2
SERIES 670 / 6670 End-of-Line Deflagration Flame Arrester Suitable for use with NEC Group D (IEC Explosion Group IIA) Vapors Sizes 1" through 4" Listed by Underwriters Laboratories in 1" and 2” sizes Suitable for use with vapors equivalent to NEC 500 Group D, IEC Group IIA Vertically mounted, parallel plate-type flame arrester Protects against fire Minimizes pressure drop under normal operating conditions Easy inspection and maintenance Factory inspected prior to shipment Available in Aluminum and Stainless Steel OBJECTIVE The Series 670/6670 Flame Arresters are designed to provide flame stopping protection for a tank’s vapor space when mounted to the end of a tank nozzle leading directly to atmosphere. The arresters prevent a flame front generated by an unconfined deflagration occurring outside the tank from propagating into the vapor space. VAPOR GROUPS The arresters are intended for use with vapors equivalent to Group D of the National Electric Code (NEC 500), IEC Group IIA. For arresters suitable for use with NEC Group C, IEC Group IIB3, please refer to Protectoseal Series 670E. TECHNIQUE The arrester is mounted on the end of a vent pipe from the tank. Vapors are allowed to escape into the atmosphere and air can be drawn into the tank through the specially designed flame arrester grid assembly. If an ignition source outside the tank is encountered, the flame arrester provides protection for the tank contents. SPECIAL FEATURES Easy Inspection, Installation and Maintenance. Design and light weight of unit permit easy, convenient handling for inspection, installation and maintenance. The weatherhood is readily removable by loosening just a few extra large wing nuts. Automatic Condensate Drainage. Vertically mounted, circular plate-type flame arrester is employed for self-drainage of condensate. This prevents accumulation of condensate subject to freezing and consequent clogging of the arrester under low temperature conditions. Positive Flame Arresting. The Series 670/6670 employs a circular-plate, precisely-spaced, type flame arrester to protect tank contents by preventing the propagation of fire into the tank. Precision embossings on alternate plates provide correct air-spacing for flame arresting function. Plates are fabricated from 1 / 16" to 3 / 32" heavy gauge metal, depending on material of construction, to resist distortion and bending during cleaning. Sizes Available. 1", 2", 3" and 4" have standard NPT female threaded connections. Adapter flanges are available in these sizes. Refer to dimension chart on reverse for flange connec- tion details. Refer to Series 670E for 6” size. Test Lab Listings. Listed by Underwriters Laboratories (UL) in 1" and 2” sizes. For arresters that meet ATEX Directive 94/9/EC Standards EN 12874 & ISO 16852, please refer to Series 670E. PRO-FLOW III ® Sizing and Selection Software. Use PRO-FLOW III ® to calculate flame arrester flow requirements in accordance with API 2000, ISO 28300, NFPA 30 and OSHA 1910.106. Quality Assurance. Each unit is inspected to meet Protectoseal’s high standards prior to shipment. CONSTRUCTION A comprehensive range of materials is offered as shown in the chart below. Other materials and features can be furnished upon request. Available Options. Material certifications for castings www.protectoseal.com Nipple Flame Arrester Series Body Hood Flange Grid Assembly 670 Aluminum Aluminum Aluminum Aluminum 6670 Aluminum Aluminum Aluminum Aluminum F670 316 S.S. 316 S.S. 316 S.S. 316 S.S. FF6670 316 S.S. 316 S.S. 316 S.S. 316 S.S. NOTE: Aluminum flanged to mate with 125# ANSI FF flanges. 316 S,S. models mate with 150# ANSI RF flanges. PROTECTOSEAL ®

670_6670_SPEC

Embed Size (px)

Citation preview

Page 1: 670_6670_SPEC

SERIES 670 / 6670End-of-Line Deflagration Flame Arrester

Suitable for use with NEC Group D (IEC Explosion Group IIA) Vapors

� Sizes 1" through 4"� Listed by Underwriters Laboratories in 1" and 2” sizes� Suitable for use with vapors equivalent to NEC 500

Group D, IEC Group IIA� Vertically mounted, parallel plate-type flame arrester� Protects against fire� Minimizes pressure drop under normal operating

conditions� Easy inspection and maintenance� Factory inspected prior to shipment� Available in Aluminum and Stainless Steel

OBJECTIVEThe Series 670/6670 Flame Arresters are designed toprovide flame stopping protection for a tank’s vapor spacewhen mounted to the end of a tank nozzle leading directly toatmosphere. The arresters prevent a flame front generatedby an unconfined deflagration occurring outside the tank frompropagating into the vapor space.

VAPOR GROUPSThe arresters are intended for use with vapors equivalent toGroup D of the National Electric Code (NEC 500), IEC GroupIIA. For arresters suitable for use with NEC Group C, IECGroup IIB3, please refer to Protectoseal Series 670E.

TECHNIQUEThe arrester is mounted on the end of a vent pipe from thetank. Vapors are allowed to escape into the atmosphere andair can be drawn into the tank through the specially designedflame arrester grid assembly. If an ignition source outside thetank is encountered, the flame arrester provides protection forthe tank contents.

SPECIAL FEATURESEasy Inspection, Installation and Maintenance. Design andlight weight of unit permit easy, convenient handling forinspection, installation and maintenance. The weatherhood isreadily removable by loosening just a few extra large wingnuts.

Automatic Condensate Drainage. Vertically mounted, circularplate-type flame arrester is employed for self-drainage ofcondensate. This prevents accumulation of condensatesubject to freezing and consequent clogging of the arresterunder low temperature conditions.

Positive Flame Arresting. The Series 670/6670 employs acircular-plate, precisely-spaced, type flame arrester to protecttank contents by preventing the propagation of fire into thetank. Precision embossings on alternate plates providecorrect air-spacing for flame arresting function. Plates arefabricated from 1⁄16" to 3⁄32" heavy gauge metal, depending onmaterial of construction, to resist distortion and bendingduring cleaning.

Sizes Available. 1", 2", 3" and 4" have standard NPT femalethreaded connections. Adapter flanges are available in thesesizes. Refer to dimension chart on reverse for flange connec-tion details. Refer to Series 670E for 6” size.

Test Lab Listings. Listed by Underwriters Laboratories (UL) in1" and 2” sizes. For arresters that meet ATEX Directive94/9/EC Standards EN 12874 & ISO 16852, please refer toSeries 670E.

PRO-FLOW III® Sizing and Selection Software. UsePRO-FLOW III® to calculate flame arrester flow requirementsin accordance with API 2000, ISO 28300, NFPA 30 andOSHA 1910.106.

Quality Assurance. Each unit is inspected to meetProtectoseal’s high standards prior to shipment.

CONSTRUCTIONA comprehensive range of materials is offered as shown inthe chart below. Other materials and features can be furnishedupon request.

Available Options.� Material certifications for castings

www.protectoseal.com

Nipple Flame ArresterSeries Body Hood Flange Grid Assembly

670 Aluminum Aluminum Aluminum Aluminum6670 Aluminum Aluminum Aluminum AluminumF670 316 S.S. 316 S.S. 316 S.S. 316 S.S.FF6670 316 S.S. 316 S.S. 316 S.S. 316 S.S.NOTE: Aluminum flanged to mate with 125# ANSI FF flanges. 316 S,S. models mate with 150#ANSI RF flanges.

PROTECTOSEAL®

Page 2: 670_6670_SPEC

Type Approved according toATEX Directive 94/9/EC,

Standards EN 12874 and ISO16852. Suitable for use with

NEC Groups C or D(IEC Groups IIB3 or IIA).

Combination Pressure / VacuumRelief Vent & Flame Arresterprovides pressure and vacuumrelief as well as protection frompropagation of externally intro-duced flames. Suitable for NECGroup D (IEC Group IIA) vapors.

End-of-Line Deflagration FlameArrester provides protection ofthe tank’s vapor space if an

ignition source is introduced out-side of the tank. Suitable forNEC Group D (IEC Group IIA)

vapors.

Series 670E (Group C, IIB3) Series 830Series 860 (Group D, IIA)

Pipe-Away Pressure VacuumRelief Vent for applications thatrequire hazardous vapors beprocessed into manifolded

piping and not released into theatmosphere.

Series 18540

Specifications Series 670 / 6670End-of-Line Deflagration Flame Arrester

ADDITIONAL PRODUCTS FROM PROTECTOSEAL

©2012 The Protectoseal Company V-670/6670/4

PROTECTOSEAL®

Safety Without Compromise

225 Foster Ave., Bensenville, IL 60106-1690P 630.595.0800 F [email protected] www.protectoseal.com

D

E,N

Connection Ht Dia B.C Dia. Holes Type

Cat. No.* FNPT ANSI** DIN 16 PN A C D E N Approval

671 1" 1- 1- 12.88" (73mm) 13.38" (86mm) - - - UL671F - 11" 1- 14.4" (112mm) 13.38" (86mm) 3.13" (80mm) .63" (16mm) 4 ULSee Series 670E - 1- 1DN 25 1- 1- - - - Note 16672 2" 1- 1- 14.63" (117mm) 16.13" (156mm) - - - UL6672F - 12" 1- 17"(178mm) 16.13" (156mm) 4.75" (120mm) .75" (19mm) 4 ULSee Series 670E - -- 1DN 50 1- 1- - - - Note 1673B 3" 1- 1- 18" (203mm) 17.5" (191mm) - - - -673BF - 13" 1- 19.88" (251mm) 17.5" (191mm) 6" (152mm) .75" (19mm) 4 -See Series 670E - 1- 1DN 80 1- 1- - - - Note 1674 4" 1- 1- 17.38" (187mm) 18.5" (216mm) - - - -674F - 14" 1- 19.38" (238mm) 18.5" (216mm) 7.5" (190mm) .75" (19mm) 8 -See Series 670E - 1- 1DN 100 1- 1- - - - Note 1* Cat. No. designates all Aluminum construction, please refer to chart on reverse for other materials.

** Aluminum flanged to mate with 125# ANSI FF flanges. 316 S,S. models mate with 150# ANSI RF flanges.

Note 1: Type Approved according to ATEX Directive 94/9/EC, Standards EN 12874 and ISO 16852 (Refer to Protectoseal Series 670E)

DIMENSIONS (NOTE: Dimensions shown are for reference only, contact Factory for certified drawings.)

Suitable for use withNEC Group D

chemical vapors,generally equivalentto ElectrotechnicalCommission (IEC)

Group IIA

For arresterssuitable for use withNEC Group C,IEC Group IIB3,please refer toProtectosealSeries 670E

For larger sizes. . . Refer to Protectoseal Series No. 860 or Series No. 670E