Upload
ashlyn-franklin
View
218
Download
0
Embed Size (px)
Citation preview
1
HVACR317 - RefrigerationRefrigerant Cycle
2
Refrigerants• Compressors are not meant to run
in a vacuum. Running a compressor in a vacuum will damage the windings.
• Refrigerants provide the cooling for compressors.
3
Refrigerants
• At atmospheric pressure, water boils at 212°F.
• If the pressure drops, the boiling point will drop as well - for example, in higher altitudes.
4
Refrigerants
• All refrigerants have a specified boiling point temperature at a specified atmospheric pressure.− Example 1: R134A at 0 psig will boil
at -14°F.− Example 2: R12 at 0 psig has a
boiling point of -20°F.− So, knowing the boiling point is at 0
psig, a chart can be created to show the boiling point at other pressures.
5
Using Temp / Pressure Chart
• The chart on the next slide is the temperature / pressure chart.– Find the column for R134A, and locate
.1 psig on the column. Look to the left and find the temperature. R134A boils at -15°F at atmospheric pressure.
– Most systems do not need to run at temperatures this cold so the pressures are increased (by the use of a compressor), which makes the boiling point increase.
6Temperature Pressure Chart
7
CFCs and HCFCs
• CFCs– Chloro Fluoro Carbons– Old refrigerants being phased out.– Contain chlorine
• HCFCs– HydroChloroFluoroCarbons– Less harmful– Contains some hydrogen
8
HFCs and Oils
• HFCs– HydroFluoroCarbon – Newer refrigerants– No damage to Ozone layer
• Refrigeration Oils– Lubrication for compressors– Polyol Ester & Alkyl Benzene are
synthetic oils.
9
Refrigerant Containers• Color Coded Containers
– Refer to your handout from National Refrigerants. You must know the colors for R22, R134A, R410A, R409A, R502 and R12.
– The oils used are specific for the type of refrigerants. Take care not to use the wrong oil with the refrigerant.
10
System Components
• System Components Consist of the
Following: – Compressor– Condenser– Metering Device– Evaporator Coil– Liquid Line– Suction Line– Filter Drier– Sight Glasses
11
Compressor
• Compressor– Pumps or circulates the refrigerant
through the system. The compressor converts low pressure vapor refrigerant to high pressure vapor refrigerant.
– The compressor does not pump liquid.
12
Condenser
• Condenser: – Rejects heat from the system.– Condenses high pressure vapor into
high pressure liquid refrigerant approximately 30F above ambient temperature.
13
Metering Device
• Metering Device:– Controls the flow of refrigerant
entering the evaporator.– Restricts the flow of refrigerant which
starts the boiling process. (Almost like a resistor in electrical circuits).
• TXV is a type of metering device. TXV stands for Thermostatic Expansion Valve.
14
Evaporator Coil & Liquid Line
• Evaporator Coil:– Absorbs heat from the medium being
cooled.– Evaporates the refrigerant into a
100% low pressure vapor.• Liquid line:
– Carries the high pressure liquid refrigerant from the condenser to the metering device.
15
Suction Line
• Suction Line:– Carries the low pressure vapor from
the evaporator to the compressor inlet.
16
Filter Dryer
• Filter Dryer:– Located on the liquid line and
removes the moisture and/or debris from the system.
– The drier material is made out of Silica gel or a molecular sieve which both filter and absorb moisture.
– The liquid line filter should be replaced any time the system is opened.
17
Filter Dryer
• Filter Dryer, cont’d– Special cleanup driers and suction
line “core type” driers are usually installed on systems that are badly contaminated.
– Make sure you are aware of the direction of the arrow on filter driers. Most are not bi-directional.
18
Sight Glasses
• Sight Glass– Located in the liquid line. Allows a
view of the refrigerant flowing in the system.
– Some sight glasses have a moisture indicator on them to let you know if moisture is in the system.
– Do NOT rely on the sight glass to charge a system. A clear sight glass can mean the system is either empty or full.
19
System Components
• Sight Glass, cont’d– DO NOT charge or diagnose a system
by the sight glass. Always use the gauges.
– Customers will call and complain about “seeing bubbles in the sight glass” and assume it is a low charge. You cannot rely on that.
– The only correct way to diagnose a refrigeration system is with Superheat and subcooling.
20
Refrigerant Cycle Sequence
• Refrigerant leaves the compressor as a high pressure vapor in the discharge line.
• Heat from the compressor and the refrigerant is released in the condenser coil.
• At this pressure, the boiling point is MUCH higher than the outdoor temperature (ambient air).
21
Refrigerant Cycle Sequence
• As the heat is removed from the refrigerant, it starts to condense to a liquid state. This is the heat of condensation.
• Once the refrigerant is 100% liquid, a sensible heat change occurs as the liquid subcools.
22
Refrigerant Cycle Sequence
• The liquid line now carries the refrigerant to the metering device.
• The refrigerant is forced through the pinhole in the metering device.
• Flash gas occurs (80% liquid, 20% vapor) as the refrigerant exits the metering device into the evaporator coil.
23
Refrigerant Cycle Sequence
• Latent heat of evaporation now occurs in the evaporator coil as the refrigerant boils off.
• When the refrigerant is 100% vapor, a sensible heat increase will further heat the vapor (this is superheat).
• The refrigerant returns to the compressor through the suction line.
24
Superheat Defined
• Superheat:– A sensible heat change that occurs in
approximately the last pass of the tubing in the evaporator coil.
– It is a sensible heat gain once the latent heat change has been completed.
– The latent heat change is the liquid changing to gas.
– When superheat is normal the heat transfer in the evaporator coil is working properly.
25
Subcooling Defined
• Subcooling:– Sensible heat change in the condenser
coil following the change of state.– After the condenser coil completely
condenses the high pressure - high temperature vapor to high pressure liquid, the temperature should drop an additional 10 - 20°F as it enters the liquid line. This additional drop is called "subcooling."
26
Additional Notes
• Flash Gas:– Right after the metering device.– 80% liquid and 20% vapor.
• Saturation Point:– The point at which the refrigerant is
100% liquid or 100% vapor. The liquid saturation point is in the condenser. The vapor saturation point is in the evaporator.
27
Additional Notes
• It is important to remember that refrigerant is NEVER used up. If it is not in the system, there must be a leak.
28
Refrigerant Cycle Diagram
CondenserEvaporator
Compressor
Metering Device
FilterDrier
29
Refrigerant State Diagram
FilterDrier
VAPOR
LIQUID