Type ELK-AG-N up to 260 °C
Advantages: Factory terminated High chemical and mechanical
resistance Can be used in all industrial areas High working temperature Can be used in liquids Easy to install, even on complex shapes Highly flexible Resistant to steam purging
This versatile heating cable is used for freeze protection and temperature maintenance, even under highly corrosive environmental conditions. The heating cable ELK-AG-N is suited and approved for use in potentially explosive atmospheres. It is highly flexible permitting its application in areas of use. Upon consultation of our engineers, this cable may likewise be used for inside trace heating of piping.
factory terminatedPTFE insulated heating cable
Heating cable und Heizbänder 1.21
Applications, especially in hazardous areas: e.g.
Heat tracing on tanks Heat tracing on vessels Heat tracing on filters Heat tracing on hoppers Pipes, valves and pumps Tank containers IBC’s Heating hoods Automotive Varnishing plants
heating cables and heating tapes 1.21
03/2
012
– A
ll rig
hts
rese
rved
. Sub
ject
to c
hang
e w
ithou
t not
ice.
*Note: The output per meter of heating cable and the maximum possible working temperatures depend on the respective application. For individual cases, we recommend that you contact our engineers – we will be pleased to advise you.
Manufactured according to DIN VDE 0253, EN 60079-30-1
Cable 60079-30-1
Pipe collar 60079-0-7
VDE mark approval 40024940
ATEX certificate PTB 09 ATEX 1029 U IBExU 04 ATEX 1005X
Classification II 2G Ex e II II 2D Ex tD A21
Technical information
Standards
Insulation PTFE
Protective braid nickel-plated copper
Outer jacket PFA
Nominal voltage 230 V
Output 25 W/m
Working temp., max. 260 °C
Heating conductor diameter 3,8 - 4,7 mm
Bending radius, min. 2,5 x outer diameter
Installation temp., min. -60 °C
Cold lead length, both ends 1,2 m, without plug
Moisture proof yes
Protection class I
Impact resistance 4 Joule
Data
Type ELK-AG-N up to 260 °C
Heating cable und Heizbänder Telefon: +49 (0) 27 36 / 44 13-0 www.eltherm.com1.22
Ex-Con connection and junction kit
Cables shall neither intersect nor contact. Provide protection by means of circuit breaker FI 30mA. Please observe the standards IEC 62395-2, EN 60519-10.
heating cables and heating tapes Phone: +49 (0) 27 36 / 44 13-0 www.eltherm.com1.22