38
Dr Yeonsook Heo Department of Architecture, University of Cambridge UK Energy Efficient Cities initiative Urban-Scale Energy Analyses of the Built Environment Seminar 39: Data Sources toward Urban-Scale Energy Modeling, Part 1

Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

  • Upload
    lamdang

  • View
    215

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Dr Yeonsook Heo

Department of Architecture, University of Cambridge UK Energy Efficient Cities initiative

Urban-Scale Energy Analyses of the Built Environment

Seminar 39: Data Sources toward Urban-Scale Energy Modeling, Part 1

Page 2: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Learning objectives for this session

• Provide an overview of Urban Building Energy Model approaches and data sources.

• Describe the tradeoffs between speed and accuracy when using calibrated archetypes.

• Understand the advantages and limitations of building archetype calibration

• Describe how urban-scale building modeling can be used to make more well-informed energy decisions.

Disclaimer: ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to ASHRAE Records for AIA members. Certificates of Completion for non-AIA members are available on request. This program is registered with the AIA/ASHRAE for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.

Page 3: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Why do we need urban-scale energy analyses?

Potential Benefits….

• Inform impact of urban measures. For example, projected growth in buildings; roll-out of new technologies; new planning laws; more stringent regulations.

• Assess relationships with exogenous influences on energy and environment: such as spatial planning, transport systems, industries, policies, etc.

• Enable synergistic planning of energy supply and transport networks in support of energy reduction and improved air quality.

Page 4: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

City-scale analysis of buildings

Page 5: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

City-scale Analysis of Buildings

Rationale for pursuing an “dynamic” energy simulation of “each building” in a building stock:

• Improved profiling of peak load duration curves (inferring specific causes of peaks and troughs in energy demand)

• Improved ability to cost energy services dependent on peak demand and time-of-use

• Improved representation of building physics (thus improved knowledge of the physical interaction between energy supply technologies, building physics)

Page 6: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Overview of data sources used for urban-scale energy analysis

EECi inventory

of building

simulation data

and models

GIS UKMap of Westminster

Westminster EPC Register

UK Public-sector DECs

Research literature

Government reports

US DoE

Open-source models

Page 7: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Why is Westminster chosen for urban-scale modelling?

Page 8: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Why is Westminster chosen for urban-scale modelling?

Non-domestic landuse area

Page 9: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Why is Westminster chosen for urban-scale modelling?

Page 10: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Extraction of physical geometry

GIS UKMap Data

Summary

• Spatial map of Westminster buildings, differentiated by type

• Buildings represented as polygons

• Multiple polygons can represent one building

• Building heights provided

Page 11: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Extraction of physical geometry

Page 12: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Spot Check 1: Polygon G9527333 - Office (NE Corner of Regent St. and Great Marlborough St.)

• This polygon represents the top three floors of the corner suite (14.5 m in height). It is an office situated above a Banana Republic retail outlet

Google StreetView

GIS Data Generated IDF (Wei’s script)

Page 13: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Spot Check 2: Polygon G9532901 - Office (NW Corner of St James Place, Alongside Hyde Park)

• This is a complete building with partial exposure on side facades, and full exposure on front and rear facades.

Google StreetView

GIS Data Generated IDF (Wei’s script)

Page 14: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Spot Check 3: Polygon G9533283 – Office (W Corner of Cleveland Row, North Side)

• This is a complete building with full exposure. Notice that there are more modelled levels than in reality. This is a floor heights issue, as the total height of the building seems to be encapsulated by the Eplus model

Google StreetView

GIS Data Generated IDF (Wei’s script)

Page 15: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Thermodynamic properties of buildings

Westminster EPC Register

Summary (Domestic sector)

• Coverage for ~64,000 dwellings

• Includes building construction information (wall type, window type, etc.)

• Includes heating system type

Summary (Non-domestic sector)

• Coverage for ~8,500 premises

• Does not include construction information

• However, includes retrofit recommendations per premises (e.g., “replace glazing”)

Page 16: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Thermodynamic properties of buildings

Research literature

Reference Smith, S. Modelling thermal loads for a non-domestic building stock. Associating a priori probability with building form and construction - using building control laws and regulations. PhD Thesis, University of Nottingham, 2009

Summary

• Provided statistical correlations building construction properties with respect to building construction age

• Suggest values for pre 19th-century buildings up to present

Page 17: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Thermodynamic properties of buildings

Government Reports and Data

References

• City of London Data store • Defra (2007-2010): Market Transformation Program (MTP) • Element Energy (2009): Uptake of energy efficiency measures • CIBSE Guide A • Etc. Summary

• Provided distribution of construction age of non-domestic building stock in Westminster borough (by type)

• Provided distribution of energy efficiency measures and energy supply systems amongst UK non-domestic buildings (present and future scenarios)

Distribution of non-domestic building construction ages, Westminster.

Page 18: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Review of baseline data for Westminster

Page 19: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Schedules of building use and operation

US Department of Energy

References

• DoE Commercial / Residential Reference Buildings

Summary

• Simple, deterministic schedules for occupancy and internal gains based on surveys of randomly selected US buildings

• Differentiated by type of building

Page 20: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Generic modeling process for buildings summarized

Assign building construction properties

Determine building type

Select building polygon

Generate 3D building model

Simulate building

UKmap

UKmap

EPCs, Literature, Government data, etc.

EECi models

EnergyPlus

Page 21: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Process for assigning building construction information (non-domestic Bldgs)

Determine building subtype (if

retail)

Sample asset rating and AC

status from EPC/DEC

distribution of all buildings

in subtypes

Sample asset rating and AC

status from nearest

neighbor(s)

Does EPC exist?

Determine building

construction likelihood from

DEC recommendations of

chosen neighbor

Determine building

construction likelihood from

exogenous data

Determine building age

Determine building age

Start

Yes

No

Source: GIS data provides building type

Source: City of London statistical data on building age by building type in Westminster

Source: Statistical data on breakdown of retail floor area by subtype (e.g., restaurants, food retail, non-food retail, etc.)

Source: Academic publications, providing statistical data on building construction properties

Source: EPC/DEC register for London and City of Westminster

Page 22: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Constructing the simulation (and the data challenge) for ~100,000 buildings

UKmap

EPCs

Other data

100 MB

80 MB

~1 MB

Geometries

as text

Sampled building

construction

properties

19 MB

20 MB

EnergyPlus 3D

models

6.6 GB

Raw data Pre-processed data

Processed simulation inputs

Page 23: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Constructing the Simulation (and data challenge)

EnergyPlus 3D

models

6.6 GB

Processed simulation inputs

Raw simulation

output files

Simulation outputs

~600-800 GB (roughly 5-8 MB per building

Answer

• Cambridge HPC Darwin computing cluster

• 10x16 processor cores used (2.6 GHz Intel Sandybridge cores)

• Simulations conducted within ~4 hours

Page 24: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Constructing the Simulation (and data challenge)

Raw simulation

output files

Simulation outputs

~600-800 GB (roughly 5-8 MB per building

Outputs:

• Annual load duration curves (heating, cooling, electricity)

• Hourly end-use energy demand, on average days (3) per month

• Monthly end-use energy demand

• Annual end-use energy demand

Processed

simulation data

~16 GB

Processed simulation outputs

Page 25: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Constructing the Simulation (and data challenge)

Outputs:

• Annual primary (gas and elec.) energy consumption per building

• Annual CO2 attributable emissions

• NO2 and PM2 emissions at source

Processed

simulation data

~16 GB

Processed simulation outputs

Final dataset

~16 GB

Calculation of primary energy and emissions

Page 26: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Westminster Annual Heat Intensity

Page 27: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Westminster Annual Heat Intensity

Page 28: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Annual Gas Consumption – Non-domestic Sector: DECC MLSOA 2011

Validating the city-scale model against measured energy use data

Measured energy use data

• Annual gas/electricity consumption

• Domestic sector: spatial aggregation at LLSOA (lower layer super output area)

• Non-domestic sector: spatial aggregation at MLSOA (middle layer super output area)

Annual Gas Consumption – Domestic Sector: DECC LLSOA 2011

Page 29: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Actual Annual Gas Consumption – Non-domestic Sector: DECC MLSOA 2011

Modelled Annual gas consumption, non-domestic sector

Comparing predicted gas energy consumption at MLSOA level vs actual

Page 30: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Actual Annual Gas Consumption – Domestic Sector: DECC LLSOA 2011

Modelled Annual gas consumption, Domestic sector

Comparing predicted gas energy consumption at LLSOA level vs actual

Page 31: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

The Good

So far, what have we achieved?

• Confident with allocation of building physical properties across Westminster stock

• 3D building geometry quality consistent with literature

• Spot checks yield “reasonable” results with respect to available benchmarks

• Initial results near MLSOA and LLSOA metered data

The Bad

• Less information on the variance of indoor equipment/lighting use

• Deterministic representation of occupancy-driven profiles yields over-amplified peaks and troughs in demand

Page 32: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Importance of representing variance in building use and operation

Building Use & Operation Minimum Maximum Base

Heating setpoint T – occupied (°C) 19.5 22.5 21.0

Heating setpoint T – unoccupied (°C) 15.0 18.0 15.6

Cooling setpoint T – occupied (°C) 22.5 25.5 24.0

Cooling setpoint T – unoccupied (°C) 25.0 28.0 30.0

Occupant density (m2/person) 4.3 22.8 9.0

Lighting power density (W/m2) 6.2 33.9 11.0

Equipment power density (W/m2) 5.7 34.0 11.0

Plausible range of parameter values for office buildings

- We have assumed uncertain parameters to have triangular distributions - We have used Latin Hypercube Sampling to draw samples from the

distributions - For the following analyses, a representational sample of 11 office

buildings was used

Page 33: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Importance of representing variance in building use and operation

Plausible range of parameter values for office buildings

0

50

100

150

200

250

300

350

400

EU

I (k

Wh

/m

2)

Westminster Office Buildings

Base EUI

Mean EUI

Page 34: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Importance of representing variance in building use and operation

Sensitivity analysis of building use and operation parameters (using standardised regression coefficients)

Operational Parameters Electricity Heating

Occupant density - 0.17

Lighting power density 0.44 - 0.35

Equipment power density 0.90 - 0.56

Heating T- occupied - 0.66

Heating T- unoccupied - 0.20

Cooling T- occupied - - 0.02

Cooling T- unoccupied - -

Page 35: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Evaluating the effect of modelling assumptions on prediction

Office Building

No. Floor

Floor Area

WWR

Daylight Control

Window U-value

Infiltration

A 6 78 0.21 1 4.0 0.6

B 5 350 0.16 0 4.6 0.5

C 6 1098 0.19 1 5.3 0.4

D 2 34 0.04 1 5.0 0.8

E 6 156 0.15 1 1.6 0.8

F 3 108 0.10 1 5.7 0.6

G 6 1026 0.09 1 5.4 0.8

H 10 1530 0.09 1 2.8 0.3

I 7 337 0.10 1 5.2 0.7

J 5 230 0.07 1 4.9 0.5

K 5 1025 0.22 1 1.4 0.7

L 11 308 0.24 0 5.2 0.5

M 6 2802 0.21 0 4.5 0.4

N 7 119 0.23 1 5.1 0.6

O 5 390 0.37 1 5.4 0.6

P 4 48 0.17 1 4.1 0.6

Q 5 600 0.03 1 5.1 0.7

R 8 312 0.10 1 5.0 0.6

S 8 552 0.12 0 5.4 0.6

T 3 369 0.32 1 6.1 0.5

Page 36: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Evaluating the effect of modelling assumptions on prediction

Equipment power density

T_heat_occ

Lighting power density

T_heat_unocc

Geometry + thermal properties

Case 1 Indiv. Indiv. Indiv. Indiv. Indiv.

Case 2 Base Indiv. Indiv. Indiv. Indiv.

Case 3 Base Base Indiv. Indiv. Indiv.

Case 4 Base Base Base Indiv. Indiv.

Case 5 Base Base Base Base Indiv.

Case 6 Base Base Base Base Base

Annual gas consumption

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1 2 3 4 5 6

CV

RM

SE

Case

Page 37: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Buildings analysis conclusions

• Modelling individual buildings is important to correctly capture variability in the energy performance of buildings

• Our project developed the semi-automated process for generating the energy simulation model of every building in the portfolio

Further work

• Incorporation of variability in building use and operation into the model

• Deeper validation analysis between individual modelled buildings and DEC-covered premises

Adequacy of urban-scale modelling

Page 38: Urban-Scale Energy Analyses of the Built Environmentweb.eecs.utk.edu/~new/presentations/2016_ASHRAE_Seminar39_Univ... · Urban-Scale Energy Analyses of the Built Environment ... Uptake

Name: Yeonsook Heo

Email address : [email protected]

Questions?