Products Solutions Services
Project management, design and component selection
Project delivery
Profibus in Process 2013
Instrument
engineering
System architecture
design
Network design Network
component
selection
Field
enclosures
Installation
Performance
& safety
calculations
Design
deliverables
Integration Test &
verification Asset
management
Maintenance &
training
Engineering principles and guidelines
Profibus in Process 2013
Engineering principles and guidelines
Profibus in Process 2013
Profibus DP
RS 485 Profibus PA
MBP Max. 1900 m
UBUS = 24 V
I BUS = < 400 mA
Profibus DP
RS 485 Profibus PA
MBP-IS Max. 1000 m
UBUS = 13,5 V
I BUS = < 110 mA
for ia / ib IIC
Engineering principles and guidelines
Profibus in Process 2013
T
Profibus PA
Profibus DP (RS 485)
1-12 13-14 15-18 19-24 25-32
120 m 90 m 60 m 30 m 1 m
Line construction with spur
Trunk line
Spur
Max. spur length (each)
No. of nodes
Networking components – PROFIBUS DP/PA - Topology
Profibus in Process 2013
Networking components – PROFIBUS DP/PA - Topology
Profibus in Process 2013
Siemens DP/PA link module P+F SK3 Compact P+F SK1
Networking components – PROFIBUS DP - Topology
Profibus in Process 2013
Networking components – Profibus DP ProfiHub
Profibus in Process 2013
ProfiHub A5
ProfiHub B5
• 5 Galvanic isolated channels (segments).
• Suitable for RS 485 based networks (PROFIBUS DP, DP-V1,
DP-V2 and MPI).
• Transmission speeds: 9,6 Kbit/s …12 Mbit/s.
• Each channel complies to the DP - RS 485 specification.
• Integrated termination facility for each channel and trunk line.
• IP 65 classification.
• Each channel can serve 1 up to 31 devices.
• No limit in serial placement or cascading of ProfiHubs.
Networking components – Profibus DP ProfiHub
Profibus in Process 2013
RS485
• Large networks with star and tree topology
• No limit in the cascading of ProfiHubs
Networking components – DP connectors
Profibus in Process 2013
• Wide choice of Cable to suit each application.
• 9-pin DIN is standard way to connect Profibus DP devices together.
• Outdoor equipment generally cable-glanded and hard-wired.
• DP has 5 pin and PA 4 pin M12 plugs and sockets
Networking components – PROFIBUS PA - Topology
Profibus in Process 2013
Networking components – PROFIBUS PA - Topology
Profibus in Process 2013
P+F Segment protector
P+F Segment protector
Weidmüller T Box
Weidmüller Junction Box
Cord sets
Segment design drawings
Profibus in Process 2013
FIT-971801-02 24 - 49 - 0
Bus 4_6 - 54 Addr. 55
FIT-971801-06 24 - 49 - 0
Bus 4_6 - 54 Addr. 57
FIT-971801-07 24 - 49 - 0
Bus 4_6 - 54 Addr. 58
FIT-971801-08 24 - 49 - 0
Bus 4_6 - 54 Addr. 59
FIT-971801-09 24 - 49 - 0
Bus 4_6 - 54 Addr. 60
LS-421001-83 17 - 36 - 0
Bus 4_6 - 54 Addr. 42
LS-421001-96 17 - 37 - 0
Bus 4_6 - 54 Addr. 53
LS-421001-108 17 - 36 - 0
Bus 4_6 - 54 Addr. 41
LS-421001-120 17 - 37 - 0
Bus 4_6 - 54 Addr. 45
PIT-421001-212 17 - 37 - 0
Bus 4_6 - 54 Addr. 50
PIT-971801-01 24 - 49 - 0
Bus 4_6 - 54 Addr. 54
PIT-971801-04 24 - 49 - 0
Bus 4_6 - 54 Addr. 56
TT-421001-094 17 - 37 - 0
Bus 4_6 - 54 Addr. 43
TT-421001-119 17 - 37 - 0
Bus 4_6 - 54 Addr. 44
TT-421001-138 17 - 37 - 0
Bus 4_6 - 54 Addr. 46
TT-421001-152 17 - 37 - 0
Bus 4_6 - 54 Addr. 47
TT-421001-160 17 - 37 - 0
Bus 4_6 - 54 Addr. 48
TT-421001-168 17 - 37 - 0
Bus 4_6 - 54 Addr. 49
TT-421001-213 17 - 37 - 0
Bus 4_6 - 54 Addr. 51
TT-421001-216 17 - 37 - 0
Bus 4_6 - 54 Addr. 52
Original Scale
The Copyright of this Drawing is reserved by Endress + Hauser Ltd.
It is issued on condition that it is not copied or reproduced either
wholly or in part to a third party without written consent.
Tel: +44 161-286-5000
description
REMOVE ALL BURRS & SHARP EDGES
UNLESS OTHERWISE STATED
ALL DIMENSIONS IN MILLIMETRES
DO NOT SCALE
PROJECTION
Checked
TITLE
E+H Ref
Approved
Drawn
Customer
rev date
Drg.No.
Revision
Date
Date
drawn
Date
app'dchk'd
IF IN DOUBT ASKNOTES:-
DJM
SHEET 1 OF 1
For Information OnlyN.T.S.
Cargill Multi-Discipline Facility
Efremov
CUSTOMER O/NO. 1 O 031500
PROJECT NO. 40531063
BP 4_6 Segment 5440531063
Fieldbus data sheets
Profibus in Process 2013
Segments calculation and design tools
Profibus in Process 2013
Integration documents
Profibus in Process 2013
Network test and verification
• Test & verification services ensure:
• The installed networks meet the network design criteria
• They are robust and reliable
• They meet the required industrial safety standards
• They are correctly documented to assist with future maintenance
• They form part of a functional asset management system
• Reliable networks contribute to:
• Higher plant availability
• Improved plant performance
• Contributes to final product quality – regulated industries
• Improvements in maintenance procedures and cost reduction
Profibus in Process 2013
Network test and verification
• Physical inspection
• Confirm that design documents have been followed.
• Checks for bus terminators.
• Check for correct cable installation • Cable type
• Spur lengths
• Bend radius
• Cable separation
• Correct labels
• Correct number of devices per network.
• Consistent earthing concept.
• Compliance with intrinsically safe requirements.
• Junction boxes correctly installed and glanded.
Profibus in Process 2013
Network test and verification
• Communication test
• Confirm all master bus settings are correct
• Confirm all devices are in data exchange
• Ensure communication retries are within accepted tolerances
• Use industry standard analysis tools to confirm: • all devices are in data exchange
• number of communication retries
• number of communication illegal responses
• Confirm devices recover after disconnection
• Confirm system recovers on start up
Profibus in Process 2013
Certified Profibus training in the UK
Profibus in process 2013
• Profibus Competence Centre
• Profibus Training Centre
• 0161 247 6273
• Profibus Training Centre
• 01625 871199
More information at www.uk.profibus.com
Products Solutions Services
Project management, design and component selection