Planning, Development & Facilities 349 Magnolia Avenue
Glendale, California 91204 Tel: 818.507.0201 Fax: 818.507.4911
Project Name: Jefferson ES-12 Classroom Bldg. DSA No: A#:03-114361 , File#:19-41
District PO No: District Contract No: 113-15/16
REQUEST FOR INFORMATION (RFI)
To: Armond Mailan
From:Chalmers Construction Services Inc.
Required by: Ara Baghdasarians
RFI No. 076
Date: 12/12/16
Answered:
REFERENCE:
Drawing(s) - Specification(s) _______________ Page(s) ___
PROPOSED SOLUTIS:As the material of steel is same for both achor bolts and base plates so it is suggested to eliminates the nut and just use the 1" washer plate including the weld all around the washer and on top of it.
DISTRICT REPRESENTATIVE’S ADDITIONAL INFORMATION:
ARCHITECT’S RESPONSE:
*This response was provided FOR INFORMATION ONLY with no effect to the contract.*This response is a CLARIFICATION of the contract. (NO COST or TIME EFFECT)*This response is a MINOR CHANGE to the contract with no effect to the contract cost or time. (NO COST or TIMEEFFECT) **This response CHANGES the contract with an anticipated effect to contract cost and/or time. (COST/TIME EFFECT) The Contractor is to prepare a Change Order Proposal before proceeding.
* This does not modify contract cost or time. If the recipient believes that the RFI has any effect on contract cost and/ortime, the recipient shall respond in writing in accordance with Contract provisions.
CONTRACTOR’S REQUEST:
As the installed anchor bolts on grid line 2 ( Between gridlines B-E ) are +/- 1" lower
than proposed elevation so It will not be enough threads out for anchor bolts after
installing the washers and nuts.
Same situation for few other base plate's anchors on different locations which It will
not be enough threads out after installing the washer and nut. ( Please Advice ) Based
on this also the 2" indicated non-shrink grout underneath the base plate will be 3".
( PLease confirm )
**See attached pictures**
>837 North Spring Street, Third Floor, Los Angeles, CA 90012 323 475 8075 / nacarchitecture.com
Seattle / Spokane / Los Angeles
January 09, 2017 Issued as response attachment to RFI #76 Re: GUSD Jefferson ES ORG response to RFI #76 DSA A#03-114361 Architect’s Response to RFI #076 DSA has approved the submitted CCD#010 which is now attached to the response to RFI#076. The CCD#010 addresses the grout and anchor bolt issues, but additional documentation for clarity has been provided as noted below. Testing shall be coordinated with the project Testing Lab and in keeping with Section #4 of DSA IR 17-8 (issued by DSA on 01-12-11). Below is from email of 12/23/2016, from Brad Brewer, NAC
• RFI#76: Low anchor bolts and grouting and shear lug o Chalmers confirmed that they will utilize “…we will use Sika 328 for locations that the grout
thickness is more than 2” “ o Chalmers confirmed the coupler nut solution is preferred, and steel fabricator provided
recommendation of coupler model number. Please confirm coupler meets ATSM parameters set in the DSA Approved CCD#010 (cut sheet documents for coupler provided by Chalmers are included in RFI#076 reference materials of response)
o Chalmers confirmed that the Steel Fabricator has enough tolerance, in keeping with the Contract Documents, to account for anchor bolts that are 1/8” short. (email from Chalmers is provide by Chalmers are included in RFI#076 reference materials of response)
NAC Response to RFI#076, as coordinated with KPFF Structural and discussed with GUSD, BPI and Chalmers. \\nac\100\it\nac-forms\2016-form-updates\don potts\new forms\word\general\letterhead.docx
RFI#076 response from NAC 01/09/2017
26
APPROVED DIV. OF THE STATE ARCHITECT
LOS ANGELES REGIONAL OFFICE
SS FLS AC
DATE
APPROVED DIV. OF THE STATE ARCHITECT
LOS ANGELES REGIONAL OFFICE
lzeitoun
DATE 01/05/2017
RFI#076 response from NAC 01/09/2017
SSK8
SSK8
SSK8
<ASREVISED>
12-28-2016 CCD-010A10
10
10
10
CCD-A010
APPROVED DIV. OF THE STATE ARCHITECT
LOS ANGELES REGIONAL OFFICE
SS FLS AC
DATE
APPROVED DIV. OF THE STATE ARCHITECT
LOS ANGELES REGIONAL OFFICE
lzeitoun
DATE 01/05/2017
RFI#076 response from NAC 01/09/2017
<ASREVISED>
SSK8
SSK10
12-28-2016 CCD-010A
10
10
CCD-A010
APPROVED DIV. OF THE STATE ARCHITECT
LOS ANGELES REGIONAL OFFICE
SS FLS AC
DATE
APPROVED DIV. OF THE STATE ARCHITECT
LOS ANGELES REGIONAL OFFICE
lzeitoun
DATE 01/05/2017
RFI#076 response from NAC 01/09/2017
<ASREVISED>
SSK8
SSK8
SSK10
SSK10
12-28-2016 CCD-010A
10
10
10
10
10 CCD-A010
APPROVED DIV. OF THE STATE ARCHITECT
LOS ANGELES REGIONAL OFFICE
SS FLS AC
DATE
APPROVED DIV. OF THE STATE ARCHITECT
LOS ANGELES REGIONAL OFFICE
lzeitoun
DATE 01/05/2017
RFI#076 response from NAC 01/09/2017
DSA FILE NUMBER: 1941DSA APPLICATION NUMBER: 03114363PROJECT NAME: Jefferson ES ORG
SSK008REFERENCE DRAWING 1/S610
NEW DETAILDATE: 12.28.2016
CCD 010
2" M
IN T
O 4
" MA
X
SSK008
6" M
IN T
O 8
"M
AX
EM
BE
D
1 1/
2" M
IN
SSK009 ROD COUPLER WHERE TOP OF THREADED
ROD HAS LESS THAN 0" OF PROJECTIONTHROUGH NUT AT TOP OF BASE PLATE
NTS
CCD-A010
APPROVED DIV. OF THE STATE ARCHITECT
LOS ANGELES REGIONAL OFFICE
SS FLS AC
DATE
APPROVED DIV. OF THE STATE ARCHITECT
LOS ANGELES REGIONAL OFFICE
lzeitoun
DATE 01/05/2017
RFI#076 response from NAC 01/09/2017
DSA FILE NUMBER: 1941DSA APPLICATION NUMBER: 03114363PROJECT NAME: Jefferson ES ORG
SSK009REFERENCE DRAWING 2/S618
NEW DETAILDATE: 12.28.2016
CCD 010
NOTES:1. SEE 1/S618 FOR BALANCE OF INFORMATION NOT SHOWN.
2" M
IN, 3
" MA
X
1" MAXTYP
NONSHRINKHISTRENGTHGROUT
SHORT ASTM A354 GRADEBD ANCHOR ROD PER 1/S618
T.O. FOUNDATIONPER PLAN
CHIPOUT AND SOLIDGROUT
BRACED FRAMEBASE PLATE
ASTM A563 DHCOUPLING NUT
EQ
EQ
ASTM A354 GRADEBD THREADED RODTO MATCH DIA OFSHORT ROD BELOW
BRACED FRAME BASE ANCHOR ROD EXTENSION
CCD-A010
APPROVED DIV. OF THE STATE ARCHITECT
LOS ANGELES REGIONAL OFFICE
SS FLS AC
DATE
APPROVED DIV. OF THE STATE ARCHITECT
LOS ANGELES REGIONAL OFFICE
lzeitoun
DATE 01/05/2017
RFI#076 response from NAC 01/09/2017
DSA FILE NUMBER: 1941DSA APPLICATION NUMBER: 03114363PROJECT NAME: Jefferson ES ORG
SSK010REFERENCE DRAWING 5/S600
NEW DETAILDATE: 12.28.2016
CCD 010
NOTES:1. SEE 5/S600 FOR BALANCE OF INFORMATION NOT SHOWN.
2" M
IN, 3
" MA
X
1" MAXTYP
NONSHRINKHISTRENGTHGROUT
SHORT ASTM A307 HEXHEAD ANCHOR BOLT PER5/S600
T.O. FOUNDATIONPER PLAN
CHIP OUT AND SOLIDGROUT
COLUMN BASEPLATE
ASTM A563 ACOUPLING NUT
EQ
EQ
ASTM A36ALLTHREAD RODTO MATCH DIA OFHEX HEAD ANCHORBOLT BELOW
GRAVITY COLUMN BASE ANCHOR ROD EXTENSION
CCD-A010
APPROVED DIV. OF THE STATE ARCHITECT
LOS ANGELES REGIONAL OFFICE
SS FLS AC
DATE
APPROVED DIV. OF THE STATE ARCHITECT
LOS ANGELES REGIONAL OFFICE
lzeitoun
DATE 01/05/2017
RFI#076 response from NAC 01/09/2017
From: Ara BaghdasarianTo: Bradford BrewerCc: [email protected]: Anchor boltsDate: Wednesday, December 14, 2016 1:36:46 PMAttachments: IMG_0749-14-12-16-09-07.png
Hello Brad,Please disregard anchors that are low 1/8”. After we sent you previous email, I talked to steel suband he told me that he has enough tolerance to adjust the 1/8”. So top of nut will be flush withanchor.Three steel plates on Grid line 2 are the ones that needed to be fix. Thank you, Sincerely, Ara BaghdasarianChalmers Construction Services Inc2600 Foothill Blvd. Suite 304La Crescenta CA 91214Office 818-957-4521Fax 818-957-4223Cell 818-220-2641
RFI#076 Reference Materials: Provided by Chalmersvia email 12/14/2016
12/20/16, 2(38 PMNut Compatibility Chart - Portland Bolt
Page 1 of 2http://www.portlandbolt.com/technical/nut-compatibility-chart/
Nut Compatibility Chart
Grade of Bolt Surface Finish Nominal Size Inches
A563 Grade and ANSI Nut Style
Recommended Suitable
Hex Heavy Hex Hex Heavy Hex
A307 Grade A & C Any
⁄ to 1 ⁄ A B,D,DH A,B,C,D,DH,DH3
>1 ⁄ to 2 A A C,D,DH,DH3
>2 to 4 A C,D,DH,DH3
A307 Grade B Any
⁄ to 1 ⁄ A B,D,DH A,B,C,D,DH,DH3
>1 ⁄ to 2 A A
>2 to 4 A
A325 Type 1Plain ⁄ - 1 ⁄ C C3,D,DH,DH3
Galvanized ⁄ - 1 ⁄ DH
A325 Type 3 Plain ⁄ - 1 ⁄ C3 DH3
A354 Grade BC
Plain⁄ to 1 ⁄ C D,DH C3,D,DH,DH3
>1 ⁄ to 4 C C3,D,DH,DH3
Galvanized⁄ to 1 ⁄ DH
>1 ⁄ to 4 DH
A354 Grade BD Plain⁄ to 1 ⁄ DH DH D,DH,DH3
>1 ⁄ to 4 DH DH3
A449
Plain⁄ to 1 ⁄ B D,DH B,C,C3,D,DH,DH3
>1 ⁄ to 3 A C,C3,D,DH,DH3
Galvanized⁄ to 1 ⁄ DH D,DH D
>1 ⁄ to 3 DH D
A490 Type 1 Plain ⁄ - 1 ⁄ DH DH3
A490 Type 3 Plain ⁄ - 1 ⁄ DH3
A687Plain ⁄ - 3 D DH,DH3
Galvanized ⁄ - 3 DH
⁄ to 1 ⁄ A B,D,DH A,B,C,D,DH,DH3
14
12
12
14
12
12
12
12
12
12
12
12
14
12
12
14
12
12
14
12
12
14
12
12
14
12
12
12
12
12
12
58
58
12
12
[email protected](800) 547-6758
RFI#076 Reference Materials: Provided by Chalmersvia email 12/14/2016
12/20/16, 2(38 PMNut Compatibility Chart - Portland Bolt
Page 2 of 2http://www.portlandbolt.com/technical/nut-compatibility-chart/
F1554 Grade 36 Any >1 ⁄ to 4 A C,D,DH,DH3
F1554 Grade 55Plain
⁄ to 1 ⁄ A B,D,DH A,B,C,D,DH,DH3
>1 ⁄ to 4 A C,D,DH,DH3
Galvanized ⁄ to 4 A C,D,DH,DH3
F1554 Grade 105Plain
⁄ to 1 ⁄ D DH,DH3
>1 ⁄ to 3 DH DH3
Galvanized ⁄ to 3 DH DH3
1. The availability of A563 grade DH nuts in nominal sizes 3/4″ and larger is very limited and generally availableonly on special orders of 50,000 or more. For smaller quantities, ASTM A194 grade 2H should be considered.
ASTM A194 Nut Compatibility ChartGrade of Bolt A194 Heavy Hex Nut Grade
A193 Grade B7 2H or 4 or 7
A193 Grade B8 (Class 1 and 2) 8
A193 Grade B8M (Class 1 and 2) 8M
A320 Grade L7 4 or 7
A320 Grade B8 (Class 1 and 2) 8
A320 Grade B8M (Class 1 and 2) 8M
For Class 2 stainless steel grades, strain hardened nuts available as a supplementary requirement
12
12
12
12
12
12
12
12
12
RFI#076 Reference Materials: Provided by Chalmersvia email 12/14/2016
12/20/16, 2(38 PMHex Coupling Nuts - Portland Bolt
Page 1 of 3http://www.portlandbolt.com/products/nuts/hex-coupling/
Related ProductsSleeve NutsTurnbucklesWashers
Related LinksCoupling Nut ThreadEngagementGalvanized NutsTapped OversizeCoupling Nut Grades
A194 A563 F594
Hex couplers are used to connect two pieces of threaded material. Hex andheavy hex couplers are threaded right hand. If a right hand-left hand coupler isneeded, consider using a sleeve nut.
See our nut compatibility chart to determine the compatible hex coupler for aspecific grade of bolt. Since hot-dip galvanizing typically adds 2.2 to 5 mils ofthickness to the threaded portion of a fastener, galvanized couplers are tappedoversize to compensate for the corrosion resistant coating on the bolts.
StockDiameters: 1/2″ – 1″Origin: Domestic and importFinish: Plain and hot-dip galvanizedGrades: A563 (grades A and DH)
AvailableDiameters: 1/2″ – 6″Origin: Domestic and importFinish: Plain and hot-dip galvanizedGrades: A563 (grades A, C, and DH), A194 grade 2H
DimensionsFinished Hex Coupler Pattern
Nomi‐nal
Size
F C H Part Numbers
Width AcrossFlats
WidthAcrossCorners
Length/Thick‐ness Import
Basic
Max Min Max Min Basic
Max Min Plain Galva‐nized
Hex Coupling Nuts
1 11 3
[email protected](800) 547-6758
RFI#076 Reference Materials: Provided by Chalmersvia email 12/14/2016
12/20/16, 2(38 PMHex Coupling Nuts - Portland Bolt
Page 2 of 3http://www.portlandbolt.com/products/nuts/hex-coupling/
⁄ ⁄ 0.688 0.663 0.794 0.756 1 ⁄ 1.760 1.690 12338 17525
⁄ ⁄ 0.813 0.782 0.939 0.891 2 ⁄ 2.135 2.067 12559 18195
⁄ 1 1.000 0.963 1.155 1.097 2 ⁄ 2.260 2.190 12557 17526
⁄ 1 ⁄ 1.250 1.212 1.443 1.382 2 ⁄ 2.510 2.440 12558 19504
1 1 ⁄ 1.375 1.325 1.588 1.511 2 ⁄ 2.760 2.690 - 18494
1 ⁄ 1 ⁄ 1.500 1.450 1.732 1.653 3 3.010 2.940 18394 -
1 ⁄ 1 ⁄ 1.625 1.575 1.876 1.825 3 3.010 2.940 18994 17529
1 ⁄ 2 2.000 1.950 2.309 2.275 3 ⁄ 3.510 3.440 - -
Dimensions per ASME B18.2.2 2010Some dimensions may vary by supplier
Heavy Hex Coupler Pattern
Nominal
Size
F C H Part Numbers
Width AcrossFlats
WidthAcrossCorners
ThicknessA563DH
Domestic
Basic
Max Min Max Min Basic
Max Min Plain Galva‐nized
⁄ ⁄ 0.875 0.850 1.010 0.969 1 ⁄ - - - -
⁄ 1 ⁄ 1.062 1.031 1.227 1.175 1 ⁄ - - 17543 17544
⁄ 1 ⁄ 1.250 1.212 1.443 1.382 2 ⁄ - - - 17527
⁄ 1 ⁄ 1.438 1.394 1.660 1.589 2 ⁄ - - - -
1 1 ⁄ 1.625 1.575 1.876 1.796 3 - - - 12343
1 ⁄ 1 ⁄ 1.812 1.756 2.093 2.002 3 ⁄ - - - -
1 ⁄ 2 2.000 1.938 2.309 2.209 3 ⁄ - - 17547 17548
1 ⁄ 2 ⁄ 2.375 2.300 2.742 2.622 4 ⁄ - - 17551 17552
1 ⁄ 2 ⁄ 2.562 2.481 2.959 2.828 4 ⁄ 4.91 4.83 - -
1 ⁄ 2 ⁄ 2.750 2.662 3.175 3.035 5 ⁄ 5.29 5.21 17553 17554
1 ⁄ 2 ⁄ 2.938 2.844 3.392 3.242 5 ⁄ 5.67 5.58 - -
2 3 ⁄ 3.125 3.025 3.608 3.449 6 6.04 5.95 17555 17556
2 ⁄ 3 ⁄ 3.500 3.388 4.041 3.862 6 ⁄ 6.80 6.70 - -
2 ⁄ 3 ⁄ 3.875 3.750 4.474 4.275 7 ⁄ 7.55 7.44 - -
2 ⁄ 4 ⁄ 4.250 4.112 4.907 4.688 8 ⁄ 8.31 8.19 - -
3 4 ⁄ 4.625 4.475 5.340 5.102 9 9.06 8.94 - -
12
1116
34
58
1316
18
34
14
78
14
12
38
34
18
12
14
58
12
12
12
78
12
58
116
78
34
14
14
78
716
58
58
18
1316
38
14
34
12
38
12
58
916
78
34
34
14
78
1516
58
18
14
12
34
12
78
12
34
14
14
58
1 3
RFI#076 Reference Materials: Provided by Chalmersvia email 12/14/2016
12/20/16, 2(38 PMHex Coupling Nuts - Portland Bolt
Page 3 of 3http://www.portlandbolt.com/products/nuts/hex-coupling/
3 ⁄ 5 5.000 4.838 5.774 5.515 9 ⁄ 9.81 9.68 - -
3 ⁄ 5 ⁄ 5.375 5.200 6.207 5.928 10 ⁄ 10.57 10.43 - -
3 ⁄ 5 ⁄ 5.750 5.562 6.640 6.341 11 ⁄ 11.32 11.17 - -
4 6 ⁄ 6.125 5.925 7.073 6.755 12 12.08 11.92 - -
4 ⁄ 6 ⁄ 6.875 6.650 7.939 7.581 13 ⁄ - - - -
5 7 ⁄ 7.625 7.375 8.805 8.408 15 - - - -
Heavy coupler dimensions are not defined by ASME 18.2.2. The width acrossthe flats and corners match the dimensions of a heavy hex nut.
14
34
12
38
12
34
34
14
18
12
78
12
58
RFI#076 Reference Materials: Provided by Chalmersvia email 12/14/2016
RFI#076 Reference Materials: Anchor BoltDimension Shy of Being Flush Provided byChalmers via email 12/14/2016