Upload
ismail-ahmad
View
69
Download
5
Embed Size (px)
DESCRIPTION
Volume tank sizing
Citation preview
377 Series Trip ValvesProduct Bulletin
62.3:377September 2004
6
SPRING
VALVE PLUG
UPPERDIAPHRAGM
EXHAUSTPORT
SUPPLYPRESSURE
LOWERDIAPHRAGM
PORT D
PORT E
LOWERPORTS
PORT F
PORT C
PLUG ASSEMBLIES
UPPER PORTS
PORT B
PORT A
VENT
MAIN SPRING
ACTUATOR
CONTROLDEVICE
CHECKVALVE
VOLUMETANK
Figure 7. Type 377U Trip Valve Shown Tripped
A2281-1 / IL
Figure 8. Volume Tank Sizing Graph
Volume Tank Sizing
Note: State and local regulations may require theuse of ASME-approved volume tanks. It is theusers responsibility to determine requirementsand applicable regulations for proper volumetank selection.
Seven different tanks of varying capacities areavailable. The volume tank must be selected so thatits pressure at any time is greater than the minimumpercentage of maximum supply pressure required tostroke the actuator (see figure 8).
377 Series Trip Valves
Product Bulletin62.3:377September 2004
7
1. Size the volume tank as indicated below:
For Actuators onSliding Stem Valves,
Determine:
For Actuators onRotary-Shaft Valves,
Determine:
Y = F/AP x 100 Y = Pr/P x 100
Where:
Y = Minimum failure positioning percentageF = Actuator thrust required in normal operation toposition the valve at the desired limit of travelA = Effective piston area (from the appropriateactuator bulletin)P = Maximum supply pressure availablePr = Highest pressure required by the actuator tostroke the valve (from the appropriate actuator sizingtechnique)
2. With the minimum failure positioning percentageobtained in step 1, enter the value on the abscissa ofthe graph in figure 8. Locate the corresponding pointon the curve, and read across to find the volume ratio,R.
3. Determine:
VT = (XA)/R
Where:X = Maximum actuator travel from the appropriateactuator bulletin. For rotary actuators, substitute totaldisplacement (XA). Actuator displacement can befound in the product bulletin, or contact your Fishersales office.VT = Minimum volume tank size requiredR = Volume ratio from step 2
Installation
The 377 Series trip valve may be mounted in anyposition without affecting normal operation.Dimensions are shown in figure 9 and tables 2 and 3.
Table 1. Guidelines for Specifying 377 Series Trip Valve
Actuator Type Fail ModeValve
Action(1) Trip Valve
Fail OpenPDTC 377U
Sliding-Fail Open
PDTO 377DSlidingStem
Fail ClosedPDTC 377D
Fail ClosedPDTO 377U
Rotary--
FullyClockwise
Clockwise to
377CWRotary
Type 1035,Series G
FullyCounter-clock
wise
Clockwise toClose
377CCW
Rotary--
FullyClockwise
- - - 377CWRotary
Type 1069 Fully Counter-clockwise
- - - 377CCW
1. PDTC—Push Down to Close; PDTO—Push Down to Open
Ordering Information
Note: Fisher does not assume responsibility forthe selection, use, or maintenance of anyproduct. Responsibility for proper selection, use,and maintenance of any Fisher product remainssolely with the purchaser and end user.
When ordering specify:
Application1. Available supply pressure2. Actuator type number and size3. Input signal range4. Operating ambient temperature5. Trip point (If the trip point is not specified, the unitis factory-set to trip at 72 percent of supply pressureor 2.8 bar (40 psig), whichever is higher.)6. Volume tank size
Trip Valve
Refer to the specifications. Review the informationunder each specification and in the referencedfigures. Specify the desired choice wherever there isa selection to be made. Be sure to specify the typenumber as described in the Available Configurationsspecification.
Refer to table 1 for guidelines on specifying thecorrect trip valve.
377 Series Trip ValvesProduct Bulletin
62.3:377September 2004
8
Table 2. Standard Volume Tank Dimensions
Tank Volume J L
Liters Inch3 mm Inches mm Inches
11.821.633.4
42.965.6
72113152036
26154001
309310309
309309
12.1612.1912.16
12.1612.16
318451607
7371095
12.517.7523.88
29.0043.12
131.1 8002Requires two 65.6 liter (4001 inch3) volume
tanks
Table 3. ASME-Approved Volume Tank Dimensions
Tank Volume J L
Liters Inch3 mm Inches mm Inches
8.524.930.0
42.868.871.6
51815201831
260941994371
208305254
305360305
8.1912.0010.00
12.0014.1912.00
337427684
681792
1087
13.2516.8126.94
26.8131.1942.81
143.2 8742Requires two 71.6 liter (4371 inch3) volume
tanks
Canadian Registered
114227303
454
69301386018480
27720
406508610
610
162024
24
103412861295
1932
40.6950.6351.00
76.06
908 55440Requires two 454 liter (27720 inch3) volume
tanks
AF4605-K
19A7995-A
A2778-4 / IL
57(2.25)CAPREMOVALCLEARANCE
0.25 18 NPTVENT CONNECTION
mm(INCH)
76(3.00)
90(3.56)
54(2.12)
141(5.56)
46(1.81)
100(3.94)
154(6.06)
PORT D
PORT E
PORT F
PORT C
STANDARD
TANK
ASME−APPROVED
TANK
LL
JJ
0.25 18 NPTSUPPLY CONNECTION
1 1
NOTEREFER TO TABLES 1 AND 2 FOR J AND L DIMENSIONS1
Figure 9. Dimensions of Trip Valve with Manifold (also see tables 2 and 3)
Fisher Marshalltown, Iowa 50158 USACernay 68700 France Sao Paulo 05424 BrazilSingapore 128461
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they arenot to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability.We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Fisher does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Fisher product remains solely with the purchaser and end-user.
�Fisher Controls International LLC 1985, 2004; All Rights Reserved Printed in USA
Fisher is a mark owned by Fisher Controls International LLC, a member of the Emerson Process Management business division of EmersonElectric Co. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their respective owners.
Emerson Process Management
www.Fisher.com