WFRC TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets, In Accordance With BS EN 1634-1: 2000, Incorporating Various Items Of Architectural Hardware. Warrington Fire Research Centre Ltd., Holmesfield Road, Warrington, UK WA1 2DS Tel: int + 44 (0) 1925 655116 Fax: int + 44 (0) 1925 646616 www.wfrc.co.ukReg.No. 1247124

WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

Embed Size (px)

Citation preview

Page 1: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC TEST REPORT NO. 139234

The Fire Resistance Performance Of Two Specimens Of Fully Insulated,

Single-Acting, Single-Leaf Doorsets, In Accordance With

BS EN 1634-1: 2000, Incorporating Various Items Of Architectural

Hardware.

Warrington Fire Research Centre Ltd., Holmesfield Road, Warrington, UK WA1 2DS Tel: int + 44 (0) 1925 655116 • Fax: int + 44 (0) 1925 646616 • www.wfrc.co.uk•Reg.No. 1247124

Page 2: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 2 of 38

Commercial in confidence

Summary Objective To determine the effects of various building hardware on the fire resistance

performance of two single-acting, single-leaf timber doorsets within a low density rigid supporting construction, in accordance with BS EN 1634-1: 2000.

Applicant Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire, WA1 2DS

Sponsor Frelan Hardware, Unit 10, Mitcham Industrial Estate, Streatham Road, Mitcham, Surrey. CR4 2AP

Summary of Tested Specimens

For the purpose of the test the specimens were referenced Doorset A and Doorset B. Each doorset had overall nominal dimensions of 2080 mm high by 1010 mm wide and incorporated a door leaf of overall nominal dimensions2040 mm high by 940 mm wide by 44 mm thick.

Each doorset included a softwood door frame and a door leaf comprising softwood stiles and rails, a flaxboard core, MDF facings and was lipped with hardwood on the vertical edges.

Each doorset incorporated a concealed closer referenced “JW 900”, fitted mid-way between the upper and middle hinge positions. The closer fitted to Doorset B was bedded on intumescent mastic and was installed with the chain mechanism disengaged. The closer fitted to Doorest A was installed without any form of bedding material and in an operable manner. Doorset B also incorporated a surface mounted closer referenced “JW901 spring arm closer”, fitted to the exposed face at the approximate mid-height of the leaf.

Both leaves were hung within a softwood frame on three brass hinges referenced “J7012” on Doorset A and “J9050” on Doorset B.

The leaves were orientated such that they opened towards the heating conditions of the test. The doorsets were each fitted with a latch which was disengaged for the test duration.

Page 3: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 3 of 38

Commercial in confidence

Test Results: Doorset A Doorset B

Sustained flaming 32 minutes 11 minutes

Gap gauge 33 minutes* 11 minutes

Integrity performance

Cotton Pad 32 minutes 11 minutes

Insulation performance

32 minutes 11 minutes

* The test duration. The test was discontinued after a period of 33 minutes

Date of Test 29th April 2004

This report may only be reproduced in full. Extracts or abridgements of reports shall not be published without permission of Warrington Fire Research Centre.

Page 4: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 4 of 38

Commercial in confidence

Signatories

Responsible Officer: R. Wakefield* Technical Officer Approved: S. Hankey* Technical Consultant Head of Department: C. Miles* Technical Manager

* For and on behalf of Warrington Fire Research Centre. Report Issued Date : 28th June 2004

Only original paper versions of this report bear signatures of the responsible Warrington Fire Research Centre staff. This copy has been produced from a .pdf format electronic file that has been provided by Warrington Fire Research Centre to the sponsor of the report and must only be reproduced in full. Extracts or abridgements of reports must not be published without permission of Warrington Fire Research Centre. The original signed paper version of this report, which also includes a silvered logo, is the sole authentic version.

Page 5: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 5 of 38

Commercial in confidence

CONTENTS PAGE NO.

SUMMARY.................................................................................................................................. 2 SIGNATORIES............................................................................................................................ 4 TEST PROCEDURE...................................................................................................................... 6 TEST SPECIMEN ........................................................................................................................ 7 Figure 1- Elevation Of Unexposed Face..................................................................................... 7 Figure 2 – Sections Through Doorsets ...................................................................................... 8 Figure 3 – Details Of Hinges To Both Doorsets ......................................................................... 9 Figure 4 – Details Of Handles And Latch To Both Doorsets..................................................... 10 Figure 5 – Details Of Closers To Both Door Leaves ................................................................. 11 SCHEDULE OF COMPONENTS .................................................................................................. 12 DOORSET CLEARANCE GAPS ................................................................................................... 15 SPECIMEN SUPPORTING CONSTRUCTION.............................................................................. 16 INSTRUMENTATION................................................................................................................ 17 TEST OBSERVATIONS.............................................................................................................. 18 TEST PHOTOGRAPHS............................................................................................................... 20 TEMPERATURE AND DEFLECTION DATA ................................................................................. 23 PERFORMANCE CRITERIA AND TEST RESULTS....................................................................... 35 ONGOING IMPLICATIONS....................................................................................................... 35 CONCLUSIONS ........................................................................................................................ 36 ADDENDUM ............................................................................................................................. 37

Page 6: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 6 of 38

Commercial in confidence

Test Procedure Introduction The doorsets are required to provide a fire separating function and were therefore

tested in accordance with BS EN 1634-1: 2000 ‘Fire resistance tests for doors and shutter assemblies - Part 1: Fire doors and shutters’. This test report should be read in conjunction with that Standard and with BS EN 1363-1: 1999, ‘Fire resistance tests - Part 1: General requirements’ and BS EN 1363-2: 1999, ‘Fire resistance tests - Part 2: Alternative and additional procedures’.

The specimens were judged on their ability to comply with the performance criteria for integrity and insulation, as required by BS EN 1634-1:2000.

Fire Test Study Group/EGOLF

Certain aspects of some fire test specifications are open to different interpretations. The Fire Test Study Group and EGOLF have identified a number of such areas and have agreed Resolutions which define common agreement of interpretations between fire test laboratories which are members of the Groups. Where such Resolutions are applicable to this test they have been followed.

Instruction To Test

The test was conducted on the 29th April 2004 at the request of Frelan Hardware, the sponsor of the test.

Test Specimen Construction

A comprehensive description of the test construction is given in the Schedule of Components. The description is based on a detailed survey of the specimens and information supplied by the sponsor of the test.

The doorsets’ storage, installation, and test preparation took place in the test laboratory over a total, combined time of 5 days.

Installation The test sponsor supplied the doorset hardware during the week commencing 19th April 2004.

The doorsets were mounted within apertures provided within a low density, rigid supporting construction. Representatives of Warrington Fire Research Centre conducted installation on the 28th April 2004.

Sampling Warrington APT Laboratories selected and sampled all of the hardware incorporated within the test during the week commencing 18th April 2004.

Page 7: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 7 of 38

Commercial in confidence

Test Specimen Figure 1- Elevation Of Unexposed Face

Do not scale. All dimensions are in mm

32

DOORSETS BUILT INTO A BLOCKWORK WALL 150 MM THICK,WITH AN AUTOCLAVED AERATED CONCRETE LINTEL ABOVE THE APERTURES

POSITIONS OF UNEXPOSED FACE THERMOCOUPLES.

3

725

HIN

GE

275

820

HIN

GE

36

2019

281827

1010 FRAME940 LEAF

25 26

1716

3433

DOORSET 'B'

1 3 5

2080

FRA

ME

2040

LEA

F

2040

LEA

F20

80 F

RAM

E

12

725

HIN

GE

275

4

DOORSET 'A'

1514

241323

11

820

HIN

GE

31

940 LEAF

29

1010 FRAME

2221

30

990

35

7 86 6

1460

CLO

SER

9 9

1460

CLO

SER

1095

0 CL

OSE

R

Page 8: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 8 of 38

Commercial in confidence

Figure 2 – Sections Through Doorsets

Do not scale. All dimensions are in mm

44

FIRE SIDE DOOR LEAF ITEM 3

1

2

2

HORIZONTAL SECTION

VERTICAL SECTION

Page 9: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 9 of 38

Commercial in confidence

Figure 3 – Details Of Hinges To Both Doorsets

Do not scale. All dimensions are in mm

HINGE TO DOORSET 'B' - ITEM 5

HINGE TO DOORSET 'A' - ITEM 4

102

27

65

12

37

10

19

Ø9

Ø6

11

38

9

17

Ø11

2Ø12

Ø6

Ø15

30

102

75

6

Page 10: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 10 of 38

Commercial in confidence

Figure 4 – Details Of Handles And Latch To Both Doorsets

Do not scale. All dimensions are in mm

HANDLE TO DOORSET 'A' - ITEM 7

HANDLE TO DOORSET 'B' - ITEM 8

Ø52 x 6120 x 19

Ø49 x 6.5130 x 19

45

PLASTICS MATERIAL

LATCH AND PLATES TO DOORSETS 'A & B' - ITEM 6

75

22 (

x 15

WID

E)

25

57 70

294610

1.2

Page 11: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 11 of 38

Commercial in confidence

Figure 5 – Details Of Closers To Both Door Leaves

Do not scale. All dimensions are in mm

2

Ø22

30

2910

6

115

1234

Ø15

8422

Ø8

PLASTIC CAP

MILD STEEL

STAINLESS STEEL RUBBING STRIP- GLUE FIXED TO DOOR LEAF

PLASTICS ROLLERMILD STEEL ARM

ADJUSTMENT HOLE

JAMB CLOSER TO DOORSET 'B' - ITEM 10

DOOR LEAF EDGE CLOSER TO DOORSETS 'A & B' - ITEM 9

2550

138

STEEL CHAIN

BRASS PLATE

DOOR FRAME

Page 12: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 12 of 38

Commercial in confidence

Schedule of Components (Refer to Figures 1 to 5) (All values are nominal unless stated otherwise) (All other details are as stated by the sponsor) Item

Description

1. Door frame Material : Softwood Density : 500 kg/m3 nominal Average moisture content : 12 % (measured with a Protimeter moisture meter by

WFRC). Overall size : 44 mm x 94 mm, with 12 mm deep rebate Jambs to head jointing method : Mortice & tennon and screwed Fixing i. method : Countersunk steel screws and plugs through jambs ii. size : 125 mm long x 5 mm diameter iii. frequency : 6 no. to hinge side jamb, with 1 no. each side of hinge.

4 no. to latch side jamb 2. Intumescent seal Manufacturer : Intumescent Seals Ltd Reference : Therm-A-Flex Material : Graphite based intumescent seal within a plastic sheath,

fitted with a brush type smoke seal Overall size : 10 mm by 4 mm Fixing method : Self-adhesive within a groove in the doorframe rebate.

Seals interrupted at hinges 3. Door leaf Manufacturer : Noberne Doors Limited. Reference : Series 2, solid core flush door Door leaf thickness : 44 mm Construction i. general : Construction details of the door leaf are known and are

retained in our confidential file relating to this investigation

ii. stiles and rails : Softwood timber iii. core : Flaxboard iv. faces : Medium density fibreboard v. lippings : Hardwood to vertical edges

Page 13: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 13 of 38

Commercial in confidence

4. Hinge to Doorset ‘A’ Manufacturer : Frelan Hardware Reference : J7012 Primary material : Brass Size i. knuckle : 102 mm long by 11 mm diameter ii. blades : 102 mm long by 27 mm wide by 3.2 mm thick Fixings i. type : Countersunk head wood screws ii. material : Brass iii. sizes : 30 mm long by 4.5 mm diameter iv. number off per blade : 4 off v. maximum distance of fixing screws

from face of door leaf :

18 mm

Bedding material : None 5. Hinge to Doorset ‘B’ Manufacturer : Frelan Hardware Reference : J9050 with 4 bearings Primary material : Brass Size i. knuckle : 109 mm long by 15 mm diameter ii. blades : 102 mm long by 30 mm wide by 2.9 mm thick Fixings i. type : Countersunk head wood screws ii. material : Brass iii. sizes : 30 mm long by 4.5 mm diameter iv. number off per blade : 4 off v. maximum distance of fixing screws from face of door leaf

:

20 mm

Bedding material : None 6. Rim latch to both door leaves Manufacturer : Frelan Hardware Reference : JL181 Materials i. latch casing : Mild steel ii. fore plate : Stainless steel iii. strike plate : Stainless steel Overall sizes : See Figure 4 Operation of latch : Disengaged Fixings i. type : Countersunk head wood screws ii. material : Steel iii. sizes : 26 mm long by 3 mm diameter iv. number off per plate : 2 off Bedding material to latch : None

Page 14: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 14 of 38

Commercial in confidence

7. Lever handle to Doorset ‘A’ Manufacturer : Frelan Hardware Reference : J4645B Material : Aluminium Overall sizes : See Figure 4 Fixing method : Screwed 8. Lever handle to Doorset ‘B’ Manufacturer : Frelan Hardware Reference : J4645B Material : Aluminium with a rubber sleeve to the escutcheon Overall sizes : See Figure 4 Fixing method : Screwed 9. Concealed door closer to jamb of both door leaves Manufacturer : Frelan Hardware Reference : JW900 Material i. body : Mild steel ii. fixing plates : Brass iii. chain : Steel Overall sizes : See Figure 5 Fitting : Body of closer concealed within edge of door leaf and

plates screw fixed Operation of closers i. Doorset ‘A’ : Engaged ii. Doorset ‘B’ : Disengaged (chain removed) Fixings i. type : Countersunk head wood screws ii. material : Brass iii. sizes : 30 mm long by 2.9 mm diameter iv. number off per plate : 4 off Bedding material to closers i. Doorset ‘A’ : None ii. Doorset ‘B’ : Body of closer encased in an acrylic based intumescent

masticmaterial Closer forces to Doorset ‘A’ Maximum opening moment : 20 Nm Maximum closing moment : 5 Nm 10. Exposed door closer to jamb of Doorset ‘B’ Manufacturer : Frelan Hardware Reference : JW901 Material : Mild steel Overall sizes : See Figure 5 Fitting : Body of closer screw fixed to jamb of door frame Bedding material : None Closer forces Maximum opening moment : 23 Nm Maximum closing moment : 7 Nm

Page 15: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 15 of 38

Commercial in confidence

Doorset Clearance Gaps

1 2 3 15 16 17

14 4 28 18

13 5 27 19

Doorset A

Doorset B

12

6 26

20

11 7 25 21

10 9 8 24 23 22

Viewed from unexposed face Viewed from unexposed face

Door Ref Gap Dimension in mm at Positions

1 2 3 4 5 6 7 8* 9* 10* 11 12 13 14 A

3.7 1.6 3.6 2.7 3.4 3.3 3.4 5.0 5.0 5.0 3.1 3.4 3.3 2.6 15 16 17 18 19 20 21 22* 23* 24* 25 26 27 28

B 3.1 2.1 3.6 3.5 3.1 3.4 3.4 5.0 5.0 5.0 1.4 1.8 1.8 2.2

A Mean 3.1 Maximum 3.7 Minimum 1.6 B Mean 2.7 Maximum 3.6 Minimum 1.4

Door Ref Gap Between Face of Leaf and Doorstop in mm at Position

1 2 3 4 5 6 7 8# 9# 10# 11 12 13 14 A

0.5 0 0.5 0 0.2 0.5 0.1 - - - 1.5 1.0 1.2 1.0 15 16 17 18 19 20 21 22# 23# 24# 25 26 27 28

B 0.8 0 0.9 1.0 1.2 0.9 1.1 - - - 0.3 0 0.5 1.0

* Dimension not included in calculations # Gap not measured DO NOT SCALE ALL DIMENSIONS ARE IN mm

Page 16: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 16 of 38

Commercial in confidence

Specimen Supporting Construction Blocks Manufacturer : Celcon Reference : Standard Material : Solid aerated concrete blocks Density : 620 (±50) kg/m3

Strength Mean : 4.0 N/mm2 Minimum : 3.6 N/mm2 Thickness : 150 mm Length : 440 mm Height : 215 mm Block configuration : Half lap, stretcher bond with no finishes Mortar Material : Cement, sand Mix ratio : 1 : 4

Page 17: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 17 of 38

Commercial in confidence

Instrumentation

General The instrumentation was provided in accordance with the requirements of the Standard.

Furnace The furnace was controlled so that its mean temperature complied with the requirements of BS EN 1363-1: 1999, Clause 5.1 using six plate thermometers, distributed over a plane 100 mm from the surface of the test construction.

General Thermocouples were provided to monitor the unexposed surface of the specimens and the output of all instrumentation was recorded at no less than one minute intervals as follows:

Thermocouples 11 to 15 (Doorset A) and 16 to 20 (Doorset B)

At five positions on the unexposed surface of the doorsets, one approximately at the centre and one at approximately the centre of each quarter section of each doorset.

Thermocouples 21 to 24 (Doorset A) and 25 to 28 (Doorset B)

At four positions on the unexposed surface of each doorset, at 100 mm in from the door leaves vertical edges, two at mid-height, and two at 100 mm below the top edge of each leaf.

Thermocouples 29 to 32 (Doorset A) and 33 to 36 (Doorset B)

At two positions on the unexposed surface of each vertical frame member at mid-height and at two positions on the top horizontal frame member.

The locations and reference numbers of the various unexposed surface thermocouples are shown in Figure 1.

Roving Thermocouple

A roving thermocouple was available to measure temperatures on the unexposed surface of the specimens at any position which might appear to be hotter than the temperatures indicated by the fixed thermocouples.

Integrity Criteria Cotton pads and gap gauges were available to evaluate the integrity of the specimens.

Furnace Pressure The furnace atmospheric pressure was controlled so that it complied with the requirements of BS EN 1363-1: 1999. Clause 5.2. The calculated pressure differential relative to the laboratory atmosphere at the top of the specimens was 13.4 (±3) Pa.

Page 18: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 18 of 38

Commercial in confidence

Test Observations Time All observations are from the unexposed face unless noted otherwise.

mins secs The ambient air temperature in the vicinity of the test construction was 11ºC at the start of the test with no variation during the test.

00 00 The test commences.

01 20 Smoke issues from around the perimeter of each leaf.

05 30 Large volumes of flames issue from the exposed core of each doorset.

07 30 The leading edge of the door leaf to Doorset A has lowered onto the threshold.

08 30 The surface mounted closer of Doorset B has fallen away and is therefore having no retaining influence upon the leaf.

10 00 The leaf of Doorset B has begun to open up. There is glowing at upper left hand corner.

11 00 Sustained flaming occurs at the head of Doorest B where a through gap in excess of6 mm by 150 mm has formed because of the leaf opening. The leaf is closed and latched to continue the test. The specimen is deemed to have failed the integrity (sustained flaming, cotton pad and through gap) criteria of the test.

15 00 The leaf of Doorset B has lowered onto the threshold.

16 00 The leading edge of Doorset A remains flush with the stop over its height. There is a large amount of discolouration at the upper hinge position and at the position of the concealed closer.

21 00 There is a small amount of discolouration on the unexposed face of Doorset A at the concealed closer position and upper hinge position.

24 30 There is a small amount of glowing at the upper hinge position of Doorset A.

25 30 A cotton wool pad is applied to area of glowing which fails to ignite.

26 10 There is a small area of glowing at the upper hinge position of Doorset B.

28 30 A cotton pad is applied to the area of glowing on Doorset B, which failed to ignite.

Page 19: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 19 of 38

Commercial in confidence

Time All observations are from the unexposed face unless noted otherwise.

mins secs The ambient air temperature in the vicinity of the test construction was 11ºC at the start of the test with no variation during the test.

31 20 Intermittent flames issue from the lower hinge position of Doorset A.

32 00 Sustained flames issue from lower hinge position of Doorset A. The specimen is deemed to have failed the integrity (sustained flaming and cotton pad) criteria of the test. The area of glowing at the upper hinge positions on each leaf continues to increase.

33 00 The test is discontinued.

Page 20: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 20 of 38

Commercial in confidence

Test Photographs

The exposed face of the test construction prior to testing

The unexposed face of the test construction prior to testing

Page 21: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 21 of 38

Commercial in confidence

The unexposed face of the test construction after 13 minutes of the test

The unexposed face of the test construction after 23 minutes of the test

Page 22: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 22 of 38

Commercial in confidence

The unexposed face of the test construction after a test duration of 28 minutes

Exposed face of the test construction directly after removal from the furnace

Page 23: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 23 of 38

Commercial in confidence

Temperature and Deflection Data

Mean Furnace Temperature, Together With The Temperature/Time Relationship Specified In The Standard

Time Specified Actual Furnace Furnace

Mins Temperature Temperature Deg. C Deg. C 0 20 18 1 349 359 2 445 503 3 502 567 4 544 573 5 576 660 6 603 664 7 626 614 8 645 617 9 663 624 10 678 642 11 693 653 12 705 660 13 717 673 14 728 685 15 739 701 16 748 719 17 757 736 18 766 747 19 774 762 20 781 773 21 789 781 22 796 786 23 802 791 24 809 795 25 815 799 26 820 802 27 826 809 28 832 817 29 837 824 30 842 830 31 847 836 32 851 838 33 856 843

Page 24: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 24 of 38

Commercial in confidence

Individual And Mean Temperatures Recorded On The Unexposed Surface Of Doorset A

Time T/C T/C T/C T/C T/C Mean Number Number Number Number Number Temp

Mins 11 12 13 14 15 Deg. C Deg. C Deg. C Deg. C Deg. C Deg. C 0 15 15 15 15 11 14 1 15 15 15 15 11 14 2 15 15 15 15 11 14 3 15 15 15 15 11 14 4 15 15 15 15 11 14 5 16 15 15 15 11 14 6 16 15 15 15 11 14 7 16 15 15 15 12 15 8 16 15 15 15 12 15 9 16 16 15 15 12 15 10 16 16 16 16 12 15 11 17 17 17 16 12 16 12 18 18 18 17 13 17 13 19 20 19 18 14 18 14 21 22 20 20 15 20 15 23 24 21 21 17 21 16 25 26 23 23 18 23 17 27 28 25 24 20 25 18 30 31 26 26 22 27 19 32 33 28 28 24 29 20 34 35 30 30 26 31 21 36 37 32 31 27 33 22 38 38 34 33 29 34 23 39 40 36 35 30 36 24 41 42 38 37 32 38 25 43 43 39 38 34 39 26 44 44 41 40 35 41 27 46 46 43 42 37 43 28 47 47 45 44 39 44 29 49 49 46 46 40 46 30 51 50 48 47 42 48 31 52 52 50 49 44 49 32 54 53 52 51 45 51 33 55 54 53 52 47 52

Page 25: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 25 of 38

Commercial in confidence

Individual And Mean Temperatures Recorded On The Unexposed Surface Of Doorset B

Time T/C T/C T/C T/C T/C Mean Number Number Number Number Number Temp

Mins 16 17 18 19 20 Deg. C Deg. C Deg. C Deg. C Deg. C Deg. C 0 12 13 12 12 12 12 1 12 13 12 12 12 12 2 12 13 12 12 12 12 3 12 13 12 12 12 12 4 12 13 12 12 12 12 5 12 13 12 12 12 12 6 12 13 13 12 13 13 7 12 13 13 12 13 13 8 12 13 13 12 13 13 9 13 13 13 12 13 13 10 13 14 13 13 13 13 11 15 15 13 13 13 14 12 18 17 14 14 14 15 13 19 18 15 15 15 16 14 20 20 15 17 17 18 15 21 23 16 18 18 19 16 23 25 17 19 20 21 17 25 27 19 21 22 23 18 26 29 20 22 24 24 19 28 31 22 24 26 26 20 30 33 23 26 28 28 21 31 34 25 27 29 29 22 33 36 27 29 31 31 23 34 37 28 30 33 32 24 36 39 31 32 34 34 25 37 40 33 34 36 36 26 39 41 35 36 38 38 27 40 42 37 38 39 39 28 42 44 39 40 41 41 29 43 45 41 42 43 43 30 45 46 43 43 44 44 31 46 47 45 46 46 46 32 47 49 47 47 48 48 33 49 50 49 49 49 49

Page 26: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 26 of 38

Commercial in confidence

Individual Temperatures Recorded On The Unexposed Surface Of Doorset A

Time T/C T/C T/C T/C Number Number Number Number

Mins 21 22 23 24 Deg. C Deg. C Deg. C Deg. C0 13 15 15 14 1 13 15 15 14 2 17 15 15 14 3 21 15 15 14 4 22 15 15 14 5 21 15 15 14 6 19 15 15 14 7 19 15 15 15 8 18 16 15 15 9 17 16 15 15 10 17 17 16 16 11 17 19 16 18 12 18 21 17 20 13 19 24 18 22 14 21 26 19 25 15 23 29 20 27 16 26 32 22 29 17 29 34 24 32 18 32 36 26 34 19 34 38 29 36 20 37 40 31 38 21 39 42 33 40 22 41 43 35 41 23 43 44 37 43 24 45 46 39 45 25 47 47 41 46 26 49 48 43 47 27 50 50 45 49 28 52 51 47 50 29 54 52 48 52 30 56 53 50 53 31 58 55 52 55 32 60 56 53 56 33 62 57 55 58

Page 27: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 27 of 38

Commercial in confidence

Individual Temperatures Recorded On The Unexposed Surface Of Doorset B

Time T/C T/C T/C T/C Number Number Number Number

Mins 25 26 27 28 Deg. C Deg. C Deg. C Deg. C0 16 16 15 15 1 16 16 15 15 2 16 16 15 15 3 16 16 15 15 4 16 16 15 15 5 16 17 15 15 6 16 17 15 15 7 16 17 15 15 8 17 17 15 15 9 17 17 16 15 10 19 17 18 16 11 32 19 20 16 12 89 20 25 17 13 73 21 27 18 14 60 21 29 19 15 54 22 31 20 16 51 24 34 21 17 49 25 36 23 18 49 28 38 25 19 49 30 40 26 20 50 34 42 28 21 50 34 43 29 22 51 36 45 31 23 52 41 46 33 24 53 45 47 35 25 53 50 49 37 26 55 56 50 38 27 56 58 51 40 28 57 56 53 42 29 59 57 55 44 30 61 58 56 45 31 63 59 58 47 32 65 61 59 49 33 67 63 61 50

Page 28: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 28 of 38

Commercial in confidence

Individual Temperatures Recorded On The Unexposed Surface Of Door Frame A

Time T/C T/C T/C T/C Number Number Number Number

Mins 29 30 31 32 Deg. C Deg. C Deg. C Deg. C0 11 11 11 11 1 11 11 11 11 2 14 11 11 11 3 21 11 11 11 4 24 12 11 11 5 26 12 11 11 6 27 12 11 11 7 28 14 11 12 8 28 20 11 11 9 29 27 11 12 10 29 27 11 12 11 31 24 12 12 12 31 22 12 12 13 32 21 12 12 14 34 20 13 12 15 35 20 14 12 16 37 23 14 12 17 38 23 15 12 18 40 22 16 12 19 41 22 16 12 20 42 23 17 12 21 43 23 18 13 22 43 24 19 13 23 43 25 21 14 24 44 26 22 15 25 44 27 23 16 26 46 28 25 18 27 47 29 26 20 28 48 30 27 22 29 50 31 29 23 30 52 33 30 25 31 55 34 31 27 32 56 36 32 28 33 60 37 33 29

Page 29: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 29 of 38

Commercial in confidence

Individual Temperatures Recorded On The Unexposed Surface Of Door Frame B

Time T/C T/C T/C T/C Number Number Number Number

Mins 33 34 35 36 Deg. C Deg. C Deg. C Deg. C0 10 13 12 11 1 10 13 12 11 2 * 15 12 11 3 17 12 11 4 19 12 11 5 21 12 11 6 22 12 11 7 23 12 11 8 24 12 11 9 23 12 11 10 24 12 11 11 28 12 11 12 32 13 11 13 34 13 12 14 34 13 12 15 35 13 12 16 37 13 12 17 38 13 13 18 39 13 13 19 41 14 14 20 42 14 14 21 46 14 15 22 47 15 16 23 49 15 16 24 53 16 17 25 56 16 18 26 58 16 18 27 61 17 19 28 65 17 19 29 69 18 20 30 73 18 21 31 77 19 21 32 79 20 22 33 81 20 23

Page 30: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 30 of 38

Commercial in confidence

Horizontal Deflections Of The Doorsets

A B C D E A B C D E

Doorset A

Doorset B

F G H I J F G H I J

K

L

M

N O K

L

M

N O

Doorset A Deflections – mm

TIME mins A B C D E F G H I J K L M N O

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 -1 -1 0 2 -1 0 0 0 1 2 0 0 0 0 0 10 -1 8 7 10 0 0 0 -1 0 2 0 10 6 4 0 15 -1 13 7 12 0 0 -1 -11 -1 2 0 18 10 6 0

Doorset B

Deflections – mm TIME mins A B C D E F G H I J K L M N O

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 5 0 0 1 3 2 0 0 1 -1 1 0 0 0 0 0 10 0 15 6 9 0 0 2 -6 -11 0 10 8 8 -2- -3 15 0 18 5 10 0 0 2 -10 -2 1 9 15 6 6 -1

Positive values indicate deflection towards the furnace.

Page 31: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 31 of 38

Commercial in confidence

Graph Showing Recorded Furnace Pressure The Head Of The Doorsets

-50.0

-40.0

-30.0

-20.0

-10.0

0.0

10.0

20.0

0 5 10 15 20 25 30 35

Time - Minutes

Rec

orde

d P

ress

ure

- P

a

Page 32: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 32 of 38

Commercial in confidence

Graph Showing Mean Furnace Temperature, Together With The Temperature/Time

Relationship Specified In The Standard

0

100

200

300

400

500

600

700

800

900

0 5 10 15 20 25 30 35

Time - Minutes

Tem

pera

ture

- D

eg. C

Specified Furnace Temperature Deg. C

Actual Furnace Temperature Deg. C

Page 33: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 33 of 38

Commercial in confidence

Graph Showing Mean Temperatures Recorded On The Unexposed Surface Of Doorset A

0

10

20

30

40

50

60

0 5 10 15 20 25 30 35

Time - Minutes

Tem

pera

ture

- D

eg. C

Page 34: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 34 of 38

Commercial in confidence

Graph Showing Mean Temperatures Recorded On The Unexposed Surface Of Doorset B

0

10

20

30

40

50

60

0 5 10 15 20 25 30 35

Time - Minutes

Tem

pera

ture

- D

eg. C

Page 35: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 35 of 38

Commercial in confidence

Performance Criteria and Test Results

Integrity It is required that the specimens retain their separating function, without either causing ignition of a cotton pad when applied, or permitting the penetration of a gap gauge as specified in BS EN 1634-1: 2000, or resulting in sustained flaming on the unexposed surface. These requirements were satisfied for the periods shown below:

Doorset A Doorset B

Sustained flaming 32 minutes 11 minutes

Gap gauge 33 minutes* 11 minutes

Cotton pad 32 minutes 11 minutes

* The test duration. The test was discontinued after a period of 33 minutes

Insulation The mean temperature rise of the unexposed surface shall not be greater than 140°C and that the maximum temperature rise shall not be greater than 180°C (except on the door frame, where the maximum temperature rise shall not exceed 360°C). Insulation failure also occurs simultaneously with integrity failure as specified in BS EN 1634-1:2000. These requirements were satisfied for the periods shown below:

Doorset A Doorset B

32 minutes 11 minutes

The test was discontinued after a period of 33 minutes

Ongoing Implications Limitations This report details the method of construction, the test conditions and the results

obtained when the specific element of construction described herein was tested following the procedure outlined in BS EN 1363-1: 1999, and where appropriate BS EN 1363-2: 1999. Any significant deviation with respect to size, constructional details, loads, stresses, edge or end conditions other than those allowed under the field of direct application in the relevant test method is not covered by this report. Annex A of BS EN 1363-1: 1999, provides guidance information on the application of fire resistance tests and the interpretation of test data.

Page 36: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 36 of 38

Commercial in confidence

Because of the nature of fire resistance testing and the consequent difficulty in quantifying the uncertainty of measurement of fire resistance, it is not possible to provide a stated degree of accuracy of the result.

Review The specification and interpretation of fire test methods are the subject of ongoing development and refinement. Changes in associated legislation may also occur. For these reasons it is recommended that the relevance of test reports over five years old should be considered by the user. The laboratory that issued the report will be able to offer, on behalf of the legal owner, a review of the procedures adopted for a particular test to ensure that they are consistent with current practices, and if required may endorse the test report.

Conclusions Evaluation Against Objective

Two specimens of single-acting, single-leaf timber doorsets incorporating various items of building hardware have been subjected to a fire resistance test in accordance with BS EN 1634-1: 2000, Fire resistance tests for door and shutter assemblies, BS EN 1363-1: 1999, General requirements and BS EN 1363-2: 1999, Alternative and additional procedures.

The evaluation of the doorsets against the requirements of BS EN 1634-1: 2000 showed that the doorsets satisfied the integrity and insulation requirements for a period of 32 minutes for Doorset A and 11 minutes for Doorset B.

The primary objective of the test was to evaluate various items of building hardware when incorporated within fire resistant doorsets. Because of this no field of direct application has been included in the report.

Page 37: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 37 of 38

Commercial in confidence

Addendum Applicant Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire,

WA1 2DS

Sponsor Frelan Hardware, Unit 10, Mitcham Industrial Estate, Streatham Road, Mitcham, Surrey. CR4 2AP

Date of Test 29th April 2004

Introduction The test referenced WFRC No. 139234 was conducted on two specimens of single-acting, single-leaf doorset, in accordance with BS EN 1634-1: 2000.

Test Results: Doorset A Doorset B

Sustained flaming 32 minutes 11 minutes

Gap gauge 33 minutes* 11 minutes

Integrity

Cotton Pad 32 minutes 11 minutes

Insulation 32 minutes 11 minutes

* The test duration. The test was discontinued after a period of 33 minutes

Discussion Doorset B incorporated a latch mechanism, which was rendered disengaged for the purpose of the test. After a period of 11 minutes integrity failure occurred due to the partial opening of the doorset after the door closing device failed to restrain the door leaf. The laboratory staff then returned the door leaf to the closed position and engaged the latch bolt. No further occurrences, which would constitute an integrity or insulation failure, occurred for the test duration.

It is therefore considered that had the latch bolt been engaged from the beginning of the test, then this would have retained the doorset in the closed position and thus the integrity and insulation performance of the doorset would have been satisfied for the full 33 minutes test duration.

Page 38: WFRC TEST REPORT NO. 139234 The Fire Resistance ... TEST REPORT NO. 139234 The Fire Resistance Performance Of Two Specimens Of Fully Insulated, Single-Acting, Single-Leaf Doorsets,

WFRC Test Report No. 139234

Page 38 of 38

Commercial in confidence

Conclusion Had the specimen referenced Doorset B been rendered latched for the duration

of the test then it is expected that the doorset would have satisfied the integrity and insulation criteria for the full 33 minute duration of the test.

Signatories Addendum by: Approved by:

C Johnson Technical Officer Technical Department Warrington Fire Research Centre

S Hankey Technical Consultant Technical Department Warrington Fire Research Centre