    27 kV MASTERCLADMediumVoltage Metal-Clad Switchgear withType VR Vacuum Circuit Breakers

    Class 6055

    CONTENTS

    Description Page

    Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

    Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

    Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

  • 8/13/2019 45PNB27KV

    2/4

    2000 Schneider Electric All Rights Reserved

    2

    1/00

    RATINGS

    16.5 to 27 kV

    1200-2000 Amperes Continuous Ratings

    16, 25 and 40 kA Symmetrical Interrupting Capacity

    125 kV BIL, peak (impulse) dielectric withstand

    60 kV, rms 1 minute 60 Hz dielectric withstand NEMA Type 1 Indoor enclosure

    APPLICATIONS AND STANDARDS

    MASTERCLAD

    medium voltage metal-clad switchgear is used in a wide

    variety of switching, control and protective applications including electric

    utility generation and distribution systems, industrial plants, commercial

    buildings, hospitals, municipal pumping stations, wastewater treatment

    plants, transportation systems and pipeline stations.

    MASTERCLAD offers a standard two-high breaker arrangement,

    incorporating a series of basic modular units, control packages and

    instrumentation that can be assembled in combinations as needed to satisfy

    user application requirements.

    MASTERCLAD switchgear with VR circuit breakers meets or exceeds the

    design standards of ANSI, IEEE, NEMA and IEC. The switchgear is tested in

    accordance with both ANSI C37.20.2 and IEC 298. The VR circuit breakers

    are tested per ANSI C37.09 and IEC 56.

    STANDARD FEATURES

    Metal-Clad Switchgear as defined by ANSI C37.20.2 includes:

    Removable (Drawout) Circuit Breaker

    Fully Compartmented Construction

    Grounded Metal Barriers enclose all live parts

    Automatic Shutters over primary contacts

    Fluidized-Bed Epoxy Insulated Bus

    Mechanical Interlocks

    Disconnect Type Voltage Transformers

    Fixed Control Power Transformer with Drawout Primary Fuses

    Grounded Breaker Truck in and between Test-Disconnected and

    Connected Positions

    Low Voltage Instrument/Control Compartment isolated from primary

    voltage areas

    Product Description

  • 8/13/2019 45PNB27KV

    3/4

  • 8/13/2019 45PNB27KV

    4/4

    Catalog No. 6055CT9901 January 2000

    Square D Company

    330 Weakley Road

    Smyrna, TN 37167

    615-459-5026

    1-888 Square D (1-888-778-2733)

    www.squared.com

    q

    Also tested per IEC 56

    a

    These values apply with circuit breaker in or out of enclosure.

    f

    Close and Latch Rating (Momentary) Amperes rms = 2.7 k (Rated Short Circuit Current)

    VR 27 kV Vacuum Circuit Breakers Rating Table on Symmetrical Current Rating Basis

    Description Preferred Ratings per ANSI C37.06-1997

    q

    Circuit

    Breaker

    Catalog

    Number

    (Ref.)

    Three

    Phase

    MVA

    Rated

    Cont.

    Current60 Hz

    A rms

    Rated

    Short

    Circuit

    Current(at rated

    Max. kV)

    kA rms

    Rated

    Max.

    Voltage

    kV rms

    Volt-

    age

    Range

    Factor k

    Inter-

    rupting

    Time

    Cycles

    Insulation Level

    Rated Withstand Rated

    Permis-

    sible

    TrippingDelay

    Y

    Sec.

    Rated Transient

    Recovery VoltageCurrent Values

    LowFreq.

    kV

    rms

    Impulse

    1.2 x50 s

    kV

    Crest

    a

    Rated

    CrestVoltage

    E2

    kV

    Crest

    Rated

    Time toCrest

    T2

    Micro-

    Sec

    Maximum

    Sym.Inter-

    rupting

    Capability

    kA rms

    3 Sec.

    Short-

    TimeCurrent

    Carrying

    Capability

    kA rms

    Close

    and

    LatchRating

    Momentary

    kA

    Crest

    f

    VR2701612 750 1200 16 27 1.0 3 60 125 2 51 105 16 16 43

    VR2701620 750 2000 16 27 1.0 3 60 125 2 51 105 16 16 43

    VR2702512 1250 1200 25 27 1.0 3 60 125 2 51 105 25 25 68

    VR2702520 1250 2000 25 27 1.0 3 60 125 2 51 105 25 25 68

    VR2704012 2000 1200 40 27 1.0 3 60 125 2 51 105 40 40 108

    VR2704020 2000 2000 40 27 1.0 3 60 125 2 51 105 40 40 108

    Top Breaker BelowBottom Circuit Breaker Above

    (Conduit Area)

    Top Breaker AboveBottom Circuit Breaker Below

    (Conduit Area)

    (6) .75 Dia.Mounting Holes

    Recommended4.00 Mounting Channels

    (3) Places(By Customer)

    Control Conduit Area(Bottom)

    36.00(914)

    34.20(869)

    .90(23)

    2.50(64)

    8.00(203)

    11.00(279)

    9.00(229)

    3.50(89)

    4.00(102)

    4.00(102)

    8.00(203)

    8.00(203)

    4.50(114)

    4.50(114)36.00

    (914)RearAisle

    110.50(2807)

    54.70(1389)

    53.30(1354)

    72.00(1829)

    Front Aisle64.00(1626)

    (Minimum)

    1.00(25)Door

    1.50(38)

    27.00(686)

    20.00(508)

    28.00(711)

    1.00(25)

    2.00(51)

    .90(23)

    Typical Indoor 1200/2000 AFloor Plan

    NOT FOR CONSTRUCTION Control Conduit Area(Top)

    2.50(64)

    8.00(203)

    1.75(44)

    2.00(561)

    Ratings

    Breaker Identification

    VR 27 025 12

    Continuous Current Rating

    kA Rating

    Voltage Rating

    Circuit Breaker Type

    Weight (Approximate)

    Section (less circuit breaker) 2600 lbs. (1179 kgs.)

    1200 A circuit breaker 600 lbs. (272 kgs.)

    2000 A circuit breaker 630 lbs. (286 kgs.)

    Dimensions are in inches (millimeters).