Copyright is owned by Constructive Details Ltd. Copying or reproduction of the contents is not permitted without the consent of Constructive Details Ltd. Constructive Details Ltd Bucknalls Lane Watford Hertfordshire WD25 9BA t: + 44 (0)1923 665300 f: + 44 (0)1923 665301 e: [email protected] w: www.constructivedetails.co.uk ©2015 A handbook of thermal bridging details incorporating InstaClad insulated thermal profile solutions Book 8 — Cold bridging solutions for insulating on retrofit External Wall Insulation. Prepared for InstaFibre Ltd by the BBA Issued: April 2015

A handbook of thermal bridging details incorporating InstaClad

Embed Size (px)

Citation preview

Page 1: A handbook of thermal bridging details incorporating InstaClad

Page 1 of 9

Copyright is owned by Constructive Details Ltd.Copying or reproduction of the contents is not permitted without the consent of Constructive Details Ltd.

Constructive Details Ltd

Bucknalls LaneWatfordHertfordshire WD25 9BA

t: + 44 (0)1923 665300f: + 44 (0)1923 665301

e: [email protected] w: www.constructivedetails.co.uk ©2015

A handbook of thermal bridging details incorporating InstaClad insulated thermal profile

solutions

Book 8 — Cold bridging solutions for insulating on retrofit External Wall Insulation.

Prepared for InstaFibre Ltd

by the BBA

Issued: April 2015

Page 2: A handbook of thermal bridging details incorporating InstaClad

Page 2 of 9

Table of Contents

List of Constructive Details

How to use this handbook

Details CD0107 - CD0109

Checklist

This handbook was prepared for InstaFibre Ltd and it provides thermal bridging junction details for external wall insulations. The drawings provided are for typical details and show all the elements essential in achieving the calculated c-values. All other site requirements and all relevant building regulations must be taken into consideration when implementing the details.

The detail in this handbook includes drawings of the junction, c-values calculated by an experienced thermal modeller and a process checklist for use on site to facilitate the achievement of the calculated c-values.

A more detailed description for each section of a Constructive Detail can be found in the original Guidance Note which is located on the first page of each Constructive Detail.

Purpose of the handbook

Page 3: A handbook of thermal bridging details incorporating InstaClad

Page 3 of 9

Detail number Detail title Page SAP Ref

CD0107 Thermo-Bead 4 E4

CD0108 Thermo-Trac 6 E5

CD0109 Thermo-Pro Fascia 8 E10

The details have been prepared taking into consideration a range of wall constructions used in the UK over the last 50 years. From this, it was deemed appropriate to use a 230 mm wall with a thermal conductivity of 3.49 W·m–1·K–1.

The c-values are provided for different thicknesses of insulation. For each band, the c-value is calculated for the worst case after considering the effect of thickness and conductivity of insulation independently. This c-value can therefore be taken for the complete range of thicknesses quoted.

In all of the details the wall finish drawn is 13 mm dense plaster. This was chosen for consistency and also as it is a common construction method.

A series of tips on interpreting the information in each Constructive Detail, is given below, starting from the first to the last page.

THERMO-BEAD THERMO-PRO FASCIA THERMO-TRAC

Please refer to www.constructivedetails.co.uk for full terms and conditions.

You may not edit or amend the contents or format or otherwise incorporate them into any other publication or work or media.

List of Constructive DetailsList of constructive details

Terms and conditions

How to use this handbook

Page 4: A handbook of thermal bridging details incorporating InstaClad

Page 4 of 9

Notes• The External Wall Insulation System (EWIS) conductivity is between 0.030 W·m–1·K–1 - 0.044 W·m–1·K–1 .

• eachresultwascalculatedusinganinternalfinishof13mmdenseplasterwithaconductivityof 0.57 W·m–1·K–1 and an external basecoat and mesh of 6 mm with a conductivity of 1.0 W·m–1·K–1

• the maximum length of the external window reveal must be 100 mm

• a minimum window frame width of 40 mm must be used

• a50mmfixingisusedat300mmcentresalongthelengthoftheThermo-Bead.

Solid Externally Insulated Wall

Jamb with InstaClad Thermo-Bead

CD0107

This indicative guidance illustrates good practice for design and construction with respect to achieving thermal performance and air barrier continuity only. It must be implemented taking due regard of site conditions and all other requirements imposed by Building Regulations.

Calculated ψ-values for this detail

All values are in W·m–1·K–1

EWIS Insulation between 90 mm - 160 mm

EWIS Insulation between 161 mm - 230 mm

EWIS Insulation between 231 mm - 300 mm

c-value (W·m–1·K–1)

Temperature Factor

c-value (W·m–1·K–1)

Temperature Factor

c-value (W·m–1·K–1)

Temperature Factor

No Thermo-Bead 1.006 0.71 1.025 0.71 1.036 0.71

Thermo-Bead 0.208 0.93 0.218 0.93 0.223 0.93

10 mm Aerogel

10 mm overlapwiith frame

internalwindowreveal

40 mm frame

externalwindowreveal

Page 5: A handbook of thermal bridging details incorporating InstaClad

Page 5 of 9

Notes (include details of any corrective action)

CD0107

Guidance checklist

Date: ........................................... Site manager/supervisor: ......................................................................................

Site name: ........................................................................................... Plot No: ........................................................

Ref. Item Yes/No Inspected (initials and date)

1. Is the EWIS insulation thickness between 90 mm - 300 mm?

2. Is the EWIS insulation conductivity between 0.030 - 0.044 W·m–1·K–1 ?

3. Hasaninternalfinishbeenapplied?

4. HasanexternalfinishbeenappliedtotheEWISinsulation?

5. HastheThermo-beadinsulatedprofilebeenused?

6. Is the length of the external window reveal < 100 mm?

7. Is the window frame width 40 mm?

8. Arethe50mmfixingsappliedat> 300 mm centres?

.......................................

.......................................

.......................................

.......................................

.......................................

Solid Externally Insulated Wall

Jamb with InstaClad Thermo-Bead

Copyright is owned by Constructive Details Ltd.Copying or reproduction of the contents is not permitted without the consent of Constructive Details Ltd.

Constructive Details Ltd

Bucknalls LaneWatfordHertfordshire WD25 9BA

t: + 44 (0)1923 665300f: + 44 (0)1923 665301

e: [email protected] w: www.constructivedetails.co.uk ©2015

.......................................

.......................................

.......................................

Page 6: A handbook of thermal bridging details incorporating InstaClad

Page 6 of 9

Notes• The External Wall Insulation System (EWIS) conductivity between 0.030 W·m–1·K–1 - 0.044 W·m–1·K–1 .

• eachresultwascalculatedusinganinternalfinishof13mmdenseplasterwithaconductivityof 0.57 W·m–1·K–1 and an external basecoat and mesh of 6 mm with a conductivity of 1.0 W·m–1·K–1

• maximumconcretefloorslabthicknessof150mmwithaconductivityof1.75W·m–1·K–1

• external wall insulation to be a maximum of 150 mm from ground level

• ensure the dpm provided with the Thermo-Trac is applied as per manufacturers instructions.

Solid Externally Insulated WallConcretegroundbearingfloor—Insulation below slab with InstaClad Thermo-TracCD0108

This indicative guidance illustrates good practice for design and construction with respect to achieving thermal performance and air barrier continuity only. It must be implemented taking due regard of site conditions and all other requirements imposed by Building Regulations.

Calculated ψ-values for this detailThese results can be achieved with a wall U value < 0.30 W·m–1·K–1.

All values are in W·m–1·K–1

Floor U value between 0.08 and 0.11 W·m–2·K–1

Floor U value between 0.12 and 0.19 W·m–2·K–1

Floor U value between 0.20 and 0.30 W·m–2·K–1

c-value (W·m–1·K–1)

Temperature Factor

c-value (W·m–1·K–1)

Temperature Factor

c-value (W·m–1·K–1)

Temperature Factor

No Thermo-Trac 1.515 0.59 1.487 0.59 1.426 0.59

Thermo-Trac 1.304 0.64 1.269 0.64 1.189 0.65

Thermo-Tracmaximumfloorslab of 150 mm

insulation below slab

damp proof membrane (dpm)

Page 7: A handbook of thermal bridging details incorporating InstaClad

Page 7 of 9

Notes (include details of any corrective action)

CD0108

Guidance checklist

Date: ........................................... Site manager/supervisor: ......................................................................................

Site name: ........................................................................................... Plot No: ........................................................

Ref. Item Yes/No Inspected (initials and date)

1. Is the EWIS insulation thickness between 90 mm - 300 mm?

2. Is the EWIS insulation conductivity between 0.030 - 0.044 W·m–1·K–1 ?

3. Hasaninternalfinishbeenapplied?

4. HasanexternalfinishbeenappliedtotheEWISinsulation?

5. Is the concretefloorslab< 150 mm with a conductivity < 1.75 W·m–1·K–1?

6. Is the EWIS insulation < 150 mm from ground level?

7. Has the DPM provided with the Thermo-Trac applied as

per manufacturers instructions?

8. HastheThermo-Tracprofilebeenused?

.......................................

.......................................

.......................................

.......................................

.......................................

Below EWIS Insulation thermal bridge junction

InstaClad Thermo-Trac

Copyright is owned by Constructive Details Ltd.Copying or reproduction of the contents is not permitted without the consent of Constructive Details Ltd.

Constructive Details Ltd

Bucknalls LaneWatfordHertfordshire WD25 9BA

t: + 44 (0)1923 665300f: + 44 (0)1923 665301

e: [email protected] w: www.constructivedetails.co.uk ©2015

.......................................

.......................................

Page 8: A handbook of thermal bridging details incorporating InstaClad

Page 8 of 9

Notes• The External Wall Insulation System (EWIS) conductivity between 0.030 W·m–1·K–1 - 0.044 W·m–1·K–1

• eachresultwascalculatedusinganinternalfinishof13mmdenseplasterwithaconductivityof 0.57 W·m–1·K–1 and an external basecoat and mesh of 6 mm with a conductivity of 1.0 W·m–1·K–1

• a maximum ceiling insulation thickness of 600 mm

• a maximum ceiling insulation conductivity of 0.044 W·m–1·K–1 was used

• two50mmfixingsshouldbeusedat600mmcentres.

Solid Externally Insulated Wall

Pitchedroof.Eaves—Insulationatceilinglevel—VentilatedloftwithInstaCladThermo-ProFasciaCD0109

This indicative guidance illustrates good practice for design and construction with respect to achieving thermal performance and air barrier continuity only. It must be implemented taking due regard of site conditions and all other requirements imposed by Buiding Regulations.

Calculated ψ-values for this detail

All values are in W·m–1·K–1

EWIS Insulation between 90 mm - 160 mm

EWIS Insulation between 161 mm - 230 mm

EWIS Insulation between 231 mm - 300 mm

c-value (W·m–1·K–1)

Temperature Factor

c-value (W·m–1·K–1)

Temperature Factor

c-value (W·m–1·K–1)

Temperature Factor

No Thermo-Pro 1.033 0.67 1.055 0.68 1.067 0.68

Thermo-Pro 0.419 0.85 0.435 0.87 0.444 0.88

10 mm Aerogel

maximum ceiling insulation of 600 mm with a conductivity of

0.044 W·m–1·K–1

ceiling insulation tofillto edge of eaves.

Page 9: A handbook of thermal bridging details incorporating InstaClad

Page 9 of 9

Notes (include details of any corrective action)

CD0109

Guidance checklist

Date: ........................................... Site manager/supervisor: ......................................................................................

Site name: ........................................................................................... Plot No: ........................................................

Ref. Item Yes/No Inspected (initials and date)

1. Is the EWIS insulation thickness between 90 mm - 300 mm?

2. Is the EWIS insulation conductivity between 0.030 - 0.044 W·m–1·K–1 ?

3. Hasaninternalfinishbeenapplied?

4. HasanexternalfinishbeenappliedtotheEWISinsulation?

5. HastheThermo-Profasciainsulatedprofilebeenused?

6. Is the ceiling insulation thickness < 600 mm?

7. Is the ceiling insulation conductivity < 0.044 W·m–1·K–1 ?

8. Havetwo50mmfixingsappliedat> 300 mm centres?

.......................................

.......................................

.......................................

.......................................

.......................................

Solid Externally Insulated Wall

Pitchedroof.Eaves—Insulationatceilinglevel—VentilatedloftwithInstaCladThermo-ProFascia

Copyright is owned by Constructive Details Ltd.Copying or reproduction of the contents is not permitted without the consent of Constructive Details Ltd.

Constructive Details Ltd

Bucknalls LaneWatfordHertfordshire WD25 9BA

t: + 44 (0)1923 665300f: + 44 (0)1923 665301

e: [email protected] w: www.constructivedetails.co.uk ©2015

.......................................

.......................................

.......................................