313
C&I of Power Plant

C&i systems

Embed Size (px)

DESCRIPTION

About sensors, transducers, transmitters and automatic control of process parameters

Citation preview

Page 1: C&i systems

C&I of Power Plant

Page 2: C&i systems

Boiler Schemes

Page 3: C&i systems

Energy Conversion

Page 4: C&i systems
Page 5: C&i systems

Work Done In Turbine

Page 6: C&i systems

Work Done In TurbineThe heat Energy in the steam is converted first to kinetic energy as it enters the Machine through nozzles, and then this kinetic energy is converted to Mechanical work as it impinges onto the rotating blades. •Further work is Done by the reaction of the steam leaving these blades when it encounters Another set of fixed blades, which in turn redirect it onto yet another set of Rotating blades. •As the steam travels through the machine in this way it Continually expands, giving up some of its energy at each ring of blades.•The moment of rotation applied to the shaft at any one ring of blades is the Multiple of the force applied to the blades and mean distance of the force.•Since each stage of rings abstracts energy from the steam, the force applied At the subsequent stage is less than it was at the preceding ring and, therefore, to ensure that a constant moment is applied to the shaft at each stage, the length of the blades in all rings after the first is made longer than that of the preceding ring.

Page 7: C&i systems

Work Done In Turbine

• This gives the turbine its characteristic tapering shape.

• The steam enters the machine at the set of blades with the smallest diameter and leaves it after the set of blades with the largest diameter.

Page 8: C&i systems

The huge cooling towers condense steam back into water. Some of the steam escapes, creating huge clouds above the cooling towers.

Page 9: C&i systems

Things that we commonly measure are: •Temperature ,Pressure •Speed, Flow rate •Force Movement, Velocity and Acceleration •Stress and Strain Level or Depth •Mass or Weight Density •Size or Volume Acidity/Alkalinity Sensors may operate simple on/off switches to detect the following: •Objects(Proximity switch) Empty or full (level switch) •Hot or cold (thermostat) Pressure high or low (pressure switch) The block diagram of a sensor is shown below.

Page 10: C&i systems

A successful Process Control Engineer has to know something about the following subjects

• Electrical Engineering• Electronic Engineering• Computers• Hydraulics

• Pneumatics• Plumbing• Physics• Chemistry• Finance

Page 11: C&i systems

• PRESSURE SENSORS – STEAM,WATER,AIR,H2GAS,CO2 GAS,OIL • TEMPERATURE SENSORS- STEAM,WATER,AIR,H2GAS,OIL ,FLUE GAS,BEARINGS• FLOW SENSORS- STEAM,WATER,AIR,OIL ,FLUE GAS,COAL• LEVEL SENSORS- DRUM,DEAERATOR,HEATERS,HOTWELL,BUNKERS,HOPPERS,MOT• VIBRATION SENSORS- TURBINE,GENERATORS,PAFANS,FDFANS,IDFANS,BFPS,MILLS• EXPANSION SENSORS- TURBINE,GENERATOR• SPEED SENSORS- TURBINE• POSITION SENSORS- VALVES• ANALYZERS- SILICA,OXYGEN,CO• WEIGHT SENSORS- COAL

Page 12: C&i systems

• PRESSURE SENSORS – GAUGES,DIFFERENTIAL PRESSUREGAUGES,SWITCHES,TRANSMITTERS • TEMPERATURE SENSORS- GAUGES,CONTACT GAUGES,SWITCHES,RTDS,THERMOCOUPLES• FLOW SENSORS- ORIFICE FLOW,AEROFOIL,MAGNETIC FLOW METER ,ENCODERS• LEVEL SENSORS- HYDRA STEP,DIFFERENTIALPRESSURE,LVDT,CAPACITANCETYPE, ULTASONIC,• VIBRATION SENSORS- SESIMIC PROBES,PROXIMITY PROBES• EXPANSION SENSORS- LVDT• SPEED SENSORS- HALL PROBE• POSITION SENSORS- LVDT,VARIABLE CAPACITANCE TYPE• ANALYZERS- SILICA,OXYGEN,PH• WEIGHT SENSORS- LOAD CELLS

Page 13: C&i systems

-4-wire system of measurement

-2-wire system of measurement

-True Zero (0-20 mA) measurement

-Live Zero (4-20 mA) measurement

Pressure Transmitter

Page 14: C&i systems

4-wire Transmitter (0-20/4-20 mA)

+ Tx-

Load Control / Monitoring mA

Wiring schematic of 4-wireTransmitter

+24 V DC

-Ve

Page 15: C&i systems

2-wire Transmitter (4-20 mA)

+ Tx

-Load

Control / Monitoring

4-20 mA

Wiring schematic of 2-wireTransmitter

+24 V DC

-Ve

- Tx drives constant current up to a Load of 600 Ω

Page 16: C&i systems

Transmitter Power supply Vs Load

400 600 800 1000 1200

40

30

20

Page 17: C&i systems

• Pressure - Gauges

• Temperature - Gauges

• Level - Gauge glass

• Flow - Flow meter

Local Monitoring

Page 18: C&i systems

Pressure Gauge

• Bourdon Type

Page 19: C&i systems

• Bourdon Type

Pressure Gauge

Page 20: C&i systems

Temperature Gauge

• Mercury Gauge

Page 21: C&i systems

Gauge Glass

• See through glass

Page 22: C&i systems

• Pressure/Flow/Level/Temperature

- Indicators, Recorders, Control System, Monitors- TFTs

RemoteMonitoring

Page 23: C&i systems
Page 24: C&i systems

How Remote Monitoring is done?

• Field data are communicated to the control room.

• Based on the information the control system takes care of safe , reliable and optimum operation.

• Control & Instrumentation deals with the above.

Page 25: C&i systems
Page 26: C&i systems

Why signals are sent to the Control Room ?Why signals are sent to the Control Room ?

• The process parameters are monitored & controlled from the control room.

• For monitoring the signal, termed measured value, is displayed.

• For Controlling the measured value is fed to or from the control panels through wires.

Page 27: C&i systems

Control Room Instruments

• Indicators• Recorders• Display screens• Annunciation windows• Push Buttons• Breakers• Switches etc.

Page 28: C&i systems
Page 29: C&i systems

Process Control

Process control is extensively used in industry and enables mass production of continuous processes such as oil refining, paper manufacturing, chemicals, power plants and many other industries. Process control enables automation, with which a small staff of operating personnel can operate a complex process from a central control room.

Page 30: C&i systems

Details of an Industrial Process

Process

Sensor

Low LevelSignal

Local SignalProcessing

Transmission Remote SignalProcessing

Display

Control

Page 31: C&i systems

Control System Evolution• Manual Control System in past involved direct operation of

manipulated variable by human. That was time consuming, tedious and difficult for round the clock operation

• Auto Control System involved electrical control was based on relays. These relays allow power to be switched on and off without a mechanical switch. It involved lot of wirings to make simple logical control decisions.

• Programmable Logic Controller (PLC) is developed with the microprocessor technology. This has control logic/ ladder logic software that eliminated the use of lot of wiring, relays & switches.

Page 32: C&i systems

Process ControlA commonly used control device called a programmable logic controller, or a PLC, is used to read a set of digital and analog inputs, apply a set of logic statements, and generate a set of analog and digital outputs. Using the example in the previous paragraph, the room temperature would be an input to the PLC. The logical statements would compare the setpoint to the input temperature and determine whether more or less heating was necessary to keep the temperature constant. A PLC output would then either open or close the hot water valve, an incremental amount, depending on whether more or less hot water was needed. Larger more complex systems can be controlled by a Distributed Control System (DCS) or SCADA system.

Page 33: C&i systems

Types of control systems• Logical/Discrete - The value to be controlled are easily

described as on-off. e.g. the Feed Pump is on-off based on certain conditions.

• Continuous - The values to be controlled change smoothly. e.g. the Drum Level.

• Linear - Can be described with a simple differential equation e.g. We are measuring the perfect flow with no disturbances like friction, turbulence, temperature change of process fluid etc.

• Non-Linear - Not Linear. Takes into account the changes due the disturbances. must change.

• Sequential - A logical controller that will keep track of time and previous events.

Page 34: C&i systems

The value to be controlled are easily described as ON-OFF. e.g. the motor is on-off. NOTE: all systems are continuous but they can be treated as logical for simplicity. For example, the BFP is turned on, when the discharge valve is closed.

Discrete

Page 35: C&i systems

Logical and sequential controlThese systems don't need to be closely monitored, an Open Loop Control System. An open loop controller will set a desired state of an equipment, but no sensors are used to verify the position.

Page 36: C&i systems

Continuous ControlA system i.e. constantly monitored and the control output adjusted is a Closed Loop Control System.

For example, heating up the temperature in a room is a process that has the specific, desired temperature the Set Point to reach and maintain constant over time. Here, the hot water flow is the controlled or the manipulated variable since it is subject to control actions. The temperature of the water is the measured variable.

Page 37: C&i systems

Programmable Logic Controller (PLC)

• Cost effective for automatically controlling complex systems.

• Flexible and can be reapplied to control other systems quickly and easily.

• Computational abilities allow more sophisticated control.

• Trouble shooting aids make programming easier and reduce downtime.

• Reliable components make these likely to operate for years before failure.

Page 38: C&i systems

Ladder LogicLadder logic is the main programming method used for PLCs. As mentioned before, ladder logic has been developed to mimic relay logic. A relay is a simple device that uses a magnetic field to control a switch.

A typical SCADA package polls numerous points in a PLC to retrieve live factory data. The polling involves executing the protocol stacks on both the PC and the PLC network board. Data is then retrieved from the PLC memory across the backplane and sent back through the same protocol levels. This makes it unsuitable for time-sensitive information. Embedding the web server in the plc ensures the timely flow of information required on the factory floor.

Page 39: C&i systems

When a voltage is applied to the input coil, the resulting current creates a magnetic field. The magnetic field pulls a metal switch (or reed) towards it and the normally open contacts touch, closing the switch. The normally closed contacts touch when the input coil is not energized.

Ladder Logic

Page 40: C&i systems

How thousands of Data managed or controlled in the control room ?

All panels through which communication with field instruments is done are interconnected or integrated through a central network called Distributed communication network. This whole system is called Distributed Control System.

Page 41: C&i systems

What is a Distributed Control System? A distributed control system (DCS) refers to a control system usually of a process or

any kind of dynamic system, in which the controller elements are not central in location (like the brain) but are distributed throughout the system with each component sub-system controlled by one or more controllers. The entire system of controllers is connected by networks for communication and monitoring.

Page 42: C&i systems

Elements of a DCS A DCS typically uses custom designed processors as controllers and uses both proprietary

interconnections and communications protocol for communication. The functionally and/or geographically distributed digital controllers are capable of executing from 1 to 256 or more regulatory control loops in one control box. The input/output devices (I/O) can be integral with the controller or located remotely via a field network. Today’s controllers have extensive computational capabilities and, in addition to proportional, integral, and derivative (PID) control, can generally perform logic and sequential control like Ladder Logic.

Page 43: C&i systems

Input and output modules form component parts of the DCS. The processor receives information from input modules and sends information to output modules. The input modules receive information from input instruments in the process (a.k.a. field) and transmit instructions to the output instruments in the field.

Page 44: C&i systems

Computer buses or electrical buses connect the processor and modules through multiplexer or de-multiplexers. Buses also connect the distributed controllers with the central controller and finally to the Human Machine Interface (HMI) or control consoles.

Page 45: C&i systems

DCSs may employ one or several workstations and it’s database can be configured at the engineering workstation. Local communication is handled by a control network(DCN ring) with transmission over twisted pair, coaxial, or fiber optic cable.

A server and/or applications processor may be included in the system for extra computational, data collection, storage and reporting capability called the History Substation.

Page 46: C&i systems

Applications of D.C.S. : Distributed Control Systems (DCSs) are dedicated systems used to control processes that are continuous or batch-oriented, such as oil refining, petrochemicals, central station power generation, pharmaceuticals, food & beverage manufacturing, cement production, steelmaking, and papermaking. DCSs are connected to sensors and actuators and use set-point control to control the flow of material through the plant.

Page 47: C&i systems

The most common example is a set point control loop consisting of a pressure sensor, controller, and control valve. Pressure or flow measurements are transmitted to the controller, usually through the aid of a signal conditioning Input/ Output (I/O) device. When the measured variable reaches a certain point, the controller instructs a valve or actuation device to open or close until the fluidic flow process reaches the desired set point. Large generation units have many thousands of I/O points and employ very large DCSs. Processes are not limited to fluidic flow through pipes, however, and can also include things variable speed drives and motor control centers, fuel processing facilities, and many others.

Page 48: C&i systems

Process diagrams The ‘process’ is an idea or concept that is developed to a certain level in order to determine the feasibility of the project. ‘Feasibility’ study is the name given to a small design project that is conducted to determine the scope and cost of implementing the project from concept to operation. To keep things simple, for example, design an imaginary coffee bottling plant to produce bottled coffee for distribution. Start by creating a basic flow diagram that illustrates the objective for the proposed plant; this diagram is called a “Process Block Diagram”.

Basic flow diagram of Coffee bottling plant

Page 49: C&i systems

P&IDsPiping & Instrumentation Drawing (original)Process & Instrumentation Diagram (also used)Process Flow Diagram – PFD (simplified version of the P&ID)

Most industries have standardized the symbols according to the ISA Standard S5.1 Instrumentation Symbol Specification

Page 50: C&i systems

Process flow diagram or piping flow diagram (PFD) The PFD is where we start to define the process by adding equipment and the piping that joins the various items of equipment together. The idea behind the PFD is to show the entire process (the big picture) on as few drawing sheets as possible, as this document is used to develop the process plant and therefore the process engineer wants to see as much of the process as possible. This document is used to determine details like the tank sizes and pipe sizes

Page 51: C&i systems

PIPING AND INSTRUMENTATION DIAGRAM (P&ID) vs PROCESS FLOW DIAGRAM•PFD gives a graphical representation of the process including hardware (Piping, Equipment) and software (Control systems); this information is used for the design construction and operation of the facility. •The PFD defines “The flow of the process” The PFD covers batching, quantities, output and composition. •The P&ID ties together the system description, the flow diagram, the electrical control schematic, and the control logic diagram. It accomplishes this by showing all of the piping, equipment, principal instruments, instrument loops, and control interlocks. The P&ID contains a minimum of text in the form of notes (the system description minimizes the need for text on the P&ID).

Page 52: C&i systems

•The P&ID defines “The control of the flow of the process” where the PFD is the main circuit; the P&ID is the control circuit. Once thoroughly conversant with the PFD & Process description, the engineers from the relevant disciplines (piping, electrical & control systems) attend a number of HAZOP(Hazard and Operability) sessions to develop the P&ID.

Page 53: C&i systems

Temperature Process

Page 54: C&i systems

The P&ID will use symbols and circles to represent each instrument and how they are inter-connected in the process.

Tag “numbers” are letters and numbers placed within or near the instrument to identify the type and function of the device.

Building the P&ID :

Page 55: C&i systems

Tag Descriptors

The first letter is used to designate the measured variable

The succeeding letter(s) are used to designate the function of the component, or to modify the meaning of the first letter.

PressureLevelFlowTemperature

IndicatorRecorderControllerTransmitter

Page 56: C&i systems

Tag Numbers Tag “numbers” are letters and numbers placed within or near the instrument to identify the type and function of the device.

Page 57: C&i systems

P&ID Example

Page 58: C&i systems

P&ID Exercise

Page 59: C&i systems

P&ID Exercise

Page 60: C&i systems

Process Flow Diagram - PFDA PFD shows less detail than a P&ID and is used only to understand how the process

works

Page 61: C&i systems
Page 62: C&i systems

Conveyer Belts Taking The Coal (Chemical Energy) Straight To The Power Station.

Page 63: C&i systems

Electrical energy is made available to our homes via huge transmission towers.

Page 64: C&i systems

The law of conservation of energy states that energy can not be created nor can it be destroyed. It can, however, change forms as from electrical into heat.Take the conversion outlined in the animation below. At every step we have a loss of energy. The efficiency of the conversion is given as a percentage and clearly an indication and not precise. The more conversion steps throughout the process of generating electricity the greater the energy losses.

Page 65: C&i systems

1) What process captures solar energy?

2) Which is the most inefficient energy conversion step in the process outlined above?

3) The more steps in the process of generating electrical energy the

4) The energy lost is in the form of

5) What type of energy is carried by steam

1. Evaporation2. Photosynthesis3. Respiration4. Condensation

1. Chemical to Heat2. Heat to Kinetic3. Kinetic to Mechanical4. Mechanical to

Electrical

1. More the electrical energy generated

2. Less the electrical energy generated

1. Electrical2. Mechanical3. Heat4. Chemical

1. Electrical2. Mechanical3. Kinetic4. Chemical

Page 66: C&i systems

1. The light globe provides us with

2. An incandescent light globe works on heating a metal filament until it glows brightly. What are the energy conversion taking place in the globe?

3. This type of globe is only 2% efficient. What does this mean?

4. Most of the energy coming into the light globe is transformed into

1. Electrical2. Light3. Heat4. Chemical

1. Electrical>Heat>Light2. Electrical>Chemical>He

at3. Chemical>Heat>Light4. Chemical>Heat> Light

1. 92% loss2. 102% efficient3. 98% loss4. 98% efficient

1. Electrical2. Light3. Heat4. Chemical

Page 67: C&i systems

Instruments are used to sense the process conditions like temerature and convert them to an electrical form for display & control .

Page 68: C&i systems
Page 69: C&i systems

The main steam and water circuits of power plant

Page 70: C&i systems

Principle of a Deaerator

Page 71: C&i systems

Water and Steam Circuit of a

combined cycle plant

Page 72: C&i systems

Draught fan Arrangemen

t

Page 73: C&i systems
Page 74: C&i systems

BOILER INSTRUMENTS & CONTROL

Page 75: C&i systems

Boiler Critical parts of the process would include the following

• lighting of the burners • controlling the level of water in the drum • controlling the steam pressure

An SIS is engineered to perform "specific control functions" to failsafe or maintain safe operation of a process when unacceptable or dangerous conditions occur- FSSS

Safety Instrumented Systems is independent from all other control system that control the same equipment in order to ensure SIS functionality is not compromised.

SIS is composed of the same types of control elements (including sensors, logic solvers, actuators and other control equipment) as a Basic Process Control System (BPCS). However, all of the control elements in an SIS are dedicated solely to the proper functioning of the SIS.

Page 76: C&i systems

BOILER INSTRUMENTATION

Page 77: C&i systems

BOILER INSTRUMENTATION 1.FLUE GAS 2.SECONDARY AIR3.SECONDARY AIR DAMPERS4.PRIMARY AIR5.MILLS6.SCANNERS7.OIL SYSTEM8.STEAM CYCLE9.FEED WATER CYCLE10.DRUM11.SOOTBLOWERS AND ASLDS12.STEAM ,FEEDWATER AND FLUE GAS ANALYSERS

Page 78: C&i systems

ControlA Plant Control System is an integrated with demand requirement applied simultaneously to the Boiler, Turbine and major auxiliary equipment.

Page 79: C&i systems
Page 80: C&i systems
Page 81: C&i systems
Page 82: C&i systems

Boiler Control Various types of Boiler control system for fossil fuel Boiler include:

•combustion (fuel and air) control- Total Air Control and Mill Air Flow Control,•steam temperature control for superheater and reheater control,•drum level and feedwater flow control,•burner sequence control and management systems•bypass and startup•coordinated Control systems to integrate all of the above with the turbine and electric generator control,•data processing, sequence of event recording, trend recording and display ,•performance calculation and analysis•alarm annunciation system,•management information system,•unit trip system.•Mill Outlet Temperature Control•Hotwell Level Control•LP / HP Heater Level Control•De-aerator Level / Pressure Control•Furnace Draft Control•HFO / LDO Pressure / Flow Control•event activated logs- alarm log/ trip log•Time Activated Logs- Shift Log / Daily Log•Operator Demand Logs- Summary Log, Performance Log, Maintenance Log

Page 83: C&i systems
Page 84: C&i systems

It is the regulation of the Boiler outlet conditions of steam flow, pressure and temperature to their desired values. In control terminology, the Boiler outlet steam conditions are called the outputs or controlled variables. The desired values of the outlet conditions are the set point or input demand signals. The quantities of fuel, air and water are adjusted to obtain the desired outlet steam conditions and are called the manipulated or controlled variables.

Examples of disruptive influence on the Boiler are fuel quality (calorific value variation ), load variation ( load demand), change in cycle efficiency.

Page 85: C&i systems

Characteristics of Different Control Modes

•Boiler-following Control

•Turbine-following Control

•Coordinated Boiler Turbine Control

•Integrated Boiler Turbine-generator Control

•Integrated Control System

Page 86: C&i systems

Boiler-following control This leads Boiler response to follow turbine response. Following a load change, the Boiler control modifies the firing rate to reach the new load level and to restore throttle pressure to its normal operating value. Load response with this type of system is rapid because the stored energy in the Boiler provides the initial change in load. The fast load response is obtained at the expense of less stable throttle pressure control.

Page 87: C&i systems
Page 88: C&i systems

Sliding pressure operation

If boiler characteristics are such that it is capable of delivering steam at lower pressure but at the rated temperature it is beneficial to vary the load by controlling the steam pressure with out throttling by the governing .This improve the efficiency due to

• Reduction in the throttling losses across the stop & regulating valves.

• Saves the pumping power – lower consumption by the B F P

• Lower wetness in the exhaust.

Page 89: C&i systems

Turbine-following control In this mode turbine response follows Boiler response. Megawatt load control is the responsibility of the Boiler while the turbine-generator is assigned secondary responsibility for throttle pressure control. With increased load demand , the Boiler control increases the firing rate which, in turn, raises throttle pressure. To maintain a constant throttle pressure, the turbine control valves open, increasing megawatt output. When a decrease in load is demanded, this process is reversed. Load response with this type of system is rather slow because the turbine-generator must wait for the Boiler to change its energy output before repositioning control valve to change load. However, this mode of operation will provide minimal steam pressure and temperature fluctuation during load change.

Page 90: C&i systems
Page 91: C&i systems

Coordinated Boiler turbine control The above two systems have certain inherent disadvantages and neither fully exploits the capabilities of both Boiler and turbine generator. Hence both are combined into a coordinated control system giving advantages of both the system and minimizing the disadvantages. It assigns the responsibility of throttle pressure control to turbine-generator i.e. the turbine-following system uses the stored energy in the Boiler thus taking advantages of the fast load response of a Boiler following system.

Page 92: C&i systems
Page 93: C&i systems

Integrated Boiler Turbine Generator Control This system consists of ratio controls that monitor pairs of controlled inputs , as follows,•Boiler energy input to generator energy output,•superheater spray water flow to feedwater flow•fuel flow to feedwater flow•fuel flow to air flow•recirculated gas to air flow; this , in effect, is a ratio of reheater absorption to absorption in primary water and steam, and•fuel to primary air flow in pulverized coal-fired units.

Page 94: C&i systems

Integrated Control System: This co-ordinates the Boiler and turbine-generator for fast and efficient response to load demand initiated by the automatic load dispatch system.

Page 95: C&i systems
Page 96: C&i systems

A Safety Instrumented System (SIS)It consists of an engineered set of hardware and

software controls which are especially used on critical process systems.

A critical process system can be identified as one which, once running and an operational problem occurs, the system may need to be put into a "Safe State" to avoid adverse Safety, Health and Environmental(SH&E) consequences.

One of the more well known critical processes is the operation of a steam boiler.

Page 97: C&i systems

FURNACE SAFE GUARD SUPERVISORY SYSTEM

Page 98: C&i systems

SCOPE OF FSSS

MASTER FUEL TRIP RELAYS

BOILERPURGE

OILSYSTEM MILLS

SECONDARYAIRDAMPERS

FLAMESCANNERS

Page 99: C&i systems

FUNCTIONS OF FSSS

Prevent any fuel firing unless a satisfactory furnace purge sequence has first been completed.

Prevent start-up of individual fuel firing equipment unless certain permissive, interlocks have been satisfied.

Monitor and control proper component sequencing during start-up and shut-down of fuel firing equipment.

Subject continued operation of fuel firing equipment to certain safety interlocks remaining satisfied.

Provide component status feedback to the operator and, in some cases, to the unit control system and / or to the data logger.

Provide flame supervision when fuel firing equipment is in service and effect an Elevation Fuel Trip or Master Fuel Trip upon certain condition of unacceptable firing / load combination.

Effect a Master Fuel Trip upon certain adverse Unit operating conditions.

Page 100: C&i systems

INTERLOCKS COVERED UNDER FSSS

PURGE PERMISSIVES

HOTV OPEN/CLOSE INTERLOCKS

HORV OPEN/CLOSE INTERLOCKS

OIL GUNS START/STOP CYCLE

BOILER PROTECTION LOGICS

COAL MILL START/STOP INTERLOCKS

COAL FEEDER START/STOP INTERLOCKS

SCANNER AIR FANS

DAMPER INTERLOCKS

Page 101: C&i systems

FURNACE

ECONOMISER

-12 MMWC1400 DEG

CENTIGRADE

-3 MMWC475 DEG

-3 MMWC

340 DEG

-3 MMWC

340 DEG

-9

1400

-7-3

12001114 667 575

Page 102: C&i systems

RAH A

RAH BESP B

ESP A

ID FAN A

ID FAN B

CHIMNEY

FROM ECONOMISER

140 C

140 0C145 C

145 C

150 C

150 C

O2 3.2%48

MMWC

48 MMWC

-400 MMWC

-150 MMWC

-400 MMWC

-150 MMWC

RAH DP75

MMWC

RAH DP75

MMWC

O2 3.2%

Page 103: C&i systems

SEC AIR41 MMWC

FLUE GAS30 MMWC

PRI AIR40 MMWC

145 C

340 C

40 C

320 C

54 C

316 C

-145 MMWC

913 MMWC

85 MMWCFROM ECONOMISER

TO MILLS

TO FURNACE

TO ESP

RAH

PRI AIR

SEC AIR

Page 104: C&i systems

RAH A

RAH B

FD FAN A

FD FAN B

38 C

38 C

310 C

310 C

150 MMWC

100 MMWC

150 MMWC

100 MMWC

SCAPH-A

SCAPH-B

FURNACE

SEC AIR FLOW

220 T/HR

220 T/HR

290 MMWC

AIRSCANNER FAN-

A SCANNER FAN-BAIR

FILTER

RAH DP35 MMWC

RAH DP35 MMWC

Page 105: C&i systems

FIRING EQUIPMENT

Secondary Air DamperThese are provided on a pulverised fuel burners.The purpose of these dampers is:* To control the amount of excess air required for complete combustion.* To create a sufficient turbulence, in the furnace.

Page 106: C&i systems

Maintenance• The correct settings are determined by

Performance and Testing Department and it’s ensured that the secondary air dampers are set correctly to ensure that the air sweep through the Boilers is kept at optimum conditions.

• The secondary air damper check is carried out on a routine basis by the Mechanical and C&I Maintenance Departments must.

Page 107: C&i systems

FURNACE

FURNACE

COAL AIR A

COAL AIR B

COAL AIR C

COAL AIR D

COAL AIR E

COAL AIR F

AUX.AIR DAMPERS AB

AUX.AIR DAMPERS CD

AUX.AIR DAMPERS DE

AUX.AIR DAMPERS EF

1

2 3

4

SA DAMPERS ATFURNACE CONER

AUX.AIR DAMPERS BC

AUX.AIR DAMPERS FF

AUX.AIR DAMPERS AA

Page 108: C&i systems

SECONDARY AIR DAMPER CONTROL (SADC)

FUEL AIR DAMPERS:

All fuel air dampers (A,B,C,D,E&F)modulate

according to the amount of primary air flow

in the respective Elevation.

All fuelAir dampers will open when boiler

trips.

All fuel Air dampers will open 100% during

purging.

Boiler load > 30%

Page 109: C&i systems

AUXILLARY FUEL AIR DAMPERS(A.F.A.Ds)

Aux.Air dampers AB,CD&EF will open by 70% when respective guns

are in service.

Aux.Air dampers will close whenever adjacent coal elevation or oil

elevation is not in service.

Boiler load < 30% the A.F.A.Ds modulate to maintain 40mmwc

differential pressure between furnace and secondary air wind box.

Boiler load > 30% the A.F.A.Ds modulate to maintain 100mmwc

differential pressure between furnace and secondary air wind box.

The A.F.A.Ds will open when boiler trips.

The A.F.A.Ds will open 100% during purging.

Page 110: C&i systems

RAH A

RAH B

PA FAN A

PA FAN B

50 C

50 C

310 C

310 C

1000 MMWC

970 MMWC

1000 MMWC

970 MMWC

TOMILLSTO

MILLS

RAH DP50

MMWC

RAH DP50

MMWC

Page 111: C&i systems

BOILER TRIP CONDITIONS Both FD Fans Off

Both ID Fans Off

Reheat Protection

Drum Level High-High (> +167 mm, delay of 10 seconds)

Drum Level Lo-Lo (< - 450 mm, delay 10 seconds)

Less than FB and loss of AC in any elevation.

Furnace Pressure High-High (> + 250 mmWC, 2 / 3 logic)

Furnace Pressure Lo-Lo ( < -200 mmWC, 2 / 3 logic )

Loss Of All Fuel Trip.

Unit Flame Failure

Loss Of 24 V DC For > 2 seconds

Loss Of 220 V DC For > 2 seconds

Trip from MMI

Air Flow < 30 %(230 T/hr)

Trip from Emergency Push Button.

Page 112: C&i systems

BOILER TRIP

When the boiler trips the following events takes place

Boiler trip red lamp comes on.

MFT A & B trip lamp comes on and reset lamp goes off. Cause of trip memory can not be reset till the furnace purge is completed. F D Fans Control is transferred to manual. I D fans vane position is transferred to manual. Pulverizers are tripped. Coal feeders are tripped. P A Fans are tripped. HFO trip valve closes. All HFO Nozzle valves closes. Upper and Lower Fuel air damper opens. Auxiliary air damper opens and control is transferred to manual. Loss of all fuel trip protection disarms. S/H and R/H spray block valves S-82 & R-31 closes and can not be opened unless

furnace purge is completed. Turbine Trips

Page 113: C&i systems

LESS THAN FIREBALL &LOSS OF AC IN ANY ELEVATION IN SERVICE

OR

ELEV AB START & LOSS OF PWR

ELEV CD START & LOSS OF PWR

ELEV EF START & LOSS OF PWR

MILL AB START & LOSS OF PWR

MILL CD START & LOSS OF PWR

MILL EF START & LOSS OF PWR

ALL MILLS OFF ANDLESS THAN FIREBALL & LOSS OF AC IN ANY ELEVATION

Page 114: C&i systems

REHEAT PROTECTION

1. TURBINE TRIP OR GENERATOR CIRCUIT BREAKER

OPEN AND HP/LP BYPASS OPENING < 2 %.

2. TURBINE WORKING (HP & IP CVS OPENING > 2 %

AND LOAD SHEDDING RELAY OPERATED AND

HP/LP BYPASS OPENING < 2 %.

3. TURBINE NOT WORKING AND BOILER WORKING

AND HP/LP BYPASS OPENING < 2 %.

Page 115: C&i systems

HPT

HPCV2

HPCV1

SHH-9

CRH-R

CRH-L

HPBP

150 Kg/Cm2

540 0C35 Kg/Cm2

340 0C

Page 116: C&i systems

HPT

IPCV2

IPCV1

RHH-4

CRH-R

CRH-L

LPBP

540 0C

RHH-1 LPT

I PT

35 Kg/Cm2

340 0C

35 Kg/Cm2

Page 117: C&i systems

Loss of all fuel armingSET

RESETMFT 5 SEC

Any elevation¾ Nozzle valve proven

All feeders off 2 SEC

All HFO Nozzle valve closed

All feeders off

HOTV NOT OPEN

2 SEC

All HFO Elevation Trip

Loss of all fuel trip

LOSS OF ALL FUEL TRIP

Page 118: C&i systems

FLAME FAILURE TRIP

ELEVATION B NO FLAME VOTE

ELEVATION C NO FLAME VOTE

ELEVATION D NO FLAME VOTE

ELEVATION E NO FLAME VOTE

ELEVATION F NO FLAME VOTE

ANY MILL O/L GATE OPEN 3 SEC

FLAME FAILURE TRIP

ELEVATION A NO FLAME VOTE

Page 119: C&i systems

INSIGHT AS TO USE OF THE FLAME FAILURE PROTECTION

• To protect a furnace against an explosion, it is necessary to monitor the combustion process.

• As soon as the fires are extinguished, tripping the PA fans should stop the PF flow and the draught plant should remain on load to clear out unburnt PF from the furnace.

• In the event of the loss of Auxiliary, the draught groups must be re-commissioned as soon as possible to clear out the unburnt PF from the furnace.

• If the above is not possible, damper positions to be checked, they must be open to ensure natural draught.

Page 120: C&i systems

FLAME FAILURE PROTECTION

• It must be remembered that the protection circuit should be in operation under high load conditions for as long as possible, since the violence of an explosion depends on the amount of PF dust present at the time.

• During light-up or under low load conditions, explosions are generally less violent, but, under these conditions the boiler is usually under direct control of the Operator who should guard against losses of ignition and trip PA fans if necessary.

Page 121: C&i systems

FLAME FAILURE VOTE LOGICS

FEEDER B OFF2 SEC

ELEVATION AB 2/4 NOZZLE VALVE NOT OPEN

ELEVATION AB 3/4SCANNERS NO FLAME

2 SEC

ELEVATION B NO FLAME VOTE

ELEVATION A NO FLAME VOTE

FEEDER A OFF

ELEVATION AB 3/4SCANNERS NOFLAME

ELEVATION AB 2/4 NOZ VLVS NOT OPEN

ELEVATION BC 3/4

SCANNERS NO FLAME

Page 122: C&i systems

FLAME FAILURE VOTE LOGICS

FEEDER F OFF

2 SEC

ELEVATION CD 2/4 NOZZLE VALVE NOT OPEN

ELEVATION CD 3/4SCANNERS NO FLAME

2 SEC

ELEVATION D NO FLAME VOTE

ELEVATION C NO FLAME VOTE

FEEDER C OFF

ELEVATION CD 3/4SCANNERS NOFLAME

ELEVATION CD 2/4 NOZ VLVS NOT OPEN

ELEVATION BC 3/4SCANNERS

NOFLAME

ELEVATION DE 3/4SCANNERS

NO FLAME

Page 123: C&i systems

FLAME FAILURE VOTE LOGICS

FEEDER F OFF

2 SEC

ELEVATION EF 2/4 NOZZLE VALVE NOT OPEN

ELEVATION EF 3/4SCANNERS NO FLAME

2 SEC

ELEVATION F NO FLAME VOTE

ELEVATION E NO FLAME VOTE

FEEDER E OFF

ELEVATION EF 3/4SCANNERS NOFLAME

ELEVATION EF 2/4 NOZ VLVS NOT OPEN

ELEVATION DE 3/4SCANNERS

NOFLAME

Page 124: C&i systems

FURNACE

FURNACE

COAL A

COAL B

COAL C

COAL D

COAL E

COAL F

OIL AB

OIL CD

OIL EF

AB SCANNERS

BC SCANNERS

CD SCANNERS

DE SCANNERS

EF SCANNERS

1

2 3

4

FURNACE CORNER

Page 125: C&i systems

Flame scanners• There are several types of flame detector. The optical flame detector

is a detector that uses Optical Sensors to detect flames. • There are also ionisation flame detectors, which use current flow in

the flame to detect flame presence, and thermocouple flame detectors.

Working Principle of The Flame Detector •Radiant intensity signals of the flame sent by a muffle burner change into relevant voltage strength signals by the photoelectric sensor. •The voltages are low and hence amplified into standard analog signals, which would be processed in the single chip microcomputer and change into relevant controlling signals to be output. •The flame detector has functions of collecting, processing input signals and output control signals.

Page 126: C&i systems

Pyrometer

• A pyrometer is a non-contacting device that intercepts and measures thermal radiation, a process known as pyrometry.

• This device can be used to determine the temperature of an object's surface.

Page 127: C&i systems

Thermopiles Pyrometers• Each thermopile consists of a large number of

thermocouples, on which the light from the fire is concentrated by means of a lens.

• The thermocouples produce a voltage signal that depends on the temperature of the fire only.

• This signal is amplified and used to control the trip circuit.

Maintenance• The lenses of the thermopiles is cleaned at all times, by

dedicated purge air fans. • Proper alignment of the thermopile is essential. A small

view hole is provided at the back of the thermopile. • Properly aligned at a fire of 1 400°C, the thermopile

should give an output of± 31,0 milli volts. • This is about normal operation.

Page 128: C&i systems

Trip CircuitSignals from the relays on the alarm and trip cards in the amplifier unit are fed to the trip circuit that is designed to make several decisions.

* Normal conditions: all four thermocouples are above 950°C indication therefore no alarm will shown and no action will be taken.

* If any one of the four thermocouples will indicate below the alarm/reset value 950°C., a “flame failure alarm” will be initiated.

* The fascia alarm will remain on until the temperature indicated by the thermopile is above 950°C. No change in the fascia indication will take place if more than one thermopile is below 950°C or if initially one and later another thermopile registers lower than 950°C.

If any thermopile indicates a temperature below the trip value 600°C, and red light situated below the corresponding indicator will also be initiated.

* Every channel has its own red light, which operates independent of the other channels. The red light will remain on until the temperature ofthat channel indicates above 600°C.

* If three of the four thermocouples have values lower than 600°C the trip circuit will automatically trip all running P.A. fans. An alarm “Flame failure trip” will also be initiated at the same time.

Page 129: C&i systems

PURGE PERMISSIVE

All HFO Nozzle Valves Closed

HFO Trip Valve closed

All MILLS Off.

All MILL O/L GATES CLOSED

All Flame Scanners Sense No Flame

All PA FANS OFF

No BOILER TRIP COMMAND

AIR FLOW > 30%(230 T/HR)

Page 130: C&i systems

PURGE PROCESS

1.OPEN ALL FUEL SECONDARY AIR DAMPERSi.e,A,B,C,D,E,F.

2. OPEN ALL AUXILLARY SECONDARY AIR DAMPERS i.e,AB,BC,CD,DE,EF,FF.

FOR 5 MINUTES:

AFTER 5 MINUTES:

CLOSE ALL SECONDARY AIR DAMPERSI.e,A,AB,B,BC,C,CD,D,DE,E,EF,F,FF.

Page 131: C&i systems

HOTV INTERLOCKSTO OPEN HOTV :

Permissives :

No. Boiler Trip persistingHFO Header temperature satisfactory >950 CHFO supply press sat. > 4.5 Kg / cm2

All HONV’s closedNo close / Trip commandOpen PB depressed

Page 132: C&i systems

HOTV INTERLOCKS

1. HOTV CLOSES AUTOMATICALLY UNDER FOLLOWING

CONDITIONS :

Any HONV not closed AND

a) HFO pressure low < 3 Kg/cm2 OR

b) Atom. steam Pr. low < 3.5 Kg/cm2

OR

c) HFO Header Temperature Lo-Lo for > 2 secs. < 90 0 C

2. Any HONV not closed and MFT acted

3. HOTV can be closed manually by pressing the close push

button.

Page 133: C&i systems

HORV INTERLOCKS

HORV can be opened by pressing the OPEN Push

button (PB) from Console if All the HONV s are

closed.

HORV closes automatically when any HONV is not

closed OR by pressing close PB.

Page 134: C&i systems

M

FT

FT

AB ELEVATION

CD ELEVATION

EF ELEVATION

HOFCVHOTV

HORV

SHORTRECIRCULATION

HFO SUPPLY

LINE

HFO RETURN

LINE

HFO SCHEME AT BOILER FRONTHFO SCHEME AT BOILER FRONT

Page 135: C&i systems

OIL GUN

ATOMISINGSTEAM VALVE

HFO NOZZLEVALVE SCAVENGE

VALVE

AB ELEVATION

CD ELEVATION

EF ELEVATION

ATOMISING STEAM SCHEME AT BOILER FRONTATOMISING STEAM SCHEME AT BOILER FRONT

OIL GUN CONNECTIONOIL GUN CONNECTION

Page 136: C&i systems

PAIR FIRING MODE (START UP)

Pairs are made of the opposite corners. (Pair 1-3 and Pair 2-4) When pair 1-3 or 2-4 start push button is pressed the following events take

place command goes to: corner 1or 2- immediately corner 3or 4- after 15 seconds. When pair 1-3 or 2-4 stop push button is pressed the following events take

place command goes to: corner 1or 2- immediately

corner 3or 4-immediately

CORNER PERMISSIVES: SCAVENGE VALVE IS CLOSED OIL GUN IS ENGAGED. HFO or LFO VALVE MANUAL ISOLATION VALVE IS OPENED. ATOMISING STEAM or AIR VALVE MANUAL ISOLATION VALVE IS OPENED. LOCAL MAINTENANCE SWITCH IN REMOTE.

Page 137: C&i systems

PAIR FIRING MODE (START UP)

CORNER START SEQUENCE:

STEAM ATOMISING VALVE OPENS.

HEA IGNITOR ROD ADVANCES.

HEA IGNITOR SPARK PRESENT FOR 15SECONDS.

HONV OPENS.

SCANNERS SEE FLAME.

NOTE: if there is no flame after 1.10 minutes of start command

a trip command goes to the corner.

Page 138: C&i systems

PAIR FIRING MODE (SHUT DOWN)CORNER STOP SEQUENCE: (Pair 1-3 and Pair 2-4)

HFO NOZZLE valve is closed.

Scavenge and atomising steam valve opens.

HEA ignitor advances and spark remains for 15 seconds.

When atomising steam valve is proven fully open, a 5 minutes counting period starts.

When 5 minutes counting period expires scavenge valve and atomising steam valve closes and further closing command goes HFO nozzle valves to reinsure that they are fully closed.

Page 139: C&i systems

Coal Mill : A Controller of Combustion Time

Hot Air~ 2500C

Coal 10 to 25 mm Size

Page 140: C&i systems

Schematic of typical coal pulverized system

A Inlet Duct;

B Bowl Orifice;

C Grinding Mill;

D Transfer Duct to Exhauster;

E Fan Exit Duct.

Page 141: C&i systems

The primary airflow measurement by round cross-sectional area venturis (or flow nozzles) should be provided to measure and control primary airflow to improve accuracy

Page 142: C&i systems

Aerodynamic Lifting of Coal Particles

Page 143: C&i systems

Pulverizer Capacity Curves

Moisture content, %

Thr

ough

put,

tons

/hr

Grindability

Page 144: C&i systems

Coal Mill : A Controller of Combustion Time

Hot Air~ 2500C

Coal 10 to 25 mm Size

Roller

Bowl

Page 145: C&i systems

Energy Balance across pulverizer is very critical for satisfactory operation of Steam Generator.

Page 146: C&i systems

Hot air

Coal

Dry pulverized coal +Air + Moisture

Puliverizer frictionaldissipation

Motor Power Input

Heat loss

Page 147: C&i systems

The Control of Coal Mills

Page 148: C&i systems

Mill PA /Differential Pressure Control

Page 149: C&i systems

Closed Loop Control of PA Flow

Page 150: C&i systems

Parallel Control of Feeder Speed & PA Flow

Page 151: C&i systems

Control of Suction Mills

Page 152: C&i systems

Mill Temperature Control

Page 153: C&i systems

A comprehensive Mill Control System

Page 154: C&i systems

Sizing of Pulverizers

• Feeder capacity is selected to be1.25 times the pulverizer capacity.

• Required fineness, is selected to be • 60% through a 200 mesh screen for lignite(75 µm), • 65% for sub-bituminous coal, • 70-75% for bituminous coal, and • 80-85% for anthracite.

• Heat input per burner is assumed to be • 75 MW for a low slagging coal and • 40 MW for a severely slagging coal, • With intermediate values for intermediate slagging potentials.

• General Capacity of A Coal Mill : 15 – 25 tons/hour.• Power Consumption: 200 – 350 kW.

Page 155: C&i systems

Prediction of Coal Drying

• For predicting the amount of coal drying which is needed from the pulverizers the following methods were accepted.

• For very high rank coals (fixed carbon greater than 93 percent), an outlet temperature of 75 to 80° C appeared most valid.

• For low- and medium-volatile bituminous coals, an outlet temperature of 65 - 70° C appeared most valid.

• Bituminous coals appear to have good outlet moisture an outlet temperature of 55 to 60° C is valid.

• For low-rank coals, subbituminous through lignite (less than 69 percent fixed carbon, all of the surface moisture and one-third of the equilibrium moisture is driven off in the mills.

Page 156: C&i systems

Logics and interlocks for the following controlFunctions are realised in this section:

1. Selection and control of LP l.O. Pumps.2. Selection and control of HP l.O.Pumps.3. Control of reducer lube oil pump.4. Control of ball & sockets lube oil pump.5. Control of grease pump or greasing sequence.6. Selection and control of trunnion seal air fans7. Control of girth gear seal air fan.8. Control of mill main motor.9. Control of mill aux motor.10. Control of P.A. Gen inlet shut-off gate.11. Control level probe blow down sequence.12. Mill start permissives.

Control for mill and Common mill auxilliaries

Page 157: C&i systems

Logics and interlocks for following Control functions are realized in this section:

1. Elevation start/stop controls.2. Control of coal feeder. 3. Control of prg air damper.4. Control of mill outlet gates.5. Control of raw coal iso- gate.6. Automatic start-up and shut-down sequence of

elevation.

CONTROLS FOR INDIVIDUAL ELEVATIONS :

Page 158: C&i systems

Depending on type of mill envisaged,

This section will have control and Interlocks for :-

1. Tube mill (one mill for 2 elevations).

Or

2. Bowl mill (one mill for each elevation).

Fuel coal section (mill section)

Page 159: C&i systems

MILL START UP SEQUENCE

STEP ‘0’ COMMAND : CLOSING OF GATES/DAMPERSSTEP ‘1’ COMM : GIRTH GEAR SEAL AIR FAN,

TRUNNION SEAL AIR FAN ON COMMSTEP ‘2’ COMM : PURGE AIR DAMPERS OPEN COMM (30 sec)STEP ‘3’ COMM : CLOSE COMM TO PURGE AIR DAMPERS

STOP AUX MOTORSTEP ‘4’ COMM : MILL MAIN MOTOR START COMMSTEP ‘5’ COMM : P.A. GENERAL I/L GATE OPEN COMM

P.C. O/L GATES OPEN COMMSTEP ‘6’ COMM : R.C. GATE OPEN COMMSTEP ‘7’ COMM : FEEDER START COMM

Page 160: C&i systems

SHUT DOWN SEQUENCE IF OTHER ELEVATION IS NOTIN SERVICE

STEP ‘1’ COMM: a) FEEDER STOP COMM & R.C. O/L GATE CLOSE COMMAND.

b)MILL O/L GATES CLOSE.c) MILL MAIN MOTOR OFF COMM 5 Mts after elevd) MILL AUX MOTOR START COMM stop command e) P.A. GEN I/L GATE CLOSE COMM

STEP ‘2’ COMM : OPEN COMM TO PURGE AIR DAMPERSSTEP ‘3’ COMM : CLOSE COMM TO PURGER AIR DAMPERS

(2.5 Mts after opening)

Page 161: C&i systems

STEP ‘1’ COMM : FEEDER STOP COMMAND

R.C. O/L GATE CLOSE COMMAND MILL O/L GATES CLOSE COMMAND

STEP ‘2’ COMM : OPEN COMM TO PURGE AIR DAMPER.

STEP ‘3’ COMM : CLOSE COMM TO PURGE AIR DAMPER.

SHUT DOWN SEQUENCE IF OTHER ELEV IS IN SERVICE

Page 162: C&i systems

MILL START PERMISSIVES

1.NO TRIP FROM MFT.

2.MILL LUBRICATION OK.

3.MILL IGNITION ENERGY AVAILABLE.

4.ELECT.MAGNET.BRAKE RELEASED.

5.BALL & SOCKET PUMP ON & ITS PRESS IS OK.

Page 163: C&i systems

ELEV- A IGNITION PERMISSIVE AVAILABLE Elev-AB Proven

Elev-B Air flow > 40 TPH

Boiler load > 30% AND OR

Ignition Permissive AvailableIgnition Permissive Available

Page 164: C&i systems

ELEV-B IGNITION PERMISSIVE AVAILABLE

3/4 Elev-AB guns proven

Elev-C air flow > 40 TPH Elev-A air flow > 40 TPH

Boiler Load > 30%

OR

ANDOR

Page 165: C&i systems

Ignition Permissive not availableElev-A IGNITION PERMISSIVE NOT AVAILABLE3/4 Elev-AB guns not proven

Boiler load < 30%

Elev-A air flow< 20 TPH

Elev-B airflow < 20 TPH

Elev-B IGNITION PERMISSIVE NOT AVAILABLE

Elev-AB guns not proven Elev-C air flow< 20 TPH

Elev-B airflow < 20 TPH

Boiler load < 30%

ANDOR

AND

ANDAND

OR

Page 166: C&i systems

1. Both Trunnion Seal air fans off > 30 Sec.

2. Mill Seal air pressure not correct.>60sec.

3. Both Mill Main Motor and Aux motor on for > 30 Secs.

4. Mill Emergency trip.

5. Mill bearing temp. very high.

6. P.A. Pressure very low.

7. Mill Reducer lubrication not o.k.

MILL TRIPMILL TRIP

Page 167: C&i systems

8. Mill Bearing lub not o.k.

9. Girth gear greasing sequence not o.k.

10. Electromagnetic brake engaged.

11. Ignition Energy not available.

12. MFT.

13. Centrifugal safety is acted.

14.Both feeders off > 10 min.

15.Both PA Fans off.

Page 168: C&i systems

BOTH HP PUMPS OFFFOR > 5 SEC

BOTH LP PUMPS OFFFOR >5 SEC

LP OIL FLOW LOW (NDE)

LP OIL FLOW LOW (DE)

HP OIL PRESS V.LOW (NDE)

HP OIL PRESS V.LOW (NDE)

HP OIL PRESS V.LOW (DE)

HP OIL PRESS V.LOW (DE)

OR

MILL BRG LUBRICATION NOT CORRECT

Page 169: C&i systems

AND

MILL BRG LUBRICATION O.K

RED LUB O.K

GIRTH GEAR GREASING SEQ O.K

MILL LUBRICATION O.K (START PREM)

FILTER

GREASEBARREL

M

GREASEDIST

GREASE DISTRIBUTOR

AIR FILTER

COMPRESSED AIR

NOZZLE

GREASE PUMPGREASE DISTRIBUTOR

Grease Spray on tothe Pinion

Page 170: C&i systems

LP OIL PUMP

ANDS

R

OR

LP OIL COMP LEVEL ADEQ

ORDER START

AUTOMATIC ON COMM

AUTOMATICOFF COMM

STOP COMM

ANY LP PUMP ON & LP OIL FLOW LOW FOR > 60S

ANY SIDE OIL FLOW LOW CHANGEOVER OF LP PUMP

Page 171: C&i systems

H.P. OIL PUMP

ANDS

R

HP OIL TEMP O.KOIL PRESS IN FEEDINGLINE NOT LOW

ORDER START

ORDER STOP

AUTOMATICON COMM

AUTOMATICOFF COMM

B&S PUMP ALSO STARTS ALONG WITH H.P PUMP

Page 172: C&i systems

AND

H.P OIL TEMP O.K

OIL PRESS IN FEEDING LINE NOT LOW

START PERMISSIVEFOR H.P & B&S PUMP.

AND B&S PRESS NDE OR D.E V.LOW

BOTH LP PUMPS OFF FOR >5 SEC

BOTH HP PUMPS OFF FOR>5 SEC

AUTOMATICOFF COMMTO B&S PUMP

Page 173: C&i systems

AND

H.P OIL TEMP O.K

OIL PRESS IN FEEDING LINE NOT LOW

START PERMISSIVEFOR H.P & B&S PUMP.

AND B&S PRESS NDE OR D.E V.LOW

BOTH LP PUMPS OFF FOR >5 SEC

BOTH HP PUMPS OFF FOR>5 SEC

AUTOMATICOFF COMMTO B&S PUMP

Page 174: C&i systems

OR

OIL PRESS IN FEEDING LINE FOR > 5 SEC

ANY H.P OIL PRESS LOW FOR > 5 SEC

AUTOMATIC OFF COMM TO H.P PUMPS

ANDREDUCER LUB OIL FLOW LOW

RED LUB OIL PUMP ON FOR > 10 SEC

AUTOMATICOFF COMM TO RED LUB OIL PUMP

Page 175: C&i systems

ANDON DEL

30 SEC

MILL MAIN MOTOR OFF

AUX MOTOR OFF

2 SEC PULSE DURATION OFFCOMM TO GIRTHGEAR SEAL AIRFAN.

TRUN SEAL AIR PRESS NOT O.K.FOR >10 SEC WITH ANY TRUN SEALAIR FAN ON

TO CAUSE CHANGEOVER OF TRUN SEAL AIR FAN

Page 176: C&i systems

OR

ONDEL

REDUCER LUB OIL TEMP V.HIGH

10 SEC

RED LUB NOT O.KREDUCER LUB OIL FLOW LOW

REDUCER LUB OIL PUMP OFF

ANDMILL BRG LUBRICATION O.K

RED LUB O.K

GIRTH GEAR GREASING SEQ O.K

MILL LUBRICATION O.K (START PREM)

Page 177: C&i systems

OR

RMILL OFF >30 SEC

ORDER STOP

SEAL AIR PRESSNOT O.K. FOR >10 SEC

ORDER START AUTOMATICON COMMANDTO TRUN SEALAIR FAN

AUTOMATIC OFF COMM

MILL MAIN MOTOR OFF – AUTOMATIC OFF COMMAND FOR P.A GEN I/L SHUT OFF GATE.

S

RUNNING FAN TRIPSAND

Page 178: C&i systems

PURGE AIR DAMPERS

AND

ELEV IGNITION PERMIT AVAILABLE

MILL RELEASE AVAILABLE

START PERM

OR

ELEV IGN PERMIT NOT AVAILABLE

MFR TRIP-1

MFR TRIP-2

AUTOMATIC OFFCOMMAND

Page 179: C&i systems

PC O/L GATES

ELEV IGN. ENERGY AVAILABLE START PERM.

OR

ELEV IGN. ENERGY NOT AVL

MILL TRIP AVAILABLE

AUTOMATICOFF COMMAND

Page 180: C&i systems

AUX MOTOR

ANDSTART PERM MILL LUBRICATION CORRECT

ELECTRO MAGNETIC BRAKE

RELEASED MILL MAIN MOTOR OFF FOR >1 SEC

OR

AUTOMATICOFF COMMAND

MILL MAIN MOTOR ON

MILL LUBRICATION NOTCORRECT

ELECTRO MAGNETIC BRAKEENGAGED FOR >10 SEC

Page 181: C&i systems

R.C FEEDER

AND

START PERMISSIVE MILL MAIN MOTOR ON

FEEDER IN REMOTE

MILL RELEASE AVL

MILL O/L TEMP OK

MILL O/L GATE Side Open

RC SHUTOFF GATE OPEN

NO MFR-1

NO MFR-2

Page 182: C&i systems

R.C FEEDER

OR

AUTOMATICOFF COMMAND

FDR ON FOR >2 SECS ANDRC SHUT OFF GATE CLOSED

MFR TRIP-2 AVAILABLEMFR TRIP-1 AVAILABLE

MILL O/L GATE SIDE CLOSED

MILL MAIN MOTOR OFF

FDR ON & NO COAL ON BELT FOR > 100 SEC

ELEV IGN ENERGY NOT AVL

SCAN DUCT TO FURN ΔP – START COMM FOR STAND BY SCAN FAN

BOTH F.D.FANS OFF – AUTOMATIC OPEN COMMAND FOR SCAN EMER DAMPER.

ANY F.D. FAN ON – AUTOMATIC CLOSE COMM FOR SCAN EMER DAMP.

Page 183: C&i systems

OPERATIONS AND MAINTENANCE CONTROLLABLE FACTORS

• Four controllable heat rate factors are directly related with furnace performance and furnace flue gas uniformity.

• These are: superheater temperature, reheater temperature, desuperheating spray water flow to the superheater, and desuperheating spray water flow to the reheater

• Balancing of the fuel and air to each burner has much to do with furnace combustion efficiency, and the completeness of combustion at the furnace exit.

• The residence time of the products of combustion from the burners to the superheater flue gas inlet is about one or two seconds.

• Not very long for furnace mixing of fuel rich and air rich lanes of combustion products.

• Optimized combustion at the superheater inlet can be quantified by use of a water-cooled high velocity thermocouple probe.

Page 184: C&i systems

• Slagging at the superheater flue gas inlet has been a problem in a number of boilers due to stratified flue gas.

• Slagging at the lower furnace results in large boulder sized clinkers blocking the lower ash hopper.

• Tube spacing becomes ever closer as the heat transfer changes from radiant in the furnace, to convective in the back pass.

• Example: The typical tube spacing of pendant superheater and reheater tubes.

• If lanes in the furnace outlet flue gas approach the ash softening or even the ash fluid temperature, upper furnace slagging and blockage can result in a very short time.

• Several cases studies should be reviewed to show how the application will improved slagging, heat-rate, capacity factor, reliability, NOx and/or fly ash carbon content.

Page 185: C&i systems

SuperheaterSuperheated steam boilers vaporize the water and

then further heat the steam in a superheater. This provides steam at much higher temperature,

but can decrease the overall thermal efficiency of the steam generating plant because the higher steam temperature requires a higher flue gas exhaust temperature. There are several ways to circumvent this problem, typically by providing – an economizer that heats the feed water, – a combustion air heater in the hot flue gas exhaust path, – both.

Page 186: C&i systems

HP

ECO

LTRH

LTSH

HTSH

HTRH

ITSH

DRUM

6

3

5

4

21

6

8

9

34

21

11

SHH

RHH

EH

WWRH

EH

RHH

RHH

RHH

SHH

SHH

SHHSHH

SHH

SHHSHH

SHH

DOWN COMERS

Page 187: C&i systems

Advantages of Superheated Steam

• Increase overall efficiency of both steam generation and its utilisation

• Gains in input temperature to a turbine outweighs any cost in additional boiler complication and expense.

• Almost all steam superheater system designs remove droplets entrained in the steam to prevent damage to the turbine blading and associated piping.

• Overcomes the practical limitations in using wet steam, as entrained condensation droplets will damage turbine blades

Page 188: C&i systems

Superheater Operation• It is similar to that of the coils on an air conditioning

unit, although for a different purpose. • The steam piping is directed through the flue gas

path in the boiler furnace. • The temperature of flue gas in this area is typically

between 1300–1600 degrees celsius (2372–2912 °F).

• Some Superheaters are radiant type; that is, they absorb heat by radiation. Others are convection type, absorbing heat from a fluid. Some are a combination of the two types.

Page 189: C&i systems

Safety Concerns- Superheated Steam • If any system component fails and allows steam to

escape, the high pressure and temperature can cause serious, instantaneous harm to anyone in its path.

• Since the escaping steam will initially be completely superheated vapour, detection can be difficult, although the intense heat and sound from such a leak clearly indicates its presence.

• While the temperature of the steam in the superheater rises, the pressure of the steam does not and the pressure remains the same as that of the boiler.

• The extreme heat (1300–1600°c) in the flue gas path will also heat the superheater steam piping and the steam within.

Page 190: C&i systems

LTSH METAL TEPERATURES

PNG PT

1

PNG PT

14

5

13

6

1211

1098

7

43

2

1

2

3

MAX TEMP:449 DEG C

Page 191: C&i systems

ITSH METAL TEPERATURES

1

PNG PT15

5

13

6

1211

1098

7

43

2

1

MAX TEMP:528 DEG C16

14

2

4

3

65

7

22

2423

25

15 16

1314

12

9

26

11

181917

20

8

21

10

Page 192: C&i systems

HTSH METAL TEPERATURES

PNG PT

1

PNG PT

14

5

13

6

1211

1098

7

43

2

1

23

MAX TEMP:563 DEG C15

16

45

67

8

Page 193: C&i systems

Heat Flux Meter• A heat flux entering steam generating tubes in

power station boilers is a critical factor in considering the safety of the tubes.

• Provides the knowledge of the distribution and magnitude of this flux during the operation of the power boiler is very important.

• The furnace wall metal temperatures are the functions of the heat fluxes and the internal heat transfer coefficients.

• In this study, a measuring device (flux-tube) and a numerical method for determining the heat flux in boiler furnaces, based on experimentally acquired interior tube temperatures, are presented.

Page 194: C&i systems

Heat Flux Meter• An inverse method helps estimate the following

parameters from temperature measurements at several interior locations of the flux-tube : • the absorbed heat flux, • the heat transfer coefficient on the inner tube surface • the temperature of water-steam mixture.

• The number of temperature sensors (thermocouples) is greater than three because the additional information can aid in more accurate estimating the unknown parameters.

• The temperature dependent thermal conductivity of the flux-tube material is assumed.

• The developed flux-tube can work for a long time in the destructive high temperature atmosphere of a coal-fired boiler.

Page 195: C&i systems

Main Steam temperature control• Measurement of S.H outlet temperature primarily

used for the control of main steam temperature

• Air flow signal is used as feed forward signal to control the spray to the S.H attemperator

• Rate of change of temperature at the attemperator outlet is used to trim the control

Page 196: C&i systems

SHH7

1

LEFT

2

RIGHT

LEFT

RIGHT

SHH8

SHH9

SHH6

SHH5

SHH4

SHH3

LTSH ITSH HTSHHP

FROMDRUM

TOHPT

SPRAY WATER

415 0C

540 0C

540 0C475 0C

475 0C480 0C

480 0C394 0C

394 0C

150 Kg/Cm2

150 Kg/Cm2

415 0C

150 Kg/Cm2

150 Kg/Cm2

Page 197: C&i systems

Steam Temperature control with 2 stage Attemperation

Page 198: C&i systems

Reheat steam temperature

• Reheat steam temperature is primarily controlled by burner tilt /gas by-pass on the case may be secondary control is provided by the attemperator

• Using the attemperator (sprom) for control leads to loss of efficiency and should not be used as primary control

• Control philosophy for the attemperator is similar to that of main steam

Page 199: C&i systems

RHH4

LEFT

RIGHT

RHH3

RHH2

RHH1

LTRH HTRH

FROMCRH

TO IPT

SPRAY WATER

35 Kg/Cm2

340 0C

340 0C 405 0C

405 0C

540 0C

540 0C408 0C

408 0C

35 Kg/Cm2

35 Kg/Cm2

35 Kg/Cm2

Page 200: C&i systems

HTRH METAL TEPERATURES

PNG PT

1

PNG PT

14

5

13

6

1211

1098

7

43

2

8

76

MAX TEMP:579 DEG C15

16

543

2

1

Page 201: C&i systems

Superheat and reheat temperature control The main steam temperature at boiler outlet is done through a temperature control system that distributes the boiler heat between steam generation, steam superheating and steam reheating. The various methods used for controlling steam temperature are: •attemperation,•gas proportioning dampers, •gas recirculation, excess air, •burner tilt control, •divided furnace with differential firing and •separately fired superheaters.

Page 202: C&i systems

ATTEMPERATION

Page 203: C&i systems

Boiler AIR AND FLUE GAS SYSTEMThe boiler air and flue gas system consists ofcombustion air system, gas recirculation system flue gas system.

Page 205: C&i systems

• The gas recirculation fan draws flue gas from the economizer outlet flue gas duct and discharge gas to the furnace.

• Modulating inlet damper controls gas recirculation flow rate. The gas recirculation flow set point is derived from the reheat steam temperature control.

Page 207: C&i systems

BURNER TILT CONTROL

Page 208: C&i systems

Water-tube boiler furnaces and gas flow patterns, (a) front-wall-fired furnace, (b) opposed-wall-fired furnace, (c) corner-fired furnace (horizontal section) x burners.

Page 209: C&i systems

SEPARATELY FIRED SUPERHEATER ARRANGEMENT• Water Drum(10) is connected to a steam

drum(11) by a substantially vertical bank(12) of generating tubes.

• The furnace space at the side of the bank opposite the boiler offtake (13) is divided to form a superheater furnace chamber(15) provided with individual fuel feeding means (16,17).

• Baffles prevent flow of gases from boiler chamber(14) to superheater chamber(15).

• Greater part of fuel for a load SP is burned in the boiler furnace and superheating there by of gases passing therefrom over the superheater (21).

• The rest fuel is burned in superheater furnace to get the final MS temperature.

• If final SH temperature increases firing in superheater furnace is decreased and that in boiler furnace is increased and viceversa.

Page 210: C&i systems

Process Control for Optimisation

Combustion control – fuel and air to boiler

• Steam pressure signal is primarily used for controlling the fuel flow and air flow to the boiler

• Steam flow signal is used for feed forward control

• It is ensured that the air flow is more than the optimum excess air during the transient load variation and restored to optimum during stable load condition

• Measurement of O2 & CO is used to trim the air flow

Page 211: C&i systems

A combustion control system regulates the fuel and air input, or firing rate, to the furnace in response to a load index. •The demand for firing rate is, therefore, a demand for energy input into the system to match a withdrawal of energy at some point in the cycle. •For boiler operation and control systems, variations in the boiler outlet steam pressure are often used as an index of an unbalance between fuel-energy input and energy withdrawal in the output steam.

Combustion control systems (air and fuel flow control)

Page 212: C&i systems

WHAT IS A GOOD COMBUSTION?

GOOD COMBUSTION MEANS:-

1) Stable Combustion.

2) Non flickering and non pulsating flame.

3)Does not require oil support if mills are operated as per FSSS logic.

4)High efficiency, i.e., ensuring minimum mechanical and chemical unburnts.

5) Will cause the least erosion and tube failures.

Page 213: C&i systems

HOW TO RECONGINSE GOOD COMBUSTION?

COLOUR OF FLAME AT BURNER ELEVATION OBSERVED THROUGH PEEP HOLES

COLOUR- PALE ORANGE WHILE ON COOL FIRING

FLAME 300 TO 400 mm AWAY FROM BURNER TIP.

FLAME TEMP. 1050 Deg.C TO 1150 Deg.C (AS MEASURED BY OPTICAL PYROMETER)

Page 214: C&i systems

COAL CALCULATION

Air Fuel ratio is defined from stoichiometry theory after we find Boiler capacity, coal specification and excess air set for perfect combustion.

One of the most important items is that the correct amount oxygen must be supplied per unit weight of fuel burned to provide complete combustion.

In addition to the correct “air-fuel” mixture, time must be allowed for complete mixing and burning, and the furnace temperature must be such as to support combustion.

Page 216: C&i systems

BOILER CAPACITY

The Boiler Capacity is defined based on the followingGenerator load demand Coal calorific value. Output steam parameters of super-heater & re-heater Input water to economizer, flue gas parameters to air heater

Page 217: C&i systems

EXCESS AIR

It is supplying just the correct amount of oxygen to assure complete combustion. It deals the difficulty of supplying sufficient oxygen for complete combustion,

while maintaining the nitrogen . It is the relation of the amount of air actually supplied to that theoretically

required for combustion, that is the measure of the efficiency of combustion.

Page 218: C&i systems

• Nitrogen % in air into the furnace is around 4 times the oxygen % in air which is responsible for combustion of fuel.

• It is an inert gas which performs no function in combustion. • As it passes through the furnace, absorbs heat and reduces the

temperature of the products of combustion, i.e. flue gas. • Hence it is the principal source of heat loss in combustion.

Page 219: C&i systems

• Any oxygen supplied to the furnace in excess of that required for combustion results in the same losses as in the case for nitrogen, and furthermore, such excess oxygen is accompanied by additional nitrogen which accentuates the combustion losses.

• On the other hand, when there is insufficient oxygen for complete combustion, the nitrogen losses become inappreciable, when compared to the losses caused by the incomplete combustion of the carbon fuel.

• If insufficient oxygen is present, carbon will not combust to CO2 (carbon dioxide) but to CO (carbon monoxide). From data previously presented, burning one pound of carbon to CO2 will release approximately 14,540 BTU's, while burning the same amount of carbon to CO will only release approximately 4,380 BTU's.

• Hence an optimum amount (3-4 %) of oxygen in flue gas at air heater inlet is maintained for effective combustion, that prevents insufficient combustion as well as heat loss due to high % of nitrogen in excess air.

Page 220: C&i systems

It is very clear that controlling the amount of oxygen required for combustion is critical. The right amount of oxygen is supplied for the complete combustion of the fuel, means Stoichiometric Combustion.

Page 221: C&i systems

An insufficient amount of air is supplied to the burners causes the following•unburned fuel•soot and smoke•carbon monoxide (the incomplete conversion to carbon dioxide) appear in the exhaust from the boiler stack•heat transfer surface fouling•Pollution•lower combustion efficiency•flame instability (i.e., the flame blows out), and the potential for an explosion. To avoid these costly and potentially unsafe conditions, boilers are normally operated at excess air levels. This excess air level also provides operating protection from an insufficient oxygen condition caused by variations in fuel quality, and variation in fuel demand from MW control.

Page 222: C&i systems
Page 223: C&i systems

• It is important to understand that "excess air" and"excess oxygen" are not the same.

• The air we breathe is roughly 21% oxygen by volume. • A 50% excess air condition implies approximately 10.5%

oxygen remains in the boiler exhaust stack.While insufficient air to the burners can be dangerous, air flows in excess of those needed for stable flame propagation and complete fuelcombustion needlessly increase flue gas flow and consequent heat losses, thereby lowering boiler efficiency.

• Minimizing these losses requires monitoring and periodic tuning.

• Ideally, the fuel/air ratio is automatically controlled based on the percentage of O2 in the stack, and an unburned hydrocarbons indication.

• These automated systems are called O2 trim packages.

Page 224: C&i systems

CHIMNEY(60 meters)

SO2 547 ppm (2000 ppm))

NOX 537 ppm (750 ppm)

CO 27 ppm

CO2 12 %

O2 3 %

Page 225: C&i systems

ANALYTICAL INSTRUMENTS

In power plant continuous online quantitative analytical instruments are used which can be broadly classified as stack monitoring instruments, gas analysers and steam and water analysers . However, a few more portable instruments are used in chemical laboratory. The instrumentation system may be in-citu or with an additional sampling system.

Page 226: C&i systems

An oxygen sensor, or lambda sensor, is an electronic device that measures the proportion of oxygen (O2) in the flue gas at air heater inlet. The original sensing element is made with a thimble-shaped zirconia ceramic coated on both the exhaust and reference sides with a thin layer of platinum and comes in both heated and unheated forms. The recent planar-style sensor reduced the mass of the ceramic sensing element as well as incorporating the heater within the ceramic structure has fast response

Page 227: C&i systems

Ultraviolet (UV) Type Gas measuring principle Ultraviolet (UV) light is often used for the analysis of NO, NO2

and SO2. Often, when the UV measuring principle is used it is actually the NDUV (Non Dispersive Ultraviolet) principle. The measurement is made by leading a gas flow through a cuvette where the UV light source and the optical filter have been placed at one end of the cuvette and a detector has been placed at the other end. The UV light source sends out a scattered UV light, and the wave length of the light that is led through the gas in the cuvette is determined by the optical filter installed between the light source and the cuvette. Different kinds of wave lengths of UV light are used to analyse different gasses.

Page 228: C&i systems

Dust and Opacity monitor•When a beam of light crosses a medium containing smokes or dust particles, some of the light is transmitted and some is lost due to scattering. •The fraction, which is transmitted, is called the transmittance and the fraction, which is lost, is the opacity.

Page 229: C&i systems

3. Feed water control

• There is a feed water regulating station with there control valves; one for 0-25% load and two for full load all are connected in parallel

• In conjunction with feed regulating station , speed control of BFP is provided to reduce the throttling losses across the control valve

• Recirculation control is provided to maintain minimum flow required to prevent flashing in the pump casing

Page 230: C&i systems

DRUM LEVEL MEASUREMENT

Page 231: C&i systems

DRUM LEVEL MEASUREMENT-DIFFERENTIAL MEASUREMENT METHOD –HYDRASTEP ELECTRODE

Page 232: C&i systems

HYDRASTEP DRUM LEVEL MONITORING

Page 233: C&i systems
Page 234: C&i systems

RING HEADER

BLOW DOWN HEADER

ECONOMISER

HANGER TUBES

345 DEG.C346 DEG.C346 DEG.C

342 DEG.C343 DEG.C343 DEG.C

-214 mm-202 mm

-177 mm-247 mm-179 mm

-22mm B-15

B-16

E-2

B-67

B-68

B-70

B-71

B-60

B-61

IBD IBD CBD

163.3 KG/SQCM

DRUM LVL

DRUM TEMP

DRUM PRESS

Page 235: C&i systems

• Drum water level is one of the most important measurement for safe and reliable Boiler operation.

• If the level is too high, • water flows into the superheater with droplets carried

into the turbine. • leaves deposits in the superheater and turbine• causes superheater tube failure • turbine water damage.

• Low water level would cause • starvation in water tube• overheating • failure.

Page 236: C&i systems

DRUM LEVEL CONTROL

Page 237: C&i systems

In single element feed water control the water in the drum is at the desired level when signal from the level transmitter equals its set point. If a deviation of water level exists, the controller applies proportional plus integral action to the difference between the drum level and set point signals to change the position of the regulating valve.

Feedwater control systems: This regulates the flow of water to a drum-type Boiler to maintain the level in the drum within desired limits. They are classified as one-, two- or three-element feed water control systems.

Page 238: C&i systems

DRUM LEVEL CONTROL CONV MASTERIn the boiler the steam flow changes according to the load demand from the turbine or from the process consuming the steam energy. To match the steam take off from the boiler, the feed water flow has to be increased or decreased as required.

Single Element ControlDuring low load operation, three-element control is not required. •Drum level measurement with it's set point is adequate. •The output of the Drum Level Controller is directly given to the Feed water by-pass Control Valve. •It is difficult to obtain steam and water flow accurately because flow transmitters are usually calibrated for high load operation. Hence it’s transferred to single element control where drum level is the only variable in the control scheme.

Page 239: C&i systems

The Kvs can be thought of as being the actual valve capacity required by the installation and, if plotted against the required flow rate, the resulting graph can be referred to as the 'installation curve. The graph looks like linear due to a few data.

Boiler Feed Pump discharge pressure usually fixed 125 bar. After Feedwater by-pass control valve almost maximum, this is the time to change master control from single element to three element control called Boiler Feed Water Pump Conversion Master.

Valve capacities are generally measured in terms of Kvr which is equal to Kv*(DP)^0.5. More specifically, Kvs relates to the pass area of the valve when fully open, whilst Kvr relates to the pass area of the valve as required by the application.

BOILER FEEDPUMP CURVE

Page 240: C&i systems

Three Element Feed water ControlFor automatic control of the feed water flow to the boiler, following three(elements) primary inputs are normally being considered. Drum level, Main Steam flow, Feed water flow. The different of steam flow and feed water flow will trigger to controller also change of level drum as a picture below.

The valve DP is the difference between the pump discharge pressure and a constant boiler pressure of 10 barg. Note that the pump discharge pressure will fall as the feed water flow increases. This means that the water pressure before the feed water valve also falls with increased flow rate, which will affect the relationship between the pressure drop and the flow rate through the valve.Fluid coupling with a scoop tube adjust is maintain pump discharge is 10 bar above steam drum pressure.

Page 241: C&i systems

The control applies proportional action to the error between the drum level signal and its set point. The sum of the drum level error signal and the steam flow signal is compared with water flow input and the difference is the combined output of the controller. Proportional plus integral action is added to provide a feed water correction signal for valve regulation or pump speed control.

Page 242: C&i systems

Two-element control comprises feedforward control loop which utilizes steam-flow measurement to control feedwater input, with level measurement assuring correct drum level.

Three-element control is a cascaded-feedforward control loop which maintains water flow input equal to feedwater demand. Drum level measurement keeps the level from changing due to flow meter errors, blowdown , or other causes.

Page 243: C&i systems
Page 244: C&i systems
Page 245: C&i systems

Feed water heating and deaerationThe feed water used in the steam boiler is a means of

transferring heat energy from the burning fuel to the mechanical energy of the spinning steam turbine.

The total feed water consists of recirculated condensate water and purified makeup water.

The metallic materials it contacts are subject to corrosion at high temperatures and pressures, hence the makeup water is highly purified before use.

A system of water softeners and ion exchange demineralizers produces water so pure that it coincidentally becomes an electrical insulator, with conductivity in the range of 0.3–1.0 microsiemens per centimeter.

SWAS : Is a system for on-line measurement of pH, conductivity, Dissolved Oxygen, Sillica etc. content in water.

Page 246: C&i systems
Page 247: C&i systems

PH 8.8 TO 9.2 8.83

CONDUCTIVITY

micromho/cm2

<5 3.33

TOTAL HARDNESS NIL NIL

SILICA < 0.02 ppm 0.007 ppm

CONDENSATE

Page 248: C&i systems

PH 8.8 TO 9.2 8.83

CONDUCTIVITY

micromho/cm2

<5 3.33

TOTAL HARDNESS NIL NIL

SILICA < 0.02 ppm 0.007 ppm

HYDRAZINE 0.02 -0.03

ppm

0.02

AMMONIA <1.0 ppm 0.16

FEED WATER

Page 249: C&i systems

PH 9.4 TO 9.7 9.58

CONDUCTIVITY

micromho/cm2

<100 24

TOTAL HARDNESS NIL NIL

SILICA < 0.02 ppm 0.007 ppm

PHOSPHATE 3 - 8 ppm 4.4

BOILER DRUM

Page 250: C&i systems

PH 8.8 TO 9.2 8.83

CONDUCTIVITY

micromho/cm2

<5 3.51

TOTAL HARDNESS NIL NIL

SILICA < 0.02 ppm 0.007 ppm

SATURATED STEAM

Page 251: C&i systems

PH 8.8 TO 9.2 8.83

CONDUCTIVITY

micromho/cm2

<5 3.51

TOTAL HARDNESS NIL NIL

SILICA < 0.02 ppm 0.007 ppm

MAIN STEAM

Page 252: C&i systems

Monitoring and maintaining proper chemical conditions are essential for reliable and efficient power plant operation. Failure to meet purity and chemical composition requirements can lead to inefficient operation and eventually component failure.

Page 253: C&i systems

Several types of measurements can be done on a continuous basis in the process stream. For example, conductivity and pH. These analyses can be performed by in-line analyzers.

Page 254: C&i systems

There are also semi-continuous methods that, because of their monitoring techniques, can not be made completely continuous. Examples of semi-continuous monitors are ones that require addition of one or more reagents that react with the sample prior to detection. These semi-continuous monitors have a controlled cycle time, or time interval, between repetitive sample introductions. The cycle time is long enough to allow detection but short enough to maintain the timely reporting of data. Silica, phosphate, and hydrazine inline analyzers are examples of this type of monitor.

Page 255: C&i systems

The most basic in-line analyzers are pH, conductivity, and oxygen monitors. These monitors have been in use for a long time. In-line monitoring systems may reduce the number of analyses performed by the chemistry staff and can provide accurate and reliable indications to the operating group.

Page 256: C&i systems

In-line monitor alarms are sometimes ignored. The alarm is often given low priority because it is assumed to be due to a malfunctioning analyzer, or to loss of sample flow. In-line monitors that continually alarm due to these causes foster this belief by frequently "crying wolf". When the monitor does alarm due to an action level incident, and it is again given low priority, serious consequences can ensue.

Page 257: C&i systems

It is therefore important that in-line monitors be maintained in good operating condition so they will be reliable. Perpetually malfunctioning monitors or sample pumps should be replaced. The integrity of the in-line chemistry monitoring system must be held in high regard. It is dependent on the effort expended by laboratory staff and instrumentation personnel to assure the system's accuracy and reliability.

The main purposes of analyzers are to:Signal the existence of corrosive conditions within the system.

Indicate the amount of scale-forming substances in the system.Monitor the carry-over in the steam.

Monitor demineralizer effluent quality.

Page 258: C&i systems

pH Analysers

Monitoring the pH of water gives an indication of the acidity or alkalinity of the solution. This is important since both high pH (alkalinity) or low pH (acidity) can contribute to the corrosion of plant equipment. Proper control of pH can reduce corrosion along with maintaining the integrity of protective films on metal surfaces. Continuous in-line pH monitoring is a simple and reliable method of measuring the acidity of water.

Page 259: C&i systems

In a power plant, the pH is usually monitored at the economizer inlet and in the boiler water. In a system with mixed metallurgy, the pH is normally maintained between 8.8 and 9.3 (low enough so ammonia will not corrode copper, but high enough so that iron is protected). In all steel systems, the pH is normally maintained somewhat higher, between 9.0 and 9.6 to provide greater protection for the iron surfaces.

Page 260: C&i systems

In order to maintain these pH levels, either ammonia or morpholine is added to the system. Since the amount of Morpholine added to the system will effect the final system pH, there must be some feedback between the pH controlling chemical addition and system pH.

Page 261: C&i systems

Water chemistry monitoring provides essential information to the plant staff so that the plant can be operated at optimum efficiency. A variety of instruments and methods are used to analyze system streams throughout the power generation cycle.

Page 262: C&i systems

History has shown it is impossible to control system pH without considering the chemical composition of the fluid, as well as process temperature, pressure and flow rate. pH control systems can range from very simple ON / OFF control, to more complex feedforward / feedback control loops.

Page 263: C&i systems

Conductivity is the ability of a material to carry an electrical current. The measurement of specific conductivity is the most common of the conductivity measurements in a power plant. It gives a good indication of the concentration of dissolved solids, or ionic impurities in the sample.

Page 264: C&i systems

Since water is a poorly ionizing substance, the addition of even the slightest trace of electrolytic material causes a large increase in conductivity. For example, a solution of pure water will double its conductance with the addition of 1 ppm of a typical salt, and 1 ppm of a strong acid will increase the specific conductivity by as much as 500%

Page 265: C&i systems

Dissolved Oxygen AnalyzersOxygen is a main factor in boiler system corrosion. Dissolved oxygen, in boiler water containing traces of chlorides or solids, is a common cause of pitting corrosion on metal surfaces.To prevent corrosion, oxygen and other gases are removed from the feedwater before it enters the boiler. Removal can be accomplished either mechanically or chemically. Deaerators are mechanical means of removing dissolved oxygen. The injection of chemicals, known as oxygen scavengers, such as sulfites or hydrazine will also reduce the levels of oxygen dissolved in the feedwater.

Page 266: C&i systems

In-line monitoring of dissolved oxygen, or DO, is performed at several points in the cycle, •the condensate pump discharge, •the deaerator inlet and outlet, •the economizer inlet. Typically, the dissolved oxygen concentration at the condensate pump discharge is less than 20 ppb.The deaerator normally reduces the DO content to below 7 ppb.The chemical oxygen scavengers further reduce the DO content to less than 5 ppb at the economizer inlet.

Page 267: C&i systems

DEAERATOR

-2200-2000

1000

-1500-1000-500

0500751 mm

700 mm722 mm

BFP SUCTION

CRH

BFP’SRECIRCULATION

DEA LVL

DR TANK

1500

8 Kg/Cm2

160 0C

1800

EXT-4

HPH-5 DRN

HPH-6 DRN

LPH-3680 T/hr 6 Kg/Cm2

6 Kg/Cm2

APRDS

Page 268: C&i systems

LTRH

LTSH

HTSH

HTRH

ITSH/HP

LTRH

LTSH

HTSH

ECO ECO

ITSH/HP

HTRHWATER WALL SB

LONG RETRACTABLESB

HALF RETRACTABLESB

frontleft

rearright

AcousticSteamLeak Detector

Page 269: C&i systems

Acoustic Steam Leak DetectorBenefits of the early detection of tube leaks:

• Increased Personnel Safety• Early warning of a small boiler tube leak can prevent expensive secondary damage and unscheduled outages • Increased availability, reduces repair time, and increases plant efficiency• Planned and scheduled orderly shutdown of a boiler at the most convenient time• An increase in boiler availability of just one day will more than cover the cost of a leak detection system• Safeguards your investments• Increased operating profits by Reducing Financial Penalties• Other benefits include the Detection of abnormal boiler operating conditions, for example the incorrect operation of soot blowers, inspection ports being left open, and steam leaks external to the boiler

Page 270: C&i systems

4. Control of secondary condensate / drain in the feed heaters

• Drain is cascade from higher pressure heaters to lower pressure heaters to maintain a constant level in the heater shells ultimately dumping in the dearator (D/A) or condenser hot well as the case may be .

•Some times, it is advantageous to dump the drain of L.P heaters in to the D/A to conserve all the heat with out losing to the C.W , even if requires a drain pump

Page 271: C&i systems

Automatic control system usually consist three kind, •Proportional, •Combination of Proportional & Integral •Combination of Proportional-Integral-Derivative Control.

BASIC CONTROL

Page 272: C&i systems

PROPORTIONAL-INTEGRAL-DERIVATIVE CONTROL

Page 273: C&i systems

Proportional Control• Produces output proportional to error.• The greater the error, the greater the control

effort; and as long as the error remains, the controller will continue to try to generate a corrective effort.

Page 274: C&i systems

Gain of the controllerThe constant of proportionality is the Gain of the controller, which is related to the proportional band of the controller.

Page 275: C&i systems

Example of Gain

0%

1000C

70%

1700C

100%

2000C

0%

100%

% o

utpu

t

Ele

ctri

cal o

utpu

t

4 mA

20 mA

% Measured Value

Measured Temperature

% PB = 70

A controller has input range of1000C - 2000C and its output iscurrent in the range 4 -20 mA.What is the numerical gain ofthe controller?

Page 276: C&i systems

Gain of the Controller

The numerical gain of the controller is the numerical value of the slope of the output/input graph.If the controller has 70% proportional band(PB) thenGain =

input

output

in

in

change

change

fractional

Fractional

100% of(20 mA – 4 mA)

70% of (2000C - 1000C)= =

16 mA

700C= 0.229 mA/0C

In some cases if output span = input span then

Gain = 100 / %PB

Page 277: C&i systems

A mechanical flow controller manipulates the valve to maintain the downstream flow rate in spite of the leakage. The size of the valve opening at time t is V(t). The flowrate is measured by the vertical position of the float F(t). The gain of the controller is A/B. This arrangement would be entirely impractical for a modern flow control application, but a similar principle was actually used in James Watt’s original fly-ball governor. Watt used a float to measure the speed of his steam engine (through a mechanical linkage) and a lever arm to adjust the steam flow to keep the speed constant.

Page 278: C&i systems

Flow control example

A portion of the water flowing through the tube is bled off through the nozzle on the left, driving the spherical float upwards in proportion to the flow rate. If the flowrate slows because of a disturbance such as leakage, the float falls and the valve opens until the desired flow rate is restored.In this example, the water flowing through the tube is the process, and its flow rate is the process variable that is to be measured and controlled. The lever arm serves as the controller, taking the process variable measured by the float’s position and generating an output that moves the valve’s piston. Adjusting the length of the piston rod sets the desired flow rate; a longer rod corresponds to a lower set point and vice versa.

Page 279: C&i systems

Proportional Control TerminologyPercentage Values of Controller output:•In a practical situation the controller will only recognize variations of the signal between the lowest possible level i.e. 0% and the maximum possible level i.e. 100%. •Thus process control engineers talk of in terms of percentage values of pressure, temperature, flow etc. instead of actual values.

Page 280: C&i systems

An ExampleSuppose a temperature controller works within the range of 200° C and 500° C Then 200 refers to 0% of measured value and 500 refers to 100% of measured valueSpan of the instrument = 500 – 200 = 300° CIf set point of the controller is 350° C and the the value of the output temperature is 300 ° C Then Actual Deviation = 350 – 300 = 50 ° C% Deviation = actual dev / Measurement span X 100 = 50 / 300 X100 = 16.67%

Page 281: C&i systems

Proportional Band• Proportional Band of the controller is the %deviation

which gives rise to 100% change in controller output.Thus a narrow proportional band means a small change in deviation produces a large change in controller output. Or the controller has a large Gain.

Proportional Band

0102030405060708090

100

0 20 40 60 80 100

Set Point

%C

on

tro

lle

r O

utp

ut

20% Proportional Band

200% Proportional Band

100%Proportional Band

Page 282: C&i systems

Proportional Control & Steady State Error

An important property of proportional control is that there will always be a steady state error or offset. Thus the controlled out put will never match the set point. Increase of gain can reduce the offsetbut this can never be zero, also too much increase of gain can cause the system to become unstable.

Page 283: C&i systems

Response of Proportional Controller

200% PB

100% PB

20% PB

• Even with 20%PB there is offset.• Narrow bands like 20% are not common.

100

TIME

Page 284: C&i systems

Effect of adjustment of PB on the system

Smaller Proportional band 1. Faster response2. Less stability3. Low offset

Larger Proportional band1. Slow response2. More stable3. Large offset

We saw that for proportional action there will always be an offset no matter how high the gain of the controller. So what we need is a mechanism which will cause the controller output to increase as long as the offset remains.Only when the offset is zero will the controller output be constant.

Page 285: C&i systems

The same mechanical controller now manipulates the valve to shut off the flow once the tank has filled to the desired level Fset. The controller’ gain of A/B has been set much lower, since the float position now spans a much greater range.

Integral Action

Page 286: C&i systems

Integral ActionThe Proportional Integral controller integrates the error signal so long as the error exists to obtain zero offset. Integral action is also called Reset action

Page 287: C&i systems

PI Control

From the figure we can see the law for PI Control.

Controller output = K E + ∫1

1

TE dt

Where KE is the contribution of the proportional controller

∫1

1

T Edt is the integral contribution.and KT1 is called Integral Action Time or Reset Time

Page 288: C&i systems

Integral Time or Reset TimeLarger Reset time less Integral actionSmaller Reset time more Integral action

Reduction of Integral action

• System takes more time to reach zero offset.• Less overshoot • More stable system

Page 289: C&i systems
Page 290: C&i systems

The Derivative Action

In the figure a) shows setpointb) shows system output and c) shows error for a PI controller. The error waveform has a wrong shape to produce the response i.e. output reaches final value without overshoot. Thus the shape of the controller output should be d) i.e. the controller goes negative to prevent overshoot. e) The additional signal is given by Derivative of the error (f).

Page 291: C&i systems

DERIVATIVE KICKERDerivative kicker is used for elimination excessive overshoot at begin and undershoot control after reaching the set point. As we know that proportional-integral control already have overshoot and undershoot and will reduce by integral control but output will take long time to reach the set point.

Derivative control will improve response but in the steam power plant control, derivative kicker is not necessary to apply.This modification is going to tweak the derivative term a bit. The goal is to eliminate a phenomenon known as “Derivative Kick”.

Page 292: C&i systems

The image here illustrates the problem. Since error=Setpoint-Input, any change in Setpoint causes an instantaneous change in error. The derivative of this change is infinity (in practice, since dt isn’t 0 it just winds up being a really big number.) This number gets fed into the pid equation, which results in an undesirable spike in the output. Luckily there is an easy way to get rid of this.

It turns out that the derivative of the Error is equal to negative derivative of Input, EXCEPT when the Setpoint is changing. This winds up being a perfect solution. Instead of adding (Kd * derivative of Error), we subtract (Kd * derivative of Input). This is known as using “Derivative on Measurement”

Page 293: C&i systems

The modifications here are pretty easy. We’re replacing +dError with -dInput. Instead of remembering the last Error, we now remember the last input. Here’s what those modifications get us. Notice that the input still looks about the same. So we get the same performance, but we don’t send out a huge Output spike every time the Setpoint changes.

This may or may not be a big deal. It all depends on how sensitive your application is to output spikes. The way I see it though, it doesn’t take any more work to do it without kicking so why not do things right?

Page 294: C&i systems

PID Controller• The derivative signal is the rate of change of error signal.• It is obtained by a circuit which differentiates the error.• Thus adding D to PI controller we get a controller which can

give rapid response without much overshoot.• PID controller is also called Three Term Controller

ControllerOutput = K E + ∫

1

1

TE dt + Td

dEdt

Td is derivative time

Making Td = 0

removes D action from

the controller

Page 295: C&i systems

PID Controller Response

PB 100%I = 0D = 0

PB 100%I = 1.5 τ D = 0

PB 100%I = 1.5 τ D = 0.3 τ

Page 296: C&i systems

PD Controller

In case of a PD controller the Derivative component has no effect on the offset. It can only reduce overshoot and make the system respond rapidly.

Page 297: C&i systems

Setting for P, I & D 1. More exponential lags in the system higher the chance of

oscillations.2. If the system contains more transport delays there is more chance

of instability.3. Low Proportional Band (high gain) can reduce offset. But it can

not eliminate offset and can reduce stability.4. Integral action removes offset but too rapid integral action can

reduce stability.5. Derivative improves response and makes the system settle down

quickly.6. Derivative is not normally used in fast systems like flow control

with minimum process lags. As the D element can over react to quick changes of measured value.

Page 298: C&i systems

Adjustment of Proportional Controllers

1. Start with a wide band (low gain) observe behavior.2. Increase gain step by step and

observe behavior.3. At a certain narrow band the offset

will be small. If the oscillation is acceptable this can be kept.

4. Else reduce gain to get optimum response.

Page 299: C&i systems

Adjustment of PI ControllersStep 1:1. With I at zero (lowest rate) follow

procedure for P controller.2. Increase band slightly to obtain a

response slightly slower than ideal.Step 2:1. With P remaining at its setting

increase integral rate in small steps while creating set point and load changes and observing the behavior until cyclic behavior increases.

2. Reduce integral rate to obtain optimum value.

Page 300: C&i systems

Adjustment of PD Controllers

Step1: With D at zero follow procedure for

P controllers until an acceptable response is obtained.

Step2:• With P kept at its setting increase

D in steps and observe behavior with set point and load changes until cyclic behavior begins to increase.

• Reduce D slightly to get an acceptable response.

• Try increasing gain slightly if the stability is OK.

Page 301: C&i systems

Adjustment of PID Controllers

Step1: I and D at zero (or minimum setting). Follow procedure for proportional controllers until a result more oscillatory than desirable is obtained.Step2: With P set increase I as before until point of instability is approached.Step3: With P and I set slowly increase D as for PD control.Step4: After setting of D, try increasing gain for better result.

Page 302: C&i systems

Detection of Excessive adjustment

The following guide line may help:1. Integral cycling has relatively long period.2. Proportional cycling has relatively moderate period.3. Derivative cycling has relatively short period.

While adjusting a controller there often will be excessive adjustment which will cause oscillations, the practical difficulty is to detect which control action is at fault. These are practical difficulties and one can only learn to deal with them with experience.

Page 303: C&i systems

FEEDBACK CONTROL A feedback loop measures a

process variable and sends the measurement to a controller for comparison to setpoint. If the process variable is not at setpoint, control action is taken to return the process variable to setpoint. Figure illustrates a feedback loop in which a transmitter measures the temperature of a fluid and, if necessary, opens or closes a hot steam valve to adjust the fluid’s temperature.

Page 304: C&i systems

FEEDFORWARD CONTROL Feedforward control is a

control system that anticipates load disturbances and controls them before they can impact the process variable. For feedforward control to work, the user must have a mathematical understanding of how the manipulated variables will impact the process variable.

Page 305: C&i systems
Page 306: C&i systems

FEEDFORWARD PLUS FEEDBACK

• Figure shows a feedforward-plus-feedback loop in which both a flow transmitter and a temperature transmitter provide information for controlling a hot steam valve.

Page 307: C&i systems
Page 308: C&i systems

CASCADE CONTROL

• Cascade control is a control system in which a secondary (slave) control loop is set up to control a variable that is a major source of load disturbance for another primary (master) control loop. The controller of the primary loop determines the setpoint of the summing contoller in the secondary loop

Page 309: C&i systems

RATIO CONTROL

• The controller performs a ratio calculation and signals the appropriate setpoint to another controller that sets the flow of the second fluid so that the proper proportion of the second fluid can be added.

Page 310: C&i systems
Page 311: C&i systems
Page 312: C&i systems

Heading-2

Page Content…..

Heading-1Heading-1

Page 313: C&i systems

OMS POWER TRAINING AND RESEARCH INSTITUTE

N-2/170, IRC VIllage, Nayapalli, BHUBANESWAR-751015. Tel. : 0674-2552984, 2552985.

website - www.omstraining.net. Email - [email protected]