1. ALL WORK SHALL CONFORM WITH ALL STATE AND LOCAL CODES.
AutoCAD SHX Text
2. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, FEES AND TAXES.
AutoCAD SHX Text
3. EACH ITEM OF EQUIPMENT SHALL BE MOUNTED AND CONNECTED IN STRICT ACCORDANCE
AutoCAD SHX Text
7. ALL EXISTING EQUIPMENT REMOVED SHALL BECOME THE PROPERTY OF THE OWNER AND
AutoCAD SHX Text
SHALL BE REMOVED, STORED, OR DISPOSED OF AT THE DIRECTION OF THE OWNER.
AutoCAD SHX Text
8. ALL OPENINGS IN ROOF, WALLS, CEILINGS AND FLOORS RESULTING FROM DEMOLITION
AutoCAD SHX Text
MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF MECHANICAL
AutoCAD SHX Text
EQUIPMENT'S ELECTRICAL REQUIREMENTS WITH THE ELECTRICAL CONTRACTOR. CON-
AutoCAD SHX Text
TRACTOR ORIGINATED MODIFICATIONS TO THE MECHANICAL EQUIPMENT'S ELECTRICAL
AutoCAD SHX Text
DESIGN" OR "PROTOTYPE" ELECTRICAL DATA, SHALL BE AT A COST TO THE MECHANICAL
AutoCAD SHX Text
INSTALLATION, DUE TO DEVIATIONS FROM THE MECHANICAL EQUIPMENT "BASIS OF
AutoCAD SHX Text
4. CONTRACTOR SHALL MAKE AN ON-SITE INSPECTION TO DETERMINE FULLY THE EXISTING
AutoCAD SHX Text
5. LOCATION OF EQUIPMENT AND OTHER MECHANICAL WORK IS INDICATED DIA-
AutoCAD SHX Text
GRAMMATICALLY BY THE DRAWINGS. DETERMINE EXACT LOCATIONS ON THE JOB SITE,
AutoCAD SHX Text
SUBJECT TO STRUCTURAL CONDITIONS AND WORK OF OTHER CONTRACTORS.
AutoCAD SHX Text
6. AFTER INSTALLATION AND START-UP, EACH ITEM OF EQUIPMENT SHALL BE THOROUGHLY
AutoCAD SHX Text
CHECKED FOR VIBRATION TRANSMISSION TO THE STRUCTURE OR EXCESSIVE NOISE, AND
AutoCAD SHX Text
IF EITHER OCCURS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR CORRECTING THE
AutoCAD SHX Text
FAULTY SITUATION IMMEDIATELY.
AutoCAD SHX Text
SHALL BE CLOSED AND FINISHED TO MATCH THE SURROUNDING AREAS.
AutoCAD SHX Text
CONTRACTOR.
AutoCAD SHX Text
WITH MANUFACTURER'S RECOMMENDATIONS & SHALL BE U.L. LISTED, AS SPECIFIED.
AutoCAD SHX Text
%%UGENERAL NOTES
AutoCAD SHX Text
CONDITIONS AND THE EXTENT OF DEMOLITION.
AutoCAD SHX Text
9.
AutoCAD SHX Text
%%UROOFTOP 1,2,3 AND RAHU 1,2,3,4 UNITS DEMOLITION DRAWING NOTES:
AutoCAD SHX Text
A
AutoCAD SHX Text
B
AutoCAD SHX Text
REMOVE EXISTING RTU AND RAHU UNITS. EXISTING ROOF CURBS SHALL REMAIN. EXISTING LOAD SIDE CONDUCTORS AND CONDUITS SHALL BE REMOVED TO THE DISCONNECTS. REMOVE EXISTING FUSED SAFETY SWITCHES FOR RTU AND RAHU UNITS. REMOVE EXISTING MOTOR STARTERS AND WEATHER TIGHT INCLOSURE ON RAHU 1,2,3,4. REMOVE GFCI SERVICE RECEPTACLE AT EACH ROOFTOP UNIT. REMOVE EXISTING GAS PIPE TO THE FIRST ELBOW ABOVE THE ROOF INCLUDING THE ISOLATION VALVE. REMOVE EXISTING PIPING IN RAHU'S FROM HOT WATER AND CHILLED WATER COILS TO BELOW THE ROOF LINE TO ACCOMMODATE PIPING TO THE NEW HOT WATER AND CHILLED WATER COILS IN PIPE BOX OF NEW UNITS. REMOVE EXISTING VIBRATION ISOLATION RAILS UNDER RTU'S IF ANY. ALL EXISTING ENERGY MANAGEMENT COMPONENTS AND WIRING SHALL BE IDENTIFIED, LABELED, AND DE-ENERGIZED. POWER TO THE COMPONENTS SHALL BE SHUT OFF AT EACH SYSTEM CONTROLLER. CONTROL CONTRACTOR SHALL COORDINATE ALL CONTROL DEMOLITION/INSTALLTION WORK WITH FCPS ENERGY MANAGEMENT DEPT. 48 HOURS BEFORE ANY WORK BEGINS, PLEASE CONTACT SERGHEI MALCOV @703.764.4373.
AutoCAD SHX Text
UNIVERSAL INPUTS
AutoCAD SHX Text
MIXED AIR TEMPERATURE
AutoCAD SHX Text
UNIVERSAL OUTPUTS RTUS
AutoCAD SHX Text
DDC POINT LIST
AutoCAD SHX Text
B
AutoCAD SHX Text
A
AutoCAD SHX Text
MOUNT ALL NEW ROOFTOP AND RAHU UNITS ON NEW CURB ADAPTERS MANUFACTURED TO ACCOMMODATE EXISTING ROOF CURBS. CURB ADAPTER SHALL BE PAINTED WITH TWO COATS OF GRAY SHERWIN WILLIAM INDUSTRIAL ENAMEL HS WEATHER PROOF OUTDOOR PAINT. RAHU 1,2,3,4 CURB ADAPTERS SHALL BE MADE TO ALLOW PIPING TO EXTEND THROUGH THE ROOF INTO NEW PIPE BOX ON UNIT. NEW PIPING SHALL BE INSIDE OF THE CURB ADAPTER. NEW RAHU'S SHALL BE SUPPLIED WITH PIPE BOX MOUNTED ON SIDE OF THE UNIT. ALL PIPING SHALL BE EXTENDED UNDER THE ROOF LINE AND PIPED PER PIPING DETAIL. PROVIDE NEW CONDENSATE DRAIN AND TRAP FOR EACH NEW RTU AND RAHU UNIT. SEE CONDENSATE DRAIN DETAIL. PROVIDE NEW GFCI RECEPTACLE AT EACH RTU AND RAHU AND CONNECT THEM TO THE EXISTING WIRES AND CONDUIT ON THE ROOF. PROVIDE NEW GAS PIPING ON ROOF FOR ALL RTU'S WITH NEW ISOLATION VALVE. SAND AND PAINT THE EXISTING AND NEW GAS PIPE ON THE ROOF TO MATCH EXISTING COLOR. VACUUM INSIDE OF THE EXISTING TO REMAIN SUPPLY AND RETURN DUCTWORK ON THE ROOF TO THE FIRST ELBOW BELOW THE ROOF LINE. BALANCING CONTRACTOR SHALL BALANCE THE OUTDOOR AIR AND SUPPLY AIR QUANTITY FOR EACH RTU AND RAHU PER SCHEDULE, BALANCING CONTRACTOR SHALL ALSO BALANCE HOT WATER AND CHILLED WATER COILS ON RAHU UNITS. CONTACT THE CONTRACTOR AND OWNER IF DESIGNED AIRFLOW CAN'T BE ACHIEVED ON SITE. CONTRACTOR SHALL TIE DUCT SMOKE DETECTOR TO UNIT SHUTDOWN FOR ALL RTU'S AND RAHU UNITS. CONTRACTOR SHALL INFORM AND COORDINATE WITH FCPS FIRE ALARM SPECIALIST (GREG ROSE 703.898.5734) PRIOR TO STARTUP OF THE NEW RTU AND RAHU UNITS. FURNISH AND INSTALL ON ALL NEW RTUS AND RAHU UNITS A NEW F.S.S. WITH NEW FUSES SIZED PER MANUFACTURES RECOMMENDATION ON NEW FREE STANDING F.S.S. ROOF MOUNTING SYSTEM PER DETAIL. PROVIDE PITCH POCKET FOR ALL RTU'S AND RAHU'S ELECTRICAL STAND TO SUPPORT CONDUITS AND WIRING. THE NEW CONDUIT SHALL BE RUN UNDERNEATH THE ROOF AND COME UP NEAR THE NEW RTU. EXTEND POWER AND CONTROLS AS NECESSARY. SEE FREE STANDING SAFETY SWITCH ROOF MOUNTING DETAIL. ANY ROOFING WORK SHALL BE DONE BY THE FOLLOWING ROOFER. COLBERT ROOFING: CHRIS COLBERT 703.550.9171 NEW RTUS AND RAHUS SHALL BE IDENTIFIED BY ENGRAVED NAME TAG WITH THE TITLE OF THE EQUIPMENT AS TAKEN FROM THE PLANS IN A POSITION THAT IS CLEARLY VISIBLE. THE LETTERS SHALL BE NOT LESS THAN " HIGH. THE TITLES SHALL BE SHORT AND CONCISE. 12" HIGH. THE TITLES SHALL BE SHORT AND CONCISE.
AutoCAD SHX Text
CONTROL CONTRACTOR SHALL REMOVE EXISTING CONTROL WIRES FROM THE UNITS WITHOUT CUTTING THEM AND LABEL EVERY CONTROL WIRE ON THE ROOF INSIDE THE NEW RTU. UPON COMPLETION, THE CONTROL CONTRACTOR SHALL VERIFY WITH FCPS TO MAKE SURE THAT ALL THE CONTROL POINTS WORK.
AutoCAD SHX Text
B
AutoCAD SHX Text
A
AutoCAD SHX Text
C
AutoCAD SHX Text
D
AutoCAD SHX Text
CONTROL CONTRACTOR MUST CALL THE FOLLOWING PEOPLE AT THE FAIRFAX COUNTY PUBLIC SCHOOLS BEFORE ANY EXISTING CONTROL WIRES AND RELAYS ARE REMOVED: SERGHEI MALCOV @(703) 764-4373
AutoCAD SHX Text
REPLACE ALL RELAYS, CURRENT SENSOR AND MIXED AIR SENSOR INSIDE THE OLD RTU WITH LIKE COMPONENTS. LABEL EACH POINT INSIDE RTU (LABEL RELAY SOCKETS, NOT RELAYS, AS TO DEVICE CONTROLLED/FUNCTION). EXTEND CONTROL WIRES AS NECESSARY.
AutoCAD SHX Text
CONTRACTOR WILL RETAIN ONE OF THE FOLLOWING CONTROL CONTRACTORS:
AutoCAD SHX Text
CONTROL UNLIMITED - MIKE LOONEY (703.897.4300) CKS BUILDING SERVICES INC. - CHRIS STEVENS (703.975.4990) METROPOLITAN CONTROLS - PAUL CABADA (443.532.5014)
AutoCAD SHX Text
RTU-1,2,3, & RAHU-1,2,3,4
AutoCAD SHX Text
SAF.STATUS (PROOF) D.I. NORM. OPEN
AutoCAD SHX Text
THE FOLLOWING ITEMS MUST BE COMPLETED BY THE CONTRACTOR BEFORE ANY WORK COULD BE PERFORMED AT THE SCHOOL. PROVIDE TRADE PERMITS TO THE OWNER. SCHEDULE A PRE-CONSTRUCTION MEETING WITH THE PRINCIPAL AND THE OWNER. SUBMIT WRITTEN PROPOSAL FROM THE CONTROL SUB-CONTRACTOR WITH THE SCOPE OF WORK. CONTROL CONTRACTOR CAN NOT START THEIR WORK UNTIL MR. SERGHEI MALCOV (703.764.4373) HAS BEEN NOTIFIED. (703.764.4373) HAS BEEN NOTIFIED. HAS BEEN NOTIFIED.
AutoCAD SHX Text
1
AutoCAD SHX Text
2
AutoCAD SHX Text
3
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
%%UNOTE:
AutoCAD SHX Text
4" O.C.
AutoCAD SHX Text
HEAVY DUTY DISCONNECT SWITCH (WP)
AutoCAD SHX Text
SECURED TO METAL FRAMING
AutoCAD SHX Text
CHANNELS.
AutoCAD SHX Text
GALVANIZED METAL FRAMING
AutoCAD SHX Text
CHANNEL SECURED TO 2"
AutoCAD SHX Text
RIGID STEEL CONDUIT
AutoCAD SHX Text
SUPPORTS-TYPICAL
AutoCAD SHX Text
RIGIDLY SECURE CONDUIT
AutoCAD SHX Text
SUPPORTS TO BUILDING
AutoCAD SHX Text
STRUCTURE (TOP AND
AutoCAD SHX Text
SAFETY SWITCH BRANCH
AutoCAD SHX Text
CIRCUIT FEED
AutoCAD SHX Text
GFI DUPLEX RECEPTACLE (WP)
AutoCAD SHX Text
SECURED TO METAL
AutoCAD SHX Text
FRAMING CHANNEL
AutoCAD SHX Text
2" RIGID STEEL CONDUIT
AutoCAD SHX Text
SUPPORT WITH CAPS-
AutoCAD SHX Text
(TYPICAL OF 2)
AutoCAD SHX Text
LIQUID-TIGHT FLEXIBLE
AutoCAD SHX Text
METAL CONDUIT TO
AutoCAD SHX Text
ROOF MOUNTED
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
PITCH POCKET
AutoCAD SHX Text
BY ROOFING
AutoCAD SHX Text
CONTRACTOR
AutoCAD SHX Text
BUILT-UP ROOF
AutoCAD SHX Text
BUILDING STRUCTURE
AutoCAD SHX Text
CONTROL WIRING CONDUIT
AutoCAD SHX Text
20"
AutoCAD SHX Text
4'-6", MAXIMUM TO HANDLE
AutoCAD SHX Text
BOTTOM CORDS)
AutoCAD SHX Text
BRANCH CIRCUIT
AutoCAD SHX Text
CONDUIT SUPPORT
AutoCAD SHX Text
JUNCTION BOX (WP)
AutoCAD SHX Text
FOR CONTROL WIRING CONDUIT
AutoCAD SHX Text
1. LOCATE SAFETY SWITCH ADJACENT ROOF MOUNTED EQUIPMENT'S POWER CONNECTION POINT. 2. DO NOT BLOCK ANY EQUIPMENT'S REMOVABLE PANELS OR IMPEDE REQUIRED WORKING CLEARANCE. 3. ALL PARTS AND MATERIALS SHALL BE GALVANIZED AND SUITABLE FOR OUTDOOR USE. 4. CONTRACTOR SHALL USE RTV SILICONE GASKET TO SEAL ALL OPENINGS INTO DISCONNECT AT FASTENING POINTS.
AutoCAD SHX Text
FREE STANDING SAFETY SWITCH ROOF MOUNTING DETAIL
AutoCAD SHX Text
SHREVEWOOD ELEMENTARY
AutoCAD SHX Text
FALLS CHURCH, VA 22043
AutoCAD SHX Text
7525 SHREVE ROAD
AutoCAD SHX Text
5025 SIDEBURN ROAD
AutoCAD SHX Text
TEL.: 703-764-2423
AutoCAD SHX Text
FAIRFAX, VIRGINIA 22032-2637
AutoCAD SHX Text
OFFICE OF FACILITIES MANAGEMENT
AutoCAD SHX Text
FAIRFAX COUNTY PUBLIC SCHOOLS
AutoCAD SHX Text
FC
AutoCAD SHX Text
PS
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DRG #:
AutoCAD SHX Text
SHEET:
AutoCAD SHX Text
NOTED
AutoCAD SHX Text
ME-1
AutoCAD SHX Text
1 OF 1
AutoCAD SHX Text
ROOFTOP UNIT REPLACEMENT
AutoCAD SHX Text
MMB-104-18
AutoCAD SHX Text
10/19/2017
AutoCAD SHX Text
C
AutoCAD SHX Text
INDOOR FAN DATA
AutoCAD SHX Text
TONS
AutoCAD SHX Text
TOTAL
AutoCAD SHX Text
(CFM)
AutoCAD SHX Text
CFM
AutoCAD SHX Text
AREA
AutoCAD SHX Text
SERVED
AutoCAD SHX Text
O.A.
AutoCAD SHX Text
MOCP
AutoCAD SHX Text
ROOFTOP UNITS (GAS/DX HIGH EFFICIENCY) SCHEDULE
AutoCAD SHX Text
SENSIBLE
AutoCAD SHX Text
COOLING DATA
AutoCAD SHX Text
(MBH)
AutoCAD SHX Text
(IN.W.G.)
AutoCAD SHX Text
(MBH)
AutoCAD SHX Text
TOTAL
AutoCAD SHX Text
E.S.P.
AutoCAD SHX Text
STAGE
AutoCAD SHX Text
(SEER/EER)
AutoCAD SHX Text
MIN
AutoCAD SHX Text
MIN
AutoCAD SHX Text
VOLT/
AutoCAD SHX Text
PH/CYCLES
AutoCAD SHX Text
CKT AMP
AutoCAD SHX Text
MINIMUM
AutoCAD SHX Text
POWER SUPPLY
AutoCAD SHX Text
BASIS OF DESIGN
AutoCAD SHX Text
LBS
AutoCAD SHX Text
WEIGHT
AutoCAD SHX Text
UNIT
AutoCAD SHX Text
7.5
AutoCAD SHX Text
280
AutoCAD SHX Text
0.75
AutoCAD SHX Text
78.2
AutoCAD SHX Text
57.6
AutoCAD SHX Text
2
AutoCAD SHX Text
12.0
AutoCAD SHX Text
460/3/60
AutoCAD SHX Text
19.90
AutoCAD SHX Text
25
AutoCAD SHX Text
1026.0
AutoCAD SHX Text
MAIN OFFICE
AutoCAD SHX Text
CAPACITY
AutoCAD SHX Text
NAT. GAS HEATING (MBH)
AutoCAD SHX Text
INPUT
AutoCAD SHX Text
CAPACITY
AutoCAD SHX Text
STAGES
AutoCAD SHX Text
OUTPUT
AutoCAD SHX Text
MIN.
AutoCAD SHX Text
72
AutoCAD SHX Text
59.2
AutoCAD SHX Text
1
AutoCAD SHX Text
TRANE
AutoCAD SHX Text
YHC092
AutoCAD SHX Text
20
AutoCAD SHX Text
15
AutoCAD SHX Text
4000
AutoCAD SHX Text
1.4
AutoCAD SHX Text
240
AutoCAD SHX Text
180
AutoCAD SHX Text
2
AutoCAD SHX Text
11.0
AutoCAD SHX Text
460/3/60
AutoCAD SHX Text
48.00
AutoCAD SHX Text
60
AutoCAD SHX Text
CAFETERIA
AutoCAD SHX Text
8200
AutoCAD SHX Text
485
AutoCAD SHX Text
388
AutoCAD SHX Text
2
AutoCAD SHX Text
YHD240
AutoCAD SHX Text
1050
AutoCAD SHX Text
1.0
AutoCAD SHX Text
155.7
AutoCAD SHX Text
117.3
AutoCAD SHX Text
2
AutoCAD SHX Text
12.1
AutoCAD SHX Text
460/3/60
AutoCAD SHX Text
33.00
AutoCAD SHX Text
45
AutoCAD SHX Text
2663.0
AutoCAD SHX Text
LIBRARY
AutoCAD SHX Text
4950
AutoCAD SHX Text
225
AutoCAD SHX Text
180
AutoCAD SHX Text
2
AutoCAD SHX Text
YHD180
AutoCAD SHX Text
2400
AutoCAD SHX Text
UNIT
AutoCAD SHX Text
RTU-1
AutoCAD SHX Text
RTU-2
AutoCAD SHX Text
RTU-3
AutoCAD SHX Text
2276.0
AutoCAD SHX Text
C.
AutoCAD SHX Text
A.
AutoCAD SHX Text
B.
AutoCAD SHX Text
D.
AutoCAD SHX Text
E.
AutoCAD SHX Text
F.
AutoCAD SHX Text
G.
AutoCAD SHX Text
H.
AutoCAD SHX Text
I.
AutoCAD SHX Text
PROVIDE BELT DRIVE FAN, MOTORIZED OUTSIDE AIR DAMPER, AND INTAKE HOOD (UNIT MOUNTED). PROVIDE COIL GUARDS (HAIL GUARDS AND SECURITY GRILLES) AND PHASE MONITOR WITH LINE AND LOAD MONITORING CAPABILITIES AND LCD DISPLAY. CONTROLS - PROVIDE STD CONVENTIONAL THERMOSTAT INTERFACE FOR HARDWIRE 2H/2C AND FAN CONNECTION. GAS HEAT - PROVIDE STAINLESS HEAT EXCHANGER. RTU-1,2,3: PROVIDE FACTORY INSTALLED AND CONTROLLED ENTHALPY COMPARISON ECONOMIZER WITH BAROMETRIC RELIEF CONTROLLED BY THE MANUFACTURER. BAROMETRIC RELIEF DAMPER PACKAGE SHALL INCLUDE DAMPER, SEALS, HARDWARE AND HOODS TO RELIEVE EXCESS INTERNAL PRESSURE. OUTSIDE DAMPER SHALL CLOSE DUE TO GRAVITY UPON UNIT SHUTDOWN. PROVIDE AND INSTALL BACNET MS/TP MODULE. THE MANUFACTURER SHALL CONFIGURE IN THE BACNET MODULE AND MADE AVAILABLE FOR FUTURE INTEGRATION. THE RTU WILL NOT BE CONTROLLED VIA BACNET AT THIS MOMENT. COMPRESSORS IN THE RTU SHALL BE INTERNALLY SPRING MOUNTED TO PROVIDE VIBRATION ISOLATION. UNIT MANUFACTURER SHALL FIELD VERIFY THE DIMENSIONS OF THE EXISTING SCREEN ENCLOSURE BEFORE SUBMITTING THE BID. THE OVERALL DIMENSIONS OF THE NEW UNITS SHALL FIT INSIDE THE EXISTING SCREEN ENCLOSURE. ANY NECESSARY MODIFICATIONS TO THE EXISTING SCREEN ENCLOSURE TO ACCOMMODATE THE CLEARANCE REQUIRED BY THE UNIT MANUFACTURER SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. PROVIDE FACTORY INSTALLED HINGED ACCESS PANELS WITH HANDLES AND FACTORY STARTUP OF THE NEW RTU'S. PROVIDE HUMAN INTERFACE CONTROLLER FOR RTU'S- 1,2,3.
AutoCAD SHX Text
COOLING OUTDOOR AMBIENT - 95F D.B., HEATING OUTDOOR AMBIENT - 10F D.B. FAN DATA INCLUDES LOSSES FOR FILTERS AND WET COILS COOLING CAPACITIES LISTED ARE GROSS CAPACITIES AND DO NOT DEDUCT FAN MOTOR HEAT EER LISTED IS AT ARI TEST CONDITIONS
AutoCAD SHX Text
"H20
AutoCAD SHX Text
OUTSIDE AIR CFM
AutoCAD SHX Text
ROOFTOP RAHU UNIT SCHEDULE
AutoCAD SHX Text
CHW
AutoCAD SHX Text
HEATING COIL
AutoCAD SHX Text
DEG.
AutoCAD SHX Text
GPM
AutoCAD SHX Text
LAT.
AutoCAD SHX Text
EAT.
AutoCAD SHX Text
LAT.
AutoCAD SHX Text
WATER
AutoCAD SHX Text
EAT.
AutoCAD SHX Text
GPM
AutoCAD SHX Text
VOLT
AutoCAD SHX Text
PH/CYCLES
AutoCAD SHX Text
FULL LOAD AMP
AutoCAD SHX Text
POWER SUPPLY
AutoCAD SHX Text
BASIS OF DESIGN
AutoCAD SHX Text
LBS
AutoCAD SHX Text
WEIGHT
AutoCAD SHX Text
UNIT
AutoCAD SHX Text
7900
AutoCAD SHX Text
2"
AutoCAD SHX Text
65%%DF
AutoCAD SHX Text
24.3
AutoCAD SHX Text
41%%DF
AutoCAD SHX Text
24.7
AutoCAD SHX Text
460/3/60
AutoCAD SHX Text
14.22 AMPS
AutoCAD SHX Text
2035.8
AutoCAD SHX Text
3950
AutoCAD SHX Text
MBH
AutoCAD SHX Text
HEAT
AutoCAD SHX Text
FLUID
AutoCAD SHX Text
FLUID
AutoCAD SHX Text
HEAT ENT
AutoCAD SHX Text
HEAT LV
AutoCAD SHX Text
287.47
AutoCAD SHX Text
180%%DF
AutoCAD SHX Text
156.75
AutoCAD SHX Text
TRANE
AutoCAD SHX Text
K14C1
AutoCAD SHX Text
7850
AutoCAD SHX Text
8200
AutoCAD SHX Text
2"
AutoCAD SHX Text
82%%DF
AutoCAD SHX Text
65%%DF
AutoCAD SHX Text
24.2
AutoCAD SHX Text
24.6
AutoCAD SHX Text
460/3/60
AutoCAD SHX Text
14.22 AMPS
AutoCAD SHX Text
3925
AutoCAD SHX Text
286.52
AutoCAD SHX Text
180%%DF
AutoCAD SHX Text
156.73
AutoCAD SHX Text
K14C1
AutoCAD SHX Text
2"
AutoCAD SHX Text
82%%DF
AutoCAD SHX Text
65%%DF
AutoCAD SHX Text
28.6
AutoCAD SHX Text
25.7
AutoCAD SHX Text
460/3/60
AutoCAD SHX Text
14.22 AMPS
AutoCAD SHX Text
2244.5
AutoCAD SHX Text
4100
AutoCAD SHX Text
312.51
AutoCAD SHX Text
180%%DF
AutoCAD SHX Text
155.71
AutoCAD SHX Text
K17C1
AutoCAD SHX Text
UNIT
AutoCAD SHX Text
RAHU-1
AutoCAD SHX Text
RAHU-2
AutoCAD SHX Text
RAHU-3
AutoCAD SHX Text
2035.8
AutoCAD SHX Text
9500
AutoCAD SHX Text
2"
AutoCAD SHX Text
82%%DF
AutoCAD SHX Text
65%%DF
AutoCAD SHX Text
30.6
AutoCAD SHX Text
29.8
AutoCAD SHX Text
460/3/60
AutoCAD SHX Text
14.22 AMPS
AutoCAD SHX Text
2562.0
AutoCAD SHX Text
4750
AutoCAD SHX Text
371.56
AutoCAD SHX Text
180%%DF
AutoCAD SHX Text
155.09
AutoCAD SHX Text
K21C1
AutoCAD SHX Text
RAHU-4
AutoCAD SHX Text
COOLING OUTDOOR AMBIENT - 95F D.B., HEATING OUTDOOR AMBIENT - 10F D.B. FAN DATA INCLUDES LOSSES FOR FILTERS AND WET COILS COOLING CAPACITIES LISTED ARE GROSS CAPACITIES AND DO NOT DEDUCT FAN MOTOR HEAT EER LISTED IS AT ARI TEST CONDITIONS
AutoCAD SHX Text
UNIT
AutoCAD SHX Text
NEW
AutoCAD SHX Text
RTU-1
AutoCAD SHX Text
RTU-2
AutoCAD SHX Text
SIZE (AMP)
AutoCAD SHX Text
NEW RTU'S & RAHU POWER WIRING, CONDUIT SIZE
AutoCAD SHX Text
RTU-3
AutoCAD SHX Text
#6
AutoCAD SHX Text
#4
AutoCAD SHX Text
#10
AutoCAD SHX Text
AWG
AutoCAD SHX Text
AWG
AutoCAD SHX Text
3/4"
AutoCAD SHX Text
UNIT
AutoCAD SHX Text
NEW
AutoCAD SHX Text
DISCONNECT
AutoCAD SHX Text
WIRING SIZE
AutoCAD SHX Text
30
AutoCAD SHX Text
AWG
AutoCAD SHX Text
1"
AutoCAD SHX Text
3/4"
AutoCAD SHX Text
30
AutoCAD SHX Text
60
AutoCAD SHX Text
CONDUIT SIZE
AutoCAD SHX Text
H-1
AutoCAD SHX Text
H-1
AutoCAD SHX Text
H-1
AutoCAD SHX Text
BREAKER PANEL
AutoCAD SHX Text
BREAKER SIZE
AutoCAD SHX Text
30 AMP
AutoCAD SHX Text
60 AMP
AutoCAD SHX Text
40 AMP
AutoCAD SHX Text
EXISTING BREAKER PANEL
AutoCAD SHX Text
EXISTING BREAKER PANEL
AutoCAD SHX Text
RAHU-1
AutoCAD SHX Text
RAHU-2
AutoCAD SHX Text
RAHU-3
AutoCAD SHX Text
RAHU-4
AutoCAD SHX Text
20 AMP
AutoCAD SHX Text
20 AMP
AutoCAD SHX Text
20 AMP
AutoCAD SHX Text
20 AMP
AutoCAD SHX Text
HMDP
AutoCAD SHX Text
HMDP
AutoCAD SHX Text
HMDP
AutoCAD SHX Text
HMDP
AutoCAD SHX Text
CFM
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
ESP
AutoCAD SHX Text
82%%DF
AutoCAD SHX Text
COOLING COIL
AutoCAD SHX Text
74.55%%DF
AutoCAD SHX Text
41%%DF
AutoCAD SHX Text
41%%DF
AutoCAD SHX Text
41%%DF
AutoCAD SHX Text
74.65%%DF
AutoCAD SHX Text
76.14%%DF
AutoCAD SHX Text
77.06%%DF
AutoCAD SHX Text
60
AutoCAD SHX Text
30
AutoCAD SHX Text
30
AutoCAD SHX Text
30
AutoCAD SHX Text
AWG
AutoCAD SHX Text
AWG
AutoCAD SHX Text
AWG
AutoCAD SHX Text
AWG
AutoCAD SHX Text
#12
AutoCAD SHX Text
#12
AutoCAD SHX Text
#12
AutoCAD SHX Text
#12
AutoCAD SHX Text
3/4"
AutoCAD SHX Text
3/4"
AutoCAD SHX Text
3/4"
AutoCAD SHX Text
3/4"
AutoCAD SHX Text
%%UROOFTOP 1,2,3 AND RAHU 1,2,3,4 UNITS NEW WORK DRAWING NOTES:
AutoCAD SHX Text
C
AutoCAD SHX Text
D
AutoCAD SHX Text
E
AutoCAD SHX Text
F
AutoCAD SHX Text
G
AutoCAD SHX Text
H
AutoCAD SHX Text
I
AutoCAD SHX Text
J
AutoCAD SHX Text
K
AutoCAD SHX Text
L
AutoCAD SHX Text
F
AutoCAD SHX Text
J.
AutoCAD SHX Text
MBH
AutoCAD SHX Text
TOTAL
AutoCAD SHX Text
169.07
AutoCAD SHX Text
158.61
AutoCAD SHX Text
127.22
AutoCAD SHX Text
127.98
AutoCAD SHX Text
1.MAXIMUM COIL FACE VELOCITY FOR NEW COILS SHALL BE 550 F.P.M.
AutoCAD SHX Text
PROVIDE %%UVARIABLE FREQUENCY DRIVE%%U FOR BELT DRIVE FAN, INTAKE AIR HOOD, OUTSIDE AIR AND RETURN AIR DAMPERS. OUTSIDE AIR DAMPER SHOULD BE ABLE TO HANDLE MINIMUM
AutoCAD SHX Text
UNITS SHALL BE PROVIDED WITH SPRING ISOLATORS AND 2" PLEATED THROWAWAY FILTERS
AutoCAD SHX Text
PROVIDE LINKAGE ON OUTDOOR AIR AND RETURN AIR DAMPERS
AutoCAD SHX Text
PROVIDE FACTORY INSTALLED HINGED ACCESS PANELS AND FACTORY STARTUP OF THE NEW RAHU'S
AutoCAD SHX Text
2.
AutoCAD SHX Text
3.
AutoCAD SHX Text
4.
AutoCAD SHX Text
5.
AutoCAD SHX Text
6.
AutoCAD SHX Text
PROVIDE INSULATED PIPE CHASE
AutoCAD SHX Text
7.
AutoCAD SHX Text
8.
AutoCAD SHX Text
UNITS SHALL BE PROVIDED WITH FACTORY FABRICATED ROOF CURB ADAPTORS
AutoCAD SHX Text
ALL RAHU'S IN THIS SCHEDULE SHALL HAVE CHILLED WATER COOLING COILS AND HOT WATER HEATING COILS.
AutoCAD SHX Text
FLOW
AutoCAD SHX Text
AIR
AutoCAD SHX Text
RETURN
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
HEATING AND COOLING COIL PIPING DETAIL
AutoCAD SHX Text
%%UCONDENSATE DRAIN
AutoCAD SHX Text
ROOF LINE
AutoCAD SHX Text
STATIC PRESSURE
AutoCAD SHX Text
H
AutoCAD SHX Text
X
AutoCAD SHX Text
ROOF TOP UNIT
AutoCAD SHX Text
H = 1" + STATIC PRESSURE
AutoCAD SHX Text
X = 1/2 * H
AutoCAD SHX Text
TOTAL HEIGHT OF TRAP = H + X + (1/2 * DIAMETER OF THE PIPE)
AutoCAD SHX Text
CLEAN OUT
AutoCAD SHX Text
UNION
AutoCAD SHX Text
CLEAN OUT
AutoCAD SHX Text
12"
AutoCAD SHX Text
12"
AutoCAD SHX Text
PIPE SUPPORT (TYP OF 2)
AutoCAD SHX Text
ERICO PYRAMID50 BLOCKS (PROVIDE SEALANT TO THE ROOFING MATERIAL)
AutoCAD SHX Text
SUPPLY FAN START/STOP
AutoCAD SHX Text
GAS HEAT 1
AutoCAD SHX Text
DX COOL 1
AutoCAD SHX Text
DX COOL 2
AutoCAD SHX Text
GAS HEAT 2
AutoCAD SHX Text
O.A. DAMPER CMD
AutoCAD SHX Text
UNIVERSAL OUTPUTS RAHUS
AutoCAD SHX Text
SUPPLY FAN START/STOP
AutoCAD SHX Text
O.A. DAMPER CMD
AutoCAD SHX Text
HEATING VALVE CMD
AutoCAD SHX Text
COOLING VALVE CMD
AutoCAD SHX Text
PROVIDE NEW CONTROL VALVE, CONTROL ACTUATOR, BALANCING AND SHUT OFF VALVES FOR HOT WATER AND CHILLED WATER COILS IN EACH NEW RAHU UNIT. PER PIPING SIZE DETAIL.
AutoCAD SHX Text
9.
AutoCAD SHX Text
DEG.
AutoCAD SHX Text
UNIT
AutoCAD SHX Text
RAHU-1
AutoCAD SHX Text
RAHU-2
AutoCAD SHX Text
RAHU-3
AutoCAD SHX Text
SUPPLY/RETURN PIPE SIZE FOR RAHU
AutoCAD SHX Text
RAHU-4
AutoCAD SHX Text
2" S 2" R
AutoCAD SHX Text
2" S 2" R
AutoCAD SHX Text
(FIELD VERIFY PIPING SIZE)
AutoCAD SHX Text
CHILLED WATER SUPPLY (S)/RETURN (R) (INCH)
AutoCAD SHX Text
HOT WATER SUPPLY (S)/RETURN (R) (INCH)
AutoCAD SHX Text
2" S 2" R
AutoCAD SHX Text
2" S 2" R
AutoCAD SHX Text
2" S 2" R
AutoCAD SHX Text
2" S 2" R
AutoCAD SHX Text
2" S 2" R
AutoCAD SHX Text
2" S 2" R
AutoCAD SHX Text
%%URAHU PIPING SIZE DETAIL
AutoCAD SHX Text
E
AutoCAD SHX Text
D
AutoCAD SHX Text
G
AutoCAD SHX Text
M
AutoCAD SHX Text
CFM AND 100%%% CFM.
AutoCAD SHX Text
PROVIDE NEW FREEZE STATS ON CHILLED WATER COIL WIRED TO SHUT DOWN SUPPLY FAN WHEN TRIPPED.
AutoCAD SHX Text
10.
AutoCAD SHX Text
UNION (TYPICAL)
AutoCAD SHX Text
AIR VENT (TYPICAL)
AutoCAD SHX Text
DRAIN (TYPICAL)
AutoCAD SHX Text
SHUT OFF VALVE (TYPICAL)
AutoCAD SHX Text
THERMOMETER (TYPICAL)
AutoCAD SHX Text
PRESSURE GAGE (TYPICAL)
AutoCAD SHX Text
1
AutoCAD SHX Text
DELETE ROOFTOP UNITS 4,5
AutoCAD SHX Text
1
AutoCAD SHX Text
ADDENDUM #1 2/13/2018
AutoCAD SHX Text
FOR S.A.C.C.