Signal Test 5-Dec 6-Dec 7-Dec 8-Dec 10-Dec 11-Dec 12-DecRecord Short Test 1 day 1 day 1 day 2 days 1 day 1 dayHolding Tank Transfer Totalizer (Optiflux) 19.4 391.6 734.7 1224.9 1531.1 1931.6 2295.4Discharge Water Totalizer (Optiflux) 19.6 555.9 1059.9 1884.8 2396.5 3015.9 3429.2Holding Tank Transfer Totalizer (PLC) 19 383 724 490 796 1197 1568Discharge Tank Totalizer (PLC) 20 545 1068 845 1403 2109 2672IWO Transfer Totalizer (Optiflux) 335.4 335.4IWO Transfer Totalizer (PLC) 0 0 0IWM Transfer Totalizer (Optiflux) 218915 21962.7IWM Transfer Totalizer (PLC) 0 0 0IWO1 Totalizer (Optiflux) 3253.4 3257.7 3261.1IWO1 Totalizer (PLC) 23 28 32IWO2 Totalizer (Optiflux) 3433.4 3434.1 3435.1IWO2 Totalizer (PLC) 1 1 2IWM Totalizer (Optiflux) 16649.2 16650.1 16652.1IWM Totalizer (PLC) 7 8 10IWG Totalizer (Optiflux) 11961 12276.9 12534.2IWG Totalizer (PLC) 1518 1841 2108
CalculationVolume transferred (Holding) 19.4 372.2 343.1 490.2 306.2 400.5 363.8Volume transferred (Discharge) 19.6 536.3 504 824.9 511.7 619.4 413.3PLC recording (Holding) 19 364 341 490 306 401 371PLC recording (Discharge) 20 525 523 845 558 706 563Totalizer Deviation (Optiflux) 1.0% 44.1% 46.9% 68.3% 67.1% 54.7% 13.6%Communication Error Rate (Holding Tank) 0.0% -2.2% -0.6% 0.0% 0.0% 0.2% 2.2%Communication Error Rate (Discharge) 5.3% -2.1% 3.8% 2.5% 9.2% 14.1% 36.3%
PLC reset PLC resetshort test shield connection finished
Other Flow Meter CalcVolume Transferred (IWO1) 4.3 3.4PLC Recording 5 4Communication Error Rate (IWO1) 25.0% 33.3%Volume Transferred (IWO2) 0.7 1PLC Recording 0 1
Volume Transferred (IWM) 0.9 2PLC Recording 1 2
Volume Transferred (IWG) 315.9 257.3PLC Recording 323 267Communication Error Rate (IWG) 2.5% 3.9%
0
100
200
300
400
500
600
0%10%20%30%40%50%60%70%80%
5-Dec 6-Dec 7-Dec 8-Dec 9-Dec 10-Dec 11-Dec 12-Dec
Discharge-Holding Deviation(see schematic process flow)
Series1 Series2
200
300
400
500
600
10.0%
20.0%
30.0%
40.0%
50.0%
Discharge-Holding to PLCCommunication Error Rate
20 mA current loop - HART™
Do FM and PLC work ?
discharge recordby gravity flow
measurement of holding transfer
Is deviation OK ?
Is error rate OK ?
Does PLC work ?
0
100
200
300
-10.0%
0.0%
10.0%
20.0%
5-Dec 6-Dec 7-Dec 8-Dec 9-Dec 10-Dec 11-Dec 12-Dec
Series1 Series2 Series3