34
1 POWER FACTOR CORRECTION POWER FACTOR CORRECTION MOHSIN RANA MOHSIN RANA BSET-01103100 BSET-01103100 University of Lahore University of Lahore

Mohsin rana

Embed Size (px)

DESCRIPTION

 

Citation preview

Page 1: Mohsin rana

11

POWER FACTOR CORRECTIONPOWER FACTOR CORRECTION MOHSIN RANAMOHSIN RANA

BSET-01103100BSET-01103100

University of Lahore University of Lahore

Page 2: Mohsin rana

22

OUTLINEOUTLINE

DEFINITIONDEFINITION

CAUSES OF LOW POWER FACTORCAUSES OF LOW POWER FACTOR

POWER FACTOR CORRECTIONPOWER FACTOR CORRECTION

ADVANTAGES OF POWER FACTOR CORRECTIONADVANTAGES OF POWER FACTOR CORRECTION

DISADVANTAGES OF LOW POWER FACTORDISADVANTAGES OF LOW POWER FACTOR

CONCLUSIONCONCLUSION

REFERENCESREFERENCES

Page 3: Mohsin rana

33

DEFINITION:DEFINITION:

Power factor (P.F) is the ratio between actual power to Power factor (P.F) is the ratio between actual power to the apparent power.the apparent power.

Actual power/Apparent power.Actual power/Apparent power.

P.F=Kw /Kva.P.F=Kw /Kva.

For a purely resistive load the power factor is unity. Active For a purely resistive load the power factor is unity. Active and reactive power are designated by P &Q respectively. and reactive power are designated by P &Q respectively. The average power in a circuit is called active power and The average power in a circuit is called active power and the power that supplies the stored energy in reactive the power that supplies the stored energy in reactive elements is called reactive power.elements is called reactive power.

Page 4: Mohsin rana

44

Active Power:: Also known as “real power” or simply “power.” Active power Also known as “real power” or simply “power.” Active power

is the rate of producing, transferring, or using electrical is the rate of producing, transferring, or using electrical energy. It is measured in watts and often expressed in energy. It is measured in watts and often expressed in kilowatts (KW) or megawatts (MW). The terms “active” or kilowatts (KW) or megawatts (MW). The terms “active” or “real” power are used in place of the term “power” alone to “real” power are used in place of the term “power” alone to differentiate it from “reactive power.differentiate it from “reactive power.

Apparent Power: The product of the voltage (in volts) and the current (in amperes). It comprises both active and reactive power . It is measured in “volt-amperes” and often expressed in “ kilovolt-amperes” (KVA) or “megavolt-amperes” (MVA).

Page 5: Mohsin rana

55

POWER FACTOR DEFINITIONPOWER FACTOR DEFINITION

Inductive loads cause the current to lag behind the Inductive loads cause the current to lag behind the voltage. The wave forms of voltage and current are then voltage. The wave forms of voltage and current are then "out of phase" with each other. The more out of phase "out of phase" with each other. The more out of phase they become then the lower the Power Factor. Power they become then the lower the Power Factor. Power Factor is usually expressed as Cos Phi. (Ø)Factor is usually expressed as Cos Phi. (Ø)

Page 6: Mohsin rana

66

Consider a canal boat being pulled by a horse. Consider a canal boat being pulled by a horse. If the horse could walk on water then the angle (Phi) Ø If the horse could walk on water then the angle (Phi) Ø

would be zero and COSINE Ø=1. Meaning all the horse would be zero and COSINE Ø=1. Meaning all the horse power is being used to pull the load. power is being used to pull the load. However the relative position of the horse influences the However the relative position of the horse influences the power. As the horse gets closer to the barge, angle Ø1 power. As the horse gets closer to the barge, angle Ø1 increases and power is wasted, but, as the horse is increases and power is wasted, but, as the horse is positioned further away, then angle Ø2 gets closer to positioned further away, then angle Ø2 gets closer to zero and less power is wasted.zero and less power is wasted.

Page 7: Mohsin rana

77

CAUSES OF LOW POWER FACTORCAUSES OF LOW POWER FACTOR

• A poor power factor can be the result of either a A poor power factor can be the result of either a significant phase difference between the voltage and significant phase difference between the voltage and current at the load terminals or it can be due to a high current at the load terminals or it can be due to a high harmonic content or distorted/discontinuous current harmonic content or distorted/discontinuous current waveform. Poor load current phase angle is generally the waveform. Poor load current phase angle is generally the result of Poor load current phase angle is generally the result of Poor load current phase angle is generally the result of an inductive load such as an induction motor result of an inductive load such as an induction motor power transformer, lighting ballasts, welder or induction power transformer, lighting ballasts, welder or induction furnace, Induction generators Wind mill generators and furnace, Induction generators Wind mill generators and high intensity discharge lightings.high intensity discharge lightings.

Page 8: Mohsin rana

88

CAUSES OF LOW POWER FACTORCAUSES OF LOW POWER FACTOR

• A distorted current waveform can be the result of a A distorted current waveform can be the result of a rectifier variable speed drive, switched mode power rectifier variable speed drive, switched mode power

supply, discharge lighting or other electronic loadsupply, discharge lighting or other electronic load. .

Page 9: Mohsin rana

99

POWER FACTOR CORRECTIONPOWER FACTOR CORRECTION

Power factor decreases with the installation of non resistive loads such as induction motors, Transformers.

Lighting ballasts and electronic equipments. Power factors can be corrected by using capacitors. These are rated in electrical units called VAR or KVAR.One VAR is equivalent to one volt of reactive power. VAR then are units of measurement for indicating just how much reactive power the capacitor will supply.

Page 10: Mohsin rana

1010

• As reactive power is usually measured in thousands

the letter K is used for thousand. the capacitor KVAR rating then shows how much reactive power the capacitor will supply. Each unit of the capacitor's KVAR will decrease the inductive reactive power demand.

Page 11: Mohsin rana

1111

POWER FACTOR CORRECTIONPOWER FACTOR CORRECTION

• Most loads on an electrical distribution system fall into Most loads on an electrical distribution system fall into one of three categories; resistive, inductive or capacitive. one of three categories; resistive, inductive or capacitive. In most plant, the most common is likely to be inductive. In most plant, the most common is likely to be inductive. Typical examples of this include transformers, fluorescent Typical examples of this include transformers, fluorescent lighting and AC induction motors. Most inductive loads lighting and AC induction motors. Most inductive loads use a conductive coil winding to produce an use a conductive coil winding to produce an electromagnetic field, allowing the motor to function.electromagnetic field, allowing the motor to function.

Page 12: Mohsin rana

1212

All inductive loads require two kinds of power to operate:All inductive loads require two kinds of power to operate: Active powerActive power (KW) - to produce the motive force (KW) - to produce the motive force Reactive powerReactive power (KVAR) - to energize the magnetic field (KVAR) - to energize the magnetic field The operating power from the distribution system is The operating power from the distribution system is

composed of both active (working) and reactive (non-composed of both active (working) and reactive (non-working) elements. The active power does useful work in working) elements. The active power does useful work in driving the motor whereas the reactive power only driving the motor whereas the reactive power only provides the magnetic field.provides the magnetic field.

Page 13: Mohsin rana

1313

POWER FACTOR CORRECTIONPOWER FACTOR CORRECTION

The amount of Power Capacitor KVAR required to correctThe amount of Power Capacitor KVAR required to correct A system to a desired Power Factor level is the difference A system to a desired Power Factor level is the difference

between the amount of KVAR in the uncorrected system between the amount of KVAR in the uncorrected system and the amount of desired KVAR in the corrected system. and the amount of desired KVAR in the corrected system. TheThe most efficient location for power factor capacitors is most efficient location for power factor capacitors is at the load. Capacitors work from the point of installation at the load. Capacitors work from the point of installation back to the generating source. Individual motor correction back to the generating source. Individual motor correction is not always practical, sometimes it is more practical to is not always practical, sometimes it is more practical to connect larger capacitors on the distribution bus or install connect larger capacitors on the distribution bus or install an automatic system at the incoming service along with an automatic system at the incoming service along with fixed capacitors at the load. fixed capacitors at the load.

Page 14: Mohsin rana

1414

KVAR CORRECTIONKVAR CORRECTION

• Capacitive Power Factor correction (PFC) is applied to

electric circuits as a means of minimising the inductive component of the current and thereby reducing the losses in the supply. The introduction of Power Factor Correction capacitors is a widely recognised method of reducing an electrical load, thus minimising wasted energy and hence improving the efficiency of a plant and reducing the electricity bill.

Page 15: Mohsin rana

1515

• It is not usually necessary to reach unity, i.e. Power Factor 1, since most supply companies are happy with a PF of 0.95 to 0.98.By installing suitably sized switched capacitors into the circuit, the Power Factor is improved and the value becomes nearer to 1 thus minimising wasted energy and improving the efficiency of a plant or power factor can be increased by synchronous motor or Synchronous generators.

Page 16: Mohsin rana

1616

POWER FACTOR CORRECTION POWER FACTOR CORRECTION METHODSMETHODS

Static Var Compensator(SVC)Static Var Compensator(SVC)

Fixed CapcitorsFixed Capcitors

Switch CapacitorsSwitch Capacitors

Synchronous CondensorsSynchronous Condensors

Static Synchronous Compensator(STATCOM)Static Synchronous Compensator(STATCOM)

Modulated power filter capacitor compensatorModulated power filter capacitor compensator

Page 17: Mohsin rana

1717

DETERMINING CAPACITOR VALUE

ExampleExample

Power Factor1=74%Power Factor1=74%

Actual Power=594 kwActual Power=594 kw

Interested to boost up=97% ,Power Factor2=97%Interested to boost up=97% ,Power Factor2=97%

Power Factor=KW/KVAPower Factor=KW/KVA

CosCos = kW / kVA = kW / kVA

= Cos-1 (PF1)= Cos-1 (PF1)

= Cos-1 (74%) =42.27 o= Cos-1 (74%) =42.27 o

Page 18: Mohsin rana

1818

The reactive power was about:The reactive power was about:

TanTan = kVAr / kW = kVAr / kW

kVAr = kW x tankVAr = kW x tankVAr = 594 kW x tan (42.27) = 540 kVArkVAr = 594 kW x tan (42.27) = 540 kVAr

If the power factor were increased to 97%, the reactive If the power factor were increased to 97%, the reactive power would be about:power would be about:

CosCos = kW / kVA = kW / kVA

= Cos-1 (PF2)= Cos-1 (PF2)

= Cos-1 (97%) = 14.07 o= Cos-1 (97%) = 14.07 o

kVAr = kW x tankVAr = kW x tan

kVAr = 594 kW x tan (14.07) = 149 kVArkVAr = 594 kW x tan (14.07) = 149 kVAr

Page 19: Mohsin rana

1919

Thus, the amount of capacitance required to boost Thus, the amount of capacitance required to boost power factor from 74% to 97% :power factor from 74% to 97% :

540 kVAr – 149 kVAr = 391 kVAr540 kVAr – 149 kVAr = 391 kVAr

So I recommended 400kvarSo I recommended 400kvar

Page 20: Mohsin rana

2020

POWER FACTOR MEASUREMENTPOWER FACTOR MEASUREMENT

Power factor can measure by using power factor meterPower factor can measure by using power factor meter

which is well known in power industry.which is well known in power industry.

Power factor can also be calculated by installing watt Power factor can also be calculated by installing watt meter along with the Ampere meter and volt meter by meter along with the Ampere meter and volt meter by using the power factor basic formula.using the power factor basic formula.

Power factor=Actual Power/ Apparent powerPower factor=Actual Power/ Apparent power

Page 21: Mohsin rana

2121

POWER FACTOR MEASUREMENTPOWER FACTOR MEASUREMENT

Page 22: Mohsin rana

2222

ADVANTAGES OF POWER FACTOR CORRECTION

Page 23: Mohsin rana

2323

Increase equipment life

Save on utility cost

Enhance equipment operation by improving voltage

Improve energy efficiency

Page 24: Mohsin rana

2424

Reduction in size of transformers, cables and switchgear Reduction in size of transformers, cables and switchgear in new installations.in new installations.

Delay costly upgrades.Delay costly upgrades.

Less total plant KVA for the same KW working power. Less total plant KVA for the same KW working power.

Improved voltage regulation due to reduced line voltage Improved voltage regulation due to reduced line voltage drop. drop.

Page 25: Mohsin rana

2525

POWER COST REDUCTION

• Utility companies in many areas include a penalty charge in the electrical rate for low power factor. The installation of power factor capacitors on the user's electrical distribution system eliminates the necessity of paying premium rates to

the utility company for poor power factor. .

Page 26: Mohsin rana

2626

• The savings the utility company derives in reduced

generation, transmission and distribution costs are passed on to the user in the form of lower electrical charges.  Three of the more common ways a utility charges a user for poor power factor are based on

Page 27: Mohsin rana

2727

KW demand with a trigger point typically between 85% KW demand with a trigger point typically between 85% and 95% and 95% KVA demand KVA demand KVAR demand KVAR demand When the utility uses either KVA demand or KVAR When the utility uses either KVA demand or KVAR demand as the basis for its penalty structure, all users demand as the basis for its penalty structure, all users pay a penalty, but those with high power factor pay a pay a penalty, but those with high power factor pay a much lower penalty or none at all.much lower penalty or none at all.

Page 28: Mohsin rana

2828

SYSTEM CAPACITY INCREASESYSTEM CAPACITY INCREASE

• By adding capacitors to the system, the power factor is By adding capacitors to the system, the power factor is improved and the KW capacity of the system is improved and the KW capacity of the system is increased. For example, a 1,000 KVA transformer with a increased. For example, a 1,000 KVA transformer with a 70% power factor provides 700 KW of power to the main 70% power factor provides 700 KW of power to the main bus. With the installation of capacitors so that the power bus. With the installation of capacitors so that the power factor is improved, say, to 90%, the KW capacity of the factor is improved, say, to 90%, the KW capacity of the system is increased to 900 KW. When a system power system is increased to 900 KW. When a system power factor is improved, the amount of reactive current flowingfactor is improved, the amount of reactive current flowing

Is lowered thus reducing transformer and distribution Is lowered thus reducing transformer and distribution circuit loads, and releasing system capacity.circuit loads, and releasing system capacity.

Page 29: Mohsin rana

2929

VOLTAGE IMPROVEMENT AND POWER VOLTAGE IMPROVEMENT AND POWER

LOSS REDUCTIONLOSS REDUCTION • System losses are also reduced through power factor System losses are also reduced through power factor

correction by reducing the total current and power in the correction by reducing the total current and power in the system. A 20% reduction in current will yield a 36% system. A 20% reduction in current will yield a 36% reduction in distribution system losses. In this situation, reduction in distribution system losses. In this situation, an energy savings of as much as 50% will be realized an energy savings of as much as 50% will be realized with the installation of power factor capacitors. with the installation of power factor capacitors.

In addition, power factor capacitors decrease the In addition, power factor capacitors decrease the

distribution system voltage drops and fluctuationsdistribution system voltage drops and fluctuations..

Page 30: Mohsin rana

3030

DISADVANTAGES OF LOW POWER DISADVANTAGES OF LOW POWER FACTORFACTOR

Increases heating losses in the transformers and Increases heating losses in the transformers and distribution equipments.distribution equipments.

Reduce plant life.Reduce plant life.

Unstabilise voltage levels.Unstabilise voltage levels.

Increase power losses.Increase power losses.

Upgrade costly equipments.Upgrade costly equipments.

Decrease energy efficiency.Decrease energy efficiency.

Increase electricity costs by paying power factor Increase electricity costs by paying power factor

surcharges.surcharges.

Page 31: Mohsin rana

3131

CONCLUSION

• By observing all aspects of the power factor it is clear that power factor is the most significant part for the utility Company as well as for the consumer. Utility company rid of from the power losses while the consumer free from low power factor penalty charges.

By installing suitably sized power capacitors into the circuit the Power Factor is improved and the value the Power Factor is improved and the value becomes nearer to 1 thus minimising line losses and becomes nearer to 1 thus minimising line losses and improving the efficiency of a plant. improving the efficiency of a plant.

Page 32: Mohsin rana

3232

REFERENCESREFERENCES

Electrical Power System Design and Analysis Electrical Power System Design and Analysis

by M.E.EI-Hawary.by M.E.EI-Hawary.

Power System Operations Power System Operations

by Robert H Miller.by Robert H Miller.

IEEE papersIEEE papers

www.ABB.comwww.ABB.com

BC Hydro (BC Hydro (www.bchydro.ca))

Page 33: Mohsin rana

VideoVideo

3333

Page 34: Mohsin rana

ANY QUESTIONANY QUESTION

3434