Smart ContainmentExtending the Life of the Data Center

Page 2: Polargy Smart Containment

The Cooling Trend

Waste, but high

Over provisioned Contain Monitor & Control

Waste, but high

margin for error

Yesterday Today Tomorrow

Efficiency, but

smaller margin

for error

� Need new tools to closely couple cooling to demand

Increased energy

& capex costs

driving change

En

erg

y

Page 3: Polargy Smart Containment

• Low ∆-T impairs CRAH efficiency

• Capacity unnecessarily limited

Air Mixing Lowers Efficiency

• Capacity unnecessarily limited

• 60% of cold air is wasted

• Typical 3X over provisioned

• Free mixing prevents tight supply

control

Page 4: Polargy Smart Containment

Containment Stops Mixing

• High ∆-T boosts CRAH efficiency

• Reduces operating expenses• Reduces operating expenses

• Capacity expands

• Eliminates hotspots

• Isolated airflow enables tight

supply control

Page 5: Polargy Smart Containment

How Does Containment Work?

• Airflow isolation barriers prevent hot return

air from mixing with cold supply air

• The hot return air stays hot, increasing the

return air temperature to the CRAH unitsreturn air temperature to the CRAH units

• The ∆-T across the CRAH increases which

results in more efficient cooling

• Makes the supply air temperature more

uniform across the server inlets, improving

reliability

Page 6: Polargy Smart Containment

Containment Systems

Vertical Panels

HorizontalPanels

Page 7: Polargy Smart Containment

Hot Aisle• Keeps ∆-T highest by

Cold Aisle• More direct path of cold

The Great Debate –

Which Aisle Do You Contain?

preventing cooling of the

hot air

• Comfort in open area

• Switch gear

• Easy to balance zones

• More direct path of cold

air to servers

• Positive air pressure

• Comfort in hot aisle

• More deployment

options

vs.

Page 8: Polargy Smart Containment

AC RACK RACK AC RACK RACK

Containment Architectures

AC RACK RACK

AC RACK RACKAC RACK RACK

AC RACK RACK

Page 9: Polargy Smart Containment

Smart Containment:

The Cooling Efficiency Stack

MONITOR CONTROLCONTAIN

• Barriers above racks• Temperature • Fan speed

• Doors on aisle ends

• Blanking panels

• Filling floor gaps

• Plenum returns with

ducted CRAHs

• Pressure

• Humidity

• Power

• Cooling plant

• Set points

• Chilled water flow

• Economizer hours

• CRAH on/off

Page 10: Polargy Smart Containment

Monitor & Control

• Automatic start/stop of CRAC units

Wireless Sensor Network

Adaptive Control Measures

units

• Adjust variable speed fans

• Change CRAC set points

• Increase chilled water set points

• Manage the usage of air side economizers

Page 11: Polargy Smart Containment

Two Sets of Gains:

1) Containment and 2) Control

CHH CCHH C

Baseline After Containment With Control

• No containment

• High degree of air mixing

• High inlet temperatures

• Cold aisle contained

• Higher ∆-T

• No change to CRAHs

• Controlled CRAHs

• ASHRAE inlet temperatures

• Increased return temperatures

Page 12: Polargy Smart Containment

Published Case Studies

LBNL

Fan speed reduction of 75%

12% reduction in cooling energy

Altera

⁰ ⁰

Altera

Server inlet variance reduced from 14⁰F to 2⁰F

12.5% energy reduction

Yahoo

Supply air temperature increased 21⁰F

21% reduction in cooling energy

Published by Accenture/Silicon Valley Leadership Group

These are not Polargy projects

Page 13: Polargy Smart Containment

• Energy savings from reduced fan speeds and lower demand on chilled water plant

Compelling ROI

chilled water plant

• Reduced heat related failures

• Power utility rebates

• More capacity out of the data center

Page 14: Polargy Smart Containment

Polargy, Inc.Polargy, Inc.Polargy, Inc.Polargy, Inc.256 Gibraltar Drive, Suite 155Sunnyvale, CA 94089888.816.8338