Document Revision: 5
ProtoNode RER and ProtoNode LER
Startup Guide
For Interfacing Product: Lochinvar’s Armor®, SYNC™/Armor X2, Knight®/Knight XL®, Crest®, Copper-Fin II ® boilers
To Building Automation Systems Utilizing: Protocols: BACnet MS/TP, BACnet IP, Modbus TCP, and LonWorks
APPLICABILITY & EFFECTIVITY
Explains the ProtoNode RER and LER hardware and how to install it.
The instructions are effective for the above as of November 2012
INS70085 Lochinvar Startup Guide Page 2 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Technical Support:
Thank you for purchasing the ProtoNode for Lochnivar Boilers. Please call Lochinvar for Technical support of the
ProtoNode product. FieldServer will not field the first phone call. If the call needs escalating, Lochinvar bring
FieldServer in to help solve problem.
Lochnivar’s contact information:
Lochinvar, LLC
300 Maddox Simpson Pkwy.
Lebanon, TN 37090
Phone: 1-800-722-2101
Technical Service email: [email protected]
www.lochinvar.com
INS70085 Lochinvar Startup Guide Page 3 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
TABLE OF CONTENTS
1 Introduction ................................................................................................................................................... 5 1.1 BTL Mark – BACnet Testing Laboratory........................................................................................................ 5
1.2 LonMark3 Certification ................................................................................................................................. 5
2 BACnet/LonWorks Setup through ProtoCessor ProtoNode RER/LER .............................................................. 6 2.1 Installation steps for the customer .............................................................................................................. 6
2.2 Record Identification Data ........................................................................................................................... 6
2.3 Setting Modbus RTU Settings on Lochinvar’s Modbus COM Board ............................................................. 7
2.4 Configure the DIP Switches .......................................................................................................................... 7
2.4.1 Setting the Node/ID Device Instance (DIP Switch A0 – A7) for BACnet MS/TP & BACnet/IP ................... 7
2.4.2 Setting the Serial Baud Rate (DIP Switch B0 – B3) for BACnet MS/TP ..................................................... 8
2.4.3 Using S0 – S3 bank of DIP Switches to select and load Configuration Files ............................................. 8
3 Interfacing the ProtoNode to Lochinvar boilers ............................................................................................ 10 3.1 ProtoNode RER and LER component layout with the cover removed ....................................................... 10
3.2 Wiring Connections to ProtoNode RER and LER ........................................................................................ 10
3.2.1 Lochinvar’s Armor, SYNC/Armor X2, Knight/Knight XL, Crest, and Copper-Fin II Low Voltage Modbus
RTU Connection Wiring to the ProtoNode: .......................................................................................................... 12
3.3 Wiring the ProtoNode RER to RS-485 Field Protocol ................................................................................. 13
3.4 Wiring the ProtoNode LER Field Port to a LonWorks network .................................................................. 14
3.5 Power-Up the ProtoNode RER or LER ........................................................................................................ 14
4 Commissioning the ProtoNode LER on a LonWorks network ........................................................................ 15 4.1 Commissioning the ProtoNode LER on a LonWorks network .................................................................... 15
4.1.1 Instructions to Upload XIF File From the ProtoNode LER Using FS GUI Web Server .............................. 15
5 Connect the ProtoNode’s Web GUI to Setup IP Address for BACnet/IP ........................................................ 17 5.1 Connect the PC to the ProtoNode via the Ethernet port ........................................................................... 17
5.2 Use the ProtoNode Web GUI to Connect to the ProtoNode ..................................................................... 18
5.3 Set IP Address for BACnet/IP TCP via GUI .................................................................................................. 18
6 Chipkin Automation’s CAS BACnet Explorer for validating the ProtoNode in the field on a BACnet MS/TP or BACnet/IP network .............................................................................................................................................. 20
6.1 Downloading Chipkin Automation’s CAS Explorer and Requesting an Activation Key .............................. 20
6.2 CAS BACnet Setup ...................................................................................................................................... 21
6.2.1 CAS BACnet MS/TP Setup ....................................................................................................................... 21
6.2.2 CAS BACnet BACnet/IP Setup ................................................................................................................. 21
Appendix A. Troubleshooting Tips ....................................................................................................................... 22 Appendix A.1. Check Wiring and Settings ................................................................................................................ 22
Appendix A.2. Take Log With Our FieldServer Utilities............................................................................................ 22
Appendix A.3. LED Diagnostics for Modbus RTU Communications between the ProtoNode and the Lochinvar
Controller’s .............................................................................................................................................................. 25
A.3.1 ProtoNode RER and LER LEDs .................................................................................................................... 25
Appendix A.4. Sync Modbus RTU Mappings to BACnet MS/TP, BACnet IP, and LonWorks .................................... 25
Appendix A.5. Knight Modbus RTU Mappings to BACnet MS/TP, BACnet IP, and LonWorks ................................. 27
Appendix A.6. Crest Modbus RTU Mappings to BACnet MS/TP, BACnet IP, and LonWorks ................................... 28
Appendix A.7. Copper-Fin II Modbus RTU Mappings to BACnet MS/TP, BACnet IP, and LonWorks ..................... 29
Appendix B. Reference ........................................................................................................................................ 31 Appendix B.1. Specifications .................................................................................................................................... 31
INS70085 Lochinvar Startup Guide Page 4 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Appendix B.1.1. Compliance with UL Regulations ............................................................................................ 31
Appendix B.2. Address DIP Switch Settings ............................................................................................................. 32
Appendix C. Limited 2 year Warranty .................................................................................................................. 38
LIST OF FIGURES
Figure 1: Lochinvar’s Modbus RTU settings for all of their boilers ................................................................................ 7 Figure 2: Lochinvar’s Modbus COM board showing serial DIP switches ....................................................................... 7 Figure 3: A0 – A7 DIP Switches for setting Device Instance/MAC Address ................................................................... 8 Figure 4: B0 – B3 DIP Switches for setting the baud rate on BACnet MS/TP................................................................. 8 Figure 5: S0 – S3 DIP Switches for selecting the proper configuration for each of Lochinvar’s Boilers ........................ 8 Figure 6: ProtoNode component layout ...................................................................................................................... 10 Figure 7: Pin outs for the Lochinvar’s Modbus RS-485 port and power to the ProtoNode ......................................... 11 Figure 8: Connection from ProtoNode to RS-485 Field Protocol –BACnet MS/TP ...................................................... 13 Figure 9: End-of-line termination on from ProtoNode to RS-485 BMS Field Protocol ................................................ 13 Figure 10: ProtoNode LER LonWorks FFT-10 2 wire screw terminal ........................................................................... 14 Figure 11: ProtoNode power pin outs ......................................................................................................................... 14 Figure 12: Sample of Fserver.XIF file being generated ................................................................................................ 16 Figure 13: Ethernet port location of ProtoNode ......................................................................................................... 17 Figure 14: FST Web GUI screen ................................................................................................................................... 18 Figure 15: FST Web GUI IP Address settings screen .................................................................................................... 19
INS70085 Lochinvar Startup Guide Page 5 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
1 INTRODUCTION
ProtoNode is an external, high performance Building Automation multi-protocol gateway that has been
preprogrammed for Lochinvar’s Armor®, SYNC™/Armor X2, Knight®/Knight XL®, Crest® and Copper-Fin II ® boilers
to support BACnet®1MS/TP, BACnet/IP and LonWorks®
2. Configurations for the various protocols are stored within
the ProtoNode and are selectable via DIP switches for fast and easy installation. It is not necessary to download
any configuration files to support the required applications.
This document provides the necessary information to facilitate installation of the ProtoNode.
1.1 BTL Mark – BACnet Testing Laboratory
1.2 LonMark3 Certification
1 BACnet is a registered trademark of ASHRAE 2 LonWorks is a registered trademark of Echelon Corporation 3 LonMark is a registered trademark of LonMark International
The BTL Mark on the ProtoNode RER is a symbol that indicates that a product has
passed a series of rigorous tests conducted by an independent laboratory which
verifies that the product correctly implements the BACnet features claimed in the
listing. The mark is a symbol of a high-quality BACnet product. Go to
http://www.bacnetinternational.net/btl/ for more information about the BACnet
Testing Laboratory.
LonMark International is the recognized authority for certification, education, and
promotion of interoperability standards for the benefit of manufacturers, integrators
and end users. LonMark International has developed extensive product certification
standards and tests to provide the integrator and user with confidence that products
from multiple manufacturers utilizing LonMark devices work together. FieldServer
Technologies has more LonMark Certified gateways than any other gateway
manufacturer, including the ProtoCessor, ProtoCarrier and ProtoNode for OEM
applications and the full featured, configurable gateways.
INS70085 Lochinvar Startup Guide Page 6 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
2 BACNET/LONWORKS SETUP THROUGH PROTOCESSOR PROTONODE RER/LER
2.1 Installation steps for the customer
1. Record the information about the unit. See Section 2.2
2. Set the Modbus RTU COM settings on the Lochinvar Boiler via DIP switches locate on the Modbus RTU
card. See Section 2.3 or the Lochinvar manual
3. Set the A, B, and S DIP Switch banks for field protocol baud rate, Node-ID/Device Instance, and proper
configuration. See Section 2.4
4. Connect the ProtoNode to the Field protocol port and Lochinvar’s Armor, SYNC/Armor X2, Knight/Knight
XL, Crest, and Copper-Fin II port to the ProtoNode’s RS-485 interface. See Section 3
5. Power up the ProtoNode RER and LER. See Section 3.6
6. Commission the ProtoNode on the LonWorks Network. This needs to be done by the LonWorks
administrator use a LonWorks Commissioning tool. See Section 4
7. If the Field protocol is BACnet/IP; run the ProtoNode web GUI to change IP. See Section 5
2.2 Record Identification Data
Each ProtoNode has a unique part number located on the underside of the unit. The numbers are as
follows:
Part number FPC-N34-103-126-0614:
o Supports Lochinvar’s Armor®, SYNC™/Armor X2, Knight®/Knight XL®, Crest® and Copper-Fin II ®
boilers to BACnet MS/TP and BACnet/IP.
Part number FPC-N35-103-401-0615:
o Supports Lochinvar’s Armor®, SYNC™/Armor X2, Knight®/Knight XL®, Crest® and Copper-Fin II ®
boilers to LonWorks.
These numbers should be recorded, as they may be required for technical support.
INS70085 Lochinvar Startup Guide Page 7 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
2.3 Setting Modbus RTU Settings on Lochinvar’s Modbus COM Board
The ProtoNode’s Modbus RTU port has been preprogrammed to support 9600 baud rate, 8 data bit, 2 stop bits, no
parity and to look for a Modbus Node-ID of 1 on the Lochinvar boilers.
Set the Lochinvar’s Modbus RTU COM setting to match Figure 1 via the DIP switches on the Lochinvar
Modbus card.
Set the DIP switch 1 to ON and 2-10 to OFF position on the Modbus COM board. This will set the Lochinvar
boiler for 9600, 8, 2, N, and Node-ID of 1.
Serial Port Setting Armor SYNC/Armor X2 Knight/Knight XL Crest Copper-Fin II
Baud Rate 9600 9600 9600 9600 9600
Data Bits 8 8 8 8 8
Stop Bits 2 2 2 2 2
Parity None None None None None
Node_ID 1 1 1 1 1
Figure 1: Lochinvar’s Modbus RTU settings for all of their boilers
Figure 2: Lochinvar’s Modbus COM board showing serial DIP switches
2.4 Configure the DIP Switches
2.4.1 Setting the Node/ID Device Instance (DIP Switch A0 – A7) for BACnet MS/TP &
BACnet/IP
The A Bank DIP switches on the ProtoNode RER allow users to set the Node-ID/Device Instance on the
Field RS-485.
DIP switches A0 – A7 can also be used to set the MAC Address for BACnet MS/TP and BACnet/IP.
INS70085 Lochinvar Startup Guide Page 8 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Figure 3: A0 – A7 DIP Switches for setting Device Instance/MAC Address
Please refer to Appendix B.2 for the full range of addresses to set Node-ID/Device Instance.
NOTE: When setting DIP Switches, please ensure that power to the board is OFF.
2.4.2 Setting the Serial Baud Rate (DIP Switch B0 – B3) for BACnet MS/TP
DIP Switches B0 – B3 can be used to set the serial baud rate to match the baud rate provided by the
Building Management System for BACnet MS/TP.
B0 B1 B2 B3
Figure 4: B0 – B3 DIP Switches for setting the baud rate on BACnet MS/TP
2.4.2.1 Baud Rate DIP Switch Selection
Baud B0 B1 B2 B3
9600 On On On Off
19200 Off Off Off On
38400 On On Off On
57600 Off Off On On
76800 On Off On On
2.4.3 Using S0 – S3 bank of DIP Switches to select and load Configuration Files
The S bank of DIP switches, S0 - S3 is used to select and load a configuration file from a group of
pretested/preloaded configuration files which are stored in the ProtoNode RER (BACnet MS/TP &
BACnet/IP) and LER (LonWorks).
S0 S1 S2 S3
Figure 5: S0 – S3 DIP Switches for selecting the proper configuration for each of Lochinvar’s Boilers
2.4.3.1 S0 – S3 DIP Switch Configuration Settings
S Bank DIP Switches
INS70085 Lochinvar Startup Guide Page 9 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
A. BACnet MS/TP and BACnet IP
The following chart describes S0 - S3 DIP Switch settings for Lochinvar’s SYNC/Armor X2, Knight, Crest, and Cooper-
fin II boilers to support BACnet MS/TP and BACnet/IP (FPC-N34).
B. LonWorks
The following chart describes S0 – S3 DIP Switch configuration settings for Lochinvar’s Armor, SYNC, Knight/Knight
XL, Crest, and Cooper-fin II boilers to support LonWorks on a ProtoNode LER (FPC-N35).
NOTE: When setting DIP Switches, please ensure that power to the board is OFF.
ProtoNode RER FPC-N34-103-126-0614 S0 S1 S2 S3
BACnet IP/BACnet MSTP/Modbus TCP SYNC/ Armor X2 Deg_C
Off Off Off Off
BACnet IP/BACnet MSTP/Modbus TCP Knight/Knight XL/Armor/Wall Mount/Wall Hung Deg_C
On Off Off Off
BACnet IP/BACnet MSTP/Modbus TCP Crest Deg_C Off On Off Off
BACnet IP/BACnet MSTP/Modbus TCP Copper-Fin II Deg_C On On Off Off
BACnet IP/BACnet MSTP/Modbus TCP SYNC/Armor X2 Deg_F Off Off On Off
BACnet IP/BACnet MSTP/Modbus TCP Knight/Knight XL/Armor/Wall Mount/Wall Hung Deg_F
On Off On Off
BACnet IP/BACnet MSTP/Modbus TCP Crest Deg_F Off On On Off
BACnet IP/BACnet MSTP/Modbus TCP Copper-Fin II Deg_F On On On Off
ProtoNode LER FPC-N35-103-401-0615 S0 S1 S2 S3
LonWorks SYNC/Armor X2 Off Off Off Off
LonWorks Knight/Knight XL/Armor/Wall Mount/Wall Hung On Off Off Off
LonWorks Crest Off On Off Off
LonWorks Copper-Fin II On On Off Off
INS70085 Lochinvar Startup Guide Page 10 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
3 INTERFACING THE PROTONODE TO LOCHINVAR BOILERS
3.1 ProtoNode RER and LER component layout with the cover removed
Figure 6: ProtoNode component layout
3.2 Wiring Connections to ProtoNode RER and LER
ProtoNode 6 Pin Phoenix connector – Pinouts
INS70085 Lochinvar Startup Guide Page 11 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Figure 7: Pin outs for the Lochinvar’s Modbus RS-485 port and power to the ProtoNode
( + )
( - )
INS70085 Lochinvar Startup Guide Page 12 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
3.2.1 Lochinvar’s Armor, SYNC/Armor X2, Knight/Knight XL, Crest, and Copper-Fin II
Low Voltage Modbus RTU Connection Wiring to the ProtoNode:
On the Lochinvar’s Modbus terminal strip, connect Pin A (RS-485+) to B+ (RS-485+) on the ProtoNode’s 6
Pin Phoenix connector.
On the Lochinvar’s Modbus terminal strip, connect Pin B (RS-485-) to A- (RS-485-) on the ProtoNode’s 6
pin Phoenix connector.
The Shield Pin the terminal strip which is Ground on the does not need to be grounded to the ProtoNode.
INS70085 Lochinvar Startup Guide Page 13 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
3.3 Wiring the ProtoNode RER to RS-485 Field Protocol
Connection from ProtoNode RER to BACnet MS/TP
The Field Protocol can be connected to the 3-pin connector on ProtoNode RER as shown:
Figure 8: Connection from ProtoNode to RS-485 Field Protocol –BACnet MS/TP
See Section 5 for information on connecting the ProtoNode RER to a BACnet/IP network.
If the ProtoNode is the last device on the BACnet MS/TP or Metasys N2 RS-485 trunk, then enable the
End-of-line termination needs to be enabled. The default is off.
Figure 9: End-of-line termination on from ProtoNode to RS-485 BMS Field Protocol
End-of-Line Switch
INS70085 Lochinvar Startup Guide Page 14 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
3.4 Wiring the ProtoNode LER Field Port to a LonWorks network
Connect the ProtoNode to the field network with the LonWorks terminal using a twisted pair non-
shielded cable. LonWorks has no polarity.
Figure 10: ProtoNode LER LonWorks FFT-10 2 wire screw terminal
3.5 Power-Up the ProtoNode RER or LER
Apply power to the device. Ensure that the power supply used complies with the specifications provided in
Appendix B.1. Ensure that the cable is grounded using the “Frame-GND” terminal. The ProtoNode is factory set to
accept both 9-30VDC and 12-24 VAC.
Voltage Pin outs
Figure 11: ProtoNode power pin outs
INS70085 Lochinvar Startup Guide Page 15 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
4 COMMISSIONING THE PROTONODE LER ON A LONWORKS NETWORK
Commissioning may only be performed by the LonWorks administrator.
4.1 Commissioning the ProtoNode LER on a LonWorks network
To commission the ProtoNode LER LonWorks port, insert a small screwdriver in the commissioning hole on the
face of the LER’s enclosure to access the Service Pin. See the illustration on the ProtoNode LER as to which way to
toggle the screw driver during commissioning.
If an XIF file is required, see steps Section 4.1.1 to generate XIF
4.1.1 Instructions to Upload XIF File From the ProtoNode LER Using FS GUI Web Server
Connect a standard cat5 Ethernet cable between the PC and ProtoNode
The Default IP Address of the ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and the
ProtoNode are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx network
For Windows XP:
Go to > >
Right-click on Local Area Connection > Properties
Highlight >
For Windows 7:
Go to > >
> >
Right-click on Local Area Connection > Properties
Highlight >
LonWorks Service Pin
INS70085 Lochinvar Startup Guide Page 16 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
For Windows XP and Windows 7, select: Use the following IP address
Click twice
Open a web browser and go to the following address: IP address of ProtoCessor/fserver.xif
Example: 192.168.1.24/fserver.xif
Download and save the file onto the PC.
Figure 12: Sample of Fserver.XIF file being generated
INS70085 Lochinvar Startup Guide Page 17 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
5 CONNECT THE PROTONODE’S WEB GUI TO SETUP IP ADDRESS FOR BACNET/IP
5.1 Connect the PC to the ProtoNode via the Ethernet port
Figure 13: Ethernet port location of ProtoNode
Connect a standard CAT5 Ethernet cable (straight through or cross) between the PC and ProtoNode
The Default IP Address of the ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and the
ProtoNode are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx network
Go to > >
Right-click on Local Area Connection > Properties
Highlight >
Select: Use the following IP address
Click twice
Ethernet Port
INS70085 Lochinvar Startup Guide Page 18 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
5.2 Use the ProtoNode Web GUI to Connect to the ProtoNode
Open PC web browser; enter the default IP address of the ProtoNode 192.168.1.24, to determine if the
ProtoNode is up and communicating.
Figure 14: FST Web GUI screen
5.3 Set IP Address for BACnet/IP TCP via GUI
Open a PC web browser, enter the default IP address of the ProtoNode 192.168.1.24 and connect to the
ProtoNode.
From the GUI main home page, click on setup and then Network Settings to enter the Edit IP Address
Settings menu.
Modify the IP address (N1 IP address field) of the ProtoNode Ethernet port.
If necessary, change the Netmask (N1 Netmask field).
Type in a new Subnet Mask.
If necessary, change the IP Gateway (Default Gateway field).
Type in a new IP Gateway.
Note: If the ProtoNode is connected to a router, the IP Gateway of the ProtoNode should be set to the IP
address of the router that it is connected to.
Reset ProtoNode.
Unplug Ethernet cable from PC and connect it to the network hub or router.
INS70085 Lochinvar Startup Guide Page 19 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Figure 15: FST Web GUI IP Address settings screen
INS70085 Lochinvar Startup Guide Page 20 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
6 CHIPKIN AUTOMATION’S CAS BACNET EXPLORER FOR VALIDATING THE PROTONODE
IN THE FIELD ON A BACNET MS/TP OR BACNET/IP NETWORK
Chipkin Automation has extended to Lochinvar and their customers a free complementary 2 week fully functional
copy of CAS BACnet Explorer that can be used to validate BACnet MS/TP and/or BACnet/IP communications of the
ProtoNode in the field without having to have the BMS Integrator on site. A Serial or USB to RS-485 converter is
needed to test BACnet MS/TP.
6.1 Downloading Chipkin Automation’s CAS Explorer and Requesting an Activation Key
To request a 2 week complementary BACnet CAS key, go to http://app.chipkin.com/activation/twoweek/
and fill in all the information. Enter Vendor Code “lochinvar12”. Once completed, the key will be sent to
the email address that was submitted. From this email from Chipkin Automation, the long key will need to
be copied and pasted into the CAS key activation page.
Go to Chipkin Automation’s web site, download, and install the CAS BACnet Explorer to your PC
http://www.chipkin.com/technical-resources/cas-bacnet-explorer/.
In the CAS Activation form, enter the email address and paste the CAS key that was sent from Chipkin
Automation. Once completed, select Activation.
INS70085 Lochinvar Startup Guide Page 21 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
6.2 CAS BACnet Setup
These are the instructions to set CAS Explorer up for the first time on BACnet MS/ST and BACnet/IP.
6.2.1 CAS BACnet MS/TP Setup
Using the Serial or USB to RS-485 converter, connect it to your PC and the 3 Pin BACnet MS/TP connector
on the ProtoNode RER.
In CAS Explorer, do the following:
o Click on settings o Check the BACnet MSTP box and uncheck the BACnet IP and BACnet Ethernet boxes. o Set the BACnet MSTP MAC address to 0. o Set the BACnet MSTP Baud Rate to 38400. o Click Ok. o On the bottom right-hand corner, make sure that the BACnet MSTP box is green. o Click on discover. o Check all 4 boxes. o Click Send.
6.2.2 CAS BACnet BACnet/IP Setup
See Section 5.1 to set the IP address and subnet of the PC that will be running the CAS Explorer.
Connect a straight through or cross Ethernet cable from the PC to the ProtoNode.
In CAS Explorer, do the following:
o Click on settings o Check the BACnet IP box and uncheck the BACnet MSTP and BACnet Ethernet boxes. o In the “Select a Network Device” box, select the network card of the PC by clicking on it. o Click Ok. o On the bottom right-hand corner, make sure that the BACnet IP box is green. o Click on discover. o Check all 4 boxes. o Click Send.
INS70085 Lochinvar Startup Guide Page 22 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Appendix A. Troubleshooting Tips
Appendix A.1. Check Wiring and Settings
No COMS on Modbus RTU side. If TX/RX is not flashing rapidly then there is a COM issue on the Modbus side and you need to check the following things: o Visual observations of LEDs on ProtoNode. See Appendix A.3 o Check baud rate, parity, data bits, stop bits o Check Modbus device address o Verify wiring
Field COM problems. o Visual observations of LEDs on ProtoNode. See Appendix A.3 o Visual dipswitch settings (using correct baud rate and device instance) o Verify IP address setting o Verify wiring
If the problem still exists, a log needs to be taken and sent to FieldServer. See Appendix A.2
Appendix A.2. Take Log With Our FieldServer Utilities
Once the log is complete, email it to [email protected]. The log will allow us to rapidly diagnose
the problem.
Make sure the FieldServer utilities are loaded on the PC.
http://fieldserver.com/techsupport/utility/utility.php
Disable any wireless Ethernet adapters on the PC/Laptop.
Disable firewall and virus protection software.
Connect a standard cat5 Ethernet cable between the PC and ProtoNode.
The Default IP Address of the ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and the
ProtoNode are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx network
For Windows XP:
Go to > >
Right-click on Local Area Connection > Properties
Highlight >
Ethernet Port
INS70085 Lochinvar Startup Guide Page 23 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
For Windows 7:
Go to > >
> >
Right-click on Local Area Connection > Properties
Highlight >
For Windows XP and Windows 7, select: Use the following IP address
Click twice
Double click on the FST Diag Utility.
Step 1: Select a Field Server IP Address.
The IP address can be entered manually or selected by clicking on button 1 using the Utility.
Type in the ProtoNode IP address Default IP Address is 192.168.1.24
Press here to retrieve the IP address.
Locate where the log is saved on the PC
INS70085 Lochinvar Startup Guide Page 24 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Step 2: Take a Log
Press the Take Log button. While the Utility runs a few DOS prompts will flash across the monitor. Don't
click or type anything in to these DOS prompts. This step may take a few minutes depending on the
chosen Log Type and computer speed. When the Utility is finished you will be presented with a log of
events that have occurred.
Step 3: Send Log
Click the “Send Log” button located near the bottom of the dialog. The following dialog should appear.
Push the ‘Locate Folder’ button to launch explorer and have it point directly at the correct folder. The file
upload.zip must be sent to [email protected].
Step 4: Close the Program
Press the exit button when the log is completed
Select a log type.
Press the Take Log button.
INS70085 Lochinvar Startup Guide Page 25 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Appendix A.3. LED Diagnostics for Modbus RTU Communications between the ProtoNode and the
Lochinvar Controller’s
Please see the diagram below for LED Locations
A.3.1 ProtoNode RER and LER LEDs
Light Description For ProtoNode RER and LER
RTC Unused
RUN The RUN LED will start flashing 20 seconds after power indicating normal operation.
ERR The SYS ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red light will indicate there is a system error on the ProtoNode. If this occurs, immediately report the related “system error” shown in the error screen of the RUI interface to FieldServer Technologies for evaluation.
RX The RX LED will flash when a message is received on the socket port.
TX The TX LED will flash when a message is sent on the socket port.
PWR This is the power light and should show steady green at all times when the ProtoNode is powered.
Appendix A.4. Sync Modbus RTU Mappings to BACnet MS/TP, BACnet IP, and LonWorks
Map_Descriptor_Name BACnet Object
Type BACnet
Object Id Lonworks Name Lonworks SNVT Type
Boiler Enable/Room Thermostat 1/Stg 1 BV 1 oBlrEn_Stg1 SNVT_switch
Tank Thermostat BV 2 oTankThermostat SNVT_switch
Manual Reset High Limit 1 BI 3 oManResHiLim1 SNVT_switch
Flow Switch 1 BI 4 oFLoSw1 SNVT_switch
Gas Pressure Switch 1 BI 5 oGasPrsSw1 SNVT_switch
Louver Proving Switch 1 BI 6 oLouverProvSw1 SNVT_switch
Air Pressure Switch/Flap Vlv 1 BI 7 oAirPrsSwFlpVlv1 SNVT_switch
Blocked Drain Switch 1 BI 8 oBlockedDrainSw1 SNVT_switch
Auto Reset High Limit 1 BI 9 oAutoResHiLim1 SNVT_switch
Flame 1 BI 10 oFlame1 SNVT_switch
Enable/Room Thermostat 1/Stg 1 BI 11 oEnRmThermStg1 SNVT_switch
Tank Thermostat BI 12 oTnkThermostat SNVT_switch
Manual Reset High Limit 2 BI 13 oManResHiLim2 SNVT_switch
Flow Switch 2 BI 14 oFLoSw2 SNVT_switch
Gas Pressure Switch 2 BI 15 oGasPrsSw2 SNVT_switch
INS70085 Lochinvar Startup Guide Page 26 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Map_Descriptor_Name BACnet Object
Type BACnet
Object Id Lonworks Name Lonworks SNVT Type
Louver Proving Switch 2 BI 16 oLouverProvSw2 SNVT_switch
Air Pressure Switch/Flap Vlv 2 BI 17 oAirPrsSwFlpVlv2 SNVT_switch
Blocked Drain Switch 2 BI 18 oBlockedDrainSw2 SNVT_switch
Flame 2 BI 19 oFlame2 SNVT_switch
Run-time Contacts BI 20 oRunTimeContcts SNVT_switch
Alarm Contacts 1 BI 21 oAlarmContacts1 SNVT_switch
CH Pump 1 BI 22 oCHPump1 SNVT_switch
DHW Pump 1 BI 23 oDHWPump1 SNVT_switch
Gas Vlv 1 BI 24 oGasVlv1 SNVT_switch
System Pump BI 25 oSystemPump SNVT_switch
Run-time Contacts 2 BI 26 oRunTimeContcts2 SNVT_switch
Alarm Contacts 2 BI 27 oAlarmContacts2 SNVT_switch
CH Pump 2 BI 28 oCHPump2 SNVT_switch
Gas Vlv 2 BI 29 oGasVlv2 SNVT_switch
Discrete Inputs 1 - 16 AI 30 oDiscInputs1-16 SNVT_count_f
Discrete Inputs 17 - 32 AI 31 oDiscInputs17-32 SNVT_count_f
Discrete Inputs 33 - 48 AI 32 oDiscInputs33-48 SNVT_count_f
System/Cascade Setpoint AI 33 oSysCascadeSP SNVT_temp_p
Cascade Total Power AI 34 oCascadeTotalPwr SNVT_lev_percent
Cascade Current Power AI 35 oCascadeCrrntPwr SNVT_lev_percent
Outlet Setpoint 1 AI 36 oOutletSP1 SNVT_temp_p
Outlet Temperature 1 AI 37 oOutletTmp1 SNVT_temp_p
Inlet Temperature 1 AI 38 oInletTmp1 SNVT_temp_p
Flue Temperature 1 AI 39 oFlueTmp1 SNVT_temp_p
Firing Rate 1 AI 40 oFiringRate1 SNVT_lev_percent
Boiler 1 Status Code AI 41 oBlr1StatusCode SNVT_count_f
Boiler 1 Blocking Code AI 42 oBlr1BlckngCode SNVT_count_f
Boiler 1 Lockout Code AI 43 oBlr1LockoutCode SNVT_count_f
Outlet Setpoint 2 AI 44 oOutletSP2 SNVT_temp_p
Outlet Temperature 2 AI 45 oOutletTmp2 SNVT_temp_p
Inlet Temperature 2 AI 46 oInletTmp2 SNVT_temp_p
Flue Temperature 2 AI 47 oFlueTmp2 SNVT_temp_p
Firing Rate 2 AI 48 oFiringRate2 SNVT_lev_percent
Boiler 2 Status Code AI 49 oBlr2StatusCode SNVT_count_f
Boiler 2 Blocking Code AI 50 oBlr2BlckngCode SNVT_count_f
Boiler 2 Lockout Code AI 51 oBlr2LockoutCode SNVT_count_f
Configuration AV 52 oConfiguration SNVT_count_f
Coils AV 53 oCoils SNVT_count_f
0-10 Volt Input/Rate Cmd/SP Cmd AV 54 o0-10VltInRtCmd SNVT_lev_percent
Tank Setpoint AV 55 oTankSP SNVT_temp_p
Tank Temperature AV 56 oTankTmp SNVT_temp_p
Outdoor Temperature AV 57 oOutdoorTmp SNVT_temp_p
System Supply Temperature AV 58 oSysSupplyTmp SNVT_temp_p
INS70085 Lochinvar Startup Guide Page 27 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Appendix A.5. Knight Modbus RTU Mappings to BACnet MS/TP, BACnet IP, and LonWorks
Map_Descriptor_Name BACnet Object
Type BACnet
Object Id Lonworks Name Lonworks SNVT Type
Room Thermostat 1 BV 1 oRmThermostat1 SNVT_switch
Room Thermostat 2 BV 2 oRmThermostat2 SNVT_switch
Room Thermostat 3 BV 3 oRmThermostat3 SNVT_switch
Tank Thermostat BV 4 oTankThermostat SNVT_switch
Flow Switch BI 5 oFlowSw SNVT_switch
Gas Pressure Switch BI 6 oGasPressureSw SNVT_switch
Louver Proving Switch BI 7 oLouverPrvingSw SNVT_switch
Air Pressure Switch BI 8 oAirPressureSw SNVT_switch
Blocked Drain Switch BI 9 oBlockedDrainSw SNVT_switch
Auto Reset High Limit BI 10 oAutoResetHiLim SNVT_switch
Flame BI 11 oFlame SNVT_switch
Room Thermostat 1 BI 12 oRmThrmostat1 SNVT_switch
Tank Thermostat BI 13 oTnkThrmostat SNVT_switch
Room Thermostat 2 BI 14 oRmThrmostat2 SNVT_switch
Run-time Contacts BI 15 oRunTimeContacts SNVT_switch
Alarm Contacts BI 16 oAlarmContacts SNVT_switch
CH Pump BI 17 oCHPump SNVT_switch
DHW Pump BI 18 oDHWPump SNVT_switch
Gas Valve BI 19 oGasValve SNVT_switch
System Pump BI 20 oSystemPump SNVT_switch
Discrete Inputs 1 - 16 AI 21 oDiscInputs1-16 SNVT_count_f
Discrete Inputs 17 - 32 AI 22 oDiscInputs17-32 SNVT_count_f
Discrete Inputs 33 - 48 AI 23 oDiscInputs33-48 SNVT_count_f
System Cascade Setpoint AI 24 oSystemCascadeSP SNVT_temp_p
System Pump Speed AI 25 oSystemPumpSpeed SNVT_lev_percent
Cascade Total Power AI 26 oCascadeTotalPwr SNVT_lev_percent
Cascade Current Power AI 27 oCascadeCrrntPwr SNVT_lev_percent
Outlet Setpoint AI 28 oOutletSP SNVT_temp_p
Outlet Temperature AI 29 oOutletTmp SNVT_temp_p
Inlet Temperature AI 30 oInletTmp SNVT_temp_p
Flue Temperature AI 31 oFlueTmp SNVT_temp_p
Firing Rate AI 32 oFiringRate SNVT_lev_percent
Boiler Pump Speed AI 33 oBlrPumpSpeed SNVT_lev_percent
Boiler Status Code AI 34 oBlrStatusCode SNVT_count_f
Boiler Blocking Code AI 35 oBlrBlockingCode SNVT_count_f
Boiler Lockout Code AI 36 oBlrLockoutCode SNVT_count_f
Configuration AV 37 oConfiguration SNVT_count_f
Coils AV 38 oCoils SNVT_count_f
0-10 Volt Input/Rate Cmd/SP Cmd AV 39 o0-10VltInRtCmd SNVT_lev_percent
Tank Setpoint AV 40 oTankSP SNVT_temp_p
Tank Temperature AV 41 oTankTmp SNVT_temp_p
Outdoor Temperature AV 42 oOutdoorTmp SNVT_temp_p
System Supply Temperature AV 43 oSystemSupplyTmp SNVT_temp_p
System Return Temperature AV 44 oSystemReturnTmp SNVT_temp_p
INS70085 Lochinvar Startup Guide Page 28 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Appendix A.6. Crest Modbus RTU Mappings to BACnet MS/TP, BACnet IP, and LonWorks
Map_Descriptor_Name BACnet Object
Type BACnet
Object Id Lonworks Name Lonworks SNVT Type
Boiler Enable BV 1 nvoBoilerEnable SNVT_switch
Tank Thermostat BV 2 nvoTnkThermostat SNVT_switch
Manual Reset High Limit BI 3 nvoManResetHiLim SNVT_switch
Flow Switch BI 4 nvoFlowSw SNVT_switch
Gas Pressure Switch BI 5 nvoGasPrsSw SNVT_switch
Louvers Proving Switch BI 6 nvoLouversPrvSw SNVT_switch
Blower Proving Switch 1 BI 7 nvoBlwrPrvSw1 SNVT_switch
Blocked Drain Switch BI 8 nvoBlkDrainSw SNVT_switch
Flame 1 BI 9 nvoFlame1 SNVT_switch
Enable BI 10 nvoEnable SNVT_switch
Tank Thermostat BI 11 nvoTnkThrmostat SNVT_switch
Blocked Flue BI 12 nvoBlockedFlue SNVT_switch
Blower Proving Switch 2 BI 13 nvoBlwrPrvSw2 SNVT_switch
Flue Damper Proving Switch BI 14 nvoFlueDmprPrvSw SNVT_switch
Flame 2 BI 15 nvoFlame2 SNVT_switch
Run Time Contacts BI 16 nvoRunTimContcts SNVT_switch
Alarm Contacts BI 17 nvoAlarmContacts SNVT_switch
SH Pump BI 18 nvoSHPump SNVT_switch
HWG Pump BI 19 nvoHWGPump SNVT_switch
Louver Relay BI 20 nvoLouverRel SNVT_switch
Gas Valve 1 BI 21 nvoGasVlv1 SNVT_switch
System Pump BI 22 nvoSysPump SNVT_switch
Vent Damper Relay BI 23 nvoVentDmprRel SNVT_switch
Gas Valve 2 BI 24 nvoGasVlv2 SNVT_switch
Blower #1 Power BI 25 nvoBlwr#1Pwr SNVT_switch
Blower #2 Power BI 26 nvoBlwr#2Pwr SNVT_switch
Spark Igniter BI 27 nvoSparkIgniter SNVT_switch
Discrete Inputs 01-16 AI 28 nvoDI_01_16 SNVT_count_f
Discrete Inputs 17-32 AI 29 nvoDI_17_32 SNVT_count_f
Discrete Inputs 33-48 AI 30 nvoDI_33_48 SNVT_count_f
System Cascade Setpoint AI 31 nvoSysCascadeSP SNVT_temp_p
System Pump Speed In AI 32 nvoSysPumpSpdIn SNVT_lev_percent
Cascade Total Power AI 33 nvoCascdTotPwr SNVT_lev_percent
Cascade Current Power AI 34 nvoCascdCrntPwr SNVT_lev_percent
Outlet Setpoint AI 35 nvoOutletSP SNVT_temp_p
Outlet Temperature AI 36 nvoOutletTmp SNVT_temp_p
Inlet Temperature AI 37 nvoInletTmp SNVT_temp_p
Flue Temperature AI 38 nvoFlueTmp SNVT_temp_p
Firing Rate AI 39 nvoFiringRate SNVT_lev_percent
Boiler Pump Speed Out AI 40 nvoBlrPmpSpdOut SNVT_lev_percent
Boiler Status Code AI 41 nvoBlrStatusCode SNVT_count_f
Boiler Blocking Code AI 42 nvoBlrBlckngCode SNVT_count_f
Boiler Lock Out Code AI 43 nvoBlrLckOutCode SNVT_count_f
Configuration AV 44 nvoConfiguration SNVT_count_f
Coils AV 45 nvoCoils SNVT_count_f
0-10 Volt Input AV 46 nvo0-10VoltInput SNVT_lev_percent
Tank Setpoint AV 47 nvoTnkSP SNVT_temp_p
INS70085 Lochinvar Startup Guide Page 29 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Map_Descriptor_Name BACnet Object
Type BACnet
Object Id Lonworks Name Lonworks SNVT Type
Tank Temperature AV 48 nvoTnkTmp SNVT_temp_p
Outdoor Temperature AV 49 nvoOutdoorTmp SNVT_temp_p
System Supply Temperature AV 50 nvoSysSupplyTmp SNVT_temp_p
System Return Temperature AV 51 nvoSysReturnTmp SNVT_temp_p
Appendix A.7. Copper-Fin II Modbus RTU Mappings to BACnet MS/TP, BACnet IP, and LonWorks
Map_Descriptor_Name BACnet Object
Type BACnet
Object Id Lonworks Name Lonworks SNVT Type
Stage 1 Enable BV 1 nvoStg1Enable SNVT_switch
Stage 2 Enable BV 2 nvoStg2Enable SNVT_switch
Stage 3 Enable BV 3 nvoStg3Enable SNVT_switch
Stage 4 Enable BV 4 nvoStg4Enable SNVT_switch
Tank Thermostat BV 5 nvoTankThrmstat SNVT_switch
High Limits BI 6 nvoHiLimits SNVT_switch
Flow Switch BI 7 nvoFlowSw SNVT_switch
Gas Pressure Switch BI 8 nvoGasPresSw SNVT_switch
Louver Proving Switch BI 9 nvoLouverProvSw SNVT_switch
Air Pressure Switch BI 10 nvoAirPresSw SNVT_switch
Flame 1 BI 11 nvoFlame1 SNVT_switch
Stage 1 On BI 12 nvoStg1On SNVT_switch
Tank Thermostat BI 13 nvoTnkThrmstat SNVT_switch
Stage 2 On BI 14 nvoStg2On SNVT_switch
Stage 3 On BI 15 nvoStg3On SNVT_switch
Stage 4 On BI 16 nvoStg4On SNVT_switch
Flame 2 BI 17 nvoFlame2 SNVT_switch
Enable 2 BI 18 nvoEnable2 SNVT_switch
Run Time Contacts BI 19 nvoRunTimContct SNVT_switch
Alarm Contacts BI 20 nvoAlarmContact SNVT_switch
HTR Pump BI 21 nvoHTRPump SNVT_switch
DHW Pump BI 22 nvoDHWPump SNVT_switch
Louver Relay BI 23 nvoLouverRelay SNVT_switch
Gas Valve 1 BI 24 nvoGasValve1 SNVT_switch
System Pump BI 25 nvoSysPump SNVT_switch
Gas Valve 2 BI 26 nvoGasValve2 SNVT_switch
Gas Valve 3 BI 27 nvoGasValve3 SNVT_switch
Gas Valve 4 BI 28 nvoGasValve4 SNVT_switch
Discrete Inputs 01-16 AI 29 nvoDI_01_16 SNVT_count_f
Discrete Inputs 17-32 AI 30 nvoDI_17_32 SNVT_count_f
Discrete Inputs 33-48 AI 31 nvoDI_33_48 SNVT_count_f
System Cascade Setpoint AI 32 nvoSysCascadeSP SNVT_temp_p
System Pump Speed AI 33 nvoSysPumpSpeed SNVT_lev_percent
Cascade Total Power AI 34 nvoCascdTotPwr SNVT_lev_percent
Cascade Current Power AI 35 nvoCascdCrntPwr SNVT_lev_percent
Outlet Setpoint AI 36 nvoOutletSP SNVT_temp_p
Outlet Temperature AI 37 nvoOutletTmp SNVT_temp_p
Inlet Temperature AI 38 nvoInletTmp SNVT_temp_p
Pool Temperature AI 39 nvoPoolTmp SNVT_temp_p
Firing Rate AI 40 nvoFiringRate SNVT_lev_percent
INS70085 Lochinvar Startup Guide Page 30 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Map_Descriptor_Name BACnet Object
Type BACnet
Object Id Lonworks Name Lonworks SNVT Type
Boiler Status Code AI 41 nvoBlrStatusCode SNVT_count_f
Boiler Blocking Code AI 42 nvoBlrBlckngCode SNVT_count_f
Boiler Lockout Code AI 43 nvoBlrLckOutCode SNVT_count_f
Configuration AV 45 nvoConfiguration SNVT_count_f
Coils AV 46 nvoCoils SNVT_count_f
0-10 Volt Input AV 47 nvo0-10VoltInput SNVT_lev_percent
Pool Setpoint AV 48 nvoPoolSetpoint SNVT_temp_p
Tank Temperature AV 49 nvoTankTmp SNVT_temp_p
Outdoor Temperature AV 50 nvoOutdoorTmp SNVT_temp_p
System Supply Temperature AV 51 nvoSysSupplyTmp SNVT_temp_p
System Return Temperature AV 52 nvoSysReturnTmp SNVT_temp_p
INS70085 Lochinvar Startup Guide Page 31 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Appendix B. Reference
Appendix B.1. Specifications
ProtoNode RER ProtoNode LER
Electrical Connections
One 6-pin Phoenix connector, one RS-485
+/- ground port, power +/- frame ground
port
One 3-pin RS-485 Phoenix connector, one
RS-485 +/- ground port
One Ethernet-10/100 Ethernet port
One 6-pin Phoenix connector, one RS-485
+/- ground port, power +/- frame ground
port
One Ethernet 10/100 BaseT port
One FTT-10 LonWorks port
Approvals
CE (EN55022;EN55024; EN60950), UL916, FCC Class A Part 15, DNP3 Conformance Tested,
OPC Self-tested for Compliance, RoHS Compliant, CSA 205 Approved
BTL Marked LonMark Certified
Power Requirements
Multi-mode power adapter: 9-30VDC or 12 - 24VAC
Physical Dimensions
11.5 cm L x 8.3 cm W x 4.1 cm H (4.5 x 3.2 x 1.6 in.)
Weight 0.2 kg (0.4 lbs)
Operating Temperature
-40°C to 75°C (-40°F to167°F)
Surge Suppression
EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT
Humidity 5 - 90% RH (non-condensing)
(Specifications subject to change without notice)
Appendix B.1.1. Compliance with UL Regulations
For UL compliance, the following instructions must be met when operating the ProtoNode.
The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating
temperature range.
The interconnecting power connector and power cable shall:
Comply with local electrical code
Be suited to the expected operating temperature range
Meet the current and voltage rating for the ProtoNode/Net
Furthermore, the interconnecting power cable shall:
Be of length not exceeding 3.05m (118.3”)
Be constructed of materials rated VW-1 or FT-1 or better
If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be
installed in a Restricted Access Area requiring a key or a special tool to gain access.
This device must not be connected to a LAN segment with outdoor wiring.
INS70085 Lochinvar Startup Guide Page 32 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Appendix B.2. Address DIP Switch Settings
A7 A6 A5 A4 A3 A2 A1 A0 Address
Off Off Off Off Off Off Off Off 0
Off Off Off Off Off Off Off On 1
Off Off Off Off Off Off On Off 2
Off Off Off Off Off Off On On 3
Off Off Off Off Off On Off Off 4
Off Off Off Off Off On Off On 5
Off Off Off Off Off On On Off 6
Off Off Off Off Off On On On 7
Off Off Off Off On Off Off Off 8
Off Off Off Off On Off Off On 9
Off Off Off Off On Off On Off 10
Off Off Off Off On Off On On 11
Off Off Off Off On On Off Off 12
Off Off Off Off On On Off On 13
Off Off Off Off On On On Off 14
Off Off Off Off On On On On 15
Off Off Off On Off Off Off Off 16
Off Off Off On Off Off Off On 17
Off Off Off On Off Off On Off 18
Off Off Off On Off Off On On 19
Off Off Off On Off On Off Off 20
Off Off Off On Off On Off On 21
Off Off Off On Off On On Off 22
Off Off Off On Off On On On 23
Off Off Off On On Off Off Off 24
Off Off Off On On Off Off On 25
Off Off Off On On Off On Off 26
Off Off Off On On Off On On 27
Off Off Off On On On Off Off 28
Off Off Off On On On Off On 29
Off Off Off On On On On Off 30
Off Off Off On On On On On 31
Off Off On Off Off Off Off Off 32
Off Off On Off Off Off Off On 33
Off Off On Off Off Off On Off 34
Off Off On Off Off Off On On 35
Off Off On Off Off On Off Off 36
Off Off On Off Off On Off On 37
Off Off On Off Off On On Off 38
Off Off On Off Off On On On 39
Off Off On Off On Off Off Off 40
Off Off On Off On Off Off On 41
Off Off On Off On Off On Off 42
INS70085 Lochinvar Startup Guide Page 33 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
A7 A6 A5 A4 A3 A2 A1 A0 Address
Off Off On Off On Off On On 43
Off Off On Off On On Off Off 44
Off Off On Off On On Off On 45
Off Off On Off On On On Off 46
Off Off On Off On On On On 47
Off Off On On Off Off Off Off 48
Off Off On On Off Off Off On 49
Off Off On On Off Off On Off 50
Off Off On On Off Off On On 51
Off Off On On Off On Off Off 52
Off Off On On Off On Off On 53
Off Off On On Off On On Off 54
Off Off On On Off On On On 55
Off Off On On On Off Off Off 56
Off Off On On On Off Off On 57
Off Off On On On Off On Off 58
Off Off On On On Off On On 59
Off Off On On On On Off Off 60
Off Off On On On On Off On 61
Off Off On On On On On Off 62
Off Off On On On On On On 63
Off On Off Off Off Off Off Off 64
Off On Off Off Off Off Off On 65
Off On Off Off Off Off On Off 66
Off On Off Off Off Off On On 67
Off On Off Off Off On Off Off 68
Off On Off Off Off On Off On 69
Off On Off Off Off On On Off 70
Off On Off Off Off On On On 71
Off On Off Off On Off Off Off 72
Off On Off Off On Off Off On 73
Off On Off Off On Off On Off 74
Off On Off Off On Off On On 75
Off On Off Off On On Off Off 76
Off On Off Off On On Off On 77
Off On Off Off On On On Off 78
Off On Off Off On On On On 79
Off On Off On Off Off Off Off 80
Off On Off On Off Off Off On 81
Off On Off On Off Off On Off 82
Off On Off On Off Off On On 83
Off On Off On Off On Off Off 84
Off On Off On Off On Off On 85
Off On Off On Off On On Off 86
Off On Off On Off On On On 87
INS70085 Lochinvar Startup Guide Page 34 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
A7 A6 A5 A4 A3 A2 A1 A0 Address
Off On Off On On Off Off Off 88
Off On Off On On Off Off On 89
Off On Off On On Off On Off 90
Off On Off On On Off On On 91
Off On Off On On On Off Off 92
Off On Off On On On Off On 93
Off On Off On On On On Off 94
Off On Off On On On On On 95
Off On On Off Off Off Off Off 96
Off On On Off Off Off Off On 97
Off On On Off Off Off On Off 98
Off On On Off Off Off On On 99
Off On On Off Off On Off Off 100
Off On On Off Off On Off On 101
Off On On Off Off On On Off 102
Off On On Off Off On On On 103
Off On On Off On Off Off Off 104
Off On On Off On Off Off On 105
Off On On Off On Off On Off 106
Off On On Off On Off On On 107
Off On On Off On On Off Off 108
Off On On Off On On Off On 109
Off On On Off On On On Off 110
Off On On Off On On On On 111
Off On On On Off Off Off Off 112
Off On On On Off Off Off On 113
Off On On On Off Off On Off 114
Off On On On Off Off On On 115
Off On On On Off On Off Off 116
Off On On On Off On Off On 117
Off On On On Off On On Off 118
Off On On On Off On On On 119
Off On On On On Off Off Off 120
Off On On On On Off Off On 121
Off On On On On Off On Off 122
Off On On On On Off On On 123
Off On On On On On Off Off 124
Off On On On On On Off On 125
Off On On On On On On Off 126
Off On On On On On On On 127
On Off Off Off Off Off Off Off 128
On Off Off Off Off Off Off On 129
On Off Off Off Off Off On Off 130
On Off Off Off Off Off On On 131
On Off Off Off Off On Off Off 132
INS70085 Lochinvar Startup Guide Page 35 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
A7 A6 A5 A4 A3 A2 A1 A0 Address
On Off Off Off Off On Off On 133
On Off Off Off Off On On Off 134
On Off Off Off Off On On On 135
On Off Off Off On Off Off Off 136
On Off Off Off On Off Off On 137
On Off Off Off On Off On Off 138
On Off Off Off On Off On On 139
On Off Off Off On On Off Off 140
On Off Off Off On On Off On 141
On Off Off Off On On On Off 142
On Off Off Off On On On On 143
On Off Off On Off Off Off Off 144
On Off Off On Off Off Off On 145
On Off Off On Off Off On Off 146
On Off Off On Off Off On On 147
On Off Off On Off On Off Off 148
On Off Off On Off On Off On 149
On Off Off On Off On On Off 150
On Off Off On Off On On On 151
On Off Off On On Off Off Off 152
On Off Off On On Off Off On 153
On Off Off On On Off On Off 154
On Off Off On On Off On On 155
On Off Off On On On Off Off 156
On Off Off On On On Off On 157
On Off Off On On On On Off 158
On Off Off On On On On On 159
On Off On Off Off Off Off Off 160
On Off On Off Off Off Off On 161
On Off On Off Off Off On Off 162
On Off On Off Off Off On On 163
On Off On Off Off On Off Off 164
On Off On Off Off On Off On 165
On Off On Off Off On On Off 166
On Off On Off Off On On On 167
On Off On Off On Off Off Off 168
On Off On Off On Off Off On 169
On Off On Off On Off On Off 170
On Off On Off On Off On On 171
On Off On Off On On Off Off 172
On Off On Off On On Off On 173
On Off On Off On On On Off 174
On Off On Off On On On On 175
On Off On On Off Off Off Off 176
On Off On On Off Off Off On 177
INS70085 Lochinvar Startup Guide Page 36 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
A7 A6 A5 A4 A3 A2 A1 A0 Address
On Off On On Off Off On Off 178
On Off On On Off Off On On 179
On Off On On Off On Off Off 180
On Off On On Off On Off On 181
On Off On On Off On On Off 182
On Off On On Off On On On 183
On Off On On On Off Off Off 184
On Off On On On Off Off On 185
On Off On On On Off On Off 186
On Off On On On Off On On 187
On Off On On On On Off Off 188
On Off On On On On Off On 189
On Off On On On On On Off 190
On Off On On On On On On 191
On On Off Off Off Off Off Off 192
On On Off Off Off Off Off On 193
On On Off Off Off Off On Off 194
On On Off Off Off Off On On 195
On On Off Off Off On Off Off 196
On On Off Off Off On Off On 197
On On Off Off Off On On Off 198
On On Off Off Off On On On 199
On On Off Off On Off Off Off 200
On On Off Off On Off Off On 201
On On Off Off On Off On Off 202
On On Off Off On Off On On 203
On On Off Off On On Off Off 204
On On Off Off On On Off On 205
On On Off Off On On On Off 206
On On Off Off On On On On 207
On On Off On Off Off Off Off 208
On On Off On Off Off Off On 209
On On Off On Off Off On Off 210
On On Off On Off Off On On 211
On On Off On Off On Off Off 212
On On Off On Off On Off On 213
On On Off On Off On On Off 214
On On Off On Off On On On 215
On On Off On On Off Off Off 216
On On Off On On Off Off On 217
On On Off On On Off On Off 218
On On Off On On Off On On 219
On On Off On On On Off Off 220
On On Off On On On Off On 221
On On Off On On On On Off 222
INS70085 Lochinvar Startup Guide Page 37 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
A7 A6 A5 A4 A3 A2 A1 A0 Address
On On Off On On On On On 223
On On On Off Off Off Off Off 224
On On On Off Off Off Off On 225
On On On Off Off Off On Off 226
On On On Off Off Off On On 227
On On On Off Off On Off Off 228
On On On Off Off On Off On 229
On On On Off Off On On Off 230
On On On Off Off On On On 231
On On On Off On Off Off Off 232
On On On Off On Off Off On 233
On On On Off On Off On Off 234
On On On Off On Off On On 235
On On On Off On On Off Off 236
On On On Off On On Off On 237
On On On Off On On On Off 238
On On On Off On On On On 239
On On On On Off Off Off Off 240
On On On On Off Off Off On 241
On On On On Off Off On Off 242
On On On On Off Off On On 243
On On On On Off On Off Off 244
On On On On Off On Off On 245
On On On On Off On On Off 246
On On On On Off On On On 247
On On On On On Off Off Off 248
On On On On On Off Off On 249
On On On On On Off On Off 250
On On On On On Off On On 251
On On On On On On Off Off 252
On On On On On On Off On 253
On On On On On On On Off 254
On On On On On On On On 255
INS70085 Lochinvar Startup Guide Page 38 of 38
ProtoCessor 1991 Tarob Court Milpitas, California 95035 USA Web: www.protocessor.com Tel: (408) 964 4444 Fax: (408) 964 4425 Toll Free: (800) 317 8319 x141 email: [email protected]
Appendix C. Limited 2 year Warranty
FieldServer Technologies warrants its products to be free from defects in workmanship or material
under normal use and service for two years after date of shipment. FieldServer Technologies will repair
or replace any equipment found to be defective during the warranty period. Final determination of the
nature and responsibility for defective or damaged equipment will be made by FieldServer Technologies
personnel.
All warranties hereunder are contingent upon proper use in the application for which the product was
intended and do not cover products which have been modified or repaired without FieldServer
Technologies approval or which have been subjected to accident, improper maintenance, installation or
application, or on which original identification marks have been removed or altered. This Limited
Warranty also will not apply to interconnecting cables or wires, consumables or to any damage resulting
from battery leakage.
In all cases FieldServer Technology’s responsibility and liability under this warranty shall be limited to
the cost of the equipment. The purchaser must obtain shipping instructions for the prepaid return of
any item under this warranty provision and compliance with such instruction shall be a condition of this
warranty.
Except for the express warranty stated above, FieldServer Technologies disclaims all warranties with
regard to the products sold hereunder including all implied warranties of merchantability and fitness
and the express warranties stated herein are in lieu of all obligations or liabilities on the part of
FieldServer Technologies for damages including, but not limited to, consequential damages arising out
of/or in connection with the use or performance of the product.