22
XM-940 Dynamic Measurement Terminal Base Catalog Number 1440-TB-A Installation Instructions Topic Page Important User Information 2 Power Requirements 8 Interconnect Limit 8 Wiring Requirements 9 Grounding Requirements 9 Mounting on the DIN Rail 14 Wiring 17 Specifications 19 FOR XM-120...124 ONLY

XM-940 Dynamic Measurement Terminal Base Installation … · XM-940 Dynamic Measurement Terminal Base 3 Publication GMSI10-IN020C-EN-P - October 2013 ATTENTION Environment and Enclosure

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

  • XM-940 Dynamic Measurement Terminal BaseCatalog Number 1440-TB-A

    Installation Instructions

    Topic Page

    Important User Information 2

    Power Requirements 8

    Interconnect Limit 8

    Wiring Requirements 9

    Grounding Requirements 9

    Mounting on the DIN Rail 14

    Wiring 17

    Specifications 19

    FOR XM-120...124 ONLY

  • 2 XM-940 Dynamic Measurement Terminal Base

    Important User Information

    Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

    In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

    The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

    No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

    Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

    Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

    WARNING Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

    ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.

    Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.

    Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.

    IMPORTANT Identifies information that is critical for successful application and understanding of the product.

    SHOCK HAZARD

    BURN HAZARD

    Publication GMSI10-IN020C-EN-P - October 2013

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/sgi-in001_-en-p.pdfhttp://www.rockwellautomation.com/literature/

  • XM-940 Dynamic Measurement Terminal Base 3

    ATTENTION Environment and Enclosure

    This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

    This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.

    This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.

    In addition to this publication, see the following:• Industrial Automation Wiring and Grounding Guidelines, publication

    1770-4.1, for additional installation requirements

    • NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures

    Publication GMSI10-IN020C-EN-P - October 2013

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdf

  • 4 XM-940 Dynamic Measurement Terminal Base

    ATTENTION Preventing Electrostatic Discharge

    This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:

    • Touch a grounded object to discharge potential static.

    • Wear an approved grounding wrist strap.

    • Do not touch connectors or pins on component boards.

    • Do not touch circuit components inside the equipment.

    • Use a static-safe workstation, if available.

    • Store the equipment in appropriate static-safe packaging when not in use.

    Publication GMSI10-IN020C-EN-P - October 2013

  • XM-940 Dynamic Measurement Terminal Base 5

    North American Hazardous Location ApprovalThe following information applies when operating this equipment in hazardous locations.

    Informations sur l’utilisation de cet équipement en environnements dangereux.

    Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

    Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.

    WARNING EXPLOSION HAZARD -• Do not disconnect equipment unless

    power has been removed or the area is known to be nonhazardous.

    • Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

    • Substitution of components may impair suitability for Class I, Division 2.

    • If this product contains batteries, they must only be changed in an area known to be nonhazardous.

    AVERTISSEMENT RISQUE D’EXPLOSION – • Couper le courant ou s'assurer

    que l'environnement est classé non dangereux avant de débrancher l'équipement.

    • Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.

    • La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.

    • S'assurer que l'environnement est classé non dangereux avant de changer les piles.

    Publication GMSI10-IN020C-EN-P - October 2013

  • 6 XM-940 Dynamic Measurement Terminal Base

    European Hazardous Location Approval

    European Zone 2 Certification (The following applies when the product bears the Ex Marking.)

    This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.

    Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-0 and EN 60079-15.

    ATTENTION This equipment is not resistant to sunlight or other sources of UV radiation.

    Publication GMSI10-IN020C-EN-P - October 2013

  • XM-940 Dynamic Measurement Terminal Base 7

    WARNING • This equipment shall be mounted in an ATEX-certified enclosure with a minimum ingress protection rating of at least IP54 (as defined in IEC 60529) and used in an environment of not more than Pollution Degree 2 (as defined in IEC 60664-1) when applied in Zone 2 environments. The enclosure must have a tool-removable cover or door. The installation of the product within an ATEX approved enclosure shall not raise the surrounding ambient temperature above the limit specified for the product.

    • This equipment shall be used within its specified ratings defined by Rockwell Automation. The XM-940 is only approved for use with ATEX approved measurement modules with relays up to 120V AC.

    • Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the rated voltage when applied in Zone 2 environments.

    • Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

    • Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.

    WARNING An electrical arc can occur if you do the following:• Insert or remove the module while backplane power is on

    • Connect or disconnect wiring while the field-side power is on

    This can cause an explosion in hazardous location installations. Be sure that power is removed or the area isnonhazardous before proceeding.

    ATTENTION Do not remove or replace a terminal base unit while power is applied. Interruption of the backplane can result in unintentional operation or machine motion.

    WARNING Wiring to or from this device, which enters or leaves the system enclosure, must utilize wiring methods suitable for Class I, Division 2 Hazardous Locations, as appropriate for the installation in accordance with the product drawings as indicated in the following table.

    Publication GMSI10-IN020C-EN-P - October 2013

  • 8 XM-940 Dynamic Measurement Terminal Base

    Power RequirementsRefer to the XM-124 Standard Dynamic Measurement installation guide,

    publication 1440-IN001, for specific power consumption and other

    requirements.

    Refer to the XM Power Supply Solutions Application Technique, publication

    ICM-AP005, for additional details.

    Interconnect LimitTotal current draw through the side connector cannot exceed 3 A. A separate

    power connection is necessary if the total current draw of the interconnecting

    modules is greater than 3 A.

    IMPORTANT There are no drawings associated with the XM-124 Standard Dynamic Measurement Module, catalog number 1440-SDM02-01RA. Be sure that the installer follows all applicable local and regional requirements for installation of the product in the planned location and environment.

    TIP If the total current draw for a row of modules is greater than 3 A, consider connecting power to a module near the center of the rail, rather than at a module on either end. Insure that there is less than 3 A load in either direction from the module where power is connected.

    Publication GMSI10-IN020C-EN-P - October 2013

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1440-IN001-in001_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/ap/icm-ap005_-en-e.pdf

  • XM-940 Dynamic Measurement Terminal Base 9

    Wiring RequirementsUse solid or stranded wire. All XM wiring should meet the following

    specifications:

    • 0.34…2.1 mm2 (22…14 AWG) copper conductors without

    pretreatment; 8.4 mm2 (8 AWG) required for grounding the DIN rail

    for electromagnetic interference (EMI) purposes

    • Recommended strip length 8 mm (0.31 in.)

    • Minimum insulation rating of 300V

    • Soldering the conductor is forbidden

    • Wire ferrules can be used with stranded conductors; copper ferrules

    recommended

    Grounding RequirementsUse these grounding requirements to ensure safe electrical operating

    circumstances, and to help avoid potential EMI and ground noise that can

    cause unfavorable operating conditions for your XM system.

    DIN Rail Grounding

    ATTENTION Do not wire more than two conductors onto any single terminal.

    ATTENTION This product is grounded through the DIN rail to chassis ground. Use zinc-plated, yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.

    Publication GMSI10-IN020C-EN-P - October 2013

  • 10 XM-940 Dynamic Measurement Terminal Base

    XM System DIN Rail Grounding

    1 Use 2.1 mm2 (14 AWG) wire.

    2 Use 8.4 mm2 (8 AWG) wire.

    Power

    Supply

    DYNAMIC MEASUREMENT

    1440-VST02-01RA

    DYNAMIC MEASUREMENT

    1440-VST02-01RA

    POSITION

    1440-TSP02-01RB

    MASTER RELAY

    1440-RMA00-04RC

    EXPANSION RELAY

    1440-REX00-04RD

    EXPANSION RELAY

    1440-REX00-04RD

    EXPANSION RELAY

    1440-REX00-04RD

    EXPANSION RELAY

    1440-REX00-04RD

    Power

    Supply

    DYNAMIC MEASUREMENT

    1440-VST02-01RA

    DYNAMIC MEASUREMENT

    1440-VST02-01RA

    EXPANSION RELAY

    1440-REX00-04RD

    EXPANSION RELAY

    1440-REX00-04RD

    1

    1

    2

    2

    2

    Publication GMSI10-IN020C-EN-P - October 2013

  • XM-940 Dynamic Measurement Terminal Base 11

    The grounding wire can be connected to the DIN rail by using a DIN Rail

    Grounding Block (see illustration below).

    DIN Rail Grounding Block

    1 Use 8.4 mm2 (8 AWG) wire.

    24V Common Grounding

    24V to the XM module must be grounded. When two or more power supplies

    power the XM system, ground the 24V Commons at a single point, such as

    the ground bus bar.

    IMPORTANT If it is not possible or practical to ground the -24V DC supply, then it is possible for the system to be installed and operate ungrounded. However, if installed ungrounded then the system must not be connected to a ground through any other circuit unless that circuit is isolated externally. Connecting a floating system to a non-isolated ground could result in damage to the XM module(s) and/or any connected device. Also, operating the system without a ground may result in the system not performing to the published specifications regards measurement accuracy and communications speed, distance or reliability.

    1

    Publication GMSI10-IN020C-EN-P - October 2013

  • 12 XM-940 Dynamic Measurement Terminal Base

    Transducer Grounding

    Make certain the transducers are electrically isolated from earth ground. Cable

    shields must be grounded at one end of the cable, and the other end left

    floating or not connected. We recommend that where possible, the cable

    shield be grounded at the XM terminal base (Chassis terminal) and not at the

    transducer.

    DeviceNet Grounding - XM-120, XM-121, XM-122, and XM-123 Modules

    The DeviceNet network is functionally isolated and must be referenced to

    earth ground at a single point. XM modules can not be used with an external

    DeviceNet power supply. Connect DeviceNet V- to earth ground at one of

    the XM modules, as shown in the illustration below.

    Grounded DeviceNet V- at XM Module

    IMPORTANT The 24V Common and Signal Common terminals are internally connected. They are isolated from the Chassis terminals unless they are connected to ground as described in this manual. See Wiring on page 17 for terminal assignments.

    ATTENTION Use of a separate DeviceNet power supply is not permitted. See the XM Power Supply Solutions Application Profile, publication ICM-AP005, for guidance in using the XM module with other DeviceNet products.

    To

    Ground

    Bus

    Publication GMSI10-IN020C-EN-P - October 2013

    http://literature.rockwellautomation.com/idc/groups/literature/documents/ap/icm-ap005_-en-e.pdf

  • XM-940 Dynamic Measurement Terminal Base 13

    DeviceNet Grounding - XM-124 Module Only

    The DeviceNet network is fully isolated from the XM-124 power and ground

    circuits. Therefore, DeviceNet network can be powered from any suitable

    DeviceNet power supply, and must be grounded at that power supply in

    accordance with DeviceNet installation instructions.

    Switch Input Grounding

    The Switch Input circuits are functionally isolated from other circuits. It is

    recommended that the Switch RTN signal be grounded at a single point.

    Connect the Switch RTN signal to the XM terminal base (chassis terminal) or

    directly to the DIN rail, or ground the signal at the switch or other equipment

    that is wired to the switch.

    Additional DeviceNet Installation Information

    For more information on the DeviceNet installation, refer to the ODVA

    Planning and Installation Manual - DeviceNet Cable System, which is

    available on the ODVA website (http://www.odva.org).

    Publication GMSI10-IN020C-EN-P - October 2013

    http://www.odva.org

  • 14 XM-940 Dynamic Measurement Terminal Base

    Mounting on the DIN RailYou can also mount the terminal base to a grounded mounting plate. Refer to

    the XM-124 Standard Dynamic Measurement Module User Manual,

    publication 1440-UM001.

    1. Position the terminal base unit on the 35 x 7.5mm DIN rail (A)

    (Allen-Bradley pt no. 199-DR1 or 199-DR4) at a slight angle.

    2. Slide the terminal base unit over leaving room for the side

    connector (B).

    Position terminal base at a slight angle and hook over the top of the DIN rail.

    Publication GMSI10-IN020C-EN-P - October 2013

    http://literature.rockwellautomation.com/idc/groups/literature/documents/um/1440-um001_-en-p.pdf

  • XM-940 Dynamic Measurement Terminal Base 15

    3. Hook the lip on the rear of the terminal base onto the top of the DIN

    rail, and rotate the terminal base onto the rail.

    4. Press down on the terminal base unit to lock the terminal base on the

    DIN rail. If the terminal base does not lock into place, use a

    screwdriver or similar device to open the locking tab, press down on

    the terminal base until flush with the DIN rail and release the locking

    tab to lock the base in place.

    5. Connect the wiring for the XM-940 terminal base unit as shown in

    Wiring on page 17.

    Publication GMSI10-IN020C-EN-P - October 2013

  • 16 XM-940 Dynamic Measurement Terminal Base

    Interconnecting Terminal Base Units

    Follow the steps below to install another terminal base unit.

    1. Position the terminal base on the 35 x 7.5mm DIN rail (A).

    2. Make certain the side connector (B) is fully retracted into the base

    unit.

    3. Slide the terminal base unit over tight against the neighboring terminal

    base. Make sure the hook on the terminal base slides under the edge

    of the terminal base unit.

    4. Press down on the terminal base unit to lock the terminal base on the

    DIN rail. If the terminal base does not lock into place, use a

    screwdriver or similar device to open the locking tab, press down on

    the terminal base until flush with the DIN rail and release the locking

    tab to lock the base in place.

    5. Gently push the side connector into the side of the neighboring

    terminal base to complete the backplane connection.

    IMPORTANT Terminal base units are mounted left to right on the DIN rail.

    Publication GMSI10-IN020C-EN-P - October 2013

  • XM-940 Dynamic Measurement Terminal Base 17

    Wiring

    Terminal Assignments

    IMPORTANT For more wiring connection information, refer to the XM-124 Standard Dynamic Measurement Module User Manual, publication 1440-UM001.

    WARNING If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

    ATTENTION The terminal block assignments are different for different terminal base units. The following table applies only to the XM-940 terminal base. Refer to the installation instructions for the specific terminal base unit for its terminal assignments.

    No. Description No. Description

    0 Transducer 1 connection (+) 26 DeviceNet V (+) (red wire)

    1 Transducer 2 connection (+) 27 DeviceNet V (-) (black wire)

    2 Signal 1 buffered output (+) 28 24V common1

    3 Signal 2 buffered output (+) 29 4…20 mA 2 (+)

    4 Tach/signal input (+) 30 4…20 mA 2 (-)

    5 Buffer Power 1 input 31 Chassis

    6 Positive Buffer Bias 32 Chassis

    7 TxD 33 Chassis

    Publication GMSI10-IN020C-EN-P - October 2013

    http://literature.rockwellautomation.com/idc/groups/literature/documents/um/1440-um001_-en-p.pdf

  • 18 XM-940 Dynamic Measurement Terminal Base

    1 Terminals are internally connected and isolated from the chassis terminals.

    8 RxD 34 Chassis

    9 XRTN1 35 Chassis

    10 Chassis 36 Chassis

    11 4…20mA 1 (+) 37 Chassis

    12 4…20mA 1 (-) 38 Chassis

    13 Chassis 39 Set Point Multiplication

    14 Chassis 40 Switch return

    15 Chassis 41 Reset relay

    16 Transducer 1 connection (-)1 42 Reserved

    17 Transducer 2 connection (-)1 43 24 V common1

    18 Buffered output return1 44 24 V in

    19 Tachometer buffer 45 24 V common1

    20 Tachometer (-) 46 Relay N.C. contact 1 (reserved if XM-124)

    21 Buffer/Xducer Power (-) 47 Relay common contact 1

    22 Buffer Power 2 input 48 Relay N.O. contact 1

    23 CAN_High (white wire) 49 Relay N.O. contact 2 (reserved if XM-124)

    24 CAN_Low (blue wire) 50 Relay common contact 2 (reserved if XM-124)

    25 +24V out 51 Relay N.C. contact 2 (reserved if XM-124)

    IMPORTANT The DeviceNet power circuit through the XM module interconnect, which is rated at only 300 mA, is not intended or designed to power DeviceNet loads. Doing so could damage the module or terminal base.

    No. Description No. Description

    Publication GMSI10-IN020C-EN-P - October 2013

  • XM-940 Dynamic Measurement Terminal Base 19

    SpecificationsThe following table lists the technical specifications for the XM-940 Dynamic

    Measurement Terminal Base

    Technical Specifications

    Attribute 1440-TB-A

    Backplane power 24V DC, 350 mA Class 2 / SELV

    Relay 120V AC, 50/60 Hz, 0.5 A resistive110V DC, 0.3 A resistive30V DC 1.5 A resistive

    Torque 0.8 N•m (7 lb•in)

    Conformal coating All printed circuit boards are conformally coated in accordance with IPC-A-610C

    Dimensions (WxDxH), approx 9.48 W x 9.53 D x 5.72 H cm3.875 W x 3.75 D x 2.25 H in.

    Wire size 0.34... 2.1 mm2 (22...14 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max

    North American temperature code T5

    IEC temperature code T4

    Enclosure type rating None (open-style)

    Publication GMSI10-IN020C-EN-P - October 2013

  • 20 XM-940 Dynamic Measurement Terminal Base

    Environmental Specifications

    Attribute 1440-TB-A

    Temperature, operatingIEC 60068-2-1 (Test Ad, Operating Cold)IEC 60068-2-2 (Test Bd, Operating Dry Heat)IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

    -20…65 °C (-4…149 °F)

    Maximum surrounding air temperature 65 °C (149 °F)

    Non-operating temperatureEC 60068-2-1 (Test Ad, Operating Cold)IEC 60068-2-2 (Test BD, Operating Dry Heat)IED 60068-2-14 (Test Nb Operating Thermal Shock)

    -40…85 °C (-40…185 °F)

    Storage temperature -40…85 °C (-40 to 185 °F)

    Relative humidityIEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

    5...95 % noncondensing

    VibrationIEC 60068-2-6 (Test Fc, Operating)

    5 g @ 10...500 Hz

    Operating shockIEC 60068-2-27 (Test Ea, Unpackaged Shock)

    15 g

    Nonoperating shockIEC 60068-2-27 (Test Ea, Unpackaged Shock)

    30 g

    Publication GMSI10-IN020C-EN-P - October 2013

  • XM-940 Dynamic Measurement Terminal Base 21

    Certifications

    Certification(1) 1440-TB-A

    c-UL-us Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

    CE European Union 2004/108/EC EMC Directive, compliant with:

    • EN 61326-1; Meas./Control/Lab., Industrial Requirements

    • EN 61000-6-2; Industrial Immunity

    • EN 61000-6-4; Industrial Emissions

    • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

    European Union 2006/95/EC LVD, compliant with:

    • EN 61131-2; Programmable Controllers (Clause 11)

    C-Tick Australian Radiocommunications Act, compliant with:

    • AS/NZS CISPR 11; Industrial Emissions

    Ex European Union 94/9/EC ATEX Directive, compliant with:

    • EN 60079-15:2010; Potentially Explosive Atmospheres, Protection "n"

    • EN 60079-0:2012; General Requirements II Ex nA IIC T4 Gc

    KC Korean Registration of Broadcasting and Communications Equipment, compliant with Article 58-2 of Radio Waves Act, Clause 3.

    (1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

    Publication GMSI10-IN020C-EN-P - October 2013

    http://www.ab.com

  • Rockwell Automation Support

    Publication GMSI10-IN020C-EN-P - October 2013 PN-218584

    Allen-Bradley, Rockwell Software, Rockwell Automation, and XM are trademarks of Rockwell Automation, Inc.

    Trademarks not belonging to Rockwell Automation are property of their respective companies.

    Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400

    Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support, you can find technical manuals, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. You can also visit our Knowledgebase at http://www.rockwellautomation.com/knowledgebase for FAQs, technical information, support chat and forums, software updates, and to sign up for product notification updates.

    For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnectSM support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/.

    Installation AssistanceIf you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.

    New Product Satisfaction ReturnRockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

    Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

    United States or Canada 1.440.646.3434

    Outside United States or Canada

    Use the Worldwide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local Rockwell Automation representative.

    United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.

    Outside United States Please contact your local Rockwell Automation representative for the return procedure.

    Supersedes Publication GMSI10-IN020B-EN-P - January 2013 Copyright © 2013 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

    http://www.rockwellautomation.com/supporthttp://www.rockwellautomation.com/knowledgebasehttp://www.rockwellautomation.com/support/http://www.rockwellautomation.com/rockwellautomation/distributor-locator/sales-locator.pagehttp://www.rockwellautomation.com/literature/

    XM-940 Dynamic Measurement Terminal Base Installation Instructions, GMSI10-IN020C-EN-PImportant User InformationNorth American Hazardous Location ApprovalPower RequirementsInterconnect LimitWiring RequirementsGrounding RequirementsMounting on the DIN RailInterconnecting Terminal Base Units

    WiringSpecifications

    Back Cover

    Introduction_Category Types

    This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards. It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printing.Find your publication type in the first section below. Use the assigned Printing Category information to determine the standard print specifications for that document type. The Printing Categories are defined below the Publication Type section. Note there may be slightly different print specifications for the categories, depending on the region (EMEA or Americas).For more information on Global Sales and Marketing Printing Standards, see publication RA-CO004 in DocMan.

    Publication Type and Print Category

    Publication TypeOff Set Print Category Spec. (See table below)JIT Spec. (See table below)DescriptionOrder Min **Order Max **Life Cycle Usage / Release Option

    ADNA - PuttmanNAAdvertisement Reprint ColourNANAPresale / Internal

    APA3D2Application Solution or Customer Success Story5100Presale / External

    ARNANAArticle/Editorial/BylineNANAPresale / Internal

    (press releases should not be checked into DocMan or printed)

    ATB3, B4D5Application techniques5100Presale / External

    BRA2 Primary, A1NABrochures5100Presale / External

    CAC2 Primary, C1NACatalogue150Presale / External

    CGNANACatalogue Guide150Presale / External

    CLNANACollection550Presale / External

    COA5, A6, A9D5Company Confidential InformationNANANA / Confidential

    CPE-onlyE-only, D5Competitive Information550NA / Confidential

    DCE-onlyE-onlyDiscount SchedulesNANAPresale / Internal

    DIA1, A3NADirect Mail5100Presale / Internal

    DMNANAProduct Demo550Presale / Internal

    DSB3D5Dimensions Sheet15Post / External

    DUB3D5Document Update15Post / External

    GRB2D6Getting Results15Post / External

    INB3 Primary, B2D5, D6Installation instructions15Post / External

    LMNANALaunch Materials550Presale / Internal

    PCB3D5Packaging Contents

    PLE-only primary, B3E-onlyPrice List550Presale / Internal

    PMB2D6Programming Manual15Post / External

    PPA3D1Profile (Single Product or Service). NOTE: Application Solutions are to be assigned the AP pub type.5100Presale / External

    QRB2 primary, B3, B5D5, D6Quick Reference15Post / External

    QSB2 primary, B3, B5D5, D6Quick Start15Post / External

    RMB2D5, D6Reference Manual15Post / External

    RNB3D5Release Notes15Post / External

    SGB1 Primary, B4D5, D6Selection Guide Colour550Presale / External

    SGB2D5, D6Selection Guide B/W550Presale / External

    SPA1, A2, A3, A4NASales Promotion NOTE: Service profiles are to be assigned the PP pub type.5100Presale / Internal

    SRB2, B3D5, D6Specification Rating Sheet5100Presale / External

    TDB2 Primary B3, B4, B5D5, D6Technical Data550Presale / External

    TGB2, B3D6Troubleshooting Guide15Post / External

    UMB2 Primary, B4D6User Manual B/W15Post / External

    WDB3D5Wiring Diagrams / Dwgs15Post / Internal

    WPB3 Primary, B5D5White Paper550Presale / External

    ** Minimum order quantities on all JIT items are based on the publication length. **

    Publication lengthMinimum Order Quantity

    77 or more pages1 (no shrink wrap required)

    33 to 76 pages25

    3 to 32 pages50

    1 or 2 pages100

    Pre-sale / MarketingAll paper in this category is White Brightness, 90% or better. Opacity 90% or better

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    A14 color170 gsm 2pp100# gloss cover, 100# gloss text

    A24 color170 gsm , folded, 4pp100# gloss cover, 80# gloss text

    A34 colorCover 170 gsm with Body 120 gsm, > 4pp80# gloss cover, 80# gloss text

    A42 color170gsm Silk – 120gsm Silk80# gloss cover, 80# gloss text

    A52 color170gsm Silk – 120gsm Silk80# gloss cover, 80# matt sheet text

    A61 color170gsm Silk – 120gsm Silk80# gloss cover, 80# matt sheet text

    A74 color cover2 color textSelection GuideCategory being deleted10 Point Cover C2S50# matte sheet text

    A84 color coverCategory being deleted50# matte sheet text, self cover

    2 color text

    Selection Guide

    A92 color100gsm bond50# matte sheet text, self cover

    Selection Guide

    Gray shading indicates Obsolete Print Catagories

    Post Sale / Technical Communication

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    B14 color cover270gsm Gloss 100gsm bond10 Point Cover C2S

    2 color text50# matte sheet text

    B21 color160gsm Colortech & 100gsm Bond90# Cover50# matte sheet text

    B31 color100gsm bond50# matte sheet text, self cover

    B42 color160gsm Colortech & 100gsm Bond90# Cover50# matte sheet text

    B52 color100gsm bond50# matte sheet text, self cover

    Catalogs

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    C14 color cover270gsm Gloss 90gsm silk10 Point Cover C2S

    4 color text45# Coated Sheet

    C24 color cover270gsm Gloss 80gsm silk10 Point Cover C2S

    2 color text32#-33# Coated Sheet

    JIT / PODAll paper in this category is White Brightness, 82% or better. Opacity 88% or better

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    D14 color170gsm white silk80# gloss cover, coated 2 sides

    D24 color120gsm white silk80# gloss text, coated 2 sides, self cover

    D34 colorCover 170gsm with Body 120gsm80# gloss cover, 80# gloss text coated 2 sides

    D41 color160gsm tab90# index

    D51 color80gsm bond20# bond, self cover

    D61 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D72 color160gsm tab90# index

    D82 color80gsm bond20# bond, self cover

    D92 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D10Combination: 4 color cover, with 2 color bodyCover 160gsm with Body 80gsm90# index, 20# bond

    Gray shading indicates Obsolete Print Catagories

    Just In Time (JIT) or Off Set (OS)?

    Use these guidelines to determine if your publication should be JIT (just in time/print on demand) or if it would be more economical to print OS (offset/on a press). OS print jobs require an RFQ (Request For Quote) in US. If your job fits into the “Either” category, an RFQ is recommended, but not required. In the US, RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the JIT category. Guidelines differ for black & white and color printing, so be sure to check the correct tables.

    Black & White Printing

    Color Printing

    Color Printing

    Print Spec Sheet

    JIT Printing SpecificationsRA-QR005J-EN-P - 6/14/2013

    Printing SpecificationYOUR DATA HEREInstructionsNO

    (required) Publication Number:GMSI10-IN020C-EN-PSample: 2030-SP001B-EN-P11” x 17”LOOSE -Loose LeafYESPre-sale / MarketingTOP

    Use Legacy Number:YES or NO8.5” x 11”PERFECT - Perfect BoundA1LEFT

    Legacy Number if applicable:Sample Legacy Number: 0160-5.338.375” x 10.875SADDLE - Saddle StitchA2RIGHTCORNER

    Publication Title:XM-940 Dynamic Measurement Terminal Base Installation InstructionsSample: ElectroGuard Selling Brief80 character limit - must match DocMan Title8.25” x 11” (RA product profile std)PLASTCOIL - Plastic Coil (Coil Bound)A4BOTTOMSIDE

    Used in Manufacturing:YESYES or NO - If Yes, must have Part No. listed below8.25” x 10.875”STAPLED1 -1 positionA3

    Part Number:PN-218584If SAP Part Number, be sure to enter PN- before the number7.385” x 9” (RSI Std)STAPLED1B - bottom 1 positionA5

    (required) CategoryD6Select Print Category A,B,C or D from category list, on "Introduction_Category Types" tab6” x 4”STAPLED2 - 2 positionsA6

    Paper Stock Color:whiteWhite is assumed. For color options contact your vendor5.5” x 8.5” (half-size)THERMAL - Thermal bound (Tape bound)A7

    Ink Color:blackOne color assumes BLACK / 4 color assume CMYK / Indicate PMS number here4.75” x 7.75”THERMALO - Thermal Bound (Tape bound - offline)A8

    (required) Page Count ofPublication:22Total page count including cover. Enter PAGE count, not SHEET count4.75” x 7” (slightly smaller half-size)A9

    (required) Finished Trim Size Width:4.75” x 7” (slightly smaller half-size)This is sheet size, before folding4.25" x 5.50"Post Sale / Technical Communication

    Fold:NoneReview key below. Leave blank if folded for saddle stitching4” x 6”B1

    Finished Fold Size:This is size after folding is completed3” x 5”B2

    Binding/Stitching:STAPLED1 -1 positionReview key below9” x 12” (Folder)B3None

    Stitching Location:CORNERBlank, Corner or SideA4 (8 ¼” x 11 ¾”) (210 x 297 mm)B4Half or V or Single Fold

    Drill Hole (Yes/No):NOAll drilled publications use the 5-hole standard, 5/16 inch-size hole and a minimum of ¼ inch from the inner page border.A5 (5.83” x 8.26”) (148 x 210 mm)B5C or Tri-Fold

    Number of Tabs Needed:5 tab in stock at RR Donnelley36” x 24” PosterCatalogsDbleParll

    Number of Pages per Pad:Average sheets of paper. 25, 50 75,100 Max24” x 36” PosterC1Sample

    Glue Location on Pad:Glue location on pads18” x 24” PosterC2Short (must specify dimensions between folds in Comments)

    (required) Business Group:Marketing CommercialAs entered in DocManJIT/PODZ or Accordian Fold

    (required) Cost Center:19134 - IAIf your Business Unit is Marketing Commercial, add the appropriate division name after 19134 using the chart on the right. All other Business Units: Enter only the number as in DocMan, no description. Example - 1902119134 - Commerc 19134 - OEM 19134 - Compone 19134 - Power C19134 - Global 19134 - Process 19134 - IA 19134 - Service 19134 - IMC 19134 - Safety 19134 - Industr 19134 - Softwar19134 - Mkt Dig 19134 - US MarkeD1Microfold or French Fold - designate no. of folds in Comments - intended for single sheet only to be put in box for manufacturing

    Comments:D2Double Gate

    FoldsHalf, V, Single C or Tri

    Dble Parll

    Z or Accordian Microfold or French

    Double Gate

    Short FoldSaddle-Stitch Items All page quantities must be divisible by 4.Note: Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location.80 pgs max. on 20# (text and cover)76 pgs max. on 20# (text) and 24# (cover)72 pgs max. on 24# (text and cover)

    Perfect Bound Items940 pgs max. w/cover (90# index unless indicated otherwise)70 pgs. min. for spine without words200 pgs min. for spine with words

    Plastcoil Bound Items530 pgs max. of 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise)

    Tape Bound Items250 pgs max. on 20# no cover240 pgs max. w/cover (90# index unless indicated otherwise)D3

    D4

    D5

    D6

    D7

    D8

    D9

    MBD000B0209.bin

    MBD000B020B.bin

    MBD000B020C.bin

    MBD000B020A.bin

    MBD000B0205.bin

    MBD000B0207.bin

    MBD000B0208.bin

    MBD000B0206.bin

    MBD000B0203.bin

    MBD000B0204.bin

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Average /GrayImageResolution 300 /GrayImageDepth 8 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 2.00000 /EncodeGrayImages true /GrayImageFilter /FlateEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Average /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure true /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice