27 kV MASTERCLADMediumVoltage Metal-Clad Switchgear withType VR Vacuum Circuit Breakers
Class 6055
CONTENTS
Description Page
Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
8/13/2019 45PNB27KV
2/4
2000 Schneider Electric All Rights Reserved
2
1/00
RATINGS
16.5 to 27 kV
1200-2000 Amperes Continuous Ratings
16, 25 and 40 kA Symmetrical Interrupting Capacity
125 kV BIL, peak (impulse) dielectric withstand
60 kV, rms 1 minute 60 Hz dielectric withstand NEMA Type 1 Indoor enclosure
APPLICATIONS AND STANDARDS
MASTERCLAD
medium voltage metal-clad switchgear is used in a wide
variety of switching, control and protective applications including electric
utility generation and distribution systems, industrial plants, commercial
buildings, hospitals, municipal pumping stations, wastewater treatment
plants, transportation systems and pipeline stations.
MASTERCLAD offers a standard two-high breaker arrangement,
incorporating a series of basic modular units, control packages and
instrumentation that can be assembled in combinations as needed to satisfy
user application requirements.
MASTERCLAD switchgear with VR circuit breakers meets or exceeds the
design standards of ANSI, IEEE, NEMA and IEC. The switchgear is tested in
accordance with both ANSI C37.20.2 and IEC 298. The VR circuit breakers
are tested per ANSI C37.09 and IEC 56.
STANDARD FEATURES
Metal-Clad Switchgear as defined by ANSI C37.20.2 includes:
Removable (Drawout) Circuit Breaker
Fully Compartmented Construction
Grounded Metal Barriers enclose all live parts
Automatic Shutters over primary contacts
Fluidized-Bed Epoxy Insulated Bus
Mechanical Interlocks
Disconnect Type Voltage Transformers
Fixed Control Power Transformer with Drawout Primary Fuses
Grounded Breaker Truck in and between Test-Disconnected and
Connected Positions
Low Voltage Instrument/Control Compartment isolated from primary
voltage areas
Product Description
8/13/2019 45PNB27KV
3/4
8/13/2019 45PNB27KV
4/4
Catalog No. 6055CT9901 January 2000
Square D Company
330 Weakley Road
Smyrna, TN 37167
615-459-5026
1-888 Square D (1-888-778-2733)
www.squared.com
q
Also tested per IEC 56
a
These values apply with circuit breaker in or out of enclosure.
f
Close and Latch Rating (Momentary) Amperes rms = 2.7 k (Rated Short Circuit Current)
VR 27 kV Vacuum Circuit Breakers Rating Table on Symmetrical Current Rating Basis
Description Preferred Ratings per ANSI C37.06-1997
q
Circuit
Breaker
Catalog
Number
(Ref.)
Three
Phase
MVA
Rated
Cont.
Current60 Hz
A rms
Rated
Short
Circuit
Current(at rated
Max. kV)
kA rms
Rated
Max.
Voltage
kV rms
Volt-
age
Range
Factor k
Inter-
rupting
Time
Cycles
Insulation Level
Rated Withstand Rated
Permis-
sible
TrippingDelay
Y
Sec.
Rated Transient
Recovery VoltageCurrent Values
LowFreq.
kV
rms
Impulse
1.2 x50 s
kV
Crest
a
Rated
CrestVoltage
E2
kV
Crest
Rated
Time toCrest
T2
Micro-
Sec
Maximum
Sym.Inter-
rupting
Capability
kA rms
3 Sec.
Short-
TimeCurrent
Carrying
Capability
kA rms
Close
and
LatchRating
Momentary
kA
Crest
f
VR2701612 750 1200 16 27 1.0 3 60 125 2 51 105 16 16 43
VR2701620 750 2000 16 27 1.0 3 60 125 2 51 105 16 16 43
VR2702512 1250 1200 25 27 1.0 3 60 125 2 51 105 25 25 68
VR2702520 1250 2000 25 27 1.0 3 60 125 2 51 105 25 25 68
VR2704012 2000 1200 40 27 1.0 3 60 125 2 51 105 40 40 108
VR2704020 2000 2000 40 27 1.0 3 60 125 2 51 105 40 40 108
Top Breaker BelowBottom Circuit Breaker Above
(Conduit Area)
Top Breaker AboveBottom Circuit Breaker Below
(Conduit Area)
(6) .75 Dia.Mounting Holes
Recommended4.00 Mounting Channels
(3) Places(By Customer)
Control Conduit Area(Bottom)
36.00(914)
34.20(869)
.90(23)
2.50(64)
8.00(203)
11.00(279)
9.00(229)
3.50(89)
4.00(102)
4.00(102)
8.00(203)
8.00(203)
4.50(114)
4.50(114)36.00
(914)RearAisle
110.50(2807)
54.70(1389)
53.30(1354)
72.00(1829)
Front Aisle64.00(1626)
(Minimum)
1.00(25)Door
1.50(38)
27.00(686)
20.00(508)
28.00(711)
1.00(25)
2.00(51)
.90(23)
Typical Indoor 1200/2000 AFloor Plan
NOT FOR CONSTRUCTION Control Conduit Area(Top)
2.50(64)
8.00(203)
1.75(44)
2.00(561)
Ratings
Breaker Identification
VR 27 025 12
Continuous Current Rating
kA Rating
Voltage Rating
Circuit Breaker Type
Weight (Approximate)
Section (less circuit breaker) 2600 lbs. (1179 kgs.)
1200 A circuit breaker 600 lbs. (272 kgs.)
2000 A circuit breaker 630 lbs. (286 kgs.)
Dimensions are in inches (millimeters).