56
036-21685-001-A-0505 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE TECHNICAL GUIDE SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS DR 036, 048, 060 and 072 3, 4, 5 and 6 NOMINAL TONS 13.0 SEER 10.4 EER ® DESCRIPTION YORK Sunline MagnaDRY™ units are convertible single package air conditioners with a common cabinet and a com- mon roof curb for the 3, 4, 5 and 6 ton sizes. The units were designed for light commercial and commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame. All units include: Powder Paint finish that meets ASTM-B-117 1000 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability (field convertible) Manufactured under the quality standards of ISO9001 Simplicity TM Control Board Copper tube/aluminum fin coils Easy access to all components Rigging holes in base rails for lifting Fork lift slots on three sides Single point power connection Complete factory package - tested, charged and wired CSA agency listing on all units WARRANTY Factory Limited Parts Warranty One-year parts warranty A Five-year parts warranty on the compressor and electric heat elements. Ten-year parts warranty on the gas-fired heat exchangers.

Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TECHNICAL GUIDE

SINGLE PACKAGE GAS/ELECTRIC UNITS

AND SINGLE PACKAGE

AIR CONDITIONERSDR 036, 048, 060 and 0723, 4, 5 and 6 NOMINAL TONS13.0 SEER10.4 EER

� �

DESCRIPTIONYORK Sunline MagnaDRY™ units are convertible single package air conditioners with a common cabinet and a com-mon roof curb for the 3, 4, 5 and 6 ton sizes. The units were designed for light commercial and commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame.

All units include:

• Powder Paint finish that meets ASTM-B-117 1000 hour salt spray standards

• Permanently lubricated motors

• Bottom or side air discharge configuration capability (field convertible)

• Manufactured under the quality standards of ISO9001

• SimplicityTM Control Board

• Copper tube/aluminum fin coils

• Easy access to all components

• Rigging holes in base rails for lifting

• Fork lift slots on three sides

• Single point power connection

• Complete factory package - tested, charged and wired

• CSA agency listing on all units

WARRANTY

• Factory Limited Parts Warranty

• One-year parts warranty

• A Five-year parts warranty on the compressor andelectric heat elements.

• Ten-year parts warranty on the gas-fired heatexchangers.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Page 2: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE OF CONTENTSDESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 4

FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . 13

FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . 14

GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 52

LIST OF FIGURES

Fig. # Pg. #

1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

2 DR036 MOISTURE REMOVAL - REHEAT MODE . . 31

3 DR048 MOISTURE REMOVAL - REHEAT MODE . . 31

4 DR060 MOISTURE REMOVAL - REHEAT MODE . . 32

5 DR072 MOISTURE REMOVAL - REHEAT MODE . . 32

6 TYPICAL FIELD POWER & CONTROL WIRING . . . 45

7 UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . . . . . 46

8 UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

9 UNIT WITH ECONOMIZER RAINHOOD . . . . . . . . . . 47

10 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD . . . . . . . . . . . . . . . . . . . . . . . . 47

11 UNIT DIMENSIONS (REAR VIEW) . . . . . . . . . . . . . . 48

12 DISCONNECT/BLOWER ACCESS LOCATION . . . . 48

13 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . 49

14 FOUR AND SIX POINT LOADING . . . . . . . . . . . . . . 50

15 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . . . . 51

LIST OF TABLES

Tbl. # Pg. #

1 DR036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . . . 16

2 DR036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE) . . . . . . . . . . 16

3 DR036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

4 DR036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE) . . . . . . . . . . . . . . . . . . . . . . . 17

5 DR048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . . . 18

6 DR048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE) . . . . . . . . . . 18

Tbl. # Pg. #

7 DR048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

8 DR048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE) . . . . . . . . . . . . . . . . . . . . . . . 19

9 DR060 & 072 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . . . 20

10 DR060 & 072 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE) . . . . . . . . . . 20

11 DR060 & 072 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) . . . . . . . . . . . . . . . . . . 21

12 DR060 & 072 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE) . . . . . . . . . . . . . 21

13 CAPACITY RATINGS . . . . . . . . . . . . . . . . . . . . . . . . 22

14 GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . . 22

15 DR036 COOLING CAPACITIES (3 TON) - NORMAL MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

16 DR036 COOLING CAPACITIES (3 TON) - REHEAT MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

17 DR048 COOLING CAPACITIES (4 TON) - NORMAL MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

18 DR048 COOLING CAPACITIES (4 TON) - REHEAT MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

19 DR060 COOLING CAPACITIES (5 TON) - NORMAL MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

20 DR060 COOLING CAPACITIES (5 TON) - REHEAT MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

21 DR072 COOLING CAPACITIES (6 TON) - NORMAL MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

22 DR072 COOLING CAPACITIES (6 TON) - REHEAT MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

23 SUPPLY AIR BLOWER PERFORMANCE (DR036 BELT DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . 33

24 SUPPLY AIR BLOWER PERFORMANCE (DR036 BELT DRIVE) - BOTTOM DUCT APPLICATION . . . . . . . . . 34

25 SUPPLY AIR BLOWER PERFORMANCE (DR048 BELT DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . 35

26 SUPPLY AIR BLOWER PERFORMANCE (DR048 BELT DRIVE) - BOTTOM DUCT APPLICATION . . . . . . . . . 36

27 SUPPLY AIR BLOWER PERFORMANCE (DR060 & DR072 BELT DRIVE) - SIDE DUCTAPPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

28 SUPPLY AIR BLOWER PERFORMANCE (DR060 & DR072 BELT DRIVE) - BOTTOM DUCTAPPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

29 BELT DRIVE BLOWER MOTOR AND DRIVE DATA . 39

30 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . . 39

2 Unitary Products Group

Page 3: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

LIST OF TABLES - CONTINUED

Tbl. # Pg. #

31 ELECTRIC HEATER CFM LIMITATIONS . . . . . . . . . 39

32 ELECTRICAL DATA - DR036 AND DR048 W/O POWERED CONVENIENCE OUTLET . . . . . . . . . . . 40

33 ELECTRICAL DATA - DR060 AND DR072 W/O POWERED CONVENIENCE OUTLET . . . . . . . . . . . 41

34 ELECTRICAL DATA - DR036 AND DR048 WITH POWERED CONVENIENCE OUTLET . . . . . . . . . . . 42

35 ELECTRICAL DATA - DR060 AND DR072 WITH POWERED CONVENIENCE OUTLET . . . . . . . . . . . 43

36 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

Tbl. # Pg. #

37 ELECTRIC HEAT CORRECTION FACTORS . . . . . . 44

38 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . . 44

39 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

40 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . 48

41 DR 4 POINT LOADS WEIGHT DISTRIBUTION . . . . 50

42 DR 6 POINT LOADS WEIGHT DISTRIBUTION . . . . 50

43 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . 50

44 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . . . . . 51

Unitary Products Group 3

Page 4: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

PRODUCT NOMENCLATURE

4 Unitary Products Group

Page 5: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

PRODUCT NOMENCLATURE - Continued

3-6T Sunline Model Number Nomenclature

Standard CabinetAA NoneAB Phase MonitorAC Coil GuardAD Dirty Filter SwitchAE Phase Monitor & Coil GuardAF Phase Monitor & Dirty Filter SwitchAG Coil Guard & Dirty Filter SwitchAH Phase Monitor, Coil Guard, & Dirty Filter SwitchAJ SS Drain PanAK SS Drain Pan & Phase MonitorAL SS Drain Pan & Coil GuardAM SS Drain Pan & Dirty Filter SwitchAN SS Drain Pan, Phase Monitor, Coil Guard & Dirty Filter SwitchAS Bottom Drain ConnectionCA CPC Controller with Dirty Filter Switch & Air Proving SwitchCB CPC Controller, DFS, APS & Phase MonitorCC CPC Controller, DFS, APS & Coil GuardCD CPC Controller, DFS, APS, Phase Monitor, & Coil GuardCE CPC Controller, DFS, APS & Technicoat Cond. CoilCF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase MonitorCG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil GuardCH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil GuardCJ CPC Controller, DFS, APS & Technicoat Evap. CoilCK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase MonitorCL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil GuardCM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil GuardCN CPC Controller, DFS, APS & Technicoat Evap. & Cond CoilsCP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase MonitorCQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil GuardCR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil GuardCS CPC Controller, DFS, APS, SS Drain PanCT CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil GuardCU CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond CoilsCV CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap CoilCW CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond CoilsCX CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond CoilsJA Johnson UNT Controller with Dirty Filter Switch & Air Proving SwitchJB Johnson UNT Controller, DFS, APS & Phase MonitorJC Johnson UNT Controller, DFS, APS & Coil GuardJD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil GuardJE Johnson UNT Controller, DFS, APS & Technicoat Cond. CoilJF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase MonitorJG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil GuardJH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil GuardJJ Johnson UNT Controller, DFS, APS & Technicoat Evap. CoilJK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase MonitorJL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil GuardJM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil GuardJN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond CoilsJP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor

Unitary Products Group 5

Page 6: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil GuardJR Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil GuardJS Johnson UNT Controller, DFS, APS, SS Drain PanJT Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil GuardJU Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond CoilsJV Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap CoilJW Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond CoilsJX Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond CoilsHA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving SwitchHB Honeywell Excel 10 Controller, DFS, APS & Phase MonitorHC Honeywell Excel 10 Controller, DFS, APS & Coil GuardHD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil GuardHE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. CoilHF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase MonitorHG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil GuardHH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil GuardHJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. CoilHK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase MonitorHL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil GuardHM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil GuardHN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond CoilsHP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase MonitorHQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil GuardHR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil GuardHS Honeywell Excel 10 Controller, DFS, APS, SS Drain PanHT Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil GuardHU Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond CoilsHV Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap CoilHW Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap and Cond CoilsHX Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond CoilsNA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving SwitchNB Novar ETC-3 Controller, DFS, APS & Phase MonitorNC Novar ETC-3 Controller, DFS, APS & Coil GuardND Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil GuardNE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. CoilNF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase MonitorNG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil GuardNH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil GuardNJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. CoilNK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase MonitorNL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil GuardNM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil GuardNN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond CoilsNP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase MonitorNQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil GuardNR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil GuardNS Novar ETC-3 Controller, DFS, APS, SS Drain PanNT Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil GuardNU Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond CoilsNV Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap CoilNW Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond CoilsNX Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond CoilsTA Technicoat Condenser CoilTB Technicoat Condenser Coil & Phase Monitor

Standard Cabinet

6 Unitary Products Group

Page 7: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TC Technicoat Condenser Coil & Coil GuardTD Technicoat Condenser Coil & Dirty Filter SwitchTE Technicoat Condenser Coil, Phase Monitor, & Coil GuardTF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter SwitchTG Technicoat Condenser Coil, Coil Guard, & Dirty Filter SwitchTH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter SwitchTJ Technicoat Evaporator CoilTK Technicoat Evaporator Coil & Phase MonitorTL Technicoat Evaporator Coil & Coil GuardTM Technicoat Evaporator Coil & Dirty Filter SwitchTN Technicoat Evaporator Coil, Phase Monitor, & Coil GuardTP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter SwitchTQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter SwitchTR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter SwitchTS Technicoat Evaporator & Condenser CoilsTT Technicoat Evaporator & Condenser Coils & Phase MonitorTU Technicoat Evaporator & Condenser Coils & Coil GuardTV Technicoat Evaporator & Condenser Coils & Dirty Filter SwitchTW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil GuardTX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter SwitchTY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter SwitchTZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter SwitchT1 Technicoat Condenser & SS Drain PanT3 Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter SwitchT4 Technicoat Evaporator & SS Drain PanT6 Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter SwitchT7 Technicoat Evaporator & Condenser Coils & SS Drain PanT9 Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter SwitchLA Simplicity Intelli-Comfort ControllerLB Simplicity Intelli-Comfort Controller, & Phase MonitorLC Simplicity Intelli-Comfort Controller, & Coil GuardLD Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil GuardLE Simplicity Intelli-Comfort Controller, & Technicoat Cond. CoilLF Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase MonitorLG Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil GuardLH Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil GuardLJ Simplicity Intelli-Comfort Controller, & Technicoat Evap. CoilLK Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase MonitorLL Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil GuardLM Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil GuardLN Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond CoilsLP Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase MonitorLQ Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil GuardLR Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil GuardLS Simplicity Intelli-Comfort Controller, SS Drain PanLT Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil GuardLU Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond CoilsLV Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap CoilLW Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond CoilsLX Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond CoilsWA Intelli-Comfort w/Mod Link ControllerWB Intelli-Comfort w/Mod Link Controller, & Phase MonitorWC Intelli-Comfort w/Mod Link Controller, & Coil GuardWD Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard

Standard Cabinet

Unitary Products Group 7

Page 8: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

WE Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. CoilWF Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase MonitorWG Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil GuardWH Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil GuardWJ Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. CoilWK Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase MonitorWL Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil GuardWM Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil GuardWN Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond CoilsWP Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase MonitorWQ Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil GuardWR Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil GuardWS Intelli-Comfort w/Mod Link Controller, SS Drain PanWT Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil GuardWU Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond CoilsWV Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap CoilWW Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond CoilsWX Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils

Hinged Filter Door & Toolless Access CabinetBA Hinged Filter Door & Toolless Access PanelsBB Phase Monitor, Hinged Filter Door & Toolless Access PanelsBC Coil Guard, Hinged Filter Door & Toolless Access PanelsBD Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsBE Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access PanelsBF Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsBG Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsBH Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsBJ SS Drain Pan & Hinged Filter Door & Toolless Access PanelsBK SS Drain Pan & Phase Monitor, Hinged Filter Door & Toolless Access PanelsBL SS Drain Pan & Coil Guard, Hinged Filter Door & Toolless Access PanelsBM SS Drain Pan & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsBN SS Drain Pan & Phase Monitor & Coil Guard, Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsBS Bottom Drain Connection, Hinged Filter Door & Toolless Access PanelsDA CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access PanelsDB CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access PanelsDC CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access PanelsDD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsDE CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access PanelsDF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsDG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access PanelsDH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsDJ CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access PanelsDK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsDL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access PanelsDM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsDN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access PanelsDP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsDQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access PanelsDR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsDS CPC Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access PanelsDT CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access PanelsDU CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access PanelsDV CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels

Standard Cabinet

8 Unitary Products Group

Page 9: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

DW CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access PanelsDX CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless

Access PanelsEA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access PanelsEB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access PanelsEC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access PanelsED Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsEE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access PanelsEF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsEG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access PanelsEH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsEJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access PanelsEK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsEL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access PanelsEM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsEN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access PanelsEP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsEQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access

PanelsER Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door &

Toolless Access PanelsES Johnson UNT Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access PanelsET Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access PanelsEU Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access PanelsEV Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access PanelsEW Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access PanelsEX Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &

Toolless Access PanelsGA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access PanelsGB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access PanelsGC Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access PanelsGD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsGE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access PanelsGF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsGG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access PanelsGH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access

PanelsGJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access PanelsGK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsGL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access PanelsGM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access

PanelsGN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access PanelsGP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access

PanelsGQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access PanelsGR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless

Access PanelsGS Honeywell Excel 10 Controller, DFS, APS, SS Drain PanGT Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil GuardGU Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond CoilsGV Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap CoilGW Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap and Cond CoilsGX Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond CoilsPA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels

Hinged Filter Door & Toolless Access Cabinet

Unitary Products Group 9

Page 10: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

PB Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access PanelsPC Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access PanelsPD Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsPE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access PanelsPF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsPG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access PanelsPH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsPJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access PanelsPK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsPL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access PanelsPM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsPN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access PanelsPP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsPQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access PanelsPR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access

PanelsPS Novar ETC-3 Controller, DFS, APS, SS Drain PanPT Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil GuardPU Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond CoilsPV Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap CoilPW Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond CoilsPX Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond CoilsUA Technicoat Condenser Coil, Hinged Filter Door & Toolless Access PanelsUB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access PanelsUC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access PanelsUD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsUE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsUF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsUG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsUH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsUJ Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access PanelsUK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access PanelsUL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access PanelsUM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsUN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsUP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsUQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsUR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsUS Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access PanelsUT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access PanelsUU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access PanelsUV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsUW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsUX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsUY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsUZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsU1 Technicoat Condenser & SS Drain Pan, Hinged Filter Door & Toolless Access PanelsU3 Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsU4 Technicoat Evaporator & SS Drain Pan, Hinged Filter Door & Toolless Access PanelsU6 Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access PanelsU7 Technicoat Evaporator & Condenser Coils & SS Drain Pan, Hinged Filter Door & Toolless Access PanelsU9 Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless

Access PanelsQA Simplicity Intelli-Comfort Controller with Hinged Filter Door & Toolless Access PanelsQB Simplicity Intelli-Comfort Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

Hinged Filter Door & Toolless Access Cabinet

10 Unitary Products Group

Page 11: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

QC Simplicity Intelli-Comfort Controller, & Coil Guard, Hinged Filter Door & Toolless Access PanelsQD Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsQE Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access PanelsQF Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsQG Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access PanelsQH Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless AccessQJ Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access PanelsQK Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsQL Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access PanelsQM Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless AccessQN Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access PanelsQP Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access PanQQ Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access PanelsQR Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & ToollesQS Simplicity Intelli-Comfort Controller, SS Drain Pan Hinged Filter Door & Toolless Access PanelsQT Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access PanelsQU Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access PanelsQV Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access PanelsQW Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access PanelsQX Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &

Toolless Access PanelsXA Intelli-Comfort w/Mod Link Controller, Hinged Filter Door & Toolless Access PanelsXB Intelli-Comfort w/Mod Link Controller, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsXC Intelli-Comfort w/Mod Link Controller, & Coil Guard, Hinged Filter Door & Toolless Access PanelsXD Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access PanelsXE Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access PanelsXF Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsXG Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access PanelsXH Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless AccessXJ Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access PanelsXK Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access PanelsXL Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access PanelsXM Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless AccessXN Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access PanelsXP Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access PanXQ Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access PanelsXR Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & ToollesXS Intelli-Comfort w/Mod Link Controller, SS Drain Pan Hinged Filter Door & Toolless Access PanelsXT Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access PanelsXU Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access PanelsXV Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access PanelsXW Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access PanelsXX Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &

Toolless Access Panels

Hinged Filter Door & Toolless Access Cabinet

Unitary Products Group 11

Page 12: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

FEATURES

All models are available with a wide variety of factory-mounted options such as stainless steel heat exchangers, electric heaters, phase monitor, convenience outlet, dirty filter switch, disconnect switch, smoke detectors, and coil guard to make them suitable for almost every application.

All units are self-contained and assembled on full perimeter base rails with forklift holes on three sides and holes for over-head rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.

All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizon-tal duct, remove the supply and return air panels on the rear of the unit.

All models are available with these “factory mounted” outdoor air damper options:

• Single enthalpy economizer

• Motorized outdoor air damper

Supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job.

All compressors are equipped with internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch to protect all system compo-nents.

• Simplicity™ Controls - Simplicity™ control boards have standardized a number of features previously available only as options or by utilizing additional controls.

• Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assis-tance. Optionally, the control board can be pro-grammed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.

• Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.

• Fan Delays - Fan on and fan off delays are fully pro-grammable and are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.

• Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.

• Nuisance Trip Protection- To prevent nuisance trouble calls, the control board uses a “three strikes, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the compressor.

• On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.

All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures.

All models are CSA listed.

• Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty.

• Gas Heat Operation - All gas heat units have a minimum AFUE of 80%. Each section includes a durable heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power vent-ing, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.

The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.

• Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uni-form distribution of air across the heating elements. Every element is fully protected against excessive tem-perature by thermal limit switches.

The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the side of the unit.

• BAS Controls - York’s Sunline™ series units offer fac-tory mounted BAS controls such as SImplicity™ INTELLI-Comfort™, Novar, Honeywell, Johnson, and CPC.

12 Unitary Products Group

Page 13: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

FIGURE 1 - UNIT CUTAWAY

FACTORY-INSTALLED OPTIONS• SINGLE INPUT ELECTRONIC ENTHALPY ECONO-

MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capa-ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

• MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2-position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is oper-ating and will drive fully closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be field assembled before installing.

• PHENOLIC COATED EVAPORATOR AND CON-DENSER COILS - Special coating process that utilizes Technicoat 10-1TM processes. Coating is applied by total immersion of the complete coil for maximum protection.

• ELECTRIC HEATERS - Wired for single point power supply. These nickel chromium heater elements are pro-vided with limit and automatic reset capability to prevent operation at excessive temperatures.

• FILTER OPTIONS - Standard units are shipped with 1” throw-away filters installed. 2” pleated filters are offered as a factory installed option.

• CONVENIENCE OUTLET - This 110 volt outlet can be “powered” by the unit with a stepdown transformer or the unit may be ordered with a “non-powered” convenience outlet that can be wired in the field.

• DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.

• BAS - Building Automation System ControlsSimplicity™ INTELLI-Comfort™ CONTROL - The York® Simplicity™ INTELLI-Comfort™ control is factory installed. It includes a supply air sensor, a return air sen-sor, and an outside air sensor. There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Outside Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor, and an Outside Air IAQ sensor. Construction mode operation, 365-day real time clock with 7 day programming plus holiday

Unitary Products Group 13

Page 14: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Com-fort™using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Out-side CO2 sensor to perform Differential Demand Ventila-tion. It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The pat-ented economizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the INTELLI-Start™ algorithm to maximize energy sav-ings by recovering the building from the Unoccupied Set-points to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity™ INTELLI-Comfort™ balances space temperature, venti-lation air temperature, CO2 and humidity for ultimate comfort.

• Simplicity™ INTELLI-Comfort™ with MOD LINK CON-TROL - The York® Simplicity™ INTELLI-Comfort™ with Mod Link control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an addi-tional control to translate communications from MOD-BUS to the BACnet MSTP protocol.

• Novar® BAS CONTROL - The Novar® ETC-3 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

• JOHNSON CONTROLS BAS CONTROL - The Johnson Control YK-UNT-1126 building automation system con-troller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air prov-ing switch.

• CPC BAS CONTROL - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building auto-mation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.

• HONEYWELL BAS CONTROL - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.

• SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.

• COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

• STAINLESS STEEL HEAT EXCHANGER - For applica-tions in corrosive environments, this option provides a full stainless steel heat exchanger assembly.

• STAINLESS STEEL DRAIN PAN - An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environ-ments.

• BOTTOM DRAIN CONNECTION - An optional bottom drain connection is available for inside the curb connec-tions for applications in cold environments to reduce freezing drain lines.

• PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of-phase condition.

• DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.

• HINGED FILTER DOOR/“TOOLLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance.

NOTE:Knobs are shipped inside the unit to prevent ship-ping damage. These must be field installed for tool-less operation.

FIELD-INSTALLED ACCESSORIES• SINGLE INPUT ELECTRONIC ENTHALPY ECONO-

MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capa-ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

• MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2-position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be field assembled before installing.

• ELECTRIC HEATERS wired for single point power sup-ply. These nickel chromium heater elements are pro-vided with limit and automatic reset capability to prevent operation at excessive temperatures.

14 Unitary Products Group

Page 15: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

• ROOF CURBS - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the fin-ished roof. These full perimeter curbs meet the require-ments of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assem-bly.

Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.

• HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.

• PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.

• HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at alti-tudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.

• LOW NOX KIT- Required to reduce the emission of nitrogen oxides below 40 nanograms per joule.

• POWER EXHAUST - Our single input economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the condi-tioned space from being over-pressurized during econo-mizer operation.

The power exhaust option can only be used on bot-tom duct configurations.

• BAROMETRIC RELIEF DAMPER - This damper acces-sory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.

• ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.

• BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.

• FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.

• CO2 SENSOR - Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits.

• COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

• HAIL GUARD - Hail guard kit is available to prevent unit from hail damage. This is a sloped hood that fits above the coil.

• GAS PIPING KIT - This kit supplies all necessary fittings and shut off valve.

REHEAT MODE SEQUENCE OF OPERATION• STANDARD A/C MODE: INPUT: Y1 ON, Y2 OFF,

HUMIDISTAT OPEN - During normal cooling operation, a Y1 call from the thermostat will bring on the unit in the standard cooling mode. Since the humidistat is open, the liquid line solenoid (SLL) will be open and the hot gas solenoid (SHG) will be closed allowing the unit to operate in the standard cooling mode.

• REHEAT MODE: INPUT: Y1 ON, Y2 OFF, HUMIDISTAT CLOSED - During reheat mode, the Y1 signal will bring on the compressor and will send the 24V signal through the humidistat, through the normally closed contacts of the hot gas relay (RHG) and will energize both the liquid line and the hot gas solenoids which directs hot gas through part of the indoor coil and decreases the sensible capacity of the unit.

• STANDARD A/C MODE: INPUT: Y1 ON, Y2 ON, HUMIDISTAT OPEN OR CLOSED - If there is a call for Y1 and Y2, the unit will be in normal cooling mode regardless of the humidistat input. The Y2 signal will energize the hot gas relay (RHG) which will keep the liquid line solenoid (SLL) open and the hot gas solenoid (SHG) closed and the unit will operate in the normal cooling mode.

Unitary Products Group 15

Page 16: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 1: DR036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)

TABLE 2: DR036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL

CONFIGURATION

Indoor Blower Speed (RPM)

Blower Static Pressure (IWG)

Airflow (CFM)

Blower Motor BHP

63 80 84 80 83 85 87 84 87

125 74 77 74 76 80 82 80 83

250 58 61 58 61 68 68 63 65

500 48 51 47 50 58 58 53 54

1000 41 45 39 43 55 55 49 50

2000 39 41 37 39 53 53 46 47

4000 41 41 38 38 55 55 49 49

8000 45 45 44 44 52 53 47 47

4. Test duct termination is flush with reverberation room wall.

5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

Cooling

Operation2

(dB)

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2. Cooling Operation – ID blower, compressor and outdoor fan operating.

3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

Cooling

Operation2

(dB)

ID Blower

Only (dB)

Cooling

Operation2

(dB)

ID Blower

Only (dB)Octave Center Freq.

ID Blower

Only (dB)

Cooling

Operation2

(dB)

ID Blower

Only (dB)

0.41 0.37 0.76 0.53

1116 928 1979 1020

0.2 0.3 0.2 0.7

DR036 / 3 Ton / Belt Drive

Horizontal Ducted Discharge

630 631 879 885

16 Unitary Products Group

Page 17: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 3: DR036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)

TABLE 4: DR036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL

CONFIGURATION

Indoor Blower Speed (RPM)

Blower Static Pressure (IWG)

Airflow (CFM)

Blower Motor BHP

63 78 82 78 82 80 85 80 84

125 70 75 70 74 71 80 71 79

250 55 60 55 60 59 61 58 62

500 47 50 47 50 52 53 49 52

1000 40 43 39 43 50 51 45 46

2000 37 40 37 39 45 46 41 43

4000 36 37 36 37 45 46 40 40

8000 44 44 44 44 45 47 44 44

4. Test duct termination is flush with reverberation room wall.

5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

Cooling

Operation2

(dB)

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2. Cooling Operation – ID blower, compressor and outdoor fan operating.

3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

Cooling

Operation2

(dB)

ID Blower

Only (dB)

Cooling

Operation2

(dB)

ID Blower

Only (dB)Octave Center Freq.

ID Blower

Only (dB)

Cooling

Operation2

(dB)

ID Blower

Only (dB)

0.36 0.33 0.71 0.49

1069 870 1903 917

0.2 0.3 0.2 0.7

632 632 881 883

DR036 / 3 Ton / Belt Drive

Vertical Ducted Inlet

UNIT DESCRIPTION / MODEL

CONFIGURATION

Indoor Blower Speed (RPM)

Blower Static Pressure (IWG)

Airflow (CFM)

Blower Motor BHP

63 80 83 80 83 83 86 82 85

125 78 79 77 78 80 83 79 82

250 55 60 54 59 63 63 58 62

500 48 51 46 50 58 59 52 53

1000 41 44 39 43 54 55 48 49

2000 37 40 35 38 50 50 42 44

4000 38 39 36 37 52 53 44 44

8000 44 45 44 44 49 50 45 45

4. Test duct termination is flush with reverberation room wall.

5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

Cooling

Operation2

(dB)

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2. Cooling Operation – ID blower, compressor and outdoor fan operating.

3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

Cooling

Operation2

(dB)

ID Blower

Only (dB)

Cooling

Operation2

(dB)

ID Blower

Only (dB)Octave Center Freq.

ID Blower

Only (dB)

Cooling

Operation2

(dB)

ID Blower

Only (dB)

0.36 0.33 0.71 0.49

1069 870 1903 917

0.2 0.3 0.2 0.7

632 632 881 883

DR036 / 3 Ton / Belt Drive

Vertical Ducted Discharge

Unitary Products Group 17

Page 18: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 5: DR048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)

TABLE 6: DR048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL

CONFIGURATION

Indoor Blower Speed (RPM)

Blower Static Pressure (IWG)

Airflow (CFM)

Blower Motor BHP

63 74 97 74 95 77 90 77 90

125 70 86 69 86 73 78 72 77

250 53 58 52 57 60 61 58 61

500 49 55 47 54 54 56 51 53

1000 42 42 38 39 50 55 45 45

2000 40 44 38 43 48 51 45 46

4000 38 44 36 41 48 52 43 45

8000 42 43 42 44 45 48 44 45

DR048 / 4 Ton / Belt Drive

Horizontal Ducted Inlet

766 769 1077 1087

0.2 0.5 0.4 1.0

1.24 0.90

1484 993 2270 1406

Cooling

Operation2

(dB)

ID Blower

Only (dB)

0.67 0.54

Cooling

Operation2

(dB)

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2. Cooling Operation – ID blower, compressor and outdoor fan operating.

3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

Cooling

Operation2

(dB)

ID Blower

Only (dB)

Cooling

Operation2

(dB)

ID Blower

Only (dB)Octave Center Freq.

ID Blower

Only (dB)

4. Test duct termination is flush with reverberation room wall.

5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

UNIT DESCRIPTION / MODEL

CONFIGURATION

Indoor Blower Speed (RPM)

Blower Static Pressure (IWG)

Airflow (CFM)

Blower Motor BHP

63 77 97 75 95 84 91 82 91

125 72 86 69 85 81 83 78 80

250 60 62 57 59 71 71 66 67

500 53 56 49 54 60 61 55 56

1000 47 47 42 43 58 59 52 52

2000 45 46 40 43 54 55 50 50

4000 46 47 40 42 57 58 52 52

8000 47 47 45 45 54 54 48 49

DR048 / 4 Ton / Belt Drive

Horizontal Ducted Discharge

766 769 1077 1087

0.2 0.5 0.4 1.0

1484 993 2270 1406

0.67 0.54 1.24 0.90

Cooling

Operation2

(dB)

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

Cooling

Operation2

(dB)

ID Blower

Only (dB)

Cooling

Operation2

(dB)

ID Blower

Only (dB)Octave Center Freq.

ID Blower

Only (dB)

4. Test duct termination is flush with reverberation room wall.

5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

2. Cooling Operation – ID blower, compressor and outdoor fan operating.

3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

Cooling

Operation2

(dB)

ID Blower

Only (dB)

18 Unitary Products Group

Page 19: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 7: DR048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)

TABLE 8: DR048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)

Unitary Products Group 19

Page 20: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 9: DR060 & 072 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)

TABLE 10: DR060 & 072 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL

CONFIGURATION

Indoor Blower Speed (RPM)

Blower Static Pressure (IWG)

Airflow (CFM)

Blower Motor BHP

63 82 87 79 88 88 89 82 87

125 75 76 72 74 82 83 78 78

250 69 69 66 66 79 79 73 73

500 64 64 60 60 72 72 66 66

1000 59 60 55 56 68 68 61 61

2000 55 55 50 50 65 65 57 57

4000 58 58 52 52 68 68 60 60

8000 55 55 49 49 66 67 56 56

Cooling

Operation2

(dB)

ID Blower

Only (dB)Octave Center Freq.

ID Blower

Only (dB)

Cooling

Operation2

(dB)

ID Blower

Only (dB)

0.6

1100

Cooling

Operation2

(dB)

ID Blower

Only (dB)

DR060 & 072 / 5 & 6 Ton / Belt Drive

Horizontal Ducted Discharge

840 845 1166 1188

0.80

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

0.50

0.3

2618

1.51

Cooling

Operation2

(dB)

0.2

1695

0.67

2. Cooling Operation – ID blower, compressor and outdoor fan operating.

3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

4. Test duct termination is flush with reverberation room wall.

5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

1.3

1323

20 Unitary Products Group

Page 21: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 11: DR060 & 072 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)

TABLE 12: DR060 & 072 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL

CONFIGURATION

Indoor Blower Speed (RPM)

Blower Static Pressure (IWG)

Airflow (CFM)

Blower Motor BHP

63 77 86 79 88 81 86 83 87

125 69 70 70 72 71 73 72 72

250 56 63 56 58 64 72 63 69

500 50 52 48 49 57 59 53 56

1000 48 51 44 45 57 58 49 52

2000 43 47 39 41 54 57 47 50

4000 47 49 40 41 55 61 47 52

8000 46 47 44 45 51 57 47 49

DR060 & 072 / 5 & 6 Ton / Belt Drive

Vertical Ducted Inlet

834 840 1171 1194

0.2 0.6 0.2 1.3

1525 1019 2624 1256

0.61 0.44 1.43 0.83

Octave Center Freq.ID Blower

Only (dB)

Cooling

Operation2

(dB)

ID Blower

Only (dB)

4. Test duct termination is flush with reverberation room wall.

5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

Cooling

Operation2

(dB)

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2. Cooling Operation – ID blower, compressor and outdoor fan operating.

3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

Cooling

Operation2

(dB)

ID Blower

Only (dB)

Cooling

Operation2

(dB)

ID Blower

Only (dB)

UNIT DESCRIPTION / MODEL

CONFIGURATION

Indoor Blower Speed (RPM)

Blower Static Pressure (IWG)

Airflow (CFM)

Blower Motor BHP

63 83 88 82 88 91 91 85 88

125 78 78 75 76 85 85 79 79

250 66 67 62 62 77 78 70 72

500 59 60 54 54 70 70 61 61

1000 57 58 51 51 68 68 57 58

2000 51 52 45 45 62 63 52 53

4000 54 54 47 47 65 66 55 56

8000 52 52 46 47 65 66 52 53

DR060 & 072 / 5 & 6 Ton / Belt Drive

Vertical Ducted Discharge

834 840 1171 1194

0.2 0.6 0.2 1.3

1525 1019 2624 1256

0.61 0.44 1.43 0.83

Cooling

Operation2

(dB)

ID Blower

Only (dB)Octave Center Freq.

ID Blower

Only (dB)

Cooling

Operation2

(dB)

ID Blower

Only (dB)

4. Test duct termination is flush with reverberation room wall.

5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

Cooling

Operation2

(dB)

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2. Cooling Operation – ID blower, compressor and outdoor fan operating.

3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

Cooling

Operation2

(dB)

ID Blower

Only (dB)

Unitary Products Group 21

Page 22: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 13: CAPACITY RATINGS

UNITSIZE

(MBH)

COOLING PERFORMANCE SOUND RATING3

MBH SEER4 EER5 DECIBELSDR036 36.01 13.01

1. Certified in accordance with the Unitary Small Equip-ment certification program, which is based on ARI Stan-dard 210/240.

11.5 84

DR048 45.51 13.01 11.5 83

DR060 56.51 13.01 11.5 81

DR072 70.02

2. Certified in accordance with the Unitary Large Equip-ment certification program, which is based on ARI Stan-dard 340/360.

3. Rated in accordance with ARI Standard 270.4. SEER = Seasonal Energy Efficiency Ratio - the total

cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.

5. EER = Energy Efficiency Ratio - the cooling capacity in BTU’s per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt (BTUH/watt).

- 10.42 84

TABLE 14: GAS HEAT RATINGS1

1. All units are single-stage heating.

MODEL MBH INPUT

MBH OUTPUT

AFUE (%)

TEMP RISE ºF

DR036N04DR036N08

50100

4079

80.980.5

15 - 4540 - 70

DR048N06DR048N10

75125

5999

80.980.3

25 - 5545 - 75

DR060N08DR060N10

100125

7999

80.580.3

25 - 5535 - 65

DR072N08DR072N10

100125

7999

80.580.3

25 - 5535 - 65

22 Unitary Products Group

Page 23: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 15: DR036 COOLING CAPACITIES (3 TON) - NORMAL MODE

Air on Evap-orator Coil

Temperature of Air on Condenser Coil75°F 85°F

CFM WB(°F)

TotalCap.1(MBH)

Total2

Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

TotalCap.*(MBH)

Total†Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

86 83 80 77 74 71 68 86 83 80 77 74 71 68

90072 49.0 2.3 24.5 22.4 20.3 18.2 16.1 - - 44.6 2.6 22.7 20.6 18.6 16.5 14.4 - -67 43.1 2.3 29.7 27.6 25.5 23.4 21.4 19.3 17.2 39.5 2.5 28.0 25.9 23.9 21.8 19.7 17.6 15.562 38.1 2.3 35.5 33.1 31.0 28.9 26.9 24.8 22.7 34.7 2.5 33.4 31.3 29.2 27.1 25.1 23.0 20.957 37.2 2.3 37.2 37.2 34.5 32.4 30.3 28.3 26.2 34.0 2.5 34.0 34.0 32.0 29.9 27.8 25.7 23.7

105072 51.1 2.3 26.9 24.5 22.1 19.7 17.3 - - 46.3 2.6 24.9 22.6 20.2 17.8 15.4 - -67 44.9 2.3 32.6 30.2 27.8 25.5 23.1 20.7 18.3 41.0 2.6 30.7 28.3 25.9 23.6 21.2 18.8 16.462 39.7 2.3 38.4 36.9 33.9 31.5 29.1 26.7 24.3 36.0 2.5 35.4 34.2 31.8 29.4 27.0 24.6 22.357 38.7 2.3 38.7 38.7 37.6 35.3 32.9 30.5 28.1 35.3 2.5 35.3 35.3 34.8 32.4 30.0 27.6 25.3

120072 53.2 2.3 29.4 26.7 24.0 21.3 18.6 - - 48.0 2.6 27.1 24.5 21.8 19.1 16.4 - -67 46.8 2.3 35.6 32.9 30.2 27.5 24.8 22.0 19.3 42.5 2.6 33.4 30.7 28.0 25.4 22.7 20.0 17.362 41.4 2.3 41.4 40.7 36.7 34.0 31.3 28.6 25.8 37.4 2.6 37.4 37.0 34.3 31.7 29.0 26.3 23.657 40.3 2.3 40.3 40.3 40.8 38.1 35.4 32.7 30.0 36.6 2.5 36.6 36.6 37.6 34.9 32.2 29.6 26.9

135072 54.4 2.4 31.5 28.5 25.5 22.5 19.5 - - 48.8 2.6 29.1 26.2 23.2 20.3 17.3 - -67 47.8 2.4 38.1 35.1 32.1 29.1 26.1 23.1 20.2 43.2 2.6 35.7 32.8 29.8 26.9 24.0 21.0 18.162 42.3 2.3 42.3 41.9 39.9 37.0 34.0 31.0 28.0 38.0 2.6 38.0 37.8 36.5 33.5 30.6 27.6 24.757 41.2 2.3 41.2 41.2 41.5 38.5 35.5 32.5 29.5 37.2 2.5 37.2 37.2 37.7 34.7 31.8 28.8 25.9

150072 55.6 2.4 33.6 30.3 27.0 23.8 20.5 - - 49.6 2.6 31.1 27.8 24.6 21.4 18.2 - -67 48.9 2.4 40.6 37.3 34.0 30.8 27.5 24.2 21.0 43.9 2.6 38.1 34.9 31.7 28.4 25.2 22.0 18.862 43.2 2.4 43.2 43.2 43.2 39.9 36.7 33.4 30.2 38.6 2.6 38.6 38.6 38.6 35.4 32.1 28.9 25.757 42.1 2.4 42.1 42.1 42.1 38.9 35.6 32.3 29.1 37.8 2.5 37.8 37.8 37.8 34.6 31.3 28.1 24.9

95°F 105°F

90072 40.1 2.8 21.0 18.9 16.8 14.7 12.6 - - 36.5 3.0 18.9 16.8 14.8 12.8 10.8 - -67 35.9 2.8 26.4 24.3 22.2 20.1 18.0 15.9 13.8 32.1 3.0 24.2 22.1 20.1 18.1 16.1 14.0 12.062 31.3 2.7 31.3 29.5 27.4 25.3 23.2 21.2 19.1 28.3 2.9 28.3 27.4 25.4 23.4 21.4 19.3 17.357 30.8 2.7 30.8 30.8 29.5 27.4 25.3 23.2 21.1 27.5 2.9 27.5 27.5 26.9 24.8 22.8 20.8 18.8

105072 41.5 2.8 22.9 20.6 18.2 15.8 13.5 - - 37.4 3.0 20.7 18.4 16.1 13.8 11.5 - -67 37.1 2.8 28.8 26.4 24.0 21.7 19.3 16.9 14.6 32.9 3.0 26.4 24.1 21.8 19.5 17.2 14.9 12.662 32.3 2.7 32.3 31.4 29.7 27.3 25.0 22.6 20.2 29.0 2.9 29.0 28.5 27.6 25.3 22.9 20.6 18.357 31.8 2.7 31.8 31.8 31.9 29.6 27.2 24.8 22.5 28.2 2.9 28.2 28.2 29.5 26.5 24.9 22.6 20.3

120072 42.8 2.8 24.9 22.3 19.6 17.0 14.3 - - 38.2 3.1 22.5 19.9 17.3 14.7 12.2 - -67 38.3 2.8 31.2 28.5 25.9 23.2 20.6 18.0 15.3 33.6 3.0 28.7 26.1 23.5 20.9 18.3 15.7 13.262 33.4 2.8 33.4 33.4 32.0 29.3 26.7 24.1 21.4 29.6 3.0 29.6 29.6 29.7 27.1 24.5 21.9 19.457 32.9 2.7 32.9 32.9 34.4 31.7 29.1 26.5 23.8 28.8 2.9 28.8 28.8 32.2 28.2 26.9 24.4 21.8

135072 43.2 2.8 26.7 23.8 20.9 18.0 15.1 - - 38.4 3.1 24.1 21.3 18.5 15.7 12.8 - -67 38.6 2.8 33.4 30.5 27.6 24.7 21.8 18.9 16.0 33.8 3.0 30.5 27.9 25.1 22.3 19.4 16.6 13.862 33.7 2.8 33.7 33.7 33.0 30.1 27.1 24.2 21.3 29.8 3.0 29.8 29.8 29.8 27.0 24.1 21.3 18.557 33.2 2.7 33.2 33.2 33.9 31.0 28.1 25.2 22.3 28.9 2.9 28.9 28.9 30.6 27.1 24.9 22.1 19.3

150072 43.6 2.8 28.6 25.4 22.2 19.0 15.9 - - 38.5 3.1 25.8 22.7 19.7 16.6 13.5 - -67 39.0 2.8 35.6 32.5 29.3 26.1 22.9 19.8 16.6 33.9 3.0 32.3 29.7 26.7 23.6 20.5 17.5 14.462 33.9 2.8 33.9 33.9 33.9 30.8 27.6 24.4 21.2 29.9 3.0 29.9 29.9 29.9 26.8 23.8 20.7 17.657 33.4 2.7 33.4 33.4 33.4 30.3 27.1 23.9 20.7 29.1 2.9 29.1 29.1 29.1 26.0 22.9 19.9 16.8

115°F 125°F

90072 32.9 3.2 16.8 14.8 12.8 10.9 8.9 - - 29.3 3.5 14.7 12.8 10.9 9.0 7.1 - -67 28.4 3.2 22.0 20.0 18.0 16.1 14.1 12.1 10.2 24.7 3.4 19.8 17.9 16.0 14.1 12.2 10.3 8.462 25.4 3.1 25.4 25.4 23.4 21.4 19.5 17.5 15.6 22.5 3.3 22.5 22.5 21.4 19.5 17.6 15.7 13.857 24.2 3.1 24.2 24.2 24.2 22.3 20.3 18.4 16.4 21.0 3.3 21.0 21.0 21.0 19.7 17.8 15.9 14.0

105072 33.3 3.3 18.4 16.2 13.9 11.7 9.4 - - 29.2 3.5 16.2 14.0 11.8 9.6 7.4 - -67 28.7 3.2 24.1 21.8 19.6 17.3 15.1 12.8 10.6 24.5 3.4 21.7 19.5 17.3 15.2 13.0 10.8 8.662 25.7 3.1 25.7 25.6 25.4 23.2 20.9 18.7 16.4 22.3 3.3 22.3 22.3 22.3 21.1 18.9 16.7 14.557 24.5 3.1 24.5 24.5 27.1 23.5 22.5 20.4 18.1 20.8 3.3 20.8 20.8 20.8 20.5 20.2 18.1 16.0

120072 33.6 3.3 20.1 17.6 15.0 12.5 10.0 - - 29.0 3.5 17.7 15.2 12.7 10.3 7.8 - -67 29.0 3.2 26.2 23.6 21.1 18.6 16.1 13.5 11.0 24.4 3.4 23.7 21.2 18.7 16.3 13.8 11.3 8.862 25.9 3.2 25.9 25.9 27.4 24.9 22.3 19.8 17.3 22.2 3.4 22.2 22.2 22.2 22.2 20.2 17.7 15.257 24.8 3.1 24.8 24.8 30.0 24.8 24.8 22.4 19.9 20.7 3.3 20.7 20.7 20.7 20.7 20.7 20.4 17.9

135072 33.6 3.3 21.6 18.8 16.1 13.3 10.6 - - 28.8 3.5 19.0 16.3 13.7 11.0 8.3 - -67 29.0 3.2 27.5 25.3 22.6 19.8 17.1 14.4 11.6 24.1 3.4 24.1 22.7 20.1 17.4 14.8 12.1 9.462 25.9 3.2 25.9 25.9 26.6 23.9 21.1 18.4 15.7 22.0 3.4 22.0 22.0 22.0 20.8 18.1 15.5 12.857 24.7 3.1 24.7 24.7 27.3 23.2 21.8 19.1 16.4 20.5 3.3 20.5 20.5 20.5 19.4 18.6 16.1 13.4

150072 33.5 3.3 23.0 20.1 17.1 14.2 11.2 - - 28.5 3.6 20.3 17.4 14.6 11.7 8.9 - -67 28.9 3.2 28.9 27.0 24.0 21.1 18.1 15.2 12.2 23.9 3.5 23.9 23.9 21.4 18.6 15.7 12.9 10.062 25.8 3.2 25.8 25.8 25.8 22.9 19.9 17.0 14.0 21.8 3.4 21.8 21.8 21.8 18.9 16.1 13.3 10.457 24.7 3.2 24.7 24.7 24.7 21.7 18.8 15.8 12.8 20.3 3.4 20.3 20.3 20.3 17.4 14.6 11.7 8.9

1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-mance table for the kW of the supply air blower motor.

2. These ratings include the condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

Unitary Products Group 23

Page 24: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 16: DR036 COOLING CAPACITIES (3 TON) - REHEAT MODE

Air on Evap-orator Coil

Temperature of Air on Condenser Coil75°F 85°F

CFM WB(°F)

TotalCap.1(MBH)

Total2

Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

TotalCap.*(MBH)

Total†Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

86 83 80 77 74 71 68 86 83 80 77 74 71 68

90072 36.2 2.2 15.4 14.6 13.7 12.8 12.0 - - 32.3 2.4 14.6 13.7 12.8 11.9 11.0 - -67 29.7 2.3 17.1 16.2 15.3 14.5 13.6 12.8 11.9 27.3 2.4 16.9 16.0 15.1 14.2 13.3 12.4 11.562 28.8 2.1 20.4 19.5 18.7 17.8 17.0 16.1 15.3 25.4 2.3 20.0 19.1 18.2 17.3 16.4 15.6 14.757 26.9 2.2 26.9 26.9 26.0 25.1 24.3 23.4 22.6 23.5 2.3 23.5 23.5 23.0 22.1 21.2 20.3 19.4

105072 37.0 2.3 16.8 15.9 14.9 13.9 12.9 - - 33.1 2.5 15.3 14.4 13.4 12.4 11.5 - -67 30.5 2.3 18.7 17.7 16.8 15.8 14.8 13.8 12.9 28.0 2.5 17.7 16.8 15.8 14.8 13.9 12.9 11.962 29.5 2.2 22.3 21.4 20.4 19.4 18.4 17.5 16.5 26.1 2.4 21.0 20.0 19.1 18.1 17.1 16.2 15.257 27.6 2.2 27.6 27.6 27.1 26.1 25.1 24.2 23.2 24.1 2.4 24.1 24.1 24.1 23.1 22.1 21.1 20.2

120072 37.9 2.3 18.3 17.2 16.1 15.0 13.9 - - 33.9 2.5 16.1 15.0 14.0 12.9 11.9 - -67 31.2 2.4 20.4 19.3 18.2 17.1 16.0 14.9 13.8 28.7 2.5 18.6 17.5 16.5 15.5 14.4 13.4 12.362 30.2 2.3 24.3 23.2 22.1 21.0 19.9 18.8 17.7 26.7 2.4 22.0 21.0 19.9 18.9 17.8 16.8 15.757 28.2 2.3 28.2 28.2 28.2 27.1 26.0 24.9 23.8 24.6 2.4 24.6 24.6 25.1 24.1 23.0 22.0 20.9

135072 40.1 2.3 19.6 18.4 17.2 16.0 14.8 - - 35.1 2.5 17.0 15.8 14.7 13.6 12.5 - -67 33.0 2.4 21.9 20.6 19.4 18.2 17.0 15.8 14.6 29.7 2.5 19.6 18.5 17.4 16.2 15.1 14.0 12.862 31.9 2.2 26.0 24.8 23.6 22.4 21.2 20.0 18.8 27.6 2.4 23.2 22.1 21.0 19.8 18.7 17.6 16.457 29.8 2.2 29.8 29.8 29.8 28.6 27.4 26.2 25.0 25.5 2.4 25.5 25.5 25.7 24.6 23.5 22.3 21.2

150072 42.2 2.2 20.9 19.6 18.3 17.0 15.6 - - 36.3 2.5 17.9 16.7 15.4 14.2 13.0 - -67 34.8 2.3 23.3 22.0 20.7 19.4 18.0 16.7 15.4 30.7 2.5 20.7 19.4 18.2 17.0 15.8 14.6 13.462 33.6 2.2 27.8 26.5 25.2 23.8 22.5 21.2 19.9 28.6 2.4 24.4 23.2 22.0 20.8 19.6 18.4 17.157 31.4 2.2 31.4 31.4 31.4 30.0 28.7 27.4 26.1 26.4 2.4 26.4 26.4 26.4 25.1 23.9 22.7 21.5

95°F 105°F

90072 28.4 2.6 13.7 12.8 11.9 11.0 10.0 - - 25.3 2.8 11.0 10.2 9.4 8.6 7.8 - -67 25.0 2.6 16.7 15.8 14.9 13.9 13.0 12.1 11.1 22.0 2.8 13.7 12.9 12.1 11.3 10.5 9.7 8.962 22.0 2.5 19.6 18.7 17.8 16.9 15.9 15.0 14.1 19.1 2.7 16.5 15.7 14.9 14.1 13.3 12.5 11.757 20.0 2.5 20.0 20.0 20.0 19.1 18.1 17.2 16.3 17.4 2.7 17.4 17.4 17.4 16.6 15.8 15.0 14.2

105072 29.2 2.7 13.8 12.8 11.9 10.9 10.0 - - 26.0 2.8 11.3 10.4 9.6 8.7 7.9 - -67 25.6 2.6 16.7 15.8 14.8 13.9 12.9 12.0 11.0 22.5 2.8 14.1 13.2 12.4 11.5 10.7 9.8 9.062 22.6 2.6 19.7 18.7 17.8 16.8 15.8 14.9 13.9 19.6 2.7 16.9 16.1 15.2 14.4 13.5 12.7 11.957 20.5 2.5 20.5 20.5 21.0 20.0 19.1 18.1 17.2 17.9 2.7 17.9 17.9 18.6 17.5 16.8 16.1 15.2

120072 30.0 2.7 13.8 12.9 11.9 10.9 9.9 - - 26.7 2.9 11.5 10.7 9.8 8.9 8.0 - -67 26.3 2.6 16.8 15.8 14.8 13.8 12.8 11.8 10.9 23.1 2.8 14.4 13.5 12.6 11.7 10.8 9.9 9.062 23.2 2.6 19.7 18.7 17.7 16.7 15.8 14.8 13.8 20.1 2.8 17.3 16.5 15.6 14.7 13.8 12.9 12.057 21.1 2.6 21.1 21.1 22.0 21.0 20.0 19.0 18.1 18.3 2.7 18.3 18.3 19.8 18.3 17.8 17.1 16.2

135072 30.1 2.7 14.3 13.3 12.2 11.2 10.1 - - 26.7 2.9 11.9 11.0 10.0 9.1 8.2 - -67 26.5 2.7 17.4 16.3 15.3 14.2 13.2 12.1 11.1 23.1 2.8 14.9 13.9 13.0 12.0 11.1 10.1 9.262 23.4 2.6 20.4 19.3 18.3 17.2 16.2 15.2 14.1 20.1 2.8 17.9 16.9 16.0 15.1 14.1 13.2 12.257 21.2 2.6 21.2 21.2 21.7 20.6 19.6 18.5 17.5 18.4 2.8 18.4 18.4 19.1 17.9 17.1 16.3 15.3

150072 30.3 2.7 14.8 13.7 12.6 11.5 10.4 - - 26.7 2.9 12.3 11.3 10.3 9.3 8.3 - -67 26.7 2.7 18.0 16.9 15.8 14.6 13.5 12.4 11.3 23.2 2.9 15.3 14.3 13.3 12.3 11.3 10.4 9.462 23.5 2.6 21.1 20.0 18.9 17.8 16.6 15.5 14.4 20.2 2.8 18.4 17.4 16.4 15.4 14.5 13.5 12.557 21.3 2.6 21.3 21.3 21.3 20.2 19.1 18.0 16.9 18.4 2.8 18.4 18.4 18.4 17.4 16.4 15.4 14.4

115°F 125°F

90072 22.2 3.0 8.3 7.6 6.9 6.2 5.6 - - 19.1 3.2 5.5 5.0 4.4 3.9 3.3 - -67 19.0 2.9 10.8 10.1 9.4 8.7 8.0 7.4 6.7 16.0 3.1 7.8 7.2 6.7 6.1 5.6 5.0 4.562 16.2 2.9 13.4 12.8 12.1 11.4 10.7 10.0 9.4 13.2 3.0 10.3 9.8 9.2 8.7 8.1 7.6 7.057 14.9 2.8 14.9 14.9 14.9 14.2 13.5 12.8 12.2 12.3 3.0 12.3 12.3 12.3 11.7 11.2 10.6 10.1

105072 22.8 3.0 8.8 8.0 7.3 6.5 5.8 - - 19.6 3.2 6.3 5.6 5.0 4.4 3.7 - -67 19.4 3.0 11.4 10.6 9.9 9.2 8.4 7.7 6.9 16.3 3.1 8.7 8.1 7.4 6.8 6.2 5.6 4.962 16.6 2.9 14.2 13.5 12.7 12.0 11.3 10.5 9.8 13.5 3.1 11.5 10.8 10.2 9.6 9.0 8.3 7.757 15.2 2.9 15.2 15.2 16.2 14.9 14.6 14.0 13.3 12.6 3.0 12.6 12.6 12.6 12.3 12.3 11.9 11.3

120072 23.4 3.1 9.3 8.5 7.7 6.9 6.1 - - 20.1 3.3 7.0 6.3 5.6 4.9 4.2 - -67 19.9 3.0 12.0 11.2 10.4 9.6 8.8 8.0 7.2 16.7 3.2 9.6 8.9 8.2 7.5 6.8 6.1 5.462 17.0 2.9 15.0 14.2 13.4 12.6 11.8 11.0 10.2 13.9 3.1 12.6 11.9 11.2 10.5 9.8 9.1 8.457 15.6 2.9 15.6 15.6 17.6 15.6 15.6 15.2 14.4 12.9 3.1 12.9 12.9 12.9 12.9 12.9 12.9 12.5

135072 23.2 3.1 9.5 8.7 7.8 7.0 6.2 - - 19.8 3.3 7.1 6.4 5.6 4.9 4.2 - -67 19.8 3.0 12.3 11.5 10.7 9.8 9.0 8.1 7.3 16.5 3.2 9.8 9.1 8.3 7.6 6.9 6.1 5.462 16.9 2.9 15.4 14.5 13.7 12.9 12.0 11.2 10.3 13.7 3.1 12.9 12.1 11.4 10.7 9.9 9.2 8.557 15.5 2.9 15.5 15.5 16.5 15.1 14.7 14.0 13.2 12.7 3.1 12.7 12.7 12.7 12.3 12.2 11.7 11.0

150072 23.1 3.1 9.8 8.9 8.0 7.1 6.3 - - 19.5 3.3 7.3 6.5 5.7 5.0 4.2 - -67 19.7 3.0 12.7 11.8 10.9 10.0 9.2 8.3 7.4 16.3 3.2 10.0 9.2 8.5 7.7 7.0 6.2 5.462 16.8 3.0 15.8 14.9 14.0 13.1 12.3 11.4 10.5 13.5 3.1 13.1 12.4 11.6 10.8 10.1 9.3 8.657 15.5 2.9 15.5 15.5 15.5 14.6 13.7 12.8 12.0 12.5 3.1 12.5 12.5 12.5 11.8 11.0 10.2 9.5

1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-mance table for the kW of the supply air blower motor.

2. These ratings include the condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

24 Unitary Products Group

Page 25: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 17: DR048 COOLING CAPACITIES (4 TON) - NORMAL MODE

Air on Evap-orator Coil

Temperature of Air on Condenser Coil75°F 85°F

CFM WB(°F)

TotalCap.1(MBH)

Total2

Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

TotalCap.*(MBH)

Total†Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

86 83 80 77 74 71 68 86 83 80 77 74 71 68

120072 57.4 2.8 33.0 30.1 27.2 24.2 21.3 - - 53.3 3.1 31.7 28.9 26.0 23.1 20.3 - -67 53.2 2.8 39.3 36.3 33.4 30.5 27.6 24.6 21.7 49.2 3.1 37.5 34.6 31.8 28.9 26.0 23.2 20.362 48.8 2.8 48.1 43.9 41.0 38.1 35.1 32.2 29.3 45.2 3.0 44.9 42.0 39.2 36.3 33.4 30.6 27.757 48.4 2.8 48.4 45.5 42.6 39.6 36.7 33.8 30.8 44.8 3.0 44.8 42.6 39.8 36.9 34.0 31.2 28.3

140072 58.5 2.8 36.3 33.0 29.6 26.3 22.9 - - 54.5 3.1 34.9 31.6 28.3 25.1 21.8 - -67 54.2 2.8 43.1 39.8 36.4 33.1 29.7 26.4 23.0 50.3 3.1 41.2 37.9 34.6 31.4 28.1 24.8 21.562 49.7 2.8 49.4 47.3 44.7 41.3 38.0 34.6 31.3 46.3 3.1 46.1 44.7 42.7 39.4 36.1 32.9 29.657 49.3 2.8 49.3 47.9 46.4 43.0 39.7 36.3 33.0 45.9 3.1 45.9 44.8 43.3 40.1 36.8 33.5 30.2

160072 59.6 2.9 39.6 35.9 32.1 28.3 24.5 - - 55.8 3.1 38.1 34.4 30.7 27.0 23.3 - -67 55.2 2.9 47.0 43.2 39.5 35.7 31.9 28.1 24.3 51.5 3.1 44.9 41.2 37.5 33.8 30.1 26.4 22.762 50.7 2.8 50.7 50.7 48.4 44.6 40.8 37.0 33.2 47.4 3.1 47.4 47.4 46.2 42.5 38.8 35.2 31.557 50.2 2.8 50.2 50.2 50.2 46.5 42.7 38.9 35.1 46.9 3.1 46.9 46.9 46.9 43.2 39.5 35.9 32.2

180072 61.7 2.8 42.3 38.2 34.1 30.0 25.9 - - 56.9 3.1 40.7 36.7 32.6 28.6 24.6 - -67 57.2 2.8 50.5 46.1 42.0 37.9 33.8 29.7 25.6 52.5 3.1 47.9 43.9 39.9 35.9 31.9 27.8 23.862 52.5 2.8 52.5 52.5 51.3 47.2 43.1 39.0 34.9 48.3 3.1 48.3 48.3 47.7 43.7 39.7 35.7 31.757 52.0 2.8 52.0 52.0 52.0 47.9 43.8 39.7 35.6 47.8 3.1 47.8 47.8 47.8 43.8 39.8 35.8 31.8

200072 63.9 2.8 45.0 40.6 36.2 31.8 27.4 - - 58.0 3.1 43.3 38.9 34.6 30.3 25.9 - -67 59.1 2.8 54.0 48.9 44.5 40.1 35.7 31.3 26.9 53.5 3.1 51.0 46.6 42.3 37.9 33.6 29.3 24.962 54.3 2.8 54.3 54.3 54.3 49.8 45.4 41.0 36.6 49.2 3.1 49.2 49.2 49.2 44.9 40.5 36.2 31.857 53.8 2.8 53.8 53.8 53.8 49.4 45.0 40.6 36.2 48.8 3.1 48.8 48.8 48.8 44.4 40.1 35.7 31.4

95°F 105°F

120072 49.1 3.4 30.5 27.7 24.8 22.0 19.2 - - 46.1 3.7 27.8 25.0 22.2 19.3 16.5 - -67 45.2 3.4 35.8 33.0 30.1 27.3 24.5 21.7 18.9 41.6 3.6 34.2 31.4 28.5 25.7 22.9 20.0 17.262 41.7 3.3 41.7 40.2 37.4 34.6 31.7 28.9 26.1 38.4 3.5 38.4 36.7 33.9 31.1 28.2 25.4 22.657 41.2 3.3 41.2 39.8 37.0 34.2 31.4 28.5 25.7 38.3 3.6 38.3 36.6 33.8 30.9 28.1 25.3 22.4

140072 50.5 3.4 33.5 30.3 27.1 23.9 20.7 - - 47.2 3.7 30.6 27.4 24.2 20.9 17.7 - -67 46.5 3.4 39.2 36.0 32.8 29.6 26.4 23.2 20.0 42.5 3.6 37.5 34.4 31.1 27.9 24.7 21.4 18.262 42.9 3.3 42.9 42.1 40.7 37.5 34.3 31.1 27.9 39.3 3.6 39.3 38.4 37.0 33.8 30.6 27.3 24.157 42.4 3.3 42.4 41.7 40.3 37.1 33.9 30.7 27.5 39.1 3.6 39.1 38.3 36.9 33.6 30.4 27.2 23.9

160072 51.9 3.4 36.5 32.9 29.3 25.7 22.1 - - 48.2 3.7 33.5 29.8 26.2 22.6 18.9 - -67 47.8 3.4 42.7 39.1 35.5 31.9 28.4 24.8 21.2 43.4 3.7 40.9 37.4 33.8 30.1 26.5 22.9 19.262 44.1 3.3 44.1 44.1 44.1 40.5 36.9 33.3 29.7 40.1 3.6 40.1 40.1 40.1 36.5 32.9 29.2 25.657 43.6 3.4 43.6 43.6 43.6 40.0 36.4 32.8 29.2 40.0 3.6 40.0 40.0 40.0 36.3 32.7 29.1 25.4

180072 52.0 3.4 39.0 35.1 31.1 27.2 23.3 - - 48.1 3.8 35.8 31.9 27.9 23.9 19.9 - -67 47.8 3.4 45.3 41.7 37.8 33.9 29.9 26.0 22.0 43.4 3.7 42.1 39.5 35.9 31.9 28.0 24.0 20.062 44.1 3.4 44.1 44.1 44.1 40.2 36.3 32.3 28.4 40.1 3.6 40.1 40.1 40.1 36.1 32.1 28.2 24.257 43.7 3.4 43.7 43.7 43.7 39.7 35.8 31.9 27.9 39.9 3.7 39.9 39.9 39.9 35.9 32.0 28.0 24.0

200072 52.1 3.5 41.6 37.3 33.0 28.7 24.5 - - 48.0 3.8 38.2 33.9 29.6 25.2 20.9 - -67 47.9 3.4 47.9 44.3 40.0 35.8 31.5 27.2 22.9 43.3 3.7 43.3 41.5 38.1 33.8 29.4 25.1 20.862 44.2 3.4 44.2 44.2 44.2 39.9 35.6 31.3 27.1 40.0 3.7 40.0 40.0 40.0 35.7 31.4 27.1 22.857 43.7 3.4 43.7 43.7 43.7 39.4 35.2 30.9 26.6 39.8 3.7 39.8 39.8 39.8 35.5 31.2 26.9 22.6

115°F 125°F

120072 43.1 4.0 25.2 22.3 19.5 16.6 13.8 - - 40.2 4.2 22.5 19.6 16.8 13.9 11.0 - -67 38.0 3.9 32.6 29.8 26.9 24.1 21.2 18.4 15.5 34.3 4.1 31.0 28.2 25.3 22.4 19.6 16.7 13.862 35.2 3.8 35.2 33.3 30.5 27.6 24.8 21.9 19.1 31.9 4.0 31.9 29.9 27.0 24.1 21.3 18.4 15.557 35.3 3.8 35.3 33.4 30.6 27.7 24.9 22.0 19.2 32.3 4.1 32.3 30.2 27.4 24.5 21.6 18.8 15.9

140072 43.8 4.0 27.8 24.6 21.3 18.0 14.8 - - 40.4 4.3 25.0 21.7 18.4 15.1 11.8 - -67 38.5 3.9 35.8 32.7 29.5 26.2 22.9 19.7 16.4 34.5 4.2 34.1 31.1 27.8 24.5 21.2 17.9 14.662 35.7 3.8 35.7 34.8 33.3 30.1 26.8 23.5 20.3 32.1 4.1 32.1 31.1 29.6 26.3 23.0 19.7 16.457 35.8 3.9 35.8 34.9 33.4 30.2 26.9 23.7 20.4 32.5 4.1 32.5 31.5 30.0 26.7 23.4 20.1 16.8

160072 44.4 4.0 30.5 26.8 23.1 19.5 15.8 - - 40.6 4.3 27.5 23.8 20.1 16.3 12.6 - -67 39.1 3.9 39.1 35.7 32.0 28.3 24.6 20.9 17.3 34.7 4.2 34.7 34.0 30.2 26.5 22.8 19.0 15.362 36.2 3.9 36.2 36.2 36.2 32.5 28.8 25.2 21.5 32.3 4.1 32.3 32.3 32.3 28.5 24.8 21.1 17.457 36.3 3.9 36.3 36.3 36.3 32.6 29.0 25.3 21.6 32.7 4.2 32.7 32.7 32.7 29.0 25.2 21.5 17.8

180072 44.2 4.1 32.6 28.6 24.6 20.6 16.6 - - 40.3 4.4 29.4 25.4 21.3 17.3 13.3 - -67 38.9 4.0 38.9 37.2 34.0 30.0 26.0 22.0 18.0 34.4 4.3 34.4 34.4 32.2 28.1 24.1 20.0 16.062 36.0 3.9 36.0 36.0 36.0 32.0 28.0 24.0 20.0 32.0 4.2 32.0 32.0 32.0 27.9 23.9 19.8 15.857 36.2 3.9 36.2 36.2 36.2 32.1 28.1 24.1 20.1 32.4 4.2 32.4 32.4 32.4 28.4 24.3 20.3 16.2

200072 44.0 4.1 34.8 30.4 26.1 21.8 17.4 - - 39.9 4.5 31.4 27.0 22.6 18.3 13.9 - -67 38.7 4.0 38.7 38.7 36.1 31.7 27.4 23.1 18.7 34.1 4.3 34.1 34.1 34.1 29.7 25.4 21.0 16.662 35.8 4.0 35.8 35.8 35.8 31.5 27.2 22.8 18.5 31.7 4.2 31.7 31.7 31.7 27.3 22.9 18.6 14.257 36.0 4.0 36.0 36.0 36.0 31.6 27.3 23.0 18.6 32.1 4.3 32.1 32.1 32.1 27.7 23.4 19.0 14.6

1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-mance table for the kW of the supply air blower motor.

2. These ratings include the condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

Unitary Products Group 25

Page 26: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 18: DR048 COOLING CAPACITIES (4 TON) - REHEAT MODE

Air on Evap-orator Coil

Temperature of Air on Condenser Coil75°F 85°F

CFM WB(°F)

TotalCap.1(MBH)

Total2

Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

TotalCap.*(MBH)

Total†Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

86 83 80 77 74 71 68 86 83 80 77 74 71 68

120072 41.4 2.8 18.5 17.3 16.0 14.7 13.5 - - 39.0 3.0 17.8 16.6 15.4 14.1 12.9 - -67 37.6 2.7 24.2 22.9 21.7 20.4 19.1 17.9 16.6 35.1 2.9 22.7 21.5 20.3 19.0 17.8 16.6 15.462 33.8 2.7 26.7 25.5 24.2 22.9 21.7 20.4 19.1 31.8 2.9 25.9 24.7 23.4 22.2 21.0 19.8 18.557 30.4 2.6 30.4 29.3 28.0 26.8 25.5 24.3 23.0 28.9 2.8 28.9 28.3 27.1 25.8 24.6 23.4 22.2

140072 43.7 2.8 20.4 19.0 17.6 16.2 14.8 - - 40.8 3.0 19.4 18.0 16.7 15.3 13.9 - -67 39.6 2.7 26.7 25.2 23.8 22.4 21.0 19.6 18.1 36.7 2.9 24.7 23.3 22.0 20.6 19.2 17.8 16.562 35.6 2.7 29.5 28.0 26.6 25.2 23.8 22.4 20.9 33.3 2.9 28.2 26.8 25.4 24.0 22.7 21.3 19.957 32.0 2.7 32.0 31.5 30.9 29.4 28.0 26.6 25.2 30.3 2.8 30.3 29.9 29.3 28.0 26.6 25.2 23.8

160072 45.9 2.8 22.4 20.8 19.2 17.6 16.0 - - 42.6 3.1 21.0 19.5 17.9 16.4 14.9 - -67 41.7 2.7 29.1 27.6 26.0 24.4 22.8 21.2 19.6 38.4 3.0 26.7 25.2 23.7 22.1 20.6 19.1 17.562 37.4 2.7 32.2 30.6 29.1 27.5 25.9 24.3 22.7 34.8 2.9 30.5 28.9 27.4 25.9 24.3 22.8 21.357 33.7 2.7 33.7 33.7 33.7 32.1 30.5 28.9 27.4 31.6 2.9 31.6 31.6 31.6 30.1 28.5 27.0 25.5

180072 47.4 2.8 23.1 21.4 19.7 18.0 16.3 - - 43.9 3.1 21.9 20.3 18.6 17.0 15.4 - -67 43.0 2.8 30.1 28.3 26.6 24.9 23.2 21.5 19.8 39.5 3.0 27.9 26.2 24.6 23.0 21.3 19.7 18.062 38.7 2.7 33.2 31.5 29.8 28.1 26.4 24.7 23.0 35.8 3.0 31.8 30.1 28.5 26.8 25.2 23.5 21.957 34.8 2.7 34.8 34.8 34.8 33.1 31.4 29.7 28.0 32.5 2.9 32.5 32.5 32.5 30.9 29.2 27.6 25.9

200072 48.9 2.9 23.8 22.0 20.2 18.3 16.5 - - 45.1 3.1 22.9 21.1 19.3 17.6 15.8 - -67 44.4 2.8 31.0 29.1 27.3 25.5 23.6 21.8 20.0 40.6 3.0 29.0 27.3 25.5 23.8 22.0 20.2 18.562 39.9 2.8 34.1 32.3 30.5 28.7 26.8 25.0 23.2 36.8 3.0 33.0 31.3 29.5 27.8 26.0 24.3 22.557 35.9 2.7 35.9 35.9 35.9 34.1 32.3 30.4 28.6 33.4 2.9 33.4 33.4 33.4 31.7 29.9 28.2 26.4

95°F 105°F

120072 36.6 3.2 17.1 15.9 14.7 13.5 12.3 - - 33.4 3.4 15.4 14.3 13.2 12.0 10.9 - -67 32.6 3.1 21.2 20.0 18.9 17.7 16.5 15.3 14.1 30.0 3.3 19.5 18.4 17.3 16.1 15.0 13.9 12.762 29.9 3.1 25.1 23.9 22.7 21.5 20.3 19.1 18.0 27.1 3.2 23.2 22.0 20.9 19.8 18.6 17.5 16.457 27.5 3.0 27.5 27.2 26.1 24.9 23.7 22.5 21.3 25.6 3.2 25.6 25.0 23.9 22.8 21.6 20.5 19.4

140072 38.0 3.3 18.4 17.0 15.7 14.4 13.0 - - 34.7 3.5 16.7 15.4 14.1 12.9 11.6 - -67 33.8 3.2 22.8 21.4 20.1 18.8 17.4 16.1 14.8 31.2 3.4 21.1 19.8 18.6 17.3 16.0 14.7 13.562 31.1 3.1 26.9 25.5 24.2 22.9 21.5 20.2 18.9 28.2 3.3 25.1 23.8 22.5 21.2 19.9 18.7 17.457 28.5 3.0 28.5 28.4 27.8 26.5 25.1 23.8 22.5 26.6 3.2 26.6 26.3 25.7 24.4 23.2 21.9 20.6

160072 39.3 3.3 19.6 18.2 16.7 15.2 13.7 - - 36.0 3.5 18.0 16.6 15.1 13.7 12.3 - -67 35.1 3.2 24.3 22.8 21.4 19.9 18.4 16.9 15.4 32.3 3.4 22.7 21.3 19.9 18.5 17.0 15.6 14.262 32.2 3.1 28.7 27.2 25.7 24.2 22.8 21.3 19.8 29.2 3.3 26.9 25.5 24.1 22.7 21.3 19.8 18.457 29.5 3.1 29.5 29.5 29.5 28.1 26.6 25.1 23.6 27.5 3.3 27.5 27.5 27.5 26.1 24.7 23.3 21.8

180072 40.3 3.3 20.8 19.2 17.6 16.0 14.4 - - 36.7 3.6 19.1 17.6 16.0 14.5 13.0 - -67 35.9 3.2 25.7 24.1 22.6 21.0 19.4 17.8 16.2 33.0 3.4 24.1 22.6 21.1 19.5 18.0 16.5 14.962 33.0 3.2 30.3 28.7 27.1 25.6 24.0 22.4 20.8 29.8 3.4 28.2 27.0 25.5 24.0 22.5 20.9 19.457 30.2 3.1 30.2 30.2 30.2 28.7 27.1 25.5 23.9 28.1 3.3 28.1 28.1 28.1 26.5 25.0 23.5 21.9

200072 41.2 3.4 21.9 20.2 18.5 16.8 15.2 - - 37.3 3.6 20.2 18.6 16.9 15.3 13.7 - -67 36.8 3.3 27.1 25.4 23.7 22.1 20.4 18.7 17.0 33.6 3.5 25.5 23.9 22.2 20.6 19.0 17.3 15.762 33.7 3.2 32.0 30.3 28.6 26.9 25.2 23.5 21.8 30.4 3.4 29.5 28.6 26.9 25.3 23.7 22.0 20.457 30.9 3.1 30.9 30.9 30.9 29.3 27.6 25.9 24.2 28.6 3.3 28.6 28.6 28.6 27.0 25.3 23.7 22.1

115°F 125°F

120072 30.2 3.7 13.7 12.7 11.6 10.5 9.4 - - 27.0 3.9 12.1 11.0 10.0 9.0 8.0 - -67 27.4 3.5 17.8 16.7 15.7 14.6 13.5 12.4 11.4 24.8 3.7 16.1 15.1 14.1 13.0 12.0 11.0 10.062 24.3 3.4 21.3 20.2 19.1 18.0 17.0 15.9 14.8 21.5 3.6 19.4 18.4 17.3 16.3 15.3 14.3 13.257 23.7 3.4 23.7 22.8 21.7 20.6 19.6 18.5 17.4 21.8 3.6 21.8 20.6 19.6 18.5 17.5 16.5 15.5

140072 31.4 3.7 15.0 13.8 12.6 11.4 10.2 - - 28.1 3.9 13.4 12.2 11.1 9.9 8.7 - -67 28.5 3.6 19.5 18.3 17.0 15.8 14.6 13.4 12.1 25.8 3.8 17.8 16.7 15.5 14.3 13.2 12.0 10.862 25.3 3.5 23.2 22.0 20.8 19.6 18.4 17.1 15.9 22.4 3.7 21.4 20.3 19.1 17.9 16.8 15.6 14.457 24.6 3.4 24.6 24.2 23.6 22.4 21.2 20.0 18.7 22.7 3.6 22.7 22.1 21.6 20.4 19.2 18.1 16.9

160072 32.6 3.8 16.4 15.0 13.6 12.3 10.9 - - 29.2 4.0 14.7 13.4 12.1 10.8 9.5 - -67 29.6 3.6 21.1 19.8 18.4 17.0 15.7 14.3 12.9 26.9 3.9 19.5 18.2 16.9 15.6 14.3 13.0 11.762 26.3 3.5 25.2 23.8 22.5 21.1 19.8 18.4 17.0 23.3 3.7 23.3 22.2 20.9 19.6 18.3 16.9 15.657 25.5 3.5 25.5 25.5 25.5 24.2 22.8 21.4 20.1 23.5 3.7 23.5 23.5 23.5 22.2 20.9 19.6 18.3

180072 33.0 3.8 17.4 15.9 14.5 13.0 11.5 - - 29.4 4.0 15.7 14.3 12.9 11.5 10.1 - -67 30.0 3.7 22.5 21.0 19.6 18.1 16.6 15.1 13.7 27.0 3.9 20.9 19.5 18.1 16.6 15.2 13.8 12.462 26.6 3.5 26.1 25.4 23.9 22.4 20.9 19.5 18.0 23.5 3.7 23.5 23.5 22.3 20.8 19.4 18.0 16.657 25.9 3.5 25.9 25.9 25.9 24.4 22.9 21.5 20.0 23.7 3.7 23.7 23.7 23.7 22.3 20.9 19.5 18.1

200072 33.5 3.8 18.5 16.9 15.3 13.7 12.2 - - 29.6 4.0 16.7 15.2 13.7 12.2 10.7 - -67 30.4 3.7 23.9 22.3 20.7 19.1 17.5 16.0 14.4 27.2 3.9 22.2 20.7 19.2 17.7 16.1 14.6 13.162 27.0 3.6 27.0 26.9 25.3 23.7 22.1 20.5 19.0 23.6 3.7 23.6 23.6 23.6 22.1 20.6 19.1 17.557 26.2 3.5 26.2 26.2 26.2 24.7 23.1 21.5 19.9 23.9 3.7 23.9 23.9 23.9 22.4 20.8 19.3 17.8

1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-mance table for the kW of the supply air blower motor.

2. These ratings include the condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

26 Unitary Products Group

Page 27: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 19: DR060 COOLING CAPACITIES (5 TON) - NORMAL MODE

Air on Evap-orator Coil

Temperature of Air on Condenser Coil75°F 85°F

CFM WB(°F)

TotalCap.1(MBH)

Total2

Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

TotalCap.*(MBH)

Total†Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

86 83 80 77 74 71 68 86 83 80 77 74 71 68

150072 68.8 3.4 38.3 34.9 31.6 28.3 24.9 - - 65.9 3.8 36.7 33.4 30.0 26.7 23.3 - -67 63.4 3.4 47.2 43.9 40.6 37.2 33.9 30.6 27.2 60.3 3.8 45.8 42.4 39.1 35.8 32.4 29.1 25.762 57.5 3.3 57.0 52.9 49.6 46.3 42.9 39.6 36.3 54.9 3.8 54.7 51.3 48.0 44.6 41.3 37.9 34.657 56.0 3.3 56.0 56.0 54.4 51.1 47.7 44.4 41.0 53.7 3.7 53.7 53.7 51.8 48.4 45.1 41.7 38.4

175072 70.4 3.4 40.8 36.9 33.0 29.2 25.3 - - 67.2 3.9 39.1 35.2 31.4 27.5 23.7 - -67 64.9 3.4 50.1 46.2 42.4 38.5 34.7 30.8 26.9 61.6 3.8 48.5 44.7 40.9 37.0 33.2 29.3 25.562 58.8 3.3 58.6 56.0 51.8 48.0 44.1 40.3 36.4 56.1 3.8 55.9 54.0 50.1 46.3 42.5 38.6 34.857 57.3 3.3 57.3 57.3 56.8 53.0 49.1 45.3 41.4 54.9 3.8 54.9 54.9 54.1 50.2 46.4 42.6 38.7

200072 71.9 3.4 43.2 38.8 34.4 30.1 25.7 - - 68.6 3.9 41.4 37.1 32.7 28.4 24.1 - -67 66.3 3.4 53.0 48.6 44.2 39.8 35.4 31.1 26.7 62.9 3.8 51.3 47.0 42.6 38.3 33.9 29.6 25.362 60.2 3.3 60.2 59.0 54.1 49.7 45.3 40.9 36.5 57.2 3.8 57.2 56.6 52.3 48.0 43.6 39.3 34.957 58.6 3.3 58.6 58.6 59.3 54.9 50.5 46.1 41.7 56.0 3.8 56.0 56.0 56.4 52.1 47.7 43.4 39.1

225072 73.5 3.4 47.2 42.5 37.9 33.2 28.6 - - 70.2 3.9 45.2 40.6 36.0 31.3 26.7 - -67 67.8 3.4 57.9 53.2 48.6 43.9 39.3 34.7 30.0 64.3 3.8 56.1 51.5 46.8 42.2 37.6 32.9 28.362 61.5 3.3 61.5 60.9 58.4 53.8 49.1 44.5 39.9 58.5 3.8 58.5 58.2 56.0 51.4 46.8 42.2 37.557 59.9 3.3 59.9 59.9 60.3 55.6 51.0 46.3 41.7 57.2 3.8 57.2 57.2 57.5 52.8 48.2 43.6 38.9

250072 75.1 3.5 51.1 46.2 41.3 36.4 31.5 - - 71.7 3.9 49.0 44.1 39.2 34.3 29.4 - -67 69.3 3.4 62.8 57.9 53.0 48.1 43.1 38.2 33.3 65.7 3.8 60.9 55.9 51.0 46.1 41.2 36.3 31.462 62.8 3.3 62.8 62.8 62.8 57.9 53.0 48.1 43.2 59.8 3.8 59.8 59.8 59.8 54.9 49.9 45.0 40.157 61.2 3.3 61.2 61.2 61.2 56.3 51.4 46.5 41.6 58.5 3.8 58.5 58.5 58.5 53.6 48.6 43.7 38.8

95°F 105°F

150072 63.0 4.3 35.1 31.8 28.4 25.1 21.7 - - 59.5 4.8 33.7 30.4 27.1 23.8 20.5 - -67 57.3 4.2 44.3 41.0 37.6 34.3 30.9 27.6 24.2 53.8 4.7 42.8 39.5 36.1 32.8 29.5 26.2 22.962 52.4 4.2 52.4 49.7 46.3 43.0 39.6 36.3 32.9 49.5 4.7 49.5 48.1 45.2 41.9 38.6 35.2 31.957 51.4 4.2 51.4 51.4 49.1 45.8 42.4 39.1 35.7 48.8 4.7 48.8 48.8 46.8 43.4 40.1 36.8 33.5

175072 64.1 4.3 37.4 33.6 29.7 25.9 22.1 - - 60.4 4.8 35.8 32.0 28.2 24.4 20.7 - -67 58.3 4.2 47.0 43.2 39.3 35.5 31.7 27.8 24.0 54.7 4.8 45.2 41.4 37.6 33.9 30.1 26.3 22.562 53.3 4.2 53.3 52.0 48.4 44.6 40.8 37.0 33.1 50.3 4.7 50.3 49.6 47.1 43.3 39.5 35.8 32.057 52.4 4.2 52.4 52.4 51.4 47.5 43.7 39.9 36.0 49.6 4.7 49.6 49.6 48.7 44.9 41.2 37.4 33.6

200072 65.3 4.3 39.6 35.3 31.0 26.7 22.4 - - 61.4 4.8 37.8 33.6 29.4 25.1 20.9 - -67 59.4 4.3 49.6 45.3 41.0 36.7 32.4 28.1 23.8 55.5 4.8 47.6 43.4 39.1 34.9 30.7 26.5 22.262 54.3 4.2 54.3 54.3 50.5 46.2 41.9 37.6 33.3 51.0 4.7 51.0 51.0 49.0 44.7 40.5 36.3 32.057 53.3 4.2 53.3 53.3 53.6 49.3 45.0 40.7 36.4 50.4 4.7 50.4 50.4 50.6 46.4 42.2 38.0 33.7

225072 66.8 4.3 43.3 38.7 34.1 29.5 24.8 - - 62.7 4.8 41.4 36.9 32.3 27.8 23.3 - -67 60.7 4.3 54.3 49.7 45.1 40.4 35.8 31.2 26.6 56.7 4.8 52.0 47.7 43.1 38.6 34.0 29.5 25.062 55.5 4.2 55.5 55.5 53.6 49.0 44.4 39.8 35.2 52.1 4.7 52.1 52.1 51.1 46.5 42.0 37.5 32.957 54.5 4.2 54.5 54.5 54.6 50.0 45.4 40.8 36.2 51.5 4.7 51.5 51.5 51.6 47.1 42.5 38.0 33.4

250072 68.3 4.3 47.0 42.0 37.1 32.2 27.3 - - 64.0 4.8 45.0 40.2 35.3 30.5 25.6 - -67 62.1 4.3 58.9 54.0 49.1 44.2 39.2 34.3 29.4 57.9 4.8 56.3 51.9 47.1 42.2 37.4 32.5 27.762 56.7 4.2 56.7 56.7 56.7 51.8 46.9 42.0 37.0 53.2 4.7 53.2 53.2 53.2 48.4 43.5 38.7 33.857 55.7 4.2 55.7 55.7 55.7 50.8 45.9 40.9 36.0 52.6 4.7 52.6 52.6 52.6 47.7 42.8 38.0 33.1

115°F 125°F

150072 56.0 5.3 32.3 29.0 25.7 22.5 19.2 - - 52.5 5.9 30.9 27.6 24.4 21.1 17.9 - -67 50.4 5.3 41.2 37.9 34.6 31.4 28.1 24.8 21.5 46.9 5.8 39.7 36.4 33.2 29.9 26.6 23.4 20.162 46.6 5.2 46.6 46.6 44.0 40.8 37.5 34.2 30.9 43.7 5.7 43.7 43.7 42.9 39.6 36.4 33.1 29.957 46.3 5.2 46.3 46.3 44.4 41.1 37.8 34.5 31.2 43.7 5.7 43.7 43.7 42.0 38.7 35.5 32.2 29.0

175072 56.7 5.3 34.2 30.4 26.7 23.0 19.3 - - 53.0 5.9 32.5 28.9 25.2 21.5 17.9 - -67 51.0 5.3 43.4 39.7 35.9 32.2 28.5 24.8 21.1 47.4 5.8 41.6 37.9 34.3 30.6 26.9 23.3 19.662 47.2 5.2 47.2 47.2 45.7 42.0 38.3 34.5 30.8 44.1 5.7 44.1 44.1 44.1 40.7 37.0 33.3 29.757 46.9 5.2 46.9 46.9 46.0 42.3 38.6 34.9 31.2 44.1 5.7 44.1 44.1 43.4 39.7 36.1 32.4 28.7

200072 57.4 5.3 36.0 31.8 27.7 23.5 19.4 - - 53.5 5.9 34.2 30.1 26.0 21.9 17.9 - -67 51.7 5.3 45.6 41.4 37.3 33.1 28.9 24.8 20.6 47.8 5.8 43.5 39.4 35.4 31.3 27.2 23.1 19.062 47.8 5.2 47.8 47.8 47.4 43.2 39.1 34.9 30.7 44.5 5.7 44.5 44.5 44.5 41.7 37.6 33.5 29.557 47.5 5.2 47.5 47.5 47.7 43.6 39.4 35.3 31.1 44.6 5.8 44.6 44.6 44.6 40.7 36.6 32.6 28.5

225072 58.6 5.4 39.5 35.1 30.6 26.1 21.7 - - 54.5 5.9 37.7 33.3 28.9 24.5 20.1 - -67 52.7 5.3 49.7 45.6 41.2 36.7 32.2 27.8 23.3 48.7 5.8 47.3 43.6 39.2 34.8 30.4 26.0 21.762 48.8 5.2 48.8 48.8 48.5 44.1 39.6 35.1 30.7 45.4 5.8 45.4 45.4 45.4 41.6 37.2 32.8 28.457 48.4 5.2 48.4 48.4 48.6 44.1 39.6 35.2 30.7 45.4 5.8 45.4 45.4 45.4 41.1 36.7 32.3 27.9

250072 59.7 5.4 43.1 38.3 33.5 28.7 23.9 - - 55.5 5.9 41.1 36.4 31.7 27.0 22.3 - -67 53.7 5.3 53.7 49.9 45.1 40.3 35.5 30.8 26.0 49.6 5.8 49.6 47.8 43.1 38.4 33.7 29.0 24.362 49.7 5.3 49.7 49.7 49.7 44.9 40.2 35.4 30.6 46.2 5.8 46.2 46.2 46.2 41.5 36.8 32.1 27.457 49.4 5.3 49.4 49.4 49.4 44.6 39.8 35.1 30.3 46.2 5.8 46.2 46.2 46.2 41.5 36.8 32.1 27.4

1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-mance table for the kW of the supply air blower motor.

2. These ratings include the condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

Unitary Products Group 27

Page 28: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 20: DR060 COOLING CAPACITIES (5 TON) - REHEAT MODE

Air on Evap-orator Coil

Temperature of Air on Condenser Coil75°F 85°F

CFM WB(°F)

TotalCap.1(MBH)

Total2

Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

TotalCap.*(MBH)

Total†Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

86 83 80 77 74 71 68 86 83 80 77 74 71 68

150072 49.3 3.4 35.4 33.4 31.3 29.3 27.3 - - 46.1 3.7 27.8 26.2 24.6 23.0 21.3 - -67 45.3 3.3 42.0 40.0 38.0 35.9 33.9 31.9 29.9 42.2 3.7 33.2 31.6 30.0 28.4 26.7 25.1 23.562 40.9 3.3 47.9 46.4 44.3 42.3 40.3 38.3 36.2 38.3 3.7 38.3 36.9 35.3 33.6 32.0 30.4 28.857 36.1 3.2 36.1 36.7 38.0 35.9 33.9 31.9 29.9 34.6 3.6 34.6 34.6 34.6 33.0 31.4 29.8 28.1

175072 49.9 3.3 30.4 28.5 26.7 24.9 23.1 - - 47.2 3.7 25.9 24.2 22.6 21.0 19.4 - -67 45.9 3.3 36.0 34.2 32.3 30.5 28.7 26.8 25.0 43.1 3.7 30.8 29.2 27.6 26.0 24.4 22.8 21.262 41.4 3.2 41.1 39.5 37.7 35.9 34.0 32.2 30.4 39.2 3.7 35.6 34.1 32.5 30.9 29.2 27.6 26.057 36.6 3.2 36.6 36.9 37.1 35.2 33.4 31.6 29.7 35.4 3.6 35.4 35.4 34.8 33.2 31.6 30.0 28.4

200072 50.6 3.3 25.4 23.7 22.1 20.5 18.8 - - 48.2 3.7 23.9 22.3 20.7 19.1 17.5 - -67 46.5 3.2 30.0 28.3 26.7 25.0 23.4 21.8 20.1 44.1 3.7 28.4 26.8 25.2 23.6 22.0 20.4 18.862 41.9 3.2 34.3 32.7 31.0 29.4 27.8 26.1 24.5 40.0 3.7 32.9 31.3 29.7 28.1 26.5 24.9 23.357 37.0 3.1 37.0 37.1 36.2 34.5 32.9 31.3 29.6 36.2 3.6 36.2 36.2 35.0 33.4 31.8 30.2 28.6

225072 52.3 3.3 26.9 25.2 23.5 21.8 20.1 - - 50.0 3.7 25.4 23.7 22.1 20.4 18.8 - -67 48.1 3.2 31.8 30.1 28.4 26.7 25.0 23.3 21.6 45.7 3.7 30.3 28.6 26.9 25.3 23.6 22.0 20.362 43.4 3.2 36.4 34.7 33.0 31.3 29.6 28.0 26.3 41.5 3.7 35.0 33.3 31.7 30.0 28.4 26.7 25.157 38.3 3.1 38.3 38.3 37.9 36.2 34.5 32.8 31.1 37.5 3.6 37.5 37.5 36.9 35.3 33.6 32.0 30.3

250072 54.1 3.3 28.4 26.7 24.9 23.2 21.4 - - 51.7 3.7 26.9 25.2 23.5 21.8 20.1 - -67 49.7 3.2 33.6 31.8 30.1 28.3 26.6 24.9 23.1 47.3 3.7 32.1 30.4 28.7 26.9 25.2 23.5 21.862 44.9 3.2 38.5 36.7 35.0 33.3 31.5 29.8 28.0 42.9 3.7 37.1 35.4 33.7 32.0 30.3 28.6 26.957 39.5 3.1 39.5 39.5 39.5 37.8 36.1 34.3 32.6 38.9 3.6 38.9 38.9 38.9 37.1 35.4 33.7 32.0

95°F 105°F

150072 42.9 4.1 20.3 19.1 17.8 16.6 15.4 - - 40.6 4.7 18.8 17.6 16.4 15.2 14.1 - -67 39.0 4.1 24.5 23.2 22.0 20.8 19.5 18.3 17.1 36.8 4.7 23.0 21.8 20.6 19.4 18.2 17.1 15.962 35.7 4.1 28.7 27.4 26.2 25.0 23.7 22.5 21.3 33.7 4.6 27.1 25.9 24.7 23.5 22.4 21.2 20.057 33.2 4.1 33.2 32.5 31.3 30.1 28.9 27.6 26.4 31.3 4.6 31.3 30.6 29.4 28.2 27.1 25.9 24.7

175072 44.4 4.1 21.3 19.9 18.5 17.2 15.8 - - 41.9 4.7 19.7 18.4 17.1 15.7 14.4 - -67 40.4 4.1 25.7 24.3 22.9 21.5 20.1 18.7 17.3 37.9 4.7 24.1 22.7 21.4 20.1 18.7 17.4 16.162 36.9 4.1 30.0 28.6 27.2 25.9 24.5 23.1 21.7 34.7 4.6 28.4 27.0 25.7 24.4 23.0 21.7 20.357 34.3 4.1 34.3 34.0 32.6 31.2 29.8 28.4 27.0 32.2 4.6 32.2 31.9 30.6 29.3 27.9 26.6 25.2

200072 45.9 4.1 22.4 20.8 19.3 17.7 16.2 - - 43.1 4.7 20.7 19.2 17.7 16.2 14.7 - -67 41.7 4.1 26.9 25.3 23.8 22.2 20.7 19.1 17.6 39.0 4.7 25.2 23.7 22.2 20.7 19.2 17.7 16.362 38.1 4.1 31.4 29.8 28.3 26.7 25.2 23.6 22.1 35.8 4.6 29.6 28.2 26.7 25.2 23.7 22.2 20.757 35.4 4.1 35.4 35.4 33.8 32.3 30.7 29.2 27.6 33.2 4.6 33.2 33.2 31.7 30.3 28.8 27.3 25.8

225072 47.6 4.2 23.9 22.3 20.7 19.0 17.4 - - 44.7 4.7 22.1 20.6 19.0 17.5 15.9 - -67 43.3 4.1 28.7 27.1 25.5 23.9 22.3 20.6 19.0 40.4 4.7 27.0 25.4 23.9 22.3 20.8 19.2 17.762 39.6 4.1 33.6 32.0 30.4 28.7 27.1 25.5 23.9 37.1 4.6 31.8 30.2 28.7 27.1 25.5 24.0 22.457 36.8 4.1 36.8 36.8 36.0 34.4 32.7 31.1 29.5 34.4 4.6 34.4 34.4 33.7 32.1 30.6 29.0 27.4

250072 49.4 4.2 25.5 23.8 22.1 20.4 18.7 - - 46.2 4.7 23.6 22.0 20.3 18.7 17.1 - -67 44.9 4.2 30.6 28.9 27.2 25.6 23.9 22.2 20.5 41.8 4.7 28.8 27.1 25.5 23.9 22.3 20.7 19.162 41.0 4.1 35.8 34.1 32.4 30.7 29.1 27.4 25.7 38.3 4.6 33.9 32.3 30.6 29.0 27.4 25.8 24.257 38.2 4.1 38.2 38.2 38.2 36.5 34.8 33.1 31.4 35.6 4.6 35.6 35.6 35.6 34.0 32.3 30.7 29.1

115°F 125°F

150072 38.3 5.2 17.3 16.1 15.0 13.9 12.7 - - 36.0 5.8 15.7 14.7 13.6 12.5 11.4 - -67 34.5 5.2 21.4 20.3 19.2 18.1 16.9 15.8 14.7 32.3 5.7 19.9 18.9 17.8 16.7 15.6 14.5 13.462 31.7 5.1 25.5 24.4 23.2 22.1 21.0 19.8 18.7 29.7 5.6 23.9 22.8 21.7 20.7 19.6 18.5 17.457 29.3 5.2 29.3 28.7 27.5 26.4 25.3 24.2 23.0 27.4 5.7 27.4 26.7 25.7 24.6 23.5 22.4 21.3

175072 39.3 5.2 18.1 16.9 15.6 14.3 13.0 - - 36.8 5.8 16.5 15.3 14.1 12.9 11.6 - -67 35.5 5.2 22.5 21.2 19.9 18.6 17.4 16.1 14.8 33.0 5.7 20.9 19.7 18.5 17.2 16.0 14.8 13.562 32.6 5.1 26.7 25.4 24.1 22.8 21.6 20.3 19.0 30.4 5.6 25.0 23.8 22.6 21.3 20.1 18.9 17.757 30.1 5.2 30.1 29.8 28.6 27.3 26.1 24.8 23.5 28.1 5.7 28.1 27.7 26.6 25.4 24.2 23.0 21.7

200072 40.4 5.2 19.0 17.6 16.2 14.7 13.3 - - 37.6 5.8 17.3 16.0 14.6 13.2 11.9 - -67 36.4 5.2 23.5 22.1 20.7 19.2 17.8 16.4 14.9 33.7 5.7 21.9 20.5 19.1 17.8 16.4 15.0 13.662 33.4 5.1 27.9 26.5 25.0 23.6 22.2 20.7 19.3 31.1 5.6 26.1 24.8 23.4 22.0 20.7 19.3 17.957 31.0 5.2 31.0 31.0 29.7 28.3 26.8 25.4 24.0 28.7 5.7 28.7 28.7 27.6 26.2 24.9 23.5 22.1

225072 41.7 5.2 20.4 18.9 17.4 15.9 14.4 - - 38.8 5.8 18.6 17.2 15.7 14.3 12.9 - -67 37.6 5.2 25.2 23.7 22.2 20.8 19.3 17.8 16.3 34.7 5.7 23.5 22.0 20.6 19.2 17.8 16.3 14.962 34.5 5.1 29.9 28.4 26.9 25.4 24.0 22.5 21.0 32.0 5.6 28.1 26.6 25.2 23.8 22.4 21.0 19.557 32.0 5.2 32.0 32.0 31.3 29.8 28.4 26.9 25.4 29.6 5.7 29.6 29.6 29.0 27.6 26.2 24.7 23.3

250072 43.0 5.2 21.7 20.2 18.6 17.1 15.5 - - 39.9 5.8 19.8 18.4 16.9 15.4 13.9 - -67 38.8 5.2 26.9 25.4 23.8 22.3 20.7 19.2 17.6 35.8 5.7 25.1 23.6 22.1 20.6 19.2 17.7 16.262 35.6 5.1 31.9 30.4 28.8 27.3 25.7 24.2 22.7 32.9 5.6 30.0 28.5 27.0 25.6 24.1 22.6 21.157 33.0 5.2 33.0 33.0 33.0 31.4 29.9 28.4 26.8 30.4 5.7 30.4 30.4 30.4 28.9 27.5 26.0 24.5

1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-mance table for the kW of the supply air blower motor.

2. These ratings include the condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

28 Unitary Products Group

Page 29: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 21: DR072 COOLING CAPACITIES (6 TON) - NORMAL MODE

Air on Evap-orator Coil

Temperature of Air on Condenser Coil75°F 85°F

CFM WB(°F)

TotalCap.1(MBH)

Total2

Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

TotalCap.*(MBH)

Total†Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

86 83 80 77 74 71 68 86 83 80 77 74 71 68

180072 84.4 4.8 45.5 41.9 38.3 34.6 31.0 - - 79.9 5.3 43.6 40.0 36.4 32.8 29.2 - -67 76.3 4.6 55.3 51.7 48.1 44.4 40.8 37.2 33.6 72.8 5.1 53.6 50.1 46.5 42.9 39.3 35.7 32.262 69.0 4.5 66.0 62.4 58.7 55.1 51.5 47.9 44.2 65.5 5.0 63.9 60.3 56.7 53.1 49.6 46.0 42.457 67.6 4.4 67.6 67.6 63.7 60.1 56.4 52.8 49.2 64.7 5.0 64.7 64.7 61.2 57.6 54.0 50.4 46.8

210072 87.4 4.8 48.7 44.6 40.4 36.3 32.2 - - 82.5 5.3 46.6 42.5 38.4 34.3 30.2 - -67 79.0 4.6 59.0 54.9 50.8 46.6 42.5 38.4 34.3 75.2 5.1 57.2 53.1 49.1 45.0 40.9 36.8 32.762 71.4 4.5 69.9 66.2 62.0 57.9 53.8 49.7 45.5 67.7 5.0 66.9 63.9 59.9 55.8 51.7 47.6 43.557 70.0 4.5 70.0 70.0 67.3 63.1 59.0 54.9 50.7 66.8 5.0 66.8 66.8 64.6 60.5 56.4 52.3 48.2

240072 90.3 4.8 51.8 47.2 42.6 37.9 33.3 - - 85.1 5.3 49.6 45.0 40.4 35.8 31.3 - -67 81.6 4.6 62.7 58.1 53.5 48.8 44.2 39.6 34.9 77.6 5.2 60.8 56.2 51.6 47.0 42.5 37.9 33.362 73.8 4.5 73.8 70.0 65.3 60.7 56.1 51.4 46.8 69.8 5.0 69.8 67.6 63.0 58.4 53.9 49.3 44.757 72.3 4.5 72.3 72.3 70.8 66.2 61.6 56.9 52.3 68.9 5.0 68.9 68.9 67.9 63.4 58.8 54.2 49.6

270072 92.1 4.8 55.0 49.9 44.8 39.8 34.7 - - 86.5 5.3 52.5 47.5 42.5 37.4 32.4 - -67 83.3 4.7 66.5 61.4 56.3 51.3 46.2 41.1 36.1 78.9 5.2 64.3 59.2 54.2 49.2 44.2 39.2 34.162 75.2 4.5 75.2 73.3 68.8 63.8 58.7 53.6 48.6 71.0 5.1 71.0 69.9 66.2 61.2 56.1 51.1 46.157 73.8 4.5 73.8 73.8 73.0 68.0 62.9 57.8 52.7 70.1 5.0 70.1 70.1 69.6 64.6 59.6 54.5 49.5

300072 93.9 4.8 58.1 52.6 47.1 41.6 36.1 - - 88.0 5.3 55.4 49.9 44.5 39.0 33.6 - -67 84.9 4.7 70.2 64.7 59.2 53.7 48.2 42.7 37.2 80.2 5.2 67.7 62.3 56.8 51.4 45.9 40.4 35.062 76.7 4.5 76.7 76.7 72.3 66.8 61.3 55.8 50.3 72.2 5.1 72.2 72.2 69.3 63.9 58.4 53.0 47.557 75.2 4.5 75.2 75.2 75.2 69.7 64.2 58.7 53.2 71.2 5.1 71.2 71.2 71.2 65.8 60.3 54.9 49.4

95°F 105°F

180072 75.3 5.8 41.6 38.0 34.5 31.0 27.4 - - 70.4 6.5 39.9 36.3 32.8 29.2 25.7 - -67 69.4 5.6 52.0 48.4 44.9 41.3 37.8 34.3 30.7 64.8 6.3 50.2 46.7 43.1 39.6 36.0 32.5 28.962 62.1 5.5 61.8 58.2 54.7 51.2 47.6 44.1 40.6 57.9 6.2 57.7 55.9 52.7 49.1 45.6 42.0 38.557 61.7 5.5 61.7 61.7 58.7 55.1 51.6 48.0 44.5 57.8 6.2 57.8 57.8 55.9 52.4 48.8 45.3 41.7

210072 77.6 5.8 44.4 40.4 36.4 32.4 28.3 - - 72.8 6.5 42.6 38.6 34.5 30.5 26.4 - -67 71.5 5.7 55.4 51.4 47.3 43.3 39.3 35.2 31.2 67.1 6.3 53.5 49.5 45.4 41.4 37.3 33.3 29.362 64.0 5.6 63.9 61.7 57.7 53.7 49.6 45.6 41.6 59.9 6.2 59.8 58.7 55.5 51.4 47.4 43.3 39.357 63.6 5.5 63.6 63.6 61.9 57.8 53.8 49.8 45.7 59.8 6.2 59.8 59.8 58.9 54.9 50.8 46.8 42.7

240072 79.9 5.8 47.3 42.8 38.3 33.7 29.2 - - 75.3 6.5 45.4 40.8 36.3 31.7 27.2 - -67 73.6 5.7 58.8 54.3 49.8 45.3 40.7 36.2 31.7 69.4 6.3 56.8 52.3 47.7 43.2 38.7 34.1 29.662 65.9 5.6 65.9 65.2 60.7 56.1 51.6 47.1 42.6 61.9 6.2 61.9 61.5 58.3 53.7 49.2 44.7 40.157 65.5 5.6 65.5 65.5 65.0 60.5 56.0 51.5 47.0 61.9 6.2 61.9 61.9 61.9 57.3 52.8 48.2 43.7

270072 81.0 5.8 50.0 45.0 40.1 35.1 30.1 - - 75.9 6.5 47.9 42.9 37.9 32.9 27.9 - -67 74.6 5.7 62.0 57.1 52.1 47.1 42.2 37.2 32.2 69.9 6.4 59.9 54.9 49.9 44.9 39.9 34.9 29.962 66.8 5.6 66.8 66.4 63.5 58.5 53.6 48.6 43.6 62.4 6.3 62.4 62.2 60.2 55.3 50.3 45.3 40.357 66.4 5.6 66.4 66.4 66.2 61.2 56.2 51.3 46.3 62.3 6.3 62.3 62.3 62.4 57.4 52.4 47.4 42.4

300072 82.0 5.8 52.7 47.3 41.8 36.4 31.0 - - 76.5 6.6 50.4 45.0 39.5 34.1 28.7 - -67 75.6 5.7 65.3 59.8 54.4 49.0 43.6 38.2 32.8 70.5 6.4 62.9 57.5 52.0 46.6 41.2 35.7 30.362 67.7 5.6 67.7 67.7 66.3 60.9 55.5 50.1 44.7 62.9 6.3 62.9 62.9 62.2 56.8 51.3 45.9 40.557 67.3 5.6 67.3 67.3 67.3 61.8 56.4 51.0 45.6 62.8 6.3 62.8 62.8 62.8 57.4 52.0 46.5 41.1

115°F 125°F

180072 65.4 7.2 38.2 34.6 31.1 27.5 23.9 - - 60.5 7.9 36.5 32.9 29.3 25.8 22.2 - -67 60.3 7.0 48.5 45.0 41.4 37.8 34.3 30.7 27.2 55.7 7.7 46.8 43.3 39.7 36.1 32.5 28.9 25.462 53.6 6.9 53.6 53.6 50.7 47.1 43.5 40.0 36.4 49.3 7.6 49.3 49.3 48.6 45.0 41.5 37.9 34.357 53.9 6.9 53.9 53.9 53.2 49.6 46.1 42.5 38.9 50.0 7.6 50.0 50.0 50.0 46.9 43.3 39.7 36.2

210072 68.1 7.2 40.8 36.7 32.7 28.6 24.5 - - 63.3 7.9 39.0 34.9 30.8 26.7 22.6 - -67 62.7 7.0 51.7 47.6 43.6 39.5 35.4 31.4 27.3 58.3 7.7 49.9 45.8 41.7 37.6 33.5 29.4 25.362 55.7 6.9 55.7 55.7 53.3 49.2 45.1 41.1 37.0 51.6 7.6 51.6 51.6 51.1 47.0 42.9 38.8 34.757 56.0 6.9 56.0 56.0 56.0 51.9 47.8 43.8 39.7 52.3 7.6 52.3 52.3 52.3 48.9 44.8 40.7 36.7

240072 70.7 7.2 43.4 38.9 34.3 29.7 25.1 - - 66.1 7.9 41.5 36.9 32.3 27.7 23.1 - -67 65.1 7.0 54.9 50.3 45.7 41.1 36.6 32.0 27.4 60.9 7.6 52.9 48.3 43.7 39.1 34.5 29.9 25.362 57.9 6.9 57.9 57.9 55.9 51.3 46.8 42.2 37.6 53.9 7.6 53.9 53.9 53.6 49.0 44.3 39.7 35.157 58.2 6.9 58.2 58.2 58.7 54.2 49.6 45.0 40.4 54.6 7.6 54.6 54.6 54.6 51.0 46.4 41.8 37.2

270072 70.8 7.2 45.8 40.8 35.8 30.7 25.7 - - 65.7 7.9 43.7 38.7 33.6 28.6 23.5 - -67 65.2 7.1 57.7 52.7 47.7 42.7 37.7 32.6 27.6 60.5 7.7 55.6 50.5 45.5 40.4 35.4 30.3 25.362 58.0 7.0 58.0 58.0 57.0 52.0 47.0 41.9 36.9 53.6 7.6 53.6 53.6 53.6 48.7 43.7 38.6 33.657 58.3 6.9 58.3 58.3 58.6 53.5 48.5 43.5 38.5 54.3 7.6 54.3 54.3 54.3 49.7 44.7 39.6 34.6

300072 70.9 7.3 48.1 42.7 37.2 31.8 26.3 - - 65.4 8.0 45.9 40.4 34.9 29.5 24.0 - -67 65.3 7.1 60.6 55.1 49.6 44.2 38.7 33.3 27.8 60.2 7.8 58.2 52.7 47.3 41.8 36.3 30.8 25.362 58.1 7.0 58.1 58.1 58.1 52.6 47.2 41.7 36.2 53.2 7.7 53.2 53.2 53.2 48.4 43.0 37.5 32.057 58.4 7.0 58.4 58.4 58.4 52.9 47.5 42.0 36.6 53.9 7.7 53.9 53.9 53.9 48.5 43.0 37.5 32.0

1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-mance table for the kW of the supply air blower motor.

2. These ratings include the condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

Unitary Products Group 29

Page 30: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 22: DR072 COOLING CAPACITIES (6 TON) - REHEAT MODE

Air on Evap-orator Coil

Temperature of Air on Condenser Coil75°F 85°F

CFM WB(°F)

TotalCap.1(MBH)

Total2

Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

TotalCap.*(MBH)

Total†Input(kW)

Sensible Capacity (MBH)*Return Dry Bulb (°F)

86 83 80 77 74 71 68 86 83 80 77 74 71 68

180072 57.6 4.3 27.1 25.6 24.2 22.8 21.4 - - 55.3 4.9 25.7 24.2 22.8 21.4 20.0 - -67 53.4 4.2 33.2 31.8 30.3 28.9 27.5 26.1 24.6 51.1 4.8 31.8 30.3 28.9 27.5 26.1 24.7 23.262 47.4 4.2 37.8 36.4 34.9 33.5 32.1 30.7 29.2 45.9 4.7 36.4 35.0 33.5 32.1 30.7 29.3 27.957 44.6 4.1 41.0 39.6 38.2 36.8 35.3 33.9 32.5 39.4 4.6 36.8 35.4 34.0 32.6 31.1 29.7 28.3

210072 61.1 4.3 29.0 27.4 25.9 24.3 22.7 - - 58.6 4.9 27.5 25.9 24.4 22.8 21.3 - -67 56.7 4.3 35.6 34.0 32.4 30.8 29.2 27.7 26.1 54.1 4.8 34.0 32.5 30.9 29.3 27.8 26.2 24.762 50.3 4.2 40.5 38.9 37.3 35.7 34.1 32.6 31.0 48.7 4.7 39.0 37.4 35.8 34.3 32.7 31.2 29.657 47.3 4.1 43.9 42.4 40.8 39.2 37.6 36.0 34.5 41.8 4.6 39.4 37.9 36.3 34.8 33.2 31.6 30.1

240072 64.6 4.4 31.0 29.2 27.5 25.8 24.0 - - 61.9 4.9 29.4 27.7 25.9 24.2 22.5 - -67 60.0 4.3 37.9 36.2 34.5 32.7 31.0 29.3 27.5 57.2 4.9 36.3 34.6 32.9 31.2 29.5 27.8 26.162 53.2 4.2 43.2 41.4 39.7 37.9 36.2 34.5 32.7 51.4 4.8 41.6 39.9 38.2 36.4 34.7 33.0 31.357 50.0 4.1 46.9 45.1 43.4 41.6 39.9 38.2 36.4 44.1 4.7 42.1 40.4 38.7 37.0 35.2 33.5 31.8

270072 65.5 4.4 31.6 29.7 27.8 25.9 24.0 - - 62.8 5.0 30.0 28.1 26.2 24.3 22.4 - -67 60.8 4.3 38.7 36.8 34.9 32.9 31.0 29.1 27.2 58.0 4.9 37.0 35.1 33.2 31.3 29.4 27.5 25.662 54.0 4.2 44.0 42.0 40.1 38.2 36.3 34.4 32.5 52.1 4.8 42.3 40.4 38.5 36.6 34.7 32.8 30.957 50.7 4.1 47.7 45.8 43.8 41.9 40.0 38.1 36.2 44.8 4.7 42.8 40.9 39.0 37.1 35.2 33.3 31.4

300072 66.4 4.4 32.3 30.2 28.1 26.0 23.9 - - 63.7 5.0 30.6 28.5 26.4 24.3 22.2 - -67 61.6 4.3 39.4 37.3 35.2 33.1 31.0 29.0 26.9 58.8 4.9 37.6 35.5 33.5 31.4 29.3 27.2 25.262 54.7 4.3 44.7 42.7 40.6 38.5 36.4 34.3 32.2 52.9 4.8 43.0 40.9 38.8 36.7 34.7 32.6 30.557 51.4 4.2 48.5 46.4 44.3 42.2 40.1 38.0 35.9 45.4 4.7 43.5 41.4 39.3 37.3 35.2 33.1 31.0

95°F 105°F

180072 53.0 5.4 24.3 22.8 21.4 20.0 18.6 - - 50.3 6.0 22.6 21.2 19.8 18.5 17.1 - -67 48.7 5.3 30.3 28.9 27.5 26.1 24.7 23.2 21.8 46.3 5.9 28.8 27.4 26.0 24.6 23.3 21.9 20.562 44.4 5.2 35.0 33.6 32.2 30.7 29.3 27.9 26.5 41.6 5.8 33.2 31.9 30.5 29.1 27.7 26.3 24.957 34.2 5.1 32.6 31.2 29.8 28.4 27.0 25.6 24.1 35.4 5.7 34.6 33.3 32.0 30.6 29.2 27.8 26.4

210072 56.1 5.5 26.0 24.5 22.9 21.4 19.8 - - 53.2 6.1 24.3 22.8 21.2 19.7 18.2 - -67 51.6 5.4 32.5 30.9 29.4 27.9 26.3 24.8 23.2 49.0 6.0 30.9 29.4 27.9 26.3 24.8 23.3 21.862 47.0 5.2 37.5 35.9 34.4 32.8 31.3 29.8 28.2 43.9 5.9 35.6 34.1 32.6 31.1 29.6 28.1 26.657 36.2 5.1 35.0 33.4 31.9 30.3 28.8 27.2 25.7 37.4 5.7 36.8 35.7 34.2 32.7 31.2 29.7 28.2

240072 59.2 5.5 27.7 26.1 24.4 22.7 21.1 - - 56.1 6.2 25.9 24.3 22.6 21.0 19.4 - -67 54.5 5.4 34.7 33.0 31.3 29.6 28.0 26.3 24.6 51.6 6.1 33.0 31.3 29.7 28.1 26.4 24.8 23.162 49.6 5.3 40.0 38.3 36.6 34.9 33.3 31.6 29.9 46.3 5.9 38.0 36.4 34.8 33.1 31.5 29.9 28.257 38.2 5.2 37.3 35.6 33.9 32.3 30.6 28.9 27.2 39.5 5.8 39.0 38.1 36.5 34.8 33.2 31.6 29.9

270072 60.1 5.5 28.3 26.4 24.5 22.7 20.8 - - 56.8 6.2 26.4 24.5 22.7 20.9 19.0 - -67 55.2 5.4 35.2 33.4 31.5 29.6 27.8 25.9 24.0 52.2 6.1 33.4 31.6 29.8 27.9 26.1 24.3 22.462 50.3 5.3 40.6 38.7 36.8 35.0 33.1 31.2 29.4 46.9 5.9 38.5 36.7 34.8 33.0 31.2 29.3 27.557 38.8 5.2 37.9 36.0 34.1 32.3 30.4 28.6 26.7 39.9 5.8 39.5 38.4 36.5 34.7 32.9 31.0 29.2

300072 60.9 5.6 28.8 26.8 24.7 22.6 20.6 - - 57.4 6.2 26.8 24.8 22.7 20.7 18.7 - -67 56.0 5.5 35.8 33.8 31.7 29.6 27.6 25.5 23.5 52.8 6.1 33.9 31.9 29.8 27.8 25.8 23.7 21.762 51.0 5.3 41.2 39.1 37.1 35.0 33.0 30.9 28.8 47.4 5.9 39.0 37.0 34.9 32.9 30.9 28.8 26.857 39.3 5.2 38.5 36.4 34.4 32.3 30.2 28.2 26.1 40.4 5.8 39.9 38.6 36.6 34.6 32.5 30.5 28.5

115°F 125°F

180072 47.7 6.7 21.0 19.6 18.3 16.9 15.5 - - 45.0 7.3 19.3 18.0 16.7 15.4 14.0 - -67 43.8 6.6 27.3 25.9 24.6 23.2 21.8 20.5 19.1 41.4 7.3 25.7 24.4 23.1 21.8 20.4 19.1 17.862 38.7 6.4 31.5 30.1 28.8 27.4 26.1 24.7 23.4 35.9 7.0 29.8 28.4 27.1 25.8 24.5 23.1 21.857 36.6 6.2 36.6 35.5 34.1 32.8 31.4 30.0 28.7 37.8 6.8 37.8 37.6 36.3 34.9 33.6 32.3 31.0

210072 50.3 6.7 22.5 21.1 19.6 18.1 16.6 - - 47.5 7.4 20.8 19.4 17.9 16.5 15.0 - -67 46.3 6.7 29.3 27.8 26.3 24.8 23.4 21.9 20.4 43.6 7.3 27.7 26.2 24.8 23.3 21.9 20.4 19.062 40.9 6.5 33.8 32.3 30.9 29.4 27.9 26.4 24.9 37.8 7.1 32.0 30.5 29.1 27.6 26.2 24.7 23.357 38.7 6.3 38.7 38.0 36.6 35.1 33.6 32.1 30.6 39.9 6.9 39.9 39.9 38.9 37.5 36.0 34.6 33.1

240072 53.0 6.8 24.1 22.5 20.9 19.3 17.7 - - 49.9 7.5 22.3 20.7 19.1 17.6 16.0 - -67 48.7 6.8 31.3 29.7 28.1 26.5 24.9 23.3 21.7 45.9 7.4 29.6 28.0 26.5 24.9 23.3 21.8 20.262 43.0 6.6 36.1 34.5 32.9 31.3 29.7 28.1 26.5 39.7 7.2 34.2 32.6 31.1 29.5 27.9 26.4 24.857 40.7 6.4 40.7 40.6 39.0 37.4 35.8 34.2 32.6 42.0 7.0 42.0 42.0 41.6 40.0 38.4 36.8 35.3

270072 53.4 6.8 24.4 22.6 20.8 19.0 17.2 - - 50.1 7.4 22.5 20.8 19.0 17.2 15.4 - -67 49.2 6.7 31.6 29.8 28.0 26.2 24.4 22.6 20.8 46.1 7.4 29.8 28.0 26.3 24.5 22.7 21.0 19.262 43.4 6.6 36.5 34.7 32.9 31.0 29.2 27.4 25.6 39.9 7.2 34.4 32.6 30.9 29.1 27.3 25.5 23.857 41.1 6.4 41.1 40.7 38.9 37.1 35.3 33.5 31.7 42.2 7.0 42.2 42.2 41.3 39.6 37.8 36.0 34.2

300072 53.9 6.8 24.8 22.8 20.8 18.8 16.8 - - 50.4 7.4 22.8 20.8 18.8 16.9 14.9 - -67 49.6 6.7 32.0 30.0 28.0 26.0 24.0 22.0 20.0 46.3 7.4 30.0 28.0 26.1 24.1 22.1 20.2 18.262 43.8 6.5 36.8 34.8 32.8 30.8 28.8 26.8 24.8 40.1 7.1 34.6 32.6 30.6 28.7 26.7 24.7 22.857 41.4 6.4 41.4 40.8 38.8 36.8 34.8 32.8 30.8 42.5 6.9 42.5 42.5 41.1 39.1 37.1 35.2 33.2

1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-mance table for the kW of the supply air blower motor.

2. These ratings include the condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

30 Unitary Products Group

Page 31: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

FIGURE 2 - DR036 MOISTURE REMOVAL - REHEAT MODE

FIGURE 3 - DR048 MOISTURE REMOVAL - REHEAT MODE

DR036 Moisture Removal @ 1200 cfm

Reheat Mode @ Various

Indoor (dry bulb / wet bulb) Conditions

0

5

10

15

20

25

65 75 85 95 105Outdoor Temperature (ºF)

Mo

istu

re R

em

oval R

ate

(lb

s W

ate

r/H

ou

r)

75db/71wb 80db/71wb 75db/67wb

85db/71wb 80db/67wb 85db/67wb

DR048 Moisture Removal @ 1600 cfm

Reheat Mode @ Various

Indoor (dry bulb / wet bulb) Conditions

0

5

10

15

20

25

30

65 75 85 95 105Outdoor Temperature (ºF)

Mo

istu

re R

em

oval R

ate

(lb

s W

ate

r/H

ou

r)

75db/71wb 80db/71wb 75db/67wb

85db/71wb 80db/67wb 85db/67wb

Unitary Products Group 31

Page 32: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

FIGURE 4 - DR060 MOISTURE REMOVAL - REHEAT MODE

FIGURE 5 - DR072 MOISTURE REMOVAL - REHEAT MODE

DR060 Moisture Removal @ 2000 cfm

Reheat Mode @ Various

Indoor (dry bulb / wet bulb) Conditions

0

5

10

15

20

25

30

35

65 75 85 95 105Outdoor Temperature (ºF)

Mo

istu

re R

em

oval R

ate

(lb

s W

ate

r/H

ou

r)

75db/71wb 80db/71wb 75db/67wb

85db/71wb 80db/67wb 85db/67wb

DR072 Moisture Removal @ 2400 cfm

Reheat Mode @ Various

Indoor (dry bulb / wet bulb) Conditions

0

5

10

15

20

25

30

35

40

65 75 85 95 105Outdoor Temperature (ºF)

Mo

istu

re R

em

oval R

ate

(lb

s W

ate

r/H

ou

r)

75db/71wb 80db/71wb 75db/67wb

85db/71wb 80db/67wb 85db/67wb

32 Unitary Products Group

Page 33: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 23: SUPPLY AIR BLOWER PERFORMANCE (DR036 BELT DRIVE) - SIDE DUCT APPLICATION

AIRFLOWCFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG1

0.2 0.3 0.4 0.5 0.6RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

800 ---- ---- ---- ---- ---- ---- 696 357 0.38 743 389 0.42 786 422 0.45900 ---- ---- ---- 656 353 0.38 706 385 0.41 753 417 0.45 797 450 0.48

1000 ---- ---- ---- 671 376 0.40 722 408 0.44 768 440 0.47 812 473 0.511100 634 364 0.39 690 398 0.43 741 431 0.46 787 463 0.50 831 496 0.531200 656 389 0.42 712 423 0.45 763 455 0.49 809 488 0.52 853 520 0.561300 681 418 0.45 737 452 0.49 787 485 0.52 834 517 0.55 877 550 0.591400 707 454 0.49 763 488 0.52 813 520 0.56 860 552 0.59 903 585 0.631500 735 496 0.53 791 530 0.57 841 562 0.60 887 594 0.64 931 627 0.671600 763 545 0.58 819 579 0.62 870 612 0.66 916 644 0.69 960 677 0.731700 793 602 0.65 849 636 0.68 900 669 0.72 946 701 0.75 990 734 0.791800 824 667 0.72 880 701 0.75 930 733 0.79 977 765 0.82 1021 798 0.861900 855 739 0.79 911 773 0.83 962 806 0.86 1008 838 0.90 1052 871 0.932000 887 819 0.88 943 853 0.92 994 886 0.95 1040 918 0.98 1084 951 1.02

AIRFLOWCFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG1

0.7 0.8 0.9 1.0 1.1RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

800 829 457 0.49 872 495 0.53 916 538 0.58 964 586 0.63 1017 642 0.69900 839 485 0.52 882 524 0.56 927 566 0.61 975 615 0.66 1027 670 0.72

1000 854 508 0.55 897 547 0.59 942 589 0.63 990 638 0.68 1043 693 0.741100 874 531 0.57 916 569 0.61 961 612 0.66 1009 660 0.71 1062 715 0.771200 896 555 0.60 938 594 0.64 983 636 0.68 1031 685 0.73 1084 740 0.791300 920 585 0.63 963 623 0.67 1007 666 0.71 1055 714 0.77 1108 770 0.831400 946 620 0.67 989 659 0.71 1034 701 0.75 1082 750 0.80 ---- ---- ----1500 974 662 0.71 1017 701 0.75 1061 743 0.80 1109 792 0.85 ---- ---- ----1600 1003 712 0.76 1045 750 0.80 1090 793 0.85 ---- ---- ---- ---- ---- ----1700 1032 769 0.82 1075 807 0.87 ---- ---- ---- ---- ---- ---- ---- ---- ----1800 1063 833 0.89 1106 872 0.94 ---- ---- ---- ---- ---- ---- ---- ---- ----1900 1094 906 0.97 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2000 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.

Factory Installed AK74 blower sheave and A39 belt.

AK61 blower sheave and A36 belt - Field installation required.

Unitary Products Group 33

Page 34: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 24: SUPPLY AIR BLOWER PERFORMANCE (DR036 BELT DRIVE) - BOTTOM DUCT APPLICATION

AIRFLOWCFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG1

0.2 0.3 0.4 0.5 0.6RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

800 ---- ---- ---- ---- ---- ---- ---- ---- ---- 749 384 0.41 791 422 0.45900 ---- ---- ---- ---- ---- ---- 720 364 0.39 764 404 0.43 806 443 0.47

1000 ---- ---- ---- 690 346 0.37 739 388 0.42 783 429 0.46 824 467 0.501100 657 334 0.36 711 376 0.40 760 417 0.45 804 458 0.49 845 497 0.531200 681 369 0.40 735 410 0.44 784 452 0.49 828 493 0.53 869 532 0.571300 707 409 0.44 761 451 0.48 809 493 0.53 854 534 0.57 895 572 0.611400 735 456 0.49 789 498 0.53 837 540 0.58 882 581 0.62 923 619 0.661500 765 509 0.55 819 550 0.59 867 592 0.64 911 633 0.68 953 672 0.721600 796 567 0.61 850 609 0.65 899 651 0.70 943 692 0.74 984 730 0.781700 829 631 0.68 883 673 0.72 932 715 0.77 976 756 0.81 1017 794 0.851800 863 701 0.75 918 743 0.80 966 785 0.84 1010 826 0.89 1051 864 0.931900 899 776 0.83 953 818 0.88 1001 860 0.92 1045 901 0.97 1087 939 1.012000 936 857 0.92 990 899 0.96 1038 941 1.01 1082 981 1.05 ---- ---- ----

AIRFLOWCFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG1

0.7 0.8 0.9 1.0 1.1RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

800 831 456 0.49 871 486 0.52 914 509 0.55 961 525 0.56 1012 532 0.57900 846 477 0.51 886 507 0.54 929 530 0.57 976 546 0.59 1027 553 0.59

1000 864 502 0.54 905 531 0.57 947 555 0.60 994 571 0.61 1046 578 0.621100 885 531 0.57 926 561 0.60 969 584 0.63 1015 600 0.64 1067 607 0.651200 909 566 0.61 950 596 0.64 992 619 0.66 1039 635 0.68 1091 642 0.691300 935 607 0.65 976 636 0.68 1018 660 0.71 1065 676 0.72 ---- ---- ----1400 963 654 0.70 1004 683 0.73 1046 707 0.76 1093 722 0.77 ---- ---- ----1500 993 706 0.76 1033 736 0.79 1076 759 0.81 ---- ---- ---- ---- ---- ----1600 1024 765 0.82 1065 794 0.85 1108 818 0.88 ---- ---- ---- ---- ---- ----1700 1057 829 0.89 1098 859 0.92 ---- ---- ---- ---- ---- ---- ---- ---- ----1800 1091 899 0.96 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----1900 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2000 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.

Factory Installed AK74 blower sheave and A39 belt.

AK61 blower sheave and A36 belt - Field installation required.

34 Unitary Products Group

Page 35: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 25: SUPPLY AIR BLOWER PERFORMANCE (DR048 BELT DRIVE) - SIDE DUCT APPLICATION

AIRFLOWCFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG1

0.2 0.3 0.4 0.5 0.6 0.7RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

1000 ---- ---- ---- ---- ---- ---- ---- ---- ---- 789 527 0.57 831 567 0.61 874 602 0.651100 ---- ---- ---- ---- ---- ---- ---- ---- ---- 811 559 0.60 854 599 0.64 896 634 0.681200 ---- ---- ---- ---- ---- ---- 791 548 0.59 833 592 0.63 876 632 0.68 918 667 0.721300 ---- ---- ---- 772 539 0.58 813 584 0.63 855 628 0.67 898 668 0.72 940 703 0.751400 ---- ---- ---- 795 579 0.62 836 624 0.67 878 668 0.72 920 708 0.76 963 744 0.801500 779 578 0.62 819 624 0.67 860 669 0.72 902 713 0.77 944 753 0.81 987 789 0.851600 804 629 0.67 844 675 0.72 885 720 0.77 927 764 0.82 970 804 0.86 1013 839 0.901700 831 685 0.74 871 731 0.78 913 777 0.83 955 820 0.88 997 861 0.92 1040 896 0.961800 860 748 0.80 901 794 0.85 942 839 0.90 984 883 0.95 1026 923 0.99 1069 958 1.031900 891 817 0.88 931 862 0.92 973 908 0.97 1015 951 1.02 1057 992 1.06 1100 1027 1.102000 924 891 0.96 964 937 1.01 1005 982 1.05 1047 1026 1.10 1090 1066 1.14 1133 1102 1.182100 959 972 1.04 999 1018 1.09 1040 1063 1.14 1082 1107 1.19 1125 1147 1.23 1167 1182 1.272200 996 1059 1.14 1036 1104 1.18 1077 1150 1.23 1119 1194 1.28 1162 1234 1.32 ---- ---- ----2300 1034 1151 1.24 1075 1197 1.28 1116 1243 1.33 1158 1286 1.38 ---- ---- ---- ---- ---- ----2400 1075 1250 1.34 1115 1296 1.39 1156 1341 1.44 ---- ---- ---- ---- ---- ---- ---- ---- ----2500 1118 1354 1.45 1158 1400 1.50 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

AIRFLOWCFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG1

0.8 0.9 1.0 1.1 1.2 1.3RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

1000 917 631 0.68 959 651 0.70 1001 660 0.71 1041 658 0.71 1081 642 0.69 1119 611 0.661100 939 663 0.71 981 683 0.73 1023 692 0.74 1064 690 0.74 1103 674 0.72 1141 643 0.691200 961 696 0.75 1003 716 0.77 1045 725 0.78 1086 723 0.78 1125 707 0.76 1163 676 0.731300 983 732 0.79 1025 752 0.81 1067 761 0.82 1108 759 0.81 1147 743 0.80 1185 712 0.761400 1006 772 0.83 1048 792 0.85 1090 801 0.86 1130 799 0.86 1170 783 0.84 ---- ---- ----1500 1030 817 0.88 1072 837 0.90 1114 847 0.91 1154 844 0.91 1194 829 0.89 ---- ---- ----1600 1055 868 0.93 1098 888 0.95 1139 897 0.96 1180 895 0.96 ---- ---- ---- ---- ---- ----1700 1083 924 0.99 1125 944 1.01 1166 954 1.02 ---- ---- ---- ---- ---- ---- ---- ---- ----1800 1112 987 1.06 1154 1007 1.08 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----1900 1142 1055 1.13 1185 1075 1.15 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2000 1175 1130 1.21 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2100 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2200 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2300 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2400 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2500 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.

Factory Installed AK61 blower sheave and A36 belt.

AK56 blower sheave and A36 belt - Field installation required.

Unitary Products Group 35

Page 36: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 26: SUPPLY AIR BLOWER PERFORMANCE (DR048 BELT DRIVE) - BOTTOM DUCT APPLICATION

AIRFLOWCFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG1

0.2 0.3 0.4 0.5 0.6 0.7RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

1000 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 833 564 0.61 879 605 0.651100 ---- ---- ---- ---- ---- ---- ---- ---- ---- 809 549 0.59 854 592 0.63 900 633 0.681200 ---- ---- ---- ---- ---- ---- 786 538 0.58 830 581 0.62 875 623 0.67 920 664 0.711300 ---- ---- ---- 766 535 0.57 808 574 0.62 851 617 0.66 896 659 0.71 942 700 0.751400 749 541 0.58 789 576 0.62 830 616 0.66 874 658 0.71 918 701 0.75 964 742 0.801500 774 587 0.63 813 622 0.67 855 662 0.71 898 705 0.76 943 747 0.80 989 788 0.851600 801 639 0.69 840 674 0.72 881 714 0.77 925 757 0.81 970 799 0.86 1015 840 0.901700 830 697 0.75 869 732 0.79 911 772 0.83 954 814 0.87 999 857 0.92 1045 898 0.961800 862 760 0.81 901 795 0.85 943 835 0.90 986 877 0.94 1031 920 0.99 1077 960 1.031900 897 828 0.89 936 863 0.93 977 903 0.97 1021 945 1.01 1066 988 1.06 1111 1029 1.102000 934 901 0.97 973 936 1.00 1015 976 1.05 1058 1018 1.09 1103 1061 1.14 1149 1102 1.182100 974 979 1.05 1013 1014 1.09 1055 1054 1.13 1098 1097 1.18 1143 1139 1.22 1189 1180 1.272200 1017 1063 1.14 1056 1098 1.18 1098 1138 1.22 1141 1180 1.27 1186 1223 1.31 ---- ---- ----2300 1063 1151 1.23 1102 1186 1.27 1144 1226 1.31 1187 1268 1.36 ---- ---- ---- ---- ---- ----2400 1111 1243 1.33 1151 1278 1.37 1192 1318 1.41 ---- ---- ---- ---- ---- ---- ---- ---- ----2500 1163 1340 1.44 1202 1376 1.48 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

AIRFLOWCFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG1

0.8 0.9 1.0 1.1 1.2 1.3RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

1000 925 642 0.69 971 673 0.72 1017 696 0.75 1061 708 0.76 1103 708 0.76 1144 693 0.741100 946 670 0.72 992 701 0.75 1037 723 0.78 1082 736 0.79 1124 735 0.79 1165 721 0.771200 967 701 0.75 1013 732 0.79 1058 755 0.81 1102 767 0.82 1145 767 0.82 1185 752 0.811300 988 737 0.79 1034 768 0.82 1079 791 0.85 1123 803 0.86 1166 803 0.86 ---- ---- ----1400 1010 779 0.84 1056 809 0.87 1102 832 0.89 1146 844 0.91 1188 844 0.91 ---- ---- ----1500 1035 825 0.89 1081 856 0.92 1126 879 0.94 1170 891 0.96 ---- ---- ---- ---- ---- ----1600 1062 877 0.94 1108 908 0.97 1153 931 1.00 1197 943 1.01 ---- ---- ---- ---- ---- ----1700 1091 935 1.00 1137 966 1.04 1182 988 1.06 ---- ---- ---- ---- ---- ---- ---- ---- ----1800 1123 997 1.07 1169 1028 1.10 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----1900 1157 1066 1.14 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2000 1195 1139 1.22 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2100 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2200 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2300 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2400 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2500 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.

Factory Installed AK61 blower sheave and A36 belt.

AK56 blower sheave and A36 belt - Field installation required.

36 Unitary Products Group

Page 37: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 27: SUPPLY AIR BLOWER PERFORMANCE (DR060 & DR072 BELT DRIVE) - SIDE DUCT APPLICATION

AIRFLOWCFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG1

0.2 0.3 0.4 0.5 0.6 0.7RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

1200 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 876 632 0.68 918 667 0.721300 ---- ---- ---- ---- ---- ---- ---- ---- ---- 855 628 0.67 898 668 0.72 940 703 0.751400 ---- ---- ---- ---- ---- ---- 836 624 0.67 878 668 0.72 920 708 0.76 963 744 0.801500 ---- ---- ---- 819 624 0.67 860 669 0.72 902 713 0.77 944 753 0.81 987 789 0.851600 ---- ---- ---- 844 675 0.72 885 720 0.77 927 764 0.82 970 804 0.86 1013 839 0.901700 831 685 0.74 871 731 0.78 913 777 0.83 955 820 0.88 997 861 0.92 1040 896 0.961800 860 748 0.80 901 794 0.85 942 839 0.90 984 883 0.95 1026 923 0.99 1069 958 1.031900 891 817 0.88 931 862 0.92 973 908 0.97 1015 951 1.02 1057 992 1.06 1100 1027 1.102000 924 891 0.96 964 937 1.01 1005 982 1.05 1047 1026 1.10 1090 1066 1.14 1133 1102 1.182100 959 972 1.04 999 1018 1.09 1040 1063 1.14 1082 1107 1.19 1125 1147 1.23 1167 1182 1.272200 996 1059 1.14 1036 1104 1.18 1077 1150 1.23 1119 1194 1.28 1162 1234 1.32 ---- ---- ----2300 1034 1151 1.24 1075 1197 1.28 1116 1243 1.33 1158 1286 1.38 ---- ---- ---- ---- ---- ----2400 1075 1250 1.34 1115 1296 1.39 1156 1341 1.44 ---- ---- ---- ---- ---- ---- ---- ---- ----2500 1118 1354 1.45 1158 1400 1.50 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

AIRFLOWCFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG1

0.8 0.9 1.0 1.1 1.2 1.3RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

1200 961 696 0.75 1003 716 0.77 1045 725 0.78 1086 723 0.78 1125 707 0.76 1163 676 0.731300 983 732 0.79 1025 752 0.81 1067 761 0.82 1108 759 0.81 1147 743 0.80 1185 712 0.761400 1006 772 0.83 1048 792 0.85 1090 801 0.86 1130 799 0.86 1170 783 0.84 ---- ---- ----1500 1030 817 0.88 1072 837 0.90 1114 847 0.91 1154 844 0.91 1194 829 0.89 ---- ---- ----1600 1055 868 0.93 1098 888 0.95 1139 897 0.96 1180 895 0.96 ---- ---- ---- ---- ---- ----1700 1083 924 0.99 1125 944 1.01 1166 954 1.02 ---- ---- ---- ---- ---- ---- ---- ---- ----1800 1112 987 1.06 1154 1007 1.08 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----1900 1142 1055 1.13 1185 1075 1.15 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2000 1175 1130 1.21 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2100 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2200 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2300 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2400 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2500 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.

Factory Installed AK56 blower sheave and A36 belt.

Unitary Products Group 37

Page 38: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 28: SUPPLY AIR BLOWER PERFORMANCE (DR060 & DR072 BELT DRIVE) - BOTTOM DUCT APPLICATION

AIRFLOWCFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG1

0.2 0.3 0.4 0.5 0.6 0.7RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

1000 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 862 453 0.49 901 498 0.531100 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 883 494 0.53 922 539 0.581200 ---- ---- ---- ---- ---- ---- ---- ---- ---- 866 489 0.53 904 536 0.58 943 581 0.621300 ---- ---- ---- ---- ---- ---- 850 488 0.52 889 535 0.57 928 581 0.62 967 627 0.671400 ---- ---- ---- 836 491 0.53 875 537 0.58 913 584 0.63 952 631 0.68 991 676 0.731500 ---- ---- ---- 862 545 0.58 901 591 0.63 940 638 0.68 978 685 0.73 1017 730 0.781600 851 559 0.60 890 604 0.65 928 650 0.70 967 697 0.75 1006 744 0.80 1045 789 0.851700 880 624 0.67 919 668 0.72 958 714 0.77 996 761 0.82 1035 808 0.87 1074 853 0.921800 911 694 0.74 949 738 0.79 988 785 0.84 1027 832 0.89 1066 878 0.94 1105 923 0.991900 942 770 0.83 981 814 0.87 1020 860 0.92 1059 907 0.97 1097 954 1.02 1136 999 1.072000 976 851 0.91 1014 895 0.96 1053 941 1.01 1092 989 1.06 1130 1035 1.11 1169 1080 1.162100 1010 938 1.01 1049 982 1.05 1087 1028 1.10 1126 1075 1.15 1165 1122 1.20 1204 1167 1.252200 1046 1030 1.11 1084 1075 1.15 1123 1121 1.20 1162 1168 1.25 1200 1215 1.30 ---- ---- ----2300 1082 1128 1.21 1121 1172 1.26 1160 1219 1.31 1198 1266 1.36 ---- ---- ---- ---- ---- ----2400 1120 1231 1.32 1159 1276 1.37 1198 1322 1.42 ---- ---- ---- ---- ---- ---- ---- ---- ----2500 1159 1340 1.44 1198 1384 1.48 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

AIRFLOWCFM

AVAILABLE EXTERNAL STATIC PRESSURE - IWG1

0.8 0.9 1.0 1.1 1.2 1.3RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP RPM WATTS BHP

1000 940 541 0.58 980 579 0.62 1019 613 0.66 1059 641 0.69 1099 662 0.71 1140 674 0.721100 961 582 0.62 1000 621 0.67 1040 654 0.70 1080 682 0.73 1120 703 0.75 1161 715 0.771200 983 624 0.67 1022 663 0.71 1062 697 0.75 1101 725 0.78 1142 745 0.80 1182 758 0.811300 1006 669 0.72 1045 708 0.76 1085 742 0.80 1125 770 0.83 1165 791 0.85 ---- ---- ----1400 1030 718 0.77 1070 757 0.81 1109 791 0.85 1149 819 0.88 1190 840 0.90 ---- ---- ----1500 1057 772 0.83 1096 811 0.87 1136 845 0.91 1176 873 0.94 ---- ---- ---- ---- ---- ----1600 1084 831 0.89 1124 870 0.93 1163 904 0.97 1203 932 1.00 ---- ---- ---- ---- ---- ----1700 1113 896 0.96 1153 935 1.00 1192 969 1.04 ---- ---- ---- ---- ---- ---- ---- ---- ----1800 1144 966 1.04 1183 1005 1.08 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----1900 1175 1042 1.12 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2000 1209 1123 1.20 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2100 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2200 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2300 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2400 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----2500 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----

1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications.

Factory Installed AK56 blower sheave and A36 belt.

38 Unitary Products Group

Page 39: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than

0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 29: BELT DRIVE BLOWER MOTOR AND DRIVE DATA

MODELSIZE

BLOWERRANGE(RPM)

MOTOR1 ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY BELT(NOTCHED)

HP FRAME DESIG-NATION

OUTSIDEDIA.(IN.)

PITCHDIA.(IN.)

BORE(IN.)

DESIG-NATION

OUTSIDEDIA.(IN.)

PITCHDIA.(IN.)

BORE(IN.)

DESIG-NATION

PITCHLENGTH

(IN.)QTY.

3 TON 790/1120 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 7/8 AK74 7.25 7.2 1 A39 40.3 14 TON 790/1120 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 7/8 AK61 5.9 5.7 1 A36 37.3 1

5, 6 TON 850/1220 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 7/8 AK56 5.4 5.2 1 A35 36.3 1

1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device.

TABLE 30: STATIC RESISTANCES

DESCRIPTION

RESISTANCE, IWG

CFM

1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000

ECONOMIZER1,3 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 0.30

ELECTRICHEATERS1

7-15KW 0.04 0.05 0.06 0.07 0.08 0.10 0.12 0.14 0.16 0.19 0.22

20-30KW 0.06 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26

COOLING ONLY2 0.08 0.10 0.12 0.14 0.16 0.18 0.20 0.23 0.26 0.29 0.32

TABLE 31: ELECTRIC HEATER CFM LIMITATIONS

UNITMODEL SIZE NOMINAL TONS VOLTAGE

MINIMUM SUPPLY AIR CFM

HEATER SIZE NOMINAL KW

5 7 10 15 20 30

3

208/230-3-60 1100 1100 1200 1200 1300 -

460-3-60 - 1100 1200 1200 1300 -

575-3-60 - - 1200 1200 1300 -

4

208/230-3-60 1300 1300 1300 1300 1300 -

460-3-60 - 1300 1300 1300 1300 -

575-3-60 - - 1300 1300 1400 -

5

208/230-3-60 1600 1600 1600 1600 1600 1600

460-3-60 - 1600 1600 1600 1600 1600

575-3-60 - - 1600 1600 1600 1800

6

208/230-3-60 1800 1800 1800 1800 1800 1800

460-3-60 - 1800 1800 1800 1800 1800

575-3-60 - - 1800 1800 1800 1800

Unitary Products Group 39

Page 40: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

1. HACR Typer Per NEC.2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.e. Chicago),

the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.

TABLE 32: ELECTRICAL DATA - DR036 AND DR048 W/O POWERED CONVENIENCE OUTLET

MODELTONNAGE VOLTAGE

COMPRESSORS OD FANMOTOR

FLA

ID BLOWER MOTOR

FLA

CONVOUTLET

FLAELECTRIC HEATER

MODEL NO.HEATER

KWHEATER

AMPS

MIN.CIRCUIT

AMPACITY(AMPS)

MAX. FUSE/BRKR1

SIZE(AMPS)

RLAEACH

LRAEACH

DR036

208-3-60 11.8 68 2.3 5.2 0

None -- -- 22.3 302CE045105252 4.0 11.1 22.3 302CE045107252 5.6 15.5 25.9 302CE04511025 8.0 22.2 34.3 352CE04511525 11.9 33.0 47.8 502CE04512025 15.9 44.1 61.7 70

230-3-60 11.8 68 2.3 5.2 0

None -- -- 22.3 302CE045105252 5.3 12.7 22.4 302CE045107252 7.5 18.0 29.1 302CE04511025 10.6 25.5 38.4 402CE04511525 15.9 38.2 54.3 602CE04512025 21.2 51.0 70.2 80

460-3-60 5.1 34 1.3 2.6 0

None -- -- 10.3 152CE045107462 6.8 8.2 13.5 152CE045110462 10.1 12.1 18.4 202CE045115462 13.6 16.4 23.7 252CE045120462 19.5 23.5 32.6 35

575-3-60 4.1 TBD 1.3 2 0

None -- -- 8.2 152CE04511058 10.6 10.2 15.2 202CE04511558 15.9 15.3 21.6 252CE04512058 21.2 20.4 28.0 30

DR048

208-3-60 11.5 84 2.3 5.2 0

None -- -- 21.9 302CE045105252 4.0 11.1 21.9 302CE045107252 5.6 15.5 25.9 302CE04511025 8.0 22.2 34.3 352CE04511525 11.9 33.0 47.8 502CE04512025 15.9 44.1 61.7 70

230-3-60 11.5 84 2.3 5.2 0

None -- -- 21.9 302CE045105252 5.3 12.7 22.4 302CE045107252 7.5 18.0 29.1 302CE04511025 10.6 25.5 38.4 402CE04511525 15.9 38.2 54.3 602CE04512025 21.2 51.0 70.2 80

460-3-60 5.8 42 1.3 2.6 0

None -- -- 11.1 152CE045107462 6.8 8.2 13.5 152CE045110462 10.1 12.1 18.4 202CE045115462 13.6 16.4 23.7 252CE045120462 19.5 23.5 32.6 35

575-3-60 5.1 34 1.3 2 0

None -- -- 9.4 152CE04511058 10.6 10.2 15.2 202CE04511558 15.9 15.3 21.6 252CE04512058 21.2 20.4 28.0 30

40 Unitary Products Group

Page 41: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

1. HACR Typer Per NEC.2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.e. Chicago),

the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.

TABLE 33: ELECTRICAL DATA - DR060 AND DR072 W/O POWERED CONVENIENCE OUTLET

MODELTONNAGE VOLTAGE

COMPRESSORS OD FANMOTOR

FLA

ID BLOWER MOTOR

FLA

CONVOUTLET

FLAELECTRIC HEATER

MODEL NO.HEATER

KWHEATER

AMPS

MIN.CIRCUIT

AMPACITY(AMPS)

MAX. FUSE/BRKR1

SIZE(AMPS)

RLAEACH

LRAEACH

DR060

208-3-60 17.3 123 2.3 5.2 0

None -- -- 29.1 352CE045105252 4.0 11.1 29.1 352CE045107252 5.6 15.5 29.1 352CE04511025 8.0 22.2 34.3 452CE04511525 11.9 33.0 47.8 502CE04512025 15.9 44.1 61.7 702CE04513025 22.2 61.6 83.5 90

230-3-60 17.3 123 2.3 5.2 0

None -- -- 29.1 352CE045105252 5.3 12.7 29.1 352CE045107252 7.5 18.0 29.1 352CE04511025 10.6 25.5 38.4 452CE04511525 15.9 38.2 54.3 602CE04512025 21.2 51.0 70.2 802CE04513025 29.6 71.2 95.5 100

460-3-60 8.4 70 1.3 2.6 0

None -- -- 14.4 202CE045107462 6.8 8.2 14.4 202CE045110462 10.1 12.1 18.4 202CE045115462 13.6 16.4 23.7 252CE045120462 19.5 23.5 32.6 352CE045130462 28.8 34.6 46.6 50

575-3-60 7 53 1.3 2 0

None -- -- 11.8 152CE04511058 10.6 10.2 15.2 202CE04511558 15.9 15.3 21.6 252CE04512058 21.2 20.4 28.0 302CE04513058 30.4 29.3 39.1 40

DR072

208-3-60 18.6 156 2.3 5.2 0

None -- -- 30.8 402CE045105252 4.0 11.1 30.8 402CE045107252 5.6 15.5 30.8 402CE04511025 8.0 22.2 34.3 452CE04511525 11.9 33.0 47.8 502CE04512025 15.9 44.1 61.7 702CE04513025 22.2 61.6 83.5 90

230-3-60 18.6 156 2.3 5.2 0

None -- -- 30.8 402CE045105252 5.3 12.7 30.8 402CE045107252 7.5 18.0 30.8 402CE04511025 10.6 25.5 38.4 452CE04511525 15.9 38.2 54.3 602CE04512025 21.2 51.0 70.2 802CE04513025 29.6 71.2 95.5 100

460-3-60 9 75 1.3 2.6 0

None -- -- 15.1 202CE045107462 6.8 8.2 15.1 202CE045110462 10.1 12.1 18.4 202CE045115462 13.6 16.4 23.7 252CE045120462 19.5 23.5 32.6 352CE045130462 28.8 34.6 46.6 50

575-3-60 7.4 54 1.3 2 0

None -- -- 12.3 152CE04511058 10.6 10.2 15.2 202CE04511558 15.9 15.3 21.6 252CE04512058 21.2 20.4 28.0 302CE04513058 30.4 29.3 39.1 40

Unitary Products Group 41

Page 42: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

1. HACR Typer Per NEC.2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.e. Chicago),

the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.

TABLE 34: ELECTRICAL DATA - DR036 AND DR048 WITH POWERED CONVENIENCE OUTLET

MODELTONNAGE VOLTAGE

COMPRESSORS OD FANMOTOR

FLA

ID BLOWER MOTOR

FLA

CONVOUTLET

FLAELECTRIC HEATER

MODEL NO.HEATER

KWHEATER

AMPS

MIN.CIRCUIT

AMPACITY(AMPS)

MAX. FUSE/BRKR1

SIZE(AMPS)

RLAEACH

LRAEACH

DR036

208-3-60 11.8 68 2.3 5.2 10

None -- -- 32.3 402CE045105252 4.0 11.1 32.9 402CE045107252 5.6 15.5 38.4 402CE04511025 8.0 22.2 46.8 502CE04511525 11.9 33.0 60.3 702CE04512025 15.9 44.1 74.2 80

230-3-60 11.8 68 2.3 5.2 10

None -- -- 32.3 402CE045105252 5.3 12.7 34.9 402CE045107252 7.5 18.0 41.6 452CE04511025 10.6 25.5 50.9 602CE04511525 15.9 38.2 66.8 702CE04512025 21.2 51.0 82.7 90

460-3-60 5.1 34 1.3 2.6 5

None -- -- 15.3 202CE045107462 6.8 8.2 19.7 202CE045110462 10.1 12.1 24.7 252CE045115462 13.6 16.4 29.9 302CE045120462 19.5 23.5 38.8 40

575-3-60 4.1 TBD 1.3 2 4

None -- -- 12.2 152CE04511058 10.6 10.2 20.2 252CE04511558 15.9 15.3 26.6 302CE04512058 21.2 20.4 33.0 35

DR048

208-3-60 11.5 84 2.3 5.2 10

None -- -- 31.9 402CE045105252 4.0 11.1 32.9 402CE045107252 5.6 15.5 38.4 402CE04511025 8.0 22.2 46.8 502CE04511525 11.9 33.0 60.3 702CE04512025 15.9 44.1 74.2 80

230-3-60 11.5 84 2.3 5.2 10

None -- -- 31.9 402CE045105252 5.3 12.7 34.9 402CE045107252 7.5 18.0 41.6 452CE04511025 10.6 25.5 50.9 602CE04511525 15.9 38.2 66.8 702CE04512025 21.2 51.0 82.7 90

460-3-60 5.8 42 1.3 2.6 5

None -- -- 16.1 202CE045107462 6.8 8.2 19.7 202CE045110462 10.1 12.1 24.7 252CE045115462 13.6 16.4 29.9 302CE045120462 19.5 23.5 38.8 40

575-3-60 5.1 34 1.3 2 4

None -- -- 13.4 152CE04511058 10.6 10.2 20.2 252CE04511558 15.9 15.3 26.6 302CE04512058 21.2 20.4 33.0 35

42 Unitary Products Group

Page 43: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

1. HACR Typer Per NEC.2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.e. Chicago),

the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.

TABLE 35: ELECTRICAL DATA - DR060 AND DR072 WITH POWERED CONVENIENCE OUTLET

MODELTONNAGE VOLTAGE

COMPRESSORS OD FANMOTOR

FLA

ID BLOWER MOTOR

FLA

CONVOUTLET

FLAELECTRIC HEATER

MODEL NO.HEATER

KWHEATER

AMPS

MIN.CIRCUIT

AMPACITY(AMPS)

MAX. FUSE/BRKR1

SIZE(AMPS)

RLAEACH

LRAEACH

DR060

208-3-60 17.3 123 2.3 5.2 10

None -- -- 39.1 502CE045105252 4.0 11.1 39.1 502CE045107252 5.6 15.5 39.1 502CE04511025 8.0 22.2 46.8 502CE04511525 11.9 33.0 60.3 702CE04512025 15.9 44.1 74.2 802CE04513025 22.2 61.6 96.0 100

230-3-60 17.3 123 2.3 5.2 10

None -- -- 39.1 502CE045105252 5.3 12.7 39.1 502CE045107252 7.5 18.0 41.6 502CE04511025 10.6 25.5 50.9 602CE04511525 15.9 38.2 66.8 702CE04512025 21.2 51.0 82.7 902CE04513025 29.6 71.2 108.0 110

460-3-60 8.4 70 1.3 2.6 5

None -- -- 19.4 252CE045107462 6.8 8.2 19.7 252CE045110462 10.1 12.1 24.7 252CE045115462 13.6 16.4 29.9 302CE045120462 19.5 23.5 38.8 402CE045130462 28.8 34.6 52.8 60

575-3-60 7 53 1.3 2 4

None -- -- 15.8 202CE04511058 10.6 10.2 20.2 252CE04511558 15.9 15.3 26.6 302CE04512058 21.2 20.4 33.0 352CE04513058 30.4 29.3 44.1 45

DR072

208-3-60 18.6 156 2.3 5.2 10

None -- -- 40.8 502CE045105252 4.0 11.1 40.8 502CE045107252 5.6 15.5 40.8 502CE04511025 8.0 22.2 46.8 502CE04511525 11.9 33.0 60.3 702CE04512025 15.9 44.1 74.2 802CE04513025 22.2 61.6 96.0 100

230-3-60 18.6 156 2.3 5.2 10

None -- -- 40.8 502CE045105252 5.3 12.7 40.8 502CE045107252 7.5 18.0 41.6 502CE04511025 10.6 25.5 50.9 602CE04511525 15.9 38.2 66.8 702CE04512025 21.2 51.0 82.7 902CE04513025 29.6 71.2 108.0 110

460-3-60 9 75 1.3 2.6 5

None -- -- 20.1 252CE045107462 6.8 8.2 20.1 252CE045110462 10.1 12.1 24.7 252CE045115462 13.6 16.4 29.9 302CE045120462 19.5 23.5 38.8 402CE045130462 28.8 34.6 52.8 60

575-3-60 7.4 54 1.3 2 4

None -- -- 16.3 202CE04511058 10.6 10.2 20.2 252CE04511558 15.9 15.3 26.6 302CE04512058 21.2 20.4 33.0 352CE04513058 30.4 29.3 44.1 45

Unitary Products Group 43

Page 44: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TABLE 36: PHYSICAL DATA

MODELS DR036 048 060 072

EVAPORATORBLOWER

Centrifugal Blower (Dia. x Wd. in.) 12 X 10 12 X 10 12 X 10 12 X 10Fan Motor HP (Belt Drive) 1 1/2 1 1/2 1 1/2 1 1/2

EVAPORATORCOIL

Rows Deep 3 4 4 4Fins Per Inch 13 13 13 13

Face Area (Sq. Ft.) 5.1 5.1 5.1 5.1

CONDENSERFANS

Propeller Dia. (in.) 24 24 24 24Fan Motor Hp 1/2 1/2 1/2 1/2

Nom. CFM 4500 4500 4500 4500

CONDENSERCOILS

Rows Deep 2 2 2 2Fins Per Inch 18 18 18 18

Face Area (Sq. Ft.) 17.1 17.1 17.1 17.1COMPRESSOR(Qty. Per Unit) Qty / Type 1/Recip 1/Recip 1/Scroll 1/Scroll

AIRFILTERS

Quantity Per Unit (15” X 20” X 1” or 2“) 2 2 2 2Quantity Per Unit (14” X 25” X 1” or 2“) 1 1 1 1

Total Face Area (sq. ft.) 6.6 6.6 6.6 6.6

CHARGE Refrigerant 22(lbs./oz.) 10/8 10/0 10/8 10/0

TABLE 37: ELECTRIC HEAT CORRECTION FACTORS

NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER

208 208 1.00240 230 0.92480 460 0.92600 575 0.92

TABLE 38: VOLTAGE LIMITATIONS1

1. Utilization Range “A” in accordance with ARI Standard 110.

POWER SUPPLY VOLTAGEMIN. MAX.

208/230-3-60 187 252

460-3-60 432 504575-3-60 540 630

44 Unitary Products Group

Page 45: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

TYPICAL POWER WIRING

TYPICAL CONTROL WIRING

FIGURE 6 - TYPICAL FIELD POWER & CONTROL WIRING

REFER TO THE ELECTRICAL DATATABLES TO SIZE THE DISCONNECTSWITCH, OVERCURRENT PROTEC-TION AND WIRING.

Unitary Products Group 45

Page 46: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

FIGURE 7 - UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW

FIGURE 8 - UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW

46 Unitary Products Group

Page 47: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

FIGURE 9 - UNIT WITH ECONOMIZER RAINHOOD

FIGURE 10 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD

DETAIL “A”

DETAIL “B”

Unitary Products Group 47

Page 48: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

FIGURE 11 - UNIT DIMENSIONS (REAR VIEW)

FIGURE 12 - DISCONNECT/BLOWER ACCESS LOCATION

TABLE 39: UTILITIES ENTRY

HOLE OPENING SIZE (DIA.) USED FOR

A 7/8” KO1

1. Opening in the bottom to the unit can be located by the side in the insulation.

Control Wiring2

2. Do not remove the 2” knockout ring.

SideBottom

B 2” KO1 Power WiringSide

BottomC 1-5/8” KO Gas Piping (Front)

D 1-1/2” KO Gas Piping (Bottom)

DISCONNECT SWITCH LOCATION

AND MOTOR ACCESS PANEL FOR

UNIT WITH “BELT-DRIVE” OPTION

CONTROL BOX

ACCESS

A,B

WIRING ENTRY

(See Detail “B”)

MOUNTING BRACKET

FOR DICONNECT SWITCH

(Shipped attached to the

blower housing inside

the blower compartment)

FIELD-SUPPLIED

DISCONNECT SWITCH

LOCATION

BLOWER MOTOR

ACCESS

FILTER

ACCESS

DOT PLUGS

TABLE 40: MINIMUM CLEARANCES

LOCATION CLEARANCE

Front24” (Cooling/Electric Heat)

32” (Gas Heat)

Rear12” (Less Economizer)

36” (With Economizer or Fixed Air/Motorized Damper)

Left Side (Filter Access) 24” (Less Economizer)36” (With Economizer)

Right Side (Cond. Coil) 24”

Below Unit1

1. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.

0”

Above Unit2

2. Units must be installed outdoors. Overhanging struc-tures or shrubs should not obstruct condenser air dis-charge outlet.

72” (ForCondenser Air Discharge)

48 Unitary Products Group

Page 49: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

FIGURE 13 - TYPICAL APPLICATIONS

Unitary Products Group 49

Page 50: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

FIGURE 14 - FOUR AND SIX POINT LOADING

447/8821/4

Y

X

A

B

C

D

CONDENSER COIL

END OF UNITFRONT OF UNIT

APPROXIMATE

CENTER OF GRAVITY

BACK OF UNIT

447/8821/4

Y

X

A

B

C

D

E

F

CONDENSER COIL

END OF UNITFRONT OF UNIT

APPROXIMATE

CENTER OF GRAVITY

BACK OF UNIT

TABLE 41: DR 4 POINT LOADS WEIGHT DISTRIBUTION

UNIT TOTAL A B C D

DR036 Cooling/ Electric 569 116 134 170 148

DR036N04 609 125 143 182 159DR036N08 629 129 148 188 164DR048 Cooling/ Electric 566 116 133 170 147DR048N06 616 126 145 185 160DR048N10 636 130 150 190 166DR060 Cooling/ Electric 580 119 137 174 151DR060N08 640 131 151 192 167DR060N10 650 133 153 195 169DR072 Cooling/ Electric 582 119 137 174 152DR072N08 642 131 151 192 167DR072N10 652 133 154 195 170

TABLE 42: DR 6 POINT LOADS WEIGHT DISTRIBUTION

UNIT TOTAL A B C D E F

DR036 Cooling/ Electric 569 76 83 91 116 106 97

DR036N04 609 81 89 98 125 113 103DR036N08 629 84 92 101 129 117 107DR048 Cooling/ Electric 566 75 83 91 116 105 96DR048N06 616 82 90 99 126 114 104DR048N10 636 85 93 102 130 118 108DR060 Cooling/ Electric 580 77 85 93 119 108 98DR060N08 640 85 93 103 131 119 109DR060N10 650 87 95 104 133 121 110DR072 Cooling/ Electric 582 78 85 94 119 108 99DR072N08 642 86 94 103 131 119 109DR072N10 652 87 95 105 133 121 111

TABLE 43: CENTER OF GRAVITY

DIMENSION 3 - 6 TON

X 44”

Y 19-¾”

50 Unitary Products Group

Page 51: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

FIGURE 15 - ROOF CURB DIMENSIONS

TABLE 44: OPERATING WEIGHTS (LBS.)

MODEL SIZE 3 TON 4 TON 5 TON 6 TON

BASICUNIT

DR (Cooling Only) 569 566 580 582

DR(Gas/Electric)

N04 609 - - -N06 - 616 - -N08 629 - 640 642N10 - 636 650 652

OPTIONS

Economizer 50Motorized Damper 26

Electric Heater5 - 7 kW 18

10 - 15 kW 2320 - 30 kW 28

ACCY.Roof Curb 92

Barometric Relief / Fixed Air Damper 10

Unitary Products Group 51

Page 52: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

GUIDE SPECIFICATIONS

GENERALUnits shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility.

York's Sunline MagnaDRYTM units are convertible single pack-ageunits. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. Cooling only, cooling with gas heat and cooling with electric heat models are available with a wide variety of factory-mounted options and field-installed accessories to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with holes in the four corners for over-head rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to pro-vide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear of the unit.

All compressors have internal pressure relief. Every refriger-ant circuit includes a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch.The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with a compressor lockout circuit, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls. All models are CSA listed. All models include a 1-year limited warranty on the complete unit. Compressors and electric heater ele-ments carry a 5-year warranty. Aluminized steel and Stain-less steel tubular heat exchangers carry a 10-year warranty.

DESCRIPTIONUnits shall be factory-assembled, single packaged, Electric Cooling/Gas Heat, Electric Cooling/Optional Electric Heat and designed for outdoor mounted installation.

The 3, 4 and 5 ton units have SEER ratings of 13.0 and the 6 ton unit is rated at 10.4 EER. They shall have built-in field convertible duct connections for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. All units the cooling performance shall be rated in accordance with ARI test pro-cedures. Units shall be CSA listed, classified to ANSI Z21.47, UL 1995/CSA No. 236 standards.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 1000 hours salt spray test per ASTMB117 standards. Indoor blower section shall be insu-lated with a minimum 1/2” thick insulation, coated on the air-side. Aluminum foil faced insulation shall be used in the furnace compartment and be fastened with ridged fasteners to prevent insulation from entering the air stream. Cabinet panels shall be “large” size, easily removable for servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications. Disposable 1" filters shall be furnished and be accessible through a removable access door, sealed airtight. Units filter track shall be designed to accommodate either 1” or 2” filters. Fan perfor-mance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating air by-pass of the coils. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards. Con-densate connection shall be a minimum of 3/4” I.D. female and be a ridged mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

The indoor fan shall be a factory installed belt drive assembly that includes an adjustable pitch motor pulley. Job site selected (B.H.P.) brake horsepower shall not exceed the motors nameplate horsepower rating, plus the service factor. Units shall be designed not to operate above service factor. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bearings shall be sealed and permanently lubri-cated for longer life and no maintenance.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to a corrosion resistant steel spider bracket and shall be dynami-cally balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated bear-ings, internally protected against overload conditions and staged independently.

REFRIGERANT COMPONENTS

Compressor:

a. Shall be internally protected with internal high-pres-sure relief and over temperature protection.

b. Shall have internal spring isolation and sound muf-fling to minimize vibration and noise, and be exter-nally isolated on a dedicated, independent mounting.

52 Unitary Products Group

Page 53: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

Coils:

a. Evaporator and condenser coils shall have alumi-num plate fins mechanically bonded to seamlessinternally enhanced copper tubes with all jointsbrazed. Special Phenolic coating shall be availableas a factory option.

b. Evaporator and Condenser coils shall be of the direct expansion, draw-thru, design.

Refrigerant Circuit and Refrigerant Safety Components shall include:

a. Thermal expansion devices (TXV’s).

b. Filter drier/strainer to eliminate any moisture or for-eign matter.

c. Accessible service gage connections on both suc-tion and liquid lines to charge, evacuate, and mea-sure refrigerant pressure during any necessary servicing or troubleshooting without losing charge.

d. The refrigeration system shall provide at least 15°F of sub-cooling at design conditions.

UNIT CONTROLS

a. Unit shall be complete with self-contained low-volt-age control circuit protected by a resetable circuitbreaker on the 24-volt transformer side.

b. Unit shall incorporate a lockout circuit which pro-vides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor.

c. Loss-of-charge/Low-pressure switch.

d. High-pressure switch.

e. Freeze-protection thermostat, evaporator coil.

f. If any of the above safety devices trip, a LED (light-emitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped.

g. Unit shall incorporate “AUTO RESET” compressor over temperature, over current protection.

h. Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up.

i. Unit control board shall have on-board diagnostics and fault code display.

j. Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down to 0°F.

k. Control board shall monitor each refrigerant safety switch independently.

l. Control board shall retain last 5 fault codes in non volatile memory, which will not be lost in the event of a power loss.

GAS HEATING SECTION

Shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition, and redun-dant main gas valve. Venter wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25°F. Burners shall be of the inshot type, constructed of aluminum coated steel and con-tain air mixture adjustments. All gas piping shall enter the unit cabinet at a single location through either the side or curb, without any field modifications. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the fol-lowing minimum protection:

a. Primary and auxiliary high-temperature limit switches.

b. Induced draft motor speed sensor.

c. Flame roll out switch (manual reset).

d. Flame proving controls.

ELECTRIC HEATING SECTION

An electric heating section, with nickel chromium elements, shall be provided in a range of 5 thru 30 KW, offering two stages of capacity - 16 KW and above on 208/230 volt heaters and 20 KW and above on 460 and 575 volt heaters. The heat-ing section shall have a primary limit control(s) and automatic reset to prevent the heating element system from operating at an excessive temperature. The heating section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required).

UNIT OPERATING CHARACTERISTICS

a. Unit shall be capable of starting and running at 125°Foutdoor temperature, exceeding maximum load crite-ria of ARI Standard 210/240. The compressor, withstandard controls, shall be capable of operation downto 0°F outdoor temperature. Unit shall be providedwith fan time delay to prevent cold air delivery beforeheat exchanger warms up (Gas heat only).

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

STANDARD LIMITED WARRANTIES

• Compressor 5 Years

• Heat Exchanger 10 Years

• Electric Heat Element 5 Years

• Other Parts 1 Year

Unitary Products Group 53

Page 54: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

OPTIONAL OUTDOOR AIR (Shall be made available by either/or):

• ELECTRONIC ENTHALPY AUTOMATIC ECONO-MIZER- Outdoor and return air dampers that are inter-locked and positioned by a fully-modulating, spring return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potenti-ometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi-tioned space during normal operation. During econo-mizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer oper-ation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The out-door intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/fil-ters shall be provided. Simultaneous economizer/com-pressor operation is also possible. Dampers shall fully close on power loss.

• MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air dampers are positioned by a 2-position, spring-return damper actuator. The maximum leakage rate for the out-door air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pres-sure differential of 0.5 IWG. A unit-mounted potentiome-ter shall be provided to adjust the outdoor damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

• ROOF CURB - 14"and 8” high, full perimeter curb with wood nailer (shipped knocked-down).

• BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit.

• PROPANE CONVERSION KIT - Contains new orifices and gas valve parts to convert from natural to L.P. gas. One per unit required.

• HIGH ALTITUDE - NATURAL GAS - Contains orifices required for applications between 2000 and 6000 feet altitude.

• HIGH ALTITUDE - PROPANE GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. Must be used with propane conversion kit.

• LOW NOX - Required to reduce the emission of nitrogen oxides below 40 nanograms per joule.

• GAS PIPING - Contains 1/2” pipe nipples, fittings and gas cock (including panel assess gaskets) required for bottom gas supply connection with external shut off.

• POWER EXHAUST OPTION - To work in conjunction with economizers.

• ELECTRIC HEATERS

• ECONOMIZER/MOTORIZED DAMPER RAIN HOOD -Contains all hood panels and the hardware for assem-bling.

• MANUAL OUTDOOR AIR DAMPER

• COIL GUARD KIT - Guard for cooling coil.

• HAIL GUARD

• FLUE EXHAUST EXTENSION

OTHER FACTORY INSTALLED OPTIONS

• POWER EXHAUST OPTION - To work in conjunction with economizers.

• STAINLESS STEEL HEAT EXCHANGER

• STAINLESS STEEL DRAIN PAN

• BOTTOM DRAIN CONNECTION

• TECHNICOAT PHENOLIC COATED CONDENSER AND EVAPORATOR COIL

• ELECTRONIC SINGLE ENTHALPY ECONOMIZER

• DIRTY FILTER SWITCH

• PHASE MONITOR

• COIL GUARD

• POWERED GFI CONVENIENCE OUTLET

• NON-POWERED GFI CONVENIENCE OUTLET

• BAS CONTROLS (Simplicity™ INTELLI- Comfort™, CPC, JOHNSON, HONEYWELL, NOVAR)

• BAS READY ECONOMIZER (BELIMO ACTUATOR WITHOUT A CONTROLLER)

• HINGED FILTER DOOR ACCESS AND TOOLESS ACCESS PANELS

• 2" PLEATED FILTERS

• DISCONNECT SWITCH

• SUPPLY AIR SMOKE DETECTOR

• RETURN AIR SMOKE DETECTOR

54 Unitary Products Group

Page 55: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

036-21685-001-A-0505

Unitary Products Group 55

Page 56: Y-TG, DR036 thru 072, Single Package Gas/Elec and Single … · 036-21685-001-a-0505 for distribution use only - not to be used at point of retail sale technical guide single package

Subject to change without notice. Printed in U.S.A. 036-21685-001-A-0505Copyright © 2005 by Unitary Products Group. All rights reserved. Supersedes: Nothing

Unitary 5005 NormanProducts York OKGroup Drive 73069