036-21510-003-A-0204
SING
AND
AIR C
DM 03
3, 4, 5
TEC
LE PACKAGE GAS/ELECTRIC UNITS
SINGLE PACKAGE
ONDITIONERS
6, 048, 060 & 076
& 6.3 NOMINAL TONS
� �
HNICAL GUIDE
DESCRIPTION
YORK Sunline 2000TM units are convertible single package air conditioners with a common cabinet and a common roof curb for the 3, 4, 5 and 6.3 ton sizes. The units were designed for light commercial and commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame.
All units include:
• Powder Paint finish that meets ASTM-B-117 750 hour salt spray standards
• Permanently lubricated motors
• Bottom or side air discharge configuration capability (field convertible)
• Manufactured under the quality standards of ISO9001
• ����������TM Control Board
• Copper tube/aluminum fin coils
• Easy access to all components
• Rigging holes in base rails for lifting
• Fork lift slots on three sides
• Single point power connection
• Complete factory package - tested, charged and wired
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21510-003-A-0204
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 8
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . 10
Fig. # Pg. #LIST OF FIGURES
1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2 TYPICAL FIELD POWER & CONTROL WIRING . . 22
3 UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . . . . 23
4 UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . 23
5 UNIT WITH ECONOMIZER RAINHOOD . . . . . . . . 24
6 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD . . . . . . . . . . . . . . . . . . . . . . . 24
7 UNIT DIMENSIONS (REAR VIEW) . . . . . . . . . . . . . 25
8 DISCONNECT/BLOWER ACCESS LOCATION . . . 25
9 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . 26
10 FOUR AND SIX POINT LOADING . . . . . . . . . . . . . 27
11 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . . . 28
Tbl. # Pg. #LIST OF TABLES
1 SOUND POWER RATING . . . . . . . . . . . . . . . . . . . 11
2 CAPACITY RATINGS - (ARI 210/240) . . . . . . . . . . 11
3 GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . 11
4 DM036 COOLING CAPACITIES (3 TON) . . . . . . . 12
5 DM048 COOLING CAPACITIES (4 TON) . . . . . . . 13
6 DM060 COOLING CAPACITIES (5 TON) . . . . . . . 14
7 DM076 COOLING CAPACITIES (6.3 TON) . . . . . . 15
8 SUPPLY AIR BLOWER PERFORMANCE (3 & 4 TON DIRECT DRIVE) - SIDE DUCT APPLICATION. . . . 16
9 SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION . . . . . 17
10 SUPPLY AIR BLOWER PERFORMANCE (6.3 TON BELT DRIVE) - SIDE DUCT APPLICATION . . . . . 18
11 BELT DRIVE MOTOR AND DRIVE DATA . . . . . . . . . . 19
12 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . 19
13 ELECTRIC HEATER SUPPLY AIR LIMITATIONS 19
14 ELECTRICAL DATA: 3 - 6.3 TON . . . . . . . . . . . . . 20
15 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . 21
16 ELECTRIC HEAT CORRECTION FACTORS . . . . 21
17 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . 21
18 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . . . 25
19 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . 25
20 DM 4 POINT LOADS WEIGHT DISTRIBUTION. . . 27
21 DM 6 POINT LOADS WEIGHT DISTRIBUTION. . . 27
22 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . 27
23 OPERATING WEIGHTS (KG / LBS.) . . . . . . . . . . . 28
2 Unitary Products Group
036-21510-003-A-0204
PRODUCT NOMENCLATURE
3-6 Ton Sunline Model Number Nomenclature
Product Catagory
D = Air Cond., Single Package
Airflow
A = Direct Drive (Must be ordered on 3 & 4-ton models)
B = Direct Drive/Single Input Econo
D = Direct Drive/Motorized Damper
L = Direct Drive/BAS Ready Econ (No BAS Controller)/2" Pleated Filters/Extra xfrmr & circuit bkr.
N = Belt Drive (Must be ordered on 5 & 6.3-ton models)
P = Belt Drive/Single Input Econo
R = Belt Drive/Motorized Damper
Y = Belt Drive/BAS Ready Econ (No BAS Controller) w/2" Pleated Filters
Additional Options
(See Next Page)
Product Generation
1 = First Generation
Product Identifier
M = R-22 Standard Efficiency (DCG/DCE)
Installation Options
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
Options
1 = Disconnect
2 = Non-Pwr'd Conv Oultet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
D M C00 A7A AA 1048
Heat Type & Nominal Heat Capacity
C00 = Cooling Only. Suitable for field installed electric heat
Electric Heat Options
E07 = 7 kW Electric Heat
E10 = 10 kW Electric Heat
E15 = 15 kW Electric Heat
E20 = 20 kW Electric Heat
E30 = 30 kW Electric Heat
Voltage
7 = 380/415-3-50
Nominal Cooling
Capacity - MBH
036 = 3 Ton
048 = 4 Ton
060 = 5 Ton
076 = 6.3 Ton
Unitary Products Group 3
036-21510-003-A-0204
PRODUCT NOMENCLATURE - Continued3-6T Sunline Model Number Nomenclature
Additional Options
AA None
AB Phase Monitor
AC Coil Guard
AD Dirty Filter Switch
AE Phase Monitor & Coil Guard
AF Phase Monitor & Dirty Filter Switch
AG Coil Guard & Dirty Filter Switch
AH Phase Monitor, Coil Guard, & Dirty Filter Switch
AS Bottom Condensate Pan
BA Hinged Filter Door & Toolless Access Panels
BB Phase Monitor, Hinged Filter Door & Toolless Access Panels
BC Coil Guard, Hinged Filter Door & Toolless Access Panels
BD Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BE Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels
BF Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BG Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BH Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
CA CPC Controller with Dirty Filter Switch & Air Proving Switch
CB CPC Controller, DFS, APS & Phase Monitor
CC CPC Controller, DFS, APS & Coil Guard
CD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CE CPC Controller, DFS, APS & Technicoat Cond. Coil
CF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CJ CPC Controller, DFS, APS & Technicoat Evap. Coil
CK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
DA CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
DB CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DC CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
DD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DE CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
DF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DJ CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
DK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
DP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
4 Unitary Products Group
036-21510-003-A-0204
EA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
EB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
ED Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
EF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
EK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
EP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
ER Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
GB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GC Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
GD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
GF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
GK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
GP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless AccessPanels
GQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
HA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
HB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard
HD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
HE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
HF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
HG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
HH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
HJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
HK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
HM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
HN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
HP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
HR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Additional Options
Unitary Products Group 5
036-21510-003-A-0204
JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
JB Johnson UNT Controller, DFS, APS & Phase Monitor
JC Johnson UNT Controller, DFS, APS & Coil Guard
JD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
JF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
JH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
JJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
JK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
JL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
JM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
JN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
JP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
JR Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
NB Novar ETC-3 Controller, DFS, APS & Phase Monitor
NC Novar ETC-3 Controller, DFS, APS & Coil Guard
ND Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
NF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
NH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
NK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
NL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
NM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
NP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
NR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
PA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
PB Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PC Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
PD Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
PF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
PK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
PP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
RC Coil Guard & American “Made in USA” Flag
TA Technicoat Condenser Coil
TB Technicoat Condenser Coil & Phase Monitor
Additional Options
6 Unitary Products Group
036-21510-003-A-0204
TC Technicoat Condenser Coil & Coil Guard
TD Technicoat Condenser Coil & Dirty Filter Switch
TE Technicoat Condenser Coil, Phase Monitor, & Coil Guard
TF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
TH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TJ Technicoat Evaporator Coil
TK Technicoat Evaporator Coil & Phase Monitor
TL Technicoat Evaporator Coil & Coil Guard
TM Technicoat Evaporator Coil & Dirty Filter Switch
TN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
TP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
TR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TS Technicoat Evaporator & Condenser Coils
TT Technicoat Evaporator & Condenser Coils & Phase Monitor
TU Technicoat Evaporator & Condenser Coils & Coil Guard
TV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
TW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
TX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
TY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
TZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
UA Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels
UB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UJ Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels
UK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
US Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels
UT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels
UV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Additional Options
Unitary Products Group 7
036-21510-003-A-0204
FEATURES
All models are available with a wide variety of factory-mounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter base rails with forklift holes on three sides and holes for over-head rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.
All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizon-tal duct, remove the supply and return air panels on the rear of the unit.
All models are available with these “factory mounted” outdoor air damper options:
• Single enthalpy economizer
• Motorized outdoor air damper
Supply air blowers are equipped with either a direct drive or a belt drive that can be adjusted to meet the exact require-ments of the job.
All compressors are equipped with internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch to protect all system compo-nents.
• ����������™ Controls - ����������™ control boards have standardized a number of features previously available only as options or by utilizing additional controls.
• Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assis-tance. Optionally, the control board can be pro-grammed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
• Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.
• Fan Delays - Fan on and fan off delays are fully pro-grammable and are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.
• Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.
• Nuisance Trip Protection- To prevent nuisance trouble calls, the control board uses a “three strikes, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the compressor.
• On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.
All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTM-B117 procedures.
• Gas Heat Operation - All gas heat units have a mini-mum AFUE of 80%. Each section includes a durable heat exchanger with aluminized steel or optional stain-less steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of
the unit.
• Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uni-form distribution of air across the heating elements. Every element is fully protected against excessive tem-perature by thermal limit switches.
The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the side of the unit.
• BAS Controls - York’s Sunline™ series units offer fac-tory mounted BAS controls such as Novar, Honeywell, Johnson, and CPC.
FACTORY-INSTALLED OPTIONS• SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capa-ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
8 Unitary Products Group
036-21510-003-A-0204
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
• MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2-position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is oper-ating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
• PHENOLIC COATED EVAPORATOR AND CON-DENSER COILS - Special coating process that utilizes
Technicoat 10-1TM processes. Coating is applied by total immersion of the complete coil for maximum protection.
• ELECTRIC HEATERS wired for single point power sup-ply. These nickel chromium heater elements are pro-vided with limit and automatic reset capability to prevent operation at excessive temperatures.
• FILTER OPTIONS - Standard units are shipped with 25mm (1”) throw-away filters installed. 50mm (2”) pleated filters are offered as a factory installed option.
• CONVENIENCE OUTLET - The unit may be ordered with a “non-powered” convenience outlet that can be wired in the field.
• DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.
• BAS - See “Additional Options” section in the product nomenclature.
• SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
• COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
• STAINLESS STEEL HEAT EXCHANGER - For applica-tions in corrosive environments, this option provides a full stainless steel heat exchanger assembly.
FIGURE 1 - UNIT CUTAWAY
Unitary Products Group 9
036-21510-003-A-0204
• PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of-phase condition.
• DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
• HINGED FILTER DOOR/“TOOLLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance.
NOTE:Knobs are shipped inside the unit to prevent ship-ping damage. These must be field installed for tool-less operation.
FIELD-INSTALLED ACCESSORIES• SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capa-ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
• MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2-position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
• ELECTRIC HEATERS wired for single point power sup-ply. These nickel chromium heater elements are pro-vided with limit and automatic reset capability to prevent operation at excessive temperatures.
• ROOF CURBS - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the fin-ished roof. These full perimeter curbs meet the require-ments of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assem-bly.
Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.
• HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.
• PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.
• HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at alti-tudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.
• POWER EXHAUST - Our single input economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the condi-tioned space from being over-pressurized during econo-mizer operation.
The power exhaust option can only be used on bot-tom duct configurations.
• BAROMETRIC RELIEF DAMPER - This damper acces-sory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
• ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
• BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.
• FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.
• CO2 SENSOR - Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits.
• COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
• PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of-phase condition.
10 Unitary Products Group
036-21510-003-A-0204
TABLE 1: SOUND POWER RATING1
UNITSIZE
CFMESP BLOWER
SOUND POWER (db 10-12 Watts)
Octave Band Centerline Frequency (Hz)SWLdB(A)
dB(A)@
10Ft.2IWG SPEED KW 63 125 250 500 1,000 2,000 4,000 8,000
036 1,200 0.6 LOW 0.60 84 84 74 67 69 62 57 52 74 41
048 1,600 0.55 HIGH 0.80 85 85 75 68 70 63 58 53 75 42
060 2,000 0.45 HIGH 1.00 86 86 76 69 71 64 59 54 76 43
076 2,200 0.3 HIGH 1.35 87 87 77 70 72 65 60 55 77 44
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-tee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
TABLE 2: CAPACITY RATINGS - (ARI 210/240)
UNIT SIZE (MBH) RATING POINT1 INDOOR DB/WB
OUTDOOR
DB/WB
TOTAL OUTPUT
kW/MBHTOTAL INPUT kW COP
2
ELECTRIC HEAT
NOMINAL
CAPACITY kW
T1 27 / 19 35 / 24 10.6 / 36.1 3.8 2.8 5.1, 7.5
T2 29 / 19 46 / 24 8.9 / 30.3 4.2 2.1 10.2, 14.6
T3 21 / 15 27 / 19 9.9 / 33.7 3.4 2.9
T1 27 / 19 35 / 24 13.5 / 46.0 4.9 2.7 5.1, 7.5
T2 29 / 19 46 / 24 11.0 / 37.5 4.0 2.7 10.2, 14.6
T3 21 / 15 27 / 19 12.2 / 41.6 4.4 2.8
T1 27 / 19 35 / 24 17.3 / 59.0 6.2 2.8 5.1, 7.5
T2 29 / 19 46 / 24 14.6 / 49.8 6.8 2.1 10.2, 14.6
T3 21 / 15 27 / 19 16.5 / 56.3 5.4 3.1 21.5
T1 27 / 19 35 / 24 20.5 / 69.9 8.6 2.4 5.1, 7.5
T2 29 / 19 46 / 24 16.2 / 55.3 9.4 1.7 10.2, 14.6
T3 21 / 15 27 / 19 19.6 / 66.9 7.8 2.5 21.5
076
036
048
060
1 . T1 = Moderate Climates, T2 = Hot Climates, T3 = Cool Climates.
2. COP = Coefficient of Performance - total output kW divided by the total input kW.
TABLE 3: GAS HEAT RATINGS
°C °F
T1 27 / 19 35 / 24 10.6 / 36.1 3.8 2.8
T2 29 / 19 46 / 24 8.9 / 30.3 4.2 2.1
T3 21 / 15 27 / 19 9.9 / 33.7 3.4 2.9
T1 27 / 19 35 / 24 13.5 / 46.0 4.9 2.7
T2 29 / 19 46 / 24 11.0 / 37.5 4.0 2.7
T3 21 / 15 27 / 19 12.2 / 41.6 4.4 2.8
T1 27 / 19 35 / 24 17.3 / 59.0 6.2 2.8
T2 29 / 19 46 / 24 14.6 / 49.8 6.8 2.1
T3 21 / 15 27 / 19 16.5 / 56.3 5.4 3.1
T1 27 / 19 35 / 24 20.5 / 69.9 8.6 2.4
T2 29 / 19 46 / 24 16.2 / 55.3 9.4 1.7
T3 21 / 15 27 / 19 19.6 / 66.9 7.8 2.5
14-31 25-55
14-31 25-55
8-25 15-45
14-31 25-55
11.7 / 39.9
17.6 / 60.0
23.1 / 78.8
23.1 / 78.8
22.0
29.3
29.3
14.6
INDOOR
DB/WB
RATING
POINT1
UNIT SIZE
(MBH)COP
2TOTAL
INPUT kW
TOTAL
OUTPUT
kW/MBH
OUTDOOR
DB/WB
GAS HEATING
TEMPERATURE RISE
(MIN-MAX)INPUT (NET)
Kw
OUTPUT
kW/MBH
076
036
048
060
1 . T1 = Moderate Climates, T2 = Hot Climates, T3 = Cool Climates.
2. COP = Coefficient of Performance - total output kW divided by the total input kW.
Unitary Products Group 11
036-21510-003-A-0204
TABLE 4: DM036 COOLING CAPACITIES (3 TON)
M3/S
WB
°C31 28 25 22 31 28 25 22 31 28 25 22
23 13.6 3.2 9.4 6.9 4.4 - 12.7 3.6 9.3 6.7 4.2 - 11.4 4.1 9.0 6.4 3.9 -
20 12.7 3.2 12.4 9.8 7.1 4.6 12.0 3.5 12.0 9.6 6.9 4.4 10.9 4.0 10.9 9.2 6.6 4.1
17 12.6 3.2 12.6 11.9 10.1 7.4 11.9 3.5 11.9 11.2 9.8 7.1 10.9 4.0 10.9 10.2 9.4 6.8
14 12.6 3.2 12.6 11.9 11.2 10.2 11.9 3.5 11.9 11.2 10.5 9.8 10.9 4.0 10.9 10.2 9.5 8.8
23 13.2 3.2 8.1 6.0 4.1 - 12.3 3.5 7.9 5.8 3.8 - 11.1 4.0 7.7 5.5 3.5 -
20 12.2 3.1 10.6 8.4 6.3 4.3 11.4 3.5 10.4 8.2 6.1 4.1 10.3 3.9 10.0 7.9 5.8 3.7
17 11.8 3.1 11.8 10.8 8.7 6.5 11.1 3.4 11.1 10.5 8.4 6.3 10.2 3.9 10.2 9.5 8.1 6.0
14 11.7 3.1 11.7 11.1 10.4 8.9 11.1 3.4 11.1 10.5 9.8 8.6 10.2 3.9 10.2 9.5 8.9 8.2
23 12.8 3.2 7.1 5.4 3.8 - 12.0 3.5 6.9 5.2 3.6 - 10.8 4.0 6.6 4.9 3.3 -
20 11.7 3.1 9.2 7.4 5.7 4.1 11.0 3.4 9.0 7.2 5.5 3.8 9.9 3.9 8.7 6.9 5.1 3.5
17 11.0 3.0 11.0 9.5 7.7 5.9 10.4 3.4 10.4 9.3 7.4 5.7 9.5 3.8 9.5 8.9 7.1 5.3
14 10.9 3.0 10.9 10.3 9.7 7.9 10.4 3.4 10.4 9.8 9.2 7.6 9.5 3.8 9.5 8.9 8.3 7.3
CFMWB
°F86 80 74 68 86 80 74 68 86 80 74 68
72 42.4 3.6 31.6 21.6 12.0 - 40.3 3.8 31.1 21.1 11.5 - 38.1 4.1 30.6 20.5 11.0 -
67 40.1 3.5 40.1 30.7 20.6 11.1 38.4 3.7 38.4 30.1 20.0 10.6 36.6 4.0 36.6 29.6 19.4 10.0
62 40.1 3.5 40.1 37.3 29.7 19.6 38.3 3.7 38.3 35.6 29.0 18.9 36.5 4.0 36.5 33.8 28.4 18.3
57 40.0 3.5 40.0 37.3 34.6 28.6 38.3 3.7 38.3 35.6 33.0 27.9 36.5 4.0 36.5 33.8 31.2 27.3
72 41.3 3.5 27.3 19.1 11.5 - 39.2 3.8 26.8 18.6 10.9 - 37.0 4.0 26.3 18.1 10.4 -
67 38.4 3.4 35.2 26.6 18.5 10.8 36.4 3.7 34.5 26.1 18.0 10.3 34.5 3.9 33.8 25.6 17.4 9.7
62 37.6 3.4 37.6 34.3 26.0 17.9 36.0 3.7 36.0 33.5 25.4 17.2 34.3 3.9 34.3 31.9 24.8 16.7
57 37.5 3.4 37.5 35.0 32.6 25.2 35.9 3.7 35.9 33.5 31.0 24.6 34.2 3.9 34.2 31.8 29.4 23.9
72 39.5 3.5 22.6 16.5 10.9 - 37.5 3.7 22.1 16.0 10.4 - 35.5 4.0 21.6 15.5 9.8 -
67 36.3 3.4 28.8 22.4 16.3 10.5 34.5 3.6 28.3 21.8 15.7 9.9 32.7 3.8 27.9 21.3 15.1 9.3
62 34.0 3.3 34.0 28.5 22.0 15.8 32.6 3.5 32.6 28.1 21.4 15.2 31.1 3.8 31.1 27.5 20.8 14.6
57 34.0 3.3 34.0 31.8 28.1 21.5 32.5 3.5 32.5 30.4 27.5 20.9 31.1 3.8 31.1 28.9 26.7 20.3
NOMINAL RATING
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
SENSIBLE CAPACITY1, MBH TOTAL
CAP.1
MBH
POWER
INPUT2
kW
SENSIBLE CAPACITY1, MBH
35°C
TOTAL
CAP.1
kW
POWER
INPUT2
kW
46°C
ENTERING DRY BULB, °C
SENSIBLE CAPACITY1, kWSENSIBLE CAPACITY
1, kW
ENTERING DRY BULB, °C
1500
1200
900
POWER
INPUT2
kW
AIR ON
COOLING
COILSENSIBLE CAPACITY
1, MBHTOTAL
CAP.1
MBH
POWER
INPUT2
kW
TOTAL
CAP.1
MBH
ENTERING DRY BULB, °F
M3/S
CFMTEMPERATURE OF AIR ON CONDENSER COIL
95°F 105°F 115°F
AIR ON
COOLING
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
27°C
ENTERING DRY BULB, °C
0.45
POWER
INPUT2
kW
0.70
0.55
TOTAL
CAP.1
kW
POWER
INPUT2
kW
TOTAL
CAP.1
kW
SENSIBLE CAPACITY1, kW
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.46kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
12 Unitary Products Group
036-21510-003-A-0204
TABLE 5: DM048 COOLING CAPACITIES (4 TON)
M3/S
WB
°C31 28 25 22 31 28 25 22 31 28 25 22
23 17.4 4.1 12.2 8.6 5.2 - 16.2 4.5 12.2 8.3 5.0 - 14.6 5.2 11.9 8.0 4.7 -
20 16.6 4.0 16.6 12.8 9.0 5.6 15.7 4.4 15.7 12.6 8.7 5.3 14.3 5.1 14.3 12.3 8.4 4.9
17 16.6 4.0 16.6 15.6 13.3 9.4 15.6 4.4 15.6 14.7 13.0 9.2 14.3 5.1 14.3 13.3 12.4 8.8
14 16.6 4.0 16.6 15.6 14.6 13.7 15.6 4.4 15.6 14.7 13.7 12.8 14.2 5.1 14.2 13.3 12.4 11.5
23 17.0 4.0 10.5 7.6 4.8 - 15.8 4.5 10.3 7.3 4.6 - 14.2 5.1 10.0 7.0 4.2 -
20 15.7 3.9 14.1 10.9 7.9 5.1 14.6 4.3 13.9 10.7 7.7 4.9 13.4 5.0 13.4 10.5 7.3 4.5
17 15.5 3.9 15.5 14.6 11.5 8.3 14.7 4.3 14.7 13.8 11.2 8.1 13.4 5.0 13.4 12.5 10.8 7.7
14 15.5 3.9 15.5 14.6 13.7 11.9 14.6 4.3 14.6 13.8 12.9 11.6 13.4 5.0 13.4 12.5 11.7 10.9
23 16.2 4.0 8.5 6.4 4.4 - 15.1 4.4 8.3 6.1 4.1 - 13.6 5.0 8.0 5.8 3.8 -
20 14.7 3.9 11.3 9.0 6.8 4.7 13.8 4.2 11.1 8.8 6.5 4.4 12.5 4.8 10.8 8.4 6.1 4.0
17 17.0 3.8 14.0 11.8 9.4 7.1 13.2 4.2 13.2 11.5 9.2 6.8 12.1 4.8 12.1 11.2 8.8 6.4
14 13.9 3.8 13.9 13.2 12.2 9.8 13.2 4.2 13.2 12.4 11.7 9.5 12.1 4.8 12.1 11.4 10.6 9.1
CFMWB
°F86 80 74 68 86 80 74 68 86 80 74 68
72 54.1 4.5 40.6 26.5 14.0 - 51.4 4.8 40.3 26.0 13.4 - 48.6 5.1 39.7 25.3 12.8 -
67 52.3 4.4 52.3 39.9 25.5 12.8 50.0 4.7 50.0 39.3 24.9 12.1 47.6 5.0 47.6 38.7 24.0 11.5
62 52.2 4.4 52.2 48.7 38.8 24.4 49.9 4.7 49.9 46.4 38.1 23.7 47.5 5.0 47.5 44.1 37.5 22.9
57 52.2 4.4 52.2 48.6 45.1 37.5 49.9 4.7 49.9 46.4 42.9 36.7 47.4 5.0 47.4 44.0 40.7 35.7
72 52.8 4.4 34.9 23.7 13.2 - 50.1 4.7 34.6 22.9 12.6 - 47.3 5.1 33.8 22.3 12.0 -
67 49.0 4.3 46.4 34.3 23.0 12.4 46.6 4.6 45.6 33.9 22.0 11.8 44.9 4.9 44.9 33.3 21.7 11.1
62 49.2 4.3 49.2 45.9 33.7 22.1 47.0 4.6 47.0 43.8 33.1 21.4 44.8 4.9 44.8 41.7 32.5 20.7
57 49.1 4.3 49.1 45.8 42.6 32.9 47.0 4.6 47.0 43.7 40.5 32.2 44.7 4.9 44.7 41.6 38.5 31.1
72 50.7 4.3 28.8 20.3 12.5 - 48.2 4.6 28.3 19.7 11.9 - 45.5 5.0 27.8 19.1 11.3 -
67 46.6 4.2 37.8 28.7 19.9 12.1 44.3 4.5 37.3 28.1 19.3 11.4 41.9 4.8 36.7 27.4 18.6 10.7
62 44.7 4.2 44.7 37.7 28.4 19.5 42.8 4.5 42.8 36.9 27.7 18.8 40.9 4.8 40.9 36.1 26.9 18.1
57 44.7 4.2 44.7 41.8 37.2 27.8 42.8 4.4 42.8 39.9 36.5 27.1 40.8 4.7 40.8 38.0 35.3 26.1
NOMINAL RATING
1600
1200
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
2000
AIR ON
COOLING
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
95°F 105°F 115°F
TOTAL
CAP.1
MBH
POWER
INPUT2
kW
SENSIBLE CAPACITY1, MBH TOTAL
CAP.1
MBH
POWER
INPUT2
kW
ENTERING DRY BULB, °F
SENSIBLE CAPACITY1, MBHSENSIBLE CAPACITY
1, MBH TOTAL
CAP.1
MBH
POWER
INPUT2
kW
0.95
0.75
0.55
CFM
SENSIBLE CAPACITY1, kW
ENTERING DRY BULB, °C ENTERING DRY BULB, °C ENTERING DRY BULB, °CPOWER
INPUT2
kW
SENSIBLE CAPACITY1, kW TOTAL
CAP.1
kW
POWER
INPUT2
kW
M3/S
AIR ON
COOLING
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
27°C 35°C 46°C
TOTAL
CAP.1
kW
POWER
INPUT2
kW
SENSIBLE CAPACITY1, kW TOTAL
CAP.1
kW
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.46kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
Unitary Products Group 13
036-21510-003-A-0204
TABLE 6: DM060 COOLING CAPACITIES (5 TON)
M3/S
WB
°C31 28 25 22 31 28 25 22 31 28 25 22
23 22.1 5.5 15.4 11.1 7.1 - 20.7 6.1 15.1 10.7 6.8 - 18.9 6.9 14.8 10.4 6.4 -
20 20.9 5.4 20.9 15.9 11.5 7.5 19.9 6.0 19.9 15.6 11.2 7.2 18.3 6.8 18.3 15.2 10.8 6.6
17 20.9 5.4 20.9 19.7 16.5 12.0 19.8 6.0 19.8 18.6 16.0 11.5 18.3 6.8 18.3 17.1 15.6 11.0
14 20.9 5.4 20.9 19.7 18.5 17.3 19.8 6.0 19.8 18.6 17.4 16.3 18.3 6.8 18.3 17.1 15.9 14.8
23 21.6 5.5 13.7 10.1 6.6 - 20.3 6.1 13.4 9.8 6.3 - 18.5 6.8 13.1 9.4 5.9 -
20 20.0 5.3 18.1 14.2 10.5 7.0 18.8 5.9 17.8 13.9 10.2 6.7 17.4 6.6 17.4 13.6 9.8 6.2
17 19.9 5.3 19.9 18.7 14.8 11.0 18.8 5.9 18.8 17.7 14.4 10.6 17.4 6.6 17.4 16.3 13.8 10.1
14 19.8 5.3 19.8 18.7 17.6 15.1 18.8 5.9 18.8 17.7 16.6 14.7 17.4 6.6 17.4 16.3 15.2 14.1
23 20.9 5.4 12.0 9.1 6.2 - 19.7 6.0 11.7 8.8 5.9 - 17.9 6.7 11.3 8.3 5.5 -
20 19.2 5.3 15.6 12.5 9.5 6.6 18.0 5.8 15.3 12.2 9.2 6.2 16.4 6.4 14.8 11.7 8.7 5.8
17 18.5 5.2 18.5 16.0 12.9 9.9 17.5 5.7 17.5 15.7 12.5 9.5 16.2 6.4 16.2 15.2 12.1 9.0
14 18.5 5.2 18.5 17.4 16.4 13.3 17.5 5.7 17.5 16.5 15.5 13.0 16.2 6.4 16.2 15.2 14.2 12.4
CFMWB
°F86 80 74 68 86 80 74 68 86 80 74 68
72 69.2 6.0 51.0 34.5 19.3 - 66.0 6.4 50.5 33.9 18.6 - 63.0 6.8 50.1 33.1 17.9 -
67 66.4 5.9 66.4 49.7 33.1 17.8 63.9 6.3 63.9 48.9 32.4 17.0 61.1 6.7 61.1 48.1 31.5 16.1
62 66.3 5.9 66.3 61.8 48.3 31.7 63.7 6.3 63.7 56.2 47.3 30.7 61.0 6.7 61.0 56.6 46.6 29.8
57 66.2 5.9 66.2 61.8 57.4 46.5 63.6 6.3 63.6 56.2 54.8 45.5 60.9 6.7 60.9 56.5 52.2 44.8
72 67.6 6.0 45.2 31.7 18.5 - 64.5 6.4 44.6 31.0 17.8 - 61.5 6.7 44.2 30.2 17.0 -
67 62.9 5.8 58.8 44.3 30.7 17.4 60.0 6.2 58.5 43.5 29.9 16.5 58.2 6.6 58.2 43.1 29.0 15.7
62 63.1 5.8 63.1 58.9 43.2 29.5 60.7 6.2 60.7 56.5 42.7 28.5 58.1 6.6 58.1 53.9 41.8 27.6
57 63.0 5.8 63.0 58.8 54.7 42.0 60.6 6.2 60.6 56.3 52.3 41.3 58.0 6.6 58.0 53.8 49.7 40.4
72 65.6 5.9 39.8 28.4 17.7 - 62.6 6.3 38.9 27.7 16.9 - 59.6 6.6 38.2 26.9 16.2 -
67 60.5 5.7 50.9 38.9 27.8 17.0 57.8 6.1 50.2 38.4 26.9 16.1 54.9 6.4 49.3 37.4 26.1 15.2
62 58.8 5.7 58.8 50.3 38.4 27.0 56.5 6.0 56.5 49.3 37.5 26.0 54.1 6.3 54.1 48.7 36.7 25.1
57 58.7 5.6 58.7 54.9 49.5 37.3 56.4 6.0 56.4 52.6 48.9 36.5 54.0 6.3 54.0 50.2 46.6 35.6
NOMINAL RATING
2000
1600
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
2400
AIR ON
COOLING
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
95°F 105°F 115°F
TOTAL
CAP.1
MBH
POWER
INPUT2
kW
SENSIBLE CAPACITY1, MBH TOTAL
CAP.1
MBH
POWER
INPUT2
kW
ENTERING DRY BULB, °F
SENSIBLE CAPACITY1, MBHSENSIBLE CAPACITY
1, MBH TOTAL
CAP.1
MBH
POWER
INPUT2
kW
1.15
0.95
0.75
CFM
SENSIBLE CAPACITY1, kW
ENTERING DRY BULB, °C ENTERING DRY BULB, °C ENTERING DRY BULB, °CPOWER
INPUT2
kW
SENSIBLE CAPACITY1, kW TOTAL
CAP.1
kW
POWER
INPUT2
kW
M3/S
AIR ON
COOLING
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
27°C 35°C 46°C
TOTAL
CAP.1
kW
POWER
INPUT2
kW
SENSIBLE CAPACITY1, kW TOTAL
CAP.1
kW
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.46kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
14 Unitary Products Group
036-21510-003-A-0204
TABLE 7: DM076 COOLING CAPACITIES (6.3 TON)
M3/S
WB
°C31 28 25 22 31 28 25 22 31 28 25 22
23 26.8 7.1 19.8 15.3 11.0 - 25.1 7.8 19.4 14.7 10.5 - 22.6 8.9 18.9 14..0 9.7 -
20 25.8 6.9 25.8 20.0 15.6 11.2 24.4 7.7 24.4 19.6 14.9 10.6 22.3 8.8 2.3 18.7 14.2 9.8
17 25.8 6.9 25.8 24.3 20.2 15.7 24.3 7.7 24.3 22.9 19.6 15.0 22.2 8.8 22.2 20.8 19.5 14.3
14 25.7 6.9 25.7 24.2 22.8 21.4 24.3 7.7 24.3 22.8 21.4 20.1 22.2 8.8 22.2 20.8 19.5 18.2
23 26.2 7.0 18.1 14.3 10.5 - 24.5 7.7 17.6 13.8 10.0 - 22.1 8.8 16.8 13.0 9.2 -
20 24.2 6.8 22.1 18.3 14.5 10.8 22.7 7.5 21.5 17.7 13.9 10.2 21.2 8.6 21.2 16.9 13.0 9.3
17 24.4 6.8 24.4 23.0 18.4 14.6 23.1 7.5 23.1 21.7 17.8 14.1 21.1 8.6 21.1 19.9 17.0 13.2
14 24.4 6.8 24.4 23.0 21.6 18.5 23.0 7.5 23.0 21.7 20.4 17.8 21.1 8.6 21.1 19.8 18.5 17.3
23 25.0 6.9 15.8 12.9 9.7 - 23.5 7.6 15.2 12.3 9.2 - 21.2 8.6 14.4 11.5 8.4 -
20 22.9 6.6 18.9 16.0 13.0 9.9 21.5 7.3 18.3 15.3 12.5 9.4 19.5 8.2 17.4 14.6 11.6 8.6
17 22.1 6.5 22.1 19.0 16.0 13.1 21.0 7.2 21.0 18.3 15.5 12.5 19.3 8.2 19.3 17.6 14.6 11.7
14 22.1 6.5 22.1 20.9 19.7 16.0 20.9 7.2 20.9 19.8 18.9 15.5 19.3 8.2 19.3 18.1 17.0 14.6
CFMWB
°F86 80 74 68 86 80 74 68 86 80 74 68
72 83.9 7.7 65.6 47.9 31.2 - 79.6 8.2 64.0 46.9 29.9 - 75.4 8.8 63.0 45.2 28.5 -
67 81.7 7.6 81.7 62.8 45.6 28.5 78.3 8.2 78.3 61.5 44.4 27.1 74.6 8.7 74.6 60.4 43.0 25.7
62 81.6 7.6 81.6 76.2 60.4 43.5 78.1 8.2 78.1 72.8 58.9 41.6 74.4 8.7 74.4 69.2 57.8 40.4
57 81.5 7.6 81.5 76.1 70.7 58.0 78.0 8.2 78.0 72.6 67.4 56.5 74.3 8.7 74.3 69.1 64.1 54.8
72 81.7 7.6 58.9 44.6 29.7 - 77.7 8.1 57.6 43.2 28.4 - 73.6 8.7 56.3 41.8 27.1 -
67 76.0 7.4 71.2 56.9 42.7 27.7 72.3 7.9 69.6 55.3 41.0 26.3 70.6 8.5 70.6 54.1 39.5 24.9
62 77.0 7.4 77.0 71.9 54.7 40.4 73.7 7.9 73.7 68.8 53.4 38.9 70.3 8.5 70.3 65.5 51.8 37.3
57 76.8 7.4 76.8 71.8 66.9 52.7 73.6 7.9 73.6 68.6 63.8 50.9 70.2 8.5 70.2 65.5 60.6 49.6
72 78.2 7.5 51.3 40.4 28.2 - 74.6 8.0 50.2 39.1 26.9 - 70.6 8.5 48.6 37.7 25.6 -
67 72.0 7.2 60.9 50.0 38.7 26.8 68.7 7.7 59.9 48.4 37.5 25.4 65.3 8.2 58.4 47.2 35.9 24.0
62 70.3 7.2 70.3 59.6 48.4 37.1 67.4 7.6 67.4 57.9 46.7 35.6 64.5 8.1 64.5 56.5 45.4 34.2
57 70.1 7.1 70.1 65.7 57.6 46.6 67.3 7.6 67.3 62.9 56.1 45.1 64.5 8.2 64.5 60.0 55.8 42.9
NOMINAL RATING
2400
1800
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
3000
AIR ON
COOLING
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
95°F 105°F 115°F
TOTAL
CAP.1
MBH
POWER
INPUT2
kW
SENSIBLE CAPACITY1, MBH TOTAL
CAP.1
MBH
POWER
INPUT2
kW
ENTERING DRY BULB, °F
SENSIBLE CAPACITY1, MBHSENSIBLE CAPACITY
1, MBH TOTAL
CAP.1
MBH
POWER
INPUT2
kW
1.40
1.15
0.85
CFM
SENSIBLE CAPACITY1, kW
ENTERING DRY BULB, °C ENTERING DRY BULB, °C ENTERING DRY BULB, °CPOWER
INPUT2
kW
SENSIBLE CAPACITY1, kW TOTAL
CAP.1
kW
POWER
INPUT2
kW
M3/S
AIR ON
COOLING
COIL
TEMPERATURE OF AIR ON CONDENSER COIL
27°C 35°C 46°C
TOTAL
CAP.1
kW
POWER
INPUT2
kW
SENSIBLE CAPACITY1, kW TOTAL
CAP.1
kW
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.46kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
Unitary Products Group 15
036-21510-003-A-0204
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (3 & 4 TON DIRECT DRIVE) - SIDE DUCT APPLICATION
M3/S WATTS M
3/S WATTS M
3/S WATTS M
3/S WATTS M
3/S WATTS
HI - - - - 0.80 825 0.78 785 0.74 755
MED 0.79 800 0.77 780 0.75 750 0.72 720 0.67 690
LOW 0.70 710 0.69 690 0.67 670 0.64 650 0.62 620
HI 0.94 960 0.91 936 0.88 910 0.85 880 0.81 845
MED 0.85 838 0.83 810 0.80 785 0.78 765 0.75 735
LOW 0.79 760 0.77 738 0.76 715 0.73 695 0.70 670
M3/S WATTS M
3/S WATTS M
3/S WATTS M
3/S WATTS
HI 0.67 725 0.64 700 0.60 680 0.56 655
MED 0.62 650 0.59 630 0.59 610 0.52 590
LOW 0.59 605 0.56 590 0.55 570 0.48 545
HI 0.77 820 0.73 790 0.67 765 0.61 740
MED 0.71 705 0.66 675 0.61 645 0.56 625
LOW 0.67 645 0.63 620 0.58 595 0.53 575
CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS
HI - - - - 1699 825 1650 785 1570 755
MED 1684 800 1631 780 1582 750 1524 720 1410 690
LOW 1487 710 1464 690 1421 670 1367 650 1315 620
HI 1996 960 1933 936 1868 910 1795 880 1722 845
MED 1804 838 1765 810 1714 785 1650 765 1589 735
LOW 1681 760 1640 738 1604 715 1541 695 1490 670
CFM WATTS CFM WATTS CFM WATTS CFM WATTS
HI 1430 725 1360 700 1280 680 1180 655
MED 1324 650 1260 630 1185 610 1100 590
LOW 1246 605 1185 590 1110 570 1020 545
HI 1635 820 1544 790 1419 765 1300 740
MED 1508 705 1407 675 1306 645 1195 625
LOW 1416 645 1337 620 1230 595 1120 575
31
41
AVAILABLE EXTERNAL STATIC PRESSURE-Pa*
M3/S
14950 74 99 124UNIT
TONNAGEMOTOR SPEED
AVAILABLE EXTERNAL STATIC PRESSURE-Pa*
223198 248
31
41
174UNIT
TONNAGEMOTOR SPEED
CFM
UNIT
TONNAGEMOTOR SPEED
AVAILABLE EXTERNAL STATIC PRESSURE-IWG*
0.20 0.30 0.40 0.50 0.60
31
41
UNIT
TONNAGEMOTOR SPEED
31
41
AVAILABLE EXTERNAL STATIC PRESSURE-IWG*
0.70 0.80 0.90 1.00
1. Side Duct application (380/415 Volts)
* . Includes allowances for a wet evaporator coil, 25mm [1 in] filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance
values on applications other than gas/electric units with side duct airflows.
16 Unitary Products Group
036-21510-003-A-0204
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1.18 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 - -1.13 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 16401.08 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 15351.04 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1410 1117 14400.99 930 1060 957 1070 983 1080 1010 1100 1039 1160 1064 1260 1092 13400.94 877 950 908 975 941 1000 976 1020 1009 1050 1040 1100 1070 12250.90 - - - - 894 885 940 940 980 980 1014 1020 1047 10950.85 - - - - 855 815 903 860 950 905 988 940 1022 9700.80 - - - - - - 884 815 925 850 964 880 1001 9100.75 - - - - - - 864 770 908 805 948 835 987 8700.71 - - - - - - - - 882 740 926 780 965 830
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1.18 - - - - - - - - - - - - - -
1.13 - - - - - - - - - - - - - -1.08 1170 1580 - - - - - - - - - - - -1.04 1148 1480 1180 1530 - - - - - - - - - -0.99 1121 1385 1155 1425 - - - - - - - - - -0.94 1100 1285 1133 1340 1169 1385 - - - - - - - -0.90 1079 1180 1110 1240 1143 1280 1178 1330 - - - - - -0.85 1058 1060 1090 1135 1122 1190 1158 1240 - - - - - -0.80 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 - - - -0.75 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 - -
0.71 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 - -
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 - -2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 16402300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 15352200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1410 1117 14402100 930 1060 957 1070 983 1080 1010 1100 1039 1160 1064 1260 1092 13402000 877 950 908 975 941 1000 976 1020 1009 1050 1040 1100 1070 12251900 - - - - 894 885 940 940 980 980 1014 1020 1047 10951800 - - - - 855 815 903 860 950 905 988 940 1022 9701700 - - - - - - 884 815 925 850 964 880 1001 910
1600 - - - - - - 864 770 908 805 948 835 987 8701500 - - - - - - - - 882 740 926 780 965 830
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
2500 - - - - - - - - - - - - - -2400 - - - - - - - - - - - - - -2300 1170 1580 - - - - - - - - - - - -
2200 1148 1480 1180 1530 - - - - - - - - - -2100 1121 1385 1155 1425 - - - - - - - - - -2000 1100 1285 1133 1340 1169 1385 - - - - - - - -1900 1079 1180 1110 1240 1143 1280 1178 1330 - - - - - -1800 1058 1060 1090 1135 1122 1190 1158 1240 - - - - - -1700 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 - - - -
1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 - -1500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 - -
1.50
51
M3/S
CFM
51
UNIT
TONNAGE
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE-IWG*
0.90 1.00 1.10 1.20 1.30 1.40
UNIT
TONNAGE
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE-IWG*
0.20 0.30 0.40 0.50 0.60 0.70 0.80
51
AVAILABLE EXTERNAL STATIC PRESSURE-Pa*
223 248 273 298 322 347 372
UNIT
TONNAGE
AIR
FLOW
M3/S
51
UNIT
TONNAGE
AIR
FLOW
M3/S
149 174 198
AVAILABLE EXTERNAL STATIC PRESSURE-Pa*
50 74 99 124
1. Side duct application (380/415 Volts)
* . Includes allowances for a wet evaporator coil, 25mm [1in] filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
Unitary Products Group 17
036-21510-003-A-0204
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (6.3 TON BELT DRIVE) - SIDE DUCT APPLICATION
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1.50 1150 2325 1182 2425 - - - - - - - - - -
1.42 1100 2010 1129 2090 1157 2150 1185 2225 - - - - - -
1.32 1045 1700 1074 1780 1102 1850 1131 1940 1160 2025 1190 2075 - -
1.23 985 1425 1015 1475 1045 1540 1075 1630 1103 1715 1135 1760 1163 1825
1.13 930 1240 958 1300 990 1350 1020 1400 1051 1430 1081 1490 1111 1600
1.04 - - 905 1070 933 1160 965 1210 997 1250 1028 1285 1060 1325
0.94 - - - - - - 919 1025 950 1100 982 1130 1014 1160
0.85 - - - - - - - - 909 925 939 1005 968 1030
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
1.50 - - - - - - - - - - - - - -
1.42 - - - - - - - - - - - - - -
1.32 - - - - - - - - - - - - - -
1.23 1193 1920 - - - - - - - - - - - -
1.13 1142 1675 1173 1730 - - - - - - - - - -
1.04 1090 1380 1124 1450 1155 1550 1186 1640 - - - - - -
0.94 1045 1175 1077 1200 1109 1275 1140 1360 1170 1460 - - - -
0.85 998 1050 1028 1060 1058 1060 1087 1075 1118 1150 1148 1250 1176 1360
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
3200 1150 2325 1182 2425 - - - - - - - - - -
3000 1100 2010 1129 2090 1157 2150 1185 2225 - - - - - -
2800 1045 1700 1074 1780 1102 1850 1131 1940 1160 2025 1190 2075 - -
2600 985 1425 1015 1475 1045 1540 1075 1630 1103 1715 1135 1760 1163 1825
2400 930 1240 958 1300 990 1350 1020 1400 1051 1430 1081 1490 1111 1600
2200 - - 905 1070 933 1160 965 1210 997 1250 1028 1285 1060 1325
2000 - - - - - - 919 1025 950 1100 982 1130 1014 1160
1800 - - - - - - - - 909 925 939 1005 968 1030
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
3200 - - - - - - - - - - - - - -
3000 - - - - - - - - - - - - - -
2800 - - - - - - - - - - - - - -
2600 1193 1920 - - - - - - - - - - - -
2400 1142 1675 1173 1730 - - - - - - - - - -
2200 1090 1380 1124 1450 1155 1550 1186 1640 - - - - - -
2000 1045 1175 1077 1200 1109 1275 1140 1360 1170 1460 - - - -
1800 998 1050 1028 1060 1058 1060 1087 1075 1118 1150 1148 1250 1176 1360
1.50
6.31
M3/S
CFM
6.31
UNIT
TONNAGE
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE-IWG*
0.90 1.00 1.10 1.20 1.30 1.40
UNIT
TONNAGE
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE-IWG*
0.20 0.30 0.40 0.50 0.60 0.70 0.80
6.31
AVAILABLE EXTERNAL STATIC PRESSURE-Pa*
223 248 273 298 322 347 372
UNIT
TONNAGE
AIR
FLOW
M3/S
6.31
UNIT
TONNAGE
AIR
FLOW
M3/S
149 174 198
AVAILABLE EXTERNAL STATIC PRESSURE-Pa*
50 74 99 124
1. Side duct application (380/415 Volts)
* . Includes allowances for a wet evaporator coil, 25mm [1in] filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
18 Unitary Products Group
036-21510-003-A-0204
TABLE 11: BELT DRIVE MOTOR AND DRIVE DATA
TABLE 12: STATIC RESISTANCES
TABLE 13: ELECTRIC HEATER SUPPLY AIR LIMITATIONS
mm inch mm inch mm inch mm inch mm inch
5 TON 812-1102 1.5 1450 56 1.0 IVL44 69-97 2.8-3.8 22 7/8 127 5.0 25 1 922 36.3 A35
6 TON 948-1227 1.5 1450 56 1.0 IVM50 86-112 3.4-4.4 22 7/8 132 5.2 25 1 947 37.3 A36
DESIG-
NATION
BELTFIXED BLOWER PULLY
BORE PITCH DIA. BOREPITCH
LENGTH
MODEL
BLOWER
RANGE
(RPM)
MOTOR1 ADJUSTABLE MOTOR PULLY
HP RPMFRAME
SIZE
SERVICE
FACTOR
DESIG-
NATION
PITCH DIA.
1. All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because
they are located in the moving air, upstream of any heating device.
0.47 0.57 0.66 0.75 0.85 0.94 1.03 1.13 1.23 1.32 1.42
17.4 19.8 22.3 27.3 32.2 37.2 42.2 49.6 57.0 64.5 74.4
7-15KW 10.0 12.4 14.9 17.4 19.8 24.8 29.8 34.7 39.7 47.1 54.6
20-30KW 14.9 17.4 19.8 22.3 27.3 32.2 37.2 42.2 49.6 57.0 64.5
14.9 17.4 19.8 22.3 24.8 27.3 29.8 34.7 39.7 47.1 54.6
19.8 25.0 29.8 34.7 39.7 44.6 49.6 57.0 64.5 71.9 79.4
1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000
0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 0.30
7-15KW 0.04 0.05 0.06 0.07 0.08 0.10 0.12 0.14 0.16 0.19 0.22
20-30KW 0.06 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26
0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.14 0.16 0.19 0.22
0.08 0.10 0.12 0.14 0.16 0.18 0.20 0.23 0.26 0.29 0.32
BOTTOM DUCT CONNECTIONS1
ELECTRIC
HEATERS1
RESISTANCE, Pa
M3/SDESCRIPTION
ECONOMIZER1, 3
RESISTANCE, IWG
CFM
ECONOMIZER1, 3
COOLING ONLY2
ELECTRIC
HEATERS1
BOTTOM DUCT CONNECTIONS1
COOLING ONLY2
DESCRIPTION
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 62.0 Pa [0.25 IWG], the unit will deliver less M3/S or CFM during full economizer operation.
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
7 10 15 20 30
M3/S 0.47 0.57 0.57 0.61 -
CFM 1100 1200 1200 1300 -
M3/S 0.61 0.61 0.61 0.61 -
CFM 1300 1300 1300 1300 -
M3/S 0.75 0.75 0.75 0.75 0.75
CFM 1600 1600 1600 1600 1600
M3/S 0.85 0.85 0.85 0.85 0.85
CFM 1800 1800 1800 1800 1800
380/415-3-50
380/415-3-50
380/415-3-50
380/415-3-50
3
4
5
6
HEATER SIZE NOMINAL KWMINIMUM
SUPPLY AIRVOLTAGE
UNIT MODEL SIZE
NOMINAL TONS
Unitary Products Group 19
036-21510-003-A-0204
TABLE 14: ELECTRICAL DATA: 3 - 6.3 TON
NONE 0.0 0.0 12.6 20
2CE045107462 4.3 6.5 12.6 20
2CE045110462 6.3 9.6 14.1 20
2CE045115462 8.5 12.9 18.3 20
2CE045120462 12.2 18.5 25.3 30
NONE 0.0 0.0 12.6 20
2CE045107462 5.1 7.1 12.6 20
2CE045110462 7.5 10.4 15.2 20
2CE045115462 10.2 14.2 19.9 20
2CE045120462 14.6 20.3 27.5 30
NONE 0.0 0.0 15.3 20
2CE045107462 4.3 6.5 15.3 20
2CE045110462 6.3 9.6 15.3 20
2CE045115462 8.5 12.9 18.6 20
2CE045120462 12.2 18.5 25.7 30
NONE 0.0 0.0 15.3 20
2CE045107462 5.1 7.1 15.3 20
2CE045110462 7.5 10.4 15.5 20
2CE045115462 10.2 14.2 20.2 25
2CE045120462 14.6 20.3 27.9 30
NONE 0.0 0.0 16.0 25
2CE045107462 4.3 6.5 16.0 25
2CE045110462 6.3 9.6 16.0 25
2CE045115462 8.5 12.9 19.5 25
2CE045120462 12.2 18.5 26.5 30
2CE045130462 18.1 27.5 37.8 40
NONE 0.0 0.0 16.0 25
2CE045107462 5.1 7.1 16.0 25
2CE045110462 7.5 10.4 16.4 25
2CE045115462 10.2 14.2 21.1 25
2CE045120462 14.6 20.3 28.8 30
2CE045130462 21.5 29.9 40.8 45
NONE 0.0 0.0 22.7 30
2CE045107462 4.3 6.5 22.7 30
2CE045110462 6.3 9.6 22.7 30
2CE045115462 8.5 12.9 22.7 30
2CE045120462 12.2 18.5 26.5 30
2CE045130462 18.1 27.5 37.8 40
NONE 0.0 0.0 22.7 30
2CE045107462 5.1 7.1 22.7 30
2CE045110462 7.5 10.4 22.7 30
2CE045115462 10.2 14.2 22.7 30
2CE045120462 14.6 20.3 28.8 30
2CE045130462 21.5 29.9 40.8 45Note 1: HACR Type per NECNote 2: These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code, the fuse block accessory 2FB04700546 is available for field installation.Note 3: Heaters are suitable for operation on 380/415V-3-50Hz power supply.
1.3 2.7
415-3-50 8.3 45 1.3 2.7
61/3
380-3-50 8.3 45
1.3 2.7
415-3-50 9.6 79 1.3 2.7
5
380-3-50 9.6 79
1.3 2.0
415-3-50 9.6 66 1.3 2.0
4
380-3-50 9.6 66
1.3 1.7
415-3-50 7.7 58 1.3 1.7
3
380-3-50 7.7 58
HeaterAmps
MinimumCircuit
AmpacityAmps
MaxFuse / BRKR1
SizeAmps
RLAEach
LRAEach
IDBlowerMotorFLA
Electric Heater Model No. 3
HeaterkW
ModelTonnage
Voltage
Compressors OD Fan Motors
FLAEach
20 Unitary Products Group
036-21510-003-A-0204
TABLE 15: PHYSICAL DATA
MODELSDM
036 048 060 076
EVAPORATORBLOWER
Centrifugal Blower Dia. x Wd. mm (in)305 X 254(12 X 10)
305 X 254(12 X 10)
305 X 254(12 X 10)
305 X 279(12 X 11)
Fan Motor HP (Direct Drive) 1/3 3/4 ---- ----
Fan Motor HP (Belt Drive) ---- ---- 1 1/2 1 1/2
EVAPORATORCOIL
Rows Deep 3 3 3 3
Fins Per Inch (25 mm) 13 13 13 13
Face Area m2 (ft2) 0.33 (3.6) 0.40 (4.3) 0.57 (5.1) 0.57 (5.1)
CONDENSERFANS
Propeller Dia. mm (in.) 610 (24) 610 (24) 610 (24) 610 (24)
Fan Motor Hp 1/2 1/2 1/2 1/2
Nom. CFM 4500 4500 4500 4500
CONDENSERCOILS
Rows Deep 1 1 1 2
Fins Per Inch (25 mm) 16 19 22 16
Face Area m2 (ft2) 1.60 (17.1) 1.60 (17.1) 1.60 (17.1) 1.60 (17.1)
COMPRESSOR(Qty. Per Unit)
Hermetic Recip. 1 1 11
(tandem)
AIRFILTERS
Quantity Per Unit (15” X 20” X 1” or 2“) 2 2 2 2
Quantity Per Unit (14” X 25” X 1” or 2“) 1 1 1 1
Total Face Area m2 (ft2) 0.59 (6.3) 0.59 (6.3) 0.59 (6.3) 0.59 (6.3)
CHARGE Refrigerant 22kg (lbs./oz)
2.7 (6/0) 3.0 (6/10) 2.8 (6/12) 4.5/10
TABLE 16: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE VOLTAGEkW CAP. MULTI-
PLIER
380 380 0.627
415 415 0.75
TABLE 17: VOLTAGE LIMITATIONS
POWER SUPPLY VOLTAGE
MIN. MAX.
380/415-3-50 342 456
Unitary Products Group 21
036-21510-003-A-0204
TYPICAL POWER WIRING
TYPICAL CONTROL WIRING
FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING
W1
W2
Y1
G
OCC
P
P1
Y2
X
R
SD
C
C
SD
SD
R
OCC
C
RC
G
Y2
Y1
W2
W1
Jumper
Smoke
Detector
24 VAC
Class 2
X
R
THERMOSTAT
TERMINALSCONTROL
TERMINAL
BLOCK
TERMINALS ON
A LIMITED
NUMBER OF
THERMOSTATS
3
1
2
4
3
1
2
4
Second stage heating not required on single stage heating units.
Second stage cooling not required on single stage cooling units.
Jumper is required if there is no Smoke Detector circuit.
Jumper is required for any combination of R, RC, or RH.
6
5
5
6
OCC is an output from the thermostat to indicate the Occupied condition.
X is an input to the thermostat to display Error Status conditions.
22 Unitary Products Group
036-21510-003-A-0204
FIGURE 3 - UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW
FIGURE 4 - UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW
829
[325/8]
1140
[447/8]
64
[21/2]
213
[83/8]
292
[111/2]
445 [171/2]
445 [171/2]
181
[77/8]
171 [63/4]
206
[81/8]
137
[53/8]
2089
[821/4]
165 [61/2]
mm[inch]
829
[325/8]
1140
[447/8]
64
[21/2]
213
[83/8]
292
[111/2]
445 [171/2]
445 [171/2]
181
[77/8]
171 [63/4]
206
[81/8]
137
[53/8]
2089
[821/4]
165 [61/2]
178 [7]
111 [43/8]
165
[61/2]
819 [321/4]
819 [321 / 4
]
mm[inch]
Unitary Products Group 23
036-21510-003-A-0204
FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD
FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD
DETAIL “A”
699
[271/2]
699
[271/2]
41
[15/8]
260
[101/4]
1140
[447/8]
502
[193/4]
mm[inch]
DETAIL “B”
454
[177/8]
184
[71/4]
699
[271/2]
485
[191/8]
1140
[447/8]
305 [12]
419 [161/2]mm[inch]
260
[101/4]
89
[31/2]
210
[81/4]
111
[43/8]
24 Unitary Products Group
036-21510-003-A-0204
FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)
mm[inch]445
[171/2]
445
[171/2]
165
[61/2]
292
[111/2]
76 [3]
200
[77/8]
117 [45/8]
292
[111/2]
FIGURE 8 - DISCONNECT/BLOWER ACCESS LOCATION
TABLE 18: UTILITIES ENTRY
HOLEOPENING SIZE (DIA.)
(mm/in)USED FOR
A 22 / 0.88 KO1 Control Wiring2Side
Bottom
B 51 / 2.0 KO1 Power WiringSide
Bottom
C 41 / 1.63 KO Gas Piping (Front)
D 38 / 1.5 KO Gas Piping (Bottom)
1. Opening in the bottom to the unit can be located by the side in the insulation.
2. Do not remove the 2” knockout ring.
DISCONNECT SWITCH LOCATION
AND MOTOR ACCESS PANEL FOR
UNIT WITH “BELT-DRIVE” OPTION
CONTROL BOX
ACCESS
A,B
WIRING ENTRY
(See Detail “B”)
MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the
blower housing inside
the blower compartment)
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
BLOWER MOTOR
ACCESS
FILTER
ACCESS
DOT PLUGS
TABLE 19: MINIMUM CLEARANCESLOCATION CLEARANCE (mm / In.)
Front610 / 24.0 (Cooling/Electric Heat)
813 / 32.0 (Gas Heat)
Rear305 / 12.0 (Less Economizer)
914 / 36.0 (With Economizer or Fixed Air/Motorized Damper)
Left Side (Filter Access) 610 / 24.0 (Less Economizer)914 / 36.0 (With Economizer)
Right Side (Cond. Coil) 610 / 24.0
Below Unit1 0
Above Unit21829 / 72.0 (For
Condenser Air Discharge)
1. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging struc-tures or shrubs should not obstruct condenser air dis-charge outlet.
Unitary Products Group 25
036-21510-003-A-0204
FIGURE 9 - TYPICAL APPLICATIONS
26 Unitary Products Group
036-21510-003-A-0204
FIGURE 10 - FOUR AND SIX POINT LOADING
TABLE 20: DM 4 POINT LOADS WEIGHT DISTRIBUTION (kg / lbs)UNIT TOTAL A B C D
DM036 Cooling/ Electric 250 / 550 55 / 122 54 / 120 69 / 153 70/155
DM036N04 277 / 610 61 / 135 60 / 133 77 / 169 78 / 172
DM048 Cooling/ Electric 268 / 590 59 / 131 58 / 129 74 / 164 76 / 167
DM048N06 295 / 650 65 / 144 64 / 142 82 / 180 83 / 184
DM060 Cooling/ Electric 286 / 630 63 / 140 62 / 137 79 / 175 81 / 178
DM060N08 313 / 690 69 / 153 68 / 150 87 / 191 88 / 195
DM076 Cooling/ Electric 313 / 690 71 / 157 82 / 181 85 / 188 74 / 164
DM076N08 338 / 745 77 / 170 89 / 195 92 / 203 80 / 177
TABLE 21: DM 6 POINT LOADS WEIGHT DISTRIBUTION (kg / lbs)UNIT TOTAL A B C D E F
DM036 Cooling/ Electric 250 / 550 37 / 81 37 / 82 36 / 80 46 / 101 47 / 103 47 / 104
DM036N04 277 / 610 41 / 91 41 / 89 40 / 88 51 / 112 52 / 114 52 / 115
DM048 Cooling/ Electric 268 / 590 40 / 88 39 / 87 39 / 85 49 / 109 50 / 110 51 / 111
DM048N06 295 / 650 44 / 97 43 / 95 43 / 94 54 / 120 55 / 121 56 / 123
DM060 Cooling/ Electric 286 / 630 42 / 94 42 / 92 41 / 91 53 / 116 53 / 118 54 / 119
DM060N08 313 / 690 46 / 102 46 / 101 45 / 100 58 / 127 58 / 127 59 / 130
DM076 Cooling/ Electric 313 / 690 46 / 102 51 / 112 56 / 124 58 / 128 53 / 117 48 / 107
DM076N08 338 / 745 50 / 111 55 / 121 60 / 133 63 / 139 57 / 126 52 / 115
1140
[447/8] 2089
[821/4]
Y
X
A
B
C
D
CONDENSER COIL
END OF UNITFRONT OF UNIT
APPROXIMATE
CENTER OF GRAVITY
BACK OF UNIT mm[inch] 1140
[447/8] 2089
[821/4]
Y
X
A
B
C
DCONDENSER COIL
END OF UNITFRONT OF UNIT
APPROXIMATE
CENTER OF GRAVITY
BACK OF UNIT mm[inch]
E
F
TABLE 22: CENTER OF GRAVITY
DIMENSION3 - 5 TON(mm / in)
6 TON(mm / in)
X 1035 / 40-¾ 1118 / 44
Y 502 / 19-¾ 559 / 22
Unitary Products Group 27
TABLE 23: OPERATING WEIGHTS (kg / lbs.)MODEL SIZE 3 TON 4 TON 5 TON 6 TON
BASICUNIT
DM (Cooling Only) 250 / 550 268 / 590 286 / 630 313 / 690
DM(Gas/Electric)
N04 277 / 610 - - -
N06 - 295 / 650 - -
N08 - - 313 / 690 338 / 745
OPTIONS
Economizer 23 / 50
Motorized Damper 12 / 26
Electric Heater
7 kW 8 / 18
10 - 15 kW 10 / 23
20 - 30 kW 13 / 28
ACCY.
Roof Curb 42 / 92
Barometric Relief / Fixed Air Damper 5 / 10
Belt-Drive Blower 2.3 / 5
FIGURE 11 - ROOF CURB DIMENSIONS
mm[inch]
495
[191/2]
495
[191/2]
495
[191/2]
946
[371/4]
1854
[73]
356 [14]
51
[2]
114
[41/2]
51
[2]
51
[2]
DUCT SIZES:
SUPPLY AIR = 489 X 489 [191/4 X 191/4]
RETURN AIR = 489 X 489 [191/4 X 191/4]
Subject to change without notice. Printed in U.S.A. 036-21510-003-A-0204Copyright © 2004 by Unitary Products. All rights reserved. Supersedes: 036-21510-002-A-0703