201Vishal Bhawan-95, Nehru Place, New Delhi-19, Ph-011-26284058 /59, +91-8744010985 Email:[email protected], Visit us at: www.bharatinfotech.net Calculation Sheet for-6 UPS:- 1. No. Of Batteries and Size Calculation for 6 kVA Online UPS with 30 min Backup:- i. Known details (FYI mentioned on UPS Catalogue): a. Load of UPS: 6 kVA b. Power Factor: 0.9 c. Efficiency of UPS (in Eco Mode): 93 % d. Total Cell Voltage (end cell voltage): 10.5 Volt e. No. Of Battery: 20 No. (DC Voltage Requirement is 240 Volt) ii. Calculation and Formula Used: a. I DC (Amp.) = (Load X 1000 X Power factor) /(efficiency X Total Cell Voltage x No. of battery) = (6 X 1000 X 0.9) / (.93 X 10.5 X 20) = 27.64Amp. b. For Ampere-Hour Calculation for your reference: - Above mentioned discharge current in point i.e. 27.64Amp, now as we require 30min. back up then from graph we recommend 12V/26AH battery which can give around 30 min battery backup. So we suggest to use 12 Volt 26Ah, SMF Grade Batteries for around 30min. backup for 6 kVA UPS.

6kVA UPS Battery Selection

Embed Size (px)

DESCRIPTION

ups

Citation preview

  • 201Vishal Bhawan-95, Nehru Place, New Delhi-19, Ph-011-26284058 /59, +91-8744010985

    Email:[email protected], Visit us at: www.bharatinfotech.net

    Calculation Sheet for-6 UPS:-1. No. Of Batteries and Size Calculation for 6 kVA Online UPS with 30 min Backup:-i. Known details (FYI mentioned on UPS Catalogue):a. Load of UPS: 6 kVAb. Power Factor: 0.9c. Efficiency of UPS (in Eco Mode): 93 %d. Total Cell Voltage (end cell voltage): 10.5 Volte. No. Of Battery: 20 No. (DC Voltage Requirement is 240 Volt)ii. Calculation and Formula Used:a. I DC (Amp.) = (Load X 1000 X Power factor) /(efficiency X Total Cell Voltagex No. of battery)= (6 X 1000 X 0.9) / (.93 X 10.5 X 20)

    = 27.64Amp.b. For Ampere-Hour Calculation for your reference: -

    Above mentioned discharge current in point i.e. 27.64Amp, now as we require 30min. back up then from graph we

    recommend 12V/26AH battery which can give around 30 min battery backup.

    So we suggest to use 12 Volt 26Ah, SMF Grade Batteries for around 30min. backup for 6 kVA UPS.