1287552750-05CK

Embed Size (px)

Citation preview

  • 7/29/2019 1287552750-05CK

    1/4

    JET DIFFUSERS

    CK Jet Diffuser

    I

    I

    I

    I

    I

    I

    I

    All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.

    Description

    Materials Outer frame: CK-A, 1.0mm thickness aluminum sheet roll formed. Concentric rings: CK-A, 1.0mm thickness aluminum sheet roll formed.

    Surface Finish Baked white powder coat as standard.

    Features Economical. Long throw capability. High air flow capability. Suitable for exposed ductwork or surface mounted. Suitable for ceiling or wall installation. Air flow direction is adjustable up to 45 upward and downward or leftward and

    rightward.

    Standard Sizes 150, 200, 250, 300, 350, 400 (mm)

    Accessories

    Radial blade damper (C1)

    CK Construction Illustrations

    ASLI CK jet diffusers are made out of a fixed outer frame and adjustable concentric

    rings, which specially designed for high volume and long throw applications. Theconcentric rings can be adjusted 45 upward and downward or leftward andrightward depending on the installation position to control the direction of airflow.CK jet diffusers are suitable to be installed on exposed ductwork or surfacemounted in stadium, factory, theatre and etc.

    Top View Section View

    CK page 1 of 4

    I CK Physical Dimension Unit:mm

    N = Neck Size

    150

    200

    250

    300

    350

    400

    D = Duct Size

    160

    210

    260

    315

    365

    415

    F = Face Size

    225

    275

    320

    370

    420

    480

    H = Height

    95

    115

    140

    155

    170

    195

    W = Wall Size

    170

    220

    265

    325

    375

    450

  • 7/29/2019 1287552750-05CK

    2/4

    JET DIFFUSERS

    CK Jet Diffuser

    All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.

    I CK Control of Air Flow Direction

    The direction of the airflow has to be predetermined before installation. If the airflow direction is upwards or downwards, the diffuser has to be installed withcircular support shaft placing horizontally. If the airflow direction is leftward or rightward, the diffuser has to be installed with circular support shaft placingvertically.

    Pointing downwards Pointing upwards

    Pointing towards left Pointing towards right

    CK page 2 of 4

  • 7/29/2019 1287552750-05CK

    3/4

    JET DIFFUSERS

    CK Jet Diffuser

    All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.

    Throw is based on terminal velocity of 0.25m/s Throw is based on isothermal condition

    NC value is based on room absorption of 10dB, re 10-12 watts Dash (-) in space indicates NC value less than 20

    The performance data is tested in zero degree deflection in axial installation (wall installation)

    I CK Air Flow Performance Data

    I CK Installation

    Neck Size(mm)

    150

    200

    250

    300

    350

    400

    Neck Vel.(m/s)Tot. Press (mmAq)

    CMH

    Throw (m)

    NC

    CMH

    Throw (m)

    NC

    CMH

    Throw (m)

    NC

    CMH

    Throw (m)

    NC

    CMH

    Throw (m)

    NC

    CMH

    Throw (m)

    NC

    20.7

    127

    2.6

    -

    226

    3.8

    -

    353

    4.6

    -

    509

    5.6

    -

    693

    6.5

    -

    905

    7.4

    -

    31.5

    191

    4

    120

    339

    5.6

    20

    530

    7

    -

    763

    8.4

    -

    1039

    9.6

    -

    1357

    10.8

    -

    41.7

    254

    5.5

    24

    452

    7.4

    24

    707

    9.5

    22

    1018

    11.2

    23

    1385

    13

    24

    1810

    15.2

    25

    52.5

    318

    6.8

    30

    565

    9.2

    30

    884

    11.6

    27

    1272

    14

    27

    1732

    16.3

    28

    2262

    18.8

    28

    63.1

    382

    8.2

    37

    679

    11

    37

    1060

    13.8

    32

    1527

    16.8

    32

    2078

    19.5

    34

    2714

    22.4

    35

    74.7

    445

    9.6

    43

    792

    13

    43

    1237

    16.2

    36

    1781

    19.5

    36

    2425

    22.6

    37

    3167

    26.4

    37

    86.5

    509

    11

    47

    905

    14.7

    47

    1414

    18.5

    40

    2036

    22.2

    40

    2771

    25.6

    41

    3619

    29.4

    42

    108.4

    636

    15.2

    50

    1131

    20.5

    50

    1767

    25.4

    44

    2545

    31

    44

    3464

    35.5

    45

    4524

    33.1

    46

    Neck Area(m2)

    0.0177

    0.0314

    0.0491

    0.0707

    0.0962

    0.1257

    Ductwork mounted Wall or ceiling mounted

    CK page 3 of 4

  • 7/29/2019 1287552750-05CK

    4/4

    JET DIFFUSERS

    CK Jet Diffuser

    All stated specifications are updated at the printing date and subject to change without notice or obligation. The actual product might differ from pictures shown.

    I

    I

    CK Order CodeModel

    CK

    Material

    A (Aluminum)

    T (Galvanized Steel)

    Neck Size (mm)

    150, 200, 250, 300, 350

    Accessories

    C1

    Example: CK-A-200mm-C1

    CK Suggested SpecificationCK-A jet diffuser shall be suitable for throw of 10 meters distance with optimum acoustic properties. The outer frame and concentric rings shall be made of1.0mm thickness aluminum sheet roll formed. The concentric rings shall be adjustable with 45 deflection upward or downward without using any tools. Theconcentric rings shall be connected to the outer frame with two circular shafts in one axis. The concentric rings shall be connected to each other with twocircular shafts in an axis, which is perpendicular to the shafts connected to the outer frame. The concentric rings shall have an aerodynamic profile to diffusethe air. The outer frame shall be detachable from the concentric rings with simple tools. The diffuser shall be epoxy coated and furnished to architecturalrequirement.

    Radial blade damper (C1) can be installed at the rear of CK to adjust the air flow rate. CK could be connected to a flexible duct. The opening of the C1 can beadjusted by a screwdriver from the face of the CK.

    CK could be mounted on a panel and supplied as a unit. The CK panel could be installed on the wall or ceiling.

    Two CK panel Three CK panel Four CK panel

    ScrewdriverC1

    CK

    Flexible Air Duct

    CK page 4 of 4