  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 1997 1

    ApplicationThe 7SA511 distance protection relayprovides fast, reliable and selective clear-ance of faults on overhead lines andcables, being fed from one or multiplepoints. The network can be radial, ring ormeshed. The system star point may beisolated, resonance earthed (e.g. Peter-son coil), solidly earthed or lowresis-tance earthed.The relay incorporates all functions nor-mally required for distance protection andcan also be applied as a time-gradedback-up protection for all types of differ-ential protection schemes.The 7SA511 can be incorporated in bothconventional switchgear systems andmodern LSA 678 substation control andprotection systems.

    ConstructionWith its compact construction the7SA511 contains all the components re-quired for current and voltage measure-ment for protection scheme logic, faultrecording and on-line measurements, op-erator panel with display field, event/alarm and command outputs, binary (con-tact) inputs, serial interfaces and powersupply with DC/DC converter.The relay can be supplied in three casevariations. The version for surface mount-ing is supplied with 100 two-tier termi-nals accessible from the front. The ver-sions for flush mounting or cubiclemounting have rear connection terminalsand are available with or without glasscover.

    Mode of operationAll data processing within the 7SA511 isdigital, from the measurement of volt-ages and currents to the tripping decisionlogic. The application of digital measure-ment to a large degree suppresses theinfluence of switching currents, transientDC current components, highfrequencytransients and harmonics.

    Serial interfacesThe relay is fitted with two serial inter-faces.The operator interface on the front panelis suitable for the connection of a PC.The operating and analysis softwareDIGSI, running under WINDOWS, is avail-able as an option to enable user-friendlyparameter setting, analysis of fault dataand records, and commissioning.The system interface (either isolatedRS232C/V.24 or fibre-optic) is availablefor connection to the SiemensSINAUT LSA 678 substation controlsystem, to a central data acquisition sy-stem, to the data concentrator DAKON orto a starcoupler.The communication protocol used is thecompatible protocol according IEC8705103. The serial information inter-face has been certified by the researchinstitute for high-voltage and high-currenttechnology (FGH) and declared to be inconformity with the IEC 8705103 stan-dard.Remote operation of the distance protec-tion relay 7SA511 with the DIGSI soft-ware is possible if a modem is connectedto the FOserial interface.For existing systems, the Siemens-spe-cific protocol to DIN 19 244 is still avail-able.

    SettingsAll settings can be input by means of theintegrated operator and display fieldpanel, or a PC. All parameters are identi-fied in clear text. The settings are storedin a non-volatile memory, so that theycannot be lost even during interruption ofthe supply voltage.All parameters are reliably stored inEEPROMs and are thus independent ofthe state of charge of the memory bat-tery.

    Self-monitoringHardware and software components aremonitored continuously and any irregula-rities are immediately detected andalarmed. As a result, the security, avail-ability and reliability of the relay are sig-nificantly improved.

    SIPROTEC 7SA511 distance protection relay (Version V3)

    Fig. 1SIPROTEC 7SA511 distance protection relay

    21

    21N

    50

    50/

    Scope of functions

    67N

    49

    78

    79

    25

    51N

    FL

    FR

    LM

    Siemens AG 1997

    Siemens AG 1997

  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 19972

    Distance protectionDistance protection is the main functionof the 7SA511 relay. The distinguishingfeatures of the relay are as follows: Availability of multiple starting options:

    a) Overcurrent fault detection b) Voltage-dependent overcurrent faultdetection V (option)The measured voltages, depending onthe selected settings and the earthfault detection, may be 3 x phase-to-earth VPH E, depending on the phasecurrent PH (see Fig. 2) or the 3 xphase-to-phase voltages VPH PH.c) Polygonal impedance characteristicfault detection Z< (option) (see Fig. 3).Either the impedances of the 3 xphase-to-phase loops or 3 x phase-to-earth loops are calculated dependingon the earth-fault detection. The effectof apparent impedances in unfaultedphases during earth faults is elimi-nated by a compensation method.

    Earth faults are detected by earth cur-rent E detection and/or residual volt-age VE measurement.

    Polygonal tripping characteristics withseparate settings for reactance X andresistance reach R (see Fig. 4). Sepa-rate settings are provided for the resis-tance reach R for phase-to-phase andphase-to-earth faults. Five distancezones are provided and they may beindependently set in the forward or re-verse direction or non-directional. Twoof the zones may also be used forzone extension schemes. In addition, adirectional and a nondirectionalbackup time stage is available.

    Directional measurement using soundphase polarization and voltage memoryfor unlimited sensitivity.

    Seven independent time delays areprovided.

    Phase-selective tripping is available foruse with single-pole or single andthree-pole rapid auto-reclosingschemes.

    Automatic blocking of the distanceprotection function is provided follow-ing detection of a V.T. failure to pre-vent incorrect distance measurement.

    Fault locatorFault location is provided through calcula-tion of the fault impedance. The distance-tofault may be output in ohms, kilome-ters or percentage of the line length.As an option, the fault location can beprovided by parallelline mutualcompensation, if the zerocurrent of theparallellines can be measured.

    SIPROTEC 7SA511 distance protection relay (Version V3)

    Fig. 2Characteristic of voltage-dependent overcurrent fault detector V PHE ( PH )

    V PHE( >>)

    V PHE( >)

    > >> PH

    V PHE

    Fault detection

    Fig. 3Characteristic of impedance fault detector (Z

  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 1997 3

    Overcurrent-time and definite-timeovercurrent protection (emergency)The distance protection 7SA511 can beused as a two-stage definite-time over-current protection. This protective func-tion can only be automatically activated ifthe measuring voltage fails resulting fromshortcircuit or fault in the V.T. circuit, orif the V.T. c.b. trips.

    Universal teleprotection interfaceFor fast selective clearance of faults overthe complete line a comprehensive tele-protection facility is provided. The follow-ing schemes may be selected: Intertrip via fault detection Intertrip via zone extension Z1B Signal comparison with zone extension

    Z1B Unblocking with directional fault detec-

    tion Directional comparison Unblocking with zone extension Z1B Blocking with zone extension Z1B Pilot wire protection Reverse interlock functionAn echo function for zero or weak infeed,and a current reversal block function forcomparison or blocking are integrated.

    Switch-on-to-fault protectionThrough the use of a binary input repre-senting manual closing of the line circuit-breaker the 7SA511 can initiate a switch-on-to-fault function. The function may beset to initiate immediate tripping fromzone Z1B or from the fault detection ele-ments.Earth-fault detection in non-earthednetworks (option)In networks with no star-point earthing,single phase-to-ground earth-fault detec-tion is provided. The following functionsare included: Detection of an earth fault by monitor-

    ing the residual displacement voltageVE

    Determination of the faulted phasethrough measurement of the phase-to-earth voltages

    Determination of the direction of theearth fault through precise measure-ment of the active and reactive com-ponents of the residual current (E)

    Annunciation or tripping in the event ofan earth fault in forward direction

    Measurement of the respective con-tent of the active and reactive compo-nent of the earth current during anearth fault.

    Sensitive earth-fault protection inearthed networks (option)In earthed networks which are subject toextreme high-resistance earth faults, it ispossible for the fault impedance to lieoutside of the distance protection imped-ance characteristic. The 7SA511 may in-clude the following optional functions forhighresistance earth fault protection: Directional earth-fault protection with

    emergency and back-up definite-timeovercurrent protection function

    Earth-fault overcurrent protection func-tion with inverse-time characteristic

    The directional earth-fault functionmay be extended to become a direc-tional comparison scheme with theuse of interstation signalling and com-parison logic.

    Automatic-reclose function (option)The 7SA511 can be ordered with an auto-reclose (AR) facility.The range of functions include: 3-pole RAR/DAR for all fault types

    (DAR: delayed ARcycle) 1-pole RAR for single-phase faults, no

    reclose for multiple-phase faults 1-pole RAR for single-phase faults,

    3-pole RAR/DAR for multiple-phasefaults

    1-pole RAR for single-phase and for2-phase faults without involvement ofearth, and 3-pole RAR/DAR for otherfaults

    Multi-shot DAR Integration with external AR equip-

    ment with communication via binary(contact) inputs and outputs

    Control of the 7SA511 AR function byan external protection scheme

    AR blocking for faults in the cable sec-tion of mixed routes (cable and over-head line).

    Power swing (option)Power swings can give rise to high equal-ization currents and small voltages. Smallvoltages, with simultaneous high cur-rents, mean small impedances, whichcan lead to tripping of the distanceprotection. In order to avoid uncontrolledtripping by the distance protection andspecific tripping in the event of synchro-nism loss, the 7SA511 distance protec-tion relay features an additional powerswing function option.The following reaction to power swingscan be set: Blocking

    The distance protection tripping func-tion may be blocked for the duration ofthe power swing

    TrippingTripping may be initiated following thedetection of a power swing outsidethe defined stability limits.

    Synchronism check (option)Where two network sections areswitched in by control command or fol-lowing a 3-pole RAR, it must be ensuredthat both network sections are mutuallysynchronous. For this purpose, the dis-tance protection relay 7SA511 features asynchronism check function. After verifi-cation of network synchronism, the func-tion enables the CLOSE command. Alter-natively, reclosing can also be verifiedafter a check for dead state of the busbaror cable.

    Thermal overload protectionFor thermal protection of cables an over-load protection with an early-warningstage is provided. The thermal replica canbe formed with the maximum or meanvalue of the respective excess tempera-tures in the three phases, or with thetemperature rise from the respectivemaximum phase current.The tripping time characteristics are ex-ponential functions to IEC 2558 and theytake account of heat loss due to the loadcurrent and the accompanying drop intemperature of the cooling medium. Theprevious load is therefore taken into ac-count in the tripping time on overload. Asettable alarm stage can output a currentor temperature-dependent indication be-fore the tripping point is reached.

    Selectable parameter changeover set-ting groups (option)Through binary (contact) inputs or via therelay setting facilities (front panel or se-rial interface) it is possible to change be-tween four sets of previously stored pa-rameter settings. This allows the rapidmodification of relay settings to matchconfiguration changes in the protectednetwork.Parameter set changeover is also pos-sible via the compatible IEC 8705103interface.

    SIPROTEC 7SA511 distance protection relay (Version V3)

  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 19974

    Fault recordingThe digitized measured values of phasecurrents, earth current, phase voltagesand residual earth voltage, together withseveral binary channels, are stored withparameterizable pretrigger and postfault time. Storage of recorded fault datais batterybuffered and therefore remainsavailable even after an interruption of theauxiliary power supply. Fault recordingcan be transmitted to a PC and to the SINAUT LSA substation control systemfor evaluation. Parallel operation of PCand substation control system is pos-sible. If the IEC8705103 protocol isused, up to 8 fault records can be stored.The data memory is organized as a ringbuffer store with a maximum length of 5s (at fN = 50 Hz). The oldest fault recordsare overwritten with the newest data. Afault record can also be started via abinary input or especially as an aid incommissioning via an integrated controlpanel or PC. The respective record dura-tion can then be parameterized.

    Function allocation for command andalarm relays, LEDs and binary inputsThe 7SA511 is equipped with 5 heavy-duty output relays. They can be linkedwith the commands for the above-men-tioned protective functions and with allother signal outputs or binary signals.For user-specific output and display ofsignals, alarm relays and LEDs may beallocated as desired. Individual signalscan be grouped. The stored LED indica-tions are protected from supply voltagefailure.All binary inputs can likewise be allocatedas desired.

    Measurement and test functionsThe 7SA511 provides a large number oftest and measurement functions, includ-ing the following: Measurement of the (in-service) im-

    pedance of six impedance loops andindication of direction, reactance andresistance

    Monitoring of the phase sequence In-service measurement L1, L2, L3 In-service measurement VL1L2,

    VL2L3, VL3L1, VL1, VL2, VL3 Active and reactive power measure-

    ment Frequency measurement Trip circuit test facility, single and

    three-pole operation Auto-reclose test facility, single and

    three-pole operation Measurement of the respective con-

    tent of the active and reactive compo-nent of the earth current during anearth fault.

    Non-volatile storage of operational re-cordsThe 7SA511 provides all the data neces-sary to analyze the operational perfor-mance of the relay following a networkfault. The following recording functionsare all secure from interruption of theauxiliary power supply. Real-time clock

    A standardized, battery-backed, real-time clock is available which may besynchronized via a binary input or viathe system serial interface. The clocktime can be set via PC and IEC8705103 interface. All events are re-corded with a date and time tag.

    Fault indicationsThe operational records (e.g. faulttype, distance-to-fault etc.) for the lastthree fault operations are available viathe integrated control panel. The lastfour operational records are availableat the PC interface via DIGSI.

    Operational indicationsAll signals not associated directly withthe fault are stored in the operationalindication buffer.

    Earth-fault protocol (isolated networks)Relays with the optional isolated/com-pensated network earth-fault detectionfunction store, record and fault detailsin a separate memory block.

    Tripping statisticsFor each pole of a circuit-breaker it ispossible to record the progressive totalof tripping and opening operations aswell as the summation of the breakingcurrent.

    Automatic data displayAn operation mode may be selected inwhich two (normal service) measuredvalues are continuously updated on theintegrated LCD display. Following afault operation two (previously se-lected) stored fault information valuesare displayed.

    User-definable binary inputs and timestages, external trippingThere are four binary inputs available forrecording of binary signals, e.g. signalsfrom other protective devices. These in-puts are stored in the operational indica-tions buffer and can be passed to alarmrelays, LEDs and the SINAUT LSAsubstation control and protection.The relay is also equipped with twoparameterizable time stages. The startand reset signals can be marshalled tobinary inputs; the timing period can bemarshalled to alarm relays and LEDs.Pickup and reset delay can be set acrossa broad range. External use of additionaltime relays for special switching require-ments will in future be dispensed with.By coupling in from outside via binary in-puts, phase-selective remote tripping cantake place with and without automaticreclosing.

    SIPROTEC 7SA511 distance protection relay (Version V3)

  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 1997 5

    Technical data

    Input circuits Rated current NRated voltage VNRated frequency fNThermal overload capability in v.t. circuits, continuous

    in c.t. circuits, continuousfor 10 sfor 1 s

    Dynamic overloadBurden v.t. circuits

    c.t. circuits at N = 1 Aat N = 5 A

    Residual current input 1 A(isolated network option)

    1 or 5 A80 to 125 V AC 50 or 60 Hz140 V AC 4 x N30 x N100 x N250 x NApprox. 0.1 VAApprox. 0.05 VAApprox. 0.2 VAApprox. 0.05 VA

    Voltage supplyvia integrated DC/DC converter

    Rated auxiliary voltage Vaux

    Permissible tolerancePermissible max. ripple (pk-pk)Power consumption quiescent

    energizedMax. operating time after auxiliary voltage drop

    24, 48 V DC 60, 110, 125 V DC 220, 250 V DC20 to +15 %12 %Approx. 16 WApprox. 26 W50 ms at Vaux 110 V

    Binary inputs Number of inputsVoltage rangeCurrent input

    10 (marshallable)24 to 250 V DC, adjustable in 4 rangesApprox. 1.7 mA

    Indication contacts Number of relayswith 1CO contact eachwith 1NO contact each

    Switching capacity make/breakSwitching voltagePermissible current continuous

    11 (marshallable)6520 W/VAMax. 250 V AC/DC 1 A

    Heavy duty contacts Number of relays, with 2 NO contacts eachSwitching capacity make

    breakSwitching voltagePermissible current continuous

    0.5 s

    5 (marshallable)1 000 W/VA30 W/VAMax. 250 V AC/DC 5 A30 A

    LED displays Ready for operation greenFault indication redMarshallable LEDs red

    1114

    Serial interfaces Operator interface

    Baud rateSystem interface

    Baud rateElectrical connection

    Insulation transmission distancefibre-optic connection

    optical wavelengthpermissible line attenuationtransmission distance

    On the front panel, not isolated, suitablefor connection of a PC1 200 to 19 200 BdControl system interface, isolated, suitablefor coupling to a central unit1 200 to 19 200 BdSimilar to V.24/V.28 to CCITT or RS232C toEIA, 2kV isolated, cable with 2 core pairs,with individual and common screening e.g.LIYCYCY/2 x 2 x 0.25 mm2

    Max. 1 kmIntegrated FSMA connector for fibre-opticconnection820 nmMax. 8 dB (for 62.5/125 m fibre)Max. 1.5 km

    Construction Housing, dimensionsWeight panel flush mounting/cubicle mounting

    panel surface mountingDegree of protection according to EN 60 529 housing

    terminals

    7XP20, see dimension drawingsApprox. 9.5 kgApprox. 11 kgIP 51IP 21

    SIPROTEC 7SA511 distance protection relay (Version V3)

  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 19976

    Technical data

    CEconformity, standards This product is in conformity with the directives of the Council ofthe European Communities on the approximation of the laws ofthe Member States relating to the electromagnetic compatibility(EMC Council Directive 89/336/EEC) and to the use of electricalequipment within defined voltage ranges (lowvoltage directive73/23/EEC). The product conforms with the international standardIEC 255 and the national standard DIN 57 435 part 303 (corres-ponding to VDE 0435 part 303).The relay is designed for use in an industrial environment, forinstallation in standard relay rooms and compartments so thatwith proper installation electromagnetic compatibility (EMC) isensured.

    Conformity is proved by tests performedby Siemens AG in line with article 10 of theCouncil Directives in accordance with thegeneric standards EN 50081 and EN 50082for the EMC directive 89/336/EEC and withstandard EN 602556 for the lowvoltagedirective.

    Insulation testsIEC 2555, DIN 57 435 part 303

    Highvoltage test (routine test), except d.c. voltage supply inputHighvoltage test (routine test), only d.c. voltage supply inputImpulse voltage test (type test), all circuits, class III

    2 kV (rms), 50 Hz2.8 kV DC5 kV (peak), 1.2/50 s, 0.5 J,3 positive and 3 negative shots at intervalsof 5 s

    EMCtests; immunity (type test)Standards: IEC 2556, IEC25522

    (international product standard)EN 500822 (generic standard)VDE 0435 part 303 (Germanproduct standard)

    High frequency test with 1 MHz interferenceIEC 255221, class III and VDE 0435 part 303, class IIIElectrostatic dischargeIEC 255222, class III and IEC 100042, class IIIRadiofrequency electromagnetic field, nonmodulatedreport IEC 255223, class IIIRadiofrequency electromagnetic field, amplitude modulatedIEC 100043, class IIIRadiofrequency electromagnetic field, puls modulatedENV 50204, class IIIFast transientsIEC 255224 class III, IEC 100044 class IV

    Conducted disturbances induced by radiofrequency fields, amplitude modulatedIEC 100046, class IIIPower frequency magnetic fieldIEC 100048, class IVIEC 2556

    2.5 kV (peak), 1 MHz, = 15 s,400 shots/s, duration 2 s4 / 6 kV contact discharge, 8 kV air dis-charge, both polarities, 150 pF, Rl = 330 10 V/m, 27 to 500 MHz

    10 V/m, 80 to 1 000 MHz, AM 80 %, 1 kHz,

    10 V/m, 900 MHz, repetition frequency 200 Hz, duty cycle 50 %2 kV, 5/50 ns, 5 kHz, burst length = 15 ms,repetition rate 300 ms, both polarities, Rl = 50 duration 1 min10 V, 150 kHz to 80 MHz, AM 80 %, 1 kHz,

    30 A /m, continuous, 300 A /m for 3 s, 50 Hz0.5 mT; 50 Hz

    EMCtests; emission (type test)Standard: EN 50081* (European generic

    standard)

    Conducted interference voltage, auxiliary voltageCISPR 22, EN 55022 and VDE 0878 part 22Interference field strength CISPR 11, EN 55011 and VDE 0875 part 11

    150 kHz to 30 MHz, class B

    30 to 1 000 MHz, class A

    Climatic stress tests permissible ambient temperature during serviceduring storageduring transport

    permissible humidity

    5 to +55 C25 to +55 C25 to +70 Cmean value per year 75 % relative humi-dity, on 30 days per year up to 95 % rela-tive humidity, condensation not permissible

    Mechanical stress testsIEC 255211, IEC 682

    permissible mechanical stress during service

    during transport

    10 to 60 Hz, 0,035 mm amplitude60 to 150 Hz, 0,5 g acceleration5 to 8 Hz, 7,5 mm amplitude8 to 150 Hz, 2 g acceleration

    SIPROTEC 7SA511 distance protection relay (Version V3)

  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 1997 7

    Technical data (continued)

    Distance protection Setting rangesEarth-fault detection

    Earth current E/N Step 0.01 0.25 to 1Displacement voltage

    1 V1 V

    VE ( 3 V0, earthed network)VE ( 3 V0, isolated network)

    2 to 100 V10 to 100 V

    Overcurrent fault detection ()Overcurrent PH/N 0.01

    Impedance fault detection (Z) 1 VPhase-to-earth voltage VPHE () 1 VPhase-to-phase voltage VPHPH (>) 1 VPhase-to-phase voltage VPHPH () 1 V

    Distance measurementCharacteristicDistance zones

    Reactance reach X 0.01 Resistance tolerance R

    for phase-to-phase faults 0.01 for phase-to-earth faults 0.01

    Time stages

    Timer range 0.01 sResidual compensation

    0.1 to 4

    Polygonal0.1 to 200 1)0.1 to 200 1)0.1 to 200 1)

    30 to 800.1 to 4

    20 to 70 V20 to 70 V40 to 130 V40 to 130 V

    Polygonal5, 2 as zone extensions and all zones maybe set in the forward, reverse or in bothdirections (non-directional)0.05 to 130 1)

    0.05 to 65 1)0.05 to 130 1)

    7 for multi-phase faults3 for single-phase faults0 to 32 s or infinite

    0.01XEXL

    ,RERL

    7 to 7

    Parallel line mutual compensation0.01XM

    XL,

    RMRL

    7 to 7

    Directional determinationfor all failure types

    Directional sensitivity

    with externally generated short-circuit trip-ping currents and voltage memoryDynamically unlimited

    Operating timesMinimum trip contactReset time

    Tolerances

    23 msApprox. 30 ms

    Measurement tolerances according to VDE 0435, Part 303 for sinusoidal quantities

    for impedance fault detection XX 5 % for 30o 90o

    RR 10 % for 0o 60o

    for distance measurement XX 5 % for 30o 90o

    RR 5 % for 0o 60o

    for amplitude measurementTimer accuracy

    5 %1 % of set value or 10 ms

    1) Impedance settings referred to N = 1 A; at N = 5 Athese values are 5 times the secondary values.

    SIPROTEC 7SA511 distance protection relay (Version V3)

  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 19978

    Technical data (continued)

    Fault locator Distance to fault

    Start signal

    Reactance per unit length Step 0.001 /kmParallel line compensationMeasurement tolerance (according to VDE 0435, Part 303for sinusoidal quantities)

    Secondary , primary , km or % of linelengthTrip output, fault detector reset or binaryinput0.01 to 5 /kmSelectable; option2.5 % line length for 30 k 90 andVK/VN 0.1 without intermediate infeed

    Power swing(devices with impedance starting Z/N Step 0.01Earth current E >/N 0.01High set o/c PH /N 0.01Timers tI>, tIE>, tI 0.01 s

    Measurement tolerance (according to VDE 0435, Part 303for sinusoidal quantities)

    0.1 to 40.1 to 40.5 to 9.990 to 32 s or infinite5 %

    Universal teleprotection interface ModesTripping

    Comparison

    Pilot wire protectionReverse interlock

    Tripping via fault detectionTripping via zone extension (POTT/PUTT)Signal comparisonDirectional comparisonUnblocking with zone extensionUnblocking with trippingBlocking

    Earth-fault detection(isolated networks)

    Earth-fault detection using Step 1 Vresidual displacement voltage VE ( 3 V0)

    10 to 100 V( )

    Faulted phase detectionVPHE < (faulted phase) 1 VVPHE > (unfaulted phase) 1 V

    Measurement tolerance (according to VDE 0435, Part 303for sinusoidal quantities)Directional determination

    Measuring principleEarth-fault current E> (active/reactive ), 1 mAcable-type c.t. angle error correction 0.1Measurement tolerance (according to VDE 0435, Part 303 for sinusoidal quantities)

    10 to 100 V10 to 100 V5 % of set value

    Active/reactive power measurement3 to 1 000 mA0 to 5 in 2 operating points10 % of set value

    Sensitive earth-fault protection(highresistance faults in earthed networks)

    Directional earth-fault protection with back-up definite-time non-directional overcurrent functiong

    Earth-current fault detection E >/N Step 0.010.1 VResidual displacement voltage VE ( 3 V0)

    0.1 to 41 to 10 V

    Directional determinationCarrier signallingOperating times

    Shortest tripping timeCurrent reversal guard timeTripping time delay 0.01 sTimer tolerance

    Undirectionalearth-fault protection with inversetime characteristic

    Characteristics according to IEC 255 3,or BS142

    Pick-up value E > N 0.01Time multiplier tIE 0.01 sTolerances

    Current pick-upOperating time

    with E and VEDirectional comparison

    Approx. 30 msApprox. 30 ms0 to 32 s or ineffective1 % of set value or 10 ms

    Normal inverseVery inverse, Extremely inverse0.1 to 40 to 32 s

    5 to 15 % of set value5 % 15 ms for 2 (/E>) 20 and 1 s tIE 30 s

    SIPROTEC 7SA511 distance protection relay (Version V3)

  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 1997 9

    Technical data (continued)Overload protection Setting ranges

    Factor k to IEC 255 8 Step 0.01Time constant 0.1 minEvaluation of thermal replicaTemperature warning stage Alarm /Off 1 %Current warn stage Alarm/ k N 0.01

    0.1 to 41 to 999.9 minmax, mean, with max50 to 100 %0.1 to 4

    Tripping time characteristic t n2 2pre

    2 ( k N )2

    Reset conditions/Off/AlarmAlarm

    Tolerances

    Approx. 0.99Approx. 0.99Approx. 0.99Class 10 % to IEC 2558

    Auto-reclose Auto-reclose operation counterModesActive times for RAR and DAR cycle Step 0.01 sDead times in RAR cycle 0.01 sDead times in DAR cycle 0.01 sReclaim times 0.01 sClose command duration 0.01 s

    Up to 10only 1-pole, only 3-pole, 1 or 3-pole0.01 to 320 s0.01 to 320 s0.01 to 1 800 s0.5 to 320 s0.01 to 32 s

    Synchronism check Modes for connectingLine dead/busbar liveLine live/busbar deadSynchronism

    Permissible voltage difference V Step 1 VPermissible frequency difference f 0.01 HzPermissible angle difference 1

    V1< / V2>V1> / V2 / V2>1 to 50 V0.01 to 1 Hz1 to 60

    Fault recording Measured valuesStarting signal

    Recording managementMaximum number of simultaneously available recordsSampling intervalMax. recording period (sum of all records)

    at 50 Hzat 60 Hz

    Pretrigger time Step 0.01 sPostfault time 0.01 sMax. period for one record 0.01 s

    iL1, iL2, iL3, iE, vL1, vL2, vL3, vETripping, fault detection, binary input, con-trol panel, PCDynamic ring buffer store, battery buffered820 sampling values per network period

    5 s4.2 s0.05 to 0.5 s0.05 to 0.5 s0.3 to 5 s

    Additional functions Operating values forCurrentVoltagePowerFrequencyEffective range

    Earth current during earth faults in isolated networksOverload valuesTolerance

    L1, L2, L3VL1L2, VL2L3, VL3L1, VL1, VL2, VL3P, Qf0 to 240 % N, 0 to 120 % VN,0 to 120 % PN, 96 to 104 % fNea, er / trip2 % of respective rating

    SIPROTEC 7SA511 distance protection relay (Version V3)

  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 199710

    Selection and ordering dataOrder No.

    Distance protection relay 7SA511 A

    Rated current at 50/60 Hz1 A5 A

    15

    Rated auxiliary voltage24, 48 V DC60, 110, 125 V DC220, 250 V DC

    245

    ConstructionFor panel surface mountingFor panel flush mounting/cubicle mountingFor panel flush mounting/cubicle mounting without glass cover

    BCE

    Functions/languageV3 with IEC 8705103 protocol, overload protection and with synchrocheck (option)Operator language GermanOperator language English

    67

    Fault detectionWith overcurrent ( )With impedance ( Z< )/Overcurrent ( )/Voltage-dependent overcurrent (V), settable optionWith voltage-dependent overcurrent (V)/Overcurrent ( ), settable option

    123

    Options AWithout wattmetric earth-fault detection without FLPCWith wattmetric earth-fault detection without FLPCWithout wattmetric earth-fault detection with FLPC

    012

    Serial system interfaceWithoutIsolated, V.24/RS232CIntegrated fibreoptic interface

    ABC

    Options BWithout AR without parameter changeover facility, without synchronism checkWith AR, 3-pole without parameter changeover facility, with synchronism checkWith AR, 1 and 3-pole without parameter changeover facility, with synchronism checkWithout AR with parameter changeover facility, with synchronism checkWith AR, 3-pole with parameter changeover facility, with synchronism checkWith AR, 1 and 3-pole with parameter changeover facility, with synchronism check

    ABCEFG

    Options CWithout power swing without earth-fault protection for earthed networksWith power swing1) without earth-fault protection for earthed networksWithout power swing with earth-fault protection for earthed networksWith power swing1) with earth-fault protection for earthed networks

    0123

    FLPC Fault location with parallel line mutual compensationAR Auto-reclose

    Operation software (German and English are standard, other languages on request)

    DIGSI program (suitable for all protection relays 7UM..., 7UT..., 7SJ..., 7SA..., ...) GermanEnglish

    Test version: GermanEnglish

    Connecting cables for protection relays (25-pin) PC (9-pin); (other variations supplied on request)

    7XS50200AA007XS50201AA007XS50210AA007XS50211AA007XV51002

    Documentation

    German: Katalogblatt LSA 2.2.11: Abzweigschutz SIPROTEC 7SA511 (Version V3)Handbuch: Abzweigschutz SIPROTEC 7SA511 (Version V3)

    E50001K5712A211A2C53000G1100C983

    English: Catalog LSA 2.2.11: SIPROTEC 7SA511 distance protection relay (Version V3)Manual: SIPROTEC 7SA511 distance protection relay (Version V3)

    E50001K5712A211A27600C53000G1176C983

    1) Only available with impedance starting (Z

  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 1997 11

    Function scope of special device ver-sionsSpecial device versions can be suppliedfor specific applications. The followingfunctions are available in all versions:Fault location, thermal overload protec-tion, load values, overcurrenttime anddefinite time overcurrent protection,

    current, voltage, active power, reactivepower, frequency measurement, switch-ing statistics with summation of inter-rupted currents per pole, integratedclock, batterybuffered signal memoryand fault recording memory.

    All equipment variants can be used inearthed and in compensated/isolated net-works. In accordance with the functionalscope of the individual equipment vari-ants, the main applications are stated inthe following table.

    Functions VersionsBasicversion

    Medium voltage High voltageversion Isolated,

    compen-sated,earthed net-work

    Earthed net-work

    Isolated/compen-sated net-work

    Earthed net-work

    Distance protection with 3 + 2 zones, 7 time stepsDirection detection with voltage or sound phase polarizationOvercurrent starting

    +++

    +++

    +++

    +++

    +++

    V/ startingImpedance startingFault location

    +

    ++

    ++

    +++

    +++

    Parallelline mutual compensation for fault locationPower swingTeleprotection interface

    +

    +

    +

    +++

    +++

    Emergency definite time overcurrent protection for measuring voltage failureThermal overloadEarthfault detection in non-earthed network

    ++

    +++

    ++

    ++

    ++

    Backup earth-fault protection (earthed network)Reclosing, 3-poleReclosing, 1/3-pole

    +

    ++

    +

    +++

    Synchronism checkProtection for switchontofaultFault recording

    ++

    +++

    +++

    +++

    +++

    Parameter changeover facilityTransient earthfault detectionFault location output, analog/BCD

    oo

    +oo

    +oo

    +oo

    +oo

    + Function included Function not includedo Function possible with add-on

    SIPROTEC 7SA511 distance protection relay (Version V3)

  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 199712

    Selection and ordering data for the special device versionsOrder No.

    Distance protection relay 7SA511 A

    Rated current at 50/60 Hz1 A5 A

    15

    Rated auxiliary voltage24, 48 V DC60, 110, 125 V DC220, 250 V DC

    245

    ConstructionFor panel surface mountingFor panel flush mounting/cubicle mountingFor panel flush mounting/cubicle mounting without glass cover

    BCE

    LanguageOperating language GermanOperating language English

    67

    Special device versionsBasic versionMediumvoltage version: isolated, compensated, earthed network (sensitive current transducer for E)

    earthed networkHighvoltage version: isolated, compensated network

    earthed network

    13322

    01022

    AFFFG

    00213

    Serial interfaceWithoutIsolated, V.24/RS232CIntegrated fibreoptic interface

    ABC

    Accessories for the distance protection relay 7SA511Order No.

    Transient earth fault relay 7SN7100 A 0 0

    Rated auxiliary voltage100 to 110/220 V, AC, 50 Hz24 V DC48 V DC60 V DC110/125 V DC220/250 V DC

    012345

    ConstructionFor panel surface mountingFor panel flush mounting/cubicle mounting

    BC

    Order No.Fault location output equipment 7SM7 0 0 0 0

    Device typeAnalog output unitBCD output unit

    01

    Rated auxiliary voltage24 V DC48 V DC60 V DC110/125 V DC220/250 V DC

    12345

    ConstructionFor panel surface mountingFor panel flush mounting/cubicle mounting

    BC

    Binary inputFor BCD output unit 7SM71: no binary inputFor analog output unit 7SM70: 24/48/60 V DC

    110/125/220 V DC

    AAC

    SIPROTEC 7SA511 distance protection relay (Version V3)

  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 1997 13

    SIPROTEC 7SA511 distance protection relay (Version V3)

    Fig. 5Connection diagram for distance protection relay 7SA511 (Version V3), state of development FF

    L1 L2 L3

    Remote reset LED

    V.T. mcb trip

    CB Aux. contact(Position ON)

    Manual close

    Carrier receive

    Carrier receivefaultyCB ready

    AR block

    AR ON

    AR OFF

    DC power supply

    L1

    L2

    L3

    CB Alarm suppressed

    Group annunciation 1Supervision of measuredquantitiesDevice operative(Alarm contact)

    General trip signal

    Reverse direction

    Reclose command

    General fault detec-tion

    Trip command L1

    Trip command L3

    Optional V.24 interface,

    wire-wound fibre optic interface

    Trip command L2

    TxDMT

    L1

    L2

    L3

    E1)

    RxDMR

    Carrier send

    AR inoperative

    Fault detection L1

    Fault detection L2

    Fault detection L3

    Fault detection E

    Binary inputs, alarm relays, command relays and LEDs are freely selectable1) option dependent sensitivity of E input:

    normal sensitivity or high sensitivity for earthfault detection

    in compensated or isolated systems2) Vx input usable depending on function

    en voltage 2 voltage for synchronism check

    L1L2L3

    E

    V L1V L2V L3V N

    V L1

    V L2

    V L3V N

    V x2)

    V xn

    V n

    V e

    Version for panel surface mounting

    L+L

    7SA511

    6B4

    8B2

    6B17B2

    7B18B1

    6B27B38B36B37B48B4

    Alarm relay 1

    Alarm relay 2

    Alarm relay 3

    Alarm relay 4

    2A2

    3A1

    3A2

    1A1

    1A2

    8A28A1

    4A1

    4A2

    Binaryinput 1

    4A3

    4A4

    Commandrelay 3

    Alarm relay 7

    2A1

    1D1

    1D2

    8D38D4

    7D1

    7D37D4

    6D16D2

    6D36D4

    6A2

    6A36A1Alarm relay 5

    3C43C2Alarm relay 6 3C3

    3D22D2

    Alarm relay 8 3D32D3

    Alarm relay 9 3D42D4

    3C12C1

    Alarm relay 10

    3D12D1

    Alarm relay 11

    8A48A37A27A17A47A3

    8D28D1

    7D2

    4B14B2

    Binaryinput 2Binaryinput 3Binaryinput 4Binaryinput 5Binaryinput 6Binaryinput 7Binaryinput 8

    Binaryinput 9Binaryinput 10

    5A35A1

    5A25A4

    Commandrelay 2

    Commandrelay 4

    Commandrelay 5

    4D34D1

    4D24D4

    4C34C1

    4C24C4

    5D35D1

    5D25D4

    5B35B1

    5B25B4

    Commandrelay 1

    3B3

    2B3

    3B2

    3B1

    2C4

    2C3

    2C2

    1C1

    1C2

    1

    3

    2

    4

    11

    12

    10

    9

    13

    14

    5354

    51

    52

    7978

    81

    8382

    8584

    8786

    555657585960

    6162

    80

    1516

    Version for panel flush mounting/cubicle mounting

    5

    6

    7

    8

    88

    67

    6368

    6564

    667170699089

    91

    9392

    969594

    3536

    3738

    3940

    4142

    4344

    9772

    7398

    4520

    2146

    4722

    2348

    4924

    2550

    9974

    75100

    76

    77

    Fibreoptic interfaceCoupling to central unit

    V.24 interface (RS232C), 2 kVisolatedCoupling to central unit

  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 199714

    Dimension drawings in mm

    Fig. 67SA511 (Version V3) with housing 7XP20402 (for panel flush mounting/cubicle mounting)

    Front view Side view Panel cutout

    206.5180

    221

    7.313.2

    255.

    8

    245

    266

    231.5

    30 29.5

    1.5

    5.4

    225

    220

    244

    172

    10

    Fibreoptic interface

    Diam. 5 or M4

    Diam. 6

    Fig. 77SA511 (Version V3) with housing 7XP20401 (for panel surface mounting)

    Front view Side view

    260

    27 29.526

    6

    71Z

    280

    344

    234

    219

    Fibreoptic interface

    126

    1.539

    40

    cross section 20 x 60(without paint)

    10051 75

    5025

    76

    7.5

    . . . . .. . . . .

    . . . . .. . . . .

    Detail Z:

  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 1997 15

    Conditions of Sale and DeliverySubject to theGeneral Conditions of Supply and Deliveryfor Products and Services of theElectrical and Electronic Industryand to any other conditions agreed uponwith the recipients of catalogs.

    The technical data, dimensions and weights are subject to change unlessotherwise stated on the individual pagesof this catalog.

    The illustrations are for reference only.

    We reserve the right to adjust the pricesand shall charge the price applying onthe date of delivery.

    Export RegulationsIn accordance with present provisions ofthe German Export List and the US Com-mercial Control List, export licences arenot required for the products listed in thiscatalog.

    An export licence may however be requi-red due to countryspecific application ofthe products.

    Relevant are the criteria stated in the de-livery note and the invoice.

    Subject to change without notice.

    TrademarksAll product designations used are trade-marks or product names of Siemens AGor of other suppliers.

    DimensionsAll dimensions in this catalog are given inmm.

    Siemens online!The Power Transmission and DistributionGroup can also be found in the Internet:

    http://www.ev.siemens.de

    Responsible for

    Technical contents: Michael Claus,Siemens AG, EV S V13, Nrnberg

    General editing: Roland Reichel/Claudia KhnSutiono,Siemens AG, EV S SUP22, Nrnberg/EV BK T, Erlangen

    Conditions of Sale and Delivery Export Regulations Trademarks Dimensions

    A 9.91 a

  • Overcurrent and Distance Relays

    Siemens LSA 2.1.11 . March 199716Siemens Aktiengesellschaft

    BereichEnergiebertragung und -verteilungGeschftsgebiet SekundrsystemePostfach 48 06D-90026 Nrnberg

    Order No.: E50001-K5712A211-A27600Printed in GermanyKG K 0397 3.0 SD 16 En 321 538 6101/U540

    PowerTransmissionand Distribution