS TO SALVAGED AND REMOVED BY THE OWNER PRIOR TO DEMOLITION ARE IDENTIFIED WITHIN THE SPECIFICATIONS.

6. CONTRACTOR SHALL VERIFY ALL DIMENSIONS WITH EXISTING CONDITIONS FOR SIZES, QUANTITIES AND LOCATIONS.

7. PROTECT ALL EXITING PIPING & INSULATION, CONDUIT/BOXES, WIRING, LIGHTING, DUCTWORK, SPRINKLER PIPING, AND ALL OTHER UTILITIES TO REMAIN IN USE. REMOVE ALL ABANDONED OR DISCONNECTED ITEMS FROM ABOVE CEILINGS.

8. ALL FURNITURE, FIXTURES AND LOOSE ITEMS TO BE REMOVED BY OWNER BEFORE COMMENCEMENT OF WORK.

9. PATCH WALLS, CEILINGS AND FLOORS WHERE ITEMS ARE REMOVED OR WERE REMOVED BY OWNER TO PREPARE AREAS FOR FINAL WORK AND FINISHES AS SPECIFIED.

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

5/15

/201

8 3:

05:0

5 PM

A1.2U479

.18

05.1

5.18

SECO

ND FL

OOR

PLAN

SAu

thor

Chec

ker

OUTD

OOR

VOLL

EYBA

LL LO

CKER

/FILM

ROOM

REN

OVAT

ION

107

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

08

REVI

SIO

N S

NO.

NAM

EDA

TE

REFERENCED ON:

1/4" = 1'-0"A1.21 SECOND FLOOR ENLARGED DEMOLITION PLAN

REFERENCED ON:

1/4" = 1'-0"A1.22 SECOND FLOOR ENLARGED FLOOR PLAN

GENERAL NOTES - FLOOR PLAN

KEYNOTES - FLOOR PLAN

LEGEND - DEMOLITION PLAN

LEGEND - FLOOR PLAN

KEYNOTES - DEMO PLAN SECOND FLOOR

GENERAL NOTES - DEMO PLAN

NOT IN PROJECT SCOPE

NOT IN PROJECT SCOPE

NOT IN PROJECT SCOPE

EXISTING GRID AND TILE TO REMAIN AT SHOWERS. SEE ELEC. DWGS. FOR LIGHTING THIS AREA

8' - 2"8' - 2"

8' - 2"

4A5.2

8' - 2"

8' - 0"

8' - 0"

8' - 0"

2A5.2

A2.21

Sim

ALIGN CEILING RADIUS TANGENT TO CURVE OF FLOORING MATERIAL

7' - 6"

2

A2.2

3

A2.2

EXISTING TO REMAIN

3

A2.2

Sim

7' - 6"

1111

R 2' - 4"

R 2' - 4"

2' - 0

"

1' - 2

"

1' - 8"

1

A5.1

START FULL TILE AGAINST SOFFIT

START FULL TILE AGAINST SOFFIT

8' - 0"*MATCH EXISTING

NEW WALL AND BULKHEAD

7'-8"

4

A2.2

*SET HT. WHERE GWB LAMINATED TO CMU HEAD AT WINDOWS

*MATCH SOFFIT HEIGHT ALONG WINDOWS

*SET HT. WHERE GWB LAMINATED TO CMU HEAD AT WINDOWS

SEE DIMENSION RCP FOR LIGHT LAYOUTS AND DIMENSIONS

R 2' - 4"

R 2' - 4"

8' - 2"

8' - 0"

8' - 2" 8' - 2"

8' - 0"R 2' - 4"

R 4' - 0"

2' - 7"

ALIGN SOFFIT WITH LOCKER CENTERLINE

ALIGN SOFFIT WITH LOCKER JOINT

3' - 3

7/8

"

120.00°

LIGHT FIXTURE

1

NOT IN PROJECT SCOPE

EXISTING CEILING TO REMAIN AT THIS LOCATION

1 1

1 1 1

11

1

MAINTAIN GRID AND TILE THIS SIDE OF NEW STUD WALL AND BULKHEAD

DEMO GRID AND TILE THIS SIDE OF NEW STUD WALL AND BULKHEAD

1 1

1 MANUAL ROLLER SHADE, SEE PLANS AND SPECS

SUPPLY & RETURN MECHANICAL DIFFUSERS

ACCESS PANEL - COORDINATE LOCATIONS WITH ARCHITECT

LINEAR SLOT DIFFUSER

GYPSUM BOARD CEILING / SOFFIT AS SPECIFIED

ACOUSTICAL PANEL CEILING AS SPECIFIED

RECESSED DOWNLIGHT

FLOURESCENT FIXTURES

WALL MOUNTED FIXTURES

EXIT LIGHTS - SEE ELECTRICAL DRAWINGS FOR LOCATIONS

PENDANT LIGHT

9' - 8"SHOWS CEILING HEIGHTS RELATIVE TO MAIN 0'-0" FINISHED FLOOR ELEVATION

STRIP FLOURESCENT FIXTURE

AP

REFER TO ELECTRICAL DRAWINGS FOR QUANTITY AND SPECIFIC FIXTURE DESIGNATIONS, AND FOR ELECTRICAL CEILING AND WALL MOUNTED DEVICES.

ALL SUSPENDED ACOUSTICAL GRIDS ARE TO BE LOCATED AS SHOWN, UNLESS NOTED OTHERWISE. REFERENCE NOTES FOR GRID START POINTS AND FULL-TILE LOCATIONS. REVIEW ALL GRID LAYOUTS WITH ARCHITECT PRIOR TO INSTALLATION TO ASSURE NO "SLIVERS" OF TILE, OVERLAPPING WALL MOLDS, OR OUT-OF-SQUARE CONDITIONS OCCUR. GRIDS NOT COMPLYING WITH THIS PROCESS OR THESE STIPULATIONS WILL BE REMOVED AND RE-INSTALLED AT CONTRACTOR'S EXPENSE.

CEILING MOUNTED EQUIPMENT, DEVICES, FIXTURES & GRILLS MUST BE COORDINATED ON REFLECTED CEILING PLANS. CEILING MOUNTED SPRINKLERS TO BE LOCATED IN CENTER OF CEILING TILE IN APC CEILINGS AND ALIGNED WITH DOWNLIGHTS IN GWB CEILINGS/SOFFITS.

SEE FP DRAWINGS FOR FIRE PROTECTION SYSTEM LAYOUT. COORDINATE ROUTING OF PIPING W/ ARCHITECTURAL DWGS AND DETAILS AS WELL AS ALL OTHER SYSTEM DRAWINGS (S's, M's, P's, & E'S). SUBMIT LAYOUT/COORDINATION DRAWING FOR REVIEW & APPROVAL PRIOR TO INSTALLATION.

PAINT ALL EXPOSED STRUCTURE/CEILING AREA, INCLUDING ROOF STRUCTURE, DUCTWORK, PLUMBING LINES, FIRE SUPPRESSION LINES, ELEC. CONDUITS & BOXES AND OTHER NON-FINISHED ITEMS, EXCEPT IN MECHANICAL ROOMS, ELECTRICAL ROOM, ELEVATOR MACHINE ROOMS, AND TEL/ DATA ROOMS, UNLESS NOTED OTHERWISE ON FINISH SCHEDULES AND INTERIOR ELEVATIONS.

ACCESS PANELS BY GENERAL CONTRACTOR. QUANTITY OF ACCESS PANELS SHOWN ON ARCHITECTURAL DRAWINGS NOT INTENDED TO BE ALL INCLUSIVE; SEE MECHANICAL DRAWINGS, PLUMBING DRAWINGS, ELECTRICAL DRAWINGS, AND FIRE PROTECTION SHOP DRAWINGS FOR ADDITIONAL ACCESS PANELS NOT SHOWN. COORDINATE EXACT LOCATION OF ACCESS PANELS NOT SHOWN WITH ARCHITECT. BRING ALL MECHANICAL, PLUMBING AND ELECTRICAL ITEMS WHICH NEED ACCESS TO THE ACCESS PANEL LOCATIONS SHOWN - BRING THE NEED FOR ADDITIONAL ACCESS PANELS TO THE ARCHITECT'S ATTENTION BEFORE PROCEEDING.

1.

2.

3.

4.

5.

6.

1. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCEMENT OF DEMOLITION AND NEW WORK. EXISTING BUILDING INFORMATION SHOWN IS BASED ON THE EXISTING DRAWINGS PROVIDED BY THE OWNER AND SELECTIVE FIELD MEASUREMENTS. GENERAL CONTRACTOR AND SUB-CONTRACTORS ARE TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO BID AND PRIOR TO CONSTRUCTION.

2. WHERE APPLICABLE, REFERENCE ABATEMENT SPECIFICATIONS FOR KNOWN AREAS CONTAINING HAZARDOUS MATERIALS. CONTACT OWNER UPON DISCOVERY OF ANY SUSPECTED ASBESTOS-CONTAINING MATERIALS OR OTHER SUSPECTED HAZARDOUS MATERIALS NOT SHOWN TO BE REMOVED IN THE PROJECT SCOPE.

3. CONTRACTOR SHALL PHOTOGRAPH ALL EXISTING CONDITIONS PRIOR TO COMMENCEMENT OF DEMOLITION OR NEW WORK TO DOCUMENT PRE-CONSTRUCTION CONDITIONS. PROVIDE ARCHITECT AND OWNER WITH ELECTRONIC COPY OF PHOTOGRAPHS.

4. ITEMS TO SALVAGED AND REMOVED BY THE OWNER PRIOR TO DEMOLITION ARE IDENTIFIED WITHIN THE SPECIFICATIONS.

5. CONTRACTOR SHALL VERIFY ALL DIMENSIONS WITH EXISTING CONDITIONS FOR SIZES, QUANTITIES AND LOCATIONS.

6. PROTECT ALL EXITING PIPING & INSULATION, CONDUIT/BOXES, WIRING, LIGHTING, DUCTWORK, SPRINKLER PIPING, AND ALL OTHER UTILITIES TO REMAIN IN USE. REMOVE ALL ABANDONED OR DISCONNECTED ITEMS FROM ABOVE CEILINGS.

7. ALL FURNITURE, FIXTURES AND LOOSE ITEMS TO BE REMOVED BY OWNER BEFORE COMMENCEMENT OF WORK.

8. PATCH WALLS, CEILINGS AND FLOORS WHERE ITEMS ARE REMOVED OR WERE REMOVED BY OWNER TO PREPARE AREAS FOR FINAL WORK AND FINISHES AS SPECIFIED.

9. SEE MECHANICAL, PLUMBING AND ELECTRICAL DEMOLITION PLANS AND NOTES FOR DEMOLITION OF LIGHTS, DEVICES, DUCTWORK, PIPING, ETC. ABOVE CEILINGS. PREPARE ALL AREAS FOR NEW CEILNGS AND UTILITIES INCLUDING RAISING AND/OR REMOVAL OF CONDUIT, PIPING, DUCTWORK, ETC. NECESSARY TO ACHIEVE NOTED CEILING HEIGHTS. CONSULT WITH ARCHITECT SHOULD ANY UTILITY CONFLICTS ARISE.

1

2

DEMO ALL CEILING GRID IN THIS SPACE AND REMOVE ALL LIGHT FIXTURES, ELECTRICAL DEVICES, HVAC DIFFUSERS, ETC. PER MECHANICAL, PLUMBING AND ELECTRICAL DEMO PLANS. CONTRACTOR TO SALVAGE AND SAVE ALL BATT INSULATION ON TOP OF CEILING TILES AND RE-INSTALL ON NEW CEILNG TILE AND GYPSUM BOARD SOFFITS AND CEILINGS. CONTRACTOR IS RESPONSIBLE FOR ADDING ADDITIONAL BATT INSULATION OF SAME TYPE, THICKNESS AND R-VALUE ABOVE CEILINGS TO CREATE A CONTINUOUS INSULATION LAYER OVER ENTIRE RENOVATION AREA.

PATCH ANY/ALL HOLES AND REPAIR DAMAGE AFTER DEMOLITION OF LIGHTS AND OTHER DEVICES. CLEAN AND REPAINT CEILING.

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

5/15

/201

8 3:

05:0

9 PM

A2.1U479

.18

05.1

5.18

ENLA

RGED

REF

LECT

ED C

EILIN

GPL

ANS

Auth

or

Chec

ker

OUTD

OOR

VOLL

EYBA

LL LO

CKER

/FILM

ROOM

REN

OVAT

ION

107

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

08

REVI

SIO

N S

NO.

NAM

EDA

TE

REFERENCED ON:

1/4" = 1'-0"A2.1 A3.12 SECOND FLOOR ENLARGED REFLECTED CEILING PLAN

REFERENCED ON:

1/4" = 1'-0"A2.1 A3.11 SECOND FLOOR ENLARGED REFLECTED CEILING DEMO PLAN

KEYNOTES - REFLECTED CEILING PLAN SECOND FLOOR LEGEND - REFLECTED CEILING PLAN

GENERAL NOTES - REFLECTED CEILING PLAN

GENERAL NOTES - DEMO REFLECTED CEILING PLAN

KEYNOTES - DEMO RCP

4A5.2

2A5.2

NOT IN PROJECT SCOPE8' - 2"

8' - 0"

8' - 0"

2

A2.2

3

A2.2

1' - 6

"

1' - 6"

1' - 6"

TYP.

R 2' - 4"

R 2' - 4"

7' - 0"

12' - 0"

4' - 0"

8' - 4"

TO C

ENTE

R P O

INT

9' - 8

3/4

"

R 2' - 4"

123.00°

8' - 2"

7' - 6"

7' - 6"

5' - 3 1/4"

4' - 1

3/8"

4' - 1

3/8"

8' - 2"

1

A5.1

4

A2.2

3

A2.2

Sim

3

A2.2

Sim

*SET HT. WHERE GWB LAMINATED TO CMU HEAD AT WINDOWS

*MATCH SOFFIT HEIGHT ALONG WINDOWS

1111

4' - 1

"2'

- 2 1

/8"

6' - 5 3/4"

R 2' - 4"

R 2' - 4"

57.00°

2' - 9 1/2"

CENTER ON FLAT PANEL DISPLAY

8' - 0"

8' - 2"

8' - 2"

8' - 2"

2"

2 1/2"SOFFIT REVEAL AT WALL

ALIGN CEILING RADIUS TANGENT TO CURVE OF FLOORING MATERIAL

WOOD TRUSSES

GWB ON METAL STUD FRAMING

SUSP. ACOUSTICAL TILE CEILING SYSTEM

WOOD TRUSSES

GWB ON 3-5/8" METAL STUD FRAMING

1 MANUAL ROLLER SHADE, SEE PLANS AND SPECS

REFER TO ELECTRICAL DRAWINGS FOR QUANTITY AND SPECIFIC FIXTURE DESIGNATIONS, AND FOR ELECTRICAL CEILING AND WALL MOUNTED DEVICES.

ALL SUSPENDED ACOUSTICAL GRIDS ARE TO BE LOCATED AS SHOWN, UNLESS NOTED OTHERWISE. REFERENCE NOTES FOR GRID START POINTS AND FULL-TILE LOCATIONS. REVIEW ALL GRID LAYOUTS WITH ARCHITECT PRIOR TO INSTALLATION TO ASSURE NO "SLIVERS" OF TILE, OVERLAPPING WALL MOLDS, OR OUT-OF-SQUARE CONDITIONS OCCUR. GRIDS NOT COMPLYING WITH THIS PROCESS OR THESE STIPULATIONS WILL BE REMOVED AND RE-INSTALLED AT CONTRACTOR'S EXPENSE.

CEILING MOUNTED EQUIPMENT, DEVICES, FIXTURES & GRILLS MUST BE COORDINATED ON REFLECTED CEILING PLANS. CEILING MOUNTED SPRINKLERS TO BE LOCATED IN CENTER OF CEILING TILE IN APC CEILINGS AND ALIGNED WITH DOWNLIGHTS IN GWB CEILINGS/SOFFITS.

SEE FP DRAWINGS FOR FIRE PROTECTION SYSTEM LAYOUT. COORDINATE ROUTING OF PIPING W/ ARCHITECTURAL DWGS AND DETAILS AS WELL AS ALL OTHER SYSTEM DRAWINGS (S's, M's, P's, & E'S). SUBMIT LAYOUT/COORDINATION DRAWING FOR REVIEW & APPROVAL PRIOR TO INSTALLATION.

PAINT ALL EXPOSED STRUCTURE/CEILING AREA, INCLUDING ROOF STRUCTURE, DUCTWORK, PLUMBING LINES, FIRE SUPPRESSION LINES, ELEC. CONDUITS & BOXES AND OTHER NON-FINISHED ITEMS, EXCEPT IN MECHANICAL ROOMS, ELECTRICAL ROOM, ELEVATOR MACHINE ROOMS, AND TEL/ DATA ROOMS, UNLESS NOTED OTHERWISE ON FINISH SCHEDULES AND INTERIOR ELEVATIONS.

ACCESS PANELS BY GENERAL CONTRACTOR. QUANTITY OF ACCESS PANELS SHOWN ON ARCHITECTURAL DRAWINGS NOT INTENDED TO BE ALL INCLUSIVE; SEE MECHANICAL DRAWINGS, PLUMBING DRAWINGS, ELECTRICAL DRAWINGS, AND FIRE PROTECTION SHOP DRAWINGS FOR ADDITIONAL ACCESS PANELS NOT SHOWN. COORDINATE EXACT LOCATION OF ACCESS PANELS NOT SHOWN WITH ARCHITECT. BRING ALL MECHANICAL, PLUMBING AND ELECTRICAL ITEMS WHICH NEED ACCESS TO THE ACCESS PANEL LOCATIONS SHOWN - BRING THE NEED FOR ADDITIONAL ACCESS PANELS TO THE ARCHITECT'S ATTENTION BEFORE PROCEEDING.

1.

2.

3.

4.

5.

6.

SUPPLY & RETURN MECHANICAL DIFFUSERS

ACCESS PANEL - COORDINATE LOCATIONS WITH ARCHITECT

LINEAR SLOT DIFFUSER

GYPSUM BOARD CEILING / SOFFIT AS SPECIFIED

ACOUSTICAL PANEL CEILING AS SPECIFIED

RECESSED DOWNLIGHT

FLOURESCENT FIXTURES

WALL MOUNTED FIXTURES

EXIT LIGHTS - SEE ELECTRICAL DRAWINGS FOR LOCATIONS

PENDANT LIGHT

9' - 8"SHOWS CEILING HEIGHTS RELATIVE TO MAIN 0'-0" FINISHED FLOOR ELEVATION

STRIP FLOURESCENT FIXTURE

AP

SUSP. ACOUSTICAL TILE CEILING SYSTEM

GWB SOFFIT ON METAL STUD FRAMING - ALIGN STUD WITH BOTTOM OF CMU HEAD

GWB PILASTER BEYOND

EXISTING EXTERIOR WALL BEYOND

*SET SOFFIT HEIGHT IN ORDER TO LAMINATE NEW 5/8" GWB AT BOTTOM OF EXISTING CMU WINDOW HEAD

EXISTING WINDOW SYSTEM TO REMAIN

CONT. SEALANT

WOOD TRUSSES

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

5/15

/201

8 3:

05:1

3 PM

A2.2U479

.18

05.1

5.18

ENLA

RGED

CEI

LING

DIME

NSIO

NPL

AN &

DET

AILS

Auth

or

Chec

ker

OUTD

OOR

VOLL

EYBA

LL LO

CKER

/FILM

ROOM

REN

OVAT

ION

107

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

08

REVI

SIO

N S

NO.

NAM

EDA

TE

REFERENCED ON:

3/8" = 1'-0"A2.2 A2.11 SECOND FLOOR DIMENSION REFLECTED CEILING PLAN

REFERENCED ON:

3" = 1'-0"A2.2 A2.12 CEILING DETAIL

REFERENCED ON:

3" = 1'-0"A2.2 A2.13 CEILING DETAIL

KEYNOTES - REFLECTED CEILING PLAN SECOND FLOOR

GENERAL NOTES - REFLECTED CEILING PLAN

LEGEND - REFLECTED CEILING PLAN

REFERENCED ON:

3" = 1'-0"A2.2 A1.24 CEILING DETAIL

A4.1

9

1' - 4 1/2" 2' - 8" 2' - 8" 1' - 4 3/8"3' - 0" 3' - 0" 2' - 11 7/8"

3' - 0" 3' - 0" 1' - 5 5/8"

NEW FLOOR TILE THIS SIDE OF STEP (CT-1)

STEP - NEW LOCATION

EXISTING TILE TO REMAIN, THIS SIDE OF STEP

4 EXISTING SHOWER STALLS AND HARDWARE TO REMAIN

TP-1

M-1

TTDND

30"X52" CLR. TP-1 TP-1

PTD

TTDND

TTDND

10

4' - 6

"

5' - 6

"

NEW GWB AND METAL STUD WALL

4A3.1

11M3A*

RE-INSTALL EXISTING WING PARTITIONS AND SEAT TO NEW METAL STUD/GWB/CERAMIC TILE WALL AT SAME LOCATION

3' - 8

"

3

A3.1

3' - 0

" F.V

.

WOMEN'S RESTROOM202

3' - 0" 3' - 0" 2' - 11 7/8"

1 LAYER 5/8" GYPSUM WALL BOARD EACH SIDE

STEEL STUDS @ 16" O.C. MAX.(SEE SPECIFIC PARTITION TYPE FOR SIZE)

WOOD TRUSSES ABOVE

WALL FINISH, SEE FINISH SCHEDULE

STEEL RUNNER ATTACHED TO CONCRETE SLAB AT 12" O.C. MAX.@ TOP AND BOTTOM OF WALL

CONCRETE SLAB FINISH FLOOR MATERIAL, SEE FINISH SCHEDULE

ACOUSTICAL BATT INSULATION @ * CONDITION (SEE LEGEND FOR SIZE)

CEILING WHERE INDICATED ON REFLECTED CEILING PLANS WHERE OCCURS

BASE, SEE FINISH SCHEDULE

BATT INSULATION ON SUSPENDED CEILING. RE-USE OR REPLACE WITH SAME TYPE/THICKNESS AS EXISTING

1 LAYER 5/8" GYPSUM WALL BOARD EACH SIDE

WALL FINISH, SEE FINISH SCHEDULE

STEEL RUNNER ATTACHED TO CONCRETE SLAB AT 12" O.C. MAX.@ TOP AND BOTTOM OF WALL

CONCRETE SLABFINISH FLOOR MATERIAL, SEE FINISH SCHEDULE

CEILING WHERE INDICATED ON REFLECTED CEILING PLANS WHERE OCCURS

BASE, SEE FINISH SCHEDULE

AT FIRE-RATED WALLS, EXTEND GWB TO RATED HORIZONTAL MEMBRANE IN CORRIDORS. INSTALL GYPSUM BOARD TIGHT TO MEMBRANE AND SEAL WITH FIRE CAULKING. PACK ALL VOIDS WITH FIRE-SAFING MATERIAL

BASIS FOR DESIGN:UL DESIGN U465 WHERE INDICATED TO BE 1-HOUR FIRE-RATED ON PLANS

STEEL STUDS @ 16" O.C. MAX.(SEE SPECIFIC PARTITION TYPE FOR SIZE)

ACOUSTICAL BATT INSULATION @ * CONDITION (SEE LEGEND FOR SIZE)

WOOD TRUSSES ABOVE

BATT INSULATION ON SUSPENDED CEILING. RE-USE OR REPLACE WITH SAME TYPE/THICKNESS AS EXISTING

1 LAYER 5/8" GYPSUM WALL BOARDSTEEL STUDS @ 16" O.C. MAX.(SEE SPECIFIC PARTITION TYPE FOR SIZE)WALL FINISH, SEE FINISH SCHEDULE

STEEL RUNNER ATTACHED TO CONCRETE SLAB AT 12" O.C. MAX.@ TOP AND BOTTOM OF WALL

CONCRETE SLAB

FINISH FLOOR MATERIAL, SEE FINISH SCHEDULE

CEILING WHERE INDICATED ON REFLECTED CEILING PLANS WHERE OCCURS

BASE, SEE FINISH SCHEDULE

ACOUSTICAL BATT INSULATION @ * CONDITION (SEE LEGEND FOR SIZE)

WOOD TRUSSES ABOVEBATT INSULATION ON SUSPENDED CEILING. RE-USE OR REPLACE WITH SAME TYPE/THICKNESS AS EXISTING

2' - 10 5/8"

110.00

°

7' - 7

7/8

"

6' - 7

5/8

"1'

- 0 1

/8"

3 5/

8"

70.04°

4' - 6" 5' - 5" 7' - 9"

R 10' - 6"R 10' - 8"

R 16' - 5"

TO C

ENTE

R P O

INT

5' - 7

1/2

"

TO C

ENTE

R PO

INT

9' - 3

"

M3A

M3CM3C

M3C

FLAT SCREEN (N.I.C.)

R 11' - 2"

R 11' - 2"

BLEND CURVE THIS LOCATION

2 3/4" 1' - 3 3/8" 10 1/2" 5 3/4"

9 7/

8"2'

- 6 3

/4"

4' - 0

1/4

"

1' - 2

"

90.00°

9 3/8"

2' - 9 3/4"

R 12' - 0"

4 3/

4"

10 5

/8"

1A5.2

2' - 9 3/4"

1' - 6 3/4"

1' - 9"

110.00

°

M3C

M2C

M2C

M2C

R 15' - 6"

R 14' - 10"

M2C

R 0' - 1

0"

WOMEN'S LOCKERROOM

203

STORAGE203B

TEAM LOUNGE201

WOMEN'S RESTROOM202

R 0' - 10"

R 0'

- 10

"

M3C

M3C

M3C

M3C

M3C

M3C

M3C

M3A

M3C

4' - 2 1/8"

PIVOT DOOR

202AD2 -

1"

LOCKERS

M1M2M3M4M6M8

M2A*

MATERIAL FINISH CONSTRUCTION

SIZE

SEE CHART BELOW

SEE CHART BELOW

SEE PARTITION SECTION

1-1/2" METAL STUD2-1/2" METAL STUD3-5/8" METAL STUD4" METAL STUD6" METAL STUD8" METAL STUD

W2W4W6W8

2X2" WOOD STUD2X4" WOOD STUD2X6" WOOD STUD2X8" WOOD STUD

C4C8C12

4" CMU (3-5/8" NOM.)8" CMU (7-5/8" NOM.)12" CMU (11-5/8" NOM.)

INSULATION DESIGNATION

S2 2" C-H STUD (SHAFT WALL)

Second Floor10' - 8"

EXISTING TILE AND GROUT BED IN SHOWERS TO REMAIN

NEW STEP LOCATION

NEW TILE CT-1, SEE SCHEDULE OF INTERIOR FINISHES

2" F

.V.

NEW WALL LOCATION

MARBLE TRANSITION, SEE FINISH PLANS

SANITARY NAPKIN DISPOSAL

ND

3' - 2

" MAX

.3'

- 10"

SEE SPECIFICATIONSFOR MIRROR TYPE

FRAMED MIRROR ON MOUNTING CLIPS

M-1

TOILET PARTITION

1' - 0

"5'

- 0"

2' - 9

"

TOILET TISSUE DISPENSER (O.F.O.I.)

LIQUID SOAP DISPENSER (O.F.O.I.)

TP-1 TTD SD

4' - 0

"

PAPER TOWEL DISPENSER (O.F.O.I.)

3' - 6

"

PTD

OWNER FURNISHED, OWNER INSTALLED (O.F.O.I.) ITEMS SHOWN FOR LOCATION ONLY

1' - 8"

ALIGN WITH PARTITION BRACE

Second Floor10' - 8"

TILED WALL BEYOND

SOLID SURFACE COUNTERTOP AND CONTINUOUS APRON

UNDERMOUNT SINK, SEE PLUMBING

MIRROR

EXISTING WALL - DEMO AS REQUIRED FOR PLUMBING WORK. RE-CONSTRUCT WALL WITH 3-5/8" METAL STUDS AND 1/2" CEMENTITIOUS TILE BACKER BOARD TO RECEIVE NEW CERAMIC TILE - SEE FINISH PLANS AND SCHEDULE.

REMOVABLE PLASTIC LAMINATE SCREEN PANEL

PROVIDE BLOCKING AS REQUIRED

MAINTAIN REQ'D. ADA/ANSI CLEARANCES

PLYWOOD RIB SUPPORT FRAMING STRUCTURE,SUPPORT COUNTERTOP AT ENDS AND BETWEEN INDIVIDUAL SINKS AS REQ'D.

2' - 1

0"

2' - 4

"6"

1' - 4

"1'

- 0"

TILED WALL

2' - 3

" MIN

. CLR

.

8" MIN. CLR.

11" MIN. CLR.

9" M

IN. C

LR.

2' - 1"

CONT. CLEAR SEALANT AT PERIMETER

CERAMIC TILE

PROVIDE BLOCKING AS REQUIRED

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

5/15

/201

8 3:

05:1

5 PM

A3.1U479

.18

05.1

5.18

ENLA

RGED

PLA

NS, P

ARTIT

ION

TYPE

S &

DETA

ILS

Auth

or

Chec

ker

OUTD

OOR

VOLL

EYBA

LL LO

CKER

/FILM

ROOM

REN

OVAT

ION

107

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

08

REVI

SIO

N S

NO.

NAM

EDA

TE

REFERENCED ON:

1/2" = 1'-0"A3.1 A1.21 ENLARGED BATHROOM PLAN

INTERIOR PARTITION 1 1/2" = 1'-0"M#A INTERIOR PARTITION

1 1/2" = 1'-0"M#B INTERIOR PARTITION 1 1/2" = 1'-0"M#C

REFERENCED ON:

1/2" = 1'-0"A3.1 A1.22 ENLARGED PLAN @ CURVED WALL

LEGEND - PARTITION TYPES

REFERENCED ON:

3" = 1'-0"A3.1 A3.14 SECTION DETAIL @ BATHROOM TILE STEP

TOILET ACCESSORIES

REFERENCED ON:

1 1/2" = 1'-0"A3.1 A3.13 SECTION AT LAVATORY COUNTER

Second Floor10' - 8"

WALL COVERING, WC-1

EXISTING FAN COIL UNIT TO REMAIN, TYP.

3

A2.2

WALL COVERING, WC-1 WALL COVERING, WC-1SEAM AT CENTER, DO NOT REVERSE

WALL COVERING, WC-1WRITE-ON SURFACE COATING OVER PAINT, SEE FINISH SCHED.

FLAT PANEL TV (N.I.C.)

FAN COIL FAN COIL FAN COIL FAN COILFAN COIL

BASE AS SCHEDULEDEXISTING WINDOWS TO REMAIN, TYP.

STORAGE201B

TEAM LOUNGE201

4

A2.2

LAMINATE ONE LAYER GWB TO CONC. WALL, PTD.

Second Floor10' - 8"

CERAMIC TILE ACCENT WALLREFRIGERATOR(N.I.C.)

SOLID SURFACE COUNTER TOP SS-1

WHITE BOARD WALL FINISH AT INSET - SEE PLANS

FLAT SCREEN TV (N.I.C.)SOLID SURFACE SILL SS-1

2A5.2

PIVOT DOOR TO LOCKER ROOM BEYOND

CURVED WALL

PLASTIC LAMINATE CASEWORK PL-1

PLASTIC LAMINATE WALL FINISH PL-1 BELOW SILLBASE AS SCHEDULED

TEAM LOUNGE201

A5.23

BASE AS SCHEDULED

Second Floor10' - 8"

WHITE BOARD WALL FINISH

FLAT PANEL TV (N.I.C.)

BASE AS SCHEDULED

FE-C

TEAM LOUNGE201

Second Floor10' - 8"

PREVIOUS STEP LOCATION - ELEVATED FLOOR TO BE DEMOLISHED UP TO SPECIFIED LOCATION - SEE PLANS

EXISTING RAISED FLOOR AND TILE TO REMAINREPAIR EXISTING WALL AND TILE AS REQUIRED, CT-2, AFTER REQUIRED DEMOLITION FOR PLUMBING WORK, SEE PLUMBING DWGS.

4 EXISTING SHOWER STALLS AND FINISHES TO REMAIN

A3.14

Sim

4' - 2

"2'

- 10"

3

A3.1

7' - 0

"

ALIGN

1' - 0

"

ELEC. OUTLETS, SEE ELEC. DWGS.

RE-INSTALL EXISTING WING PARTITIONS AND SEAT TO NEW METAL STUD/GWB/CERAMIC TILE WALL AT SAME LOCATION

MIRRORS M-1,SEE SPEC.

TOILET PARTITIONS TP-1

7' - 0

"

WOMEN'S RESTROOM202

4"

SS-1, TOPPL-1, APRON

LIGHT FIXTURESEE ELEC. DWGS..

Second Floor10' - 8"

WHITE BOARD WALL FINISH AT INSETFUTURE GRAPHIC AT

WALL BEYOND

FLAT SCREEN TV (N.I.C.)

BASE AS SCHEDULED

SOLID SURFACE COUNTER AND P-LAM CASEWORK

TEAM LOUNGE201

Second Floor10' - 8"

4A5.2

GWB ON METAL STUDS, PTD. AT ENDS OF LOCKERS. CONTINUE FLUSH INTO WINDOW JAMB

REVEAL AT TOP OF LOCKERS BEYOND

8' - 2

"

CUSTOM WOOD/LAMINATE LOCKERS, SEE DETAILS

GWB ON METAL STUDS, PTD. AT ENDS OF LOCKERS

GWB, PTD.

BASE AS SCHEDULED

FAN COIL

WOMEN'S LOCKERROOM

203

Second Floor10' - 8"

FAN COIL FAN COIL

EXISTING WINDOW TO REMAIN, WITH NEW TRANSLUCENT PRIVACY FILM

EXISTING WINDOW TO REMAIN, WITH NEW TRANS\LUCENT PRIVACY FILM

CUSTOM WOOD/LAMINATE LOCKERS, SEE DETAILS

GWB, PTD.

BASE AS SCHEDULED

GWB ON METAL STUDS, PTD. AT ENDS OF LOCKERS

8' - 2

"

REVEAL AT TOP OF LOCKERS BEYOND

WOMEN'S LOCKERROOM

203

Second Floor10' - 8"

CUSTOM WOOD/LAMINATE LOCKERS, SEE DETAILSGWB ON METAL STUDS, PTD. AT

ENDS OF LOCKERS

GWB, PTD. AT WINDOW JAMB

GWB, PTD.

EXISTING WINDOW TO REMAIN, WITH NEW TRANS\LUCENT PRIVACY FILM

FAN COIL

GWB ON METAL STUDS, PTD. AT ENDS OF LOCKERS

FIELD VERIFY SOFFIT HEIGHT TO CONTINUE GWB INTO WINDOW HEAD FLUSH

BASE AS SCHEDULED

FAN COIL

WOMEN'S LOCKERROOM

203

A5.25

TYP.

Second Floor10' - 8"

CUSTOM WOOD/LAMINATE LOCKERS, SEE DETAILS

FAN COIL

REVEAL AT TOP OF LOCKERS BEYONDGWB, PTD. BEYOND GWB AND RADIUSED GFRG WALL, PTD. GWB, PTD. BEYOND

FIELD VERIFY SOFFIT HEIGHT TO CONTINUE GWB INTO WINDOW HEAD FLUSH

WOMEN'S LOCKERROOM

203

BASE AS SCHEDULED

Second Floor10' - 8"

2' - 1

0"

MIRROR M-1PAPER TOWEL DISPENSER (O.F.O.I.)

SOLID SURFACE LAVATORY COUNTER

WOMEN'S RESTROOM202

Second Floor10' - 8"

7' - 8

"

TOILET PARTITION

GWB HEADER BEYOND

TILE STEP BEYOND

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

5/15

/201

8 3:

05:1

9 PM

A4.1U479

.18

05.1

5.18

INTE

RIOR

ELE

VATIO

NSAu

thor

Chec

ker

OUTD

OOR

VOLL

EYBA

LL LO

CKER

/FILM

ROOM

REN

OVAT

ION

107

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

08

REVI

SIO

N S

NO.

NAM

EDA

TE

REFERENCED ON:

3/8" = 1'-0"A4.1 A1.21 INTERIOR ELEVATION @ TEAM LOUNGE - SOUTH

REFERENCED ON:

3/8" = 1'-0"A4.1 A1.22 INTERIOR ELEVATION @ TEAM LOUNGE - NORTH

REFERENCED ON:

3/8" = 1'-0"A4.1 A1.23 INTERIOR ELEVATION @ TEAM LOUNG - EAST

REFERENCED ON:

3/8" = 1'-0"A4.1 A1.29 INTERIOR ELEVATION @ RESTROOM - NORTH

REFERENCED ON:

3/8" = 1'-0"A4.1 A1.26 INTERIOR ELEVATION @ TEAM LOUNGE - WEST

REFERENCED ON:

3/8" = 1'-0"A4.1 A1.28 INTERIOR ELEVATION @ LOCKER ROOM - EAST

REFERENCED ON:

3/8" = 1'-0"A4.1 A1.24 INTERIOR ELEVATION @ LOCKER ROOM - SOUTH

REFERENCED ON:

3/8" = 1'-0"A4.1 A1.27 INTERIOR ELEVATION @ LOCKER ROOM - WEST

REFERENCED ON:

3/8" = 1'-0"A4.1 A1.25 INTERIOR ELEVATION @ LOCKER ROOM - NORTH

REFERENCED ON:

3/8" = 1'-0"A4.1 A1.210 INTERIOR ELEVATION @ RESTROOM - WEST

REFERENCED ON:

3/8" = 1'-0"A4.1 A1.211 INTERIOR ELEVATION @ RESTROOM - EAST

DOOR WIDTH

DOOR

HEI

GHT

D1

INTERIOR1-3/4" SOLID CORE FLUSH WOOD

DOOR W/ STAINED FINISH

F1

INTERIORHOLLOW METAL

2" DOOR WIDTH 2"

2"DO

OR H

EIGH

T

DOOR WIDTH

DOOR

HEI

GHT

D2

INTERIORCUSTOM PIVOT DOOR

PIVOT HARDWARE, SEE HDWR. SCHED.

1/4" TEMPERED GLAZING WITH TRANSLUCENT PRIVACY FILM

6" 6"

6"10

"

R 0' - 10"

70.00°

1' - 9

1/2

" F.V

.

CUSTOM WOOD/LAMINATE LOCKER, SEE DETAILS

EXISTING WALL TO REMAIN

5/8" GWB ON 3-5/8" METAL STUD FRAMING

METAL STUD FRAMING AND BLOCKING AS REQ'D.

GFRG RADIUSED WALL CAP

5/8" GWB ON 3-5/8" METAL STUD FRAMING - 1-HR RATED, SEE PARTITION TYPES

1"

1 3/

8" F

OR E

LEC.

ROU

TING

5/8" GYP. BD.

EXISTING WALL TO REMAIN

EXISTING FAN COIL UNIT TO REMAIN

EXISTING WINDOW AND FRAME TO REMAIN -PROTECT THROUGHOUT CONSTRUCTION

3 5/8" METAL STUD FRAMING

5/8" GWB ON 2-1/2" METAL STUD FRAMING,SEE PARTITION TYPES

5/8" 6 3/4" 5/8"8"

2 1/

2"3

5/8"

CONTINUE GWB INTO WINDOW JAMB AND LAMINATE TO CMUNOTE: COORDINATE WITH ARCHITECT CONCERNING GWB THICKNESS AT SPACE BETWEEN CMU JAMB AND FAN COIL - NOTCHING GWB AT FAN COIL MAY BE REQ'D AT SOME LOCATIONS

EXISTING WINDOW AND FRAME TO REMAIN - PROTECT THROUGHOUT CONSTRUCTION

CUSTOM WOOD/LAMINATE LOCKER, SEE DETAILS

EXISTING WALLS TO REMAIN

5/8" GWB ON 2-1/2" METAL STUD FRAMING

FAN COIL UNIT TO REMAIN

WOOD/LAMINATE FILLER CLOSURE PANEL AT HEIGHT OF FAN COIL TO CLOSE OFF CORNER

1/2"

GAP

1 3/

8" F

OR E

LEC.

ROU

TING

SUSP. ACOUSTICAL TILE CEILING SYSTEM FLUSH ON BOTH SIDES

WOOD TRUSSES

GWB ON 2X6 WOOD HEADER WALL FRAMING

2X6 SOLID WOOD HEADER WALL SECURED TO WOOD TRUSS SYSTEM AS REQ'D. TO SUPPORT TOP CLOSER MOUNT OF PIVOT DOOR

8" F

.V.

OVERHEAD CONCEALED DOUBLE ACTING CLOSER WITH CENTER PIVOTS, SEE HARDWARE SCHED.

WOOD PIVOT DOOR

6 3/4"

EXISTING WALL TO REMAIN

EXISTING FAN COIL UNIT BELOW TO REMAIN

EXISTING WINDOW AND FRAME TO REMAIN -PROTECT THROUGHOUT CONSTRUCTION

5/8" GWB ON 3-5/8" METAL STUD FRAMING

CUSTOM WOOD/LAMINATE LOCKER, SEE DETAILS

COORDINATE CLEARANCES WITH LOCKER INSTALLATION

CONTINUE GWB INTO WINDOW JAMB AND LAMINATE TO CMUNOTE: COORDINATE WITH ARCHITECT CONCERNING GWB THICKNESS AT SPACE BETWEEN CMU JAMB AND FAN COIL - NOTCHING GWB AT FAN COIL MAY BE REQ'D AT SOME LOCATIONS

1 1/

2" F

OR E

LEC.

ROU

TING

1"

1' - 1

1 7/

8"

4 1/4"

CUSTOM WOOD/LAMINATE LOCKER, SEE DETAILS

EXISTING WALLS TO REMAIN

5/8" GWB ON 2-1/2" METAL STUD FRAMING

EXISTING WINDOW TO REMAIN

COORDINATE CLEARANCES WITH LOCKER INSTALLATION

SET FINISH OF GWB TO OUTSIDE OF WINDOW FRAME

1 1/2" FOR ELEC. ROUTING

2"

FRAME WIDTHVERIFY

TYPESEE PARTITION

DOOR FRAME BEYOND

DOOR AS SCHEDULED

HOLLOW METAL DOOR FRAME AS SCHEDULED

CONT. SEALANT BOTH SIDES, TYP.

5/8" GYP. BOARD BOTH SIDES, TYP.

BATT INSULATION IN SOME LOCATIONS, SEE PARTITION TYPE

METAL STUD HEADER - SEE STRUCT. DWGS.

METAL STUDS @ 16" O.C., TYP.

1 LAYER 5/8" GYP. BD. BOTH SIDESCONT. SEALANT, BOTH SIDES

METAL STUD @ 16" O.C., TYP.

DOUBLE METAL STUDS @ JAMB

HOLLOW METAL DOOR FRAME AS SCHEDULED

DOOR AS SCHEDULED

3 ANCHOR CLIPS PER JAMB

BATT INSULATION AT SOME LOCATIONS, SEE PARTITION TYPES

TYPE

SEE

PART

ITOI

N

1 LAYER 5/8" GWB ON 2-1/2" METAL STUD FURRING - SEE PLANS AND PARTITION TYPES

EXISTING HOLLOW METAL FRAME TO REMAIN

DOOR AS SCHEDULED (SEE PLAN FOR ORIENTATION IN FRAME)

CONT. SEALANT

EXISTING WALL TO REMAIN

1 LAYER 5/8" GWB ON 2-1/2" METAL STUD FURRING - SEE PLANS AND PARTITION TYPES

EXISTING HOLLOW METAL FRAME TO REMAIN

DOOR AS SCHEDULED (SEE PLAN FOR ORIENTATION IN FRAME)

CONT. SEALANT

EXISTING WALL TO REMAIN

EXISTING WALL TO REMAIN

EXISTING FAN COIL UNIT BELOW TO REMAIN

EXISTING WINDOW AND FRAME TO REMAIN -PROTECT THROUGHOUT CONSTRUCTION

5/8" GWB ON 2-1/2" METAL STUD FRAMING

CUSTOM WOOD/LAMINATE LOCKER, SEE DETAILS

COORDINATE CLEARANCES WITH LOCKER INSTALLATION

CONTINUE GWB INTO WINDOW JAMB AND LAMINATE TO CMUNOTE: COORDINATE WITH ARCHITECT CONCERNING GWB THICKNESS AT SPACE BETWEEN CMU JAMB AND FAN COIL - NOTCHING GWB AT FAN COIL MAY BE REQ'D AT SOME LOCATIONS

1"

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

5/15

/201

8 3:

05:2

1 PM

A5.1U479

.18

05.1

5.18

DOOR

SCH

EDUL

E, D

OOR

AND

FRAM

E TY

PES

& PL

AN D

ETAI

LS

Auth

or

Chec

ker

OUTD

OOR

VOLL

EYBA

LL LO

CKER

/FILM

ROOM

REN

OVAT

ION

107

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

08

REVI

SIO

N S

NO.

NAM

EDA

TE

DOOR SCHEDULE

Mark

DOORFRAMETYPE HEAD JAMB SILL RATING HDWR REMARKSWIDTH HEIGHT

FRAMETYPE

DOORTYPE

Second Floor201A 3' - 0" 7' - 2" D1 EX H2 J2 20 MIN.202A 4' - 0" 8' - 0" D2 - PIVOT HDWR. NO FRAME202B 3' - 0" 7' - 2" D1 F1 H1 J1 20 MIN.203A 3' - 0" 7' - 2" D1 EX H2 J2204A 3' - 0" 7' - 2" D1 F1 H1 J1206A 3' - 0" 7' - 2" D1 F1 H1 J1215A 3' - 0" 7' - 2" D1 EX H2 J2Second Floor: 7

DOOR & FRAME TYPES

REFERENCED ON:

1 1/2" = 1'-0"A5.1 A1.22 PLAN DETAIL @ NORTH LOCKERS

REFERENCED ON:

1 1/2" = 1'-0"A5.1 A1.24 PLAN DETAIL @ WINDOW PILASTER

REFERENCED ON:

1 1/2" = 1'-0"A5.1 A1.23 PLAN DETAIL @ NORTH LOCKERS

REFERENCED ON:

3" = 1'-0"A5.1 A2.11 HEAD DETAIL AT PIVOT DOOR

REFERENCED ON:

1 1/2" = 1'-0"A5.1 A1.26 PLAN DETAIL @ SOUTH LOCKERS

REFERENCED ON:

1 1/2" = 1'-0"A5.1 A1.25 PLAN DETAIL @ WEST LOCKERS

NOTE: DOOR AND FRAME HEIGHTS TO MATCH EXISTING DOORS TO REMAIN. FIELD VERIFY BEFORE MANUFACTURE.

REFERENCED ON:

3" = 1'-0"A5.1H1 HEAD DETAIL

REFERENCED ON:

3" = 1'-0"A5.1J1 JAMB DETAIL

REFERENCED ON:

3" = 1'-0"A5.1H2 HEAD DETAIL

REFERENCED ON:

3" = 1'-0"A5.1J2 JAMB DETAIL

REFERENCED ON:

1 1/2" = 1'-0"A5.1 A1.27 PLAN DETAIL @ SOUTH LOCKERS

Second Floor10' - 8"

2"8'

- 0"

EXISTING WOOD TRUSSES

METAL STUD HEADER

SUSP. GRID AND TILE CEILING -SEE RCP FOR LOCATIONS ADJACENT TO LOCKERS

2"

CUSTOM WOOD/LAMINATE LOCKER PL-2

CONT. SEALANT

PRE-FINISHED LAMINATE REVEAL BLOCK (PL-2) BY LOCKER MFR. (AT 8'-2" SUSP. GRID CEILING ONLY; NOT AT 8'-0" GWB CEILING SOFFIT)

2' - 0"

1' - 0

"1'

- 2"

2"4'

- 0"

2"1'

- 4"

2"

4' - 2

"1'

- 8"

GWB CEILING SOFFIT -SEE RCP FOR LOCATIONS ADJACENT TO LOCKERS

METAL HANGING ROD

5' - 6

"

FIXED SHELF, PL-2

LOWER SHELF, PL-2

ELEC. OUTLET WITH (1) OUTLET AND (2) USB PORTS, SEE ELEC. DWGS.(1 PER LOCKER)

LOCKER FASCIA, PL-2

2' - 6

"

1"

BASE, PL-2

1"

VENTED DRAWER, PL-2, ON HEAVY-DUTY SLIDES WITH (3) ROUTED 3/8" VENT SLOTS AT 2" O.C.

DRAWER PULL, SEE SPECS

1"

CLOTHES HOOK (3) PER LOCKER, SEE SPECS.

6"

5' - 0

"

Second Floor10' - 8"

6 1/4" SOLID SURFACE SILL SS-1

EXISTING WOOD TRUSSES

7' - 6

"

2' - 1

0"

GWB ON 3-5/8" METAL STUD FRAMING

TEAM LOUNGE201

STORAGE203B

BASE AS SCHEDULED

PL-1 WALL FINISH BELOW SILL

WHITE BOARD PAINT FINISH ABOVE SILL

1 1/

2"

Second Floor10' - 8"

2' - 1"

BASE AS SCHEDULED

HARDWARE - SEE SPECS

1/2" BACKER PANEL ON 3/4" X 3-1/2" HARDWOOD WEB FRAMING

1/4" DIA. HOLES @ 3" O.C. W/ HEAVY DUTY SHELF SUPPORTS

3/4" ADJUSTABLE SHELF

SOLID SURFACE COUNTER TOP SS-1

DRAWER

HARDWARE - SEE SPECS

ELEC. OUTLET, SEE ELEC. DWGS.

CERAMIC TILE ACCENT WALL, SEE FINISH PLANS

EXISTING WOOD TRUSSES

PLASTIC LAMINATE CABINETS, PL-1

Second Floor10' - 8"

2A5.2

3' - 5 1/8"2' - 8"1' - 8"2' - 8"2' - 8"2' - 8"2' - 8"2"

2' - 1

0"1

1/2"

CERAMIC TILE ACCENT WALL

REFRIGERATOR(N.I.C.)

SOLID SURFACE COUNTER TOP SS-1

24" DEEP BASE CABINETS WITH ADJUSTABLE SHELVES, PL-1

7' - 6

"

24" DEEP BASE CABINET WITH DRAWERS, PL-1

GWB SOFFIT BEYOND

Second Floor10' - 8"

CUSTOM WOOD/LAMINATE LOCKER PL-2

GWB CEILING SOFFIT -SEE RCP FOR LOCATIONS ADJACENT TO LOCKERS

METAL HANGING ROD

FIXED SHELF, PL-2

LOWER SHELF, PL-2

ELEC. OUTLET WITH (1) OUTLET AND (2) USB PORTS, SEE ELEC. DWGS.

VENTED DRAWER, PL-2, ON HEAVY-DUTY SLIDES WITH (3) ROUTED 3/8" VENT SLOTS AT 2" O.C.

LOCKER FASCIA, PL-2

SUSP. GRID AND TILE CEILING -SEE RCP FOR LOCATIONS ADJACENT TO LOCKERS

8' - 0

"2"

2" REVEAL WHERE ADJACENT TO CEILING GRID LOCATIONS, SEE SECTION

1' - 0

"1'

- 2"

4' - 2

"1'

- 8"

2' - 0"

2' - 6

"

2"

DRAWER PULL, SEE SPECS

5 1/4" 1' - 0" 5 1/4"

2"2"

BASE, PL-2

CLOTHES HOOK (3) PER LOCKER, SEE SPECS.

5' - 0

"

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

5/15

/201

8 3:

05:3

0 PM

A5.2U479

.18

05.1

5.18

CASE

WOR

K &

LOCK

ER D

ETAI

LSAu

thor

Chec

ker

OUTD

OOR

VOLL

EYBA

LL LO

CKER

/FILM

ROOM

REN

OVAT

ION

107

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

08

REVI

SIO

N S

NO.

NAM

EDA

TE

REFERENCED ON:

A5.26 AXONOMETRIC AT LOCKERS

REFERENCED ON:

1" = 1'-0"A5.2 A1.24 SECTION AT LOCKER

REFERENCED ON:

1" = 1'-0"A5.2 A3.11 SECTION AT CURVED WALL

REFERENCED ON:

1" = 1'-0"A5.2 A1.22 SECTION AT BREAK AREA CASEWORK

REFERENCED ON:

1/2" = 1'-0"A5.2 A4.13 CASEWORK ELEVATION @ TEAM LOUNGE

REFERENCED ON:

1" = 1'-0"A5.2 A4.15 ELEVATION AT LOCKER

CPT-2

LVT

CPT-2CPT-1

EX.

NOT IN PROJECT SCOPEFLAT SCREEN TV(N.I.C.)

CPT-1

CPT-2

NEW RUBBER FLOORING (RBT)AT STAIRS/FIRST FLOOR LANDING

CPT-1

CPT-1

FLAT SCREEN TV (N.I.C.)

PING PONG TABLE N.I.C.

CORRIDORH204

STAIR 2ND FLRST01

COMM./ELEC.215

STORAGE201B

TEAM LOUNGE201

STORAGE203B

WOMEN'S RESTROOM202

CORRIDORH202

WOMEN'S LOCKERROOM

203

CT-3

P-1/WB-1

P-1/WB-1

P-4

RS-1RS-1RS-1RS-1

CPT-3 @ SECOND FLOOR LANDING

P-1,WG*

P-1,WG*

CT-2, INFILL AS REQ'D

WC-1 WC-1 WC-1 WC-1

ALIGN NEW FLOOR FINISH WITH DOOR JAMB

STEP,SS-2

DIRECTION OF GRAIN

DIRECTION OF GRAIN

DIRECTION OF GRAIN

DIRECTION OF GRAIN

DIRECTION OF GRAIN

DIRECTION OF GRAIN

LONG AXIS OF TILE

WFWF

WF

PL-1 (BELOW SILL)

CT-2

P-3 P-3 P-3

REPAINT EAST WALL AND REPLACE CHAIR RAIL TO MATCH EX, EAST WALL ONLY . SEE FLOOR PLAN AND DEMO PLAN NOTES

NOT IN PROJECT SCOPE

RS-1

EXISTING BASE TO REMAIN, UNLESS DAMAGE, THEN REPLACE W RB-2

FT-1

FT-3

FT-2

FT-4

ABBREVIATION DESCRIPTION BASIS OF DESIGN

BASERB-1

FLOOR

WALLS

P-1

CEILINGSAPC-1

CT-1

LVTRBT

GB/P-2

4" RUBBER COVE

PAINT--GENERAL WALL COLOR

ACOUSTICAL PANEL CEILING-STD.

GROUT-FLOORS

LUXURY VINYL TILE - PLANK RUBBER TILE AND TREAD

GYPSUM WALL BOARD - PAINTED

JOHNSONITE, RECESS WALL BASE, #48 GREY WG

LOW-SHEEN, EGGSHELL, TO MATCH SW#9166 DRIFT OF MIST

ARMSTRONG, GEORGIAN #1752 OR EQ., 2X2 BEVELED TEGULAR, STD. 15/16" GRID

MILLIKEN, FREELAY, HERITAGE WOOD, #HER208JOHNSONITE, RUBBER STAIR TREADS/RISERS, BAMBOO FINISH, COLOR: #48 GREY WG, VIBMTR TREAD, BMRT TILE.

SEE P-2 ABOVE

CT-2 CERAMIC TILE- T-ROOMS AMERICAN OLEAN OR EQ, COLOR TO MATCH EXISTING, FIELD VERIFY

WC-1 WALLCOVERING-METALLIC TEXTURE

MISC.

CASEWORKRS ROLLER SHADES MANUAL ROLLER SHADE, 5% MESH

T PARTITIONS SOLID PLASTIC POLYMER

ABET LAMINATI, COLOR: #598, FINISH: PAPIER

CARPET - TILE, WALK-OFF TEXTURE

P-3* PAINT-WALLS EGGSHELL- TO MATCH SW#7019 GAUNTLET GREY

P-2 PAINT-CEILINGS, 'WHITE TONE,' FLAT FLAT--TO MATCH SW # 7005 PURE WHITE

P-4 PAINT- PRIMARY ACCENT EGGSHELL-TO MATCH USC CUSTOM 'GARNET' SW# CCE 02 32 64 128

MILLIKEN, QUADRUS, LIFTOFF, COLOR: #LIF144-27 BOUNDARY

SS-1

PL-2

CPT-3CPT-2 CARPET - ACCENTCPT-1 CARPET - TILE, FIELD MILLIKEN, ARCADIA, SHORELINE, #144 ACREAGE

COUNTERTOPS, LAVS, SILLS

PLASTIC LAMINATE - LOCKERS

CORIAN, COLOR: DOVE

SCRANTON PRODUCTS, HINY HIDERS, METALLIC COLLECTION, STAINLESS EX

WB-1 WRITE-ON SURFACE COATING OVER PAINT

CHILEWICH, WALLTEX CHAIN WEAVE FG, COLOR: PEWTER

SPC SPECIALTY CEILING 4" SOFFIT DRYWALL/TRIM UNIT, FOR INSET OF STRETCH FABRIC GRAPHIC - ARMSTRONG AXIOM TRIM OR EQ.

PL-1 PLASTIC LAMINATE-GEN. CASEWORKWILSONART #COSMIC STRANDZ

P-5 PAINT- TO MATCH EGGSHELL-TO MATCH EXISTING

MILLIKEN, ARCHIPELAGO, SEA GRAPE, COLOR: 171 SAND

ATLAS CONCORDE, MOTION SILVER, 12 X24

CT-3 CERAMIC TILE-ACCENT WALL ATLAS CONCORDE, 3D WALL, BLADE, WHITE MATTE, 16X32 (~5.50/SF)

WOLF GORDON WINK OR EQ. WRITE-BOARD PAINT ON PAINTED DRYWALL

WG* WALL GRAPHIC-FUTURE* WALL GRAPHIC LOCATION ONLY--FOR FUTURE REFERENCE, N.I.C.

APC-1* SEE APC-1 ABOVE REPLACE TILES ONLY, EXISTING GRID TO REMAIN

GR-1CERAMIC TILE

LATICRETE, #78 STERLING SILVER, SANDED

GR-2 GROUT-WALLS LATICRETE, #44 BRIGHT WHITE, UNSANDED

WF WINDOW FILM TRANSLUCENT FILM TO BE APPLIED TO EXISTING GLASS, SEE SPEC.

EX WD EXISTING WOOD BASE, PAINTED PAINT, AS SCHEDULED

APC-2 ACOUSTICAL PANEL- MOISTURE RESIST. ARMSTRONG, CERAMAGUARD #605 OR EQ., 2X2 W. ALUM. GRID

P-3 PAINT-TRIM, RAILS, FRAMES, U.N.O. SEMI-GLOSS, COLOR TO MATCH SW#7019 GAUNTLET GREY

SS-2 TILE THRESHOLD@ SHOWERS MARBLE THRESHOLD, STD. CARRERA MARBLE

RB-2 4" RUBBER COVE JOHNSONITE, STANDARD WALL BASE, BLACK

EX EXISTING NO NEW FINISH

BR BRICK EXISTING BRICK, TO REMAIN

LOBBYV102

VESTIBULEV101

STAIR 1ST FLRST01

CORRIDORH101

DIRECTION OF GRAIN

DIRECTION OF GRAIN

ELEC.113

P-1 P-1

EXTEND NEW CARPET TO SEAMOF EXISTING CPT

FT-3

FT-3

FT-2 FT-2

EX

CPT-1

EX CT

CT-1

RBT

CPT-2

CPT-3

LVT

WHERE SPECIFIC PRODUCTS ARE INDICATED, ITEM DESIGNATION INCORPORATES QUALITY AND AESTHETIC APPEARANCE FOR 'BASIS OF DESIGN.' SEE SPECIFICATIONS FOR EQUAL MANUFACTURER'S PER PRODUCT TYPE INDICATED. DEPENDING ON LOCATION OF ITEM, ALTERNATES SHALL MATCH IN COLOR/ TEXTURE, AS WELL AS PERFORMANCE CRITERIA, PER ARCHITECT'S APPROVAL.

ALL PAINT COLOR SELECTIONS SHALL BE FIELD VERIFIED WITH ARCHITECT IN LIGHTED CONDITIONS PRIOR TO FINAL INSTALLATION, SEE SPEC. RE: MOCK-UPS

SEE FINISH PLANS FOR FLOOR MATERIAL TRANSITIONS AT DOOR THRESHOLDS AND IN OPEN FLOOR AREAS.

REFERENCE REFLECTED CEILING PLANS FOR EXTENT/LOCATION OF CEILING FINISH DESIGNATIONS AND HEIGHTS.

SEE FINISH PLANS AND/OR ENLARGED INTERIOR PLANS & ELEVATIONS FOR EXTENT OF SPECIFIC FINISH DESIGNATIONS.

FINISH COLUMNS IN OPEN AREAS TO MATCH ADJACENT WALLS, UNLESS NOTED OTHERWISE.

SEE FINISH PLANS FOR BLINDS AND ROLLER SHADE LOCATIONS.

SEE SILL DETAILS, FLOORING SPECIFICATIONS AND FINISH SCHEDULE FOR TRANSITION STRIPS.

ALL FURNITURE N.I.C., TYPICAL.

NO TRANSITION STRIP BETWEEN LVT AND CARPET EDGE@ TEAM LOUNGE

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

DOOR AND FRAMEAS SCHEDULED

CERAMIC TILE

METAL TRANSITION STRIP, SEE TILE SPECS

CARPET

DOOR AND FRAMEAS SCHEDULED

RBT

RESILIENT MOULDING, SEE RESILIENT ACCESSORIES

CARPET

DOOR AND FRAMEAS SCHEDULED

CARPET

RESILIENT MOULDING, SEE RESILIENT ACCESSORIES

CARPET

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F TH

E GA

RVIN

DES

IGN

GROU

P, IN

C.

THE

REPR

ODUC

TION

, COP

YING

, OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

TH

E W

RITT

EN C

ONSE

NT O

F TH

E GA

RVIN

DES

IGN

GROU

P IS

PR

OHIB

ITED

AND

ANY

IN

FRIN

GEM

ENT

WIL

L BE

SUB

JECT

TO

LEG

AL A

CTIO

N.

@20

03 G

ARVI

N DE

SIGN

GRO

UP, I

NC.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

5/15

/201

8 3:

05:4

6 PM

A6.1U479

.18

05.1

5.18

ENLA

RGED

FINI

SH P

LANS

&SC

HEDU

LES

Auth

or

Chec

ker

OUTD

OOR

VOLL

EYBA

LL LO

CKER

/FILM

ROOM

REN

OVAT

ION

107

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

08

REVI

SIO

N S

NO.

NAM

EDA

TE

REFERENCED ON:

1/4" = 1'-0"A6.11 SECOND FLOOR ENLARGED FINISH PLAN

SCHEDULED INTERIOR FINISHES

REFERENCED ON:

1/4" = 1'-0"A6.1 A1.12 FIRST FLOOR ENLARGED FINISH PLAN

FINISH LEGEND GENERAL NOTES - INTERIOR FINISHES

NOTE: ALL WALL ORIENTATIONS BASED ON PLAN NORTH "UP" THE PAGE

REFERENCED ON:

1" = 1'-0"A6.13 FT1 - CPT/TILE

FINISH SCHEDULE - ALTERNATE NO. 1

ROOMNO. ROOM NAME BASE FLOOR

WALL FINISHCEILING Comments LevelNORTH EAST SOUTH WEST

H101 CORRIDOR EX,P-3 CPT-1 P-1,WG* P-1 P-1 P-1 APC-1* First FloorV101 VESTIBULE EX WD,P-3 CPT-3 P-1 P-1 P-1 P-1 APC-1* First FloorV102 LOBBY EX WD,P-3 CPT-1 -- P-1 P-1 P-1 APC-1*,EX/GB/P-5 First Floor

FINISH SCHEDULE - BASE BID

ROOMNO. ROOM NAME BASE FLOOR

WALL FINISHCEILING Comments LevelNORTH EAST SOUTH WEST

201 TEAM LOUNGE RB-1 LVT,CPT-1,CPT-2 P-1,P-4,CT-3,PL-1 P-1/WB-1,P-4 P-1,WC-1,WB-1,P-3 P-1/WB-1,P-1 APC-1,GB/P-1 RS-1 Second Floor201B STORAGE RB-1 CPT-2 P-1 P-1 P-1 P-1 APC-1 RS-1 Second Floor202 WOMEN'S RESTROOM EX/CT-2 CT-1,EX EX,CT-2 EX EX EX APC-2 Second Floor203 WOMEN'S LOCKER ROOM RB-1 CPT-1,CPT-2 P-3*,P-1 P-3*,P-1 P-3* P-3* APC-1 WF Second Floor203B STORAGE RB-1 CPT-1 P-1 P-1 P-1 P-1 APC-1 Second FloorH202 CORRIDOR EX/RB-2 EX EX EX/P-5 P-5 EX EX Second FloorH204 CORRIDOR EX/RB-2 CPT-3, EX P-1 P-1 P-1 P-1 EX Second FloorST01 STAIR 1ST FLR RB-1 RBT P-1 P-1 P-1 P-1 EX First FloorST01 STAIR 2ND FLR RB-1 RBT,CPT-3 P-1 P-1 P-1 P-1 EX Second Floor

ALTERNATE NO. 1

NOTE: ALL WALL ORIENTATIONS BASED ON PLAN NORTH "UP" THE PAGE

REFERENCED ON:

1" = 1'-0"A6.14 FT2 - CPT/ RBT

REFERENCED ON:

1" = 1'-0"A6.15 FT3 - CPT/CPT

21

1

1 1

1 1 1

1 1

1

1

1

WOMEN'SRESTROOM

202

STORAGE203B

WOMEN'SLOCKERROOM

203

TEAMLOUNGE

201

STORAGE201B

STAIR 2NDFLRST01

CORRIDORH204

COMM./ELEC.215

CORRIDORH204

CORRIDORH202

10ø

14x8 8ø

A 200

A 200

B 285B 50

B

DEMOLITION NOTES

REMOVE EXISTING CEILING GRILLE AND DUCT BACK TO TRUNK DUCT. PATCH TRUNK DUCT WITH SHEET METAL AND MASTIC. PATCH INSULATION TO MATCH EXISTING.

REMOVE EXISTING TRANSFER GRILLE AND DUCT BACK TO FIRE DAMPER.

1

2

REGISTERED

PROFES

SI O

N A L E N G I N E E R

W I L L I A MC

.LI

VIN

GSTON

SOUTHCA

R OL I N A

No. 1

7994

C E R T I F I C A T EOF

AUT

HORIZATION

SOUTHCA

R OL I N A

SWYG

ERT A

NDAS

SOCIA

TES,

LTD.

NO. C

00227

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G A

ND T

HE D

ESIG

N TH

EREO

N AR

E TH

E PR

OPE

RTY

OF

THE

GAR

VIN

DESI

GN

GRO

UP, I

NC.

THE

REPR

ODU

CTIO

N, C

OPY

ING

, OR

USE

OF

THIS

DRA

WIN

G W

ITHO

UT

THE

WRI

TTEN

CO

NSEN

T O

F TH

E G

ARVI

N DE

SIG

N G

ROUP

IS

PRO

HIBI

TED

AND

ANY

INFR

ING

EMEN

T W

ILL

BE S

UBJE

CT

TO L

EGAL

ACT

ION.

@20

03 G

ARVI

N DE

SIG

N G

ROUP

, INC

.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

C O N S U L T I N G E N G I N E E R S

Swygert & Associates

DBA Swygert & Assoc., Ltd.Post Office Box 11686Columbia, S.C. 29211

Telephone: (803) 791-9300Facsimile: (803) [email protected] M1.1U4

79.1

8

05.1

1.18

SECO

ND F

LOOR

PLA

NSDE

M

WCL

OUTD

OOR

VOLL

EYBA

LL L

OCKE

R/FI

LMRO

OM R

ENOV

ATIO

N

139

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

05

5−15−18

1/4" = 1'-0"M1.11 SECOND FLOOR DEMOLITION PLAN

1/4" = 1'-0"M1.12 SECOND FLOOR RENOVATION PLAN

REV

ISIO

NS

NO

.N

AM

ED

ATE

GENERAL NOTESALL WORK SHALL BE IN ACCORDANCE WITH THE 2015 INTERNATIONAL MECHANICAL CODE, 2015 INTERNATIONAL FUEL GAS CODE, 2009 INTERNATIONAL ENERGY CONSERVATION CODE, AND 2005 SMACNA HVAC DUCT CONSTRUCTION STANDARD. ALL LOCAL CODES OR REQUIREMENTS STILL APPLY.

VISIT SITE PRIOR TO BIDDING. THIS CONTRACTOR SHALL DETERMINE DIFFICULTY OF INSTALLATION AND REFLECT THIS IN HIS BIDDING.

DO NOT SCALE DRAWINGS. SEE ARCHITECTURAL DRAWINGS AND REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF DOORS, WINDOWS, AIR DISTRIBUTION, ETC.

DO NOT SCALE DRAWINGS. THIS CONTRACTOR SHALL VERIFY ALL EXISTING ITEMS AND LOCATIONS IN THE FIELD.

ALL PIPING AND DUCTWORK LOCATIONS SHALL BE COORDINATED WITH WORK UNDER OTHER DIVISIONS OF THE SPECIFICATIONS TO AVOID INTERFERENCE.

ALL DUCTWORK INSULATION SHALL BE RUN CONTINUOUSLY THROUGH PARTITIONS.

ALL MECHANICAL ITEMS EXTENDING THROUGH WALLS SHALL BE FLASHED AND COUNTERFLASHED.

THIS CONTRACTOR SHALL PROVIDE ALL ITEMS OF MISCELLANEOUS STEEL AS REQUIRED FOR INSTALLATION OF ALL MECHANICAL ITEMS.

CORRECT SETTINGS ON ALL BALANCING FITTINGS SHALL BE PERMANENTLY MARKED. PROVIDE ORANGE FLAGGING RIBBON ON EACH DAMPER HANDLE FOR EASY IDENTIFICATION.

THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ANY NECESSARY DISMANTLING OF EQUIPMENT TO BE REMOVED.

ITEMS REMOVED UNDER THIS CONTRACT SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE DISPOSED OF PROPERLY.

THE HVAC SYSTEMS SHALL NOT BE OPERATED DURING HEAVY CONSTRUCTION OPERATIONS INCLUDING MASONRY, GYPSUM BOARD SANDING, HEAVY CLEANUP ACTIVITIES, OR OTHER ACTIVITIES THAT CREATE AIRBORNE PARTICLES OR DEBRIS. ALL SYSTEMS SHALL BE CLEAN OF CONSTRUCTION DEBRIS, DUST AND DIRT AT FINAL COMPLETION. DUCT CLEANING AND UNIT/COIL CLEANING SHALL BE PERFORMED IF REQUIRED. IF EQUIPMENT OPERATES DURING CONSTRUCTION PROVIDE FILTER MEDIA OVER ALL RETURN GRILLES AND RETURN DUCT OPENINGS TO PROTECT DUCTS AND EQUIPMENT.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

100A

LEGEND

TYPE "A" DIFFUSER, 100 CFM

SYMBOL DESCRIPTION

48"x24" RECTANGULAR DUCT

RETURN AND FRESH AIR DUCTWORK

RECTANGULAR SUPPLY DUCTWORK

48x24

CONNECTION POINT OF NEW TO EXISTING

EXHAUST DUCTWORK

B

TAG

A

NECK SIZE

PERFORATED SUPPLY

DESCRIPTION

PRICE

MANUFACTURER

APDC

MODEL

LAY-IN

FRAME CFM MAX NC

30

FACE SIZE REMARKS

1, 2

AIR DISTRIBUTION SCHEDULE

1. PROVIDE WITH STANDARD WHITE FINISH.2. PROVIDE ALUMINUM OR ALUMINIZED STEEL CONSTRUCTION.

PERFORATED EXHAUST PRICE APDDR LAY-IN

126-250 8"ø

30

24"x24"

1, 20-1,000 22"x22" 24"x24"

INSULATE BACKPAN OF ALL DIFFUSERSAND GRILLES

DIFFUSER (SEE SCHEDULEFOR MODEL AND SIZE)

RIGID ROUND SHEET METALELBOW (INSULATED)

ROUND SHEET METALRUNOUT (INSULATED)

SPIN-IN FITTING WITH 45° EXTRACTORAND MANUAL BALANCING DAMPER WITHSTANDOFF LOCKING QUADRANT (INSULATED)

L.P. SUPPLYTRUNK DUCT(INSULATED)

FLEXIBLE DUCT RUNOUT (SAME SIZEAS DIFFUSER NECK) 8'-0" LONG MAX.

MIN. 5"

RETURN GRILLE; SEE AIRDISTRIBUTION SCHEDULEFOR GRILLE SIZE

SEE ARCHITECTURALDRAWINGS FORCEILING TYPE

SAME SIZE AS GRILLENECK SIZE

RIGID ROUND SHEET METALELBOW (INSULATED)

PAINT INSIDE OF PLENUMFLAT BLACK

REGISTERED

PROFES

SI O

N A L E N G I N E E R

W I L L I A MC

.LI

VIN

GSTON

SOUTHCA

R OL I N A

No. 1

7994

C E R T I F I C A T EOF

AUT

HORIZATION

SOUTHCA

R OL I N A

SWYG

ERT A

NDAS

SOCIA

TES,

LTD.

NO. C

00227

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G A

ND T

HE D

ESIG

N TH

EREO

N AR

E TH

E PR

OPE

RTY

OF

THE

GAR

VIN

DESI

GN

GRO

UP, I

NC.

THE

REPR

ODU

CTIO

N, C

OPY

ING

, OR

USE

OF

THIS

DRA

WIN

G W

ITHO

UT

THE

WRI

TTEN

CO

NSEN

T O

F TH

E G

ARVI

N DE

SIG

N G

ROUP

IS

PRO

HIBI

TED

AND

ANY

INFR

ING

EMEN

T W

ILL

BE S

UBJE

CT

TO L

EGAL

ACT

ION.

@20

03 G

ARVI

N DE

SIG

N G

ROUP

, INC

.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

C O N S U L T I N G E N G I N E E R S

Swygert & Associates

DBA Swygert & Assoc., Ltd.Post Office Box 11686Columbia, S.C. 29211

Telephone: (803) 791-9300Facsimile: (803) [email protected] M2.1U4

79.1

8

05.1

1.18

DETA

ILS,

NOT

ES, S

CHED

ULES

, AND

LEGE

ND

DEM

WCL

OUTD

OOR

VOLL

EYBA

LL L

OCKE

R/FI

LMRO

OM R

ENOV

ATIO

N

139

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

05

5−15−18

REV

ISIO

NS

NO

.N

AM

ED

ATE

NO SCALECEILING DIFFUSER DETAIL

NO SCALEDUCTED RETURN GRILLE DETAIL

21 1

3 3

5

3

6

EXISTING WALLCLEANOUT TOREMAIN

WOMEN'SRESTROOM

202

STORAGE203B

WOMEN'SLOCKERROOM

203

TEAMLOUNGE

201

STORAGE201B

STAIR 2NDFLRST01

CORRIDORH204

COMM./ELEC.215

CORRIDORH204

CORRIDORH202

P-1

P-1 P-1P-2P-2P-2

P-3APV

PIPING TO BE ROUTED AROUNDELECTRICAL ROOM OF FLOORBELOW

2"

½" (ABOVECEILING)

4

3

2

2

2

11 1

5

¾"

¾"

6

2"

FD

½" (TO ICE MAKERBOX)

½"

DEMOLITION NOTES

EXISTING WALL MOUNTED FLUSH VALVE WATER CLOSET TO BE REMOVED COMPLETELY. CAP EXISTING WASTE, VENT, AND SUPPLY PIPING AS REQUIRED.

EXISTING COUNTERTOP LAVATORY TO BE REMOVED COMPLETELY. CAP EXISTING WASTE, VENT, AND SUPPLY PIPING AS REQUIRED.

EXISTING SHOWER VALVE AND HEAD TO BE REMOVED COMPLETELY. CAP EXISTING SUPPLY PIPING AS REQUIRED.

EXISTING DRINKING FOUNTAIN AND WATER FILTER TO BE REMOVED COMPLETELY. CAP EXISTING VENT AND SUPPLY PIPING AS REQUIRED. EXISTING WASTE PIPING BELOW FLOOR TO BE REUSED.

CUT EXISTING TRENCH GRATE BODY AND FRAME AS REQUIRED FOR NEW FLOOR PLAN. FINISH END OF GRATE SMOOTH AND CAP DRAIN BODY AT 4" FROM NEW WALL.

EXISTING WALL HYDRANT AND BOX TO BE REMOVED AND RELOCATED. CAP EXISTING SUPPLY LINE AS REQUIRED. SEE RENOVATION PLAN FOR NEW LOCATION.

1

2

3

4

5

6

NOTES TO SHEET

CONNECT NEW 1¼" WASTE LINE, ¾" COLD WATER LINE, AND ½" HOT WATER LINE TO EXISTING WASTE AND SUPPLY PIPING IN CHASE.

CONNECT NEW 4" WASTE LINE AND 1" SUPPLY LINE TO EXISTING WASTE AND SUPPLY PIPING IN CHASE.

TURN SUPPLY PIPING DOWN INTO CHASE AND CONNECT TO EXISTING DOMESTIC WATER LINES.

CONNECT TO EXISTING WASTE LINE AT REMOVED DRINKING FOUNTAIN.

RELOCATE EXISTING WALL HYDRANT AND BOX TO NEW WALL OF SHOWER STALL. MOUNT AT 18" ABOVE FINISHED FLOOR.

EXTEND INTO CHASE AND CONNECT TO NEAREST EXISTING WASTE LINE.

1

2

3

4

5

6

REGISTERED

PROFES

SI O

N A L E N G I N E E R

T O D DF .

SWYGERT

SOUTHCA

R OL I N A

No. 1

5574

C E R T I F I C A T EOF

AUT

HORIZATION

SOUTHCA

R OL I N A

SWYG

ERT A

NDAS

SOCIA

TES,

LTD.

NO. C

00227

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G A

ND T

HE D

ESIG

N TH

EREO

N AR

E TH

E PR

OPE

RTY

OF

THE

GAR

VIN

DESI

GN

GRO

UP, I

NC.

THE

REPR

ODU

CTIO

N, C

OPY

ING

, OR

USE

OF

THIS

DRA

WIN

G W

ITHO

UT

THE

WRI

TTEN

CO

NSEN

T O

F TH

E G

ARVI

N DE

SIG

N G

ROUP

IS

PRO

HIBI

TED

AND

ANY

INFR

ING

EMEN

T W

ILL

BE S

UBJE

CT

TO L

EGAL

ACT

ION.

@20

03 G

ARVI

N DE

SIG

N G

ROUP

, INC

.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

C O N S U L T I N G E N G I N E E R S

Swygert & Associates

DBA Swygert & Assoc., Ltd.Post Office Box 11686Columbia, S.C. 29211

Telephone: (803) 791-9300Facsimile: (803) [email protected] P1.1U4

79.1

8

05.1

1.18

SECO

ND F

LOOR

PLA

NSDE

M

TFS

OUTD

OOR

VOLL

EYBA

LL L

OCKE

R/FI

LMRO

OM R

ENOV

ATIO

N

139

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

05

5−15−18

1/4" = 1'-0"P1.11 SECOND FLOOR DEMOLITION PLAN

1/4" = 1'-0"P1.12 SECOND FLOOR RENOVATION PLAN

REV

ISIO

NS

NO

.N

AM

ED

ATE

GENERAL NOTESALL WORK SHALL BE PERFORMED ACCORDING TO ALL LOCAL, STATE, NATIONAL CODES, AND THE 2015 INTERNATIONAL PLUMBING CODE.

DO NOT SCALE DRAWINGS. SEE ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONS, FIXTURE LOCATIONS, ETC.

CONTRACTOR SHALL, PRIOR TO BIDDING, VISIT THE SITE AND DETERMINE SCOPE OF WORK, MATERIALS REQUIRED AND DIFFICULTY OF INSTALLATION. WORK SHALL BE INSTALLED COMPLETE AND OPERATIVE.

COORDINATE CLOSELY WITH ALL WORK DONE UNDER OTHER DIVISIONS OF THE SPECIFICATIONS TO AVOID INTERFERENCE AND CONFLICT.

OPENINGS THROUGH WALLS AND FLOORS SHALL BE CUT NO LARGER THAN REQUIRED FOR INSTALLATION AND SHALL BE SMOOTH.

ALL OPENINGS THROUGH WALLS SHALL BE FLASHED AND COUNTER FLASHED.

ALL PIPING IS SHOWN DIAGRAMMATIC. HOWEVER, CONTRACTOR SHALL PROVIDE ALL REQUIRED FITTINGS AND PIPING FOR ALL OFFSETS AND/ OR CHANGES IN ELEVATION.

ALL PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH THE SPECIFICATIONS, AND AS DETAILED ON THESE DRAWINGS.

CONTRACTOR SHALL VERIFY ACTUAL LOCATIONS AND INVERTS OF THE EXISTING UTILITIES PRIOR TO START OF CONSTRUCTION.

ALL PIPING INSULATION SHALL BE RUN CONTINUOUSLY.

CEILING REMOVAL AND REPLACEMENT AS REQUIRED FOR INSTALLATION OF NEW PIPING ON FLOOR BELOW SHALL BE BY THIS CONTRACTOR. REPLACE ANY DAMAGED TILES WITH NEW. CEILING TILES TO BE REPLACED WITH GRID REMAINING IN FIRST FLOOR LOBBY BY OTHERS UNDER ALTERNATE NO. 1. SEE ARCHITECTURAL PLANS FOR SCOPE.

THIS CONTRACTOR SHALL EXTEND A 1/2-INCH COPPER LINE FROM NEAREST COLD WATER SUPPLY TO REFRIGERATOR ICE MAKER. PROVIDE OATEY, OR APPROVED EQUAL, MODEL 38681 ICE MAKER BOX WITH VALVE MOUNTED AT 2'-0" ABOVE FINISHED FLOOR.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

LEGEND

DOMESTIC COLD WATER LINE

DOMESTIC HOT WATER LINE

SANITARY WASTE LINE

PIPE TURNS TO, AWAY,

SYMBOL DESCRIPTION

APV AUTOMATIC PLUMBING VENT

CONNECTION POINT OF NEW TO EXISTING

BALL VALVE

PLUMBING FIXTURE SCHEDULE

P. NO.

P-1

MIN. SUPPLY

CWNAMEFIXTURE MFGR. MFGRS. NO. SIZE HW REMARKS

1"KINGSTONWATER CLOSET KOHLER K-4325 - - - - -

P-3 1/2"LUSTERTONESINK ELKAY ELUH281610 30½"x18½" 1/2" UNDERCOUNTER MOUNTED WITH DELTA MODEL 9978-DST FAUCET WITH PULL OUT SPRAY HOSE, LK-35 CUP STRAINER, McGUIRE 2167 1/2" CAST BRASS SUPPLIES WITH STOPS, McGUIRE 8912 1-1/2" P-TRAP, AND T&S BRASS MODEL B-1210-01-WFK GLASS FILLER WITH WATER FILTRATION KIT. NOTE DEPTH OF SINK WHEN ROUGHING IN PIPING.

WITH SLOAN MODEL 111-XL FLUSH VALVE, AND BENEKE 527 SEAT, AND CHAIR CARRIER.

P-2 3/8"CAXTONLAVATORY KOHLER K-2211 20¼"x17¼" UNDERCOUNTER MOUNTEDWITH DELTA MODEL 22C651FAUCET, WATTS, OR APPROVEDEQUAL, SERIES LFUSG-B ASSE 1070 THERMOSTATIC MIXINGVALVE, McGUIRE 155WC OFFSET GRID DRAIN, McGUIRE H165 3/8"CAST BRASS SUPPLIES WITHSTOPS, AND McGUIRE 88721-1/4" P-TRAP. MOUNT MIXINGVALVE AS HIGH AS POSSIBLEUNDER COUNTERTOP.

3/8"

FD - -- - -FLOOR DRAIN ZURN ZN-415-S - - - - - WITH 5"x5" SQUARE NICKLE BRONZE STRAINER, P-TRAP, AND PROSET, OR APPROVED EQUAL, TRAP GUARD.

18" TO TOP OF SEAT

P-1

FLUSH VALVE

FINISHED WALL

SUPPLY PIPE SUPPORT

CLOSET CARRIERASSEMBLY

CAULK AROUND PERIMETEROF WALL MOUNTED FIXTURE

CLOSETCARRIERASSEMBLY

SUPPLY PIPESUPPORT

SINK

FINISHED WALL

STUDOR, INC., ORAPPROVED EQUAL,2" MINI-VENTAUTOMATICPLUMBING VENT

2"

4" MINIMUM

FINISHEDFLOOR

SEE FLOOR PLANFOR CONTINUATION

REGISTERED

PROFES

SI O

N A L E N G I N E E R

T O D DF .

SWYGERT

SOUTHCA

R OL I N A

No. 1

5574

C E R T I F I C A T EOF

AUT

HORIZATION

SOUTHCA

R OL I N A

SWYG

ERT A

NDAS

SOCIA

TES,

LTD.

NO. C

00227

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G A

ND T

HE D

ESIG

N TH

EREO

N AR

E TH

E PR

OPE

RTY

OF

THE

GAR

VIN

DESI

GN

GRO

UP, I

NC.

THE

REPR

ODU

CTIO

N, C

OPY

ING

, OR

USE

OF

THIS

DRA

WIN

G W

ITHO

UT

THE

WRI

TTEN

CO

NSEN

T O

F TH

E G

ARVI

N DE

SIG

N G

ROUP

IS

PRO

HIBI

TED

AND

ANY

INFR

ING

EMEN

T W

ILL

BE S

UBJE

CT

TO L

EGAL

ACT

ION.

@20

03 G

ARVI

N DE

SIG

N G

ROUP

, INC

.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

C O N S U L T I N G E N G I N E E R S

Swygert & Associates

DBA Swygert & Assoc., Ltd.Post Office Box 11686Columbia, S.C. 29211

Telephone: (803) 791-9300Facsimile: (803) [email protected] P2.1U4

79.1

8

05.1

1.18

DETA

ILS,

NOT

ES, S

CHED

ULE,

AND

LEGE

ND

DEM

TFS

OUTD

OOR

VOLL

EYBA

LL L

OCKE

R/FI

LMRO

OM R

ENOV

ATIO

N

139

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

05

5−15−18

NO SCALEWALL MOUNTED WATER CLOSET SUPPLY DETAIL

NO SCALEAUTOMATIC PLUMBING VENT

REV

ISIO

NS

NO

.N

AM

ED

ATE

ELECTRICAL SYMBOL LEGENDDESCRIPTIONSYMBOL SYMBOL

SINGLE RECEPTACLE (WALL MOUNTED @ 18"AFF)

DUPLEX RECEPTACLE (WALL MOUNTED @ 18"AFF)

PHONE OR DATA OUTLET (WALL MOUNTED @ 18"AFF)

MOTOR CONNECTION (AS NOTED)

J JUNCTION BOX (WALL MTD)

J JUNCTION BOX (FLOOR MOUNTED)

DUPLEX RECEPTACLE (FLOOR MOUNTED)

QUADPLEX RECEPTACLE (FLOOR MOUNTED)

DISCONNECT SWITCH, (REFER TO EQUIPMENT CONNECTION SCHEDULE)

DISCONNECT SWITCH, (NON PROTECTED)

SP SPEAKER (CEILING MOUNTED)

SP SPEAKER (WALL MOUNTED)

DUPLEX RECEPTACLE (CEILING MOUNTED)

QUADPLEX RECEPTACLE (CEILING MOUNTED)

R SECURITY CARD READER

S SMOKE DETECTOR (WALL MOUNTED)

D SMOKE DETECTOR (DUCT MOUNTED)

A FIRE ALARM AUDIBLE DEVICE (WALL MOUNTED @ 7'-6" AFF)

WF Wi-Fi ACCESS POINT (CEILING MOUNTED)

AIUADDRESSABLE INTERFACE UNIT (MONITOR OR CONTROL TYPE)

HANDHOLEHH

DESCRIPTION

FSD FIRE / SMOKE DAMPER

W CCTV CAMERA (WALL MOUNTED)

C CCTV CAMERA (CEILING MOUNTED)

PUSH BUTTON CONTROL

H HEAT DETECTOR (CEILING MOUNTED)

SPD SURGE PROTECTION DEVICE

CABLE TRAY

KITCHEN EQUIPMENT CALLOUT (REFER TO SCHEDULE)#

DUPLEX RECEPTACLE (@ 6" ABOVE COUNTER)

DUPLEX RECEPTACLE (GFI TYPE @ 18"AFF)

DUPLEX RECEPTACLE (USB TYPE @ 18"AFF)

QUAD RECEPTACLE (WALL MOUNTED @ 18"AFF)

QUAD RECEPTACLE (GFI TYPE @ 18"AFF)

QUAD RECEPTACLE (USB TYPE @ 18"AFF)

QUAD RECEPTACLE (@ 6" ABOVE COUNTER)

J JUNCTION BOX (CEILING)

PHONE OR DATA OUTLET (MTD ABOVE COUNTER)

PHONE OR DATA OUTLET (FLOOR MOUNTED)

V FIRE ALARM VISUAL DEVICE (WALL MOUNTED @ 7'-6" AFF)

A/V FIRE ALARM AUDIBLE/VISUAL DEVICE (WALL MOUNTED @ 7'-6" AFF)

FIRE ALARM AUDIBLE DEVICE (CEILING MOUNTED)

FIRE ALARM VISUAL DEVICE (CEILING MOUNTED)

FIRE ALARM AUDIBLE/VISUAL DEVICE (CEILING MOUNTED)

A

V

A/V

S SMOKE DETECTOR (CEILING MOUNTED)

FIRE ALARM PULL STATION (WALL MOUNTED @ 48" AFF TOP OF BOX)

F

T FIRE ALARM TAMPER SWITCH

P FIRE ALARM PRESSURE SWITCH

H HEAT DETECTOR (WALL MOUNTED)

F FIRE ALARM FLOW SWITCH

MULTI-PHASE RECEPTACLE (AS NOTED ON PLAN)

CONDUIT CALLOUT (# INDICATES DIAMETER)#" C.

LIGHTING CONTROL CALLOUT (REFER TO SCHEDULE)#

K SECURITY KEY PAD

PANELBOARD (SURFACE MOUNTED)

PANELBOARD (RECESS MOUNTED)

PIV PRESSURE INDICATING VALVE

#

LIGHT SWITCH, SINGLE POLE

LIGHT SWITCH, 3 WAY TYPE

LIGHT SWITCH, 4 WAY TYPE

LIGHT SWITCH, AUTOMATIC (CONNECT TO LCS)

LIGHT SWITCH, DIGITALLY TIMED (0-30 MINUTES)

LIGHT SWITCH, DIMMER TYPE

LOWER CASE SUBSCRIPT INDICATES SWITCH-LEGa

T

D

A

4

3

OS OCCUPANCY SENSOR (CEILING MOUNTED)

OS OCCUPANCY SENSOR (WALL MOUNTED)

PC PHOTOCELL LIGHTING CONTROL

KEY NOTE CALLOUT (REFER TO KEY NOTES ON SHEET)#

CONTROL PANEL (SURFACE MOUNTED)

CONTROL PANEL (RECESS MOUNTED)

REMOTE TEST STATION FOR DUCT MOUNTED DETECTORS (WALL MOUNTED)REMOTE TEST STATION FOR DUCT MOUNTED DETECTORS (CEILING MOUNTED)

T

T

MMOTOR RATED SNAP SWITCH IN NEMA 1 ENCLOSURE

ELECTRICAL METERING DEVICE

ELECTRICAL UTILITY METER & C/T CABINET

M

M

DUPLEX REC/DATA COMBINATION (FLOOR MOUNTED)

QUADPLEX REC/DATA COMBINATION (FLOOR MOUNTED)

MULTI-LEVEL SWITCHING CONFIGURATION

DUPLEX RECEPTACLE (GFI TYPE @ 6" ABOVE COUNTER)DUPLEX RECEPTACLE (USB TYPE @ 6" ABOVE COUNTER) OR NOTED OTHERWISE

QUAD RECEPTACLE (GFI TYPE @ 6" ABOVE COUNTER)QUAD RECEPTACLE (USB TYPE @ 6" ABOVE COUNTER)

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

US21804US21804US21804

No. 26181

RANILORACHTUOS

J EENI

GNE

LANOISSEFORPDESN E CI LA

S

O N E AR

T

L. HERA

No. 26181

RANILORACHTUOS

J EENI

GNE

LANOISSEFORPDESN E CI LA

S

O N E AR

T

L. HERA

No. 26181

RANILORACHTUOS

J EENI

GNE

LANOISSEFORPDESN E CI LA

S

O N E AR

T

L. HERA

No. C00953ASSOC. INC.

BELKAENGINEERING

ANILORACHTUOS

CERT I F I CATE OF AUTHOR I ZAT

I ON

No. C00953ASSOC. INC.

BELKAENGINEERING

ANILORACHTUOS

CERT I F I CATE OF AUTHOR I ZAT

I ON

No. C00953ASSOC. INC.

BELKAENGINEERING

ANILORACHTUOS

CERT I F I CATE OF AUTHOR I ZAT

I ON

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F BE

LKA

ENGI

NEER

ING

ASSO

CIAT

ES,

INC.

THE

REP

RODU

CTIO

N,

COPY

ING,

OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

THE

WRI

TTEN

CO

NSEN

T OF

BEL

KA E

NGIN

EERI

NG

ASSO

CIAT

ES IS

PRO

HIBI

TED

AND

ANY

INFR

INGE

MEN

T W

ILL

BE

SUBJ

ECT

TO L

EGAL

ACT

ION.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

05-15-18

5/15

/201

8 2:

10:3

0 PM

E0.1U479

.18

05.1

5.18

ELEC

TRIC

AL N

OTES

& LE

GEND

SAu

thor

Chec

ker

OUTD

OOR

VOLL

EYBA

LL LO

CKER

/FILM

ROOM

REN

OVAT

ION

139

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

05

ELECTRICAL DRAWING INDEX

# SHEET NAMEE0.1 ELECTRICAL NOTES & LEGENDS

E1.0 ELECTRICAL DEMOLITION PLANS

E1.1 FIRST AND SECOND FLOOR LIGHTING PLANS

E1.2 SECOND FLOOR POWER RENOVATION PLAN

GENERAL EXISTING CONDITION NOTES1 AREAS OF WORK EXIST FOR THIS PROJECT WHICH ARE NOT ACCESSIBLE OR HAVE LIMITED ACCESS DURING

DESIGN. AS SUCH CONTRACTOR SHALL VERIFY ALL UTILITIES IN AREA OF WORK BEFORE DEMOLITION OF ANYSERVICE. ANY ELECTRICAL COMPONENTS NOT SHOWN SHALL BE IDENTIFIED AND THE ARCHITECT ANDENGINEER SHALL BE NOTIFIED AS SOON AS POSSIBLE. NO ELECTRICAL REWORK SHALL BE COMMENCEDWITHOUT COORDINATION OF BOTH ARCHITECT AND ENGINEER.

2 IN AREAS WHERE THE EXISTING CEILINGS ARE NOT SLATED TO BE REMOVED, THE CONTRACTOR SHALL WORKTHRU THE EXISTING CEILINGS (SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR AREA OF WORK). THECONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING ANY DAMAGED TILE OR GRID THAT IS A RESULT OFTHEIR WORK.

3 REFER TO ARCHITECTURAL PLANS FOR PHASING OF CONSTRUCTION.

4 THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING A FIRESTOP SYSTEM IN ALL PENETRATIONS OFFIRE-RATED WALLS CREATED BY THE REMOVAL OF EXISTING ELECTRICAL CONDUIT OR CABLES, AS WELL ASTHOSE CREATED BY NEWLY INSTALLED CONDUITS AND SLEEVES.

5 WHERE INSTALLATION REQUIRES CUTTING OR DRILLING OF THE EXISTING FLOOR SLAB, THE CONTRACTORSHALL X-RAY THE EXISTING SLAB PRIOR TO WORK TO ENSURE THAT NO EXISTING UTILITIES OR STRUCTURALELEMENTS IN THE SLAB WILL BE COMPROMISED BY THE WORK. NOTIFY THE ARCHITECT/ENGINEER OF ANYCONFLICTS THAT WILL REQUIRE RELOCATING THE PROPOSED SLAB WORK. THE CONTRACTOR SHALL BERESPONSIBLE FOR THE REPAIR OF ANY DAMAGED UTILITIES OR STRUCTURAL ELEMENTS CAUSED BY THE SLABDEMOLITION.

6 SUPPORT ALL EXISTING CONDUITS AND JUNCTION BOXES ABOVE THE CEILING PER NEC IN THECONSTRUCTION AREA.

7 REMOVE ALL ABANDONED CONDUIT, WIRE, AND COMMUNICATION CABLES ABOVE THE CEILING IN THECONSTRUCTION AREA.

8 PROVIDE JUNCTION BOX COVER PLATES ON ALL EXISTING JUNCTION BOXES ABOVE THE CEILING IN THECONSTRUCTION AREA.

9 SUPPORT ALL EXISTING COMMUNICATION CABLES ABOVE THE CEILING IN THE CONSTRUCTION AREA

10 WHERE INFORMATION SHOWN ON THESE DRAWINGS CONFLICTS WITH VERIFIED FIELD CONDITIONS, IT SHALL BEBROUGHT TO THE ATTENTION OF THE ENGINEER

GENERAL "ELECTRICAL" NOTES1 BRANCH CIRCUIT WIRING SHALL BE NO. 12 AWG UNLESS NOTED OTHERWISE. WHERE CONDUCTOR AND

RACEWAY SIZE ARE SHOWN AT HOMERUN, SUCH SIZE SHALL BE USED FOR THE ENTIRE CIRCUIT.EXCEPTION: FINAL CONNECTION TO DEVICES, IN OUTLET BOXES, IS NOT REQUIRED TO BE LARGER THAN NO.12 AWG.

2 20A/120V BRANCH CIRCUITS EXCEEDING 100' IN LENGTH FROM PANEL TO FARTHEST DEVICE OR FIXTURESHALL USE NO. 10 CONDUCTORS AND 3/4"C.

3 PRIOR TO ROUGH-IN, COORDINATE THE LOCATION AND MOUNTING HEIGHT OF ALL WALL AND CEILINGMOUNTED DEVICES WITH THE ARCHITECTURAL ELEVATIONS, MILLWORK SHOP DRAWINGS, AND EXISTINGCONDITIONS. IN THE EVENT OF A CONFLICT, NOTIFY THE ARCHITECT. MINOR ADJUSTMENTS IN DEVICELOCATION, I.E. 5'-0" IN ANY DIRECTION SHALL BE DONE AT NO ADDITIONAL COST TO THE OWNER.

4 COORDINATE THE LOCATION OF ALL FLOOR-MOUNTED OUTLETS WITH THE ARCHITECT PRIOR TO ROUGH-IN.

5 PROVIDE FLEXIBLE CONDUIT FOR ALL CONDUITS CROSSING EXPANSION JOINTS. REFER TO ARCHITECTURALDRAWINGS FOR LOCATION OF EXPANSION JOINTS.

6 OUTLET BOXES FOR SWITCHES, RECEPTACLES, ETC MOUNTED ON OPPOSITE SIDES OF FIRE RATED PARTITIONSSHALL NOT BE MOUNTED IN THE SAME WALL CAVITY. SEPARATE WALL PENETRATIONS BY MOUNTING ONOPPOSITE SIDES OF WALL STUDS OR OTHER VERTICAL STRUCTURAL MEMBER IN THE WALL.

7 ALL FLOOR BOXES SHALL BE INSTALLED TO MAINTAIN THE FIRE RATING OF THE FLOOR. COORDINATE COREDRILLING HOLES IN FLOOR WITH STRUCTURAL ENGINEER.

8 RACEWAYS SHALL BE INSTALLED CONCEALED IN NEW WALL CONSTRUCTION ABOVE CEILINGS, BELOW FLOOR,AND IN OTHER CAVITIES TO THE GREATEST EXTENT POSSIBLE. WHERE EXPOSED RACEWAYS MUST BE USED,LAYOUT RACEWAYS TO MINIMIZE THE NUMBER OF VERTICAL RUNS.

9 FEEDER CONDUITS, BRANCH CIRCUITS AND CABLE TRAY ROUTING SHALL COMPLY WITH DETAILS ON DRAWINGSAND SHALL BE COORDINATED WITH THE WORK OF OTHER TRADES BEFORE AND DURING CONSTRUCTION.

10 WHERE LIGHT SWITCH AND ABOVE COUNTER RECEPTACLES ARE INDICATED TO BE MOUNTED ADJACENT TOEACH OTHER, THE DEVICES SHALL BE MOUNTED AT THE SAME HEIGHT UNDER A COMMON DEVICE PLATE.

11 REFER TO THE ARCHITECTURAL DRAWINGS FOR PROJECT PHASING.

12 THE ARRANGEMENT, GROUPING, AND ROUTING OF BRANCH CIRCUITS SHALL BE PROVIDED AT THECONTRACTOR'S DISCRETION IN ACCORDANCE WITH GENERALLY ACCEPTED PRACTICE FOR ELECTRICAL WORK,THE NATIONAL ELECTRICAL CODE REQUIREMENTS, LOCAL ORDINANCES, AND THE FOLLOWING:

12.1 A COMMON NEUTRAL SHALL NOT BE INSTALLED IN A HOMERUN FOR 2 OR 3 BRANCH CIRCUITS UNLESSDIRECTION IS PROVIDED BY THE ENGINEER IN WRITTING FOR A SPECIFIC APPLICATION.

12.2 MULTIPLE SINGLE-POLE BRANCH CIRCUITS (UP TO 3 HOTS, 3 NEUTRALS, 1 GROUND) RATED FOR 30-AMPSOR LESS MAY BE PULLED INTO A SINGLE RACEWAY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SIZINGTHE RACEWAYS AND DERATING CONDUCTORS PER NEC ARTICLE 310.15.

12.3 BRANCH CIRCUIT, FEEDER & COMMUNICATION CIRCUITS SHALL BE ROUTED OVERHEAD UNLESS PRIORAPPROVAL HAS BEEN GRANTED BY THE ARCHITECT AND ENGINEER.

12.4 A GROUND CONDUCTOR SHALL BE PROVIDED IN ALL RACEWAYS UNLESS NOTED OTHERWISE.

13 PROVIDE EXPANSION JOINT COUPLINGS ANYWHERE A CONDUIT PASSES THROUGH A BUILDING EXPANSIONJOINT.

14 WHERE FLOOR MOUNTED RECEPTACLES/DEVICES ARE GROUPED, PROVIDE DEVICES GROUPED IN ONE FLOORBOX.

15 COORDINATE THE ROUTING OF UNDERGROUND CONDUCTORS/CONDUIT WITH STRUCTURAL FOOTINGS ANDUNDERGROUND UTILITIES.

16 THE USE OF MC CABLE IS NOT ALLOWED.

17 SEAL ALL EXISTING AND NEW FIRE RATED WALL AND FLOOR PENETRATIONS IN THE CONSTRUCTION AREA

18 SEE THE ARCHITECTURAL DRAWINGS FOR ALL LOCATIONS OF FIRE RATED WALLS.

19 WHEREVER ON THE ELECTRICAL DRAWINGS THE WORD "PROVIDE" IS USED, IT SHALL BE INFERRED TO MEAN"FURNISH AND INSTALL".

GENERAL "POWER" NOTES1 ALL BRANCH CIRCUITS INDICATED ON THESE PLANS TO BE LARGER THAN NO. 12 AWG SHALL BE SIZED AS

INDICATED FOR THE ENTIRE LENGTH OF THE CIRCUIT.

2 WHEN A RECEPTACLE IS INDICATED TO BE MOUNTED ADJACENT TO A COMPUTER/TELEPHONE/ TELEVISIONOUTLET, THE DEVICE(S) SHALL BE MOUNTED WITHIN 6" CENTER-TO-CENTER.

3 PROVIDE AND INSTALL AN ENGRAVED LAMINATED PLASTIC NAMEPLATE ON EACH ITEM OF ELECTRICALEQUIPMENT SERVING MECHANICAL EQUIPMENT WHICH MATCH MECHANICAL DESCIPTIONS, TO INDICATE THEDESIGNATION OF THE UNIT ON THE PLANS & THE BRANCH CIRCUIT SERVING THE EQUIPMENT.

4 PROVIDE NEMA CONFIGURATION RECEPTACLES TO MATCH PLUGS ON EQUIPMENT FURNISHED.

5 WHERE SPEED CONTROLLER IS INDICATED TO BE PROVIDED WITH FANS, IT SHALL BE PROVIDED BYMECHANICAL CONTRACTOR AND INSTALLED BY ELECTRICAL CONTRACTOR.

6 PROVIDE LABEL ON INSIDE FACE OF COVER PLATE OF ALL RECEPTACLES, SWITCHES & WALL MOUNTEDDEVICES INDICATING PANEL AND BRANCH CIRCUIT TO WHICH EACH DEVICE IS CONNECTED.

7 ALL WIRING DEVICES SHALL BE GREY WITH SMOOTH STAINLESS STEEL WALL PLATES.

GENERAL "SIGNAL" NOTES1 EXTEND A 1" CONDUIT WITH PULL WIRE FROM EACH COMMUNICATIONS OUTLET TO NEAREST CABLE-TRAY OR

THE EXISTING COMMUNICATION BACKBOARD. TURN CONDUIT 12" INTO CEILING CAVITY A MINIMUM OF 6"ABOVE THE CEILING AND TERMINATE WITH AN INSULATED PROTECTIVE BUSHING. COMMUNICATION OUTLETBOX SHALL BE 4" SQUARE WITH SINGLE GANG RING.

2 PROVIDE ALL DUCT SMOKE DETECTORS AND ACCESSORIES NECESSARY FOR INTERLOCKING WITH MECHANICALEQUIPMENT (AHU'S, SMOKE DAMPERS, ETC). COORDINATE WITH MECHANICAL PLANS FOR LOCATIONS ANDREQUIREMENTS. DETECTORS SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR, INSTALLED BY MECHANICALCONTRACTOR, WIRED TO FIRE ALARM SYSTEM BY ELECTRICAL CONTRACTOR, AND TIED TO MECHANICALCONTROLS FOR AHU SHUTDOWN BY MECHANICAL CONTRACTOR.

3 ALL COMMUNICATIONS OUTLET BOXES SHALL BE 2-1/2" DEEP.

4 PROVIDE 1" CONDUIT TO ABOVE THE LOCAL ACCESIBLE CEILING FOR ALL COMMUNICATION WALL MOUNTEDDEVICES. PROVIDE SLEEVES SIZED FOR 40% EXPANSION THROUGH CORRIDOR WALLS.

5 CABLE SHALL BE CONCEALED IN ALL FINISHED AREAS AND ROUTED PARALLEL OR PERPENDICULAR TO THEBUILDING STRUCTURE.

6 ALL FIRE ALARM CABLE SHALL BE INSTALLED IN METALLIC CONDUIT. COORDINATES WITH FIRE ALARM SYSTEMMANUFACTURER FOR CABLE ROUTING AND QUANTITIES.

GENERAL "LIGHTING" NOTES1 SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR THE EXACT LOCATION OF ALL CEILING MOUNTED LIGHTING

FIXTURES.

2 EXACT LOCATIONS OF LIGHTING FIXTURES IN MECHANICAL SPACES SHALL BE DETERMINED IN THE FIELD. DONOT SUPPORT FIXTURES FROM DUCT OR PIPING. PROVIDE CHAIN OR TRAPEZE-TYPE HANGERS WHEREFIXTURES CAN NOT BE MOUNTED DIRECTLY TO CEILING.

3 LIGHTING FIXTURE CATALOG NUMBERS ARE INDICATIVE OF THE STYLE OF FIXTURE REQUIRED. CONTRACTORSHALL PROVIDE FIXTURES WITH THE PROPER TRIM, VOLTAGE AND OPTIONS NECESSARY FOR INSTALLATION.

4 DOUBLE-FACED EXIT FIXTURES SHALL BE OF THE SAME MANUFACTURER & SERIES AS THE SINGLE TYPESPECIFIED.

5 REGARDLESS OF CATALOG NUMBER INDICATED IN SCHEDULE, PROVIDE BATTERY PACKS FOR ALL FIXTURESINDICATED ON THE DRAWINGS TO BE EMERGENCY TYPE.

6 ALL EXIT SIGNS SHALL BE CONNECTED TO LOCAL LIFE SAFETY LIGHTING CIRCUIT AHEAD OF ALL SWITCHING.

7 REGARDLESS OF CATALOG NUMBER INDICATED IN SCHEDULE, ALL EXIT SIGNS SHALL BE PROVIDED WITH ABATTERY PACK, SHALL BE WIRED AHEAD OF LOCAL SWITCH AND SHALL NOT BE SWITCHED.

8 REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING DETAILS OF LIGHT FIXTURE TO ACOUSTICAL CEILINGSYSTEM AND STRUCTURE.

GENERAL "DEMOLITION" NOTES1 ALL ELECTRICAL EQUIPMENT TO BE REMOVED SHALL REMAIN THE PROPERTY OF THE OWNER. THE

CONTRACTOR SHALL NOT DISPOSE OF ANY MATERIALS UNTIL RELEASED BY OWNER'S PROJECT MANAGER.MATERIALS THAT OWNER'S PROJECT MANAGER CHOOSES TO RETAIN SHALL BE DELIVERED BY THECONTRACTOR TO A LOCATION DESIGNATED BY THE PROJECT MANAGER. ALL OTHER MATERIALS SHALL BEPROPERLY DISPOSED OF BY THE CONTRACTOR.

2 REMOVE ALL EXPOSED ABANDONED COMMUNICATION CABLE FOUND DURING THE CONSTRUCTION PROCESS.SUPPORT ALL EXISTING REMAINING CABLE PER THE NEC.

3 ELECTRICAL DEVICES NOT SHOWN ON WALLS TO BE DEMOLISHED SHALL BE DEMOLISHED AT NO ADDITIONALCOST TO OWNER.

4 ELECTRICAL DEVICES NOT SHOWN ON CEILINGS OR WALLS TO REMAIN SHALL REMAIN IN PLACE. PROTECTFROM DAMAGE DURING CONSTRUCTION

5 ELECTRICAL DEVICES NOT SHOWN ON CEILINGS TO BE REMOVED SHALL BE TEMPORARILY DISCONNECTED ANDREMOVED DURING DEMOLITION AND RE-INSTALLED ON NEW CEILING IN SAME LOCATION.

ABBREVIATIONS

ABR DESCRIPTION(E) EXISTING

AFC ABOVE FINISHED CEILING

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

BAS BUILDING AUTOMATION SYSTEM

BFC BELOW FINISHED CEILING

BFG BELOW FINISHED GRADE

BOD BOTTOM OF DEVICE

CBB COMMUNICATIONS BACK BOARD

cd CANDELA

CLG CEILING

ECB ENCLOSED CIRCUIT BREAKER

EF EXHAUST FAN

FACP FIRE ALARM CONTROL PANEL

FCU FAN COIL UNIT

FDS FUSED DISCONNECT SWITCH

FSD FIRE/SMOKE DAMPER

GBB GROUND BUSS BAR

GFCI GROUND-FAULT CIRCUIT-INTERRUPTING

GFI GROUND-FAULT INTERRUPTING

GP GENERAL PURPOSE

HP HEAT PUMP

ICP IRRIGATION CONTROL PANEL

IG ISOLATED GROUND

J-BOX JUNCTION BOX

LCS LIGHTING CONTROL SYSTEM

NEC NATIONAL ELECTRIC CODE

NFDS NON-FUSED DISCONNECT SWITCH

OC ON CENTER

RFAP REMOTE FIRE ALARM ANNUNCIATOR PANEL

RTU ROOF TOP UNIT

SD SMOKE DETECTOR

SPD SURGE PROTECTION DEVICE

TGB TELEPHONE GROUNDING BUSS BAR

UNO UNLESS OTHERWISE NOTED

UTP UNSHIELDED TWISTED PAIR

VFD VARIABLE FREQUENCY DRIVE

W/ WITH

WH WATER HEATER

WP WEATHERPROOF

XFMR TRANSFORMER

DEMOLITION/RENOVATION NOTATIONIF NO ANNOTATION IS SHOWN ASSUME EXISTING TO REMAIN INPLACE FOR SOLID LINES AND DEMOLISH FOR DASHED LINES.

DEVICES AND EQUIPMENT NOT SHOWN SHALL BE ASSUMED TOBE EXISTING TO REMAIN IN PLACE.

E EXISTING FIXTURE OR DEVICE TO REMAIN IN PLACE. REPLACEANY BROKEN DEVICES OR PLATES; COLOR TO MATCH EXISTING.

R EXISTING FIXTURE OR DEVICE TO BE REMOVED BY THEELECTRICAL CONTRACTOR. MAINTAIN CONTINUITY OF REMAININGPORTIONS OF BRANCH CIRCUIT.

RE EXISTING DEVICE TO BE REMOVED BY THE ELECTRICALCONTRACTOR. EXISTING CIRCUIT SHALL BE RETAINED. PROVIDENEW DEVICE AS SHOWN ON RENOVATION PLANS.

RN RELOCATED FIXTURE (NEW LOCATION).

RR EXISTING FIXTURE TO BE RELOCATED BY THE ELECTRICALCONTRACTOR TO NEW LOCATION SHOWN ON RENOVATION PLAN.

LIGHT FIXTURE SCHEDULE

SYMBOL

FIXTURE SPECIFICATIONS LAMPING ELECTRICAL

MOUNTING REMARKS NOTESTYPEFIXTURE

DESCRIPTION MANUFACTURER CAT. # NO. LAMP TYPEFIXT.LOAD VOLTS

.

.

A 4' STRIP FIXTURE COLUMBIA LCL4-35LW-E-U LED, 2,491LUMENS, 3500K

24 120 V CEILING SURFACE

.

.

AW 4' STRIP FIXTURE COLUMBIA LCL4-35LW-E-U LED, 2,491LUMENS, 3500K

24 120 V WALL MOUNTED 88"AFF

.

.

BF 4' LINEAR SLOT FIXTURE,FLANGE

NULITE RF2 06L35 UNV D 1CFRF WH 4'

LED, 2,928LUMENS, 3500K

27 120 V RECESSED

.

.

BG 4' LINEAR SLOT FIXTURE,GRID

NULITE RG2 06L35 UNV D 1CFRF WH 4'

LED, 2,928LUMENS, 3500K

27 120 V GRID

.

.

BGE SAME AS FIXTURE "BG"EXCEPT WITH BATTERY

NULITE RG2 06L35 UNV D 1CFRF WH 4' EMG

LED, 2,928LUMENS, 3500K

27 120 V GRID

.

.

D 3" DIAMETER DOWNLIGHT,BLACK REFLECTOR

LITON LR3LH21 W T35 LED, 650LUMENS, 3500K

12 120 V RECESSED

.

.

EXISTING EXISTING LIGHT FIXTURE,SEE

DEMOLITION/RENOVATIONNOTATION SCHEDULE,

SHEET E0.1

120 V

.

.

F 4" DIAMETER DOWNLIGHT,SPECULAR REFLECTOR

LITON LHALD411C35-D10P1/LRALD4SSF062B60-T35

LED, 1,100LUMENS, 3500K

13 120 V RECESSED

.

.

FE 4" DIAMETER DOWNLIGHT,SPECULAR REFLECTOR

LITON LHALD411C35-D10P1EM2/LRALD4SSF062B60-T35

LED, 1,100LUMENS, 3500K

13 120 V RECESSED

G 3' DIAMETERSEMI-RECESSED PENDANT

PRUDENTIAL LTG P4030LED35MOFWAD1SCUNVSMR7X7DM01

LED, 9,900LUMENS, 3500K

95 120 V SEMI-RECESSED

X1 EXIT SIGN, EDGE-LITSURFACE MOUNTED

LIGHTALARMS 6 UEN RM LED 3 120 V CEILING/WALL

LIGHT FIXTURE SCHEDULE NOTES1 LUMENS LISTED IN SCHEDULE REPRESENT DELIVERED LUMENS OF FIXTURES.

2 THREE DIGIT NUMBERS LISTED IN LAMP COLUMN REPRESENT CRI AND COLOR TEMPERATURE. FIRST DIGITINDICATES MINIMUM CRI AND LAST TWO DIGITS INDICATE COLOR TEMPERATURE. EXAMPLE: 830 INDICATESMINIMUM CRI OF 80 AND A COLOR TEMPERATURE OF 3000K.

3 SEE ARCHITECTURAL RCP AND ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHTS.

4 CONFIRM QUANTITIES OF FIXTURES SHOWN IN RCP MATCH QUANTITIES SHOWN ON ELECTRICAL PLANS PRIORTO BID. IF NO DISCREPANCIES ARE NOTED PRIOR TO BID THE HIGHEST QUANTITY OF EACH FIXTURE TYPESHOWN SHALL BE PROVIDED.

REVI

SIO

NS

NO.

NAM

EDA

TE

KEYPLAN AREA OF WORKFIRST FLOOR

A/VA/V

A/V

A/V

A/V

A/V

R

EXISTINGPANEL "M"

EXISTING ADEMCO5110XM DACT

E

E

E E

E

E E

E E

E

E

E

E

R

R R

R RRRR

R RRR

RR R R R

R

RR

R

R

R

R R

RR

RR

RR E E

R R

R R R R

RRR

2

2 2 22

R

3

RR R R R R

R

R

R

E

RR

E

R

EXISTINGPANEL "B"

EXISTINGPANEL "BB"

215COMM./ELEC.

TYPICAL1

TYPICAL4

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

US21804US21804US21804

No. 26181

RANILORACHTUOS

J EENI

GNE

LANOISSEFORPDESN E CI LA

S

O N E AR

T

L. HERA

No. 26181

RANILORACHTUOS

J EENI

GNE

LANOISSEFORPDESN E CI LA

S

O N E AR

T

L. HERA

No. 26181

RANILORACHTUOS

J EENI

GNE

LANOISSEFORPDESN E CI LA

S

O N E AR

T

L. HERA

No. C00953ASSOC. INC.

BELKAENGINEERING

ANILORACHTUOS

CERT I F I CATE OF AUTHOR I ZAT

I ON

No. C00953ASSOC. INC.

BELKAENGINEERING

ANILORACHTUOS

CERT I F I CATE OF AUTHOR I ZAT

I ON

No. C00953ASSOC. INC.

BELKAENGINEERING

ANILORACHTUOS

CERT I F I CATE OF AUTHOR I ZAT

I ON

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F BE

LKA

ENGI

NEER

ING

ASSO

CIAT

ES,

INC.

THE

REP

RODU

CTIO

N,

COPY

ING,

OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

THE

WRI

TTEN

CO

NSEN

T OF

BEL

KA E

NGIN

EERI

NG

ASSO

CIAT

ES IS

PRO

HIBI

TED

AND

ANY

INFR

INGE

MEN

T W

ILL

BE

SUBJ

ECT

TO L

EGAL

ACT

ION.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

05-15-18

5/15

/201

8 2:

18:2

1 PM

E1.0U479

.18

05.1

5.18

ELEC

TRIC

AL D

EMOL

ITION

PLA

NSAu

thor

Chec

ker

OUTD

OOR

VOLL

EYBA

LL LO

CKER

/FILM

ROOM

REN

OVAT

ION

139

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

05

SCALE: 1/4" = 1'-0"E1.0

1

ALTERNATE NO.1FIRST FLOOR DEMOITIONLIGHTING PLAN

SCALE: 1/4" = 1'-0"E1.0

2 SECOND FLOOR LIGHTING DEMOLITION PLAN

SCALE: 1/4" = 1'-0"E1.0

3 SECOND FLOOR POWER DEMOLITION PLAN

KEY NOTES

1 REMOVE DEVICES AND ASSOCIATED CIRCUIT COMPLETELY BACK TO PANELOF ORIGIN. EXISTING BREAKER SHALL BE REUSED IN RENOVATION PHASE.

2 REMOVE LIGHTING FIXTURES AS INDICATED AND TURN OVER TO OWNER.RETAIN EXISTING LIGHTING CIRCUIT IN THIS AREA FOR REUSE INRENOVATION PHASE.

3 CLEAN AND RELAMP EXISTING FIXTURES TO REMAIN. IN AREAS WHEREEXISTING CEILING TILES ARE BEING REPLACED, SUPPORT EXISTINGFIXTURES IN PLACE AND REINSTALL IN NEW CEILING TILE.

4 EXISTING FIRE ALARM AUDIO/VISUAL DEVICES MAY BE REUSED INRENOVATION PHASE WITH CANDELA ADJUSTMENT.

REVI

SIO

NS

NO.

NAM

EDA

TE

N0 8 12 164

SCALE: 1/4" = 1'-0"

OS

OS

OS

BG

BGE

BG

BGE

ABGE

BG

BGE

BG201B

STORAGE

201

TEAMLOUNGE

202

WOMEN'SRESTROOM

ST01

STAIR2ND FLR

215COMM./ELEC.

H204CORRIDOR

203

WOMEN'SLOCKERROOM

D

DDD

D abcd

BF

BF

F

F

F

F

FE

F

FE

F

F FE

F

FG

FE F

DDD

X1

X1

E ERN

1

1

1a

1a

1a

1a

1b

1b

1b

1b

1

1

1

1

1

1

1 1

1b

1b

1b

1c

1c 1c

1c

1d

1c

1c 1c

1e1e1e 1

1

D e

NL

RN RN RN

2

AW

RN

RN

f

f f f

E

E

E

E

EE

E E

E

E

E

E E

TYPICAL1

TYPICAL1

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

US21804US21804US21804

No. 26181

RANILORACHTUOS

J EENI

GNE

LANOISSEFORPDESN E CI LA

S

O N E AR

T

L. HERA

No. 26181

RANILORACHTUOS

J EENI

GNE

LANOISSEFORPDESN E CI LA

S

O N E AR

T

L. HERA

No. 26181

RANILORACHTUOS

J EENI

GNE

LANOISSEFORPDESN E CI LA

S

O N E AR

T

L. HERA

No. C00953ASSOC. INC.

BELKAENGINEERING

ANILORACHTUOS

CERT I F I CATE OF AUTHOR I ZAT

I ON

No. C00953ASSOC. INC.

BELKAENGINEERING

ANILORACHTUOS

CERT I F I CATE OF AUTHOR I ZAT

I ON

No. C00953ASSOC. INC.

BELKAENGINEERING

ANILORACHTUOS

CERT I F I CATE OF AUTHOR I ZAT

I ON

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F BE

LKA

ENGI

NEER

ING

ASSO

CIAT

ES,

INC.

THE

REP

RODU

CTIO

N,

COPY

ING,

OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

THE

WRI

TTEN

CO

NSEN

T OF

BEL

KA E

NGIN

EERI

NG

ASSO

CIAT

ES IS

PRO

HIBI

TED

AND

ANY

INFR

INGE

MEN

T W

ILL

BE

SUBJ

ECT

TO L

EGAL

ACT

ION.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

05-15-18

5/15

/201

8 2:

18:3

5 PM

E1.1U479

.18

05.1

5.18

FIRST

AND

SEC

OND

FLOO

RLIG

HTIN

G PL

ANS

Auth

or

Chec

ker

OUTD

OOR

VOLL

EYBA

LL LO

CKER

/FILM

ROOM

REN

OVAT

ION

139

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

05

KEY NOTES

1 CLEAN AND RELAMP EXISTING FIXTURES TO REMAIN. IN AREAS WHEREEXISTING CEILING TILES ARE BEING REPLACED, SUPPORT EXISTINGFIXTURES IN PLACE AND REINSTALL IN NEW CEILING TILE.

2 CONNECT NEW FIXTURES IN THIS LOCATION TO EXISTING LIGHTINGCIRCUIT IN THIS AREA. REPLACE EXISTING CONTROLS WITH CEILINGMOUNTED DUAL TECHNOLOGY OCCUPANCY SENSORS. ONE SENSOR SHALLCONTROL FIXTURES IN THE TOILET/SINK AREA, AND SWITCH SHALLCONTROL FIXTURES IN SHOWER.

GENERAL NOTES1 ALL LIGHTING SHOWN ON THIS SHEET SHALL BE FED FROM EXISTING

LIGHTING BRANCH CIRCUIT IN PANEL "B" UNLESS NOTED OTHERWISE.CIRCUIT NUMBERS SHOWN ARE FOR LOADING PURPOSES ONLY. FIELDVERIFY AVAILABLE CIRCUITS.

2 ELECTRICAL CONTRACTOR SHALL LOCATE ALL JUNCTION BOXES ANDOTHER ACCESSIBLE TEMS OVER ADJACENT GRID CEILINGS AND NOTOVER HARD GWB CEILING.

0 8 12 164SCALE: 1/4" = 1'-0"

SCALE: 1/4" = 1'-0"E1.1

1 SECOND FLOOR LIGHTING RENOVATION PLAN

SCALE: 1/4" = 1'-0"E1.1

2

ALTERNATE NO.1FIRST FLOOR LIGHTINGRENOVATION PLAN

REVI

SIO

NS

NO.

NAM

EDA

TE

N

GJ

J

A/V

J

J

A/V

A/V

S

S

A/V

A/V

E1.22

TYPICAL1

E1.2

3 2

FRIDGE

3TV

A/V

3

TV

A/V

203

WOMEN'SLOCKERROOM

202

WOMEN'SRESTROOM

ST01

STAIR2ND FLR

H204CORRIDOR

215COMM./ELEC.

201BSTORAGE

201

TEAMLOUNGE

203BSTORAGE

EXISTINGPANEL "BB"

EXISTINGPANEL "B"

1

1

1112

2

2

2

5 5 5

33

44

E

6666677

7

7

7

8

8

8

88 9 9 9

9

9

10

10

10

10

10

E 11

TYPICAL1

4

4

30cd

135cd

30cd

30cdWP

EXISTINGDATA RACK

2' - 4"

1' - 6"3' - 4"

FRIDGE

REMOTE GFCI

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

(803) 731-0650 p | (803) 960-6443 c

ENGINEERING

7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210

ASSOCIATES, INC.

BELKA

[email protected]

CONTACT: CLIFF STRINGFIELD

US21804US21804US21804

No. 26181

RANILORACHTUOS

J EENI

GNE

LANOISSEFORPDESN E CI LA

S

O N E AR

T

L. HERA

No. 26181

RANILORACHTUOS

J EENI

GNE

LANOISSEFORPDESN E CI LA

S

O N E AR

T

L. HERA

No. 26181

RANILORACHTUOS

J EENI

GNE

LANOISSEFORPDESN E CI LA

S

O N E AR

T

L. HERA

No. C00953ASSOC. INC.

BELKAENGINEERING

ANILORACHTUOS

CERT I F I CATE OF AUTHOR I ZAT

I ON

No. C00953ASSOC. INC.

BELKAENGINEERING

ANILORACHTUOS

CERT I F I CATE OF AUTHOR I ZAT

I ON

No. C00953ASSOC. INC.

BELKAENGINEERING

ANILORACHTUOS

CERT I F I CATE OF AUTHOR I ZAT

I ON

PRO

JEC

T N

O.

DAT

E

DRAWING NO.

DR

AWN

BY:

CH

ECK

ED B

Y:

THIS

DRA

WIN

G AN

D TH

E DE

SIGN

TH

EREO

N AR

E TH

E PR

OPER

TY O

F BE

LKA

ENGI

NEER

ING

ASSO

CIAT

ES,

INC.

THE

REP

RODU

CTIO

N,

COPY

ING,

OR

USE

OF T

HIS

DRAW

ING

WIT

HOUT

THE

WRI

TTEN

CO

NSEN

T OF

BEL

KA E

NGIN

EERI

NG

ASSO

CIAT

ES IS

PRO

HIBI

TED

AND

ANY

INFR

INGE

MEN

T W

ILL

BE

SUBJ

ECT

TO L

EGAL

ACT

ION.

PRO

JEC

T TI

TLE

A/E

SEAL

A/E

SEAL

DR

AWIN

G T

ITLE

05-15-18

5/15

/201

8 2:

55:4

9 PM

E1.2U479

.18

05.1

5.18

SECO

ND FL

OOR

POW

ERRE

NOVA

TION

PLAN

TSR

CES

OUTD

OOR

VOLL

EYBA

LL LO

CKER

/FILM

ROOM

REN

OVAT

ION

139

Sout

h M

arion

Stre

etCo

lumbia

, SC

292

05

KEY NOTES

1 SEE DETAIL 2/E1.2 THIS SHEET FOR ELEVATION.

2 THIS RECEPTACLE SHALL BE FED VIA REMOTE GFCI DEVICE. REMOTE GFCIDEVICE SHALL BE MOUNTED SUCH THAT IT IS AT THE SAME ELEVATIONAS ADJACENT RECEPTACLES AND IN AN ACCESSIBLE LOCATION ABOVECOUNTER.

3 AT EACH FLAT SCREEN TV LOCATION, PROVIDE ONE FLUSH MOUNTED TVBOX (CHIEF# PAC526 OR APPROVED EQUAL). PROVIDE ONE 20 AMPDUPLEX RECEPTACLE IN SIDE PANEL OF BOX. CONTRACTOR SHALLPROVIDE 1" CONDUIT FROM THIS TV LOCATION TO ABOVE ACCESSIBLECEILING. COORDINATE MOUNTING HEIGHT AND LOCATION WITH ARCHITECTPRIOR TO ROUGH-IN.

4 PROVIDE 4" SQUARE BOX WITH DOUBLE GANG PLASTER RING AND1-1/4" CONDUIT WITH PULLSTRING FROM JUNCTION BOX TO TV CHIEFBOX LOCATION FOR PC/LAPTOP INPUT.

GENERAL NOTES1 CIRCUIT NUMBERS SHOWN ARE FOR LOADING PURPOSES ONLY. PROVIDE

SIX 20 AMP SINGLE POLE BREAKERS IN EXISTING PANEL "BB" AND SIX20 AMP SINGLE POLE BREAKERS IN EXISTING PANEL "B". PROVIDE2#12, 1#12 GND IN 3/4"C TO DEVICES SHOWN. PANELS "BB" AND"B" ARE FED FROM EXISTING PANEL "M" LOCATED IN FIRST FLOORMECHANICAL ROOM.

2 ELECTRICAL CONTRACTOR SHALL LOCATE ALL JUNCTION BOXES ANDOTHER ACCESSIBLE TEMS OVER ADJACENT GRID CEILINGS AND NOTOVER HARD GWB CEILING.

SCALE: 1/4" = 1'-0"E1.2

1 SECOND FLOOR POWER RENOVATION PLAN

SCALE: 1/2" = 1'-0"E1.2

2 LOCKER POWER ELEVATIONSCALE: 1/2" = 1'-0"E1.2

3 TEAM LOUNGE POWER ELEVATION

0 8 12 164SCALE: 1/4" = 1'-0"

REVI

SIO

NS

NO.

NAM

EDA

TE

N