10
14th World Conference on Seismic Isolation, Energy Dissipation and Active Vibration Control of Structures September 9-11 2015 San Diego, Ca USA 1 DESIGN OF A 24-STORY DAMPED STEEL FRAME BASED ON CHINESE AND JAPANESE BUILDING CODES Demin FENG Technology Development Division, Fujita Corp. Ono 2025-1, Atsugi City, 243-0125, Japan [email protected] Hui XIA NPO Asia Construction Technology Promotion Organization Higashi Nippori 4-33-7-3F, Arakawa-ku, Tokyo 116-0014, Japan [email protected] Wenguang LIU Department of Civil Engineering, Shanghai Univ. No 149, Yan-Chang Road, 200072 Shanghai, China [email protected] ABSTRACT - In Japanese and Chinese building codes, a two-stage design philosophy, damage limitation (small earthquake, Level 1) and life safety (extreme large earthquake, Level 2), is adopted. It is very interesting to compare the design method of a damped structure based on the two building codes. In the Chinese code, in order to be consistent with the conventional seismic design method, the damped structure is also designed at the small earthquake level. The effect of damper systems is considered by the additional damping ratio concept. The design force will be obtained from the damped design spectrum considering the reduction due to the additional damping ratio. The additional damping ratio by the damper system is usually calculated by a time history analysis method at the small earthquake level. The velocity dependent type dampers such as viscous dampers can function well even in the small earthquake level. But, if steel damper is used, which usually remains elastic in the small earthquake, there will be no additional damping ratio achieved. On the other hand, a time history analysis is used in Japan both for small earthquake and extreme large earthquake level. The characteristics of damper system and ductility of the structure can be modelled well. An existing 24-story steel frame is modified to demonstrate the design process of the damped structure based on the two building codes. Viscous wall type damper and low yield steel panel dampers are studied as the damper system. Keywords: damper, dynamic response analysis, building code, damping ratio, energy absorption 1 INTRODUCTION In Japan and China, the application number of the damped building has been increased significantly. In Japan, there have been more than 1191 buildings in the end of 2013. But neither the design criteria of the damped buildings nor manufacturing inspection criteria of the dampers are covered in the building code. JSSI (2013) has published a manual book concerning the mechanism, design, fabrication, testing, quality control, and analytical modelling of various types of dampers, as well as design, construction, and analysis of damped buildings. On the other hand, the energy dissipation technology has been used widely in the high-rise buildings with the construction boom in China. Both the design criteria of the damped buildings and manufacturing inspection criteria of the

Design of a 24-story damped steel frame based on Chinese and Japanese building codes

  • Upload
    fujita

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

14th World Conference on Seismic Isolation, Energy Dissipation and Active Vibration Control of Structures

September 9-11 2015 San Diego, Ca USA

1

DESIGN OF A 24-STORY DAMPED STEEL FRAME BASED ON CHINESE

AND JAPANESE BUILDING CODES

Demin FENG

Technology Development Division, Fujita Corp.

Ono 2025-1, Atsugi City, 243-0125, Japan

[email protected]

Hui XIA

NPO Asia Construction Technology Promotion Organization

Higashi Nippori 4-33-7-3F, Arakawa-ku, Tokyo 116-0014, Japan

[email protected]

Wenguang LIU

Department of Civil Engineering, Shanghai Univ.

No 149, Yan-Chang Road, 200072 Shanghai, China

[email protected]

ABSTRACT - In Japanese and Chinese building codes, a two-stage design philosophy, damage limitation

(small earthquake, Level 1) and life safety (extreme large earthquake, Level 2), is adopted. It is very

interesting to compare the design method of a damped structure based on the two building codes. In the

Chinese code, in order to be consistent with the conventional seismic design method, the damped structure is

also designed at the small earthquake level. The effect of damper systems is considered by the additional

damping ratio concept. The design force will be obtained from the damped design spectrum considering the

reduction due to the additional damping ratio. The additional damping ratio by the damper system is usually

calculated by a time history analysis method at the small earthquake level. The velocity dependent type

dampers such as viscous dampers can function well even in the small earthquake level. But, if steel damper

is used, which usually remains elastic in the small earthquake, there will be no additional damping ratio

achieved. On the other hand, a time history analysis is used in Japan both for small earthquake and extreme

large earthquake level. The characteristics of damper system and ductility of the structure can be modelled

well. An existing 24-story steel frame is modified to demonstrate the design process of the damped structure

based on the two building codes. Viscous wall type damper and low yield steel panel dampers are studied as

the damper system.

Keywords: damper, dynamic response analysis, building code, damping ratio, energy absorption

1 INTRODUCTION

In Japan and China, the application number of the damped building has been increased significantly.

In Japan, there have been more than 1191 buildings in the end of 2013. But neither the design

criteria of the damped buildings nor manufacturing inspection criteria of the dampers are covered in

the building code. JSSI (2013) has published a manual book concerning the mechanism, design,

fabrication, testing, quality control, and analytical modelling of various types of dampers, as well as

design, construction, and analysis of damped buildings. On the other hand, the energy dissipation

technology has been used widely in the high-rise buildings with the construction boom in China.

Both the design criteria of the damped buildings and manufacturing inspection criteria of the

2

dampers have been well documented in the building code.

In this paper, the design flow chart and the features of the two building code on damped

buildings are summarized first. In both Japanese and Chinese building codes, a two-stage design

philosophy, damage limitation (small earthquake, Level 1) and life safety (extreme large earthquake,

Level 2), is adopted. In Japanese code, allowable stress elastic design is used in Level 1 and non-

linear design in Level 2 earthquake. In order to utilize the energy dissipation technology, the

designer has to do non-linear dynamic response analysis and the damped building has to be certified

by the Ministry. Usually, the damped building has better performance target than aseismic one. In

Chinese code, elastic design is used in Level 1 and specification design in Level 2. In accordance

with the aseismic design, the damped building is also designed at small earthquake level (Level 1)

where the earthquake load is decreased by considering the additional damping ratio contributed by

the dampers. But hysteric dampers like BRB or steel panel dampers will not yield in Level 1, so

only stiffness contribution will be considered. Since the response shape such as drift angle at Level

1 and Level 2 is different much, the damper’s performance cannot be evaluated well only basing on

the response values at Level 1. The performance target is set the same as the aseismic one usually in

China.

An existing 24-story steel frame is modified to demonstrate the design process of the damped

structure based on the two building codes. Velocity dependent type viscous wall type damper and

hysteric type low yield steel panel dampers are studied as the damper system. The response values

and energy absorption are compared.

2 DAMPED STRUCTURE DESIGN IN CHINESE BUILDING CODE

The damped structure design method is adopted in the building code GB50011-2001 at first,

and then updated in GB50011-2010. The manufacturing inspection criteria of the dampers are

covered in the code JG/T209-2012. JGJ 297-2013 gives detailed technical specifications of damped

structure design and manufacturing inspection criteria of the dampers. The damped structure design

method based on the building code GB50011-2010 is summarized here.

The limit state design concept is adopted in the aseismic design. The response values

calculated from Level 1 are combined by various factors and checked with the design strength of

materials. Specification design is conducted in Level 2 to meet the requirements of ductility and

deformation capacity. The response spectrum analysis method is usually used to design. There are

four segments in the design response spectrum which are combined functions of the zone factor, the

site class and the response reduction factor as shown in Eq. (1) and Fig. 1. For design of a damped

structure, the earthquake load is decreased by considering the additional damping ratio contributed

by the dampers. The calculation of the additional damping ratio is shown in Eq. (2).

0.65)]5(2.0[

5)(

1.0

1.0)1.0

45.045.0(

)(

max12

max2

max2

max2

TTTT

TTTT

T

TT

TT

g

gg

gg

g

g

(1)

Where, max: seismic zone factor;

: spectrum shape coefficients;

: response reduction factor defined in Eq. (A.1)

Tg: characteristic period related to the site soil profile;

: effective damping ratio of the damped structure.

3

63.0

05.09.0

0,324

)05.0(02.0 11

(A.1)

55.0,6.108.0

05.01 22

)4/(1

n

j

scjd WW (2)

where, d: additional damping ratio of dampers;

Wcj: total energy dissipated by dampers;

Ws: total input earthquake energy;

The additional damping ratio of dampers is usually calculated by the average response values

from multiple Level 1 input motions using elastic time history analysis. In addition to Eq.(2), it can

be calculated also by comparing response values such as top displacement value, story drift angle,

shear force or resistant moment of base story. The effective damping of the damped structure is a

sum of the additional damping ratio with the structure damping ratio, which is usually 5% for RC

structure, 3% for steel structure. The pseudo velocity spectra with damping ratio of 5%, 8% and

12% were calculated from Eq.(1) and shown in Fig.1, where Intensity 8, Tg=0.4s were used. It can

be seen, the response pseudo velocity value increased with the period which usually have a constant

value in other building codes. The reduction due to the damping ratio is smaller (Feng, 2006).

Figure 1 - The pseudo velocity spectra with damping ratio of 5%, 8% and 12% (Intensity 8,

Tg=0.4s)

3 DAMPED STRUCTURE DESIGN IN JAPANESE BUILDING CODE

In Japan, there have been more than 1191 buildings in the end of 2013. But neither the design

criteria of the damped buildings nor manufacturing inspection criteria of the dampers are covered in

the building code. JSSI (2013) has published a manual book concerning the mechanism, design,

fabrication, testing, quality control, and analytical modelling of various types of dampers, as well as

design, construction, and analysis of damped buildings. AIJ (2014) recommended provisions for

steel dampers such as BRB and panel dampers.

In Japanese code, allowable stress elastic design is used in Level 1 and non-linear design in

Level 2 earthquake. In order to utilize the energy dissipation technology, the designer has to do

non-linear dynamic response analysis and the damped building has to be certified by the Ministry.

4

The number of damped buildings and classification of dampers used are shown in Fig.2 (JSSI,

2015). The hysteric damper is most popular one due to its cheap cost. However, in the Great East

Japan (Tohoku) Earthquake on March 11, 2011, there observed ground motions having strong long

period and long duration time. The velocity dependent type dampers such as oil damper (bi-linear

property with velocity) and viscous damper increased more and more.

The performance target of a damped building is usually higher than the aseismic one as

shown in Table 1. Moreover it is important to check the cumulative deformation on hysteric type

dampers.

Figure 2 - The number of damped buildings and classification of dampers (JSSI, 2015).

Table 1 - The performance target of a damped building

Level 1 Level 2

Ground

motions

Three motions compatible with

design spectrum and three

recorded motions with peak

velocity normalized to 25cm/s

Three motions compatible with

design spectrum and three recorded

motions with peak velocity

normalized to 50cm/s

Super-

structure

Drift angle < 1/300

(aseismic: 1/200)

stress ≦ short term allowable

strength

Drift angle < 1/150

(aseismic: 1/100)

Story ductility factor < 2

Member ductility factor < 4

Hysteric

damper

Checking cumulative deformation

4 A DAMPED STRUCTURE MODEL

A 24-story damped steel structure (Feng, 2013) is analysed to understand the design

procedure of both building codes. Two types of damper system: velocity dependent viscous wall

damper and hysteric low yield steel panel damper are used (JSSI, 2013).

5

4.1 Structure model

For dynamic response analysis, the super-structure was modelled as a nonlinear bending-shear

type multiple-degree-of-freedom system. The parameters used in the model were obtained from a

static pushover analysis and shown in Table 2. In Fig.3 are shown typical story shear model

parameters comparing with the pushover analysis results, which agreed very well. The bending

spring was assumed as elastic. The shear spring model was modelled as tri-linear or bi-linear

depending on the column materials. The CFT columns in 1st and 2

nd stories are modelled as tri-

linear, while the steel columns above 3rd

story as modelled as bi-linear model. By using the bending

shear model, the shear deformation relating with dampers can be calculated directly. A varying-

stiffness proportional damping system was assumed in the time history analysis. The damping ratio

for bending spring was assumed as 0.02, while the damping ratio for shear spring was assumed as

0.02 corresponding 1st natural period. The three natural periods were obtained from the mode

analysis as 3.292s, 1.107s and 0.659s, respectively

To limit analysis cases, only one synthetic input motion was used which is compatible with

Chinese design spectrum (Intensity 8, Tg=0.4s) (Feng, 2006). The peak acceleration was 0.397g.

Time duration and time interval were 120s and 0.01s, respectively. The synthetic motion was used

as Level 2 motion directly in both building codes. For Chinese Level 1 motion, the peak

acceleration value was normalized to 0.07g. The pseudo velocity spectra of both Level 1 and Level

2 motion are compared with Chinese and Japanese design spectra in Fig.4.

40x103

30

20

10

0

Sh

ea

r fo

rce

(kN

)

6050403020100

Displacement (mm)

1F

10F

15F

20F

3F

Figure 3 - The story shear model parameters comparing with pushover analysis results

Figure 4 - The pseudo velocity spectra of both Level 1 and Level 2 motion comparing with Chinese

and Japanese design spectra.

6

Table 2 – Parameters of the super-structure bending-shear MDOF model

Floor Mass Height TypeBending

stiffness

Elastic

stiffnessRatio of Ratio of Crack load Yield load

Kr K1 K2/K1 K3/K1 Qc Qy

(t) (m) (KN・m/rad) (KN/mm) (kN) (kN)

RF 216 84.75 Bilinear 1.508E+08 137.9 - 0.324 - 1794

23F 1067 80.55 Bilinear 2.298E+09 403.1 - 0.460 - 5037

22F 1078 76.25 Bilinear 5.123E+09 660.1 - 0.454 - 7418

21F 1073 72.95 Bilinear 5.654E+09 697.7 - 0.454 - 9370

20F 1073 69.65 Bilinear 5.969E+09 723.1 - 0.447 - 11215

19F 1080 66.35 Bilinear 7.449E+09 768.1 - 0.426 - 12922

18F 1083 63.05 Bilinear 7.537E+09 788.0 - 0.428 - 14507

17F 1085 59.75 Bilinear 7.555E+09 802.5 - 0.398 - 16091

16F 1085 56.45 Bilinear 7.556E+09 805.1 - 0.304 - 17499

15F 1087 53.15 Bilinear 7.537E+09 802.1 - 0.202 - 18977

14F 1086 49.85 Bilinear 7.506E+09 801.3 - 0.131 - 20202

13F 1087 46.55 Bilinear 7.519E+09 811.7 - 0.091 - 21173

12F 1088 43.25 Bilinear 7.469E+09 816.5 - 0.065 - 22125

11F 1088 39.95 Bilinear 7.420E+09 831.0 - 0.048 - 23053

10F 1091 36.65 Bilinear 7.351E+09 845.7 - 0.038 - 23892

9F 1091 33.35 Bilinear 7.283E+09 851.3 - 0.032 - 24632

8F 1091 30.05 Bilinear 7.216E+09 858.8 - 0.029 - 25345

7F 1094 26.75 Bilinear 7.819E+09 884.3 - 0.027 - 25972

6F 1097 23.45 Bilinear 7.736E+09 893.9 - 0.028 - 26419

5F 1098 20.15 Bilinear 7.952E+09 919.5 - 0.031 - 26722

4F 1098 16.85 Bilinear 7.879E+09 1001.7 - 0.038 - 26629

3F 1098 13.55 Bilinear 7.773E+09 1574.9 - 0.062 - 23692

2F 1669 10.25 Trilinear 1.503E+10 2518.0 0.284 0.044 5238 28847

1F 1787 5.25 Trilinear 1.540E+10 4766.5 0.330 0.060 5912 29519

K2: Stiffness after crack; K3: Stiffness after yield

4.2 Dampers

Two types of damper system: velocity dependent viscous wall damper and hysteric low yield

steel panel damper are used (JSSI, 2013). The viscous wall damper is modelled by Maxwell model.

The steel panel damper is modelled by bi-linear model.

5 DYNAMIC RESPONSE ANALYSIS RESULTS

Dynamic response analysis results of Level 1 and Level 2 motions are summarized following

mainly Chinese code. In Level 1 analysis, the procedure to calculate the additional damping ratio of

dampers is demonstrated. In Level 2 analysis, the performance target is set to story drift angle

required by both codes, and the story ductility factor following Japanese code.

5.1 Response Analysis of the Aseismic Model

Dynamic response analyses were carried out on the aseismic model at Level 1 and Level 2

input motions. The story drift angle and energy absorption diagram at Level 2 are shown in Fig.5.

The maximum of story drift angle at Level 1 was 1/375, smaller than code requirement of 1/250.

The maximum of story drift angle at Level 2 was 1/42, larger than code requirement of 1/50. From

the energy absorption diagram in Fig.5, it can be understood that at Level 2 input, the super-

7

structure became yielding and absorbed half of the input energy. Thus the story ductility factor was

so much high as 5.1 in 3rd

story.

RF

20F

15F

10F

5F

1F

Flo

or

30x10-320100

Drift angle (rad.)

1/100

Level 1 Level 2

60x103

50

40

30

20

10

0E

ner

gy

(k

N m

)

120100806040200

Time (s)

Ei

Ed

Ek

Es

Aseismic, Level 2

Ei: input energy; Ed: energy absorbed by structure’s damping;

(a) Story drift angle Es: energy absorbed by structure’s plasticity; Ek: kinetic energy

(b) Energy absorption diagram at Level 2 input

Figure 5 - The story drift angle and energy absorption diagram at Level 2 input

The performance target of the damped structure at Level 2 input was set as: the story drift

angle less than 1/100; the story ductility factor less than two.

In Chinese code, the dampers’ effect is evaluated at Level 1 input. It is usually better to place

dampers according the response results at Level 1 input. In this study, the performance target of the

damped structure was set at Level 2 input, so the dampers’ planning was carried out based on the

Level 2 response results. The dampers planning are shown in Table 3.

Table 3 – The dampers planning

Type Number C(kN/[m/s])K(KN/mm) Type Number K(kN/mm) Fy(KN) β

14F VFD-NL×2000×60 3 14091 1410 MYD-S×2000×2.0 1 1048 2099 0.01

13F VFD-NL×2000×60 3 14091 1410 MYD-S×2000×2.0 1 1048 2099 0.01

12F VFD-NL×2000×60 3 14091 1410 MYD-S×2000×2.0 1 1048 2099 0.01

11F VFD-NL×2000×60 3 14091 1410 MYD-S×2000×2.0 1 1048 2099 0.01

10F VFD-NL×2000×60 3 14091 1410 MYD-S×2000×2.0 1 1048 2099 0.01

9F VFD-NL×2000×60 3 14091 1410 MYD-S×2000×2.0 1 1048 2099 0.01

8F VFD-NL×2000×60 3 14091 1410 MYD-S×2000×2.0 2 2096 4198 0.01

7F VFD-NL×2000×60 3 14091 1410 MYD-S×2000×2.0 2 2096 4198 0.01

6F VFD-NL×2500×60 4 23484 2360 MYD-S×2000×2.0 2 2096 4198 0.01

5F VFD-NL×2500×60 4 23484 2360 MYD-S×2000×2.0 2 2096 4198 0.01

4F VFD-NL×2500×60 4 23484 2360 MYD-S×2000×2.0 2 2096 4198 0.01

3F VFD-NL×2500×60 4 23484 2360 MYD-S×2000×2.0 3 3144 6297 0.01

2F VFD-NL×2000×60 3 14091 1410 MYD-S×2000×2.0 1 1048 2099 0.01

1F MYD-S×2000×2.0 1 1048 2099 0.01

Low yield steel panel damperViscous wall damperFloor

F=CV0.45

8

5.2 Response Analysis of the Damper Structures at Level 1 Input

Response analysis results of the damper structures at Level 1 input are shown in Fig.6. In the

case of viscous wall damper, all response results: story drift angle, story shear force coefficient and

floor acceleration became smaller. In the case of steel panel damper, the dampers did not yield at

Level 1 input and contributed stiffness to the main structure. The natural periods of the damped

structure with steel dampers became shorter as: 2.452s, 0.945s and 0.557s. Thus, the story drift

angle became smaller, while shear force coefficient and floor acceleration became larger.

The energy absorption diagram of the damped structure with viscous damper is shown in

Fig.7. From Eq.(2), the additional damping ratio of the dampers was calculated as 5.5%.

0.160.120.080.040.00

Response acc. (g)

RF

20F

15F

10F

5F

1F

3.0x10-32.01.00.0

Drift angle (rad.)

0.160.120.080.040.00

Shear force coefficient

Aseismic

Viscous

Steel

Figure 6 - Response analysis results of the damper structures at Level 1 input

1400

1200

1000

800

600

400

200

0

En

erg

y (

kN

m)

120100806040200

Time (s)

Ei

Ed

EkEs

Em

Viscous damperLevel 1

Ei: input energy; Em: energy absorbed by viscous dampers; Ed: energy absorbed by structure’s damping;

Es: energy absorbed by structure’s plasticity; Ek: kinetic energy

Figure 7 - The energy absorption diagram of the damped structure with viscous damper

9

5.3 Response Analysis of the Damper Structures at Level 2 Input

Response analysis results of the damper structures at Level 2 input are shown in Fig.8. In both

cases of viscous wall damper and steel panel damper, the performance target was satisfied. The

story drift angle was less than 1/100, and the story ductility factor was 1.6.

In the case of viscous wall damper, all response results: story drift angle, story shear force

coefficient and floor acceleration became smaller like the response results at Level 1 input. The

energy absorption diagram of the damped structure with viscous damper is shown in Fig.9. From

Eq.(2), the additional damping ratio of the dampers was calculated as 6.1% for reference.

In the case of steel panel damper, although not good as the viscous wall damper, all response

results became smaller than the aseismic model.

From Table 3, it can be seen for the same performance target, the amount of viscous wall

dampers was more than that of steel panel dampers. The natural period of the model is about 3.3s,

thus the story velocity was small. The damping force by the viscous wall dampers was 60% of the

rating damping force. In Table 4, is shown the shear force ratio between dampers and main

structures. Although the number of steel panel dampers was fewer, the ratio was larger.

0.40.30.20.10.0

Response acc. (g)

RF

20F

15F

10F

5F

1F

25x10-320151050

Drift angle (rad.)

1/100 0.40.30.20.10.0

Shear force coefficient

Aseismic

Viscous

Steel

Figure 8 - Response analysis results of the damper structures at Level 2 input

60x103

50

40

30

20

10

0

En

erg

y (

kN

m)

120100806040200

Time (s)

Ei

Ed

EkEs

Em

Viscous damper, Level 2

120100806040200

Time (s)

Ei

Ed

EkEs

Eh

Steel damper, Level 2

Ei: input energy; Em, Eh: energy absorbed by dampers; Ed: energy absorbed by structure’s damping;

Es: energy absorbed by main structure’s plasticity; Ek: kinetic energy

Figure 9 - The energy absorption diagram of the damped structure at Level 2 input

10

Table 3 – The shear force ratio between dampers and main structure

Floor Viscous Steel

14F 0.073 0.111

13F 0.065 0.105

12F 0.058 0.100

11F 0.056 0.093

10F 0.059 0.089

9F 0.062 0.085

8F 0.068 0.181

7F 0.070 0.174

6F 0.126 0.168

5F 0.133 0.164

4F 0.134 0.161

3F 0.198 0.253

2F 0.092 0.070

1F - 0.065

SUM 1.194 1.819

6 CONCLUSIONS

In this paper, the design flow chart and the features of the Chinese and Japanese building code

on damped buildings were summarized. An existing 24-story steel frame was modified to

demonstrate the design process of the damped structure. Velocity dependent type viscous wall type

dampers and hysteric type low yield steel panel dampers were studied as the damper system. The

response values and energy absorption diagram were compared.

The viscous wall type dampers had better performance and reduced responses of the main

structure at both Level 1 and Level 2 inputs. The additional damping ratios of the dampers based on

Chinese code were 5.5% at Level 1 input and 6.1% at Level 2 input, respectively.

The steel panel dampers contributed stiffness at Level 1 input and had good performance at

Level 2 input.

The optimization of damper planning should be carried out based on the response values at

Level 2 input.

References

Architectural Institute of Japan (AIJ) [2014], Recommended provisions for seismic damping systems

applied to steel structures (in Japanese).

Feng, D., etc. [2006] “A comparative study of seismic isolation codes worldwide (Part I, II)”, 1st

ECEES, Geneva, No.63, No.66,

Feng, D., etc. [2013] “Response analysis on a 24-story damped steel structure”, 10th

Japan-China

building structure technology symposium, Nanjing (in Chinese)

Japan Society of Seismic Isolation (JSSI) [2013], Manual for design and construction of passively-

controlled Buildings (3rd

edition) (in Japanese).

Japan Society of Seismic Isolation (JSSI) [2015], Annual meeting report (in Japanese).

Ministry of Construction, P.R.China [2010], Code for seismic design of buildings, GB50011-2010

(in Chinese).

Ministry of Construction, P.R.China [2012], Dampers for vibration energy dissipation of buildings,

JG/T209-2012 (in Chinese).

Ministry of Construction, P.R.China [2013], Technical specification for seismic energy dissipation

of buildings, JGJ 297-2013 (in Chinese).