64
ASHRAE 90.1-2019 vs 2018 IECC: Mechanical October 12, 2021 Providing effective energy strategies for buildings and communities ICC Preferred Provider # 2396 ICC Course # 29754

ASHRAE 90.1-2019 vs 2018 IECC: Mechanical

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

ASHRAE 90.1-2019 vs 2018 IECC: Mechanical

October 12, 2021

Providing effective energy strategies for buildings and communities

ICC Preferred Provider # 2396ICC Course # 29754

1. Understand the relationship between and organizational differences

in the IECC and ASHRAE 90.1

2. Understand differences between prescriptive HVAC and Service

Water requirements in the IECC and ASHRAE 90.1

3. Understand similarities between prescriptive HVAC and Service

Water requirements in the IECC and ASHRAE 90.1

4. Understand existing building HVAC and Service Water requirements

in the IECC and ASHRAE 90.1

Leaning Objectives

SEDAC is a Preferred Education Provider with the International Code Council (ICC). Credits earned on

completion of this program will be reported to ICC for ICC members. Certificates of Completion will be issued

to all participants.

This workshop is approved for 1.5 LU/HSW CES credits from the American Institute of Architects (AIA). Credits

earned on completion will be reported for AIA members.

The Smart Energy Design Assistance Center (SEDAC) is an applied research program at University of Illinois.

Our mission: Reduce the energy footprint of Illinois and beyond.

Who We Are

SEDAC is the Illinois Energy Conservation Code Training Provider

This training program is sponsored by

Illinois State Energy Office

Energy Code Training Program

Technical support [email protected]

Online resources at

smartenergy.illinois.edu/energy-code

www.smartenergy.Illinois.edu/energy-code/

Access to 2018 IECC, Illinois Amendments & Chicago Energy Conservation Code

https://codes.iccsafe.org/content/IECC2018P4 https://www2.illinois.gov/cdb/business/codes/IllinoisAccessibilityCode/Documents/2018%20Illinois%20Specific%20Amendments%20with%20Modifications%20Shown.pdf

https://codes.iccsafe.org/content/document/1491

Access to 2016 & 2019 ASHRAE 90.1

https://www.ashrae.org/technical-resources/standards-and-guidelines/read-only-versions-of-ashrae-standards

2019 2016

Free Preview Versions of ASHRAE Standards

Code. Are adopted as law by

authorities having jurisdiction over

the way buildings are constructed.

In Illinois, the State has adopted

the IECC.

The IECC has adopted ASHRAE

as a standard that can be used to

show code compliance.

IECC

Energy Code Compliance

Standard. In Illinois, ASHRAE is a

standard that can be used to show

compliance.

ASHRAE

Remember! You must choose one You must choose one path or the other – not allowed to

“cherry pick” requirements.

SEDAC 2021/2022 Fall Series Workshops

90.1-2019 vs 2018 IECC: Mechanical TODAY!

90.1-2019 vs 2018 IECC: Lighting and Electrical – 11/9/21

90.1-2019 vs 2018 IECC: Performance-Based Compliance – 12/14/21

Registration: https://smartenergy.illinois.edu/energy-code-training/webinars

Or: https://smartenergy.illinois.edu/energy-code/workshops/

Overview

2018 IECCASHRAE 90.1

2 routes to energy code compliance for commercial buildings in Illinois…

2 Paths:

Both Illinois law and the 2018 IECC allow ASHRAE 90.1 as an alternative path to

demonstrate compliance for commercial buildings.

2 Definitions

Organization - Overall

IECC1 Purpose, Scope, Admin, Etc.

Existing Buildings

C401. General

C402. Envelope

C403. Mechanical

C404. Service Water

Heating

C405. Electrical &

Lighting

C406. Additional

Efficiency Packages

C407. Total Building Performance

C408. Maintenance & Commissioning

Chapter 5

Components

Code Compliance

3 General Req.

3 & 4. Definitions, Admin, Etc.

Organization - Overall

ASHRAE1 & 2. Purpose & Scope

11. Energy Cost Budget Method

5. Building Envelope

6. HVAC

7. Service Hot Water

8. Power

9. Lighting

10. Other Equipment

3 & 4. Definitions, Admin, Etc.

Our Series – Register Today!

https://smartenergy.illinois.edu/

energy-code/workshops/1 & 2. Purpose & Scope

11. Energy Cost Budget Method

5. Building Envelope

6. HVAC

7. Service Hot Water

8. Power

9. Lighting

10. Other Equipment

Organization - HVAC

ASHRAE

Hint! Requirements are organized by the

chosen Compliance Path, not components.

1. Climate Zone Differences

Red counties moved to warmer CZ(Calhoun, Clark, Coles, Cumberland, Greene, Jersey)Green counties moved to cooler CZ

ASHRAEIECCZone 5 in IECC Zone 4 in ASHRAE

ASHRAE Additions not

in IECC

Like-for-like replacement, where compliance

would require extensive revisions to other

systems, equipment, or elements of a building,

compliance is not required.

ASHRAE

2. Like for Like Replacement

ASHRAE has a simplified compliance path.

This may be used if all of the following

applies:

• Building 2 stories or less

• Gross floor area less than 25,000 SF

• Each HVAC system complies with 6.3.2

ASHRAE

2. Simplified HVAC Path (6.3)

Single HVAC zones

Variable flow per 6.5.3.2.1 (Multi-stage fan above 5 tons)

Unitary packages or split-system with required efficiency

Air economizer

Exhaust air energy recovery per 6.5.6.1

Manual changeover or dual setpoint t-stat

Heat pump auxiliary heat minimization

ASHRAE

2. Simplified HVAC Path (6.3.2)

No reheat

Scheduled system operation w/ manual override

Hotel/Motel see 6.4.3.3.5 (50+ rooms)

Piping Insulation

Ductwork insulation per Table 6.8.2 and sealed

per 6.4.4.2.1

Air Balance required

ASHRAE

2. Simplified HVAC Path (6.3.2 cont.)

Outdoor Air and exhaust per 6.4.3.4

If separate heating/cooling systems, interlock

required preventing simultaneous operation

Design Capacity above 10,000 CFM requires

optimum start

DCV per 6.4.3.8, standby per 6.5.3.8,

ventilation per 6.5.3.7

Door switch per 6.5.10

ASHRAE

2. Simplified HVAC Path (6.3.2 cont.)

Photo Courtesy of Garage Doors Unlimited

Requires the following data:

• Blade span (diameter)

• Rated airflow and power @ max speed

ASHRAE

2. Large Diameter (>7’) Ceiling Fans

Photo Courtesy of RuppAir

Mechanical cooling shall not

reduce humidity below a

dewpoint of 55°F or relative

humidity of 60% in the coldest

zone whichever is lower

ASHRAE

Dehumidification

Fossil fuel or electricity shall not

be used to produce relative

humidity above 30% in the

warmest zone served by the

system

ASHRAE

Humidification

Photo Courtesy of Blackall Mechanical

Requires DDC for particular

applications and meeting

qualifications (See Table

6.4.3.10.1)

ASHRAE

Direct Digital Controls

Specifies minimum requirements

in 6.4.3.10.2

Zone 5A Zone 4AWater Cooled 1,500 tons 1,000 tonsAir Cooled 860 tons 570 tons

ASHRAE

Chiller Plant Monitoring

Requires electric and efficiency measurement recorded at least every 15

minutes for 36 months for chiller plants sized:

Photo Courtesy of Onset

Zones with only Auto-off lighting

controls, and 62.1 occupancy

permits ventilation to 0 when in

occupied-standby.

Shall do the following 5 min after

vacated:

ASHRAE

Occupied-standby

Heating & Cooling Setpoints

setback 1°F

Zero airflow when space in

deadband

Photo Courtesy of Lighting Controls Association

Where reheat is permitted and

supply & return openings are

above 6’ off floor, supply temp is

limited to not more than 20°F

above room temp

ASHRAE

Supply Temp Reheat Limit

Photo Courtesy of Barcol-Air

Preheating jackets shall be

automatically turned off when

humidification is not required

Dispersion-tube hot surfaces

insulated at least R-0.5

ASHRAE

Humidification

Preheat coils shall stop heat

output when mechanical cooling

is occurring

Photo Courtesy of AprilAire

Chilled water and Condenser

piping designed to limit velocity

per Table 6.5.4.6

Ranges from 5-13 ft/sec

depending on run time and if the

flow is variable or not

ASHRAE

Pipe Sizing

Photo Courtesy of Rocky Mountain Institute

Chilled water coils to have at

least 15F delta and leaving water

temperature of at least 57F at

design conditions

ASHRAE

Coil Selection

Exceptions for constant air

volume systems, smaller (5000

CFM or less) systems, and less

common applications.

Photo Courtesy of Froztec

• 1-10 mmBtu/h

• Excludes units of 300 kBtu or

smaller

• Return water must be limited

to 120F or below

High Capacity Space Heating

Chart Courtesy of Weil McLain

ASHRAE

• Different requirements for non-

transient dwellings. 60%

enthalpy recovery ratio at

winter design condition

ASHRAE

Exhaust Air Energy Recovery

Photo Courtesy of ERI Corporation

• Required for facilities that:

• Operate 24 hrs/day

• Design load exceeds 1

mmBtu/h

• Heat-rejection equipment of

water-cooled systems

exceeds 6 mmBtu/h

ASHRAE

Service Water Heat Energy Recovery

Condenser heat recovery shall

supply 7% of cooling capacity for

following conditions:

• Inpatient hospital operating

24/7

• Design CHW capacity >3.6

mmBtu/h

Space Conditioning Heat Recovery

ASHRAE• Simultaneous heating and

cooling occurs above 60F

OAT

• Indoor pools over 500 sf with

dehumidifiers shall have one

of the following:

ASHRAE

Pool Dehumidifier Energy Recovery

1. Exhaust sensible or total

energy recovery of at least

50%

2. Condenser heat recovery to

use 100% for pool heating

when needed

• Conditioned space with a door

opening to the outdoors shall

be provided with controls that

when door is opened:

ASHRAE

Door Switches

• Disable heating or lower

setpoint to 55F or lower

• Disable cooling or raise

setpoint to 90F or higher

• Excludes entries with

automatic closing devices

Photo Courtesy of Control By Web

• HVAC serving only a computer

room with load greater than

10kW shall use ASHRAE 90.4

Energy Standard for Data

Centers

ASHRAE

IT loads 90.4

• Has recommendations for

spaces indirectly conditioned

ie. return air plenums

ASHRAE

Duct Insulation – Indirectly Conditioned

ASHRAE & IECC

Comparisons

Addition served by existing HVACR systems

and equipment, existing equipment does not

need to comply.

New systems need to comply.

ASHRAE & IECC

2. Addition w/ existing Equipment

IECC

• At least 1 thermostatic control per zone

• 5°F deadband

• Programmable thermostat or BAS

• Setback controls

• Optimum Start for DDC systems

• Zone isolation

• Hotel/Motel guest room controls

ASHRAE & IECC

2. Mandatory Similarities

IECC

10°F heating setback

4°F for radiant system

5°F cooling setback

ASHRAE

Setback Temperatures

Setback to 55°F heating

Setback to 85°F cooling

IECC

Lumps setback and shutdown

together under one item: Timeclock

or programmable controls providing

7-day schedule.

2-hr override to be provided

10-hr back-up

No other options listed

IECC

Setback Control Options

ASHRAESplits setback from shut-down.

Setback is same as IECC

Shutdown includes following control

options:

• Occupancy sensor

• Manual timer w/ 2hr limit

• Interlock to security system

Space Temp

Occupied Setpoint

Outdoor Temp

Time to Occupancy

Floor Temp for radiant systems

ASHRAE

Optimum Start

Adjust start time in order to bring

space to desired temperature

immediately prior to scheduled

occupancy

IECC

Zone 4 – 10 cfm/ft2

Zone 5 – 4 cfm/ft2

ASHRAE

Motorized Damper Leakage

4 cfm/ft2

IECC

Photo Courtesy of Price Industries

Detect contaminants and

stage/modulate to 50% or less

capacity

ASHRAE

Enclosed Parking Garage Ventilation

Stage/modulate to 50% or less

capacity or;

Intermittently operate less than

20% of time (or as required to

maintain acceptable contaminant

levels)

IECC

Photo Courtesy of Greg Seiber

Exception for<30,000 SF or

1,500 SF/hp or more & no

heating or mechanical cooling

ASHRAE

Enclosed Parking Garage Ventilation

Exception for 1,125 CFM/hp or

more & no heating or mechanical

cooling

Exception for exhaust capacity

<22,500 cfm

IECC

Photo Courtesy of Blackrock HVAC

• Design Outdoor Airflow <750

cfm

• >75% of outdoor air is

provided for makeup for that

space or transferred to other

spaces for makeup

• Ventilation for specific

occupancy categories

ASHRAE

Demand Controlled Ventilation Exceptions

• Design Outdoor Airflow <1,200

cfm

• Supply minus makeup/transfer

<1,200 cfm

• Ventilation only for process

loads

IECC

Eliminate economizer

requirements by increasing

cooling efficiency by 42% in

Zone 4A and 49% in Zoner 5A

ASHRAE

Economizer Exception

Eliminate economizer

requirements by increasing

cooling efficiency by 20% in

Zone 4A

IECC

Uses Fan Efficiency Index

1.00 or higher

ASHRAE

Fan Efficiency

Uses Fan Efficiency Grade

67 or higher

IECC

Photo Courtesy of Rocky Mountain ASHRAEPhoto Courtesy of Greenheck

• 15% up to 240,000 Btu/h

• 10% above 240,000 Btu/h

ASHRAE

Hot Gas Bypass Limit

• 50% up to 240,000 Btu/h

• 25% above 240,000 Btu/h

IECC

Photo Courtesy of York Central

Hydronic systems with 3 or more

control valves must be variable

flow.

ASHRAE

Variable Flow Controls

Hydronic systems of 300,000

Btu/h or more must be variable

flow

IECC

Service Water Heating

• Equipment shall be sized per

manufacturer’s published

guidelines, engineering

standards and handbooks

acceptable to AHJ

ASHRAE

Service Water Heating Load Calculation

• 120F or lower as needed for

intended use

• 110F for public lavatories

ASHRAE

Service Water Heating Temp Limits

• Time switches or other

automatic controls to switch

off system during extended

periods when hot water not

required

ASHRAE

Temp Maintenance Controls

• More specific about start and

stop of pumps/maintenance

system. Clearer compliance.

IECC

• Required for heated pools

indoors or outdoors

• Pools heated above 90F must

have a cover of R-12 or better

unless 60% solar or site

recovered energy

ASHRAE

Pool Covers

• Required for outdoor heated

pools unless 75% energy over

the season is site recovered

energy

IECC

• Provides provisions if

equipment can serve both

space heating and service

water heating; At least one of

the following:

ASHRAE

Shared Equipment

• Low standby loss

• Demonstrated savings over

separate units

• Total capacity <150,000 Btu/h

• Supply volume limit:

• Public lavatory: 2 ounces

• All other: ½ gallon

Heated Pipe Length

IECC

Replacement Equipment needs to meet the same requirements as new

construction without requiring alterations to building systems outside the

scope of alteration or replacement

• I.e. Load calculation, Economizer, DCV, etc.

ASHRAE & IECC

Existing Buildings

IECC

Questions?

[email protected]