www.soyal.com.twV180807ACCESS CONTROL SYSTEM
255
0.0.0.0
255
192.168.1.171
3F
2F
1F
CH
1C
H2
CH1/CH2 support up to 8 units of controllers respectively
Broadcast Opening Doors with Fire Alarm System Linkage
AR-727CM-IO
ACCESS CONTROL SYSTEM
Ethernet / UDP Mode:Select【Sole or Any】AR-727CM linkage Sources by Access Controllers
CH1/CH2 RS485 Mode:Assign【Specified or All】Access Controllers to open by AR-727CM
Set up Access Controller to accept the “any” Fire Alarm linkage source to open the door when the fire occurs.
Set up Access Controller to accept the “sole” Fire Alarm linkage source to open the door when the fire occurs.
Specified Access Controllers Linkage - Input Node ID of Access Controllers in the blank column of Select Node ID of AR727CM-CH1/2
All Access Controllers Linkage – Input Number “255” in the first blank column ofSelect Node ID of AR727CM-CH1/2
Fire Alarm Control Panelsends Fire Signal
Serial Network Server & Converter
UDP / RS-485
A
B
A
B
HUB/Switch
www.soyal.com.twV180807ACCESS CONTROL SYSTEM
1 2 3
4
2 3
4
After entering Network Setting page, IPaddress could be changed if needed.
For First enter the setting page, the LoginAccount is needed. The default Login nameis admin and the password is not needed. (After login, the login Name and passwordcould be changed.)
Open IE Browser and input IP Address of 727CM (Default IP address is http://192.168.1.127)
Press “Update” Button to write the new IP address to devices and then enter the setting page again by inputting the new IP Address.
255
After the settings are completed, please press “Update” Button to save and write the newsettings to device.
If only the specified doors need to be unlockedautomatically when the fire occurs, pleaserespectively input the Node ID of Access Controllers
If all doors need to be unlocked automaticallywhen the fire occurs, please input Number “255” in the first blank Column of Select NodeID of AR727CM-CH1/2
After entering Channel Setting page, changethe status of Fire Alarm (DI0) Open Doorsfrom Disable (default) to Enable.1
2
3
1
2
3
4
1
2
3
4
4
192.168.1.171
After the settings are completed, please press “Update” Button to save and write the newsettings to device.
If only the specified doors need to be unlockedautomatically when the fire occurs, pleaserespectively set the Secondary DNS Serverof specified controllers to 727CM IP Address, then the specified controllers can accept the command from the Sole Fire Alarm LinkageSource to open the door.
If all doors need to be unlocked automaticallywhen the fire occurs, please set the SecondaryDNS Server of each controller to 0.0.0.0, then the controller can accept the commandfrom any Fire Alarm Linkage Source to open the door.
Open IE Browser and input IP Address ofE/V5 Access Controllers, enter Network Setting page.
1
2
3
4
192.168.1.171
0.0.0.0
255
Login AR-727CM and Change IP address
CH1/CH2 RS485 Mode:Assign【Specified or All】Access Controllers to open by AR-727CM
Ethernet/UDP Mode:Select【Sole or Any】AR-727CM linkage Sources by Access Controllers
1
UDP / RS485 Setting Procedure of BroadcastingOpening Doors with Fire Alarm System Linkage