Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
Copyright © Lower Colorado River Authority and SEL 2016
A Current Story –When Primary Met Secondary
Genardo CorpuzLower Colorado River Authority
Swagata Das and Ariana HargraveSchweitzer Engineering Laboratories, Inc.
1 2I IIRT
k+
=1 2IOP I I= +
Percentage-Restrained Differential
IOP
IRTExternal
Internal
Slope
Restrain
Operate
Minimum Operate Current
Unrestrained Pickup
Protected Zone
87I1 I2
Know Equipment Being Protected
Bϕ
H3J1 J2
Aϕ
H2
Cϕ
H1
Control Cabinet
Digital Relay
CT Secondary Wiring at Junction Box
One-Line Diagram
Internal Inspection Reveals Damage onH3 Bushing and Its CT Secondary Wiring
Pitting and Carbon
Deposits From Arc
Junction Box J1 Scorched
Fault Root Cause
Why Did Bus Relay Operate for External Fault?
Transformer Relay Filtered Event Report 200100
0–100–200
531
–1–3–5503010
–10
87UTRIP
Current (A secondary)
Current (A secondary)
Operate Current (pu of tap)
2.0 3.2 4.4 5.6 6.8 7.0 8.2 9.4 10.6 11.8Time (cycles)
IAW1IBW1ICW1
IAW2IBW2ICW2
IOP1_PUIOP2_PUIOP3_PUU87P
Backup Overcurrent Relay Raw Event Report300
200
100
0
–100
–200
–300 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0Time (cycles)
Cur
rent
(A s
econ
dary
)
IA_SECIB_SECIC_SEC
A/D Limit
A/D Limit
Bus Relay Raw Event Report2010
0–1015
5
–5–15300
100
–100
–30087U
TRIP12 3 4 5 6 7 8 9 10
Time (cycles)
IAW4IBW4ICW4
IAW3IBW3ICW3
CB1 Current (A secondary)
CB2 Current (A secondary)
T1 High-Side Current
(A secondary)
IAW1IBW1ICW1
IB Phasors at Cycle 3, Current In = Current Out
IB Phasors at Cycle 4, Current In ≠ Current Out
10,500∠–98.1°
Bus Relay Operate and Restraint Quantities70
50
30
10
–10453525155
–5
87U87U2
TRIP12 3 4 5 6 7 8 9
Time (cycles)
Operate Current (pu of tap)
Restraint Current (pu of tap)
IOP1IOP2IOP3U87P
IRT1IRT2IRT3
300
200
100
0
–100
–200
–30011.27 11.29 11.31 11.33 11.35 11.37
Time (seconds)
IB_TransformerIB_Bus
Cur
rent
(A s
econ
dary
)
True Sequence of Events
Top Gear Towing Challenge
Primary Currents Can Cause Thermal DamageCurrent Input Ratings
• 15 A continuous
• 500 A for 1 second
• 625 A / 1,250 A for 1 cycle
Primary Voltages Can Cause Dielectric Failure
Current inputs rated to withstand
2,500 Vac
“Spark Gap Effect” Saves the Day
Ground Wire
80 kV
• Respect power system• Request visual inspection during installation• Analyze event reports, even if root cause is known Download all event types
Implement automatic event retrieval system
Synchronize all relays to GPS time source
Recommendations
• Primary system exposure can damage relays Inspect for damage, perform meter and dielectric tests
• Settings expertise alone is not enough Know equipment you are protecting
Recommendations
Questions?