    1/4

    Contract No.76/2010-EP

    Document No.

    V-30-1380-001REV

    2

    DATE: 0 3 OCT11 SHEET 1 of 4

    Prepared BUI DINH NAM

    Checked PHAM HONG NAM

    DETAILED ELECTRICAL LOAD DATA Approved BUI XUAN MANH

    DETAILED ELECTRICAL LOAD DATA

    FOR CONSTRUCTION

    Bio-fuel Ethanol Plant in Northern Region ProjectDist ribut ionPVC

    PD

    DP D (Sit e)Proc M

    MICO

  • 7/31/2019 V-30-1380-001

    2/4

  • 7/31/2019 V-30-1380-001

    3/4

  • 7/31/2019 V-30-1380-001

    4/4

    1) Rated kW : Motor Nameplate or Feeder Power/Current Rating.

    2) Absorbed kW : Mechanical Power Input to Drive Shaft to Obtain Rated Output from Driven Equipment or Absorbed Electrical Power For Non-Motor Loads

    3) Usage factor : Number of Hours in an Average Day That Equipment is Operated, Expressed as the Ratio (hours operated per day)/24

    4) Load type: M = Motor, F = Feeder

    2. Key for Starter Types 3. Key for Operation Type

    1) DOL : Direct On Line Starter 1) C = Continuous Operation ( usage factor = 1)2) CON : Fused Contactor Feeder 2) I : Intermittent Operation ( usage factor = 0.2)

    3) CB : Circuit Breaker 3) S/B: Standby Operation (usage factor = 0)

    4) SS : Solid State Soft Start

    5) VSD : Variable Speed Drive

    6) SD : Star/Delta Starter

    7) FUS : Fuse Switch Feeder

    8) 2SP : Two Speed Starter

    9) REV : Reversing DOL Starter

    4. Calculations

    1) Absorbed kW = Rated kW*Load factor

    2) Input power kW=Absorbed kW / Efficiency Factor

    3) Input power kVAR = Input power kW*TAN(ACOS(Power factor))

    4) Input power kVA : {SQRT((Input power kW)**2) + (Input power kVAR )**2)}