Upload
jeffrey-lam
View
594
Download
0
Tags:
Embed Size (px)
Citation preview
IT infrastructure Design Concepts
Network Design Philosophy
Data center Design Philosophy
•Security,
•availability,
•scalability,
•manageability.
•Network designed to
prevents unauthorised access
identify and isolate illegal actions.
•Usually neglected in the physical
layer.
•Critical to monitor both logical &
physical connectivity.
•Asset management
Security
Availability
Design
PhilosophyIssues solutions
•Security,
•availability,
•scalability,
•manageability.
Availability
•Networks are designed to minimize the
occurrence of service problems
•Redundancy based design.
•Capacity to be higher than minimum to
cater for
increased traffic loads
bandwidth intensive applications
•SlowtimeTM
Network must not only be up but
throughput must be maximised.
•High performance / bandwidth solutions
•Ability to grow with your business
•System must adapt to ever-
changing network requirements
•Scalable deployment of network
services
speed of deployment
optimise existing investment
Flexibility / Scalability
KISS
Managing a network should be easy
designed for dummies
real time information
Facilitate upgrades and maintenance
Flexible to meet any sudden
changes.
Manageability
Current network technologies
Gigabit EthernetGigabit Ethernet
Summary - Gigabit Ethernet & 10Gigabit Ethernet
Application Standards Application Bitrate
Fiber IEEE 802.3z 1000BASE-SX 1 Gbps
Fiber IEEE 802.3z 1000BASE-LX 1 Gbps
Copper IEEE 802.3z 1000BASE-CX 1 Gbps
Copper IEEE 802.3ab 1000BASE-T 1 Gbps
Copper TIA/EIA-854 1000BASE-TX 1 Gbps
Fiber IEEE 802.3ae 10GBASE-SX 10 Gbps
Fiber IEEE 802.3ae 10GBASE-LX 10 Gbps
Fiber IEEE 802.3ae 10GBASE-EX 10 Gbps
Fiber IEEE 802.3ae 10GBASE-LX4 10 Gbps
Copper IEEE 802.3an 10GBASE-T 10 Gbps
Copper IEEE 802.3af Power over Ethernet N.A.
10 Gigabit Ethernet10 Gigabit Ethernet
IEEE 802.3ae
10Gbps over fiber cabling
completed June 2002
Application Wavelength 62.5/125 um 62.5/125um 50/125 um 50/125 um SMF160/500 Mhz-km 200/500 Mhz-km 500/500 Mhz-km 2000/500 Mhz-km
OM1 OM2 OM3
10GBASE-SX 850nm 28m 35m 86m 300m -
10GBASE-LX 1310nm - - - - 10km
10GBASE-EX 1550nm - - - - 40km
10GBASE-LX4 1310nm 300m 300m 300m 300m 10km
10GbaseSX - OM3 Multimode fiber able
10GbaseLX - Singlemode fiber cable
10 Gigabit Ethernet10 Gigabit Ethernet
Objectives
•35m over Cat 6 UTP cabling
•100m over augmented Cat 6 cabling
current cabling may not support 10GBase-T.
•Existing Cat 6 cabling need to be qualified to TSR 155 / TR24750
•New cabling standard Cat 6A to be published under EIA/TIA 568b.2-10
IEEE 802.3an
10 Gigabit Ethernet on twisted pair cabling
standard completed in July 2006
Full Spectrum “Zero Water peak” Fiber
Normal fiber operating windows
O LE S C U
0.3
0.6
0.9
1.2
Wavelength (nm)
Lo
ss
(dB
/
km
)
Conventional
Fiber Loss
0
1250 1300 1350 1400 1450 1500 1550 1600
Why are there no applications @ 1400nm?
ANSWER: HIGH LOSS!!!
1350nm to 1450nm (E-band)
traditionally no operation due to high loss.
Standard Fiber Partially Blocked by Water
1310 nm band
1400 nm band
1550 nm band
Lanes ClosedLanes Closed
E-band
•1280 to 1625nm
•highest loss at 1383nm
•loss caused by hydroxl ions in the glass
•traditional manufacturing process unable to remove these ions.
•Commonly known as “Water Peak”
•Ordinary singlemode fiber (G.652 compliant fiber) suffers from
this problem.
− 9um SINGLEMODE
− G.652.C compliant
− no water peak
− removes Hydroxl ions from fiber
− Increases capacity per Fiber
− Due to elimination of water peak causing high loss
− 60% more usable wavelengths
− Maximizes support for CWDM / DWDM
− Low Cost Future Proofing for Next Generation Equipment
Zero Water Peak Full Spectrum fiber Singlemode Fiber
Zero Water Peak Full Spectrum FiberEliminates high loss & opens E-band channel capacity
availing full spectrum for any use
Zero Water Peak fiber opens PossibilitiesZero Water Peak fiber opens Possibilities
O LE S C U
0
0.3
0.6
0.9
1.2
1250 1300 1350 1400 1450 1500 1550 1600
Wavelength (nm)
Lo
ss
(dB
/ k
m) Conventional
Fiber Loss
“water peak”
Full Spectrum
fiber
Standard Fiber Partially Blocked by Water
1310 nm band
1400 nm band
1550 nm band
240 opticalchannels
Lanes ClosedLanes Closed
Which would you rather have?
Zero Water Peak Fiber Completely Open,
1310 nm band
1400 nm band
1550 nm band
400 opticalchannels
Zero Water Peak Fiber gives additional optical channels for DWDM/CWDM
High availabilty requires
− high capacity medium to avoid network congestion
Scalabilty requires a medium that
− supports current network methodology
− supports current technology
− flexibility in exploiting new technologies
Design concept 1Design shall provide 10Gigabit Ethernet &
support next generation technologies (DWDM)
Preterminated cabling systems
Structured vs. Unstructured Cabling Solutions
200 Jumper Cables200 Jumper Cables 3 Trunk Cables3 Trunk Cables
Point-to-Point
Jumper Cable Installation
Point-to-Point
Jumper Cable InstallationStructured Optical Cabling SolutionStructured Optical Cabling Solution
Data center considerations
• Fast installation
•Installer spend less time in data center
•shorter cut-over
• High Performance
•minimise down-time
•Low loss allow for flexibility in design
• Minimise space used
•Data center high cost due to supporting facilities
• No chemicals
•confined areas - fumes difficult to disperse
•prevents accidental fires / damage
Connector Options
Connectors
• Modules support wide range of connectors
– SC, ST, LC
• Modules connect to trunk
– MTP connectors.
MTP
connectorSC, ST, LC, MTRJ connectors
Plug & Play
• Improve installation time by as much as 70%
• Saves up to 60% rack and floor space
• No site terminations, no chemicals
• Factory terminated & tested for high performance
Scalabilty requires
− rapid deployment / expansion
− factory terminated performance
Manageability requires
− lower cable counts for easy handling
Design Concept 2Datacenter cabling shall be preterminated
for fast deployment & expansion
Angled Patchpaneldesign
Vertical Cable ManagerVertical Cable ManagerVertical Cable ManagerVertical Cable Manager
Angled Angled Angled Angled PatchpanelPatchpanelPatchpanelPatchpanel
CISCO 6500 seriesCISCO 6500 seriesCISCO 6500 seriesCISCO 6500 series
Angled Patchpanel
Allows cables to be routed
directly to vertical CM.
No need for horizontal cable
managers
Double Your Double Your Double Your Double Your Double Your Double Your Double Your Double Your Density !Density !Density !Density !Density !Density !Density !Density !
•Eliminates Eliminates Eliminates Eliminates horizontal cable horizontal cable horizontal cable horizontal cable mgrs.mgrs.mgrs.mgrs.
•Saves floor Saves floor Saves floor Saves floor space & rental.space & rental.space & rental.space & rental.
Angled Angled Angled Angled PatchpanelPatchpanelPatchpanelPatchpanel
Angled Angled Angled Angled patchpanelpatchpanelpatchpanelpatchpanel Conventional patchpanel
vs.
No Horizontal Cable Managers !!!
COMPARISIONCOMPARISIONCOMPARISIONCOMPARISION
Density Doubled!!!
021No. of horizontal cable managers
4221No. of patchpanels
1008504No. of ports
Angled patchpanel.Conventional patchpanels
COMPARISIONCOMPARISIONCOMPARISIONCOMPARISION
Manageability requires
− patchcords to be routed easily and neatly
− both equipment and patchpanel
− ease of search
− patchcords to maintain bend radius
Scalability requires
− space to be maximised for future expansion
Design concept 3Patching solution must be based on angled
patch design.
Integrated Network MonitoringIntegrated Network Monitoring
Network Mgt solution
Traditional Network Management System (NMS)
�Monitors active equipment.
�Gives info on logical level.
�No info at the physical level.
ROUTER SWITCH PATCHPANEL DEVICES
Integrated Network MonitoringIntegrated Network Monitoring
Intelligent Cabling solutions
� Gives physical information.
�Monitors patchpanels and location of devices.
ROUTER SWITCH PATCHPANEL DEVICES
Intelligent cabling solution
Integrated Network MonitoringIntegrated Network Monitoring
Intelligent cabling integrated with NMS
�Monitors both active and passive devices.
� Gives complete physical & logical information.
� Complete real time information on network.
� Aids troubleshooting & maintenance.
ROUTER SWITCH PATCHPANEL DEVICES
Intelligent cabling solutionNetwork Mgt solution
Manageability requires
− always knowing how your cabling are patched
− integration of physical layer with network monitoring
Security requires
− any unauthorised changes to be tracked
Design Concept 4Cabling system shall be supported by a intelligent
cabling system
Design Concept 1
Cabling shall support 10G & next generation technologies
Design Concept 2
Datacenter cabling shall be preterminated for fast deployment & expansion
Design Concept 3
Patching solution must be based on angled patch design.
Design Concept 4
Cabling system shall be supported by a intelligent cabling system
Design concept - SummaryDesign concept - Summary
Design Concept 1
Cabling shall support 10G & next generation technologies
>>>GIGASPEED X10D / Teraspeed / Lazrspeed
Design Concept 2
Datacenter cabling shall be preterminated for fast deployment & expansion
>>>INSTAPATCH
Design Concept 3
Patching solution must be based on angled patch design.
>>>GIGASPEED X10D ANGLED PATCH
Design Concept 4
Cabling system shall be supported by a intelligent cabling system
>>>IPATCH
Design concept - SummaryDesign concept - Summary