20 feet Containerized Solution
Specifications
CSCU 3024635
Version Date: August 2019
Sample
2
Legal Provisions No part of this User Manual (“Manual”) may be reproduced, or transmitted, in any form or by any means, without the prior written permission of Kilowatt Labs, Inc. (“Kilowatt” or the “Company”). Specifications in this Manual are subject to change without notice. While every attempt has been made to make the Manual accurate and up-to-date, users are cautioned that product improvements may cause the Company to make changes to specifications without advance notice. Users are encouraged to consult the Company or its Resellers before using the Manual. Neither the Company nor its Resellers shall be liable for any indirect, incidental, or consequential damages under any circumstances caused by reliance on the material presented, including, but not limited to, omissions, typographical errors, arithmetical errors or listing errors in the content material. The content of this manual shall not be modified without the written authorization of the Company. Trademarks All trademarks are recognized, even if not explicitly identified as such. Kilowatt Labs® is a registered trademark of the Company. Warning Selling and installation of this product is only through the Company’s Resellers who are
trained on installation, operation and maintenance of the Sirius modules.
Sample
3
Container Overview:
Sample
4
Electrical Drawing:
Mechanical Drawing:
Sample
5
Module Rack:
1. 30 Module Rack:
2. 20 Module Rack:
Sample
6
Container Description:
ITEM NAME DESCRIPTION MU
1 Energy Server 20kW Capacity, 380V-3P input 1 Set
2 Sirius Capacitor Module 1.36kWh, 2.4V 150 PCS
3 Monitoring Machine
LCD w/ Mouse and keyboard 1 PC
UPS (600VA) & Battery (465Wh) 1 Set
CPU 1 PC
4
DC Breaker ELCB 250, CNS 250 4P 1 PC
MAIN Distribution Panel
MCCB ABS104c, 125 Ah 1 PC
Switch SBN440, 4P 40 A 1 PC
Switch CEC441J, 4P 40 A 1 PC
MCB MCN116A, 1P 6kVA C-16A 1M 3 PCS
MCB MCN132A, 1P 6kVA C-32A 1M 3 PCS
Output DB Panel MCCB, ABS104c, 125 Ah 1 PC
Generator Panel MCCB, ABS104c, 125Ah 1 PC
5 Isolator Switch 1P, 35 A, 250V 1 PC
6 Fire Extinguisher Automatic Dry Power Fire
Extinguisher 2 PC
7 Camera DS-2CD1121-1 2 PC
8 Embedded NVR DS-7600 Series NVR 1 PC
9 Module Sensor PBAT 802 150 PCS
10 Sensor Combiner PBAT 600 3 PCS
11 Communication Gate Way
PBAT GATE 1 PC
12 Power Supply 24 V 1 PC
13 Protocol Converter Protocol Converter 1 PC
14 Motion Sensor 1 Set
Sample
7
Storage Bank Specifications:
CSCU 3024635
PERFORMANCE SPECIFICATIONS
Voltage (Nominal) 360 Vdc
Maximum Charge Voltage 405 Vdc
Discharge Cut-Off Voltage 325 Vdc
Total Energy 204600 Wh
Maximum Charge Rate 60 A
Maximum Discharge Rate 60 A
ENVIRONMENTAL SPECIFICATIONS
Cell Operating Temperature3 -30 OC to 80 OC
Operating Humidity Non-Condensing
SMART FEATURES
Monitoring Data Temperature, Total Voltage, individual
cell monitoring, Current and Energy
Remote control (optional) Via Sirius Remote Control
Communication and Connectivity Ethernet/RS 485
Alarm Audible alarm in the event of
Over/under-Voltage, Over-Current, Over Temperature
CENTAURI VIEW SOFTWARE
Module Monitoring Current, Voltage, Temperatures,
Graphs, Daily reports and data logging
System Monitoring
Instant Generator Solar Power, Daily Generated Solar Energy, Daily
Consumption Solar Energy, Total Generated Solar energy from the start,
Daily Consumption Energy
SAFETY PERFORMANCE
Over/under voltage Hardware protection, Module shut
down
Over Current Hardware protection, Module shut
down
Over temperature Hardware protection, Module shut
down
Additional Safety DC circuit breaker
COMPLIANCE8
INFORMATION
EN55032:2015, EN55024:2010, EN61000-4-2:2009, EN61000
EN61000:2008+A2:2010
PRECAUTIONS
Alarm In case of alarm, immediately rectify/attend to the cause of the alarm.
Physical Damage In case the Module is physically damaged due to any event, do not install and energize the Module under any circumstances and contact your Reseller.
Short Circuit Ensure precautions to prevent short-circuit under all circumstances.
Galvanic isolation When connecting to external devices ensure that galvanic isolation does not exceed 1000V.
15 Recessed box
16 Ethernet Switch 8 port-Ethernet Switch 1 PC
17 Sockets Standard Socket 2 Set
18 Lights Fluorescent Light Tube 3 PCS
19 Exit Light 2 PC
Sample
8
Charge/Discharge Current
Under no circumstances must the charge/discharge current exceed 60A.
Charging Voltage Under no circumstances must the charging voltage exceed 405 Vdc for more than 60 seconds.
Charge Cycle During charge cycle ensure never to exceed constant voltage of 405 Vdc and constant current of 60A.
1Self-discharge is the natural decay of the Module total voltage over time. Module self-discharge is 2% in Sleep Mode (switched off) and 9.6% in Switched-On Mode. 2The Module C-Rate refers to the rate at which a Module is charged or discharged. A 1C rate means that the current will charge or discharge the entire Module in 1 hour. 3The temperature range indicates the range in which the supercapacitor cells can operate. The performance of the cells may vary if they are continuously operated outside a temperature range of -10⁰C to 55⁰C, and/or at C-rates higher than the maximum charge/discharge rate specified in this spec sheet. The operating temperature range of the Module varies based on the application. If the Module is to be operated continuously outside a temperature range of -10oC to 55oC, and/or at C-rates higher than the maximum charge/discharge rate specified in the spec sheet, please consult Kilowatt Labs or its Reseller prior to deploying. 4Projected life of supercapacitor cells. Cycle life will vary if cycled more than 4 times a day. 5Additional terms and conditions, including a limited warranty, will apply at the time of purchase. 6Projected Calendar life of supercapacitor cells from the date of first operation. 7Shelf life is the life of the Module (in years) from the date it is manufactured to the time it is first operated. 8CE certification is completed for supercapacitor cells. Product dimensions are for reference only unless otherwise identified and may change without notice. For critical applications, please contact your Reseller.
Sample
9
1.Centauri Energy Server
Rated power 20 kW
Rated current 45 A
Output power factor 1
Rated input voltage 380 Vac ± 20%
Rated output voltage 380 Vac ± 1%
Battery voltage 360 Vdc
Operating mode AC and PV complementation
PV INPUT
Max. voltage (Voc) 750 Vdc
Optimum operating voltage (Vamp) 450 ~ 550 Vdc
Max. conversion efficiency ≥ 98%
Floating charge voltage (25℃) 414 Vdc ± 1%
Equalizing charge voltage (25℃) 428 Vdc ± 1%
MPPT Max. current 120 A
Max. PV power 2 * 25 KW
Number of PV input 2 + 1 (reserve)
MPPT modules 2 + 1 (reserve)
AC RECTIFIER
Input voltage range 380 V ± 20% three-phase
Rated frequency 50 Hz / 60 Hz ± 5 Hz (settable)
Power factor 0.8
Floating charge voltage (25℃) 410 V ± 1%
Equalizing charge voltage (25℃) 415 V ± 1%
Max. charging current 38 A
INVERTER
Inverter voltage 380 Vac three-phase + N+PE
Phase voltage 220 / 230 / 240 Vac (settable)
Sample
10
Output voltage precision ± 1%
Transient voltage range ± 5%
Transient recovery time 20 ms
Rated frequency 50 Hz / 60 Hz ± 1 Hz (settable)
Frequency tracking range 50 Hz / 60 Hz ± 3 Hz
Peak factor 3: 1
Waveform Sinusoidal
Waveform distortion ≤ 3% (linear load)
Voltage unbalance ± 3% (100% unbalanced load)
Overload
≥ 105% ~ 110% for 1 hr: ≥ 110% ~ 125% for 10 mins; ≥ 125% ~ 150% for 1 min; ≥ 150% shut down in 10 s;
≥ 200% shut down immediately;
Short circuit Current-limiting, shut down immediately until the user
start up
Max. efficiency ≥ 92%
BYPASS
Rated voltage 380 Vac three-phase + N+PE
Voltage range ± 20%
Rated frequency 50 Hz / 60 Hz ± 5 Hz
Max. current 57 A
TRANSFER TIME
Inverter– Bypass 0 ms
Bypass – Inverter 0 ms
COMMUNICATIONS
Remote control Energy server startup, shutdown, abnormal clearance,
EPO, battery self-test
Communication interface RS232, RS485, SNMP (optional)
Dry contacts output Bypass input abnormal, rectifier input abnormal, system
fault, system alarm, low battery, output overload, fan fault, generator ON / OFF
Load Handling Curve
OTHERS
Operating temperature 0℃ ~ 40℃
Max. relative humidity 90% (non-condensing)
Max. altitude 1000 m at rated power (derating 1% for each additional
100 m); Max. 4000 m
Sample
11
Noise level at 1 m ≤ 65 dB (varies with loads and temperature)
IP rating IP20
Dimensions (W × D × H) (mm) 600 × 700 × 1750
Packaged dimensions (W ×D × H) (mm) 690 × 790 × 1850
Weight (kg) 380
2. Sirius Module 1364Wh 2.4VDC:
Part No. 1364-2.4-B-0.53C-TM-SD-A-CS
PERFORMANCE SPECIFICATIONS
Voltage (Nominal) 2.4 Vdc
Maximum Charge Voltage 2.7 Vdc
Discharge Cut-Off Voltage 2.2 Vdc
Total Energy 1364 Wh
Maximum Charge Rate 300 A
Maximum Discharge Rate 300 A
Fuse Breaking Amps 800 A
ENVIRONMENTAL SPECIFICATIONS
Cell Operating Temperature3 -30 OC to 80 OC
Operating Humidity Non-Condensing
Module Casing Material Aluminum
Terminal Type F12
SMART FEATURES
Monitoring Data Temperature, Total Voltage, Current
and Energy Remote control (optional) Via Sirius Remote Control
Communication and Connectivity Ethernet
Alarm Audible alarm in the event of
Over/under-Voltage, Over-Current, Over Temperature
SIRIUSVEIW SOFTWARE
Module Monitoring Current, Voltage, SOC, Temperatures,
Total Energy delivered, Graphs
System Monitoring Modules Monitoring (connected in
parallel or series)
MODULE SERVICE LIFE
Projected Cycle Life4,5 1 million cycles
Projected Calendar Life5,6 45 years
Shelf Life7 10 years
Warehousing Can be stored at any SOC without
affecting cycle life
Sample
12
SAFETY PERFORMANCE
Over/under voltage Hardware protection, Module shut
down
Over Current Hardware protection, Module shut
down
Over temperature Hardware protection, Module shut
down
Additional Safety Fuse
COMPLIANCE8
INFORMATION
EN55032:2015, EN55024:2010, EN61000-4-2:2009, EN61000
EN61000:2008+A2:2010
PRECAUTIONS
Alarm In case of alarm, immediately rectify/attend to the cause of the alarm.
Physical Damage In case the Module is physically damaged due to any event, do not install and energize the Module under any circumstances and contact your Reseller.
Short Circuit Ensure precautions to prevent short-circuit under all circumstances.
Galvanic isolation When connecting to external devices ensure that galvanic isolation does not exceed 1000V.
Charge/Discharge Current
Under no circumstances must the charge/discharge current exceed 300A.
Charging Voltage Under no circumstances must the charging voltage exceed 2.7 Vdc for more than 60 seconds.
Charge Cycle During charge cycle ensure never to exceed constant voltage of 2.7 Vdc and constant current of 300A.
1Self-discharge is the natural decay of the Module total voltage over time. Module self-discharge is 2% in Sleep Mode (switched off) and 9.6% in Switched-On Mode. 2The Module C-Rate refers to the rate at which a Module is charged or discharged. A 1C rate means that the current will charge or discharge the entire Module in 1 hour. 3The temperature range indicates the range in which the supercapacitor cells can operate. The performance of the cells may vary if they are continuously operated outside a temperature range of -10⁰C to 55⁰C, and/or at C-rates higher than the maximum charge/discharge rate specified in this spec sheet. The operating temperature range of the Module varies based on the application. If the Module is to be operated continuously outside a temperature range of -10oC to 55oC, and/or at C-rates higher than the maximum charge/discharge rate specified in the spec sheet, please consult Kilowatt Labs or its Reseller prior to deploying. 4Projected life of supercapacitor cells. Cycle life will vary if cycled more than 4 times a day. 5Additional terms and conditions, including a limited warranty, will apply at the time of purchase. 6Projected Calendar life of supercapacitor cells from the date of first operation. 7Shelf life is the life of the Module (in years) from the date it is manufactured to the time it is first operated. 8CE certification is completed for supercapacitor cells. Product dimensions are for reference only unless otherwise identified and may change without notice. For critical applications, please contact your Reseller.
Sample
13
3. Centauri View Monitoring:
3.1 Auxiliary Supply UPS with 465Wh12V Module:
Auxiliary Supply UPS Model 600VA
Input mode Inverter mode BLU mode
Rated values
Input voltage 220VAC
Input frequency
50Hz
Number of input phases
Single phase
Input voltage range 120~300VAC 145~285VAC
Input frequency range 38~70Hz
Output voltage Mains mode
BLU mode : 198V~242V / INV mode : 175V~255V
ESD mode 220V±5% (resistive load)
Output frequency
Mains mode Synchronous with grid power
ESD mode 50HZ±1Hz
Waveform Mains mode Tracking mains power ESD mode Sine wave
Output power factor 0.8 Output power 600VA/480W
Protection
Over temperature protection
When heatsink temperature exceeds 90ºC: Shut down charger in mains mode, and shut down inverter in ESD
mode Over voltage protection
Shut down output when the voltage is above 285+/-10V
Under voltage protection
Shut down output when the voltage is below 120+/-10V
LCD Monitor
Monitoring CPU
Auxiliary Supply UPS
DC Circuit Breaker
Sample
14
Short circuit protection
Shut down output
Audible noise ≤55dB(1m) Insulation resistance > 2MΩ(500Vdc)
Dielectric strength 2820Vdc
Overload capacity (precision: +/-10%)
1. Mains mode: 1) 100% load, long term operation. 2) 100~120% shut down output after 3min, re-startup automatically after 30s, after re-startup 3 times, if the overload still exists, then enter failure mode and the unit needs to be started up manually. 3) 120~130% shut down output after 30s, re-startup automatically after 30s, after re-startup 3 times, if the overload still exists, then enter failure mode and the unit needs to be started up manually. 4) ≥130% shut down output immediately, re-startup automatically after 30s, after re-startup 3 times, if the overload still exists, then enter failure mode and the unit needs to be started up manually. 2. ESD mode: 1) 100% load, long term operation. 2) 100~110% shut down output after 10s, re-startup automatically after 30s (with soft startup), after re-startup 3 times, if the overload still exists, then enter failure mode and the unit needs to be started up manually. 3) ≥110% shut down output immediately, re-startup automatically after 30s (with soft startup), after re-startup 3 times, if the overload still exists, then enter failure mode and the unit needs to be started up manually.
Rated ESD voltage
12V
Charging voltage 13.8V±0.3V
Charging current 10A/20A optional
Extension port 1M Cable
Red: to ESD positive Black: to ESD negative
Mechanical Specifications
Unit Dimensions
272*285*165 mm
Package Dimensions
380*375*255 mm
Net Weight (KG)
11.4
Gross Weight (KG)
12.7
Environmental Specifications
Operating Temperature
0°C-40°C
Storage Temperature
-25°C-55°C
Relative Humidity
20%-95% (no condensation)
Elevation <1000m, for elevation above 1000m, de-rate with
reference to GB7260.3-2003 4.1.1
Sample
15
Cooling Mode Air cooling
Sirius Module 465Wh12V:
Part No. 465-12-B-1.7C-CS
PERFORMANCE SPECIFICATIONS
Voltage (Nominal) 12 Vdc
Maximum Charge Voltage 13.5 Vdc
Discharge Cut-Off Voltage 11 Vdc
Total Energy 465 Wh
Maximum Charge Rate 70 A
Maximum Discharge Rate 70 A
ENVIRONMENTAL SPECIFICATIONS
Cell Operating Temperature3 -30 OC to 80 OC
Operating Humidity Non-Condensing
Module Casing Material Aluminum
Terminal Type Anderson Connectors
MODULE SERVICE LIFE
Projected Cycle Life4,5 1 million cycles
Projected Calendar Life5,6 45 years
Shelf Life7 10 years
Warehousing Can be stored at any SOC without
affecting cycle life
COMPLIANCE8
INFORMATION
EN55032:2015, EN55024:2010, EN61000-4-2:2009, EN61000
EN61000:2008+A2:2010
PRECAUTIONS
Physical Damage In case the Module is physically damaged due to any event, do not install and energize the Module under any circumstances and contact your Reseller.
Short Circuit Ensure precautions to prevent short-circuit under all circumstances.
Galvanic isolation When connecting to external devices ensure that galvanic isolation does not exceed 1000V.
Charge/Discharge Current
Under no circumstances must the charge/discharge current exceed 70A.
Charging Voltage Under no circumstances must the charging voltage exceed 13.5 Vdc for more than 60 seconds.
Charge Cycle During charge cycle ensure never to exceed constant voltage of 13.5 Vdc and constant current of 70 A.
3.2 Monitoring CPU:
PERFORMANCE
Processor Up to 7th generation Intel® Core™ i7
Operating System Windows 10 Pro
Memory Up to 32 GB 2 DDR4 UDIMM 2400MHz
Storage
• 2280 M.2 PCIe SSD (up to 256 GB)
• 3.5" HDD (up to 1 TB) • 2.5" SSD (up to 128 GB)
• Slim ODD
Graphics • Intel Integrated HD Graphics 630
• Intel Integrated HD Graphics 610
Sample
16
• Optional NVIDIA® GT730 2G GDDR3
• Optional NVIDIA® GT730 1G GDDR5
PSU 180W/210W PSU
SECURITY Security • Smart USB Protection • TPM 2.0
CONNECTIVITY
Front I/O Ports • 4 x USB 3.0
• Card reader (optional)
• 2 x audio
Rear I/O Ports
• 2 x USB 3.0
• 2 x USB 2.0
• VGA
• HDMI
• DP
• 1 x serial, 1 x optional serial • Optional parallel port
• LAN
• 2 x audio
Wireless Connection 1×1802.1 1b/g/n/ac
CERTIFICATIONS Green Certifications
• Energy Star 6.1
• GREENGUARD®
• EPEAT® Gold
• RoHS/WEEE/REACH
DESIGN Dimensions (W x D x H) 92.5 mm × 290.9 mm × 343.5 mm / 3.64" x 11.45" x 13.52"
SOFTWARE Preloaded Software • Lenovo App Explorer
• Lenovo Companion 3.0
• Microsoft Office 2016 (Trial)
3.3 LCD Monitor:
PANNEL
Size 17" (43.3cm)
Type TN
Color Gamut 72% NTSC
Color Depth (Number of Colors) 16.7M
Aspect Ratio 5: 4
Pixel Pitch(mm) 0.264 x 0.264
Resolution 1280 x 1024
Brightness 250cd/m2
Contrast Ratio (Type) 5000000: 1(DFC), 1,000:1(Native)
Response Time 5ms (On/Off)
Viewing Angle 170°/160° (CR≥10)
Surface Treatment Non glare
PHYSICAL FEATURES
Set (with Stand, W x D x H, mm) 370 x 95 x 315
Set (without Stand, W x D x H, mm) 370 x 62 x 315
Box (W x D x H, mm) 429 x 159 x 377
Sample
17
Wall Mount VESA Compatible (75mmx75mm)
Weight (kg, with Stand) 3.3
Weight (kg, without Stand) 2.9
Box(kg) 4.5
Set (with Stand, W x D x H, mm) 370 x 95 x 315
SPECIAL FEATURES
USB Yes (1)
General Function
sRGB, DDC/CI, Intelligent Auto (Auto Resolution), Plug & Play
STAND
Base Detachable -
Tilt (Angle) 15° (forwards) ~ 68°(backwards)
Swivel (Angle) -
Pivot -
Base Detachable -
CONNECTIVITY
Signal Input D-Sub
Others USB (Touch Screen connection)
ENERGY RATINGS
Comparative Energy Consumption 60kWh/Year
Star Rating 5 Stars
Active Standby 0.2W
GENERAL
Accessories Power Cord, D-sub, USB Cable
Regulation Compliance TUV-Type, FCC-B, CE, C-Tick, CB, MEPS VESA Mount,
Windows7
4. Circuit Breakers:
MODEL POLES RATED
AMPERAGE QUANTITY
DC Breaker CB ELCB 4P 250 A 1PC
MCCB ABS104c - - 1 PC
Sample
18
Main distribution Panel
Switch SBN440 4P 40A 1 PC
Switch CEC441J 4P 40A 1 PC
MCB MCV116A 1P 16A 3 PC
MCB MCV132A 1P 32A 3 PC
Output DB Panel
MCCB ABS104c - - 1 PC
Generator Panel
MCCB ABS104c - - 1 PC
5. Isolator Switch:
Application Current rating 35A
Standard BSEN 60947-3
Number of Poles 1
Function O-I
Rated Operational Current 20 35 63
Rated operational Voltage 250 V
Rated Insulation Voltage 250 V
Rated Impulse-withstand Voltage (Uimp) 2.5 KV
Frequency 50 / 60 Hz
Utilization Category AC23A
Rated making capacity 10Ie
Rated Breaking Capacity 8Ie
Rated short - time withstand current 15 Ie for 1s
Pollution Degree 3
Degree of Protection IP56
Tightening Torque 1
Terminal Capacity Flexible Type mm² 1.5-2.5
Terminal Capacity rigid Type mm² 1.5-2.5
Contact Opening Type Normal Gap
Switch Actuating Method Manual Operation
Method of mounting Surface
Type of Terminal Screw Type
Type of Enclosure Enclosed
Material Engg. Plastic
Quality Management System ISO 9001: 2008
Sample
19
6. FE36 FIRE EXTINGUISHER:
7. IR Fixed Dome Network Camera (DS-2CD1121-I)
SPECIFICATION MODEL FE36
Capacity (kg) 6
Fire rating 21a
144b
Diameter (mm) 275
Breadth (mm) n/a
Height (mm) 210
Discharge range (m) 8
Discharge time (sec) 7.9 9.11 18-20
Empty weight (kg) 6
Total weight (kg) 15
Packing final volume (m3) 0.03
Cylinder wall thickness (mm) 2
Hose automatic type
Class of fire a,b,c &e
Extinguishing agent hfc-236fa
Operating pressure (bar) 15
Testing pressure (bar) -
Nozzle -
Valve -
Bottom base -
Rising pipe plastic /aluminum
Temperature range -20°c to +60°c
Cylinder material cold rolled steel
Painting super finished electro plastic polyester
epoxy resin
Printing clear attractive silk screen printing
Mounting ceiling mounted
Sample
20
Key Features:
1/2.8″ progressive scan CMOS Up to 2.0 megapixel 2.8mm/4mm/6mm fixed focal lens Up to 30 m IR range Dual stream Digital WDR (Wide Dynamic Range) 3D DNR (Digital Noise Reduction) PoE (Power over Ethernet) IP67, IK10 Mobile monitoring via Hik-Conn
Sensor CMOS Image Sensor
Horizontal Resolution 2MP
Signal system PAL/NTSC
Effective pixels 1920 x 1080
S/N Ratio >62dB
Lens 2.8mm
Minimum illumination Color: 0.01 Lux @ (F1.2, AGC ON), 0 Lux
with IR
IR LED EXIR
IR LED Range 30 μέτρα
Shutter Speed 1/3 s to 1/100, 000 s, support slow
shutter
Video output 1RJ-45
Power supply 12 VDC ± 25%, PoE (802.3af)
Power Consumption Max. 5 W/6.5 W (PoE)
Working temperature -30 °C to 60 °C
Dimensions 69.1 mm × 66 mm × 172.7 mm
Weight 500g
8. Embedded NVR (DS-7600 Series NVR):
Sample
21
Key Features
- 4 Channel PoE IP Camera Ports - Support for up to 8MP recording and playback - Support for 4k video output - H.264/H.264+/H.265 video codecs - 1 SATA interface to connect 1 x 10TB hard drive - Support for VCA detection alarm - Compatible with third-party IP cameras - Supports Hikvision's ANPR solutions
Number of Channels 4
Number of PoE Ports 4
Incoming Bandwidth 40 Mbps
Outgoing Bandwidth 80 Mbps
Number of Bays 1
ANPR Ready Yes
HDD Capacity Supplied 0GB
Maximum Memory Capacity 10TB
9. Module Sensors:
10. Sensor Combiner:
Sample
22
11. Communication Gate Way:
12. Power Supply(24V):
13. Protocol Converter:
Sample
23
14. Motion Sensor:
15. Recessed box: 1 Recessed Box with 63A Industrial socket and Plug(5-pin) and 6 number of 50mm dia holes for cable entry.
16. Double Sockets:
Sample
24
2 double sockets of 13A
17. Double LED light:
4’ double LED light fittings (2nos), emergency exit light(2nos)
18. Exit Light (ROBUS R8MLED-01):
Power Consumption (W) 2.6
Batteries (NiCad) 3.6v 1.5Ah
Discharge duration >3hrs after 24 hr charge
Light output in emergency (lm) 60
Ambient Temperature Range (0C) 0 ≤ Ta ≤ +25
IP Rating 65
Weight (Kg) 0.57