COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC CODES FOR LARGE OFFICE BUILDINGS IN TEXAS Jaya Mukhopadhyay Juan-Carlos Baltazar, Ph.D. Hyojin Kim, Jeff S. Haberl, Ph.D., P.E., Cyndi Lewis, Bahman Yazdani, P.E. Energy Systems Laboratory Texas A&M University 20 th October 2011 New York Energy Systems Laboratory Texas A&M University System October 2011 ESL-TR-11-10-10

COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

  • Upload
    others

  • View
    43

  • Download
    1

Embed Size (px)

Citation preview

Page 1: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

COMPARISON OF ASHRAE

STANDARD-90.1, 189.1

AND IECC CODES

FOR LARGE OFFICE

BUILDINGS

IN TEXAS

Jaya Mukhopadhyay

Juan-Carlos Baltazar, Ph.D.

Hyojin Kim, Jeff S. Haberl, Ph.D., P.E.,

Cyndi Lewis, Bahman Yazdani, P.E.

Energy Systems Laboratory

Texas A&M University

20th October 2011

New York Energy Systems Laboratory

Texas A&M University System

October 2011

ESL-TR-11-10-10

Page 2: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

STRUCTURE

BACKGROUND

METHODOLOGY

CLIMATE ZONE DECRIPTION

BASE CASE DESCRIPTION

RESULTS

SUMMARY

Energy Systems Laboratory 2011 2/30

ESL-TR-11-10-10

Page 3: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

BACKGROUND

Codes compared:

ASHRAE 90.1-1989

ASHRAE 90.1-1999

ASHRAE 90.1-2004

ASHRAE 90.1-2007

IECC 2009

ASHRAE 90.1-2010

ASHRAE 189.1-2009

The purpose is to assess the

stringency of each code

ASHRAE 90.1-1989 selected as the

base-case

Energy Systems Laboratory 2011 3/30

ESL-TR-11-10-10

Page 4: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

METHODOLOGY

Performance option outlined in the

codes used to design the base case

DOE-2.1e used for simulations

Analysis conducted for

Site energy usage

Source energy usage

Energy Systems Laboratory 2011 4/30

ESL-TR-11-10-10

Page 5: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

CLIMATE ZONES

Three counties selected for analysis

Each county represents a climate zone

Harris (Climate Zone 2A)

Tarrant (Climate Zone 3A)

Potter (Climate Zone 4B)

The counties cover the major

population hubs in the state

5/30 Energy Systems Laboratory 2011

POTTER

TARRANT

HARRIS

ESL-TR-11-10-10

Page 6: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

BASE-CASE

The input was categorized into the

following categories:

Program

Form

Fabric

Equipment

Energy Systems Laboratory 2011 6/30

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

FR

AC

TIO

N O

F O

CC

UP

AN

CY

HOUR OF DAY

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

FR

AC

TIO

N O

F O

CC

UP

AN

CY

HOUR OF DAY

ESL-TR-11-10-10

Page 7: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

FR

AC

TIO

N O

F P

OW

ER

HOUR OF DAY

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

FR

AC

TIO

N O

F O

CC

UP

AN

CY

HOUR OF DAY

Operating Schedules

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

FR

AC

. O

F W

AT

ER

US

AG

E

HOUR OF DAY

BASE-CASE: Program

Schedules include:

Occupancy

Infiltration

Service hot water demand

Lighting

Equipment

HVAC system & fan

ASHRAE 90.1-1989 used as reference

Assumed same for all codes, except

ASHRAE 90.1-2010 equipment schedules

modified to reflect 50% of receptacle

outlets switched off when not in use

Energy Systems Laboratory 2011 7/30

OCCUPANCY

LIGHTING & EQUIPMENT

SHW USAGE

ESL-TR-11-10-10

Page 8: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

BASE-CASE: Program

Space Temperatures 70°F for space heating

75°F for space cooling

Thermostat setback of 5°F

Energy Code Ver. of ASHRAE 62.1 cfm/per. cfm/sqft Resultant OA cfm

ASHRAE 90.1-1989 1981 5 - 1625

ASHRAE 90.1-1999 1989 20 - 6500

ASHRAE 90.1-2004 1999 20 - 6500

ASHRAE 90.1-2007 2004 5 0.06 6983

ASHRAE 90.1-2010 2007 5 0.06 6983

IECC 2009 2007 5 0.06 6983

ASHRAE 189.1-2009 2007 5 0.06 6983

+

Energy Systems Laboratory 2011 8/30

Ventilation Requirements Peak occupancy: 275 sq.ft. / person

ASHRAE 62.1 used to calculate the

ventilation requirements

ESL-TR-11-10-10

Page 9: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

BASE-CASE: Form

Six story office building:

Footprint area: 14,884 sq.ft.

Total floor area: 89,304 sq.ft.

Floor to floor height: 13 ft.

Floor to ceiling height: 9 ft.

Window to wall area ratio: 40%

No shading except ASHRAE 189.1-2009

(PF for South: 0.50)

Aspect ratio:

For ASHRAE 90.1-1989: 2.5:1

For other models: 1.5:1

Four perimeter zones & core zone for each

floor: 15 ft. deep

Energy Systems Laboratory 2011 9/30

ESL-TR-11-10-10

Page 10: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

BASE-CASE: Fabric

ASHRAE 90.1-1989 requires 0.038

cfm/sq.ft.

No specifications for whole building

infiltration in ASHRAE 90.1-1999, 2004,

2007 or IECC 2009

Air-barriers mandatory in the ASHRAE

90.1-2010 & ASHRAE 189.1- 2009

Energy Code Operating Hours

ACH

Non-Operating Hours

ACH

ASHRAE 90.1-1989 – 2007 & IECC 2009

Core Zones 0.043 0.170

Perimeter Zones 0.070 0.280

ASHRAE 90.1-2010 & 189.1-2009

Core Zones 0.0095 0.0375

Perimeter Zones 0.0155 0.0618

Infiltration

Energy Systems Laboratory 2011 10/30

Air Change method used

When HVAC system ON, infiltration

reduced by 75%

ESL-TR-11-10-10

Page 11: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

BASE-CASE: Fabric

Building Envelope Characteristics Steel frame walls

Roof insulation entirely above metal deck

Slab-on-grade for the floor

Energy Systems Laboratory 2011 11/30

Climate Zone ASHRAE 90.1

1989

ASHRAE 90.1

1999

ASHRAE 90.1

2007

IECC

2009

ASHRAE 90.1

2010

ASHRAE

189.1

2009

Steel Frame Walls

2A R-6.5 R-13 R-13 R-13 R-13 R-13+R-5 c.i

3A R-6.5 R-13 R-13+R3.8 c.i R-13+R3.8 c.i R-13+R3.8 c.i R-13+R-5 c.i

4B R-16.5 R-13 R-13+R7.5c.i R-13+R7.5c.i R-13+R7.5c.i R-13+R10 c.i

Insulation Entirely Above Roof

2A R-13.5 c.i R-15 c.i R-20 c.i R-20 c.i R-20 c.i R-25 c.i

3A R-15.75 c.i R-15 c.i R-20 c.i R-20 c.i R-20 c.i R-25 c.i

4B R-15.5 c.i R-15 c.i R-20 c.i R-20 c.i R-20 c.i R-25 c.i

Metal Frame Window U-Value

2A U-1.15 U-1.22 U-0.75 U-0.75 U-0.75 U-0.75

3A U-1.15 U-1.22 U-0.65 U-0.65 U-0.65 U-0.65

4B U-0.81 U-0.46 U-0.55 U-0.55 U-0.55 U-0.45

Window SHGC

2A 0.61 0.17 0.25 0.25 0.25 0.25

3A 0.61 0.15 0.25 0.25 0.25 0.25

4B 0.61 0.25 0.40 0.40 0.40 0.40

Slab On Grade

2A N.R N.R N.R N.R N.R N.R

3A N.R N.R N.R N.R N.R N.R

4B N.R N.R N.R N.R N.R R-10 at 4ft.

Increase in Stringency

ESL-TR-11-10-10

Page 12: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

BASE-CASE: Fabric

Roof & Wall Absorptance

Roof & Wall Emittance

Energy Systems Laboratory 2011 12/30

Energy Code Roof / Wall Absorptance

ASHRAE 90.1-1989

0.7 / 0.7 ASHRAE 90.1-1999

ASHRAE 90.1-2004

ASHRAE 90.1-2007

IECC 2009 0.75 / 0.75

ASHRAE 90.1-2010 CZ 2&3: 0.45 / 0.7

CZ 4 : 0.7 / 0.7

ASHRAE 189.1-2009 0.55 / 0.7

Energy Code Roof / Wall Emittance

ASHRAE 90.1-1989

0.9 / 0.9 ASHRAE 90.1-1999

ASHRAE 90.1-2004

ASHRAE 90.1-2007

IECC 2009 0.75 / 0.75

ASHRAE 90.1-2010 0.9 / 0.9

ASHRAE 189.1-2009

ESL-TR-11-10-10

Page 13: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

Plug Loads

BASE-CASE: Equipment

Energy Code Lighting Power Density

(W/sq.ft.)

ASHRAE 90.1-1989 1.57

ASHRAE 90.1-1999 1.3

ASHRAE 90.1-2004 1

ASHRAE 90.1-2007 1

IECC 2009 1

ASHRAE 90.1-2010 0.9

ASHRAE 189.1-2009 0.9

Lighting Systems

0.75 W/ sq.ft. assumed across all the codes

Energy Systems Laboratory 2011 13/30

Daylight diming controls assumed for

ASHRAE 90.1-2010 and 189.1 codes

ESL-TR-11-10-10

Page 14: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

BASE-CASE: Equipment

HVAC Systems – ASHRAE 90.1-1989

Office building > 75,000sqft or > 3 floors

SYSTEM 5

Specifications for SYSTEM 5

Built-up VAV w/ reheat

Supply fan static pressure – 4 in. w.c.

Total fan efficiency – 55%

Fan control –Variable speed drive

Cooling – Chiller

Heating – Hot water boiler

Energy Systems Laboratory 2011 14/30

ESL-TR-11-10-10

Page 15: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

BASE-CASE: Equipment

HVAC Systems – ASHRAE 90.1-1999, 2004, 2007,

2010 & IECC 2009

Water Fossil Fuel

Energy Systems Laboratory 2011 15/30

Specifications for SYSTEM 2

Built-up VAV w/ reheat

Fan control –Variable speed drive

Cooling – Chiller

Heating – Hot water boiler

System 2

ESL-TR-11-10-10

Page 16: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

BASE-CASE: Equipment

HVAC Systems –ASHRAE 189.1-2009

Energy Systems Laboratory 2011 16/30

Specifications for SYSTEM 7

VAV with perimeter reheat

Supply fan control – VAV

Cooling system – Chilled water

Heating system – Hot water fossil

fuel boiler

System 7

Office building > 75,000sqft or > 3

floors

SYSTEM 7

ESL-TR-11-10-10

Page 17: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

ASHRAE 90.1 1999 Climate zone2A,3A,4B

To select type of fan Table 11.3.2A Budget System Descriptions, Note 4

Pick SV-A output report

From SVA report pick up: Cooling capacity Fan electricity usage To decide economizer and type of fan

To select economizer Table 6.3.1 Minimum System Size for which an Economizer is Required

Power > 25 HP?

Fan control: Inlet vane

Fan control type: Variable speed drive

No

Yes

Select SHW efficiency according to size. Table 7.2.2 Performance Requirements for Water Heating Equipment

Pick SS-P output report

From SS-P report Pick up size of SHW-heater to decide efficiency of SHW

No

Pick PV-A output report

From PV-A report Pick up size of equipment to decide number of chillers and boilers: - HW-BOILER -HERM-CENT-CHILLER

Calculation of chiller size Btu/hr/12000 = tons

Chiller size >300 tons?

Table 11.4.3B Number of chillers

# of chillers = 1

Chiller size >600 tons?

# of chillers = 2

# of chillers ≥ 2 ≤ 800tons

Select chiller type according to size of each chiller. Table 11.4.3C Water chillers types

Select chiller efficiency according to size of each chiller. Table 6.2.1C Water Chilling Packages - Minimum Efficiency Requirements

No

Yes

Yes

Calculation of boiler size Btu/hr

Boiler size >600 kBtu/hr?

Table 11.4.3A, Budget System Descriptions, Note 6

# of boilers = 1

# of boilers = 2

No

Yes

Select boiler efficiency according to size. Table 6.2.1F Gas and Oil-Fired Boilers, Minimum Efficiency Requirements

Start

RUN 1

Select base-case system

STOP RUN 2

ESL-TR-11-10-10

Page 18: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

BASE-CASE: Equipment

Chillers & Boilers

Climate

Zone

ASHRAE 90.1

1989

ASHRAE 90.1

1999

ASHRAE 90.1

2007

IECC

2009

ASHRAE 90.1

2010

ASHRAE

189.1

2009

Chiller Type and Specifications

2A

Number: 1

Recip.

COP 3.8

Number: 1

Screw

COP 4.45

Number: 1

Screw

COP 4.45

Number: 1

Screw

COP 4.54

Number: 1

Screw

COP: 4.54

Number: 1

Screw

COP: 4.54

3A

Number: 1

Recip.

COP 3.8

Number: 1

Screw

COP 4.45

Number: 1

Screw

COP 4.45

Number: 1

Recip.

COP 4.54

Number: 1

Recip.

COP: 4.54

Number: 1

Screw

COP: 4.54

4B

Number: 1

Recip.

COP 3.8

Number: 1

Screw

COP 4.45

Number: 1

Screw

COP 4.45

Number: 1

Recip.

COP 4.54

Number: 1

Recip.

COP: 4.54

Number: 1

Screw

COP: 4.54

Gas Boiler Type and Specifications (Et % )

2A

3A

4B

Number: 1

80 %

Number: 2

80 %

Number: 2

80 %

Number: 2

75 %

Number: 2

80 %

Number: 2

89 %

Energy Systems Laboratory 2011 18/30

Increase in Stringency

ESL-TR-11-10-10

Page 19: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

BASE-CASE: Equipment

Requirements for implementing

economizers more stringent with newer

versions of the codes

Trade-offs are provided in some codes by

increasing cooling efficiency

Economizers

Climate

Zone

ASHRAE 90.1

1989

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

2A × × × × ×

Diff. Enthalpy

Trade-off:

17%

×

3A × × × ×

Diff. Enthalpy

Trade-off:

15%

Diff. Enthalpy

Trade-off:

27%

Diff. Enthalpy

Trade-off:

15%

4B

(Note 1)

Diff. Drybulb

Fixed Drybulb

Fixed Drybulb

Diff. Drybulb

Diff. Drybulb

Diff. Drybulb

Diff. Drybulb

Min. Size

of System ≥ 65 kBtu/hr

≥ 65 kBtu/hr

Table 6.3.1

≥ 65 kBtu/hr

Table 6.5.1

≥ 65 kBtu/hr

Table 6.5.1

≥ 54 kBtu/hr

Table

503.3.1(2)

≥ 54 kBtu/hr

Table 6.5.1A

≥ 33 kBtu/hr

Table 7.4.3.4A

Energy Systems Laboratory 2011 19/30

ESL-TR-11-10-10

Page 20: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

BASE-CASE: Equipment

Gas fired storage water heater with a hot

water recirculation loop

The gallons/hour per person required was

set at 0.4 gallons/hour

Assumed 100,000 Btu/hr input rating for

106 gallon tank

Standard Specifications Min. Specifications

ASHRAE 90.1 1989

Fuel Type: Gas

Storage Capacity: ≥ 100 gals

Input Rating: ≥75,000 Btu/hr

Et: 77%

SL: 1.3+38/V

All Other Codes

Et: 80%

SL: Q/800 + 110x(V)^0.5

Service Hot Water

Energy Systems Laboratory 2011 20/30

ESL-TR-11-10-10

Page 21: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

BASE-CASE: Equipment

ASHRAE

90.1

1989

ASHRAE 90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE 90.1

2010

ASHRAE

189.1

2009

Fan Control

VSD ≥ 25 hp VSD

< 25 hp Inlet vane

≥ 5 hp VSD

Fan Specifications

Supply Total SP: 4 in wc

Eff.: 55%

For VAV fans

≥ 20,000cfm

1.5 hp/1000 cfm

For VAV fans

1.5 hp/1000 cfm

For VAV fans

1.35 hp/1000

cfm

Supply Air Fans & Fan Control

Energy Systems Laboratory 2011 21/30

Requirements more stringent with newer

versions of the codes

ESL-TR-11-10-10

Page 22: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

BASE-CASE: Equipment

ASHRAE Standard 189.1-2009 requires

not less than 6 kBtu/sq.ft. of on-site

renewable energy

For the base case building of 89,304 sq.ft.

area: Annual on-site renewable energy

535.8 MMBtu

Several options available to generate this

amount of energy on-site:

Solar thermal systems

Photovoltaic systems

Renewable Energy Systems

Energy Systems Laboratory 2011 22/30

ESL-TR-11-10-10

Page 23: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

Energy Systems Laboratory 2011

BUILDING ENERGY PERFORMANCE SUMMARY

(MMBtu)

DIFFERENCE w/ ASHRAE 90.1 1989

(%)

ASHRAE

90.1

1989

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

Climate Zone 2A

ELEC 4652.6 4045.5 3671.6 3570.3 3557.9 2683.8 2655.3 13.0 21.1 23.3 23.5 42.3 42.9

GAS 1262.8 884.9 924.3 607.1 640.0 681.0 485.8 29.9 26.8 51.9 49.3 46.1 61.5

TOTAL 5915.4 4930.3 4595.9 4177.3 4197.9 3364.8 3141.1 16.7 22.3 29.4 29.0 43.1 46.9

Climate Zone 3A

ELEC 4684.2 4034.7 3595.2 3541.7 3416.0 2610.8 2364.3 13.9 23.2 24.4 27.1 44.3 49.5

GAS 1634.5 1230.2 664.1 637.0 670.7 693.8 487.5 24.7 59.4 61.0 59.0 57.6 70.2

TOTAL 6318.6 5264.9 4259.1 4178.6 4086.5 3304.6 2851.8 16.7 32.6 33.9 35.3 47.7 54.9

Climate Zone 4B

ELEC 4385.7 3873.2 3516.3 3508.1 3495.4 2562.1 2349.3 11.7 19.8 20.0 20.3 41.6 46.4

GAS 1906.2 1246.1 1129.3 1015.0 1072.0 1078.3 695.1 34.6 40.8 46.8 43.8 43.4 63.5

TOTAL 6291.9 5119.2 4645.6 4523.1 4567.5 3640.3 3044.4 18.6 26.2 28.1 27.4 42.1 51.6

Energy Systems Laboratory 2011 23/30

RESULTS Site Energy Consumption

23/30

% Above ASHRAE 90.1 1989

Climate Zone 2A

0.0

1000.0

2000.0

3000.0

4000.0

5000.0

6000.0

7000.0

ASHRAE

90.1

1989

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

En

erg

y C

on

sum

pti

on

(M

MB

tu)

ELECTRICITY GAS TOTAL

16.7% 22.3% 29.4% 29.0% 43.1% 46.9%

ESL-TR-11-10-10

Page 24: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

Energy Systems Laboratory 2011 24/30 Energy Systems Laboratory @2011

BUILDING ENERGY PERFORMANCE SUMMARY

(MMBtu)

DIFFERENCE w/ ASHRAE 90.1 1989

(%)

ASHRAE

90.1

1989

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

Climate Zone 2A

ELEC 4652.6 4045.5 3671.6 3570.3 3557.9 2683.8 2655.3 13.0 21.1 23.3 23.5 42.3 42.9

GAS 1262.8 884.9 924.3 607.1 640.0 681.0 485.8 29.9 26.8 51.9 49.3 46.1 61.5

TOTAL 5915.4 4930.3 4595.9 4177.3 4197.9 3364.8 3141.1 16.7 22.3 29.4 29.0 43.1 46.9

Climate Zone 3A

ELEC 4684.2 4034.7 3595.2 3541.7 3416.0 2610.8 2364.3 13.9 23.2 24.4 27.1 44.3 49.5

GAS 1634.5 1230.2 664.1 637.0 670.7 693.8 487.5 24.7 59.4 61.0 59.0 57.6 70.2

TOTAL 6318.6 5264.9 4259.1 4178.6 4086.5 3304.6 2851.8 16.7 32.6 33.9 35.3 47.7 54.9

Climate Zone 4B

ELEC 4385.7 3873.2 3516.3 3508.1 3495.4 2562.1 2349.3 11.7 19.8 20.0 20.3 41.6 46.4

GAS 1906.2 1246.1 1129.3 1015.0 1072.0 1078.3 695.1 34.6 40.8 46.8 43.8 43.4 63.5

TOTAL 6291.9 5119.2 4645.6 4523.1 4567.5 3640.3 3044.4 18.6 26.2 28.1 27.4 42.1 51.6

RESULTS Site Energy Consumption

% Above ASHRAE 90.1 1989

Climate Zone 3A

0.0

1000.0

2000.0

3000.0

4000.0

5000.0

6000.0

7000.0

ASHRAE

90.1

1989

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

En

erg

y C

on

sum

pti

on

(M

MB

tu)

ELECTRICITY GAS TOTAL

16.7% 32.6% 33.9% 35.3% 47.7% 54.9%

ESL-TR-11-10-10

Page 25: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

Energy Systems Laboratory 2011 25/30 Energy Systems Laboratory @2011

BUILDING ENERGY PERFORMANCE SUMMARY

(MMBtu)

DIFFERENCE w/ ASHRAE 90.1 1989

(%)

ASHRAE

90.1

1989

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

Climate Zone 2A

ELEC 4652.6 4045.5 3671.6 3570.3 3557.9 2683.8 2655.3 13.0 21.1 23.3 23.5 42.3 42.9

GAS 1262.8 884.9 924.3 607.1 640.0 681.0 485.8 29.9 26.8 51.9 49.3 46.1 61.5

TOTAL 5915.4 4930.3 4595.9 4177.3 4197.9 3364.8 3141.1 16.7 22.3 29.4 29.0 43.1 46.9

Climate Zone 3A

ELEC 4684.2 4034.7 3595.2 3541.7 3416.0 2610.8 2364.3 13.9 23.2 24.4 27.1 44.3 49.5

GAS 1634.5 1230.2 664.1 637.0 670.7 693.8 487.5 24.7 59.4 61.0 59.0 57.6 70.2

TOTAL 6318.6 5264.9 4259.1 4178.6 4086.5 3304.6 2851.8 16.7 32.6 33.9 35.3 47.7 54.9

Climate Zone 4B

ELEC 4385.7 3873.2 3516.3 3508.1 3495.4 2562.1 2349.3 11.7 19.8 20.0 20.3 41.6 46.4

GAS 1906.2 1246.1 1129.3 1015.0 1072.0 1078.3 695.1 34.6 40.8 46.8 43.8 43.4 63.5

TOTAL 6291.9 5119.2 4645.6 4523.1 4567.5 3640.3 3044.4 18.6 26.2 28.1 27.4 42.1 51.6

RESULTS Site Energy Consumption

% Above ASHRAE 90.1 1989

Climate Zone 4B

0.0

1000.0

2000.0

3000.0

4000.0

5000.0

6000.0

7000.0

ASHRAE

90.1

1989

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

En

erg

y C

on

sum

pti

on

(M

MB

tu)

ELECTRICITY GAS TOTAL

18.6% 26.2% 28.1% 27.4% 42.1% 51.6%

ESL-TR-11-10-10

Page 26: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

Energy Systems Laboratory 2011 26/30

BUILDING ENERGY PERFORMANCE SUMMARY

(MMBtu)

DIFFERENCE w/ ASHRAE 90.1 1989

(%)

ASHRAE

90.1

1989

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

Climate Zone 2A

ELEC 14655.7 12743.3 11565.5 11246.4 11207.4 8454.0 8364.2 13.0 21.1 23.3 23.5 42.3 42.9

GAS 1389.1 973.4 1016.7 667.8 704.0 749.1 534.4 29.9 26.8 51.9 49.3 46.1 61.5

TOTAL 16044.8 13716.7 12582.3 11914.3 11911.4 9203.1 8898.6 14.5 21.6 25.7 25.8 42.6 44.5

Climate Zone 3A

ELEC 14755.2 12709.3 11324.9 11156.4 10760.4 8224.0 7447.5 13.9 23.2 24.4 27.1 44.3 49.5

GAS 1798.0 1353.2 730.5 700.7 737.8 763.2 536.3 24.7 59.4 61.0 59.0 57.6 70.2

TOTAL 16553.2 14062.5 12055.4 11857.1 11498.2 8987.2 7983.8 15.0 27.2 28.4 30.5 45.7 51.8

Climate Zone 4B

ELEC 13815.0 12200.6 1076.3 11050.5 11010.5 8070.6 7400.3 11.7 19.8 20.0 20.3 41.6 46.4

GAS 2096.8 1370.7 1242.2 1116.5 1179.2 1186.1 764.6 34.6 40.8 46.8 43.8 43.4 63.5

TOTAL 15911.8 13571.3 12318.6 12167.0 12189.7 9256.7 8164.9 14.7 22.6 23.5 23.4 41.8 48.7

RESULTS Source Energy Consumption

Conversion from Site to Source Energy:

Electricity : 3.13 x Site Electricity Consumption

Source Natural Gas: 1.1 x Site Natural Gas Consumption

ESL-TR-11-10-10

Page 27: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

Energy Systems Laboratory 2011 27/30

BUILDING ENERGY PERFORMANCE SUMMARY

(MMBtu)

DIFFERENCE w/ ASHRAE 90.1 1989

(%)

ASHRAE

90.1

1989

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

Climate Zone 2A

ELEC 14655.7 12743.3 11565.5 11246.4 11207.4 8454.0 8364.2 13.0 21.1 23.3 23.5 42.3 42.9

GAS 1389.1 973.4 1016.7 667.8 704.0 749.1 534.4 29.9 26.8 51.9 49.3 46.1 61.5

TOTAL 16044.8 13716.7 12582.3 11914.3 11911.4 9203.1 8898.6 14.5 21.6 25.7 25.8 42.6 44.5

Climate Zone 3A

ELEC 14755.2 12709.3 11324.9 11156.4 10760.4 8224.0 7447.5 13.9 23.2 24.4 27.1 44.3 49.5

GAS 1798.0 1353.2 730.5 700.7 737.8 763.2 536.3 24.7 59.4 61.0 59.0 57.6 70.2

TOTAL 16553.2 14062.5 12055.4 11857.1 11498.2 8987.2 7983.8 15.0 27.2 28.4 30.5 45.7 51.8

Climate Zone 4B

ELEC 13815.0 12200.6 11076.3 11050.5 11010.5 8070.6 7400.3 11.7 19.8 20.0 20.3 41.6 46.4

GAS 2096.8 1370.7 1242.2 1116.5 1179.2 1186.1 764.6 34.6 40.8 46.8 43.8 43.4 63.5

TOTAL 15911.8 13571.3 12318.6 12167.0 12189.7 9256.7 8164.9 14.7 22.6 23.5 23.4 41.8 48.7

RESULTS Source Energy Consumption

0

2,000

4,000

6,000

8,000

10,000

12,000

14,000

16,000

18,000

ASHRAE

90.1

1989

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

En

erg

y C

on

sum

pti

on

(M

MB

tu)

ELECTRICITY GAS

% Above ASHRAE 90.1 1989

Climate Zone 2A

14.5% 21.6% 25.7% 25.8% 42.6% 44.5%

ESL-TR-11-10-10

Page 28: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

Energy Systems Laboratory 2011 28/30 Energy Systems Laboratory @2011

BUILDING ENERGY PERFORMANCE SUMMARY

(MMBtu)

DIFFERENCE w/ ASHRAE 90.1 1989

(%)

ASHRAE

90.1

1989

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

Climate Zone 2A

ELEC 14655.7 12743.3 11565.5 11246.4 11207.4 8454.0 8364.2 13.0 21.1 23.3 23.5 42.3 42.9

GAS 1389.1 973.4 1016.7 667.8 704.0 749.1 534.4 29.9 26.8 51.9 49.3 46.1 61.5

TOTAL 16044.8 13716.7 12582.3 11914.3 11911.4 9203.1 8898.6 14.5 21.6 25.7 25.8 42.6 44.5

Climate Zone 3A

ELEC 14755.2 12709.3 11324.9 11156.4 10760.4 8224.0 7447.5 13.9 23.2 24.4 27.1 44.3 49.5

GAS 1798.0 1353.2 730.5 700.7 737.8 763.2 536.3 24.7 59.4 61.0 59.0 57.6 70.2

TOTAL 16553.2 14062.5 12055.4 11857.1 11498.2 8987.2 7983.8 15.0 27.2 28.4 30.5 45.7 51.8

Climate Zone 4B

ELEC 13815.0 12200.6 11076.3 11050.5 11010.5 8070.6 7400.3 11.7 19.8 20.0 20.3 41.6 46.4

GAS 2096.8 1370.7 1242.2 1116.5 1179.2 1186.1 764.6 34.6 40.8 46.8 43.8 43.4 63.5

TOTAL 15911.8 13571.3 12318.6 12167.0 12189.7 9256.7 8164.9 14.7 22.6 23.5 23.4 41.8 48.7

0

2,000

4,000

6,000

8,000

10,000

12,000

14,000

16,000

18,000

ASHRAE

90.1

1989

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

En

erg

y C

on

sum

pti

on

(M

MB

tu)

ELECTRICITY GAS

RESULTS Source Energy Consumption

% Above ASHRAE 90.1 1989

Climate Zone 3A

15.0% 27.2% 28.4% 30.5% 45.7% 51.8%

ESL-TR-11-10-10

Page 29: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

Energy Systems Laboratory 2011 29/30 Energy Systems Laboratory @2011

BUILDING ENERGY PERFORMANCE SUMMARY

(MMBtu)

DIFFERENCE w/ ASHRAE 90.1 1989

(%)

ASHRAE

90.1

1989

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

Climate Zone 2A

ELEC 14655.7 12743.3 11565.5 11246.4 11207.4 8454.0 8364.2 13.0 21.1 23.3 23.5 42.3 42.9

GAS 1389.1 973.4 1016.7 667.8 704.0 749.1 534.4 29.9 26.8 51.9 49.3 46.1 61.5

TOTAL 16044.8 13716.7 12582.3 11914.3 11911.4 9203.1 8898.6 14.5 21.6 25.7 25.8 42.6 44.5

Climate Zone 3A

ELEC 14755.2 12709.3 11324.9 11156.4 10760.4 8224.0 7447.5 13.9 23.2 24.4 27.1 44.3 49.5

GAS 1798.0 1353.2 730.5 700.7 737.8 763.2 536.3 24.7 59.4 61.0 59.0 57.6 70.2

TOTAL 16553.2 14062.5 12055.4 11857.1 11498.2 8987.2 7983.8 15.0 27.2 28.4 30.5 45.7 51.8

Climate Zone 4B

ELEC 13815.0 12200.6 11076.3 11050.5 11010.5 8070.6 7400.3 11.7 19.8 20.0 20.3 41.6 46.4

GAS 2096.8 1370.7 1242.2 1116.5 1179.2 1186.1 764.6 34.6 40.8 46.8 43.8 43.4 63.5

TOTAL 15911.8 13571.3 12318.6 12167.0 12189.7 9256.7 8164.9 14.7 22.6 23.5 23.4 41.8 48.7

0

2,000

4,000

6,000

8,000

10,000

12,000

14,000

16,000

18,000

ASHRAE

90.1

1989

ASHRAE

90.1

1999

ASHRAE

90.1

2004

ASHRAE

90.1

2007

IECC

2009

ASHRAE

90.1

2010

ASHRAE

189.1

2009

En

erg

y C

on

sum

pti

on

(M

MB

tu)

ELECTRICITY GAS

RESULTS Source Energy Consumption

% Above ASHRAE 90.1 1989

Climate Zone 4B

14.7% 22.6% 23.5% 23.4% 41.8% 48.7%

ESL-TR-11-10-10

Page 30: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

SUMMARY Site vs. Source Energy Consumption

Energy Systems Laboratory 2011 30/30

Improvement over ASHRAE 90.1 1989:

SITE ENERGY SOURCE ENERGY

ASHRAE 90.1-1999 16.7%-18.6% 14.5%-15.0%

ASHRAE 90.1-2004 22.3%- 32.6% 21.6%-27.2%

ASHRAE 90.1-2007 28.1%-33.9% 23.5%-28.4%

IECC 2009 27.4%-35.3% 23.4%-25.8%

ASHRAE 90.1-2010 42.1%-47.7% 41.8%-45.7%

ASHRAE 189.1-2009 46.9%-54.9% 44.5%-51.8%

ESL-TR-11-10-10

Page 31: COMPARISON OF ASHRAE STANDARD-90.1, 189.1 AND IECC … · 2018-12-06 · BACKGROUND Codes compared: ASHRAE 90.1-1989 ASHRAE 90.1-1999 ASHRAE 90.1-2004 ASHRAE 90.1-2007 IECC 2009 ASHRAE

Thank You!

Energy Systems Laboratory

Texas A&M University System

October 2011

ESL-TR-11-10-10