2
Type ELK-AG-N up to 260 °C Advantages: Factory terminated High chemical and mechanical resistance Can be used in all industrial areas High working temperature Can be used in liquids Easy to install, even on complex shapes Highly flexible Resistant to steam purging This versatile heating cable is used for freeze protection and temperature maintenance, even under highly corrosive environmental conditions. The heating cable ELK-AG-N is suited and approved for use in potentially explosive atmospheres. It is highly flexible permitting its application in areas of use. Upon consultation of our engineers, this cable may likewise be used for inside trace heating of piping. factory terminated PTFE insulated heating cable 1.21 Applications, especially in hazardous areas: e.g. Heat tracing on tanks Heat tracing on vessels Heat tracing on filters Heat tracing on hoppers Pipes, valves and pumps Tank containers IBC’s Heating hoods Automotive Varnishing plants heating cables and heating tapes 1.21

Eltherm ELK-AG-N Heat Trace Cable - Spec Sheet

Embed Size (px)

Citation preview

Page 1: Eltherm ELK-AG-N Heat Trace Cable - Spec Sheet

Type ELK-AG-N up to 260 °C

Advantages: Factory terminated High chemical and mechanical

resistance Can be used in all industrial areas High working temperature Can be used in liquids Easy to install, even on complex shapes Highly flexible Resistant to steam purging

This versatile heating cable is used for freeze protection and temperature maintenance, even under highly corrosive environmental conditions. The heating cable ELK-AG-N is suited and approved for use in potentially explosive atmospheres. It is highly flexible permitting its application in areas of use. Upon consultation of our engineers, this cable may likewise be used for inside trace heating of piping.

factory terminatedPTFE insulated heating cable

Heating cable und Heizbänder 1.21

Applications, especially in hazardous areas: e.g.

Heat tracing on tanks Heat tracing on vessels Heat tracing on filters Heat tracing on hoppers Pipes, valves and pumps Tank containers IBC’s Heating hoods Automotive Varnishing plants

heating cables and heating tapes 1.21

Dan Macey
TH1
Page 2: Eltherm ELK-AG-N Heat Trace Cable - Spec Sheet

03/2

012

– A

ll rig

hts

rese

rved

. Sub

ject

to c

hang

e w

ithou

t not

ice.

*Note: The output per meter of heating cable and the maximum possible working temperatures depend on the respective application. For individual cases, we recommend that you contact our engineers – we will be pleased to advise you.

Manufactured according to DIN VDE 0253, EN 60079-30-1

Cable 60079-30-1

Pipe collar 60079-0-7

VDE mark approval 40024940

ATEX certificate PTB 09 ATEX 1029 U IBExU 04 ATEX 1005X

Classification II 2G Ex e II II 2D Ex tD A21

Technical information

Standards

Insulation PTFE

Protective braid nickel-plated copper

Outer jacket PFA

Nominal voltage 230 V

Output 25 W/m

Working temp., max. 260 °C

Heating conductor diameter 3,8 - 4,7 mm

Bending radius, min. 2,5 x outer diameter

Installation temp., min. -60 °C

Cold lead length, both ends 1,2 m, without plug

Moisture proof yes

Protection class I

Impact resistance 4 Joule

Data

Type ELK-AG-N up to 260 °C

Heating cable und Heizbänder Telefon: +49 (0) 27 36 / 44 13-0 www.eltherm.com1.22

Ex-Con connection and junction kit

Cables shall neither intersect nor contact. Provide protection by means of circuit breaker FI 30mA. Please observe the standards IEC 62395-2, EN 60519-10.

heating cables and heating tapes Phone: +49 (0) 27 36 / 44 13-0 www.eltherm.com1.22

Dan Macey
TH1