23
BRE Global Client Report An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for: Devar International Holdings Pty Ltd Date: 06 June 2019 Report Number: P104650-1003 Issue 1 BRE Global Ltd Watford, Herts WD25 9XX Customer Services 0333 321 8811 From outside the UK: T + 44 (0) 1923 664000 F + 44 (0) 1923 664010 E [email protected] www.bre.co.uk Prepared for: Devar International Holdings Pty Ltd 3 Skirmish Court Victoria Point Queensland 4165 Australia

BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

BRE Global Client Report An extended application report on the fire performance of Suresnap

fire collars installed in concrete floors against EN 15882-3:2009

Prepared for: Devar International Holdings Pty Ltd

Date: 06 June 2019

Report Number: P104650-1003 Issue 1

BRE Global Ltd Watford, Herts WD25 9XX Customer Services 0333 321 8811 From outside the UK: T + 44 (0) 1923 664000 F + 44 (0) 1923 664010 E [email protected] www.bre.co.uk

Prepared for: Devar International Holdings Pty Ltd 3 Skirmish Court Victoria Point Queensland 4165 Australia

Page 2: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 1 of 22

This report is made on behalf of BRE Global and may only be distributed in its entirety, without amendment, and with attribution to BRE Global Ltd to the extent permitted by the terms and conditions of the contract. Assessment results relate only to the specimens tested. BRE Global has no responsibility for the design, materials, workmanship or performance of the product or specimens assessed. This report does not constitute an approval, certification or endorsement of the product assessed and no such claims should be made on websites, marketing materials, etc. Any reference to the results contained in this report should be accompanied by a copy of the full report, or a link to a copy of the full report.

BRE Global’s liability in respect of this report and reliance thereupon shall be as per the terms and conditions of contract with the client and BRE Global shall have no liability to third parties to the extent permitted in law.

Prepared by

Name Andy Russell

Position Principal Consultant

Date 06 June 2019

Signature

Authorised by

Name Tony Baker

Position Laboratory Manager – Fire Resistance

Date 06 June 2019

Signature

Date of this report 06 June 2019

Date of next review 06 June 2024

Page 3: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 2 of 22

Table of contents

1 Introduction 3 2 Scope 3 3 Supporting data 3 4 Description of the proposed fire collars 3

4.1 Suresnap cast-in H65S collar 3

4.2 Suresnap cast-in H100S collar 3

4.3 Suresnap cast-in H110S collar 4

4.4 Suresnap cast-in H150S collar 4

4.5 Sealing around pipes 4

5 Extended application 5

5.1 Separating elements 5

5.2 Pipe dimensions 5

5.2.1 PVC pipes with no pipe coupling within fire collar 5 5.2.2 PVC pipes with pipe coupling within fire collar 6 5.2.3 PP pipes with no pipe coupling within fire collar 7 5.2.4 PP pipes with pipe coupling within fire collar 8 5.2.5 PE-HD pipes with no pipe coupling within fire collar 9 5.2.6 PE-X pipes with no pipe coupling within fire collar 10

6 Conclusion 11 7 Figures 12 8 Validity of the extended application 16 Appendix A Supporting data 17

A.1 BRE Global test report no. P112838-1000 Issue 1 17

A.2 BRE Global test report no. P112838-1001 Issue 1 17

A.3 BRE Global test report no. P112838-1002 Issue 1 18

A.4 BRE Global test report no. P112838-1003 Issue 2 19

A.5 BRE Global test report no. P112838-1004 Issue 1 19

A.6 BRE Global test report no. P112838-1005 Issue 2 20

A.7 BRE Global test report no. P112838-1006 Issue 1 21

A.8 BRE Global test report no. P112838-1007 Issue 1 21

Page 4: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 3 of 22

1 Introduction

A series of fire resistance tests in accordance with EN 1366-3:2009 have been carried out on Suresnap fire collars fitted around plastic pipes penetrating concrete floors. This extended application report considers the fire performance of the fire collars when fitted around pipes of different materials, diameters and wall thicknesses.

2 Scope

This extended application report considers the fire performance of Suresnap fire collars, when fitted around plastic pipes passing through concrete floors, against the integrity and insulation criteria of EN 1366-3:2009, for fire exposures of up to 240 minutes from the underside. The extended application has been carried out in accordance with EN 15882-3:2009.

3 Supporting data

Details of the supporting data used in the preparation of this extended application are given in appendix A.

4 Description of the proposed fire collars

4.1 Suresnap cast-in H65S collar The Suresnap cast-in H65S collar, details of which are shown in figure 1, comprises a 1.6mm-thick polypropylene casing with an 84mm inner diameter and a 168mm-diameter base flange. The 250mm-high collar casing, which is cut down in length to match the floor thickness, incorporates a 280mm x 65mm x 5mm-thick intumescent sheet and a rubber ring seal. The closing mechanism comprises three 3.15mm-diameter galvanised steel springs bound with nylon fuse links and a 322mm x 63mm x 0.25mm-thick stainless steel mesh.

4.2 Suresnap cast-in H100S collar The Suresnap cast-in H100S collar, details of which are shown in figure 2, comprises a 1.6mm-thick polypropylene casing with a 126.5mm inner diameter and a 213mm-diameter base flange. The 250mm-high collar casing, which is cut down in length to match the floor thickness, incorporates a 412mm x 85mm x 4mm-thick intumescent sheet and a rubber ring seal. The closing mechanism comprises three 3.15mm-diameter galvanised steel springs bound with nylon fuse links and a 460mm x 83mm x 0.25mm-thick stainless steel mesh.

Page 5: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 4 of 22

4.3 Suresnap cast-in H110S collar The Suresnap cast-in H110S collar, details of which are shown in figure 3, comprises a 1.9mm-thick polypropylene casing with a 138mm inner diameter and a 194mm x 184mm rectangular base flange. The 248mm-high collar casing, which is cut down in length to match the floor thickness, incorporates a 451mm x 85mm x 4mm-thick intumescent sheet and a rubber ring seal. The closing mechanism comprises four 3.15mm-diameter galvanised steel springs bound with nylon fuse links and a 503mm x 83mm x 0.25mm-thick stainless steel mesh.

4.4 Suresnap cast-in H150S collar The Suresnap cast-in H150S collar, details of which are shown in figure 4, comprises a 2mm-thick polypropylene casing with a 182mm inner diameter and a 292mm-diameter base flange. The 250mm-high collar casing, which is cut down in length to match the floor thickness, incorporates a 600mm x 110mm x 6mm-thick intumescent sheet and a rubber ring seal. The closing mechanism comprises four 4mm-diameter galvanised steel springs bound with nylon fuse links and a 640mm x 109mm x 0.25mm-thick stainless steel mesh.

4.5 Sealing around pipes Where there is a gap between the aperture in the floor and the pipe circumference, this is filled using one of the following methods:

a) For gaps up to 10mm wide: No backfill, Weber Saint Gobain No-shrink General Purpose Construction Grout or Sika Everbuild Everflex LMA 200 Contractors Sealant.

b) For gaps between 10mm wide and 20mm wide: Weber Saint Gobain No-shrink General Purpose Construction Grout or Sika Everbuild Everflex LMA 200 Contractors Sealant.

c) For gaps between 20mm wide and 30mm wide: Weber Saint Gobain No-shrink General Purpose Construction Grout.

Where Weber Saint Gobain No-shrink General Purpose Construction Grout is used, a cardboard gasket is located between the pipe and the aperture in the floor and the grout applied in the gap above this. The cardboard gasket is positioned either 30mm below the upper surface of the floor or on the rubber ring of the collar if this is less than 30mm below the surface of the floor.

Where Sika Everflex LMA 200 Contractors Sealant is used, this is applied between the pipe and the aperture in the floor to a depth of 10mm.

Where the pipes are grouted in, PE foam strip, nominally 5mm thick, may be applied around the pipe, flush with the top of the floor to the full depth of the grout. This is done for acoustic purposes. The PE strip may also be used in isolation where the gap between the pipe and the aperture in the floor is small, i.e. less than 10mm.

Page 6: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 5 of 22

5 Extended application

5.1 Separating elements A decrease in the thickness or density of the supporting construction is not permitted. Therefore, as the tested fire collars were tested cast into concrete floor slabs with a thickness of 150mm and an average measured density of 2240kg/m3, this is the minimum permitted specification.

An increase in thickness of the supporting construction is permitted provided that the fire collar is installed so that it is flush with the underside of the floor slab.

5.2 Pipe dimensions A change in pipe dimensions is permitted within the diameter and wall thickness range tested provided the seal thickness and depth remains the same across the pipe dimension range. In the case of pipe closure devices this refers to the thickness and length of the intumescent component. For the purposes of this extended application report the H100S and H110S data has been combined as the thickness and length of the intumescent component is the same in both collar types.

The PE100 pipes detailed within the test reports are PE-HD pipes that comply with EN 1519-1.

5.2.1 PVC pipes with no pipe coupling within fire collar Table 1 summarises the test data for PVC pipes with no pipe coupling within the fire collar.

Table 1 Test data summary for PVC pipes (no pipe coupling within fire collar)

Test report Penetration Fire collar type Pipe diameter

(mm)

Pipe wall thickness

(mm)

Fire resistance

Integrity (min)

Insulation (min)

P112838-1006 Fire collar 1 H65S 40 3.0 240 209

P112838-1004 Fire collar 2 H65S 65 4.7 240 240

P112838-1001 Fire collar 4 H100S 50 2.0 240 223

P112838-1001 Fire collar 3 H100S 100 3.2 240 240

P112838-1005 Fire collar 3 H110S 50 2.0 240 240

P112838-1002 Fire collar 4 H110S 100 3.2 202 202

P112838-1002 Fire collar 6 H110S 100 3.2 239 218

P112838-1004 Fire collar 5 H150S 100 3.2 173 173

Page 7: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 6 of 22

Test report Penetration Fire collar type Pipe diameter

(mm)

Pipe wall thickness

(mm)

Fire resistance

Integrity (min)

Insulation (min)

P112838-1003 Fire collar 3 H150S 150 2.0 151 151

On the basis of test data detailed in table 1, it is possible to assess the fire collars for use with pipes of the following dimensions and fire resistance periods.

Table 2 Minimum and maximum pipe sizes for different sizes of fire collar (no pipe coupling within fire collar)

Collar type Pipe diameter range (mm)

Pipe wall thickness range (mm)

Classification against EN 13501-2:2016

H65S 40 to 65 3.0 to 4.7 EI 180, E 240

H100S and H110S 50 to 100 2.0 to 3.2 EI 180, E 180

H150S 100 to 150 2.0 to 3.2 EI 120, E 120

5.2.2 PVC pipes with pipe coupling within fire collar Table 3 summarises the test data for PVC pipes with a pipe coupling within the fire collar.

Table 3 Test data summary for PVC pipes (pipe coupling within fire collar)

Test report Penetration Fire collar type Pipe diameter

(mm)

Pipe wall thickness

(mm)

Fire resistance

Integrity (min)

Insulation (min)

P112838-1003 Fire collar 2 H65S 40 3.0 240 218

P112838-1004 Fire collar 3 H65S 65 4.7 240 240

P112838-1001 Fire collar 2 H100S 50 2.0 240 226

P112838-1001 Fire collar 1 H100S 100 3.2 240 233

P112838-1000 Fire collar 3 H110S 50 3.7 202 202

P112838-1000 Fire collar 2 H110S 100 6.6 202 202

P112838-1000 Fire collar 5 H150S 100 6.6 194 172

Page 8: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 7 of 22

Test report Penetration Fire collar type Pipe diameter

(mm)

Pipe wall thickness

(mm)

Fire resistance

Integrity (min)

Insulation (min)

P112838-1000 Fire collar 1 H150S 150 9.5 202 148

On the basis of test data detailed in table 3, it is possible to assess the fire collars for use with pipes of the following dimensions and fire resistance periods.

Table 4 Minimum and maximum pipe sizes for different sizes of fire collar (pipe coupling within fire collar)

Collar type Pipe diameter range (mm)

Pipe wall thickness range (mm)

Classification against EN 13501-2:2016

H65S 40 to 65 3.0 to 4.7 EI 180, E 240

H100S and H110S 50 to 100 2.0 to 6.6 EI 180, E 180

H150S 100 to 150 6.6 to 9.5 EI 120, E 180

5.2.3 PP pipes with no pipe coupling within fire collar Table 5 summarises the test data for PP pipes with no pipe coupling within the fire collar.

Table 5 Test data summary for PP pipes (no pipe coupling within fire collar)

Test report Penetration Fire collar type Pipe diameter

(mm)

Pipe wall thickness

(mm)

Integrity (min)

Insulation (min)

P112838-1007 Fire collar 1 H65S 40 1.8 240 240

P112838-1007 Fire collar 5 H65S 50 1.8 240 214

P112838-1007 Fire collar 3 H110S 50 1.8 226 226

P112838-1007 Fire collar 2 H110S 110 2.7 198 164

P112838-1007 Fire collar 4 H150S 160 3.9 144 124

P112838-1006 Fire collar 4 H150S 160 4.9 208 131

On the basis of test data detailed in table 5, it is possible to assess the fire collars for use with pipes of the following dimensions and fire resistance periods.

Page 9: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 8 of 22

Table 6 Minimum and maximum pipe sizes for different sizes of fire collar (no pipe coupling within fire collar)

Collar type Pipe diameter range (mm)

Pipe wall thickness range (mm)

Classification against EN 13501-2:2016

H65S 40 to 50 1.8 EI 180, E 240

H110S 50 to 110 1.8 to 2.7 EI 120, E 180

H150S 160 3.9 to 4.9 EI 120, E 120

5.2.4 PP pipes with pipe coupling within fire collar Table 7 summarises the test data for PP pipes with a pipe coupling within the fire collar.

Table 7 Test data summary for PP pipes (pipe coupling within fire collar)

Test report Penetration Fire collar type Pipe diameter

(mm)

Pipe wall thickness

(mm)

Integrity (min)

Insulation (min)

P112838-1003 Fire collar 1 H65S 40 1.8 240 227

P112838-1002 Fire collar 5 H65S 50 1.8 240 231

P112838-1002 Fire collar 2* H110S 50 1.8 118 118

P112838-1002 Fire collar 3 H110S 110 3.4 240 234

P112838-1005 Fire collar 1 H150S 110 3.4 240 239

P112838-1005 Fire collar 2* H150S 160 4.9 8 7

*Note: Fire collar 2 in BRE Global report no. P112838-1002 failed prematurely when it caught fire due to the sustained flaming from an adjacent specimen. Fire collar 2 in BRE Global report no. P112838-1005 failed prematurely due to the pipe slipping out of the collar. This was due to the deformation of the pipe allowing it to slip out of the support collar. This would not happen in practice. The results of these two specimens have therefore been ignored with respect to the extended application.

On the basis of test data detailed in table 7, it is possible to assess the fire collars for use with pipes of the following dimensions and fire resistance periods.

Page 10: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 9 of 22

Table 8 Minimum and maximum pipe sizes for different sizes of fire collar (pipe coupling within fire collar)

Collar type Pipe diameter range (mm)

Pipe wall thickness range (mm)

Classification against EN 13501-2:2016

H65S 40 to 50 1.8 EI 180, E 240

H110S 110 3.4 EI 180, E 240

H150S 110 3.4 EI 180, E 240

5.2.5 PE-HD pipes with no pipe coupling within fire collar Table 9 summarises the test data for PE-HD pipes with no pipe coupling within the fire collar.

Table 9 Test data summary for PE-HD pipes (no pipe coupling within fire collar)

Test report Penetration Fire collar type Pipe diameter

(mm)

Pipe wall thickness

(mm)

Integrity (min)

Insulation (min)

P112838-1006 Fire collar 5 H65S 32 3.0 240 238

P112838-1004 Fire collar 6 H65S 63 3.0 240 240

P112838-1004 Fire collar 4 H65S 63 5.8 240 240

P112838-1001 Fire collar 6 H100S 50 3.0 215 215

P112838-1001 Fire collar 5 H100S 110 4.2 240 240

P112838-1003 Fire collar 6 H110S 25 2.0 240 179

P112838-1000 Fire collar 4 H110S 50 3.0 164 164

P112838-1006 Fire collar 6 H110S 50 4.6 222 222

P112838-1007 Fire collar 6 H110S 110 4.0 223 175

P112838-1000 Fire collar 6 H110S 110 4.3 202 202

P112838-1006 Fire collar 3 H110S 110 10.0 216 212

P112838-1005 Fire collar 4 H150S 110 4.2 240 202

P112838-1005 Fire collar 5 H150S 110 10.0 240 193

Page 11: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 10 of 22

Test report Penetration Fire collar type Pipe diameter

(mm)

Pipe wall thickness

(mm)

Integrity (min)

Insulation (min)

P112838-1005 Fire collar 6 H150S 160 6.2 163 160

P112838-1004 Fire collar 1 H150S 160 14.6 240 182

On the basis of test data detailed in table 9, it is possible to assess the fire collars for use with pipes of the following dimensions and fire resistance periods.

Table 10 Minimum and maximum pipe sizes for different sizes of fire collar (no pipe coupling within fire collar)

Collar type Pipe diameter range (mm)

Pipe wall thickness range (mm)

Classification against EN 13501-2:2016

H65S 32 to 63 3.0 to 5.8 EI 180, E 240

H110S 25 to 110 2.0 to 10.0 EI 120, E 120

H150S 110 to 160 4.2 to 14.6 EI 120, E 120

5.2.6 PE-X pipes with no pipe coupling within fire collar Table 11 summarises the test data for the PE-X pipes with no pipe coupling within the fire collar.

Table 11 Test data summary for PE-X pipes (no pipe coupling within fire collar)

Test report Penetration Fire collar type Pipe diameter

(mm)

Pipe wall thickness

(mm)

Integrity (min)

Insulation (min)

P112838-1003 Fire collar 5 H65S 15 2.6 240 223

P112838-1002 Fire collar 1 H65S 63 8.6 100 100

On the basis of test data detailed in table 11, it is possible to assess the fire collars for use with pipes of the following dimensions and fire resistance periods.

Table 12 Minimum and maximum pipe sizes for different sizes of fire collar (no pipe coupling within fire collar)

Collar type Pipe diameter range (mm)

Pipe wall thickness range (mm)

Classification against EN 13501-2:2016

H65S 15 to 63 2.6 to 8.6 EI 90, E 90

Page 12: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 11 of 22

6 Conclusion

Therefore it is our opinion that the Suresnap Fire Collars, as described in section 4, will provide the classifications detailed in tables 2, 4, 6, 8, 10 and 12 against EN 13501-2:2016 when installed in concrete floors with a minimum thickness of 150mm.

Page 13: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 12 of 22

7 Figures

Figure 1 H65S fire collar

Page 14: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 13 of 22

Figure 2 H100S fire collar

Page 15: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 14 of 22

Figure 3 H110S fire collar

Page 16: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 15 of 22

Figure 4 H150S fire collar

Page 17: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 16 of 22

8 Validity of the extended application

This assessment is issued on the basis of test data and information to hand at the time of issue. If contradictory evidence becomes available to BRE Global the extended application will be unconditionally withdrawn and the applicant will be notified in writing.

Similarly the extended application is invalidated if the assessed construction is subsequently tested since actual test data is deemed to take precedence over an expressed opinion. The extended application is valid for a period of five years after which it is recommended that it be submitted to BRE Global for re-evaluation.

Next review date: 07 May 2024

Page 18: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 17 of 22

Appendix A Supporting data

A.1 BRE Global test report no. P112838-1000 Issue 1 Six Suresnap fire collars manufactured by Snap Fire Systems cast into a 150mm-thick concrete floor, were submitted to a fire resistance test in accordance with EN1366 Part 3: 2009 for a duration of 202 minutes on 05 September 2018.

The collars were labelled 1, 2, 3, 4, 5 and 6 and all pipes had uncapped ends both within and outside of the furnace.

The fire collars performed as follows:

• Fire collar 1 – H150S fitted with 150mm x 9.5mm + 9.5mm coupled PVC pipe § Insulation - 148 minutes § Integrity - 202 minutes. No failure for test duration

• Fire collar 2 – H110S fitted with 100mm x 6.6mm + 6.6mm coupled PVC pipe

§ Insulation - 202 minutes. Maximum temperature rise limit, 180°C, not exceeded for the duration of the test

§ Integrity - 202 minutes. No failure for test duration

• Fire collar 3 – H110S fitted with 50mm x 3.7mm + 3.7mm coupled PVC pipe § Insulation - 202 minutes. Maximum temperature rise limit, 180°C, exceeded just

before test termination § Integrity - 202 minutes. No failure for test duration

• Fire collar 4 – H110S fitted with 50mm x 3.0mm PE-HD pipe

§ Insulation - At time of integrity failure § Integrity - Sustained flaming after 164 minutes of test

• Fire collar 5 – H150S fitted with 100mm x 6.6mm + 6.6mm coupled PVC pipe

§ Insulation - 172 minutes § Integrity - Sustained flaming after 194 minutes of test

• Fire collar 6 – H110S fitted with 110mm x 4.3mm PE-HD pipe

§ Insulation - 202 minutes. Maximum temperature rise limit, 180°C, not exceeded for the duration of the test

§ Integrity - 202 minutes. No failure for test duration

A.2 BRE Global test report no. P112838-1001 Issue 1 Six Suresnap fire collars manufactured by Snap Fire Systems cast into a 150mm-thick concrete floor, were submitted to a fire resistance test in accordance with EN1366 Part 3: 20091 for a duration of 240 minutes on 07 September 2018.

The collars were labelled 1, 2, 3, 4, 5 and 6 and all pipes had uncapped ends both within and outside of the furnace.

The fire collars performed as follows:

• Fire collar 1 – H100S fitted with 100mm x 3.2mm + 3.2mm coupled PVC pipe § Insulation - 233 minutes § Integrity - 240 minutes. No failure for test duration

Page 19: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 18 of 22

• Fire collar 2 – H100S fitted with 50mm x 2.0mm + 2.0mm coupled PVC pipe

§ Insulation - 226 minutes. § Integrity - 240 minutes. No failure for test duration.

• Fire collar 3 – H100S fitted with 100mm x 3.2mm PVC pipe

§ Insulation - 240 minutes. Maximum temperature rise limit, 180°C, not exceeded for the duration of the test

§ Integrity - 240 minutes. No failure for test duration

• Fire collar 4 – H100S fitted with 50mm x 2.0mm PVC pipe § Insulation - 223 minutes § Integrity - 240 minutes. No failure for duration of test

• Fire collar 5 – H100S fitted with 110mm x 4.2mm PE-HD pipe

§ Insulation - 240 minutes. Maximum temperature rise limit, 180°C, not exceeded for the duration of the test

§ Integrity - 240 minutes. No failure for duration of test

• Fire collar 6 – H100S fitted with 50mm x 3.0mm PE-HD pipe § Insulation - At time of integrity failure § Integrity - Sustained flaming after 215 minutes of test

A.3 BRE Global test report no. P112838-1002 Issue 1 Six Suresnap fire collars manufactured by Snap Fire Systems cast into a 150mm-thick concrete floor, were submitted to a fire resistance test in accordance with 476: EN1366 Part 3: 20091 for a duration of 240 minutes on 13 September 2018.

The collars were labelled 1, 2, 3, 4, 5 and 6 and all pipes had uncapped ends both within and outside of the furnace.

The fire collars performed as follows:

• Fire collar 1 – H65S fitted with 63mm x 8.6mm PEX-a pipe § Insulation – At time of integrity failure § Integrity - Sustained flaming after 100 minutes of test

• Fire collar 2 – H110S fitted with 50mm x 1.8mm + 1.8mm bell end PP pipe

§ Insulation – At time of integrity failure § Integrity - Sustained flaming after 118 minutes of test

(Note: Both insulation and integrity failures to pipe 2 occurred at these times due to pipe 1 flaming intensely and falling over towards pipe 2 along with pooling of flaming molten plastic that couldn’t be extinguished)

• Fire collar 3 – H110S fitted with 110mm x 3.4mm + 3.4mm bell end PP pipe § Insulation - 234 minutes. for the duration of the test § Integrity - 240 minutes. No failure for test duration

• Fire collar 4 – H110S fitted with 100mm x 3.2mm PVC pipe

§ Insulation - At time of integrity failure § Integrity - Sustained flaming after 202 minutes of test

• Fire collar 5 – H65S fitted with 50mm x 1.8mm + 1.8mm bell end PP pipe

§ Insulation - 231 minutes § Integrity - 240 minutes. No failure for duration of test

Page 20: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 19 of 22

• Fire collar 6 – H110S fitted with 100mm x 3.2mm PVC pipe

§ Insulation – 218 minutes § Integrity - Sustained flaming after 239 minutes of test

A.4 BRE Global test report no. P112838-1003 Issue 2 Six Suresnap fire collars manufactured by Snap Fire Systems cast into a 150mm-thick concrete floor, were submitted to a fire resistance test in accordance with 476: EN1366 Part 3: 20091 for a duration of 240 minutes on 17 September 2018.

The collars were labelled 1, 2, 3, 4, 5 and 6 and all pipes had uncapped ends both within and outside of the furnace.

The fire collars performed as follows:

• Fire collar 1 – H65S fitted with 40mm x 1.8mm + 1.8mm bell end PP pipe § Insulation - 227 minutes § Integrity - 240 minutes. No failure for test duration

• Fire collar 2 – H65S fitted with 40mm x 3.0mm + 3.0mm coupled PVC pipe

§ Insulation - 218 minutes § Integrity - 240 minutes. No failure for test duration

• Fire collar 3 – H150S fitted with 150mm x 2.0mm PVC pipe

§ Insulation - 151 minutes § Integrity - Sustained flaming after 151 minutes of test

• Fire collar 4 – H110S with manifold fitted with 100mm x 3.0mm PVC pipe

§ Insulation - 227 minutes § Integrity - 240 minutes. No failure for test duration

• Fire collar 5 – H65S fitted with 15mm x 2.6mm PEX-a pipe

§ Insulation - 223 minutes § Integrity - 240 minutes. No failure for test duration

• Fire collar 6 – H110S fitted with 25mm x 2.0mm PE100 pipe

§ Insulation – 179 minutes § Integrity - 240 minutes. No failure for test duration

A.5 BRE Global test report no. P112838-1004 Issue 1 Six Suresnap fire collars manufactured by Snap Fire Systems cast into a 150mm-thick concrete floor, were submitted to a fire resistance test in accordance with EN1366 Part 3: 20091 for a duration of 240 minutes on 19 September 2018.

The collars were labelled 1, 2, 3, 4, 5 and 6 and all pipes had uncapped ends both within and outside of the furnace.

The fire collars performed as follows:

• Fire collar 1 – H150S collar with 160mm x 14.6mm PE100 pipe § Insulation - 182 minutes § Integrity - 240 minutes. No failure for test duration

• Fire collar 2 – H65S collar with 65mm x 4.7mm PVC pipe

Page 21: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 20 of 22

§ Insulation - 240 minutes. Maximum temperature rise limit, 180°C, not exceeded for the duration of the test

§ Integrity - 240 minutes. No failure for test duration

• Fire collar 3 – H65S collar with 65mm x 4.7mm + 4.7mm coupled PVC pipe § Insulation - 240 minutes. Maximum temperature rise limit, 180°C, not exceeded

for the duration of the test § Integrity - 240 minutes. No failure for test duration

• Fire collar 4 – H65S collar with 63mm x 5.8mm PE100 pipe

§ Insulation - 240 minutes. Maximum temperature rise limit, 180°C, not exceeded for the duration of the test

§ Integrity - 240 minutes. No failure for test duration

• Fire collar 5 – HS150S collar with 100mm x 3.2mm PVC pipe § Insulation - At time of integrity failure § Integrity - Sustained flaming after 173 minutes of test

• Fire collar 6 – HS65S collar with 63mm x 3mm PE-HD pipe

§ Insulation - 240 minutes. Maximum temperature rise limit, 180°C, not exceeded for the duration of the test

§ Integrity - 240 minutes. No failure for test duration

A.6 BRE Global test report no. P112838-1005 Issue 2 Six Suresnap fire collars manufactured by Snap Fire Systems cast into a 150mm-thick concrete floor, were submitted to a fire resistance test in accordance with EN1366 Part 3: 20091 for a duration of 240 minutes on 21 September 2018.

The collars were labelled 1, 2, 3, 4, 5 and 6 and all pipes had uncapped ends both within and outside of the furnace.

The fire collars performed as follows:

• Fire collar 1 – H150S fitted with 110mm x 3.4mm + 3.4mm bell end PP pipe § Insulation - 239 minutes § Integrity - 240 minutes. No failure for test duration

• Fire collar 2 – H150S fitted with 160mm x 4.9mm + 4.9mm bell end PP pipe

§ Insulation - 7 minutes § Integrity - Flaming of cotton fibre pad after 8 minutes of test Note: The pipe deformed and slid down out of the support collar after 8 minutes of test and melted.

• Fire collar 3 – H110S fitted with 50mm x 2.0mm PVC pipe

§ Insulation - 240 minutes § Integrity - 240 minutes. No failure for test duration

• Fire collar 4 – H150S fitted with 110mm x 4.2 mm PE-HD pipe

§ Insulation - 202 minutes § Integrity - 240 minutes. No failure for test duration

• Fire collar 5 – H150S fitted with 110mm x 10.0mm PE100 pipe

§ Insulation - 193 minutes § Integrity - 240 minutes. No failure for test duration

Page 22: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Page 21 of 22

• Fire collar 6 – H150S fitted with 160mm x 6.2mm PE-HD pipe § Insulation – 160 minutes § Integrity - Sustained flaming after 163 minutes of test

A.7 BRE Global test report no. P112838-1006 Issue 1 Six Suresnap fire collars manufactured by Snap Fire Systems cast into a 150mm-thick concrete floor, were submitted to a fire resistance test in accordance with EN1366 Part 3: 20091 for a duration of 240 minutes on 26 September 2018.

The collars were labelled 1, 2, 3, 4, 5 and 6 and all pipes had uncapped ends both within and outside of the furnace.

The fire collars performed as follows:

• Fire collar 1 – H65S fitted with 40mm x 3mm PVC pipe § Insulation - 209 minutes § Integrity - 240 minutes. No failure for test duration

• Fire collar 2 – H110S no pipe fitted collar cap on top with rockwool filling underneath

§ Insulation - At time of integrity failure § Integrity - Sustained flaming after 143 minutes of test

• Fire collar 3 – H110S fitted with 110mm x 10mm PE100 pipe

§ Insulation - 212 minutes § Integrity - Sustained flaming after 216 minutes of test

• Fire collar 4 – H150S fitted with 160mm x 4.9mm PP pipe

§ Insulation - 131 minutes § Integrity - Sustained flaming after 208 minutes of test

• Fire collar 5 – H65S fitted with 32mm x 3mm PE-HD pipe

§ Insulation - 238 minutes § Integrity - 240 minutes. No failure for duration of test

• Fire collar 6 – H110S fitted with 50mm x 4.6mm PE100 pipe

§ Insulation - At time of integrity failure § Integrity - Sustained flaming after 222 minutes of test

A.8 BRE Global test report no. P112838-1007 Issue 1 Six Suresnap fire collars manufactured by Snap Fire Systems cast into a 150mm-thick concrete floor, were submitted to a fire resistance test in accordance with EN1366 Part 3: 20091 for a duration of 240 minutes on 28 September 2018.

The collars were labelled 1, 2, 3, 4, 5 and 6 and all pipes had uncapped ends both within and outside of the furnace. Collar 6 comprised two collars immediately next to each other and are designated pipes 6a and 6b.

The fire collars performed as follows:

• Fire collar 1 – H65S fitted with 40mm x 1.8mm PP pipe § Insulation - 240 minutes § Integrity - 240 minutes. No failure for test duration

• Fire collar 2 – H110S fitted with 110mm x 2.7mm PP pipe

Page 23: BRE Global Client Report€¦ · An extended application report on the fire performance of Suresnap fire collars installed in concrete floors against EN 15882-3:2009 Prepared for:

An extended application report on the fire performance of Suresnap fire collars installed in concrete floors

against EN 15882-3:2009 Report Number: P104650-1003

Issue 1

Commercial in Confidence © BRE Global Ltd 2019

Report Ends

Page 22 of 22

§ Insulation - 164 minutes § Integrity - Sustained flaming after 198 minutes of test

• Fire collar 3 – H110S fitted with 50mm x 1.8mm PP pipe

§ Insulation - 226 minutes § Integrity - Sustained flaming after 226 minutes of test

• Fire collar 4 – H150S fitted with 160mm x 3.9mm PP pipe

§ Insulation - 124 minutes § Integrity - Sustained flaming after 144 minutes of test

• Fire collar 5 – H65S fitted with 50mm x 1.8mm PP pipe

§ Insulation - 214 minutes § Integrity - 240 minutes. No failure for test duration

• Fire collar 6 – 2 x H110S fitted with 2 x 110mm x 4.0mm HDPE pipes

§ Insulation - 175 minutes (6b) § Integrity - Sustained flaming after 223 minutes of test (6b)