502042-UEN_-_AM_G650I_1p2

Embed Size (px)

Citation preview

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    1/353

    Relion650 series

    Generator protection REG650Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    2/353

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    3/353

    Document ID: 1MRK 502 042-UENIssued: June 2012

    Revision: -Product version: 1.2

    Copyright 2012 ABB. All rights reserved

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    4/353

    CopyrightThis document and parts thereof must not be reproduced or copied without written

    permission from ABB, and the contents thereof must not be imparted to a thirdparty, nor used for any unauthorized purpose.

    The software and hardware described in this document is furnished under a licenseand may be used or disclosed only in accordance with the terms of such license.

    TrademarksABB and Relion are registered trademarks of the ABB Group. All other brand or

    product names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.

    WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.

    ABB AB

    Substation Automation Products

    SE-721 59 Vsters

    Sweden

    Telephone: +46 (0) 21 32 50 00

    Facsimile: +46 (0) 21 14 69 18

    http://www.abb.com/substationautomation

    http://http//WWW.ABB.COM/SUBSTATIONAUTOMATION
  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    5/353

    DisclaimerThe data, examples and diagrams in this manual are included solely for the concept

    or product description and are not to be deemed as a statement of guaranteedproperties. All persons responsible for applying the equipment addressed in thismanual must satisfy themselves that each intended application is suitable andacceptable, including that any applicable safety or other operational requirementsare complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including butnot limited to personal injuries or death) shall be the sole responsibility of the

    person or entity applying the equipment, and those so responsible are herebyrequested to ensure that all measures are taken to exclude or mitigate such risks.

    This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requestedto notify the manufacturer. Other than under explicit contractual commitments, inno event shall ABB be responsible or liable for any loss or damage resulting fromthe use of this manual or the application of the equipment.

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    6/353

    ConformityThis product complies with the directive of the Council of the European

    Communities on the approximation of the laws of the Member States relating toelectromagnetic compatibility (EMC Directive 2004/108/EC) and concerningelectrical equipment for use within specified voltage limits (Low-voltage directive2006/95/EC). This conformity is the result of tests conducted by ABB inaccordance with the product standards EN 50263 and EN 60255-26 for the EMCdirective, and with the product standards EN 60255-1 and EN 60255-27 for the lowvoltage directive. The product is designed in accordance with the internationalstandards of the IEC 60255 series.

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    7/353

    Table of contentsSection 1 Introduction.....................................................................15

    This manual......................................................................................15

    Intended audience............................................................................1 5

    Product documentation.................................................................. ...16

    Product documentation set..........................................................16

    Document revision history...........................................................17

    Related documents......................................................................17

    Symbols and conventions.................................................................18

    Symbols.......................................................................................18

    Document conventions................................................................19

    Section 2 Application......................................................................21REG650 application..........................................................................21

    Available functions............................................................................24

    Main protection functions.............................................................24

    Back-up protection functions.......................................................24

    Control and monitoring functions.................................................25

    Communication............................................................................28

    Basic IED functions.....................................................................29

    REG650 application examples.........................................................30Adaptation to different applications.............................................30

    Single generator connected via a unit transformer to a

    High Voltage (HV) system......................................................31

    Single generator, including the auxiliary transformer,

    connected via an unit transformer to a High Voltage

    (HV) system............................................................................32

    Generating unit, including both generator and unit

    transformer, connected to a solidly earthed High

    Voltage (HV) system..............................................................33

    Generating unit, including both generator and unit

    transformer, connected to a high impedance earthed

    High Voltage (HV) system......................................................34

    Functionality table..................................................................35

    Single generator/transformer unit, connected to a solidly

    earthed High Voltage (HV) system, with redundant

    protection................................................................................38

    Single generator/transformer unit, connected to a high

    impedance earthed High Voltage (HV) system, with

    redundant protection..............................................................39

    Two generators having one three-winding unit

    transformer, connected to a solidly earthed High

    Table of contents

    1

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    8/353

    Voltage (HV) system, with redundant protection with unit

    differential protection including the generators.......................40

    Two generators having one three-winding unit

    transformer, connected to a solidly earthed High

    Voltage (HV) system, with redundant protection with unit

    transformer differential protection...........................................41

    Functionality table..................................................................42

    Section 3 REG650 setting examples..............................................45Calculating general settings for analogue TRM inputs 4I 1I 5U... ... .47

    Calculating general settings for analogue AIM inputs 6I 4U.............48

    Preprocessing blocks SMAI..............................................................49

    Calculating settings for global base values for setting function

    GBASVAL.........................................................................................50

    Calculating settings for generator differential protectionGENPDIF .........................................................................................51

    Calculating settings for underimpedance protection for

    generators and transformers ZGCPDIS ..........................................53

    Calculating settings for zone 1....................................................53

    Calculating settings for zone 2....................................................54

    Calculating settings for zone 3....................................................54

    Calculating settings for the Load encroachment function............55

    Calculating settings for out-of-step protection OOSPPAM ..............56

    Calculating settings for loss of excitation LEXPDIS ........................61

    Negative-sequence time overcurrent protection for machinesNS2PTOC ........................................................................................65

    Calculating settings for four step phase overcurrent protection

    3-phase output OC4PTOC ..............................................................65

    Calculating settings for generator phase overcurrent

    protection.....................................................................................65

    Calculating settings for step 1................................................65

    Calculating settings for step 2................................................66

    Calculating settings for auxiliary transformer phase

    overcurrent protection..................................................................66

    Calculating settings for step 1................................................67

    Calculating settings for step 4................................................67

    100% Stator earth fault protection, 3rd harmonic based

    STEFPHIZ .......................................................................................68

    Stator earth fault protection (neutral point voltage)..........................70

    Section 4 Analog inputs..................................................................71Introduction.......................................................................................71

    Setting guidelines.............................................................................71

    Setting of the phase reference channel.......................................71

    Setting of current channels..........................................................72

    Example 1..............................................................................72

    Table of contents

    2

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    9/353

    Example 2..............................................................................73

    Examples on how to connect, configure and set CT

    inputs for most commonly used CT connections....................74

    Example on how to connect a star connected three-phase CT set to the IED.........................................................75

    Example how to connect single-phase CT to the IED............77

    Setting of voltage channels.........................................................79

    Example.................................................................................79

    Examples how to connect, configure and set VT inputs

    for most commonly used VT connections..............................79

    Examples onhow to connect a three phase-to-earth

    connected VT to the IED........................................................80

    Example how to connect the open delta VT to the IED

    for low impedance earthed or solidly earthed power

    systems..................................................................................81

    Example on how to connect a neutral point VT to the

    IED.........................................................................................83

    Section 5 Local human-machine interface.....................................87Local HMI.........................................................................................87

    Display.........................................................................................87

    LEDs............................................................................................89

    Keypad........................................................................................89

    Local HMI functionality................................................................90

    Protection and alarm indication..............................................90Parameter management ........................................................92

    Front communication..............................................................92

    Single-line diagram.................................................................93

    Section 6 Differential protection.....................................................95Transformer differential protection T2WPDIF and T3WPDIF ..........95

    Identification................................................................................95

    Application...................................................................................95

    Setting guidelines........................................................................96

    Inrush restraint methods.........................................................96

    Overexcitation restraint method.............................................96

    Cross-blocking between phases............................................97

    Restrained and unrestrained differential protection................97

    Elimination of zero sequence currents...................................98

    Internal/External fault discriminator........................................99

    Differential current alarm......................................................101

    Switch onto fault feature.......................................................101

    Setting example.........................................................................101

    CT Connections....................................................................101

    1Ph High impedance differential protection HZPDIF .....................103

    Table of contents

    3

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    10/353

    Identification..............................................................................103

    Application.................................................................................103

    The basics of the high impedance principle.........................104

    Connection examples for high impedance differentialprotection...................................................................................110

    Connections for 1Ph restricted earth fault and high

    impedance differential protection.........................................110

    Setting guidelines......................................................................111

    Configuration........................................................................111

    Settings of protection function..............................................111

    Restricted earth fault protection REFPDIF...........................112

    Alarm level operation............................................................114

    Generator differential protection GENPDIF ...................................115

    Identification..............................................................................115

    Application.................................................................................116

    Setting guidelines......................................................................117

    General settings...................................................................117

    Percentage restrained differential operation........................118

    Negative sequence internal/external fault discriminator

    feature..................................................................................120

    Other additional options.......................................................121

    Open CT detection...............................................................122

    Section 7 Impedance protection...................................................125Underimpedance protection for generators and transformers

    ZGCPDIS .......................................................................................125

    Identification..............................................................................125

    Application.................................................................................125

    Setting guidelines......................................................................125

    Loss of excitation LEXPDIS............................................................127

    Identification..............................................................................127

    Application.................................................................................127

    Setting guidelines......................................................................133

    Out-of-step protection OOSPPAM .................................................136

    Identification..............................................................................136

    Application.................................................................................136

    Setting guidelines......................................................................139

    Load enchroachment LEPDIS........................................................142

    Identification..............................................................................142

    Application.................................................................................142

    Setting guidelines......................................................................142

    Resistivereach with load encroachment characteristic........142

    Section 8 Current protection.........................................................145

    Table of contents

    4

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    11/353

    Four step phase overcurrent protection 3-phase output

    OC4PTOC .....................................................................................145

    Identification..............................................................................145

    Application.................................................................................145Setting guidelines......................................................................146

    Settings for steps 1 to 4 .......................................................147

    2nd harmonic restrain...........................................................149

    Four step residual overcurrent protection, zero, negative

    sequence direction EF4PTOC .......................................................155

    Identification..............................................................................155

    Application.................................................................................155

    Setting guidelines......................................................................157

    Settings for steps 1 and 4 ....................................................157

    Common settings for all steps..............................................159

    2nd harmonic restrain...........................................................160

    Sensitive directional residual overcurrent and power protection

    SDEPSDE .....................................................................................161

    Identification.............................................................................. 161

    Application.................................................................................161

    Setting guidelines......................................................................162

    Thermal overload protection, two time constants TRPTTR ...........169

    Identification..............................................................................169

    Application.................................................................................169

    Setting guideline........................................................................170

    Breaker failure protection 3-phase activation and output

    CCRBRF ........................................................................................172

    Identification..............................................................................17 3

    Application.................................................................................173

    Setting guidelines......................................................................173

    Pole discordance protection CCRPLD ..........................................176

    Identification..............................................................................176

    Application.................................................................................176

    Setting guidelines......................................................................177

    Directional over-/under-power protection GOPPDOP/

    GUPPDUP......................................................................................178

    Application.................................................................................178

    Directional overpower protection GOPPDOP ...........................180

    Identification.........................................................................180

    Setting guidelines.................................................................180

    Directional underpower protection GUPPDUP..........................184

    Identification.........................................................................184

    Setting guidelines.................................................................184

    Accidental energizing protection for synchronous generator

    AEGGAPC......................................................................................187

    Table of contents

    5

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    12/353

    Identification..............................................................................187

    Application.................................................................................187

    Setting guidelines......................................................................187

    Negative-sequence time overcurrent protection for machinesNS2PTOC ......................................................................................188

    Identification..............................................................................188

    Application.................................................................................189

    Features...............................................................................189

    Generator continuous unbalance current capability.............190

    Setting guidelines......................................................................192

    Operate time characteristic..................................................192

    Start sensitivity.....................................................................193

    Alarm function......................................................................193

    Voltage-restrained time overcurrent protection VR2PVOC............194Identification..............................................................................194

    Application.................................................................................194

    Base quantities.....................................................................194

    Application possibilities........................................................195

    Under-voltage seal-in...........................................................195

    Setting guidelines......................................................................196

    Voltage restrained overcurrent protection for generator

    and step-up transformer.......................................................196

    Overcurrent protection with undervoltage seal-in.................196

    Section 9 Voltage protection........................................................199Two step undervoltage protection UV2PTUV ................................199

    Identification..............................................................................199

    Application.................................................................................199

    Setting guidelines......................................................................200

    Equipment protection, such as for motors and

    generators............................................................................200

    Disconnected equipment detection......................................200

    Power supply quality ...........................................................200

    Voltage instability mitigation.................................................200

    Backup protection for power system faults...........................200

    Settings for Two step undervoltage protection.....................201

    Two step overvoltage protection OV2PTOV ..................................202

    Identification..............................................................................202

    Application.................................................................................202

    Setting guidelines......................................................................203

    Two step residual overvoltage protection ROV2PTOV .................205

    Identification..............................................................................205

    Application.................................................................................205

    Setting guidelines......................................................................206

    Table of contents

    6

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    13/353

    Equipment protection, such as for motors, generators,

    reactors and transformers....................................................206

    Stator earth-fault protection based on residual voltage

    measurement.......................................................................206

    Power supply quality............................................................210

    High impedance earthed systems........................................210

    Direct earthed system..........................................................211

    Settings for Two step residual overvoltage protection..........212

    Overexcitation protection OEXPVPH ............................................213

    Identification..............................................................................213

    Application.................................................................................214

    Setting guidelines......................................................................215

    Recommendations for input and output signals...................215

    Settings................................................................................215

    100% Statorearth fault protection, 3rd harmonic based

    STEFPHIZ......................................................................................216

    Identification..............................................................................216

    Application.................................................................................216

    Setting guidelines......................................................................220

    Rotor earth fault protection.............................................................222

    Section 10 Frequency protection....................................................223Underfrequencyprotection SAPTUF .............................................223

    Identification..............................................................................223

    Application.................................................................................223

    Setting guidelines......................................................................223

    Overfrequency protection SAPTOF ...............................................224

    Identification..............................................................................224

    Application.................................................................................224

    Setting guidelines......................................................................225

    Rate-of-change frequency protection SAPFRC .............................225

    Identification..............................................................................226

    Application.................................................................................226

    Setting guidelines......................................................................226

    Section 11 Secondarysystem supervision.....................................229Fuse failure supervision SDDRFUF...............................................229

    Identification..............................................................................229

    Application.................................................................................229

    Setting guidelines......................................................................230

    General.................................................................................230

    Setting of common parameters............................................230

    Negative sequence based....................................................231

    Zero sequence based...........................................................232

    Table of contents

    7

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    14/353

    Delta U and delta I ...............................................................232

    Dead line detection...............................................................233

    Breaker close/trip circuit monitoring TCSSCBR.............................233

    Identification..............................................................................233Application.................................................................................233

    Section 12 Control..........................................................................239Synchrocheck, energizing check, and synchronizing

    SESRSYN......................................................................................239

    Identification..............................................................................239

    Application.................................................................................239

    Synchronizing.......................................................................239

    Synchrocheck.......................................................................240

    Energizing check..................................................................242

    Voltage selection..................................................................243

    External fuse failure..............................................................244

    Application examples.................................................................245

    Singlecircuit breaker with single busbar..............................245

    Single circuit breaker with double busbar, external

    voltage selection...................................................................245

    Single circuit breaker with double busbar, internal

    voltage selection...................................................................246

    Double circuit breaker..........................................................247

    1 1/2 circuit breaker..............................................................248

    Setting guidelines......................................................................250

    Apparatus control ..........................................................................255

    Identification..............................................................................255

    Application.................................................................................255

    Interaction between modules.....................................................258

    Setting guidelines......................................................................260

    Bay control (QCBAY)...........................................................260

    Logic rotating switch for function selection and LHMI

    presentation SLGGIO.....................................................................2 60

    Identification..............................................................................260

    Application.................................................................................260

    Setting guidelines......................................................................261

    Selector mini switch VSGGIO.........................................................261

    Identification..............................................................................261

    Application.................................................................................261

    Setting guidelines......................................................................262

    IEC61850 generic communication I/O functions DPGGIO.............262

    Identification..............................................................................262

    Application.................................................................................262

    Setting guidelines......................................................................263

    Table of contents

    8

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    15/353

    Single point generic control 8 signals SPC8GGIO.........................263

    Identification..............................................................................263

    Application.................................................................................263

    Setting guidelines......................................................................263Automation bits AUTOBITS............................................................264

    Identification..............................................................................264

    Application.................................................................................264

    Setting guidelines......................................................................264

    Section 13 Logic.............................................................................265Tripping logic common 3-phase output SMPPTRC .......................265

    Identification..............................................................................265

    Application.................................................................................265

    Three-phase tripping ...........................................................265

    Lock-out................................................................................266

    Blocking of the function block...............................................266

    Setting guidelines......................................................................266

    Trip matrix logic TMAGGIO............................................................267

    Identification..............................................................................267

    Application.................................................................................267

    Setting guidelines......................................................................267

    Configurable logic blocks................................................................268

    Identification..............................................................................268

    Application.................................................................................269Configuration........................................................................269

    Fixed signals FXDSIGN..................................................................270

    Identification..............................................................................270

    Application.................................................................................270

    Boolean 16 to integer conversion B16I...........................................271

    Identification..............................................................................271

    Application.................................................................................271

    Setting guidelines......................................................................272

    Boolean 16 to integer conversion with logic node

    representation B16IFCVI................................................................272

    Identification..............................................................................272

    Application.................................................................................272

    Setting guidelines......................................................................272

    Integer to boolean 16 conversion IB16A........................................272

    Identification..............................................................................272

    Application.................................................................................273

    Setting guidelines......................................................................273

    Integer to boolean 16 conversion with logic node

    representation IB16FCVB...............................................................273

    Identification..............................................................................273

    Table of contents

    9

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    16/353

    Application.................................................................................273

    Settings......................................................................................273

    Section 14 Monitoring.....................................................................275IEC61850 generic communication I/O functions SPGGIO.............275

    Identification..............................................................................275

    Application.................................................................................275

    Setting guidelines......................................................................275

    IEC61850 generic communication I/O functions 16 inputs

    SP16GGIO.....................................................................................275

    Identification..............................................................................275

    Application.................................................................................275

    Setting guidelines......................................................................276

    IEC61850 generic communication I/O functions MVGGIO.............276

    Identification..............................................................................276

    Application.................................................................................276

    Setting guidelines......................................................................276

    Measurements................................................................................277

    Identification..............................................................................277

    Application.................................................................................277

    Setting guidelines......................................................................279

    Setting examples.......................................................................281

    Measurement function application for a 400 kV OHL...........282

    Measurement function application for a generator...............284

    Event counter CNTGGIO................................................................286

    Identification..............................................................................286

    Application.................................................................................286

    Setting guidelines......................................................................286

    Disturbance report .........................................................................287

    Identification..............................................................................287

    Application.................................................................................287

    Setting guidelines......................................................................288

    Binary input signals..............................................................291

    Analog input signals.............................................................291

    Sub-function parameters......................................................292

    Consideration.......................................................................292

    Measured value expander block MVEXP.......................................293

    Identification..............................................................................293

    Application.................................................................................293

    Setting guidelines......................................................................294

    Station battery supervision SPVNZBAT.........................................294

    Identification..............................................................................294

    Application.................................................................................294

    Insulation gas monitoring function SSIMG.....................................295

    Table of contents

    10

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    17/353

    Identification..............................................................................295

    Application.................................................................................295

    Insulation liquid monitoring function SSIML....................................295

    Identification..............................................................................295Application.................................................................................295

    Circuit breaker condition monitoring SSCBR..................................295

    Identification..............................................................................295

    Application.................................................................................296

    Section 15 Metering.......................................................................299Pulse counter PCGGIO..................................................................299

    Identification..............................................................................299

    Application.................................................................................299

    Setting guidelines......................................................................299

    Energy calculation and demand handling EPTMMTR....................300

    Identification..............................................................................300

    Application.................................................................................300

    Setting guidelines......................................................................301

    Section 16 Station communication.................................................303IEC61850-8-1 communication protocol .........................................303

    Identification..............................................................................303

    Application.................................................................................303

    Horizontal communication via GOOSE................................305

    Setting guidelines......................................................................307

    DNP3 protocol................................................................................307

    IEC 60870-5-103 communication protocol.....................................308

    Section 17 Basic IED functions......................................................309Self supervision with internal event list ..........................................309

    Identification..............................................................................309

    Application.................................................................................309

    Time synchronization......................................................................310

    Identification..............................................................................310

    Application.................................................................................310Setting guidelines......................................................................311

    Parameter setting group handling..................................................313

    Identification..............................................................................313

    Application.................................................................................313

    Setting guidelines......................................................................314

    Test mode functionality TESTMODE..............................................314

    Identification..............................................................................314

    Application.................................................................................314

    Setting guidelines......................................................................314

    Table of contents

    11

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    18/353

    Change lock CHNGLCK.................................................................315

    Identification..............................................................................315

    Application.................................................................................315

    Setting guidelines......................................................................316IED identifiers TERMINALID..........................................................316

    Identification..............................................................................316

    Application.................................................................................316

    Customer specific settings...................................................316

    Product information PRODINF.......................................................316

    Identification..............................................................................316

    Application.................................................................................317

    Factory defined settings.......................................................317

    Primary system values PRIMVAL...................................................318

    Identification..............................................................................318Application.................................................................................318

    Signal matrix for analog inputs SMAI.............................................318

    Identification..............................................................................318

    Application.................................................................................318

    Setting guidelines......................................................................319

    Summation block 3 phase 3PHSUM..............................................321

    Identification..............................................................................321

    Application.................................................................................321

    Setting guidelines......................................................................322

    Global base values GBASVAL.......................................................322Identification..............................................................................322

    Application.................................................................................322

    Setting guidelines......................................................................322

    Authority check ATHCHCK.............................................................323

    Identification..............................................................................323

    Application.................................................................................323

    Authorization handling in the IED.........................................323

    Authority status ATHSTAT.............................................................324

    Identification..............................................................................324

    Application.................................................................................324Denial of service.............................................................................325

    Identification..............................................................................325

    Application.................................................................................325

    Setting guidelines......................................................................325

    Section 18 Requirements...............................................................327Current transformer requirements..................................................327

    Current transformer classification..............................................327

    Conditions..................................................................................328

    Fault current..............................................................................329

    Table of contents

    12

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    19/353

    Secondary wire resistance and additional load.........................329

    General current transformer requirements................................329

    Rated equivalent secondary e.m.f. requirements......................330

    Transformer differential protection.......................................3301 Ph high impedance differential protection.........................331

    Breaker failure protection.....................................................332

    Non-directional instantaneous and definitive time, phase

    and residual overcurrent protection......................................332

    Non-directional inverse time delayed phase and residual

    overcurrent protection..........................................................333

    Directional phase and residual overcurrent protection.........334

    Current transformer requirements for CTs according to

    other standards..........................................................................335

    Current transformers according to IEC 60044-1,

    class P, PR...........................................................................335

    Current transformers according to IEC 60044-1, class

    PX, IEC 60044-6, class TPS

    (and old British Standard, class X).......................................335

    Current transformers according to ANSI/IEEE.....................335

    Voltage transformer requirements..................................................336

    SNTP server requirements.............................................................337

    SNTP server requirements........................................................337

    Section 19 Glossary.......................................................................339

    Table of contents

    13

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    20/353

    14

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    21/353

    Section 1 Introduction

    1.1 This manualThe application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purposea typical protection function can be used. The manual can also be used whencalculating settings.

    1.2 Intended audienceThis manual addresses the protection and control engineer responsible for

    planning, pre-engineering and engineering.

    The protection and control engineer must be experienced in electrical powerengineering and have knowledge of related technology, such as protection schemesand communication principles.

    1MRK 502 042-UEN - Section 1Introduction

    15

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    22/353

    1.3 Product documentation1.3.1 Product documentation set

    Planning&purchase

    Engineering

    Installing

    Commissioning

    Operation

    Maintenance

    Decommissioning

    deinstalling&disposal

    Application manual

    Operation manual

    Installation manual

    Service manual

    Engineering manual

    Commissioning manual

    Communication protocolmanual

    Technical manual

    Planning&purchase

    Engineering

    Installing

    Commissioning

    Operation

    Maintenance

    Decommissioning

    deinstalling&disposal

    Planning&purchase

    Engineering

    Installing

    Commissioning

    Operation

    Maintenance

    Decommissioning

    deinstalling&disposal

    Application manualApplication manual

    Operation manualOperation manual

    Installation manualInstallation manual

    Service manualService manual

    Engineering manualEngineering manual

    Commissioning manualCommissioning manual

    Communication protocolmanualCommunication protocolmanual

    Technical manualTechnical manual

    en07000220.vsd

    IEC07000220 V1 EN

    Figure 1: The intended use of manuals in different lifecycles

    The engineering manual contains instructions on how to engineer the IEDs usingthe different tools in PCM600. The manual provides instructions on how to set up aPCM600 project and insert IEDs to the project structure. The manual alsorecommends a sequence for engineering of protection and control functions, LHMI

    functions as well as communication engineering for IEC 60870-5-103, IEC 61850and DNP3.

    The installation manual contains instructions on how to install the IED. Themanual provides procedures for mechanical and electrical installation. The chaptersare organized in chronological order in which the IED should be installed.

    The commissioning manual contains instructions on how to commission the IED.The manual can also be used by system engineers and maintenance personnel forassistance during the testing phase. The manual provides procedures for checkingof external circuitry and energizing the IED, parameter setting and configuration as

    Section 1 1MRK 502 042-UEN -Introduction

    16

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    23/353

    well as verifying settings by secondary injection. The manual describes the processof testing an IED in a substation which is not in service. The chapters are organizedin chronological order in which the IED should be commissioned.

    The operation manual contains instructions on how to operate the IED once it hasbeen commissioned. The manual provides instructions for monitoring, controllingand setting the IED. The manual also describes how to identify disturbances andhow to view calculated and measured power grid data to determine the cause of afault.

    The service manual contains instructions on how to service and maintain the IED.The manual also provides procedures for de-energizing, de-commissioning anddisposal of the IED.

    The application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purposea typical protection function can be used. The manual can also be used whencalculating settings.

    The technical manual contains application and functionality descriptions and listsfunction blocks, logic diagrams, input and output signals, setting parameters andtechnical data sorted per function. The manual can be used as a technical referenceduring the engineering phase, installation and commissioning phase, and duringnormal service.

    The communication protocol manual describes a communication protocolsupported by the IED. The manual concentrates on vendor-specific implementations.

    The point list manual describes the outlook and properties of the data pointsspecific to the IED. The manual should be used in conjunction with thecorresponding communication protocol manual.

    1.3.2 Document revision historyDocument revision/date History-/June 2012 First release

    1.3.3 Related documentsDocuments related to REG650 Identity numberApplication manual 1MRK 502 042-UEN

    Technical manual 1MRK 502 043-UEN

    Commissioning manual 1MRK 502 044-UEN

    Product Guide 1MRK 502 045-BEN

    Type test certificate 1MRK 502 045-TEN

    Rotor Earth Fault Protection with Injection Unit RXTTE4 and REG670 1MRG001910

    Application notes for Circuit Breaker Control 1MRG006806

    1MRK 502 042-UEN - Section 1Introduction

    17

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    24/353

    650 series manuals Identity numberCommunication protocol manual, DNP3 1MRK 511 257-UEN

    Communication protocol manual, IEC 6185081 1MRK 511 258-UEN

    Communication protocol manual, IEC 60870-5-103 1MRK 511 259-UEN

    Cyber Security deployment guidelines 1MRK 511 268-UEN

    Point list manual, DNP3 1MRK 511 260-UEN

    Engineering manual 1MRK 511 261-UEN

    Operation manual 1MRK 500 095-UEN

    Installation manual 1MRK 514 015-UEN

    1.4 Symbols and conventions1.4.1 Symbols

    The electrical warning icon indicates the presence of a hazardwhich could result in electrical shock.

    The warning icon indicates the presence of a hazard which couldresult in personal injury.

    The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presenceof a hazard which could result in corruption of software or damageto equipment or property.

    The information icon alerts the reader of important facts andconditions.

    The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.

    Although warning hazards are related to personal injury, it is necessary tounderstand that under certain operational conditions, operation of damagedequipment may result in degraded process performance leading to personal injuryor death. Therefore, comply fully with all warning and caution notices.

    Section 1 1MRK 502 042-UEN -Introduction

    18

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    25/353

    1.4.2 Document conventionsA particular convention may not be used in this manual.

    Abbreviations and acronyms in this manual are spelled out in the glossary. Theglossary also contains definitions of important terms.

    Push button navigation in the LHMI menu structure is presented by using thepush button icons.To navigate between the options, use and .

    HMI menu paths are presented in bold.Select Main menu/Settings.

    LHMI messages are shown in Courier font.To save the changes in non-volatile memory, select Yesand press .

    Parameter names are shown in italics.The function can be enabled and disabled with the Operationsetting.

    The ^ character in front of an input or output signal name in the function blocksymbol given for a function, indicates that the user can set an own signal namein PCM600.

    The * character after an input or output signal name in the function blocksymbol given for a function, indicates that the signal must be connected toanother function block in the application configuration to achieve a validapplication configuration.

    1MRK 502 042-UEN - Section 1Introduction

    19

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    26/353

    20

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    27/353

    Section 2 Application

    2.1 REG650 applicationREG650 is used for the protection and monitoring of generating plants. The IED isespecially suitable for applications in distributed control systems with highdemands on reliability. It is intended mainly for small and medium size generationstations.

    REG670 may be used when more extensive protection systems are required or in

    combination with REG650 to provide redundant schemes.

    A wide range of protection functions is available to achieve full and reliableprotection for different types of generating plants, for example hydro power plantsand thermal power plants. This enables adaptation to the protection requirements ofmost generating plants.

    Protection functions are available for detecting and clearing internal faults, such asgenerator stator short circuits and earth faults, generator rotor earth faults, unittransformer short circuits and earth faults and faults in the external power system,fed from the generating plant.

    Two packages have been defined for the following applications:

    Generator protection IED including generator differential protection (B01) Generator-transformer unit protection IED including transformer differential

    protection (B05)

    In many generating plants, the protection system can be designed with acombination of the two packages, that is, two IEDs of either same type or differenttypes, will give redundant protection for a generating unit (generator and unittransformer) depending on the requirements for the plant design.

    The packages are configured and ready for use. Analogue inputs and binary input/output circuits are pre-defined.

    The pre-configured IED can be changed and adapted with the graphicalconfiguration tool.

    1MRK 502 042-UEN - Section 2Application

    21

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    28/353

    A, B, C or D

    ~

    59N UN>

    STEF PHIZ

    59THD U3d/N

    REG650-B01

    TR PTTR

    49 Ith

    LEX PDIS

    40

    OEX PVPH

    24 U/f>

    UV2 PTUV

    27 3U

    OC4 PTOC

    51 3I>

    GEN PDIF

    87G 3Id/I

    SA PTUF

    81U f/U

    OC4 PTOC

    51 3I>

    CC RPLD

    52PD PD

    CC RBRF

    50BF 3I> BF

    YY

    Generator CB

    AuxiliaryTransformer

    UnitTransformer

    29MVA121/11kV

    YNd5

    ExcitationTransformer

    HV CB

    ROV2 PTOV

    59N 3Uo>

    TR PTTR

    49 Ith

    OOSPPAM

    78 Ucos

    SESRSYN

    25 SC

    1)

    2)

    3)

    3) Input for independent directional (sensitive) EF function. It can be used for different purposes.

    (e.g. as rotor EF with RXTTE4 or stator EF for generators operating in parallel)

    FieldCB

    HZ PDIF

    87N IdN

    2)Input for independent non-directional EF function. It can be used for different purposes (e.g. as stator EF protection or turn-to-turn protection for generators with split winding or even HV sideEF protection). Alternatively it can be used for High-Impedance REF protection.

    ROV2 PTOV

    59N 3Uo>

    CV MMXN

    Meter.

    GUP PDOP

    32

    GOP PDUP

    37 P

    EF4 PTOC

    67N

    SDEPSDE

    67N

    Rotor EF protection 64R

    GUP PDOP

    32Q

    SA PFRC

    81R df/dt

    390kVA11/0.37kV

    Dyn11

    50/5

    1600/5

    1600/5

    10/1

    1.6MVA11/0.4kV

    EF4 PTOC

    51N IN>

    11 0.11 0.11/ /

    33 3kV

    11 0.11 0.11/ /

    33 3kV

    11 / 0.113

    kV

    200/1

    100/52500/5

    1000

    29MVA11kV

    150rpm

    RXTTE4

    D

    C B

    A

    H J, G or H

    200/5

    G

    Y200/1

    J

    C MSQI

    Meter.

    IEC10000299-2-en.vsd

    Q

    P

    IN> IN>

    UV2 PTUV

    27 3U

    T3DPDIF

    87T 3Id/I

    SA PTUF

    81U f/ U

    OC4 PTOC

    51 3I>

    CC RPLD

    52PD PD

    CC RBRF

    50BF 3I> BF

    YY

    Generator CB

    HV CB

    ROV2 PTOV

    59N 3Uo>

    TR PTTR

    49 Ith

    OOSPPAM

    78 Ucos

    SESRSYN

    25 SC

    Note:

    2)Input for independent non-directional EF function. It can be used for different purposes (e.g. as stator EF protection or turn-to-turn protection for gene rators with split winding or even HV

    side EF protection). Alternatively it can be used for High-Impedance REF protection.

    1)Inputs for independent directional (sensitive) E F function. It can be used for different purposes

    (e.g. as rotor EF with RXTTE4 or stator EF for generators running in parallel)

    1)

    2)

    FieldCB

    TR PTTR

    49 Ith

    OC4 PTOC

    51 3I>

    HZ PDIF

    87N IdN

    EF4 PTOC

    51N IN>

    GT01

    ROV2 PTOV

    59N 3Uo>

    59N UN>

    YY

    CV MMXN

    Meter.

    GOP PDUP

    37 P

    EF4 PTOC

    67N

    SDEPSDE

    67N

    Rotor EF protection 64R

    CV MMXN

    Meter.

    GOP PDOP

    32Q

    SA PFRC

    81R df/dt

    3)

    3)Alternatively step-up transformer HV side open delta VT can be connected here

    Generator CB

    Auxiliary

    Transformer

    Unit

    Transformer

    29MVA

    121/11kVYNd5

    ExcitationTransformer

    390kVA

    11/0.37kV

    Dyn11

    50/5

    1600/5

    29MVA

    11kV

    150rpm

    200/1

    100/5

    1.6MVA

    11/0.4kV

    11 0.11 0.11/ /

    33 3kV

    110 0.11 0.11/ /

    33 3kV

    11/ 0.11

    3kV

    2500/5

    1000

    RXTTE4

    C

    B

    E

    A

    D

    A or B

    D or E

    200/5

    G

    1600/5

    10/1H J, G or H

    Y200/1

    J

    SDD RFUF

    60FL

    C MSQI

    Meter.

    IEC10000300-2-en.vsd

    IN> IN>

    Q

    P

    On On On On

    Two step residual overvoltage ProtectionROV2PTOV , U0>, instance 1

    OnGen Term

    OnGen Term

    OnGen Neutr point

    OnGen Neutr point

    Two step residual overvoltage ProtectionROV2PTOV , U0>, instance 2

    OnT sec side

    OnT sec side

    OnT sec side

    OnT HV neutr point

    Overexcitation protection OEXPVPH On On On On

    100% Stator earth fault protection, 3rd harmonicbased STEFPHIZ / 95 % fundamental based

    On On Applicationdependent

    Applicationdependent

    Underfrequency protection SAPTUF , instance 1 On On On On

    Underfrequency protection SAPTUF, instance 2 Off Off Off Off

    Underfrequency protection SAPTUF, instance 3 Off Off Off Off

    Underfrequency protection SAPTUF, instance 4 Off Off Off Off

    Overfrequency protection SAPTOF, instance 1 On On On On

    Overfrequency protection SAPTOF, instance 2 Off Off Off Off

    Overfrequency protection SAPTOF, instance 3 Off Off Off Off

    Overfrequency protection SAPTOF, instance 4 Off Off Off Off

    Table continues on next page

    Section 2 1MRK 502 042-UEN -Application

    36

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    43/353

    Function Application 1 Application 2 Application 3 Application 4Rate-of-change frequency protection SAPFRC,instance 1

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Rate-of-change frequency protection SAPFRC ,

    instance 2

    Off Off Off Off

    Synchrocheck, energizing check, and synchronizingSESRSYN

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Applicationdependent

    1) The generator should have reverse power protection. If the generator consumes low reverse power at motor operation (< 1 % of SN),

    low forward power protection should be used. In other cases, reverse power protection should be used.2) Voltage-restrained time overcurrent protection add (VR2PVOC) can be used instead of the underimpedance protection.

    1MRK 502 042-UEN - Section 2Application

    37

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    44/353

    2.3.1.6 Single generator/transformer unit, connected to a solidly earthedHigh Voltage (HV) system, with redundant protection

    REG650 (B01)

    3

    3

    3

    3

    1

    1

    3

    1

    1

    3

    Aux

    Rotor

    DC

    Rotor EF

    injection

    IinjUinj

    REG650 (B05)

    IEC10000128-1-en.vsd

    IEC10000128 V1 EN

    Figure 8: Single generator/transformer unit, connected to a solidly earthed

    High Voltage (HV) system, with redundant protection

    REG650 (B01) is used as the main protection for the generator and REG650 (B05)is used as the main protection for the unit transformer and as back-up protection forthe generator. The combination of the protections also gives redundant protectionfor the auxiliary system transformer.

    Section 2 1MRK 502 042-UEN -Application

    38

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    45/353

    Table 6: Data for the generator application exam pleParameter ValueGenerator rated voltage (UN,Gen) 1 20 kV

    Transformer high voltage side rated voltage (UN,THV)

    11 220 kV

    Generator rated power (SN) 1 150 MVA

    Short circuit power level infeed at HV-side 500 10000 MVA

    2.3.1.7 Single generator/transformer unit, connected to a high impedanceearthed High Voltage (HV) system, with redundant protection

    REG650 (B01)

    3

    3

    3

    3

    1

    1

    3

    1

    3

    Aux

    Rotor

    DC

    Rotor EF

    injection

    IinjUinj

    REG650 (B05)

    1

    IEC10000129-1-en.vsd

    IEC10000129 V1 EN

    Figure 9: Single generator/transformer unit, connected to a high impedance

    earthed High Voltage (HV) system, with redundant protection

    1MRK 502 042-UEN - Section 2Application

    39

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    46/353

    REG650 (B01) is used as the main protection for the generator and REG650 (B05)is used as the main protection for the unit transformer and as back-up protection forthe generator. The combination of the protections also gives redundant protectionfor the auxiliary system transformer.

    Table 7: Data for the generator application exam pleParameter ValueGenerator rated voltage (UN,Gen) 1 20 kV

    Transformer high voltage side rated voltage (UN,

    THV)

    11 220 kV

    Generator rated power (SN) 1 150 MV

    Short circuit power level infeed at HV-side 500 5000 MVA

    2.3.1.8 Two generators having one three-winding unit transformer,connected to a solidly earthed High Voltage (HV) system, withredundant protection with unit differential protection including thegeneratorsREG650 (B05)

    3

    3

    3

    1

    1

    3

    1

    3

    3

    3

    1

    1

    1

    3

    1

    3

    Rotor

    DC

    Rotor EF

    injection

    IinjUinj

    REG650 (B01)

    Aux

    Rotor

    DC

    Rotor EF

    injection

    IinjUinj

    REG650 (B01)

    3

    Aux

    IEC10000130-1-en.vsd

    IEC10000130 V1 EN

    Figure 10: Two generators having one three-winding unit transformer,

    connected to a solidly earthed High Voltage (HV) system, with

    redundant protection with unit differential protection including the

    generators

    Section 2 1MRK 502 042-UEN -Application

    40

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    47/353

    REG650 (B01) is used as the main protection for the generator and REG650 (B05)is used as the main protection for the unit transformer and as back-up protection forthe generator. The combination of the protections also gives redundant protectionfor the auxiliary system transformer.

    Table 8: Data for the generator application exam pleParameter ValueGenerator rated voltage (UN,Gen) 1 20 kV

    Transformer high voltage side rated voltage (UN,

    THV)

    11 220 kV

    Generator rated power (SN) 1 150 MVA

    Short circuit power level infeed at HV-side 500 10000 MVA

    2.3.1.9 Two generators having one three-winding unit transformer,connected to a solidly earthed High Voltage (HV) system, withredundant protection with unit transformer differential protectionREG650 (B05)

    3

    3

    3

    1

    1

    3

    1

    3

    3

    3

    1

    1

    1

    3

    1

    3

    Rotor

    DC

    Rotor EF

    injection

    IinjUinj

    REG650 (B01)

    Aux

    Rotor

    DC

    Rotor EF

    injection

    IinjUinj

    REG650 (B01)

    3

    Aux

    IEC10000131-1-en.vsd

    IEC10000131 V1 EN

    Figure 11: Two generators having one three-winding unit transformer,

    connected to a solidly earthed High Voltage (HV) system, with

    redundant protection with unit transformer differential protection

    REG650 (B01) is used as the main protection for the generator and REG650 (B05)is used as the main protection for the unit transformer and as back-up protection for

    1MRK 502 042-UEN - Section 2Application

    41

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    48/353

    the generator. The combination of the protections also gives redundant protectionfor the auxiliary system transformer.

    Table 9: Data for the generator application exam pleParameter ValueGenerator rated voltage (UN,Gen) 1 20 kV

    Transformer high voltage side rated voltage (UN,

    THV)

    11 220 kV

    Generator rated power (SN) 1 150 MVA

    Short circuit power level infeed at HV-side 500 10000 MVA

    2.3.1.10 Functionality tableThe proposal for functionality choice for the different application cases are shownin table 10.

    The recommendations have the following meaning:

    On: It is recommended to have the function activated in the application. Off: It is recommended to have the function deactivated in the application. Application dependent: The decision to have the function activated or not is

    dependent on the specific conditions in each case.

    Application 5 8 in table10are according to application examples

    given in previous sections.

    Tab le 10: Recommended funct ions in the d if fe rent app li ca tion examp lesFunction Application 5 Application 6 Application 7 Application 8Generator differential protection GENPDIF (B01) On On On On

    Transformer differential protection T3WPDIF (B05) On On On On

    1Ph High impedance differential protection HZPDIF Applicationdependent

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Underimpedance protection for generators andtransformers ZGCPDIS (B01)

    On On On On

    Underimpedance protection for generators andtransformers ZGCPDIS (B05)

    Off Off Off Off

    Load encroachment LEPDIS Applicationdependent

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Out-of-step protection OOSPPAM (B01) On On On On

    Out-of-step protection OOSPPAM (B05) Off Off Off Off

    Loss of excitation (underexcitation) protectionLEXPDIS (A01)

    On On On On

    Loss of excitation (underexcitation) protectionLEXPDIS (B05)

    Off Off Off Off

    Table continues on next page

    Section 2 1MRK 502 042-UEN -Application

    42

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    49/353

    Function Application 5 Application 6 Application 7 Application 8Four step phase overcurrent protection OC4PTOC ,instance 1 (B01)

    OnAux T

    OnAux T

    OnAux T

    OnAux T

    Four step phase overcurrent protection OC4PTOC ,

    instance 1 (B05)

    On On On On

    Four step phase overcurrent protection OC4PTOC ,instance 2

    Off Off Off Off

    Four step residual overcurrent protection EF4PTOC ,instance 1 (B01)

    Off Off Off Off

    Four step residual overcurrent protection EF4PTOC ,instance 1 (B05)

    OnT HV

    OnT HV

    OnT HV

    OnT HV

    Four step residual overcurrent protection EF4PTOC ,instance 2

    Off Off Off Off

    Sensitive directional residual overcurrent and powerprotection SDEPSDE (B01)

    OnRotor EF

    OnRotor EF

    OnRotor EF

    OnRotor EF

    Sensitive directional residual overcurrent and power

    protection SDEPSDE (B05)

    Off Off Off Off

    Thermal overload protection TRPTTR , instance 1 On On On On

    Thermal overload protection TRPTTR , instance 2 Off Off Off Off

    Breaker failure protection CCRBRF (B01) On On On On

    Breaker failure protection CCRBRF (B05) OnHV CB

    OnHV CB

    OnHV CB

    OnHV CB

    Pole discordance protection CCRPLD Applicationdependent

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Directional under-power protection GUPPDUP (lowforward power protection), (B01)

    1) 1) 1) 1)

    Directional underpower protection GUPPDUP (Low

    forward power protection), (B05)

    Off Off Off Off

    Directional overpower protection GOPPDOP ,instance 1 (reverse power protection), (B01)

    1) 1) 1) 1)

    Directional overpower protection GOPPDOP ,instance 1 (reverse power protection), (B05)

    Off Off Off Off

    Directional overpower protection GOPPDOP ,instance 2

    Off Off Off Off

    Accidental energizing protection for synchronousgenerator AEGGAPC (B01)

    On On On On

    Accidental energizing protection for synchronousgenerator AEGGAPC (B05)

    Off Off Off Off

    Negative-sequence time overcurrent protection formachines NS2PTOC On On On On

    Voltage-restrained time overcurrent protectionVR2PVOC (B01)

    2) 2) 2) 2)

    Voltage-restrained time overcurrent protectionVR2PVOC (B05)

    Off Off Off Off

    Two step undervoltage protection UV2PTUV , U< On On On On

    Two step overvoltage protection OV2PTOV , U> On On On On

    Two step residual overvoltage protectionROV2PTOV , U0>, instance 1 (B01)

    OnGen Neutr point

    OnGen Neutr point

    OnGen Neutr point

    OnGen Neutr point

    Table continues on next page

    1MRK 502 042-UEN - Section 2Application

    43

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    50/353

    Function Application 5 Application 6 Application 7 Application 8Two step residual overvoltage protectionROV2PTOV , U0>, instance 1 (B05)

    OnT sec side

    OnT sec side

    OnT sec side

    OnT sec side

    Two step Residual Overvoltage Protection

    ROV2PTOV , U0>, instance 2 (B01)

    On

    Gen Term

    On

    Gen Term

    On

    Gen Term

    On

    Gen Term

    Two step residual overvoltage protectionROV2PTOV , U0>, instance 2 (B05)

    Off OnT HV neutr point

    OnT sec side 2

    OnT sec side 2

    Overexcitation protection OEXPVPH On On On On

    100% Stator earth fault protection, 3rd harmonicbased STEFPHIZ / 95 % fundamental based (B01)

    On On On On

    100% Stator earth fault protection, 3rd harmonicbased STEFPHIZ / 95 % fundamental based (B05)

    Off Off Off Off

    Underfrequency protection SAPTUF , instance 1 On On On On

    Underfrequency protection SAPTUF , instance 2 Off Off Off Off

    Underfrequency protection SAPTUF, instance 3 Off Off Off Off

    Underfrequency protection SAPTUF, instance 4 Off Off Off Off

    Overfrequency protection SAPTOF, instance 1 On On On On

    Overfrequency protection SAPTOF, instance 2 Off Off Off Off

    Overfrequency protection SAPTOF, instance 3 Off Off Off Off

    Overfrequency protection SAPTOF, instance 4 Off Off Off Off

    Rate-of-change frequency protection SAPFRC,instance 1

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Rate-of-change frequency protection SAPFRC,instance 2

    Off Off Off Off

    Synchrocheck, energizing check, and synchronizingSESRSYN(B01)

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Applicationdependent

    Synchrocheck, energizing check, and synchronizingSESRSYN (B05)

    Off Off Off Off

    1) The generator should have reverse power protection. If the generator consumes low reverse power at motor operation (< 1 % of SN),

    low forward power protection should be used. In other cases, reverse power protection should be used.2) Voltage-restrained time overcurrent protection add (VR2PVOC) can be used instead of the underimpedance protection.

    Section 2 1MRK 502 042-UEN -Application

    44

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    51/353

    Section 3 REG650 setting examples

    The application example has a generation unit protected by one REG650 B01(Main 1) and one REG650 B05 (Main 2) as shown in figure 12.

    REG650 (B01)

    3

    3

    3

    3

    1

    1

    3

    1

    1

    3

    Aux

    Rotor

    DC

    Rotor EF

    injection

    IinjUinj

    REG650 (B05)

    145 kV

    IEC10000155-1-en.vsd

    IEC10000155 V1 EN

    Figure 12: Power plant protection application

    The following data is assumed:

    Table 11: Data for the unit transformerItem DataTransformer rated power SN 25 MVA

    Transformer high voltage side rated voltage UN1 145 kV

    Transformer low voltage side rated voltage UN2 10.5 kV

    Transformer vector group YNd11

    Table continues on next page

    1MRK 502 042-UEN - Section 3REG650 setting examples

    45

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    52/353

    Item DataTransformer short circuit voltage ek 12 %

    Maximum allowed continuous overload 1.30 * SN

    Phase CT ratio at 145 kV level 150/1 A

    CT at 145 kV earth point 150/1 A

    Phase CT ratio at 10 kV level 1500/1 A

    10 kV VT ratio 11 0 11 0 11kv

    33 3

    . ./ /

    High Positive sequence source impedance at theHV side

    10 ohm (about 2100 MVA) with a phase angle 85

    High Zero sequence source impedance at theHV side

    j20 ohm

    Table 12: Data for the generatorItem DataGenerator rated power SN 25 MVA

    Generator rated voltage UN 10.5 kV kV

    Rate power factor cosn 0.90

    xd 1.0 per unit (pu)

    xd 0.4 pu

    xd 0.25 pu

    Phase CT ratio at generator terminal side 1500/1 APhase CT ratio at generator neutral point side 1500/1 A

    Generator neutral point VT ratio 110.11 kV

    3/

    Generator 10 kV terminal VT ratio 11 0 11 0 11kV

    33 3

    . ./ /

    Table 13: Data for the auxiliary transform erItem DataTransformer rated power SN 1.0 MVA

    Transformer high voltage side rated voltage UN1 10.5 kV

    Transformer low voltage side rated voltage UN2 0.4 kV

    Transformer vector group Dyn5

    Transformer short circuit voltage ek 4 %

    Phase CT ratio at 10.5 kV level 100/1 A

    Section 3 1MRK 502 042-UEN -REG650 setting examples

    46

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    53/353

    Only settings that need adjustment due to the specific applicationare described in setting examples. It is recommended to keep thedefault values for all settings that are not described. Refer toTechnical manual for setting tables for each protection and controlfunction.

    Refer to setting guideline section in Application manual forguidelines on how to set functions that are not presented in settingexamples.

    Use parameter setting tool in PCM600 to set the IED according tocalculations for the particular application.

    3.1 Calculating general settings for analogue TRMinputs 4I 1I 5UThe transformer module (TRM) has the capability of 4 current inputs (tapped to 1or 5 A), 1 current input (tapped to 0.1 or 0.5 A) and 5 voltage inputs.

    The generator neutral point phase CTs (three-phase current transformer group) areconnected to inputs 1 3 (L1, L2 and L3).

    The generator neutral point CT can be connected to input 4 (not used here).

    The rotor earth fault current measurement is connected to input 5.

    The generator terminal side phase VT is connected to inputs 6 - 8 (L1, L2 and L3).

    The generator neutral point VT is connected to input 9.

    The rotor earth fault voltage measurement is connected to input 10.

    1. Set the current transformer inputs.1.1. Set CTStarPoint1to To Object.

    The CT secondary is earthed towards the transformer.1.2. Set CTSec1to 1 A.

    (The rated secondary current of the CT)1.3. Set CTPrim1to 1500 A.

    (The rated primary current of the CT)1.4. Set the same values for current inputs 2 and 3.1.5. Set CTStarPoint4to.1.6. Set CTSec4to.

    1MRK 502 042-UEN - Section 3REG650 setting examples

    47

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    54/353

    1.7. Set CTPrim4to.1.8. Set CTStarPoint5to To Object.1.9. Set CTSec5to 1 A.1.10. Set CTPrim5to 1000 A.

    2. Set the voltage transformer inputs.

    2.1. Set VTSec6to 110 V.(The rated secondary voltage of the VT, given as phase-to-phase voltage)

    2.2. Set VTPrim6to 11 kV.(The rated secondary voltage of the VT, given as phase-to-phase voltage)

    2.3. Set the same values for current inputs 7 and 8.2.4. Set VTSec9to 110 V.

    (The rated secondary voltage of the VT)2.5. Set VTPrim9to 6.35 kV.

    This gives equivalent of ratio

    110.11 kV

    3/

    EQUATION2379 V1 EN

    2.6. Set VTSec10to 120 V.2.7. Set VTPrim10to 120 kV.

    3.2 Calculating general settings for analogue AIMinputs 6I 4UThe analogue input module (AIM) has the capability of 6 current inputs (tapped to1 or 5 A) and 4 voltage inputs.

    The generator terminal side phase CTs (three-phase current transformer group) areconnected to inputs 1 3 (L1, L2 and L3).

    The auxiliary transformer 10 kV phase CTs (three-phase current transformergroup) are connected to inputs 4 6 (L1, L2 and L3).

    The transformer 10 kV phase VT is connected to inputs 7 - 9 (L1, L2 and L3).

    The generator terminal side open delta VT is connected to input 10.

    1. Set the current transformer inputs.

    1.1. Set CTStarPoint1to To Object.The CT secondary is earthed towards the transformer.

    1.2. Set CTSec1to 1 A.(The rated secondary current of the CT)

    1.3. Set CTPrim1to 1500 A.

    Section 3 1MRK 502 042-UEN -REG650 setting examples

    48

    Application Manual

  • 8/12/2019 502042-UEN_-_AM_G650I_1p2

    55/353

    (The rated primary current of the CT)1.4. Set the same values for current inputs 2 and 3.1.5. Set CTStarPoint4to To Object.

    The CT secondary is earthed towards the bus transformer.1.6. Set CTSec4to 1 A.

    (The rated secondary current of the CT)1.7. Set CTPrim4to 100 A.

    (The rated primary current of the CT)1.8. Set the same values for current inputs 5 and 6.

    2. Set the voltage transformer inputs.

    2.1. Set VTSec7to 110 V(The rated secondary voltage of the VT, given as phase-to-phase voltage)

    2.2. Set VTPrim7to 11 kV.(The rated secondary voltage of the VT, given as phase-to-phase voltage)

    2.3. Set the same values for current inputs 8 and 9.3. Set VTSec10to 110 V.

    (The rated secondary voltage of the VT multiplied by 3)4. Set VTPrim10to 19.05 kV.

    This gives equivalent of ratio

    11 0 11kv

    33

    ./

    EQUATION2355 V1 EN

    3.3 Preprocessing blocks SMAIMany of the protection functions must be enabled to operate also during generatorrun-up, i.e. in circumstances where the